The document describes the JUPITER-9000K/6000K/3000K-H1 Smart Transformer Station. It is a prefabricated and pre-tested station housed in a 20' shipping container for easy transportation. It features a high efficiency transformer, low self-consumption for higher solar yields, real-time monitoring of components, and remote control capabilities. The technical specifications table provides details on the input, output, protection, and general characteristics of the transformer stations.

Uploaded by

Andrei Taranu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
217 views

Model Transformator

The document describes the JUPITER-9000K/6000K/3000K-H1 Smart Transformer Station. It is a prefabricated and pre-tested station housed in a 20' shipping container for easy transportation. It features a high efficiency transformer, low self-consumption for higher solar yields, real-time monitoring of components, and remote control capabilities. The technical specifications table provides details on the input, output, protection, and general characteristics of the transformer stations.

Uploaded by

Andrei Taranu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

JUPITER-9000K/6000K/3000K-H1

Smart Transformer Station

Simple Efficient
Prefabricated and Pre-tested, No Internal Cabling Needed Onsite High Efficiency Transformer for Higher Yields
Compact 20’ HC Container Design for Easy Transportation Lower Self-consumption for Higher Yields

Smart Reliable
Real-time Detection of Transformer, LV Panel and RMU Robust Design against Harsh Environments
High Precision Sensor of LV Electricity Parameters Optimal Cooling Design for High Availability and Easy O&M
Remote Control of ACB and MV Circuit Breaker Comprehensive Tests from Components, Device to Solution

Schematic Diagram

Transformer

LV Panel RMU

SOLAR.HUAWEI.COM
JUPITER-9000K/6000K/3000K-H1
Technical Specifications
Technical Specifications JUPITER-9000K-H1 JUPITER-6000K-H1 JUPITER-3000K-H1

Input
Available Inverters SUN2000-330KTL-H1 / SUN2000-330KTL-H2
Max. LV AC Inputs 30 22 11
1 1 1
AC Power 9,000 kVA @40℃ 6,600 kVA @40℃ 3,300 kVA @40℃
Rated Input Voltage 800 V
LV Panel Segregation Form 2b
LV Main Switches ACB (4,000 A, 2 x 1 pcs) ACB (2,900 A, 2 x 1 pcs) ACB (2,900 A, 1 x 1 pcs)
LV Main Switches for SUN2000-330KTL MCCB (400 A, 2 x 15 pcs) MCCB (400 A, 2 x 11 pcs) MCCB (400 A, 11 pcs)
Output
2
Rated Output Voltage 10~35 kV
Frequency 50 Hz or 60 Hz
Transformer Type Oil-immersed, Conservator Type
Transformer Cooling Type ONAN
Transformer Tappings ± 2 x 2.5%
Transformer Oil Type Mineral Oil (PCB Free)
Transformer Vector Group Dy11-y11 Dy11
Transformer Min. Peak Efficiency Index Tier 1 or Tier 2 In Accordance with EN 50588-1
RMU Type SF6 Gas Insulated
RMU Transformer Protection Unit MV Vacuum Circuit Breaker Unit
RMU Cable Incoming / Outgoing Unit Direct Cable Unit or Cable Load Break Switch Unit
Auxiliary Transformer Dry Type Transformer, 5 kVA, Single-phase, li0
Output Voltage of Auxiliary Transformer 230 / 127 Vac
Protection
Transformer Detection & Protection Oil Level, Oil Temperature, Oil Pressure and Buchholz
Protection Degree of MV & LV Room IP 54
Internal Arcing Fault of STS IAC A 20 kA 1s
MV Relay Protection 50/51, 50N/51N
LV Overvoltage Protection Type I+II
Anti-rodent Protection C5-Medium
Features
2 kVA UPS Optional 3
MV Surge Arrester for Transformer Optional 3
General
Dimensions (W x H x D) 6,058 x 2,896 x 2,438 mm (20’ HC ISO Container)
Weight < 28 t < 23 t < 15 t
Operating Temperature Range -25℃ ~ 60℃ 4

Relative Humidity 0% ~ 95% (Non-condensing)


Max. Operating Altitude 1,000 m 5

MV-LV AC Connections Prewired and Pretested, No Internal Cabling Onsite


LV & MV Room Cooling Smart Cooling without Air-across for Higher Availability
Communication Modbus TCP, Preconfigured with SmartACU2000D
Standards Compliance
IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1
1: More detailed AC power of STS, please refer to the de-rating curve.
2: Rated output voltage from 10 kV to 35 kV, more available upon request
3: Extra expense needed for optional features which standard product doesn’t contain, more options upon request.
4: When ambient temperature ≥55℃, awning shall be equipped for STS on site by customer.
5: For higher operating altitude, pls consult with Huawei.