DTCB Gea-12723ee A4 HR
DTCB Gea-12723ee A4 HR
Pre-engineered solution set that digitizes XD|GE primary equipment and provides factory
installed and configured protection, monitoring, diagnostics and communications.
GE
Digital Energy
Dead Tank Circuit Breakers — 72.5–800kV
363kV Dead Tank SF6 Circuit Breaker 800kV Dead Tank SF6 Circuit Breaker
2 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
Primary Plus
XD|GE offers Primary Plus™ for all its critical power delivery
equipment. Primary Plus is a pre-engineered solution set
that provides utilities and large industrial facilities with
a means to reduce the time and labor associated with
substation construction, expansion, and maintenance, while
utilizing technologies and methodologies familiar to existing
engineering resources.
GEDigitalEnergy.com 3
Dead Tank Circuit Breakers — 72.5–800kV
The LW24-72.5 is an outdoor dead tank SF6 circuit breaker with puffer type Type LW24-126/145/252/T outdoor dead tank SF6 circuit breaker product
interrupter technology and a spring operating mechanism. line incorporates world class advanced technology at these kV ratings.
Puffer type interrupting technology has been applied for many years, is well Single pressure puffer type interrupting technology is employed. This
proven and is accepted as the industry standard. Performance & reliability industry standard technology simplifies the design and assembly,
is enhanced with this technology. improves reliability and provides superior arc interruption capabilities
for successful interruption of all industry standards’ interruption
The operating mechanism used in this breaker, the CT20-II, is a spring driven
requirements.
mechanism. The advantages of this spring operated mechanism include
improved stability and reliability, increased stability with ambient temperature The operating mechanism is a spring design, which makes the product
changes, and minimal to zero maintenance given the lack of oil or gas simple in construction and light in weight with higher reliability and less
component. noise in operation.
The LW24-72.5 product has received independent KEMA certification for This family of dead tank circuit breakers will have independent
shunt capacitor bank switching tests. certifications from XIHARI, MHI, or KEMA depending on the rating class
and design.
This dead-tank breaker design is the most widely produced by XD|GE with
over 2,000 units shipped and in service over the last few years.
2.3. Max. wind velocity 35m/s 2.3. Max. wind velocity 35m/s
2.4. Pollution class: IV class 2.4. Pollution class: III, IV class
2.5. Typical ambient temperature: -35°C to +40°C 2.5. Typical ambient temperature: -35°C to +40°C
2.6. Max. temperature difference daily: 25°C 2.6. Max. temperature difference daily: 25°C
2.7. Seismic withstand capability 0.5g 2.7. Seismic withstand capability 0.5g
2.8. Ice coating: ≤ 10mm 2.8. Ice coating: ≤ 10mm
2.9. Max. radiance from sun: 1000 W/m2 2.9. Max. radiance from sun: 1000 W/m2
72.5kV Dead Tank Circuit Breaker 126kV Dead Tank Circuit Breaker
4 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
363kV - 800kV series dead tank breakers are tested and certified per IEC®
standards by XIHARI®, the national HV lab in China.
800kV Dead Tank Circuit Breaker 550kV Dead Tank SF6 Circuit Breaker
GEDigitalEnergy.com 5
Dead Tank Circuit Breakers — 72.5–800kV
Technology
This pressurized and compressed gas goes to the arc between the
stationary contact and moving contact. The nozzle concentrates the gas
flow to the arc for efficient cooling.
Trip spring
Trip spring
Cam Cam
Arc Nozzle Moving arcing Puffer Fixed
Ratchet
Ratchet contact cylinder finger
Closing
Closing spring
spring
LeverLever Ratchet
Ratchet wheelwheel
Trip spring
Cam
Ratchet
Closing spring
Closing-holding
latch
interrupter
open coil
Trip trigger
6 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
GEDigitalEnergy.com 7
Dead Tank Circuit Breakers — 72.5–800kV
XD|GE’s technology portfolio is built in state-of-the-art manufacturing and Advanced Test Facilities
testing facilities with robust quality processes which provide customers
XIHARI®, the Xi’an High Voltage Apparatus Research Institute, is an integral
with products that meet the critical and demanding reliability and
part of the XD|GE alliance. XIHARI has extensive testing capabilities at
environmental challenges of transmission applications.
its facility sites, which include a: High Power Laboratory, High Voltage
Laboratory, Artificial Climate Laboratory, EMC Laboratory, and an
Operational Test Circuit for HVDC Thyristor Valves.
Manufacturing Excellence
XD|GE designs a broad range of switchgear in five specialized production The testing hall meets all of the requirements of ISO/IEC® 17025 and
facilities including machining, surface treatment, insulating, housing and houses some of the largest test equipment in the world, providing the
casting. capacity to test primary equipment as large as 1,100kV AC. The High
Voltage Apparatus Laboratory in XIHARI is a government authorized
Additionally, there are two specialized facilities that produce both the national high-voltage apparatus quality supervision and inspection test
spring and hydromechanical operating mechanisms. center. It is an independent third-party laboratory for type tests, routine
Final production is completed in three workshop assembly lines that tests, performance tests and certificate tests for high-voltage apparatus.
total more than 50,000 square meters. Components such as aluminum The testing facilities at XIHARI also include an extension environmental
enclosures, cast resin insulators, current and voltage transformers, and laboratory. Testing capabilities here include high altitude testing, high
operating mechanisms are manufactured by XD|GE through a completely humidity testing, and temperature testing from -70° C up to +150° C.
integrated manufacturing model.
The switchgear facilities are ISO® 9001 certified, ISO 14001 certified for
environmental management systems, as well as OSHA® 18001 certified for
health and safety management systems.
Exceptional Quality
A focus on quality is an ongoing strategic initiative for XD|GE and that is
evident throughout the manufacturing environment. The quality process
begins with an incoming inspection of all materials to ensure the best
possible inputs before manufacturing begins.
8 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
This support infrastructure covers the entire life cycle of the product.
From the coordination of transportation logistics to the completion of site
acceptance testing and warranty service, the highly qualified XD|GE team
is available throughout the implementation.
Finally, XD|GE offers a 24x7 global support service to address and direct
any customer application and field questions.
GEDigitalEnergy.com 9
Dead Tank Circuit Breakers — 72.5–800kV
Primary Plus
• Digitized primary equipment for replacing labor-intensive, individually terminated copper wires
• Electrical protection solutions to monitor and react to fault conditions
• Secure and ruggedized communications infrastructure devices including wireless radios, fiber optic multiplexers
and Ethernet switches
Digitized Substation
10 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
LW24-72.5
LW24-72.5
2115
2530 10° 10°
2320
1160
30° 30°
1360
3650
2806
2363
Grounding
2×4-M10 Terminal
981
32
56
885
300
32
120 920 120 56
1280
M20
85
1280
500
500
920
150
392
280
80
400
940
16
R6
All measurements
are in millimeters (mm)
GEDigitalEnergy.com 11
Dead Tank Circuit Breakers — 72.5–800kV
LW24-126
LW24-126/LW24-145
2030
251 1560 3200
1510 1510
C
2 800
N1 10
M
2-
40
14
40
3820
22x2.4
4-ф
100
370
102
225
45
530
45 30
1750
1530
1000
2*4-M10
1070
1670
2300
3820
3900
1000
50
175
175
180 34
1000 1300 610
6-ø12 180
120x200
120
1500 200
120
1000
500 500
38 120 R7
50
1205
100
250 100
650
2070
1300
1800
85 50
(865)
R7
650
200
100
630
250
38
610
220
100
280
250
370
12 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
LW24-252
outline and foundation drawing
LW24-252
3000 - 4000 3000 - 4000
(2860)
P1 P2
(5165)
(2511)
591
1220
1320
Phase A Phase B Phase C
P1 P1 P1
t22 Aluminum 9-φ18
Alloy Plate A-A
45 45
2860
145
.5
R9
A A
45 45 45
P2
10
P2 P2
10
0°
800
0°
10
924
Cement
A-A Foundation
70
Anchor Bolt
320 M30*800 Grounding
E E E
Position (2 places)
245
1220
220
1380
1380
A
245
A E E 320 C E
300
500
All measurements
145 C
are in millimeters (mm)
373
GEDigitalEnergy.com 13
Dead Tank Circuit Breakers — 72.5–800kV
873
510
700
920
(3463)
6534
1500
(1438)
14 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
LW13A-363
5000 5000
2180
2200
200
1000
1120
5
84
800
4620
1100
2500
7300
Anchor Bolt
3325
M30X800
80
1800
800
820
All measurements
are in millimeters (mm)
125
GEDigitalEnergy.com 15
Dead Tank Circuit Breakers — 72.5–800kV
LW13A-550/Y
550kV DTB
Outline Drawing
LW13A-420 / LW13A-550
Phase A
Phase C Phase B
8000 8000
80
2450
I
2850
(1000)
(1180)
800
5
R=84
80
1100
0
0
30
1500
6190
8395
Anchor Bolt
M30X1000
1000 105
1000
2150
3195
1600
150
125 All measurements
800 are in millimeters (mm)
16 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
LW13-800
General Assembly Drawing LW13-800 DTB
10249
11000 11000
7607
4681
12966
13146
12108
3000
3820
560
2000
3820
3864
4239
Grounding Ground
1680
LCP
Block
800
630
500
1460
500
1580 4523
190
5620
P1 P1 P1
Terminal Pad
36
LCP 9-Ø24 65 65 65
R900
65 65
220
Aluminum
Alloy Plate
P2 P2 P2
Size of
Grounding Block
Copper Soldering
70*70
70
40
70
15 100
15
130
GEDigitalEnergy.com 17
Dead Tank Circuit Breakers — 72.5–800kV
Technical Specifications
1. Electrical Parameters
1. 1 Rated voltage (kV) 72.5 126 145 252 363 363 420 550 800
1. 2 Rated frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 50 50 50/60
3150/4000/
1. 3 Rated continuous current (A) 3150 3150 3150 4000 3150/4000 5000 5000 5000
5000
1. 4 Rated short circuit
40 40 31.5/40 50/63 50 50/63 50/63 50/63 50/63
breaking current (kA)
1. 5 Making current (kA) 104 104 80/104 130/164 130 130/164 135/171 135/171 135/171
1. 6 Rated peak withstand current (kA) 104 104 80/104 130/164 130 130/164 135/171 135/171 135/171
1. 7 Specific creepage distance (mm/kV) 25/31 25/31 25/31 25/31 25/31 25/31 25 25 25
1. 8 Short line fault breaking current (kA) 36/30 36/30 28.35/23.63 45/37.5 45/37.5(50kA); 56.7/47.25(63kA)
PRODUCT TYPE LW24-72.5 LW24-126 LW24- 145 LW24-252 LW23-363 LW13A-363 LW13A-420 LW13A-550 LW13-800
2. Mechanical Parameters
Spring/ Spring/ Spring/
2. 1 Type of mechanism Spring Spring Spring Hydro- Hydro- Hydro- Hydro-mechanical
mechanical mechanical mechanical
2. 2 Mechanical endurance (times) ≥5000 ≥5000 ≥5000 ≥5000 ≥5000 ≥5000 ≥5000 ≥5000 ≥5000
2. 3 Rated operating sequence O-0.3s-CO-180s-CO
2. 4 Close time (ms) ≤100 ≤100 ≤100 ≤110 ≤100 ≤100 ≤100 ≤100 ≤100
2. 5 Open time (ms) ≤30 ≤30 ≤30 ≤30 ≤20 ≤20 ≤20 ≤20 ≤20
2. 6 Breaking time (ms) ≤60 ≤60 ≤60 ≤60 ≤40 ≤40 ≤40 ≤40 ≤40
2. 7 Close-open time (ms) 40-50 40-50 40-50 50-70 40-50 40-50 40-50 40-50 40-50
2. 8 Operating asynchronism (ms)
Between poles ≤2 ≤3 ≤3 ≤3 ≤3 ≤3 ≤3
Open ≤4 ≤4 ≤5 ≤4 ≤4 ≤4 ≤5
Close
2. 9 Operating asynchronism (ms)
Across break ≤2 ≤2 ≤2 ≤2 ≤2
Open ≤3 ≤3 ≤3 ≤3 ≤3
Close
2. 10 Number of breaks per pole 1 1 1 1 1 2 2 2 2
2. 11 Three phase operation/
3p 3p 3p 3p/1p 1p 1p 1p 1p 1p
single phase
2. 12 Rated SF6 gas pressure (Mpa) 0.4/0.5 0.5 0.5 0.6 0.5 0.5 0.6 0.6 0.6
2. 13 Leakage of SF6 gas per year (%) ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5
2. 14 Weight (kg) 1550 3400 3400 9000 10000 18000 18000 18000 60000
18 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV
Ordering
LW * - * / * * - *
SF6 Circuit Breaker
Outdoor LW
Design Sequence No. 24
13/ 13A
23
Rated Voltage 72.5
126
145
252
363
420
550
800
Operating System:
T: Spring Mechanism T
Y: Hydro-mechanical Mechanism Y
Rated Current (A) 1250
2000
3150
4000
5000
Rated Interrupting Current (kA) 31.5
40
50
63
Dead Tank Circuit Breaker Product Line Dead Tank Circuit Breaker Product Line
With Spring Mechanism: With Hydro-mechanical Mechanism:
LW24-72.5/T1250-31.5 LW24-252/Y4000-63
LW24-72.5/T2000-31.5 LW23-363/Y3150-50
LW24-72.5/T2500-31.5 LW23-363/Y4000-50
LW24-72.5/T3150-40 LW13A-363/Y3150-50
LW24-126/T3150-40 LW13A-363/Y4000-50
LW24-145/T3150-31.5 LW13A-363/Y5000-50
LW24-145/T3150-40 LW13A-363/Y3150-63
LW24-252/T4000-50 LW13A-363/Y4000-63
LW13A-363/Y5000-63
LW13A-420/Y5000-63
LW13A-550/Y5000-63
LW13-800/Y5000-63
GEDigitalEnergy.com 19
GEDigitalEnergy.com
Digital Energy
Toll Free: +1 877-605-6777
Direct: +1 678-844-6777
[email protected]
GE, the GE monogram, Primary Plus and Multilin are trademarks of the General Electric Company.
g
GE Digital Energy reserves the right to make changes to specifications of products described at any
time without notice and without obligation to notify any person of such changes.