Scaling, Corrosion and Water Treatment On Steam Generator Systems 30 Bar
Scaling, Corrosion and Water Treatment On Steam Generator Systems 30 Bar
Introduction of Referent
The referent is senior expert with over 40 years experience in Materials Investigation, Failure
Analysis, Water Chemistry and Corrosion in TÜV SÜD Industry Service, Munich, Germany.
Fig. 3 Oxygen corrosion on fire tube Fig. 4 Oxygen corrosion on smoke tube
of a horizontal shell boiler of a horizontal shell boiler
Fresh oxygen corrosion appears yellow-brownish, older corrosion and already heated corro-
sion spots brown to dark brown. Corrosion effects are intensified by increasing conductivity.
Other form of corrosion on lower pressure boiler systems is
- acid corrosion due to carbonic acid within steam and condensate lines, see Figs. 5+6,
because corrosion on carbon steel is as higher as lower the pH, and
- erosion corrosion or flow assisted corrosion (FAC) and cavitation, both significantly affected
by flow conditions.
FAC may be observed on pumps and pump impellers as well as on water pipes and valves as
the result of a too low pH in combination with too high flow rate, see Fig. 7.
Cavitation is the result of steam bubble formation and their subsequent implosion (distinct au-
dible!), e.g. on top of condensate pipes with condensate/steam mixtures, see Fig. 8 or pumps
operating in hot water. Elevated pressure at pump inlet solves the problem.
Fig. 9 Specific conductivity at 25 °C of some solutions of acids (1,2), bases (3,4) and salts (5-
10) in water.
TÜV SÜD Industry Services IS-ATW1-MUC, KW-Chemie-E 2007< 30bar Page 2
Industrial Seminar, Hung Yen 2007
TÜV SÜD
Industrie Service GmbH
Westendstrasse 199
80686 München Page 3
Germany
Dissolved in water, the above mentioned substances dissociate into ions with different electri-
cal charge depending of their valence. The ions are divided into cations with positive charge,
like mono-valent sodium ion (Na+), bi-valent calcium ion (Ca++) or tri-valent iron ion (Fe+++) and
anions with negative charge, like mono-valent chloride ion (Cl–), bi-valent sulphate ion (SO4– –)
or tri-valent phosphate ion (PO4– – –).
Also water (H2O) dissociates in traces into one mono-valent hydrogen (H+) cation and one
mono-valent negative hydroxyl ion (OH –), which leads to a very little electrical conductivity.
Purest water shows a conductivity at 25 °C of ca. 0.055 µS/cm corresponding to a specific
resistance of about 18.2 MΩ⋅cm = 18,200,000 Ω⋅cm!
For comparison, in Asia rain water may have a conductivity about 10-20 µS/cm, river water
(unaffected from sea water) 100 - 300 µS/cm and well water or domestic similar values. River
water near the sea and brackish water may have conductivity up to 10,000 - 20,000 µS/cm.
The conductivity of waters affects corrosion activities, as higher the conductivity as higher the
corrosion rate.
1.3.2 pH-Value
The very low dissociation of pure water defines the neutral pH of 7.0, values below pH 7 char-
acterise acidic conditions with increasing acidity down to pH 0 and pH values above 7 that of
basic or alkaline conditions up to pH 14. Attention: Any single pH-step results to a 10 fold con-
centration change! For instance, 0.4 mg/l caustic soda (NaOH) in pure water result to a pH of
9, a content of 4 mg/l NaOH to pH 10, 40 mg/l to pH 11 and 400 mg/l NaOH to a pH of 12 etc.
A caustic alkalinity of 1 mmol/l corresponds to 40 mg/l caustic soda (NaOH).
Moderate alkaline water conditions (pH 9-12) are important to protect iron from corrosion! Acid
or acidic water dissolves the magnetite protective layer and attacks iron/steel.
1.3.3 Hardness
The total hardness of water (mainly calcium and magnesium compounds) must be divided into
carbonate hardness and non-carbonate hardness.
Carbonate hardness (calcium-/magnesium-bi-carbonate) is only soluble in water together with
a specific amount of carbonic acid (carbon dioxide dissolved in water). If this amount of carbon
dioxide is removed due to boiling or reduced by spraying on air or heating, calcium carbonate
(lime stone) will precipitate and forms carbonate scale.
In tropical and sub-tropical countries with heavy rain falls and little lime stone formation, the
carbonate hardness of raw water is relatively low.
Non-carbonate hardness (calcium-/magnesium-chloride, -sulphate, -nitrate etc.) itself is well
soluble in water, only calcium sulphate (gypsum) forms scale if its concentration exceeds
about 2 g/l = 2,000 mg/l. Raw water - particularly river water contaminated with sea water - or
brackish water, shows high non-carbonate hardness because sea water contains - beside very
high sodium chloride content - also much calcium and magnesium chloride.
In presence of silica (silicon acid, silicon oxide) both, carbonate and non-carbonate hardness
are forming scale of calcium-/magnesium-silicate (silicate scale), which reduces heat transfer
extremely.
The most easy, safe and common way to remove hardness is application of a softener. It ex-
changes calcium and magnesium compounds to highly water soluble sodium compounds.
1.3.4 Alkalinity
Alkalinity allows determination of different water constituents, which are important for boiler
operation, by an easy titration method using 0.1 N acid for (positive) + M/P-values and 0.1 N
TÜV SÜD Industry Services IS-ATW1-MUC, KW-Chemie-E 2007< 30bar Page 3
Industrial Seminar, Hung Yen 2007
TÜV SÜD
Industrie Service GmbH
Westendstrasse 199
80686 München Page 4
Germany
base for (negative) – P/M values. Alkalinity is divided into total alkalinity, composite alkalinity
and caustic alkalinity.
The total alkalinity (+ M-alkalinity) indicates bicarbonates (e. g. from carbonate hardness, or
sodium bi-carbonate [reaction product of carbonate hardness in softeners] and includes the
composite alkalinity (+ P-alkalinity) and caustic alkalinity - if any. As far as water shows only
+ M-alkalinity, only bi-carbonates exist (like carbonate hardness or sodium bi-carbonate, which
is typical for raw water).
A negative M-value (– M-value) indicates acidic conditions at a pH below 4.3 and must be ti-
trated with 0.1 N NaOH.
The composite alkalinity (+ P-alkalinity) indicates all alkaline compounds above a pH 8.2 like
sodium carbonate, tri-sodium phosphate and free caustics (e.g. caustic soda) and has re-
placed measurement of caustic alkalinity. Composite alkalinity includes caustic alkalinity!
A negative P-value (– P-value) indicates a pH below 8.2 and weak alkaline and acidic condi-
tions respectively and must be titrated with 0.1 N NaOH.
The caustic alkalinity indicates the content of free caustics only, but needs a special procedure
before titration against P-indicator (Phenolphthalein).
The M-indicator (Methylorange) changes its colour at pH 4.3, the P-indicator (Phenolphthalein)
at pH 8.2, which means in presence of P-alkalinity the water is alkaline! The connection be-
tween +/ – P -value, +/ – M-value and pH and the changes of the indicators can be seen in
Fig. 10.
For shell boiler, the boiler water should be at least tested for composite alkalinity (P-alkalinity)
and total alkalinity (M-alkalinity).
Fig. 10
contact with oxygen (air) brown flocks are formed that may cause deposits in softeners and
reduce the activity of softener resin. Iron compounds lead to brown stains on fabrics.
In many cases aeration makes iron compounds removable in mechanical filters. For manga-
nese compounds aeration is often insufficient and stronger oxidation measures are necessary.
1.3.7 Organics
Organics in raw water may origin from nature (e.g. rotted leaves, peat) or human or industrial
sources (e.g. waste water, industrial effluents), also condensate return can be contaminated
through product (e.g. milk, vegetable oil, solvents). Many organics lead to foam formation in
steam generators that affects the steam quality due to carry over of boiler water. Some organ-
ics, like sugar and alcohols decompose to organic acids and lower the pH of the boiler water.
Oil and fat is able to set level control systems out of order, to block side glasses and may form
dangerous scale. Hydro carbons with boiling point below approx. 130 °C regularly do not have
negative effects to boiler.
1.3.8 Gases (Oxygen, Nitrogen, Carbon dioxide etc.)
Oxygen, nitrogen and carbon dioxide is always dissolved in water if it is or was exposed to air.
The solubility of all gases in water depends strongly on temperature, see Fig. 11. Oxygen
leads to oxygen corrosion on carbon or low-alloyed steel if the pH is too low and/or the steel
can not form or maintain a protective layer of magnetite. Nitrogen does not harm boiler opera-
tion. Carbon dioxide lowers the pH-value and leads to acid corrosion on carbon steel.
Fig. 11: Solubility of oxygen and nitrogen in pure water at 1 bar absolute
Oxygen and nitrogen in water is easy to reduce by heating and becomes nearly zero at boiling
conditions! Some chemicals, like sodium sulphite and hydrazine are able to bind oxygen
chemically. Carbon dioxide can be only removed by heating if the water’s pH is below 7-8 or at
pH > 8, if the operation temperature of a thermal deaerator is above 135-140 °C.
2 Water Treatment
Water treatment in this paper means any method to minimise scaling or corrosion in boilers.
It can be done in form of an “Inner water treatment” or “Extern water treatment”.
- Inner boiler water treatment or “chemical treatment” means treatment by exclusively dosing
of chemicals to the boiler feedwater or boiler water with the consequence of sludge forma-
tion within the boiler itself. Presupposition for this kind of water treatment is limited heat
transfer (steam production < 25 kg/m²⋅h), coal or wood firing (not oil!) and sufficient blow
down. The inner side of the boiler must be easy accessible to remove sludge.
This method may be used for small vertical shell boiler only.
- Extern boiler water treatment applies at least softening to bind hardness on the softener
resin and replace hardness by sodium, but can be improved by additional reverse osmosis
(RO) units or e.g. demineralisation. This treatment can be used for any kind of steam boiler
but requires also sufficient blow down to meet the related boiler feedwater and boiler water
requirements. It must be applied for water tube boiler!
The treated water is mostly dosed (conditioned) with some chemicals to adjust e. g. pH or
alkalinity. Thermal deaeration is also an external treatment step.
- Physical water treatment, using e.g. magnets, high frequency fields, high voltage fields etc.
is a not accepted method for boiler feed water or boiler water treatment, because all this
methods do not remove hardness and do not affect silica or silicates!
2.1 Inner boiler water Treatment
Scaling doe to hardness and silicates can be significantly reduced if sufficient tri-sodium phos-
phate is dosed proportional to the fed hardness and feedwater flow. Carbonate and non-
carbonate hardness react with phosphate and form calcium- and magnesium- phosphate
sludge, which remains mostly in suspended form in the boiler water. During operation, the
sludge must be removed by sufficient blow down. After operation, sediment sludge must be
removed by additional blow down.
Phosphate has a higher affinity to calcium and magnesium than carbonate or silica and avoids
formation of carbonate and silicate scale. In parallel carbonate hardness becomes exchanged
to sodium carbonate, which is alkaline, increases alkalinity and the solubility of silica.
For one cubic meter (m³) water with 1 meq/l hardness, an amount of 120 g tri-sodium phos-
phate (technical grade with 10 mol of crystal water, Na3PO4⋅10 H2O [20 % P2O5]) dissolved in
at least 5 l water is necessary. For instance, to treat 1 m³ feedwater with 3 meq/l = 1,5 mmol/l
= 150 mg/l CaCO3 total hardness an amount of ca. 350 g Na3PO4 ⋅10 H2O is necessary.
Inner boiler water treatment is easy, as far as the total hardness of the raw water is low (less
than 1-1.5 mmol/l), or rain water is used.
Fig. 12:
Fig. 13
Regeneration takes ca. 60 minutes and includes following steps: Back washing (to remove
unsolved particles from the resin bed, but not too fast - otherwise resin is lost!), application of
clear brine for about 30 minutes, rinsing of the brine, final rinsing and testing for hardness.
Necessary equipment for continuous supply of softened water: 2 softener filter (or one and a
storage tank) made of coated steel or glass fibre reinforced polyester, filter internals and resin,
flow meter, water meter, sampling valve for softened water, brine tank with side glass or level
control, injector to dilute brine to about 10 % salt solution and drain valve.
Attention: Softening is the minimal requirement for oil fired steam or hot water boiler with
common heat transfer and for water tube boiler, if there are no further requirements to boiler
operation and steam quality. Optimised quantity of condensate return is very advantageous.
TÜV SÜD Industry Services IS-ATW1-MUC, KW-Chemie-E 2007< 30bar Page 6
Industrial Seminar, Hung Yen 2007
TÜV SÜD
Industrie Service GmbH
Westendstrasse 199
80686 München Page 7
Germany
The water downstream of RO-units (so called permeate) that is fed with softened water is free
of hardness, shows low conductivity (regularly < 20 µS/cm, mostly due to sodium bicarbonate)
and silica < 0.2 mg/l SiO2!
During thermal deaeration, residual sodium bicarbonate decomposes to alkaline sodium car-
bonate, increases the pH and leads to an excellent weak alkaline BFW for low and medium
pressure boiler.
For pH adjustment in the BW dosing of tri-sodium phosphate is essentially!
RO-units need less control, space for installation, chemicals and are for a water demand
< 20-40 m³/day much cheaper and easier to handle than other treatment methods, but once
again the water pre-treatment must be done professionally.
Permeate is recommended if the conductivity of the raw water or boiler feedwater is high and if
better steam quality is required, e.g. for food production, cosmetic or pharmacy industry.
Optimised quantity of condensate return is very advantageous.
Fig. 14
Principles of Osmosis and
Reverse Osmosis (RO).
Fig. 15
Partly unrolled cross flow membrane
module
2.2.3 Deaeration
Thermal deaeration is the simplest way to minimise the content of dissolved gases in water
like oxygen, nitrogen and carbon dioxide, because their solubility in water depends strongly on
the temperature and becomes zero at boiling conditions, see Fig. 11.
Common are tray deaerator, sketch see Fig.16 operating at over-pressure of 0.3-1 bar. They
heat the BFW to temperatures > 100 °C and reduce oxygen to the limits < 0.02 mg/l as far as
the deaerator has a sufficient number (at least 4-5) of trays, like vertical deaerator. Horizontal
deaerator with 2-3 trays reduces the oxygen content only to about 0.1-0.3 mg/l.
For smaller plant at least partial thermal deaeration at temperatures between 50 and 80°C is
recommended, which can be easy achieved with sufficient hot condensate return and indirect
heating with blow-down water using a tube coil within the storage tank. Remaining oxygen can
be eliminated by dosing of an oxygen scavenger like sodium sulphite.
Fig. 16
Fig.17:
The smoke tubes are fitted into the front and rear tube-sheet with a gap between tube and
tube-sheet and welded at the flue gas side only, which leads to heated gaps at these spots
and to localised concentration of boiler water constituents within the gaps.
Water-tube boiler are mostly gas/oil/coal fired steam generators with natural or assisted circu-
lation for pressures up to 180 bar and a steam production in industrial plants up to approx.
500 t/hr equipped with super-heater, de-super-heater and feedwater pre-heaters.
Quick start up boiler are mainly small gas or oil fired water tube boiler with natural or forced
circulation that produce saturated steam in less than 30 minutes but with higher BW content in
steam than other boiler.
existing water treatment possible to meet the requirements under economical conditions?
Steam Purity and Steam Requirements is warranty related!
Check the boiler manufacturer’s guarantee of the steam produced and compare it with the
requirements or demand for processing. The BW content in steam should not exceed 0,1 -
0.2 %. As far as the steam is used for indirect heating only, up to 0.5 % BW content in steam
is acceptable. The BW content in steam must be guarantied by the boiler manufacturer!
Applicable Feedwater and Boiler Water Requirements are shown in the following for:
Water Treatment:
In general softening of the make-up water or boiler feedwater should be standard to avoid
scaling and sludge formation within the boiler.
If there is no make-up or boiler feedwater treatment with a softener, at least “Inner Boiler Wa-
ter Treatment” (IBWT) through dosing of suitable chemicals in sufficient amount must be ap-
plied.
Sufficient intermittent blow-down and rinsing of show glasses as well as external level control-
lers/indicators etc. is essentially, at least once per day, with IBWT every 8 hrs.
Requirements:
The following values show safety related minimum requirements for both softened boiler feed-
water and not softened feedwater that becomes treated within the boiler itself (“Inner Boiler
Water Treatment” (IBWT) to minimise corrosion and deposition.
Notes
a
Water samples must be clear filtered to get correct values!
b
Oxygen content is reduced physically if water is heated at ambient pressure up to:
- 85 °C the oxygen content is reduced to approx. 2 mg/l
- 95 °C the oxygen content is reduced to approx. 0.5 mg/l.
At lower temperatures the oxygen content can be reduced through dosing of oxygen
scavenger e. g. sodium sulphite.
c
Undissolved matter as sediment sludge after settling time of 1 hr.
Requirements:
The noted safety related minimum requirements for the boiler feedwater, boiler water or circu-
lating hot water are set to reduce the risk of corrosion, sludge formation or deposition within
the boiler. The values stated shall apply to continuous operation. During start-up, some values
may deviate for a restricted period of time and to a limited extent to be specified by the boiler
manufacturer.
A Steam Generator
A 1 Boiler Feedwater (BFW)
For boiler with operation pressure bar(g) > 0.5 - 15 > 15 - 30
∗ Total Hardness (Ca + Mg) a
ppm CaCO3 <2 <1
∗ pH value at 25 °C ⎯ (7.5) 8 - 9.5 8.5 - 9.5
∗ Oxygen b mg/l < 0.1 < 0.02
A 2.1 Boiler Water (BW) Using BFW with direct Conductivity > 30 µS/cm
Boiler with operation pressure bar(g) > 0.5 - 15 > 15 - 30
∗ Direct Conductivity at 25 °C c µS/cm < 4 000 < 2 000
∗ pH value at 25 °C ⎯ 10.5 - 12.0 10.5 - 11.8
∗ Composite Alkalinity (P-value) c ppm CaCO3 100 - 900 100 - 600
∗ Total Hardness (Ca + Mg) a ppm CaCO3 < 10 <3
∗ Phosphate (PO4) a, d mg/l 10 - 30 10 - 30
∗ Silica (SiO2) mg/l < 120 < 100
A 2.2 Boiler Water (BW) Using BFW with direct Conductivity ≤ 30 µS/cm
Boiler with operation pressure bar(g) > 0.5 - 15 > 15 - 30
∗ Direct Conductivity at 25 °C µS/cm < 2 000 < 1 000
∗ pH value at 25 °C ⎯ 10.5 - 11.5 10.5 - 11.3
∗ Composite Alkalinity (P-value) ppm CaCO3 25 - 250 10 - 100
∗ Total Hardness (Ca + Mg) a ppm CaCO3 <3 <1
∗ Phosphate (PO4) a, d mg/l 10 - 30 10 - 20
∗ Silica (SiO2) mg/l < 100 < 80
d
Tri-sodium phosphate dosing must be applied for shell boiler, if BFW with direct conductivity
≤ 30 µS/cm is used, but it is also recommended for BFW > 30 µS/cm!
∗ most important values; mg/l is equal to ppm in water.
keep Ca- /Mg-compounds in solution but are not too aggressive to iron oxides like chelants
and applicable for boiler pressure < 120 bars.
Chelants are strong complex forming agents like EDTA, NTA and keep hardness and metal
ions in solution. Too high concentrations attack the protective iron oxide layer and are not rec-
ommended in low pressure industrial boiler.
6 Preservation
Preservation means basically any method to avoid corrosion - mostly oxygen corrosion - on
the waterside of boilers, parts of it or auxiliary components made of low-alloyed steel during
shutdown and stand-by, but also during storage and transportation.
A sufficient and commonly present protective layer of iron oxides on the waterside of boilers
(being in operation before shut down for at least 1 month) is able to protect low-alloyed steel in
presence of humidity or moisture and air for restricted time only.
If softened water or permeate is used, the time without preservation is restricted to approx. 1
week, but with frequent shut-down times much shorter!
Exceeding times or frequent shut-down times requires preservation methods by either
- Wet preservation (in absence of air) e.g. by replacing of air by nitrogen or complete kept
filling of the boiler with at least alkaline water, better containing oxygen scavenger, or
- Dry preservation (in absence of moisture) by drying with desiccants, e.g. silica gel or
regenerative circulating dryers.