The document discusses the measurement of winding resistance in transformers. It explains that winding resistance measurement determines the quality of connections and status of the winding. The measurement requires time for the current to stabilize due to the energy stored in the inductor. Larger transformers require more time for magnetization to stabilize before an accurate reading can be made. A formula is provided to calculate resistance at a desired temperature based on the measured resistance and temperatures. An example transformer specification is given along with the estimated time of 4 hours and 15 minutes to complete winding resistance tests on its windings.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
32 views34 pages
Shamco Winding Resitance Tests
The document discusses the measurement of winding resistance in transformers. It explains that winding resistance measurement determines the quality of connections and status of the winding. The measurement requires time for the current to stabilize due to the energy stored in the inductor. Larger transformers require more time for magnetization to stabilize before an accurate reading can be made. A formula is provided to calculate resistance at a desired temperature based on the measured resistance and temperatures. An example transformer specification is given along with the estimated time of 4 hours and 15 minutes to complete winding resistance tests on its windings.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34
1.
Measurement of the Total Path
Resistance of all copper conductor and connections between two points 2. It is the DC Resistance. 1. Determine quality of connections: 1. Bushing Cap to Lead Conductor 2. Conductor to Tap Changer 3. Low Voltage Lead to Low Voltage Bushing 4. State of Brazed Connections 2. Determine the status of the Winding 1. Broken Strands 2. Open Circuits 3. Shorted Turns The voltage across an inductor is proportional to the rate of change of the current with time through it. v = L di/dt
The energy stored in an inductor with a circulating current
can be represented by the formula: w (t) = 1/2 I2L Where, w(t) = Energy as a function of time I = Current in amperes L = Inductance in Henry Before the desired current will flow (for testing purposes), this energy requirement must be met and implies that some time requirement will also be necessary before the measurement can be made. This time requirement applies only to the charging time. Additional time must be allowed to stabilize the current before a measurement can be made. The ultimate time required to make a reading is limited by an inherent time lag between the application of a steady current and the time the magnetization of the core becomes stable. Depending on the size and the construction of the transformer, testing times could be very short for small transformers or very long for the larger, highly inductive transformers. Ts Tk Rs Rm Tm Tk Rs=Resistance at Desired Temperature Ts Rm=Resistance Measured Ts=Desired Temperature Tm=Temperature at which Measurement is taken Tk=234.5 for Copper, 225 for Aluminum Td Steady State Resistance Measurement Resistance
Winding Resistance •H1-H0: 17 taps at 5 min per test i.e. 85 mins •H2-H0: 17 taps at 5 min per test i.e. 85 mins •H3-H0: 17 taps at 5 min per test i.e. 85 mins
•Therefore winding Resistance tests: 255min or 4 hours 15
minutes excluding setup, LV side tests and initial winding charge assuming LTC