Air Conditioning COURSE معدل
Air Conditioning COURSE معدل
Fathy El-Wahsh
1.1. Introduction:
• Air Conditioning (A/C):
Is the science and practice of controlling the indoor climate in term of
temperature , air motion , humidity , air purity and noise.
• Psychrometry:
Psychrometry consists of the interactions between heat, moisture and air.
It is basically the study of moist air. and / or; the study of the properties of
mixtures of air and water vapor.
Atmospheric air:
Is a mixture of many gases plus water vapor and a number of pollutants
(Fig.1.1).
Moist Air :
Working substance in air conditioning is the moist air which is a mixture of two
gases .
One of these is dry air which itself is a mixture of a number of gases and the
other is water vapor which may exist in a saturated or super heated state.
Both are treated as perfect gases since both exist in the atmosphere at low
pressures . By: Dr. Fathy El-Wahsh
1.1. Introduction:
Moist Air :
Working substance in air conditioning is the moist air which is a mixture of two
gases .
One of these is dry air which itself is a mixture of a number of gases and the
other is water vapor which may exist in a saturated or super heated state.
Both are treated as perfect gases since both exist in the atmosphere at low
pressures .
In addition Gibbs-Dalton laws for non reactive mixture of gases can be applied
to the dry air part only to obtain its properties as a single pure substance .
T1 = T2 = T
V1 = V2 = V
P1 + P2 =P
m1 + m2 = m
P1 V1 = m1 R T1 & P2 V2 = m2 RT2
Indoor air for human comfort typically contains ~1% moisture by mass.
Sensible heat ( Qs ) :
Is the heat added or removed from the moist air at constant moisture content ( ω )
Latent heat ( Ql ) : Is the heat added or removed from the moist air at constant
DBT i.e. increases or decreases its By:
moisture contents .
Dr. Fathy El-Wahsh
Thermometers, dry bulb and
wet bulb
A SLING PSYCHROMETER.
Moist air also can be described in terms of the relative humidity Ø , defined as the
ratio of the mole fraction of water vapor in a given moist air sample to the mole
fraction in a saturated moist air sample at the same mixture temperature and
pressure :
,Also, the specific enthalpy of moist air per kg of dry air is given by
h = ha + ω hv
ha= Cpa T = 1.005 T
hv= Cpw Td + hfg + Cpv (T- Td) at Td= 0.0
hv= 2501 + Cpv T =2501 + 1.84 T
By: Dr. Fathy El-Wahsh
h = 1.005 T + ω ( 2501 + 1.84 T )
Humidity Ratio:
Mass Flow of Water Vapour mv
Mass Flow of Dry Air ma
m v RuT
paV m a RaT
m a RuT pvV m v RvT
Ma Mv
M v pvV
RuT M v pv pv
0.622
M a paV M a pa pa
RuT
Calculation of psychrometric properties from p, DBT and WBT:
Empirical Relations:
(a) The initial humidity ratio can be evaluated . This requires the partial pressure of
the water vapor, pv1, which can be found from the given relative humidity and pg
from Table at 70F as follows
1
3
ω1 = mv1/ma1
ω3 = mv3 /ma3
ω3 - ω1 = mω2/ma1
And dividing by ma1
• All data essential for the complete thermodynamic and psychometric analysis of
air conditioning processes can be summarized in a psychometric chart .
• Based on a barometric pressure of 101.325 kPa
• Sensible/total heat ratio for water added at 30°C
• Specific enthalpy (kJ/kg)
• Wet bulb temperature (°C) (sling)
• Specific volume (m3/kg)
• Percentage saturation
• Dry bulb temperature (°C)
• Specific enthalpy (kJ/kg)
• Moisture content (kg/kg) (dry air
ADP
Humidification. (a) Control volume. (b) Steam injected. (c) Liquid injected.
By: Dr. Fathy El-Wahsh
Evaporative Cooling
Tw
DBT
DBT WBT
WBT w
w
Tw
b. Adiabatic saturation: tw = tWBT. Here the sensible heat transfer from air to
water is exactly equal to latent heat transfer from water to air. Hence, no
external cooling or heating of water is required. That is this is a case of
pure water recirculation. This is shown by process O-B in Fig. 2.11. This
the process that takes place in a perfectly insulated evaporative cooler.
c. Cooling and humidification: tDPT < tw < tWBT. Here the sensible heat
transfer is from air to water and latent heat transfer is from water to air, but
the total heat transfer is from air to water, hence, water has to be cooled
externally. This is shown by Process O-C in Fig.2.11.
e. e) Heating and humidification: tw > tDBT. Here both sensible and latent
heat transfers are from water to air, hence, water has to be heated
externally. This is shown by Process O-E in Fig.2.11..
.
The sensible (QS) and latent (QL) heat transfer rates are given by:
Thus the total heat transfer and its direction depends upon the enthalpy
difference (or potential) between water and air (hi-ha).
If hi > ha; then the total heat transfer is from water to air and water gets
cooled.
If hi < ha; then the total heat transfer is from air to water and water gets
heated.
If hi = ha; then the net heat transfer is zero, i.e., the sensible heat transfer
rate is equal to but in the opposite direction of latent heat transfer.
Temperature of water remains at its wet bulb temperature value
• Example: In the previous example, water is sprayed at the rate of 4 kg water for every 1
kg air. What is the water temperature rise?
• Enthalpy of air before = 45.79 kJ/kg
• Enthalpy of air after = 26.7 kJ/kg
• Heat lost per kilogram air = 19.09 kJ
• Heat gain per kilogram water = 19.09/4 = 4.77 kJ
• Temperature rise of water =4.77/4.187= 1.1 K
Where :
trm which is the room dry-bulb temperature
tsa which is the supply air dry-bulb temperature
cfmsa which is the supply air quantity
tm which is the mixture of outdoor and return air dry-bulb temperature
tldb which is the leaving dry-bulb temperature
cfmda which is the dehumidfied air quantity
By: Dr. Fathy El-Wahsh
• Definitions
• Room Sensible Heat Ratio ( SHR ) = Room Sensible heat/Room Total heat;
• By Pass Factor (BPF) : Is the factor that determine the quantity of air that by pass
the cooling coil with out contacting its surfaces ;.
• Where TADP is the apparatus dew point temperature of the cooling coil .
• Grand sensible heat factor GSHF (for cooling coils):Is defined as the ratio
between grand sensible heat and the total heat removed by the coil;
• The first part is identical to that in the previous Example , and the second step is
the addition of sensible heat in a reheat coil.
Generally, the inputs are the building specifications and its usage
pattern and any other special requirements.
Metabolic Rate: The rate at which the chemical energy is converted into
heat and work.
Taking the human body as the control volume, one can write the
thermal energy (heat) balance equation for the human body as:
Where:
ADu = Surface area of the naked body, m2
m = Mass of the human being, kg
h = Height of the human being, m
The total heat transfer rate from the skin Qsk is given by:
Qsk = ± Qconv ±Qrad + Qevp
Where:
Qconv = Heat transfer rate due to convection (sensible heat)
Qrad = Heat transfer rate due to radiation (sensible heat), and
Qevp = Heat transfer rate due to evaporation (latent heat)
By: Dr. Fathy El-Wahsh
According to Belding and Hatch, the convective, radiative and
evaporative heat transfer rates from the naked body of an average adult ,
Qc, Qr and Qe, respectively, are given by:
The air inspired by a human being is at ambient conditions, while air expired is
considered to be saturated and at a temperature equal to the core temperature.
For comfort, the rate of heat stored in the body Qst should be zero, i.e.,
Qst = 0 at neutral condition
By: Dr. Fathy El-Wahsh
Factors affecting thermal comfort:
1. Physiological factors such as age, activity, sex and health. These factors
influence the metabolic rate. It is observed that of these factors, the most
important is activity. Other factors are found to have negligible effect on
thermal comfort.
2. Insulating factor due to clothing. The type of clothing has strong influence
on the rate of heat transfer from the human body. The unit for measuring the
resistance offered by clothes is called as “clo”. 1 clo is equal to a resistance of
about 0.155 m2.K/W.
The direct indices are the dry bulb temperature, humidity ratio, air velocity and
the mean radiant temperature (Tmrt).
The mean radiant temperature Tmrt affects the radiative heat transfer and is
defined (in K) as:
where:
Tg = Globe temperature measured at steady state by a thermocouple placed at
the center of a black painted, hollow cylinder (6” dia) kept in the conditioned
space, K.
Ta = Ambient DBT, K
V = Air velocity in m/s,
and C = A constant, 0.247 X 109 By: Dr. Fathy El-Wahsh
The derived indices combine two or more direct indices into a single factor.
Important derived indices are the effective temperature, operative temperature,
heat stress index, Predicted Mean Vote (PMV), Percent of People Dissatisfied
(PPD) etc.
Effective temperature (ET): This factor combines the effects of dry bulb
temperature and air humidity into a single factor.
It is defined as the temperature of the environment at 50% RH which results in
the same total loss from the skin as in the actual environment.
Operative temperature (Top): This factor is a weighted average of air DBT and
Tmrt into a single factor. It is given by:
Where:
hr and hc are the radiative and convective heat transfer coefficients and Tamb is
the DBT of air.
The scale is based on empirical equations relating the above comfort factors. The
scale varies from +3 (hot) to –3 (cold) with 0 being the neutral condition.
Then a Predicted Mean Vote (PMV) that predicts the mean response of a large
number of occupants is defined based on the thermal sensation scale.
The PMV is defined by Fanger as: PMV=[0.303exp(−0.036M)+ 0.028]L
where
M: is the metabolic rate and L: is the thermal load on the body that is the
difference between the internal heat generation and heat loss to the actual
environment of a person experiencing thermal comfort.
The thermal load has to be obtained by solving the heat balance equation for the
human body.
[
PPD=100 − 95 exp − (0.03353 PMV 4 +El-Wahsh
By: Dr. Fathy 0.2179 PMV2 ) ]
Selection of outside design conditions:
The ambient temperature and moisture content vary from hour-to-hour and
from day-to-day and from place-to-place.
For most of the major locations of the world, meteorological data is available
in the form of mean daily or monthly maximum and minimum temperatures
and corresponding relative humidity or wet bulb temperature.
2-Air at condition of DBT = 45ċ , RH= 20 % enter to an air cooler and exit at RH= 60 % . Find
: a) DBT of exit air . b) The moisture content (ω ) at exit . c) plot the psychometric process .
( answers a- 31.5 ċ , b- 5.5 kg wv /kg da ) .
3- Moist air at DBT =30ċ and WBT = 25ċ enter a cooling coil and exit from it at saturation
state with DBT = 15 ċ . IF the air is supplied to the coil at 3 m3 /s find : a) All the properties
of air at inlet and outlet . b) The sensible heat that has been removed by the cooling coil .
c) The a mount of moisture that has been removed from the air by the cooling coil. (
answers a-hin = 77 kJ/kg , ω1=0.018 kg wv/kg da ,ν1= 0.882 m 3/kg , RH1 = 68%. , Tdp =
23.4 ċ , h2 = 42 kJ/kg , ω2 =0.0106 kg wv /kg da ,ν2= 0.831 m3/kg , RH2 = 100 % b- 115.6
kW c- 0.0248 kg wv/s ) .
4-Two air streams are mixed the first at DBT=21ċ ,WBT= 14ċ and the second at DBT= 28ċ
,WBT= 20 ċ with mass flow rates of 1 kg/s and 3 kg/s for the first and second respectively .
Find the moisture content ,enthalpy ,and the DBT for the mixture and plot the process on
the psychometric chart . (answers : 0.01 kgwv/kgda , 52.15 kJ/kg , 26.25 ċ ) .
By: Dr. Fathy El-Wahsh
Psychometric analysis and air conditioning cycles :
These analysis include summer air conditioning cycle and winter air conditioning
cycle which may cover the four basic combined processes discussed previously :
1- Cooling and dehumidification process: There four methods that may be used
to carry out the dehumidification process . a) cooling the air to temperature
below its dew point, b) using absorption process , d) using adsorption materials,
c) compress and cool the air . The first method represents the normal practice to
cool and dehumidify the moist air in air conditioning systems .
• The winter air conditioning cycle can be done into two methods .
• The first method is to preheat the air and then cooling it adiabatically up to a
given point and then reheat it to the supply conditions .
• The other method is to heat the air and then used an air washer to humidify the
air up to a given point then reheat it to the supply conditions .
Fig.4.2: A summer air conditioning system with outdoor air for ventilation and
a zero by-pass factor
Thus the actual benefit of reheat coil depends may vary from system.
ii. The cooling coil should have 2 to 6 rows for moderate climate and 6 to 8
rows in hot and humid climate. The by-pass factor of the coil varies from 0.05
to 0.2. The bypass factor decreases as the number of rows increases and vice
versa. The fin pitch and air velocity should be suitable.
iii. If chilled water is used for cooling and dehumidification, then the coil ADP
will be higher than about 4oC. By: Dr. Fathy El-Wahsh
EVAPORATIVE AIR CONDITIONING SYSTEMS:
Introduction
Evaporative air conditioning systems are inexpensive and offer an attractive
alternative to the conventional summer air conditioning systems in places,
which are hot and dry.
This system is based on the principle that when moist but unsaturated air
comes in contact with a wetted surface whose temperature is higher than the
dew point temperature of air, some water from the wetted surface
evaporates into air.
The latent heat of evaporation is taken from water, air or both of them. In
this process, the air loses sensible heat but gains latent heat due to transfer
of water vapor. Thus the air gets cooled and humidified.
The cooled and humidified air can be used for providing thermal comfort.
By: Dr. Fathy El-Wahsh
Classification of Evaporative Cooling Systems:
1. Direct evaporation process
2. Indirect evaporation process
3. A combination or multi-stage systems
The air gets cooled and dehumidified due to simultaneous transfer of sensible
and latent heats between air and water- air is brought in contact with the
wetted surface or spray of water droplets in the air washer-
The cooled and humidified air is supplied to the conditioned space, where it
extracts the sensible and latent heat from the conditioned space.
Thus the moisture content of the supply air remains constant in an indirect
evaporative cooling system, while its temperature drops.
One simple improvement is to sensibly cool the outdoor air before sending it
to the evaporative cooler by exchanging heat with the exhaust air from the
conditioned space.
It is also possible to mix outdoor and return air in some proportion so that
the temperature at the inlet to the evaporative cooler can be reduced,
thereby improving the performance.
Evaporative cooling systems are ideal in hot and dry places, i.e., in
places where the dry bulb temperature is high and the coincident wet
bulb temperature is low.
By: Dr. Fathy El-Wahsh
Fig.5.3: A two-stage evaporative
cooling system
5. Ensures a very good ventilation due to the large air flow rates involved,
hence, are very good especially in 100 % outdoor air applications
6. Better air distribution in the conditioned space due to higher flow rates
2. Since the required air flow rates are much larger, this may create
draft and/or high noise levels in the conditioned space
• Example :
• Refrigerant For the same duty, liquid R.22 enters the expansion valve at 33°C, evaporates
at 5°C, and leaves the cooler at 9°C. Fan power is 0.9 kW. What mass flow of refrigerant is
required?
• Total load, = 16.4 kW
• Enthalpy of R.22, evaporated at 5°C,superheated to 9°C = 309.39 kJ/kg
• Enthalpy of liquid R.22 at 33°C = 139.84 kJ/kg
• Refrigerating effect = 169.55 kJ/kg
• Required refrigerant mass flow, 16.4/(169.55)= 0.097 kg/s
Example :
A room is to be maintained at 21°C, with a preferred 50% saturation, using air at 13°C dry
bulb, 78% saturation and reheat. The load is 0.7 sensible/total ratio. (See Figure below) .Air at
the supply condition can be re-heated to about 18°C and will rise from 18°C to 21°C in the
room, picking up the quantity of heat ‘B’ as shown. The final condition will be 50% saturation,
as required (line abc).
Alternatively, supply air is used directly, without re-heat. It now picks up the quantity of heat
‘A’ (about three times as much) and only one-third the amount of air is needed. The final
condition will be about 55% saturation. This is still well within comfort conditions, and should
be acceptable (line ad).
1- Sol-Air Temperature:
and Rsi is the inside surface thermal resistance, Rso is the outside surface
thermal resistance, and R1, R2, etc. are the thermal resistances of the
composite layers of the fabric.
• The amount of heat to be removed (or supplied in winter) to treat the fresh
air supply can be calculated, knowing the inside and ambient states.
• It must be broken into sensible and latent loads, since this affects the coil
selection.
• 2. Supply system heat gain qss, because of the supply fan heat gain qsf , and supply
duct heat gain qsd
• 3. Return system heat gain qrs because of heat gains of recessed electric lights and
ceiling plenum qrp, of return duct qrd , and return fan qrf , if any
• 4. Sensible and latent load because of the outdoor ventilation rates Qo to meet the
requirements of the occupants and others. In Fig., the summer air conditioning cycle O-
m-cc-s-r-rf-m consists of an adiabatic mixing process O-m-rf, a cooling and
dehumidifying process m-cc, a supply system heat gain process cc-s,a space conditioning
process r-s, and a return system heat gain process r-rf. Here, O indicates the status of
outdoor air, m the mixture of outdoor air and recirculating air, cc the conditioned air
leaving the coil, s the supply air, r the conditioned space, and rf the recirculating air
By: Dr. Fathy El-Wahsh
Sensible and latent load because of the outdoor ventilation
rates Qo to meet the requirements of the occupants and
others
2. The space cooling load is used to determine the supply volume flow rate , whereas the
coil load is used to determine the size of the cooling coil in an air-handling unit or DX coil in a
packaged unit.
3. A cooling load component influences both and the size of the cooling coil, whereas a
cooling coil load component may not affect .
4. Infiltration heat gain is an instantaneous cooling load. From Fig. 6.4, it is apparent that
the load due to the outdoor ventilation air Qo, sometimes called the ventilation load, is a coil
load. If Qo is considered a cooling load, the volume flow rate of the air system will be
oversized
By: Dr. Fathy El-Wahsh
Air-conditioning methods
• Requirement
• The cooling load of an air-conditioned space comprises estimates of the sensible
and latent heat gains, and is QS + QL. This rate of heat flow is to be removed by a
cooling medium which may be air,water, brine or refrigerant, or a combination of
two of these.
Removal of sensible and latent heat from conditioned space. (a) Flow of cooling
medium. (b) Process line By: Dr. Fathy El-Wahsh
Central station system. All air
All-air system
The centralization of all plant away from the
conditioned space, originating from considerations of
safety, also ensures the best access for operation and
maintenance and the least transmission of noise.
Since all air passes through the plantroom, it is possible
to arrange for any proportion of outsideBy:air
Dr. Fathy
up toEl-Wahsh
100%.
Re-heat for individual zones
Where a central plant serves a number of separate rooms and floors, this resolves
into a system with re-heat coils in each zone branch duct. It will be recognized that
this is wasteful of energy and can, in the extreme, require a re-heat load almost as
high as the cooling load.
• In air-conditioning systems, all flow is turbulent, and formulas and charts show the
resistance to air flow of ducting of various materials, together with fittings and changes
of shape to be met in practice.
• Velocities in common use are as follows:
• High-velocity system, main ducts 20 m/s
• High-velocity system, branch ducts 15 m/s
• Low-velocity system, main ducts 10 m/s
• Low-velocity system, branch ducts 6 m/s
• Ducts in quiet areas 3–4 m/s
• The frictional resistance to air flow within a duct system follows the general law:
where a is a coefficient based on the roughness of the duct surface and the density of the air.
Duct-sizing charts are based on this law. Since such charts cannot cater for all shapes, they
give resistances for circular ducts, and a subsidiary chart shows how to convert rectangular
shapes to an equivalent resistance round duct.
By: Dr. Fathy El-Wahsh
• Pressure Characteristics of the Airflow
• Equal-Friction Method
• This method sizes the air duct so that the duct friction loss per unit length at various duct
sections always remains constant. The final dimensions of sized ducts should be rounded
to standard size. The total pressure loss of the duct system equals the sum of the frictional
• losses and dynamic losses at various duct sections along the critical path.
d
c
FIGURE .Various types of air duct: (a) rectangular duct; (b) round duct with spiral
seam; (c) flat oval duct; (d) flexible duct.
By: Dr. Fathy El-Wahsh
Heat Recovery
• The aim of heat recovery is to avoid wastage of any quantity of heat or cold
energy which has been generated within a system. Methods of recovery may
be passive or active. Mechanical heat recovery systems will generally be
found under the description of Heat Pumps. Recovery of rejected or wasted
heat requires a careful analysis of the heat flow within the systems under
survey.
Points to examine are:
1. Where cooled or warmed air is exhausted from a building or process, this
might be used in heat exchangers to pre-cool or pre-warm fresh air brought in to
replace it.
2. Where cooled or warmed liquids leave a process, heat exchangers can
provide the means of pre-cooling or pre-warming fresh liquids entering. One of
the main instances of this is the warm waste water from showers in changing
rooms.
3. Hot discharge gas from a refrigeration circuit can be used to heat water .
4. Condenser heat can be diverted into a building, for heating in winter.
• 1. The rotating heat exchanger wheel. The wheel has a rotating matrix, the
mass of which picks up heat from one duct air flow and transfers it to the other.
If the matrix is coated in a hygroscopic material, there may also be some
transfer of moisture.
• 2. Coils in the two ducts, with a fluid circulated between them. It is important to
get the fluid in counterflow in the two airstreams (see also Figure 1.4c). If fresh
air is to be heated in winter, the fluid must be a non-freeze solution.
• 3. Heat pipes between the two ducts. These comprise a coil made with closed
pipes, filled with a volatile liquid. This liquid will condense in one coil and
evaporate in the other, at the same pressure and therefore at the same
temperature
• Many of these devices are direct acting on the controlled device and do not
require a controller to process the signal.
By: Dr. Fathy El-Wahsh
• Proportional detectors measure the process condition, which can then be compared
by the controller with the required value. They are not direct acting, and need a
controller to convert the signal to a working instruction to the controlled device.
Proportional detectors include:
The primary function of an AHU is to transmit processed air from the air
conditioning plant to the conditioned space and distribute it properly
within the conditioned space.
3. Supply and return air fans which provide the necessary energy to
move the air throughout the system
Where:
Ρ/ρg is the pressure head, V2/2g is the velocity head and Z is the static head,
In all actual fluid flows, some energy will be lost in overcoming friction, this is
referred to as head loss.
The head loss will cause the total pressure to decrease in the flow direction.
Then Bernoulli’s equation can be modified to:
To overcome the fluid friction and the resulting head, a fan is required in
air conditioning systems.
The FTP should be such that it overcomes the pressure drop of air
as it flows through the duct and the air finally enters the conditioned
space with sufficient momentum so that a good air distribution can
be obtained in the conditioned space.
Where:
f is the dimensionless friction factor, L is the length of the duct and D is the diameter
in case of a circular duct and hydraulic diameter in case of a non-circular duct.
Where:
Q. air is the volumetric flow rate of air in m /s, L is the length and D is the inner
3
Rectangular ducts:
Where:
K is the dynamic loss coefficient, which is normally obtained from experiments.
a) Turns, bends or elbows: The most common type of bends used in air
conditioning ducts are 90⁰ turns shown in Fig.
The equivalent lengths are available as function of geometry for other types
of turns and bends
Where:
Vd and Vu are the air velocities in the downstream and upstream ducts, respectively.
The dynamic pressure drop from the upstream (u) to branch (b), Δpu-b is given by:
Introduction:
The purpose of the duct design is to select suitable dimensions of duct
for each run and then to select a fan, which can provide the required
supply airflow rate to each conditioned zone.
The following methods are most commonly used for simpler lay-outs
such as the one shown in Fig.8.1.
1. Velocity method
2. Equal Friction Method
3. Static Regain method
ii. Find the diameters of main and branch ducts from airflow rates and velocities
for circular ducts. For rectangular ducts, find the cross-sectional area from flow
rate and velocity, and then by fixing the aspect ratio, find the two sides of the
rectangular duct
iii. From the velocities and duct dimensions obtained in the previous step, find the
frictional pressure drop for main and branch ducts using friction chart or
equation.
iv. From the duct layout, dimensions and airflow rates, find the dynamic pressure
losses for all the bends and fittings
v. Select a fan that can provide sufficient FTP for the index run
vi. Balancing dampers have to be installed in each run. The damper in the index
run is left completely open, while the other dampers are throttled to reduce the
flow rate to the required design values.
By: Dr. Fathy El-Wahsh
2. Equal friction method:
In this method the frictional pressure drop per unit length in the main and
branch ducts (Δpf/L) are kept same, i.e.,
Then the stepwise procedure for designing the duct system is as follows:
I. Select a suitable frictional pressure drop per unit length (Δpf/L) so that the
combined initial and running costs are minimized.
ii. Then the equivalent diameter of the main duct (A) is obtained from the selected value
of (Δpf/L) and the airflow rate. As shown in Fig.8.1, airflow rate in the main duct Q. A is
equal to the sum total of airflow rates to all the conditioned zones, i.e.,