1702544864165power Transformer Without DGA (1)
1702544864165power Transformer Without DGA (1)
TECHNICAL SPECIFICATION
FOR
POWER TRANSFORMERS
CHIEF ENGINEER/PD&C
HVPNL, PANCHKULA
CONTENTS
ANNEXURES
II. NIFPES 27
IS:13155 Method of test for carbon type(PNA) analysis of mineral oil by infra red `
spectrophotometer.
IS:1367 Hot Dip Galvanized cooling on threaded fasteners.
IS:6272 Industrial cooling fans
IEEE:32 IEEE standard requirement terminology and test procedure for neutral grounding device.
ASTM-876M & IS 3024: American society for testing material for CRGO
CBIP Manual on transformer.
2.2 The works covered by the specification shall be designed, engineered, manufactured, built, tested and
commissioned in accordance with the Acts, Rules, Laws and Regulations of India.
2.3 The equipment to be furnished under this specification shall conform to latest issue with all amendments of
standard specified above.
2.4 In addition to meeting the specific requirement called for in the Technical Specification, the equipment shall
also conform to the general requirement of the relevant standards and shall form an integral part of
Specification.
2.5 The Bidder shall note that standards mentioned in the specification are not mutually exclusive or complete in
themselves, but intended to compliment each other.
2.6 The Contractor shall also note that list of standards presented in this specification is not complete. Whenever
necessary the list of standards shall be considered in conjunction with specific IS/IEC.
2.7 When the specific requirements stipulated in the specification exceed or differ than those required by the
applicable standards, the stipulation of the specification shall take precedence.
2.8 Other internationally accepted standards which ensure equivalent or better performance than that specified in
the standard referred shall also be accepted.
2.9 In case governing standards for the equipment is different from IS or IEC, the salient points of difference
shall be clearly brought out alongwith English language version of standard or relevant extract of the same.
The equipment conforming to standards other than IS/IEC shall be subject to Employer's approval.
2.10 The bidder shall clearly indicate in his bid the specific standards in accordance with which the works will be
conformed.
4.00 BAY WIDTH AND HEIGHT :The bidder may specifically note that the total length& total height of the
transformer shall be such that two transformers can be adjusted in adjacent bays including fire wall (thickness
of 650mm approx.) between them. The centre line of the transformer tank/ central bushing should be in line
with the centre line of bay & total length of the transformer should be such that the radiator can be
accommodated on either side of transformer tank in the specified bay width maintaining adequate clearances
for safety and proper working on either side.
4.1 The bay widths & heights are given as under:
5.6 To prevent transformer movement during earthquake, clamping device should be provided for fixing the
transformer to the foundation.
6.00 PRINCIPAL TECHNICAL PARAMETERS:
The transformers covered in this specification shall meet the technical requirements listed
hereunder.
8. Current of all the windings and the regulating winding at the lowest tap should not exceed 250
density A/cm.Sq
Item 400/220 220/132 220/66 220/33 132/33 132/11 66/11 66/33 kV
No kV T/F kV T/F kV T/F kV T/F kV T/F kV T/F kV T/F T/F
. with
bushing
CTs
9. Type of Plinth of height approx. 850mm
Mounting
10. Suitable for 50 Hz± 5%
system
Frequency
11. Highest system Voltage (KV rms)
a. HV side 420 245 245 245 145 145 72.5 72.5
b. LV side 245 145 72.5 36 36 12 12 36
12. Minimum Neutral Insulating Voltage
a. HV side 52 36 36 36 36 36 36 36
b. LV side - - 36 36 36 36 36 36
13. Rated short duration Power frequency withstand Voltage for 1 minute (kV rms)
a. HV side 630 395 395 395 230 230 140 140
b. LV side 460 230 140 70 70 28 38 70
c. HV neutral 95 70 70 70 70 70 70 70
d. LV neutral - - 70 70 70 70 70 70
14. Rated lightning impulse withstand Voltage1.2/50 microsecond impulse (kVp)
a. HV side 1300 950 950 950 550 550 325 325
b. LV side 950 550 325 170 170 95 95 170
c. HV neutral 250 170 170 170 170 170 170 170
d. LV neutral - - 170 170 170 170 170 170
15. Bushings
a. HV Rated 420 245 245 245 145 145 72.5 72.5
side Voltage
(kV)
One minute 630 460 460 460 275 275 140 140
power
frequency
withstand
voltage kV
(rms.)
1.2/50 1425 1050 1050 1050 650 650 325 325
micro sec.
lightning
impulse
withstand
voltage
(kVp)
Minimum 10500 6125 6125 6125 3625 3625 1815 1815
creepage
distances
(mm) total
25mm/kv
Minimum 50% of the total creepage distance
creepage
distances
(mm)
protected
Maximum 4.0
Creepage
Factor
Sr. Item 400/220 220/132 220/66 220/33 132/33 132/11 66/11 66/33 kV
No kV T/F kV T/F kV T/F kV T/F kV T/F kV T/F kV T/F T/F
with
bushing
CTs
b. LV Rated 245 145 72.5 36 36 36 36 36
Voltage
side (kV)
Rated 1250 800 2000 for 2000 1000 1200 2000 1000
current 160MVA,
(Amp.) 1000 for
100MVA
One minute 460 275 140 70 70 70 70 70
power
frequency
withstand
voltage kV
(rms.)
1.2/50 1050 650 325 170 170 170 170 170
micro sec.
lightning
impulse
withstand
voltage
(kVp)
Minimum 6125 3625 1815 900 900 900 900 900
creepage
distances
(mm) total
25mm/kv
Minimum 50% of the total creepage distance
creepage
distances
(mm)
protected
Maximum 4.0
Creepage
Factor
c. HV Rated 52 36 36 36 36 36 36 36
Voltage
neut (kV)
ral
Rated 3150 1000 2000 2000 630 630 630 630
current
(Amp.)
One minute 95 70 70 70 70 70 70 70
power
frequency
withstand
voltage kV
(rms.)
1.2/50 250 170 170 170 170 170 170 170
micro sec.
lightning
impulse
withstand
voltage
(kVp)
Minimum 1300 900 900 900 900 900 900 900
creepage
distances
(mm) total
25mm/kv
Minimum 50% of the total creepage distance
creepage
distances
(mm)
protected
Maximum 4.0
Creepage
Factor
Sr. Item 400/220 220/132 220/66 220/33 132/33 132/11 66/11 66/33 kV
No kV T/F kV T/F kV T/F kV T/F kV T/F kV T/F kV T/F T/F
with
bushing
CTs
d. LV Rated - - 36 36 36 36 36 36
Voltage
neut (kV)
ral
Rated - - 2000 2000 1000 1200 2000 1000
current
(Amp.)
One minute - - 70 70 70 70 70 70
power
frequency
withstand
voltage kV
(rms.)
1.2/50 - - 170 170 170 170 170 170
micro sec.
lightning
impulse
withstand
voltage
(kVp)
Minimum - - 900 900 900 900 900 900
creepage
distances
(mm) total
25mm/kv
Minimum 50% of the total creepage distance
creepage
distances
(mm)
protected
Maximum 4.0
Creepage
Factor
16. OLTC
a. Rated Voltage 220 132 132 132 66 66 66 66
(kV)
b. Rated current 1000 800 500 300 350 350 350 350
(A)
c. Tappings On load On load On load tappings at On load tappings at neutral end of HV side
tappings tappingso neutral end of HV side for variation +5% to -15% in steps of 1.25%
on 220kV n132kV for variation +10% to - each
side for side for 10% in steps of 1.25%
variation variation - each
+10% to - 5% to
10% in +15% in
steps of steps of
1.25% 1.25%
each each
17. Insulating Oil Naphthenic type, min, B.D.V. 70kV at 2.5 mm gap
d. PD 100pC max
22. Power 2
frequency over
voltage
withstand
requirement for
control wiring
(kV rms) (for 1
minute)
23. Noise level Shall be as per NEMA standard publication TR-1, max. 80dB
NOTES:
1. The ratings and other characteristics which are not covered elsewhere shall be, as detailed in
annexure-I:
2. The transformers shall be designed to have short circuit rating of five seconds as per IS: 2026.
The thermal ability to withstand short circuit shall be judged by calculation to be supplied above in
the tender.
The dynamic ability to withstand short circuit shall be demonstrated by test, except in case
of 20/25MVA, 66/33kV T/F, in case testing facility is available in India other-wise calculations will be
supplied along with contract drawing.
3. The above flux density has been specified to meet with the over fluxing of the core due to
temporary over voltage of the order of 31% for l min, 44% for 5 seconds that may appear abnormal
conditions such as those following sudden loss of large loads. Yoke bolt area and flitch plate areas
shall not be counted in the net core area if these are provided for fastening core
4. The limits of temperature rise mentioned above will have to be satisfied by the manufacturer by
carrying out the heat run test at the lowest negative tap. This test shall be carried out by feeding
1.1 times the total losses at 75oC at highest current tap.
5. The safe over load capacity of the transformer and the duration of overload under maximum
temperature conditions without any damage to the winding or harmful effects on the insulation shall
be clearly stated in the tender which must be as per IEC-354/IS: 6600, guide for loading of oil
immersed transformer.
6. The transformer shall have % impedance on max rated MVA base with tolerance as per IS:
2026/Part-1 (1983). Impedance shall include positive and zero sequence and shall be expressed in
terms of the branches of the star connected equivalent diagram, all on the same KVA base and
range shall be given for each branch of the equivalent circuit in turn. Percentage tolerance allowed
at extreme tap should be as applicable to normal tap.
7. The transformer shall be suitable for continuous operation with a +/- 5% frequency variation from
a normal of 50 Hz without exceeding the temperature rise as specified in Clause 7.1 above.
8. The transformer shall be so designed as to suppress the harmonics voltage specially the 3rd& 5th,
to eliminate wave form distortion and interference with communication circuits due to high
frequency disturbances. Limiting percentage of harmonics at normal voltage and at maximum
system voltage shall be stated in the tender.
9. Losses:-
The losses of each transformer at principal tap rating at full load at 75 deg. C shall be less than or
equal to specified in Annexure-I. The manufacturers have to adhere to these limits and their bids
shall be rejected, if any one of no-load loss, load loss or auxiliary loss exceeds the maximum limits
as specified in Annexure-I.
With specified fixed loss figures of maximum losses, manufacturers have to adhere to
these figures by designing transformer suitably. Therefore there will be no capitalization at
tender stage. The order will be placed to lowest bidder as per HVPNL policy.
The stray losses shall not be more than 18% of full load losses at 75 0C, calculated from
measured losses and the purchaser shall reject the transformer in case, no load losses or load
losses or auxiliary losses or stray losses exceed the value specified.
The measurement of losses shall be carried out with 3 (Three) Watt meter method only and
CTs, meters used for these measurements shall be of class of accuracy of 0.2s or better and PT’s of
class of accuracy of 0.2 or better. However, no weightage shall be given for supply of transformer,
with losses (measured during routine tests) less than the losses specified in Annexure –I.
a. The transformer and accessories shall be so designed as to facilitate inspection, cleaning and repairs. The
requirement of Indian Electricity Rules shall be kept in view.
b. The design shall ensure satisfactory operation under severe working conditions due to fluctuating load of steel
furnaces and voltage variations in the system including those, due to short circuits. The transformer shall be
designed as to minimize the risk of accidental short circuits caused by animals, birds or vermins.
The design shall incorporate every reasonable precaution and provision for the safety of all those concerned
in the operation and maintenance of the equipment keeping in view the requirements of Indian Electricity
Rules.
c. All material used shall be of the best quality and of class most suitable for working under specified conditions
and shall withstand the atmospheric conditions and temperature variations without undue deterioration or
distortion or setting up of undue stress in any part thereof.
d. Cast iron shall not be used for any parts other than the radiator valve bodies.
e. Corresponding parts liable to replace shall be interchangeable.
f. All taper pins to be used in the mechanism shall be split types as per latest edition of IS: 2393.
g. All mechanism should be rust and corrosion proof. Means shall be provided for lubrication of moving parts not
immersed in oil.
h. The construction shall be such as to avoid air or water pockets. Special care shall be exercised to reduce
noise and vibration to the minimum level.
i. Steel bolts of suitable finish will be used for diameters above 6mm. Brass bolts or studs used for electrical
connections shall not be of less than 6mm diameter. On outdoor equipment, all bolts, nuts & washers in
contact with current carrying non-ferrous parts shall be phosphor bronze.
j. All nuts, bolts and pins shall be locked except those, which are external to the transformer. If bolts and nuts
are so placed as to be inaccessible by means of ordinary spanners, the Contractor shall provide suitable
special spanners.
k. Labels shall be provided for all apparatus like relays, switches, fuses, etc. housed in any cubicle or
marshalling kiosks. These shall be of incredible material with matt/satin finish and permanent lettering. Labels
mounted on black surface shall have white letters and danger notices shall have red lettering on a white
background. The labels shall be secured by means of brass screws or rust protected steel screws.
l. The outer most radial spacers of the winding shall be locked in position by means of vertical strips so that the
same cannot fall off/get displaced.
m. The manufacturers must ensure proper & complete tightening of the nuts of the coil clamping bolts. The nuts
of all the coil clamping bolts will be tightened to designed value & the job be carried out with torque spanners.
The devices used for locking the nuts of coil clamping bolts must be of such a quality and such care should be
taken first in tightening. The nuts and next in locking them in position that the arrangement does not become
loose due to stresses caused by short circuits and fluctuating loads etc.
n. Neoprene Gasket shall be provided. Metal tops shall be provided for preventing over compression wherever
compressible gaskets are provided.
i) The core shall be built up with thin laminations of high grade. non-ageing, low loss, high permeability cold
rolled super grain oriented silicon steel. Known as MOH High B Grade or superior grade CRGO steels of
maximum 0.27 mm or low lamination thickness especially suitable for transformer core.
ii) (a) (i) Bidder should have in house core cutting facility for proper monitoring & control on quality
and also to avoid any possibility of mixing of prime material with defective/second grade material. The
purchaser may witness the core-cutting operation. In case the in house core cutting facility for core
cutting is not available then the same shall be carried out in the presence of the representative of
HVPN.
(ii) Inspection call notice for the purpose should be accompanied with the following documents as
applicable as a proof toward use of Prime core materials:-
a) Invoice of supplier.
b) Mills test certificates.
c) Packing list.
d) Bill of lading.
e) Bill of entry certificates by customs.
Core material shall be directly procured either from the manufacturer or through their accredited marketing
organisation of repute and not through any agent.
iii) After being sheared, the laminations shall be treated to remove all burrs. They shall be coated with a baked
enamel insulation coating. The insulation shall be inert to the action of hot transformer oil and shall be
perfectly adhesive. Paper and varnish insulation shall not be accepted. Particulars of proposed insulation shall
be stated in the tender. Laminations shall be checked for burrs during stage inspection.
iv) The core shall be rigidly clamped and/or bolted to ensure adequate mechanical strength and to prevent
vibrations during operation. The bolts used in the assembly of the core shall be suitably insulated and the
clamping structure shall be constructed that the eddy currents will be minimum.
v) Construction of the core shall be such that number of steps in the limb and yoke shall be matching and
dimensionally identical to minimize the effect of cross fluxing and better mechanical strength.
vi) The core shall be provided with Lugs suitable for lifting the complete core and coil assembly of transformer.
The Core & coil shall be fixed in the tank such that its shifting will not occur when the transformer is moved or
when a short circuit occurs.
vii) The design of magnetic circuit shall be such as to avoid static discharge development of short circuit paths
within itself or to the earthing clamping structure and the production of flux components at right angles to the
plane of the lamination which may cause local heating.
viii) Every care shall be exercised in the selection treatment and handling of core steel to ensure that the
laminations are flat and that finally assembled core is free from distortions.
ix) The supporting frame work of the core shall be so designed as to avoid the presence of pockets which would
prevent complete emptying of the tank through the drain valve or cause trapping of air during filling.
x) Oil ducts where necessary should be formed across the plane of the lamination and be given a suitable slope
to assist oil circulation. The overall design of core and winding should be such that free flow of oil is not
obstructed.
xi) The frame work and clamping arrangement shall be earthed by connecting to the tank body through a copper
strip. Yoke bolt area should be compensated if bolts are used for fastening of the core.
xii) The insulation of core to bolts and core to clamp plates shall be able to withstand a voltage of
2 KV RMS for one minute.
xiii) Core and windings shall be capable of withstanding shocks during transport, installation, service and adequate
provision shall be made to prevent movement of core and winding relative to tank during these conditions.
xiv) All steel sections used for supporting the core shall be thoroughly sand blasted after cutting drilling and
welding.
xv) All the CRGO vendors having BIS certification and approval from PGCIL shall be considered.
xvi) The tenderers should indicate the maximum flux density allowable continuously as well as for time intervals of
1 minute and 5 seconds and the limit of flux density at which core material used by them saturates.
xvii) The name of the core material must be mentioned in the tender. The successful tenderer shall be required to
furnish magnetization curves of the core material/design calculations and such other data/documents deemed
fit by the Purchaser for being satisfied that flux density is as desired.
xviii) Purchaser shall inspect the built-up core for verification of flux density for which all facilities shall be provided.
The purchaser shall inspect/test the core material for various tests as per relevant IEC/IS to ensure quality.
Core may also be inspected during horizontal assembly, built-up assembly.
NOTES:
i) The design of limb and yoke shall be so co-ordinate that there is no cross fluxing at the joints.
ii) The tenderer shall ensure that the CRGO supplier should have BIS certification.
(7.3) WINDING:
a. The windings shall have graded insulation whereas the neutral points shall be insulated uniformly as
per IS: 2026.
b. The transformers shall be capable of operation without danger on any particular tapping at the rated
KVA when the voltage may vary by ± 10% of the voltage corresponding to the tapping.
c. The windings and connections as well as the insulating material shall not soften ooz, shrink or
collapse during service.
d. No strip conductor wound on edge shall have a width exceeding six times its thickness. The
conductors shall be transposed at sufficient intervals to minimize eddy currents and equalize the
current and temperature distribution along the windings.
e. The windings and connections shall be properly brazed to withstand shocks during transportation or
transient conditions during service.
f. Adequate pre-shrinkage of the coil assembly using pre-compressed press board material having low
moisture content for the radial spacer blocks shall be ensured by the manufacturers so that there is no
displacement of the radial spacer blocks due to frequent short circuits on the transformers.
g. All windings after being wound and all fibrous hygroscopic materials used in the construction of the
transformer shall be dried under vacuum and impregnated with hot oil.
i. In addition to this the drying process be sufficiently extended for proper stabilization of the coil
assembly. More than one cycle of soaking in oil followed by retightening of the coil assembly
should be adopted.
h. The coil clamping rings wherever used shall preferably be of flat insulated steel laminations. Axial
laminated material except bakelised paper shall not be used.
i. The clamping arrangement shall exert equal pressure on all columns of spacers of the transformer
windings built of sections or disc-coils separated by spacers. In no case, spiral winding will be used
either for HV or LV windings.
j. The radial spacer blocks must be made of pre-compressed pressboard material, which will not soften
while in contact with oil or fray out into fibers or edges. The slots should be so dimensioned that the
blocks will not come out of the slots.
i. Uniform distribution of coil clamping force shall be designed by using an adequately large number of
coil clamping bolts and by transferring the clamping force from clamping bolts to the clamping plates
through intermediate members which can spread the clamping force over a large area.
k. All joints shall be brazed/crimped considering the vibrations due to short circuits and load fluctuations.
(7.4) TANK
i) The tank shall be fabricated of a suitable grade steel and strong enough to allow the lifting of complete
transformer with oil by means of a crane or jacks and transported to site without over-straining the joints
etc.
ii) The main tank body shall be capable of withstanding a vacuum of 100.64 kN/m2 (760mm of Hg.)
iii) The base shall be so designed as to allow the transformer to be moved by skidding without any injury.
iv) All channeled constructions and stiffeners shall be designed to avoid retention of water.
v) The transformer shall preferably be of bell type tank with the joint 500 mm above the bottom of tank.
vi) The tank construction shall be free of air pockets. Where such pockets cannot be avoided, vent pipes of
15 mm internal diameter shall be provided to vent gases into the main expansion pipes. In case of short
branch pipes, however, minimum diameter may be taken as 6mm.
vii) All joints other than those, which may have to be broken, shall be welded. When required they shall be
double welded. All bolted joints to the tank shall be fitted with suitable oil tight gaskets, which shall give
satisfactory service under the operating conditions and guaranteed temperature rise conditions. Special
attention shall be given to the methods of making hot oil tight joints between the tank and the cover and
also, between the cover and the bushings and all other out-lets to ensure that the joints can be remade
satisfactorily at site and with ease by semi-skilled labour.
viii) Suitable lifting lugs for lifting the transformer filled with oil shall be provided on the tank.
ix) Four jacking lugs shall be provided to enable the transformer complete with oil to be lifted or lowered by
means of jacks. The lugs shall be fitted at a minimum height (excluding under base if detachable) of
300mm for transformer upto 10 tons weight and of 500mm for transformer above 10 tons weights.
(7.5) TANK COVER
i) The tank cover shall be of bolted type and of adequate strength so as not to distort, when lifted. Suitable
inspection cover shall be provided with lifting arrangements to give access to bushings, winding
connections or testing the earth connections. The weight of each inspection cover shall not exceed 25
Kg.
ii) Pockets shall be provided in the position of Max. oil temperature at CMR for fitting a thermometer and
for bolts of oil and winding temperature indicators. The thermometer pockets shall be fitted with a
captive screwed cap to prevent ingress of water.
iii) Suitable No. of jacking bolts shall be provided on tank cover, inspection covers/windows including
OLTC.
iv) Neoprene Gasket shall be provided.
(7.6) FITTINGS
CONSERVATOR TANK, OIL GAUGE AND BREATHER
i) An adequate conservator tank of air cell type complete with sump and drain valves shall be provided in such a
position as not to obstruct the electrical connections to the transformer.
ii) If the sump is formed by extending the feed pipe inside the conservator, this extension shall be at least 25mm.
iii) One end of the conservator shall be bolted type to facilitate cleaning.
iv) The conservator shall be provided with a magnetic oil level gauge.
v) The oil connections from the transformer tank to the conservator shall be at rising angle of 3 to 9 degrees to
the horizontal upto Buchholz relay. The inside diameter of the pipe shall be 80mm. The Buchholz relay will
have suitable valves on its both side so as to facilitate its testing at site as well as cut off oil supply to the
transformer.
vi) The conservator shall be provided with oil preservation system, which should be suitable either to remove
moisture continuously from air entering the air space with which they are connected or may not allow direct
contact of atmospheric air with oil during operation, in addition to silica gel-breather.
VALVES:
i) The transformers shall be provided with 2 No. filter valve each of 50 mm size one mounted close to the top of
the main tank & the other close to bottom of the tank oil circulation and one drain valve of 80mm size with
plug. The conservator shall have drain plug of 25mm size.
ii) Two robust sampling valves with spouts suitable for taking samples of top, and bottom oil. The top sampling
valves shall be brought down by internal pipe connections. Suitable name plates shall be affixed to the
sampling valves. The sampling device shall not be fitted on the filter valve.
iii) Two air release plug of 15mm shall be provided.
iv) Plugs shall be supplied for all valves opening to atmosphere.
v) All valves shall be of gun metal and comply with the latest edition of IS:3639.
PRESSURE RELIEF DEVICES:
A suitable pressure relief device shall be provided for rapid release of any pressure in transformer which
may endanger the equipment. The device (s) shall operate at static pressure less than hydraulic test
pressure for transformer tank of OLTC chamber. If the device is mounted on tank cover, it shall be fitted with
a skirt projecting 25mm inside the tank and of such construction as to avoid gas accumulation.
In addition to pressure relief device(s) the provision of explosion vent should also be made and the
diaphragm shall be situated above max. oil level or second PRD on the opposite side of first PRD be
provided.
.
THERMOSYPHON FILTER ARRANGEMENT
Thermosyphon filter arrangement shall be provided on the transformer for preserving the quality of
Transformer Oil. The filter assembly shall be mounted on the Transformer as well as ground supported and
connected with pipes and shut off valves. Suitable instructions required to be followed for commissioning,
dismantlement & maintenance of the filter arrangement, re-generation and storage of the adsorbent etc. must
be included in the instruction manual. A detailed drawing showing internal arrangement shall also be required
to be submitted. Suitable capacity pump (alongwith motor) shall also be provided to boost circulation of oil.
The pump and motor should not be in main pipe line. It should be in bypass pipe line having suitable valve to
isolate from main pipe line. The main pipe line should have two shut off valves at the bottom.
NOTE: -The pump and motor should be weather proof (Flow well Type).
The oil & absorbent capacity required in the Thermosyphon Filter is as under: -
(i) Quantity of oil 2.0% of total oil by weight.
(ii) Quantity of absorbent 1.25% of total oil by weight.
The connectors shall have six number bolts provided with check nuts & washers. The connectors shall
have rating corresponding to those of equipment or higher and shall be designed most liberally with a
higher factor of safety to comply in all respects with temperatures rise, resistance, tensile strength
short-circuit withstand capability tests as specified in IS: 5561-1970 or amendment thereof (Latest
edition). Aluminum alloy used in the manufacture of Bi-metallic connectors shall conform to
designation Grade 4600 of IS: 617-1975. The steel bolts, nuts washers and check nuts shall be hot dip
galvanized marked with ISI certification mark or of GKW make.
(7.8) MARSHALING BOX: -
i) A sheet steel (of 10 SWG size) vermin proof well ventilated and weather proof marshaling box of suitable
construction shall be provided for the transformer auxiliary apparatus. The box shall have domed or sloping
roofs. Ventilation louvers, suitably padded with felt, shall also be provided. It shall be painted as per Cl.5.14.
ii) The marshaling box shall accommodate temperature indicators. Local electrical control of tap changer (if
same cannot be housed in motor drive housing.), Control & protection equipment for cooling plant, terminal
boards and gland plates for cable etc. The equipment shall be mounted on panels and panels wiring shall be
done at the back for interconnections.
iii) The temperature indicators shall be mounted at about 1600mm from ground level.
iv) A metal clad heater with thermostat, controlled by a waterproof rotary switch on the outside of the box, shall
be provided.
v) The incoming cables shall enter from the bottom with gland plate not less than 450mm from the base of the
box. Care shall be taken to avoid ingress of water from the cable trench.
vi) For each circuit, suitably rated power contactors, MCBs/MCCBs as required for entire auxiliary power supply
distribution scheme including distribution to DM boxes, Online Gases and moisture monitoring system and shall
be provided by contractor in cooler control cabinet/ Marshalling.
(7.9) EARTHING TERMINALS:
Two earthing pads suitable for connecting 50x8mm mild steel flat shall be provided at positions close to the
two diagonally opposite bottom corners of tank. These grounding terminals shall be suitable for bolted
connection. Two earthing terminals shall also be provided each on marshalling box and any other
equipment mounted separately. The earthing terminal should be suitable of carrying full low voltage short
circuit current of transformer for 4 seconds.
i) Before painting or filling with oil or compound all un-galvanised parts shall be completely cleaned and freed
from rust, scale and grease by pickling, degreasing process and all external surface cavities on castings
shall be filled by metal deposition.
ii) The interior of all transformer tanks and other oil filled chambers and internal structural steel works shall be
cleaned of all scale and rust by shot blasting or other approved method. These surfaces shall be spray
painted with hot oil resisting varnish or paint. Unexposed welds need not be painted.
iii) Except for nuts, bolts and washers, which may have to be removed for maintenance purposes, all external
surfaces shall receive a minimum of three coats of spray paint.
iv) The primary coat shall be applied immediately after cleaning. The second coat shall be of an oil and weather
resisting nature and preferably of a shade or colour easily distinguishable from the primary and final coats
and shall be applied after the primary coat has been touched up where necessary. The final coat shall be of
a glossy oil and whether resisting non-fading paint of shade No. 631 of IS:5. Primer paint shall be ready
make zinc chrome as per IS:104 ; intermediate and final coats of paint shall be as per IS:2932.
v) Nuts, bolts and washers which may have to be removed for maintenance purposes shall receive a minimum
of one coat of paint after erection.
vi) All interior surfaces of mechanism chambers and kiosks except those which have receive anticorrosion –
treatment shall receive three coats of paint applied to the thoroughly cleaned metal surface. The final coat
shall be of an approved light coloured anti-condensation mixture.
vii) Any damage to paint work incurred during transport and erection shall be made good by the supplier by
thoroughly cleaning the damaged portion and applying the full number of coats of paint that had been
applied before the damage was caused.
viii) One coat of additional paint shall be given at site to the purchase. Supplier will also supply the requisite
quantity of paint.
ix) Cubical and marshalling kiosk sheets shall be phosphated before application of enamel paint.
a. CORE:-
i) Slitting/Cutting of core.
ii)Measurement of flux Density.
iii)
No Load Loss Measurement by providing dummy coils.
iv)Tests of CRGO sample taken from the core shall be carried-out for Carlite test (Resistance
Measurement), Watt Loss Test, Lamination Thickness & Aging Tests.
v) Physical inspection for quality of workmanship.
b. WINDINGS:
i. Measurement of cross-sectional area for current density.
ii. Measurement of weight of bare copper/ cover by resistance methods.
iii. The purity test of copper shall be got conducted on sample of copper for assessing its quality, from
two independent NABL accredited laboratories.
c. TANK:
i) Vacuum Test:
One transformer tank out of the lot shall be subjected to vacuum pressure of 100.64 kN (760 mm of hg).
The tanks to be designed for full vacuum shall be tested at an internal pressure of 3.33 KN/M 2 (25mm of
Hg.) for one hour.
The permanent deflection of flat plates after the vacuum has been released shall not exceed the values
given below without affecting the performance of the Transformer.
----------------------------------------------------------------------------------------------------------------------------
Horizontal length of flat plate(mm). Permanent deflection (mm).
----------------------------------------------------------------------------------------------------------------------------
Upto& including 750 5.0
751-1250 6.5
1251-1750 8.0
1751-2000 9.5
2001-2250 11.0
2251-2500 12.5
2501-3000 16.0
above 3000 19.0
--------------------------------------------------------------------------------------------------------------------------
These charges and other terms and conditions shall be valid for one and a half years after the supply of the
equipment. The contractor shall also furnish, if necessary, special erection, tools and plant instruments on rental
basis.
Annexure-I
Current Transformer Parameters (on each phase) for 3-ph 315 MVA 400/220 kV Auto Transformers:
(a) Ratio
(d) Application
Core-1 60 mA 60 mA 60 mA
Core–2 - - -
1.3 NOTE:
1. Accuracy class PS as per IEC 60044.
2. Class (for the relevant protection and duties) as per IEC 60185.
Losses:-
The losses of each transformer at OFAF rating (at full load at 75 deg. C ) shall be:-
Losses:-
The losses of each transformer at OFAF rating (at full load at 75 deg. C ) shall be:-
[
5. 220/66kV 100 MVA TRANSFORMER
Max. Continuous capacity:
a) ONAN 50 MVA
b) ONAF 75 MVA
c) OFAF 100 MVA
Losses:-
The losses of each transformer at OFAF rating (at full load at 75 deg. C ) shall be:-
1 Activation of NIFPES
Mal-functioning of fire prevention/extinguishing systems is their major shortcoming which
leads to interruption in power supply. The contractor shall ensure that the chances of
malfunctioning of NIFPES are practically nil. To achieve this objective, the contractor shall
work out his scheme of activating signals which, while preventing mal-operation, should not
be too rigorous to make the operation of NIFPES impracticable in case of actual need.
Transformer isolation shall be the mandatory pre-requisite for activation of the system in
automatic mode or remote mode in the control room. In addition, at least following electrical-
signals shall be provided in series for activating NIFPES.
NIFPES should be a stand alone dedicated system for each oil filled transformer. It should
have a fire extinguishing (F.E.) cubicle placed on a plinth at a distance of 6-10 mtrs. from the
transformer. The F.E. cubicle may be connected to the transformer oil tank (near its top) and
to the oil tank placed in pit, from its bottom through oil pipes with gate valves. The F.E.
cubicle should house a pressurised nitrogen cylinder connected to the transformer oil tank
(near its bottom). Cable connections are to be provided from signal box placed on the
transformer to the control box in the control room and from control box to F.E. cubicle. Fire
detectors placed at the top of transformer are to be connected in parallel to the signal box.
The signal box may be connected to a pre-stressed non-return valve fitted between the
conservator tank and Buchholz relay. Control box is also to be connected to relay panel in
control room for system activation signals.
2.2 Operation
On receipt of all activating signals, drain of pre-determined quantity of oil commences thus
removing high temp. top oil layer. Simultaneously nitrogen is injected under high pressure at
a pre-fixed rate, stirring the oil thus bringing the temperature of top oil layer down. Nitrogen
occupies the space created by oil drained out and acts as an insulating layer between the
-0-
tank oil and fire on top cover. Pre-stressed non-return valve blocks oil flow from conservator
tank, thus isolating it & preventing aggravation of fire.
it shall be made of 3 mm thick steel sheet, painted dark red from inside and outside with
hinged split doors fitted with high quality tamper proof lock. It shall be complete with the base
frame and the following:-
Nitrogen gas cylinder with regulator and falling pressure electrical contact
manometer.
Oil drain pipe with mechanical quick drain valve.
Electro mechanical control equipment for oil drain and pre-determined regulated
nitrogen release.
Pressure monitoring switch for back-up protection for nitrogen release.
Limit switches for monitoring of the system.
Flanges on top panel for connecting oil drain and nitrogen injection pipes for
transformer.
Panel lighting (CFL type)
Oil drain pipe extension of suitable sizes for connecting pipes to oil pit.
2.5 Control box
Control box for monitoring system operation, automatic control and remote operation, with
following alarms indication, light switches, push buttons, audio signal, line fault detection
suitable for tripping and signaling on 110V DC/220V DC supply.
System on*
PNRV open*
Oil drain valve closed*
Gas inlet valve closed*
PNRV closed^
Fire detector trip^
Buchholz relay trip^
Oil drain valve open^
Extinction in progress^
Cylinder pressure low^
Differential relay trip^
PRV operated^
Transformer trip^
System out of service
Line fault fire detector
Line fault differential relay
Line fault buchholz relay
Line fault PRV
Line fault transformer trip
Line fault PNRV
Auto / Manual/Off
Extinction release on
Extinction release off
Lamp test
Visual/Audio alarm
Visual/Audio alarm
Visual/audio alarm for DC supply fail
The signals marked (*) shall be in the top most row of control box panel. The
signals marked (^) shall follow next.
-1-
PNRV is to be fitted in the conservator pipe line between conservator and Buchholz relay. It
shall have the proximity switch for remote alarm, indication and with visual position
indicator. The PNRV should be of the best quality because malfunction of PNRV shall be of
serious consequence as its closing leads to stoppage of breathing of transformer.
2.7 Fire detectors
The system shall be complete with adequate number of fire detectors fitted on the top of oil
tank, OLTC/OFF ckt. tap changer rated for 141 degree C for heat sensing each fitted with
two no. cable glands (water proof/weather proof).
2.8 Signal box
It shall be fitted on the transformer for terminating cable connections form PNRV and fire
detectors and for further connection to the control box.
2.9 Cables
Fire survival cables, able to withstand 750 degree C , 4 core x 1.5 mm sq. for connection of
fire detectors in parallel shall be used.
Fire retardant low smoke (FRLS) cable 12 core x 1.5 mm sq. for connection between
transformer signal box/marshalling box to control box and control box to fire extinguishing
cubicle shall be used.
Fire retardant low smoke cable 4 core x 1.5mm sq. for connection between control box to
DC supply source and fire extinguishing cubicle to AC supply source, signal box/marshalling
box to pre-stressed non return valve connection on transformer shall be used.
2.10 Pipes
Pipes, complete with connections, flanges, bends tees etc. shall be supplied along with the
system.
3 Other items
a. oil drain and nitrogen injection openings with gate valves on transformer tank at suitable
locations.
b. Flanges with dummy piece in conservator pipe between Buchholz relay and conservator
tank for fixing PNRV.
c. Fire detector brackets on transformer top cover.
d. Spare potential free contacts for system activating signals i.e. differential relay buchholz
relay, pressure relief valve, transformer isolation (master trip relay).
e. Pipe connections between transformer to fire extinguishing cubicle and fire extinguishing
cubicle to oil pit.
f. Cabling on transformer top cover for fire detectors to be connected in parallel and inter
cabling between signal box to control box and control box to fire extinguishing cubicle.
g. Mild steel oil tank (having capacity equal to 10% of transformer’s total oil or 10000 Liters,
whichever is higher) for each T/F with moisture proof coating and sheet thickness of minimum
5 mm, with watertight cover, to be placed in the pit. This tank shall be provided with the
manhole, air vent pipe through silica gel breather, drain valve and a spare gate valve at the
top.
The location of the tank shall be approved by the employer.
h. DC-DC converter 220-110V DC (optional, incase 110V, supply is not available.)
i. Gate valves on oil drain pipe and nitrogen injection pipe should be able to withstand full
vacuum. A non-return valve shall also be fitted on nitrogen injection pipe between
transformer and gate valve.
j. The F.E. cubicle shall be painted with post office red colour (shade 538 of IS-5). All the
exposed parts i.e. pipes, supports, signal box etc shall be painted with enameled paint.
k. Civil works of F.E.Cubicle and oil pit are not in the scope of bidder.
4 Interlocks
It shall be ensured that once the NIFPES gets activated manually or in auto mode, all the
connected breakers shall not close until the system is actually put in OFF mode. Also PNRV
shall get closed only if all the connected breakers are open.
5 Technical particulars
5.1 Fire extinction period
On commencement of nitrogen injection : Max. 30 secs.
From the moment of system activation to : Max. 3 mins.
Complete cooling.
Fire detectors heat sensing temperature : 1410C
Heat sensing area : 800mm radius
Pre-stressed non return valve setting for : minimum 60 ltr. Per operation.min.
Capacity of nitrogen cylinder : minimum 68 ltr. water cap.
and shall hold minimum 10 cubic mete gas
to 150 bar pressure.
Power Source :
Control Box : 110V DC/220V DC
Fire extinguishing cubicle for lighting : 230V AC
-2-
Annexure-IV
2 Rating (MVA)
4 Winding Connection
5 Vector Group
6 Number of Phase
7 Frequency (Hz)
8 Type of cooling
10 Impedance data
b Mounting
-3-
Guaranteed Technical Particulars of T/F
S. NO. DESCRIPTION PARTICULARS
ii Type
ii Type
f Radiator details
v Type of mounting
14 Thermal Data
i 1.25
ii 1.4
-4-
S. NO. DESCRIPTION PARTICULARS
iii 1.5
17 Bushings
a High voltage
i) Manufacturer
ii) Type
v) Mounting
b Low voltage
i) Manufacturer
ii) Type
iii) Mounting
i) Manufacturer
ii) Type
iii) Mounting
b) Number of steps
Guaranteed Technical Particulars of T/F
-5-
d) Step voltage
e) Type
21 Insulation level
a) HV windings
b) LV Winding
c) HV Bushing
d) LV Bushing
e) Neutral Bushing
22 Approximate dimensions
a) Tank (lxbxh) mm
b Windings (Kg)
c) Insulation (Kg)
e) Oil (Kg)
g) Total weight Kg
25 Clearances
i) In oil (mm)
26 Conservator
27 Capacitance values
a) HV to earth (pf)
-7-
Guaranteed Technical Particulars of T/F
30 Oil
a) Quality of oil
c) Standards applicable
31 Core
a) Type of construction
32 Winding
i) HV (A/Sq.cm)
ii) LV (A/Sq.cm)
c) Conductor area
i) HV (sq.mm)
ii) LV (sq.mm)
i) i) HV (sq.mm)
ii) LV (sq.mm)
33 Tank
a) Type
b) Material
c) Approx Thickness of
i) Sides (mm)
34 Radiator
a) Make
-9-
Guaranteed Technical Particulars of T/F
c) Thickness
a) Main Tank
37 Temperature indicators
a) OTI
i) Manufacturer
ii) Range
iii) Accuracy
b) WTI
i) Manufacturer
ii) Range
iii) Accuracy
c) RWTI
i) Manufacturer
ii) Range
iii) Accuracy
38 Terminal connectors
a) Make
c) Governing standard
Note: If there is any change in the above GTPs, same shall conform to Technical
Specifications/relevant ISS. If there is any change in GTPs, so warranted by specific make of
equipment, same shall be taken care at the time of approval of drawings.
- 10 -