Covered Court Arc Design
Covered Court Arc Design
NOTE:
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR SUMMARY
ENGINEERING ASST. SQ 2
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF OF
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO QUANTITIES
PREPARED: SHARYN C. SUPEÑA 1 1 15
CALINOG, ILOILO GIZA P. PLAZA ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
TABLE OF CONTENTS REPUBLIC OF THE PHILIPPINES
STRUCTURAL
SANITARY
PLUMBING
ELECTRICAL
E-1 VOLTAGE DROP CALCULATION,
SCHEDULE OF LOADS W/ BACK UP
COMPUTATION, ELECTRICAL PLAN, ONE
LINE DIAGRAM, GENERAL NOTES, LEGEND
ELECTRICAL
THIS SITE BILLBOARD
PB PROJECT BILLBOARD
LINOG
TO POB. CA
MECHANICAL
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR PERSPECTIVE, ENGINEERING ASST. A-1 3
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF SITE DEVELOPMENT
PREPARED: ALAN M. LACUESTA JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO PLAN,
VICINITY MAP
1 5 15
CALINOG, ILOILO GIZA P. PLAZA ARCHITECT II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
SCHEDULE OF SPAN PER COLUMN
NAME LENGTH SPAN ( LS)
SPAN-1 4500 MM
SPAN-2 4500 MM
SPAN-3 5000 MM
B SPAN-3&4 10000 MM A B C D E F G
SPAN-4 5000 MM
A B C D E F G SPAN-5 4500 MM 0.50MM THK. PRE PAINTED HI- RIB
CURVE TYPE LONG SPAN ROOFING
0.701mm THK. PRE- PAINTED
LENGTH SPAN-6 4500 MM GUTTER (GAUGE 24)
( BOX TYPE)
FLOOR LENGTH = 28000 MM APEX LINE OF TRUSS
1000 SPAN-1 SPAN-2 SPAN-3 & 4 SPAN-5 SPAN-6 1000
FLOOR WIDTH = 14000 MM
3500
TOP OF ROOF BEAM
8600
EXISTING STAGE
5000
1500
1500
2 2
TOP OF COURT SLAB
100
NATURAL GROUND LINE
FRONT
3
A-2
ELEVATION
FRONT ELEVATION
SCALE 1:150 M
WIDTH
A A
G F E D C B A
1 1 ( BOX TYPE)
1500
1500
APEX LINE OF TRUSS
3500
1000 SPAN-1 SPAN-2 SPAN-3 SPAN-4 SPAN-5 SPAN-6 1000
TOP OF ROOF BEAM
LENGTH
8600
A B C D E F G
5000
B
TOP OF COURT SLAB
100
NATURAL GROUND LINE
1
FLOOR PLAN
FLOOR PLAN REAR
2 ELEVATION
REAR ELEVATION
A-2 SCALE 1:150 M A-2 SCALE 1:150 M
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR FLOOR PLAN, FRONT
ELEVATION,
ENGINEERING ASST. A-2 4
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF RIGHT ELEVATION,
PREPARED: ALAN M. LACUESTA JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO SCHEDULE OF
SPAN PER COLUMN
2 3 15
CALINOG, ILOILO GIZA P. PLAZA ARCHITECT II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
1 2 2 1
0.551MM THK. PRE- PAINTED 0.701mm THK. PRE- PAINTED 0.551MM THK. PRE- PAINTED 0.701mm THK. PRE- PAINTED 50
SIDE FLASHING (GAUGE 26) GUTTER (GAUGE 24) SIDE FLASHING (GAUGE 26) GUTTER (GAUGE 24) 10
( BOX TYPE) ( BOX TYPE)
0
50
APEX LINE OF TRUSS APEX LINE OF TRUSS
50
350
350
3500
3500
250
TOP OF ROOF BEAM TOP OF ROOF BEAM
8600
8600
GUTTER BEND LAYOUT
SB-1 SB-1 GUTTER
7
A-3
BEND LAYOUT
SCALE 1:20 M
5000
5000
TOP OF COURT SLAB TOP OF COURT SLAB
100
100
NATURAL GROUND LINE NATURAL GROUND LINE
CU
RV
A-3 SCALE 1:150 M A-3 SCALE 1:150 M
E
RO
OF
IN
G
G.I. STRAP AT 1200 MM O.C.
STAINLESS STRAINER
2 1
PRE- PAINTED GUTTER
( BOX TYPE)
1500
SB-1
6 EAVES DETAIL
A-3 SCALE 1:20 M
SLOPE
WITDH
3500
SEE TRUSS DETAIL
8600
1500
1500
5000
RD RD RD RD RD RD RD
1000 LENGTH 1000
TOP OF COURT SLAB
100
NATURAL GROUND LINE
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR FLOOR PLAN, FRONT
ELEVATION,
ENGINEERING ASST. A-3 5
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF RIGHT ELEVATION,
PREPARED: ALAN M. LACUESTA JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO SCHEDULE OF
SPAN PER COLUMN
3 3 15
CALINOG, ILOILO GIZA P. PLAZA ARCHITECT II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
GENERAL CONSTRUCTION NOTES
GENERAL NOTES NOTES ON REINFORCEMENT NOTES ON COLUMNS
1. IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN AND DISTANCES AND SIZES SHALL NOT BE 1. UNLESS OTHERWISE NOTED IN PLANS, THE YIELD STRENGTH OF REINFORCING BRS SHALL BE: 1. PROVIDE EXTRA SETS OF TIES AT 100mm O.C. FOR TIES COLUMN REINFORCEMENT ABOVE AND BELOW
SCALED FOR CONSTRUCTION PURPOSES. A. FOOTINGS, FOOTING BEAMS AND GIRDERSS--------------fy = 414 MPa (60,000 psi ) BEAM-COLUMN CONNECTIONS FOR A DISTANCE FROM FACE OF CONNECTION EQUAL TO THE GREATER OF
THE OVERALL THICKNESS OF COLUMN, 1/6 THE CLEAR HEIGHT OF COLUMN OR 450mm.
B. COLUMNS AND SHEAR WALLS ------------------------------------fy = 414 MPa (60,000 psi)
2. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESIONS IN FLOOR SLABS, OPENINGS IN THE
WALLS AND SLABS, INTERIOR PARTITIONS, LOCATION OF DRAINS ETC. C. BEAMS AND GIRDER---------------------------------------------------fy = 414 MPa (60,000 psi)
NOTES ON BEAMS AND GIRDERS
2. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST MONOLITHICALLY 1. UN LESS, OTHERWISE NOTED IN THE PLANS. CAMBER ALL BEAMS AND GIRDER AT LEAST 6mm FOR EVERY
D. NO-LOAD BEARING WALL PARTITIONS, BEDDED SLABS, FLOOR & ROOF SLABS, PARAPETS, CATCH BASIN, 4.50m OF SPAN. EXCEPT CANTILEVERS FOR WHICH THE CAMBER SHALL BE AS NOTED IN THE PLANS OR AS
SIDEWALK,---------------------------------------------------------------------fy = 275 MPa (40,000 psi) WITH THE CORE WITH THE MINIMUM THICKNESS OF 40mm AND NOT LESS THAN 40 TIMES THE MAXIMUM SIZE
3. IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS, AND ELEVATIONS BETWEEN THE STRUCTURAL PLANS, AND ORDERED BY THE ENGINEER BUT IN NO CASE LESS THAN 20mm FOR EVERY 3.0m OF FREE SPAN.
OF COARSE AGGREAGATEE IN MILIMETERS.
ARCHITECTURAL DRAWINGS, THE CONTRACTOR SHALL NOTIFY BOTH STRUCTURAL ENGINEER AND ACRCHITECT.
2. ALL REINFORCING BARS SIZE 10mm OR LARGER SHALL BE DEFORMED IN ACCORDANCE WITH A STM A 706. BARS SMALLER THAN 3. WHERE COLUMNS CHANGE IN SIZE. VERTICAL REINFORCEMENTS SHALL BE OFFSET AT A SLOPE OF NOT
10mm MAY BE PLAIN. 2. TYPICAL BARS BENDING AND CUTTING DETAILS FOR BEAMS SHALL BE AS SHOWN IN FIG. B-1
MORE THAN 1 IN 6 AND EXTRA 10mm TIES AT 100mM SHALL BE PROVIDED THRU OUT THE OFFSET REGION.
4. ALL CONCRETE WORK SHALL BE DONE IN ACCORDANCE WITH ACI318-95 BUILDING CODE REQUIREMENTS FOR REINFORCED 3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE W/ TABLE A & TABLE B ( TABLE OF LAP
CONCRETE AND ALL STRUCTURAL STEEL WORK ACCORDING TO AISC SPECIFICATION (9TH EDITION) IN SO FAR AS THEY DO NOT SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE SHOWN ON DRAWING, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE.
CONFLICT WITH LOCAL BUILDING CODE REQUIREMENT. 4. UNLES OTHERWISE INDICATED IN THE PLANS, LAP SPLICES FOR VERTICAL COLUMN REINFORCEMENT SHALL
BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND THE SPLICE LENGTH SHALL NOT BE LESS THAN
40 BAR DIAMETERS. WELDING OR APPROVED MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT LAP SPLICES ARE ALLOWED
MORE THAN ALTERNATE BARS ARE WELDED OR MECHANICALLY SPLICED AT ANY LEVEL AND THE VERTICAL ONLY IN THIS PORTION
5. ACI REFRES TO AMERICAN CONCRETE INSTITUTE, AISC TO AMERICAN INSTITUTE OF STEEL CONSTRUCTION AND ASTM TO AMERICAN UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINOUS ELEVATED SLAB SHALL BE CUT AS FOLLOWS:
DISTANCES BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS THAN 600mm.
SOCIETY OF TESTING MATERIALS. L1 L2 L3
L2/3 L2/3 L3/3 L3/3
6. CONSTRUCTION NOTES AND TYPICAL DEAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED. MODIFY TYPICAL
2D 2D 2D 2D 2D
DETAILS AS DIRECTED T O MEET SPECIAL CONDITIONS.
NOTES ON CONCRETE SLABS
7. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, MISCELLANEOUS IRON, PRE-CAST
1. ALL SLAB REINFORCEMENTS SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM THE TOP OF SLAB.
D
CONCRETE, ETC. SHALL BE SUBMITTED FOR ENGNEERS APPROVAL BEFORE FABRICATION. H JOINT HOOP SPACE @ "2Sh" WHEN THERE ARE
BEAMS HAVING WIDTH OF AT LEAST ONE-HALF THE
COLUMN WIDTH & DEPTHS NOT LESS THAN THREE
2. UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINOUS ELEVATED SLAB SHALL BE CUT AS FOLLOWS: CROSS-TIE L2/5 L2/5 L3/5 L3/5
8. CONTRACTOR SHALL NOTE AND PROVIDE ALL MEISCELANEOUS CURBS, SILLS, STOOLS, EQUIPMENT'S AND MECHANICAL BASES THAT QUARTERS OF THE DEEPEST BEAM THAT FRAME
ARE REQUIRED BY THE ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS. INTO FOUR SIDES OF THE COLUMN. ALL OTHER
350mm MAX
CONDITIONS USE HOOPS @"Sh" CENTERS. BOTTOM BARS WEB BARS
2 - Ø12mm SIDE BARS
TOP BARS
10
9. ALL RESULTS OF MATERIAL TESTING FOR CONCRETE, REINFORCING BARS & STRUCTURAL STEEL MUST BE NOTED & APPROVED BY L1 L2
H
m
THE STRUCTURAL ENGINEER.
in
L1/3 TOP BAR L1/3 L2/3 TOP BAR
.
FIG. B-1
NOTES ON CONCRETE MIXES & PLACING
CONF. REINF.
L1/6 BOTTOM BAR L1/6 L2/5 L2/5 BOTTOM BAR
1. ALL CONCRETE SHALL DEVELOP MIN. COMPRESSIVE STENGTH AT THE END OF TWENTY EIGHT (28) DAYS W/ CORRESPONDING
MAXIMUM SIZE AGGREGATE & SLUMPS AS FOLLOWS. JOINT HOOP SPACE @ "2Sh" WHEN THERE ARE TABLE 'A' TABLE 'B'
D
BEAMS HAVING WIDTH OF AT LEAST ONE-HALF THE TENSION BARS COMPRESSION BARS
JOINT REINF.
QUARTERS OF THE DEEPEST BEAM THAT FRAME LAPPED SPLICED IN MILLIMETERS LAPPED SPLICED IN MILLIMETERS
AGGREGATE
INTO FOUR SIDES OF THE COLUMN. ALL OTHER
ALL OTHERS, INCLUDING 4000 PSI ( 27.6 MPa) 20mm 100mm CONDITIONS USE HOOPS @"Sh" CENTERS. BAR SIZE fc'= 20.7MPa(3000psi) fc'= 27.6 .7MPa(4000psi) BAR SIZE fc'= 20.7MPa(3000psi) fc'= 27.6 .7MPa(4000psi)
SLABS, DEFORMED DEFORMED
TYPICAL BAR BENDING AND CUTTING DETAILS FOR SLLABS EMBEDMENT LAPPED EMBEDMENT LAPPED EMBEDMENT LAPPED EMBEDMENT LAPPED
D
LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN FOR REINFORCING BARS NEAR THE SUPPORTS. THE SPACING
Sh
12mmØ 300 300 300 300 12mmØ 275 300 250 300
3000 PSI ( 27.6 MPa) 20mm 100mm OF THE BARS AT THE COLUMN STRIPS SHALL NOT BE MORE THAN ONE AND A HALF ( 1 1/2) SLAB THICKNESS.
SLAB ON FILL 16mmØ 300 400 300 400 16mmØ 350 400 325 400
FOOTING 3000 PSI ( 27.6 MPa) 20mm 100mm
COLUMN TIES AS
20mmØ 400 550 350 500 20mmØ 450 500 475 500
4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION AND SHALL NOT BE LESS FOR COL. BAR SPLICES SEE TABLE OF MIN. LAP 625 625
2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS: 25mmØ 600 800 550 750 25mmØ 550 550
THAN 0.0025 X GROSS-SECTIONAL AREA (Ag) OF THE SLAB (SEE SCHEDULE BELOW) SPLICE LENGTH OF COLUMN REINFORCEMENT
SUSPENDED SLABS -----------------------------------------------------------------------------------------------------------20mm ( SPACING OF TIES ALONG THIS REGION SHALL NOT 28mmØ 750 1000 650 850 28mmØ 625 675 625 675
SLAB ON GRADE-----------------------------------------------------------------------------------------------------------------40mm BE LESS THAN 100mm)
32mmØ 950 1300 850 1100 32mmØ 700 775 700 775
WALL ABOVE GRADE----------------------------------------------------------------------------------------------------------25mm
NOTE: TOP PLAIN BARS, MULTIPLY VALUE BY 2 NOTE: TOP PLAIN BARS, MULTIPLY VALUE BY 2
BEAMS STIRRUPS AND COLUMN TIES---------------------------- ----------------------------------------------------40mm SCHEDULE OF MINIMUM SLAB REINFORCEMENT
WHERE CONCRETE IS EXPOSED TO VALUES GIVEN ABOVE CAN ALSO BE USED FOR
Sh
THICKNESS MINIMUM TEMPERATURE BARS
D
COLUMNS.
EARTH BUT POURED AGAINST FOORMS------------------------------------------------------------------------------50mm
WHERE CONCRETE IS DEPOSITED 100mm 10mm Ø @ 250mm EACH WAY NOTE: IF THE BEAM REINFORCING BRS END IN A WALL THE CLEAR DISTNCE FROM THE BAR TO THE FARTHEST FACE OF THE WALL SHALL
D JOINT REINF.
DIRETLY AGAINST EARTH---------------------------------------------------------------------------------------------------75mm 3.
125mm 10mm Ø @ 225mm EACH WAY NOT BE LESS THAN 25mm. EMBEDMENT LENGTH SHALL BE AS SHOWN IN A TABLE Ä"FOR TENSION BARS AND TABLE 'B'FOR
3. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION IN ITS FINAL POSITION WITHPUT SEGREGATION. RE-HANDLING OR PLACING ALL CONCRETE REINF. DETAIL SHOULD BE DONEIN
ACCORDANCE WITH THE LATEST EDITION OF ACI COMPRESSION BARS. UNLESS SPECIFIED IN PLAN, TOP BAR SHALL NOT BE SPLICED WITH IN THE COLUMN OR WITHIN A DISTANCE
SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS OR WHEELBARROWS, NO CHUTES WILL BE ALLOWED EXCEPT TO 150mm 10mm Ø @ 185mm EACH WAY TWICE THE MEMBER DEPTH FROM THE FACE OF COLUMN. AT LEAST TWO STIRRUPS SHALL BE PROVIDED AT ALL SPLICES.
TRANSFER CONCRETE FROM HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED SIX DETAILING MANUAL
CONF. REINF.
(6) METERS IN AGGREGATE LENGTH. 175mm 10mm Ø @ 150mm EACH WAY
t
7. FOUNDATION --------------------------------------------------------------------------------------------------------------------24 HRS. A AT ANY LEVEL NO MORE THAN ALTERNATE BARS
SUSPENDED SLAB EXCEPT WHEN SHOULD BE SPLICED MIN. DISTANCE BET. TWO
ADDITIONAL LOADS ARE IMPOSED------------------------------------------------------------------------------------- 8 DAYS ADJACENT BARS SPLICES SHALL BE 600mm. WEB BARS
Ø12X1000 LONG AT
ht.
SEE NOTE
t OR 41 D
WALLS-------------------------------------------------------------------------------------------------------------------------------21 DAYS MID-DEPTH OF SLAB AT SLEEVES FOR UTILITY
t
WITHIN CENTER
DOWN INTO EDGE BEAM. EXTENDED 4 - Ø12@ 1800 LOG SEE NOTE
BEAMS ---------------------------------------------------------------------------------------------------------------------------- 14 DAYS EACH CORNER PIPES MAX. 51 D
D
TOP BARS BEND BARS MIN. OF 1200 (4'-0") INTO BARS
HALF OF "H
COLUMNS--------------------------------------------------------------------------------------------------------------------------21 DAYS 1 - Ø12 TOP & BOT BARS
L/4
0.025M Ø
8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE CONSTRUCTION JOINTS TO THE 4 - Ø12 BOTT. BARS TOP BARS @ SUPPORT (CONT) SEPARATOR PROVIDE 3-Ø10 EXTRA STIRR. EACH
STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE POURING FOR APPROVAL. SEE NOTE SIDE OF SLEEVES
400
JT. REINF.
ATTAINED THEIR WORKING CONDITION AND STRENGTH. NOTE:
JT. REINF.
SLAB THRU CONCRETE BEAM
D
0
38mm
60
AND GIRDER
NOTES ON FOOTINGS
60
1 - Ø12 EA.
400
1. FOOTINGS ARE DESIGNED FOR AN ALLOWANCE SOIL BEARING PRESSURE F 96 KPa (2000 psf). CONTRACTOR SHALL REPORT TO THE
ENGINEER, IN WRITING, THE ACTUAL SOIL CONDITIONS UNCOVERED AND COMFIORM ACTUAL BEARING CAPACITY OF SOIL BEFORE TOP & BOT SPLICE BOTTOM BARS AT MID SPAN FIG. B-2 FIG. B-3
DEPOSITING CONCRETE.
IN TWO WAY SLAB EXTEND SECTION "A" EXTRA TOP BARS @ SUPPORT
BARS UP TO BEAM SUPPORT
OMIT TRIMMER BARS WHERE 6. WHEN A BEAM CROSSES A GIRDER, REST BEAM ON TOP OF GIRDER BARS, BEAM REINFORCING BAR SHALL
2. FOOTING SHALL REST AT LEAST 1500mm BELOW NATURAL GRADE LIN UNLESS OTHERWISE INDICATED IN PLANS. NO FOOTING SHALL 60
REST ON FILL.
0 OPENING IS FRAME BY BEAM TYPICAL DETAIL OF COL. LAP SPLICE & EXT. BE SYMMETRIAL BOUT CENTER LINE WHENEVER POSSIBLE.
GIRDER TO COL. CONNECT. 7. GENERALLY NO SPLICES SHALL BE PERMITTED AT A POINTS WHERE CRICTICAL BENDING STERSSES OCCUR,
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENTS SHALL BE 75mm CLEAR FOR CONCRETE DEPOSITED THE GROUND AND TYPICAL SLAB SPLICES WHERE SO PERMITTED SHALL BE INDICATED IN THE TABLE 'A' AND 'B'. WLEDED SPLICES SHALL
50mm FOR CONCRETE DEPOSITED AGAINST THE FORMWORK.
TYPICAL CORNER SLAB DETAIL OPENING DETAIL DEVELOP IN TENSION AT LEAST 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR, NOT MORE THAN 50%
OF THE BARS AT ANY ONE SECTION IS ALLOWED TO BE SPLICED THEREIN.
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR ENGINEERING ASST. S-1 6
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF GENERAL NOTES
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO PREPARED: SHARYN C. SUPEÑA 1 7 15
CALINOG, ILOILO GIZA P. PLAZA ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
GENERAL CONSTRUCTION NOTES
NOTES ON CONCRETE WALLS 2. DESIGN STRESSES
A. CONCRETE
1. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL COMPRESSIVE STRENGTH @ 28 DAYS fc' = 20.70 MPa ( 3,000 psi )
FLR .SLAB OR BEAM REINFORCEMENT UNLESS OTHERWISE INDICATED IN THE PLANS. B. REINFORCING BARS
NOTES ON CONCRETE HOLLOW BLOCKS WALLS DOWEL BARS TO
a. FOR BARS 16MMØ AND GREATER (INTERMEDIATE GRADE DEFORMED BAR) fy = 414 MPa (60,000 psi )
MATCH VERT. BARS
B. FOR BARS LESS THAN 16MMØ (STRUCTURAL GRADE DEFORMED BAR) fy = 275 MPa (40,000 psi )
1. UNLESS OTHERWISE SHOWN IN PLANS ALL CONCRETE HOLLOW BLOCKS AND CERAMIC BLOCKS REINFORCEMENT C. STRUCTURAL STEEL, ASTM - A36
DOWEL
WALL VERTICAL
SHALL BE REINFORCED AS SHOWN IN THE SCHEDULE OF CONCRETE HOLLOW BLOCKS AND THICKNESS SECTION
400
FOR TRUSSES, BRACINGS, & STRUTS fy = 248 MPa (36,000 psi )
VERIFY ARCHITECTURAL
HORIZONTAL VERTICAL REMARKS
CERAMIC BLOCK REINFOREMENT.
1. ALL JOINTS AND CELLS 100mm 10Ømm @ 250mm O.C. 10Ømm @ 300mm O.C. HORIZONTAL BARS
D. PURLINS
VERT.
CONTAINING REINFORCING 125mm 10Ømm @ 200mm O.C. 10Ømm @ 250mm O.C. BARS COLD FORMED LIGHT GAGE SHAPES fy = 248 MPa (36,000 psi )
AT CENTERS VERTICAL
2. PROVIDE 150mm X 300mm STIFFENER COLUMN REINFORCED WITH 12-12mm WITH 6mM TIES AT BARS SHALL BE FILLED W/ HOR. E. MASONRY UNIT (CHB)
150mm 12Ømm @ 250mm O.C. 12Ømm @ 300mm O.C. BARS STAGGERED OUT
150mm IN CENTE WHERE CONCRETE HOLLOWBLOCK REMINATES AND EVERY 3.0M LENGTH OF CONCRETE GROUT BARS
NON-LOAD BEARING CHB WALLS fm' = 3.45 MPa (500 psi )
CONCRETE HOLLOW BLOCKS WALLS UNLESS NOTED IN STRUCTURAL PLANS. F. WELDS-USED E-60xx ELECTRODE
1. FOR REINFORCEMENTS SEE REINFORCING BARS SHALL HAVE 25mm CLEAR CONCRETE COVER FROM FACE OF WALL EXCEPT FOR WALLS IN CONTACT
CONSTRUCTION NOTES WITH THE GROUND WHERE A MINIMUM OF 60mm SHALL BE PROVIDED, AND FOR EXPOSED FAES OF FORMED WALLS G. STRUCTURAL BOLTS, ASTM-A307
WHERE THE MINIMUM SHALL BE 50mm CLEAR. a. Ft = 96.60 MPa (14,000 psi ) b. Fv = 69 MPa ( 10,000 psi )
DOWEL
400
1 - Ø CONT. HOR. BARS 2. CARRY VERTICAL BARS AT LEAST 60MM ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES WHEN NECESSARY STOP AT
SCHEDULE OF CONC. HOLLOW BLOCK AND CERAMIC BLOCK REINFORCEMENT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALLS ENDS. VERTICAL AND HORIZONTAL BARS SHALL BE SPLICED NOTES ON CONSTRUCTION JOINTS IN CONCRETE
BLOCK FOR FLOOR SLAB ONLY
REINFORCEMENT NOTES BY LAPPING A DISTANCE EQUAL 30 DIAMETERS AND WIRED SECURELY WITH 16 G.I. WIRE PROVIDEDTHAT SPLICES IN WHERE A CONSTRUCTION JOINT IS TO BE MADE, THE SURFACE OF CONCRETE SHALL BE CLEANED
THICKNESS 1.
A. MINIMUM LAPS AT SPLICE = 0.25M
ADJASCENT BARS ARE STAGGERED AT LEAST 1.50M O.C. AND ALL LAITANCE AND STANDING WATER REMOVED, SHEAR KEY SHALL BE PROVIDED AT THE
HORIZONTAL VERTICAL
B. PROVIDE RIGHT ANGLED REINFORCEMENT JOINT.
75mm 10mmØ @ 600mm O.C. 10mmØ @ 600mm O.C. AT CORNERS 0.92M LONG 4. UNLESS OTHERWISE NOTED IN THE PLANS, ALL OPENINGS IN WALLS 250mm OR THICKER SHALL BE REINFORCED AROUND
125mm
TYPICAL SECTION OF MASONRY WITH
1. 2-20mmØ BARS FOR 225mm, 200mmn, 175mm, 150mn, USE 2-16mmØ, FOR 125mm AND 100MM WALLS, USE 2-12mmØ MAIN REINFORCEMENTS TO BE
10mmØ @ 600mm O.C. 10mmØ @ 600mm O.C. C. WHERE CHB OR CER. BLK. WALL DOWELS
JOIN COL. R.C. BEAMS AND WALL, DOWELS PARTITION REINFORCEMENTS BARS. ALL WALLS AND SPACED ACCORDING TO THE SCHEDULE UNLWESS OTHERWISE NOTED (SEE FIG. 1) CONTINOUS ( TOP & BOTT. BARS)
150mm 10mmØ @ 600mm O.C. 10mmØ @ 600mm O.C. WITH THE SAME SIZE AS VERT. OR HOR.
REINFORCEMENTS SHALL BE PROVIDED WHERE JOINTS IS AT POINT OF
200mm MAIN REINFORCEMENTS
12mmØ @ 600mm O.C. 12mmØ @ 600mm O.C. STRESS, PROVIDE SHEAR RODS TO BE CONTINUOUS
WITH ENGINEERS APPROVAL
Ø10 X 1000 LONG
4- Ø16 VERT. BARS 30 BAR DIA. 30 BAR DIA. @ 300 O.C.
REINFORCING CONCRETE LINTEL BEAM IN 50
(MIN) (MIN)
4- Ø16 VERT. BARS
550
40
CONCRETE BLOCK WALLS
D/3
550
SEE CONSTRUCTION NOTES
t /3
D/3
D
LINTEL IN BLOCKS WALLS
t /3
FOR MASONRY WALL REIN-
t
D/3
FORCEMENTS (TYPICAL)
t /3
CLEAR TOTAL MIN. HEIGHT OF REINFORCEMENT
SPAN LENGTH fc' LINTEL FIN FLR LVL
("L") (L+0.40M) (MPa) (MM) BEAM SLAB
250
2.40 M 2.90 M 17 250 1-Ø12 1-Ø10 Ø6mm @ 200
2.70 M 3.10 M 250 1-Ø16 1-Ø12 Ø10mm @ 200 3 - Ø10 BOTT BARS
DOWEL TO MATCH 2. WELDS SHALL DEVELOP THE FULL STRENGTH OF MEMBERS JOINED UNLESS OTHERWISE SHOWN
OR DETAILED IN THE DRAWINGS.
CHB VERT BARS DOOR
OPENING
12 THK. EXPANSION JOINT NOTE:
WITH MASTIC FILLER 300 PROVIDE THESE ADDITIONAL BARS FOR
1 - Ø16 VERT. BARS NOTES ON WELDS ALL OPENINGS PLUS BRS (NOT SHOWN) 39mm
DOWEL
( TYP. )
PARALLEL TO SIDE OF OPENING EQUAL CLEAR WINDOW
400
CHB WALL 1. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS STRUCTURE SHALL
COMPLY WITH ALL THE PERTINENT PROVISION OF AISC SPECIFICATION FOR DESIGN, FABRICATION TO THE NUMBER OF TERMINATED BARS OPENING
DOWEL
250
CHB WALL (SEE CONSTRUCTION 2. ALL STRUCTURAL STEEL SHAPES SHALL BE CONCFORM TO ASTM A36 STRUCTURAL STEEL UNLESS SEE ARCHITECTURAL & MECHANICAL
NOTES) OTHERWISE INDICATED.
FOR SIZE AND SPACING PLANS FOR SLAB OPENING LOCATION
3 - Ø10 BARS ( AS SHOWN)
OF HOR. & VERT. BARS 3. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE MEMBERS CONNECTED.
Ø10 BOTT BARS @ 300 O.C.
SEE CONSTRUCTION NOTES. 400 4. UNLESS OTHERWISE SPECIFIED ALL WELDING RODS SHALL CONFORM AWS E60 ELECTRODED.
CORNER WALL OPENING OR END WALL 5. ALL BOLTS USED UNLESS OTHERWISE SPECIFIED SHALL BE ASTM A 307 BOLTS.
DOWEL
( TYP. )
CHB WALL 12 THK. EXPANSION JOINT B. NO PIPES SHALL BE ALLOWED TO PASS THRU BEAMS VERTICALLY.
400
2. REINFORCEMENT PARTIALLY EMBEDED IN CONCRETE SHALL NOT BE FILLED BENT, EXCEPT AS
WITH MASTIC FILLER C. NO PIPES SHALL BE EMBEDED IN COLUMNS SHOWN IN THE DESIGN DRAWINGS OR PERMITTED BY THE STRUCTURAL ENGINEER.
DOWEL
D+2db
D db
400 A. DEAD LOAD
135º HOOKS
L
DOWEL CONCRETE - 23.56 kN/m³
STEEL - 76.93 kN/m³
INTERSECTION WALL INTERSECTIG R.C. COLUMN OR WALL 150mm THK. CHB WALL - 2.73 kPa
4db or 65mm
TYPICAL CHB FOOTING DETAILS 100mm THK. CHB WALL - 2.11 kPa
6
TYPICAL CONNECTION DETAIL OF MASONRY WALL ( WHERE APPLICABLE ) db
D
B. LIVE LOAD 180º END HOOKS
ROOF - 1.00 kPa
db
C. WIND LOAD (NSCP 2010)
BASIC WIND VELOCITY, V = 250 KPH
12 db
200(MIN) 200(MIN) P = qh[(GCpf)-(GCpi)] (DESIGN WIND PRESSURE)
L
WHERE: qh = VELOCITY PRESSURE, kPa)
D
Ø10 STIRRUPS
FOR SIZE AND SPACING GCpf = EXTERNAL PRESSURE COEFFICIENT
GCpi = INTERNAL PRESSURE COEFFICIENT
90º HOOKS
OF HOR. & VERT. BARS
VERIFY DEPRESSION
(MIN) (MIN)
D = FOR BEAM
Cvl
400
t = FOR SLAB
OPENING Vmin =
1- Ø10 VERT. R ( DEFORMED) ( mm) ( DEFORMED) ( mm)
D + 2db L L D + 2db L L
BARS TYPICAL 2- Ø12 TOP BARS WHERE: W= TOTAL DEAD LOAD
10mmØ 60 75 125 150 10mmØ 40 125 85 100
D = FOR BEAM T = NATURAL PERIOD = C t (h n) ;
2t = FOR SLAB WHERE: C = NUMERICAL COEFFICIENT 12mmØ 75 100 150 200 12mmØ 50 165 115 115
30 BAR DIA. h = BUILDING HEIGHT 16mmØ 95 125 175 250 16mmØ 65 200 140 150
FIN. FLR. LVL. SECTION (MIN) I = IMPORTANCE FACTOR = 1.50
R = NUMERICAL FACTOR = 8.50 20mmØ 115 150 200 300 20mmØ 115 250 165 300
SEISMIC COEFFICIENT Cv = 0.44Nv 25mmØ 150 200 230 450 25mmØ 150 365 230 405
ELEVATION Ca = 0.64 N
TYPICAL DETAIL FOR BEAM NEAR SOURCE FACTOR ( 10km ) Nv = 1.2 28mmØ 240 300 350 550
Na = 1.0
TYP. DET. OF LINTEL BEAM AT CHB WALL OPENING OR SLAB CHANGE SOFFIT Z = SEISMIC ZONE = 0.40 ( ZONE 4 )
32mmØ 300 335 450 600
S = SOIL TYPE = D
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR ENGINEERING ASST. S-2 7
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF GENERAL NOTES
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO PREPARED: SHARYN C. SUPEÑA 2 7 15
CALINOG, ILOILO GIZA P. PLAZA ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
SCHEDULE OF SPAN PER COLUMN
NAME LENGTH SPAN ( LS)
SPAN-1 4500 MM
SPAN-2 4500 MM
SPAN-3 5000 MM
SPAN-3&4 10000 MM
SPAN-4 5000 MM
SPAN-5 4500 MM SCHEDULE OF FOOTING
SPAN-6 4500 MM
FOOTING DIMENSIONS
FLOOR LENGTH = 28000 MM REINFORCEMENT
in mm
FLOOR WIDTH = 14000 MM FOOTING REMARKS
MARKS
LENGTH WIDTH DEPTH Thickness
(L) (W) (D) ( t) BAR Y BAR X
A B C D E F G
LENGTH
2 TB TB TB TB TB 2
W
NAT. GRADE LNE
COLUMN SCHEDULE
X - BARS
C -1
FOUNDATION LEVEL TO
GROUND FLOOR LEVEL
350
Y - BARS
D
L
350
MAIN BARS : 8 -16 mm Ø
WIDTH
WIDTH
TB
TB
E X I S T I N G S L A B C O U R T
t
TIES :2-10 mm Ø 6@ .050 m., 5 @
0.10 m. 5 @ 0.15 m.REST @ 0.20 M.
0.50 m. THK. GRAVEL BED
(PLAN ) ( SECTION )
TB TB TB TB TB TB
1 1
C1/F1 C1/F1 C1/F1 C1/F1 C1/F1 C1/F1 C1/F1
2 - 16MMØ
SPAN-1 SPAN-2 SPAN-3 SPAN-4 SPAN-5 SPAN-6 200 200
400
400
2 - 16MMØ 2 - 16MMØ
A B C D E F G @ SUPPORT @ MIDSPAN
2 - 16MMØ
(SECTION)
2 TIETIE
BEAM
BEAMDETAIL
DETAIL
S-3 SCALE 1:30 M
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM FOUNDATION PLAN, MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR TIE BEAM DETAIL, ENGINEERING ASST. S-3 8
SCHEDULE OF SPAN
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF PER COLUMN,
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO SCHEDULE OF FOOTING, PREPARED: SHARYN C. SUPEÑA 3 7 15
CALINOG, ILOILO SCHEDULE OF COLUMN,
GIZA P. PLAZA ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
PLAN AND SECTION
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
2 s- 75MM X 75MM X 6MM
2 s- 75MM X 75MM X 6MM
2 s- 75MM X 75MM X 6MM
TOP CHORD BAR
BOTTOM CHORD BAR
2 s-50MM X 50MM X 6MM 2 s-50MM X 50MM X 6MM 6MMX 550MM X 120MM
VERTICAL MEMBER BAR SPOT DETAIL 5 WELDED GUSSET PLATE (TYP.)
DIAGONAL MEMBER BAR
LENGTH S-4
475 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 475 2 s- 50MM X 50MM X 6MM
WEB MEMBER BAR
600
600
600
542
542
150 MMX 300MM X 6MM
GUSSET PLATE (TYP.) SPOT DETAIL 6
SPOT DETAIL 4
S-4 3 SEE CORBEL DETAIL
S-4
1488
1488
S-5
2 s- 75MM X 75MM X 6MM
REFER TO BRACKET DETAIL LENGTH LENGTH REFER TO BRACKET DETAIL
946
946
1500 1500
LENGTH
112
2∠s- 75MMX 75MMX6MM 2∠s- 75MMX 75MMX6MM 2∠s- 75MMX 75MMX6MM 2∠s- 75MMX 75MMX6MM
140
TOP CHORD BAR BOTTOM CHORD BAR TOP CHORD BAR BOTTOM CHORD BAR
600
LENGTH LENGTH
500 500 500 500 500 500 500 500 325 500 500 500 500 500 500 500 500 500 500 500 500 500 500 325
654
542
500
600
1488
150 MMX 300MM X 6MM
140
150 MMX 300MM X 6MM
20MM X 12MM 6MM THK.
GUSSET PLATE (TYP.)
34
GUSSET PLATE (TYP.)
946
20
GUSSET PLATE
2∠s-75MMX75MM X 6MM
2 STEEL BEAM 3 (SB-3)DETAIL BRACKET BAR
1 STEEL BEAM
STEEL BEAM 2(SB-2) DET.
2 (SB-2)DETAIL S-4 SCALE 1:40 M
FULLY WELD
4-12 MM Ø X 300MM
LONG BENT ANCHOR
1500
S-4 SCALE 1:40 M
6 SPOT DETAIL BOLTS W/ NUTS
AND WASHERS
250 MM X 250 MM X 12MM
STEEL BASE PLATE
S-4 SCALE 1:10 M
140
18000 MM 600 MM 28 29 2
140
4000 MM 600 MM 8 9 10
SB-2 4500 MM 600 MM 10 11 10 300
5000 MM 600 MM 10 11 10
FULLY WELD
6000 MM 600 MM 12 13 1
7000 MM 600 MM 14 15 1 FULLY WELD
SB-3 8000 MM 600 MM 16 17 2
9000 MM 600 MM 18 19 1 4 SPOT DETAIL 5 SPOT DETAIL
10000 MM 600 MM 20 21 1 S-4 SCALE 1:10 M S-4 SCALE 1:10 M
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM SCHEDULE OF STEEL BEAM, MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR DETAIL OF SB -1,
DETAIL OF SB-2,
ENGINEERING ASST. S-4 9
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF DETAIL OF SB -3,
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO SPOT DETAILS,
PREPARED: SHARYN C. SUPEÑA 4 7 15
CALINOG, ILOILO STEEL BRACKET, ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
SECTION OF STEEL BEAM GIZA P. PLAZA
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
1∠- 5MM THK. X38MMX38MM 1∠-5MM THK. X38MMX38MM
TOP & BOTTOM CHORD VERT. MEMBERS
1∠- 5MM THK. X38MM
1∠-5MM THK. X38MMX38MM END FLASHING
X38MM TOP & BOTTOM
VERT. MEMBERS
CHORD
1∠- 5MM THK. X38MMX38MM
C- PURLINS
TOP & BOTTOM CHORD
A B C D E F G FASCIA COVER
0.60 MM THK. 0.551MM THK. PRE- PAINTED P.G.I.FASCIA COVER FIN. (GAUGE 24)
400
0.551 MM THK. P.G.I. SHEETS FASCIA COVER
400
LENGTH P.G.I. SHEETS FASCIA FRAME
(GAUGE 24) 1∠- 5MM THK. X38MMX38MM
FASCIA COVER VERT. MEMBERS
1000 SPAN-1 SPAN-2 SPAN-3 SPAN-4 SPAN-5 SPAN-6 1000
400 400 400 (SECTION)
400 400 400 400 ( SECTION) (PLAN)
100MM X 50MM X 2MM 12MMØ CROSS BRACING BAR
C-PURLINS AT ± 649 MM (SEE DETAIL) FASCIA FRAME
FASCIA 2 DETAIL
FRAME 2 DETAIL
7
SEE FASCIA FRAME-2 DETAIL
S-5 SCALE 1:20 M 6 FASCIA FRAME 1 DETAIL
1500
1500
S-5 SCALE 1:20 M
SPAN-1 4500 MM
BA
OSS GTH
±35
SPAN-2 4500 MM
SEE FASCIA FRAME-1 DETAIL
00
L
CIN
SPAN-3 5000 MM
G
SAG ROD
SAG ROD
SAG ROD
SAG ROD
SAG ROD
TRUSS
TRUSS
TRUSS
TRUSS
TRUSS
WIDTH
WIDTH
SPAN-3&4 10000 MM
TRUSS
TRUSS
SB-1
SB-1
CG
CG
CG
CG
CG
CG
50
( CR R LEN
BA
WELDED JOINT
200
100
BUCKLE PLATE
610
SPAN-5 4500 MM
BRA )
WELDED JOINT
CIN
50
SPAN-6 4500 MM
G
1500
SEE FASCIA FRAME-2 DETAIL CONN. DETAIL OF CROSS
12MMØ TENSION BAR (SEE DETAIL)
1000 SPAN-1 SPAN-2 SPAN-3 SPAN-4 SPAN-5 SPAN-6 1000
4 BRACING ON COLUMN
12 MM X 500MMX300 MM
STEEL BASE PLATE S-5 SCALE 1:8 M
LENGTH ( WELDED TO BOTTOM
OF STEEL BEAM)
2- 12MMØ X300MM LONG
A B C D E F G BEND ANCHOR BOLTS W/
NUTS AND WASHERS ON
6- 12MMØ X300MM LONG
BEND ANCHOR BOLTS W/
12MMX600MMX300MM STEEL
NUTS AND WASHERS
BASE PLATE ( WELDED FIN.)
1000
50MMØ G.I PIPE
L TOP CHORD
300
38MMØ G.I. PIPE COLUMN
500 500 500 500 500 500 500 500 500 500 WEB MEMBERS
300
4-16MM Ø BARS W/
400
10MMØ TIES AT
100MM O.C. BOTTOM OF
300
CORBEL DETAIL
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES CENTER GIRT,
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM
ROOF FRAMING PLAN,
SCHEDULE OF
MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR SPAN PER COLUMN ENGINEERING ASST. S-5 10
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF FASCIA FRAME 1 DETAIL,
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO
FASCIA FRAME 2 DETAIL,
CONNECTION DETAIL OF CROSS
PREPARED: SHARYN C. SUPEÑA 5 7 15
CALINOG, ILOILO BRACING ON TRUSSES,
GIZA P. PLAZA ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
CONNECTION DETAIL OF CROSS
BRACING ON COLUMN ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
LENGTH
12MMØ (PLAIN
BAR) SAG ROD
50MMØ G.I. PIPE (SCHED 40 )
TOP CHORD BAR 0.50MM THK. PRE PAINTED HI- RIB
1 50MMØ G.I. PIPE (SCHED 40 )
CURVE TYPE LONG SPAN ROOFING 2
38 ROWS - 100MM X 50MM X 2MM C-PURLINS
BOTTOM CHORD BAR AT ±649 W/ 50MMX50MM BAR CLEATS
400
38 MM Ø G.I. PIPE
LATERAL MEMBER
SPOT DETAIL 2
S-6
0
0
LENGTH LENGTH
LENGTH
LATERAL MEMBER 2-BOTTOM CHORDS (FULLY LATERAL MEMBER 50mmØ G.I. PIPE WELDED
38MMØ G.I. PIPE(SCHED 40 ) WELDED TO BASE PLATE) (FULLY WELDED )
(FULLY WELDED ) 2-BOTTOM CHORDS (FULLY
DOUBLE WEB MEMBERS
WELDED TO BASE PLATE)
50mmØ G.I. PIPE WELDED
50mmØ G.I. PIPE WELDED
LATERAL MEMBER(FULLY
WELDED ) 50mmØ G.I. PIPE WELDED
8-12MMX300MM LONG BENT FULLY WELDED
ANCHOR BOLTS W/ STD.
90
STEEL BEAM
NUTS & WASHERS 300X300X12MM BASE PLATE 8-12MMX300MM LONG BENT
ANCHOR BOLTS W/ STD. FULLY WELDED
NUTS & WASHERS
∠ BAR STEEL BEAM
COLUMN
90
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
TYPICAL ANCHORAGE DETAIL
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR STEEL BEAM/ TRUSSES ENGINEERING ASST. S-6 11
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF ANCHORAGE DETAIL,
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO SCHEDULE OF TRUSSES
AND MEMBERS,
PREPARED: SHARYN C. SUPEÑA 6 7 15
CALINOG, ILOILO MAIN TRUSS DETAIL GIZA P. PLAZA ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
50MM Ø SCH. 40 G.I. PIPE
TOP & BOTTOM CHORD
CENTER GIRT
( WELDED JOINT ) CENTER GIRT
CENTER GIRT
BOTTOM CHORD
STABILIZER, BOTH SIDES 150MMX150MMX4MM 6mm DIAGONAL BAR
( WELDED JOINT ) BOTTOM CHORD
STEEL PLATE ( WELDED ON OPPOSITE DIRECTION
JOINT)
0.02
5
8
3.5
S-7
0.02
150MMX150MMX4MM
0.02
STEEL PLATE ( WELDED 250 MM RADIUS X 12MM
0.02
JOINT) THK. STEEL PLATE
STEEL
2∠s- 75mmx75mmx6mm 5 TOP VIEW BEAM
DIAGONAL BAR ( WELDED
S-7 SCALE 1: 5 M.
150MMX150MMX4MM JOINT)
STEEL PLATE (WELDED JOINT)
4 BRACING ISOMETRIC
S-7 SCALE 1:5 M
2∠s- 75mmx75mmx
6mm DIAGONAL BAR
ON OPPOSITE DIRECTION
6MMØ J-BOLTS W/
STD. NUTS AND WASHERS 3.32 3.32
ANCHORED TO C-PURLINS
CENTER GIRT
50 MM X 50 MM ANGLE
BAR CLEATS ( WELDED FIN.)
3.22
3.02
2∠s- 75mmx75mmx6mm
DIAGONAL BAR
±6
00
MM
O.C 250 MM RADIUS X 12MM
.
45°
45°
THK. STEEL PLATE
3.
72
O.C
.
STEEL
BEAM
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
SAG ROD ISOMETRIC,
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM CONNECTION DETAIL MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR OF SAG ROD,
CLEATS,
ENGINEERING ASST. S-7 12
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF J-BOLTS & PURLINS,
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO BRACING DETAIL (OUTSIDE),
PREPARED: SHARYN C. SUPEÑA 7 7 15
CALINOG, ILOILO BRACING DETAIL (INSIDE), ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
BRACING ISOMETRIC, GIZA P. PLAZA
BRACING DETAIL SECTION ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
2-16 mm Ø HANDLE BARS
100
40 400 40
REMOVABLE CB COVER
60 480 60
A B C D E F G INLET
100 mm Ø PVC DOWNSPOUT
100
60
100
150MM Ø PVCSDP 150MM Ø PVCSDP 150MM Ø PVCSDP 150MM Ø PVCSDP 150MM Ø PVCSDP ( VERIFY) 150 mm Ø PVCDP (2% SLOPE)
CB CB CB CB CB CB
2 2
INLET
600
400
600
INLET OUTLET
OUTLET
200
95
100
100
60
REMOVABLE R.C. 4-12 mm Ø BARS, E.W.
100 100 COVER WITH 2-16 mm Ø 150 mm Ø PVC DP 100 400 100
150
HANDLE BAR (2% SLOPE)
400 600
600
3 DETAIL OF SECTION
2 DETAIL OF CATCH BASIN P-1 SCALE 1:20 M
P-1 SCALE 1:20 M
A
WIDTH
WIDTH
RD
B
2 DS RD
C
CB 15 DS RD
0M
M ØP
VC
SD
CB P 15 DS
D
0M
MØ
PV
CSD
CBP F
RD
1 1 RD
150
MM
ØP G
CB CB CB CB CB CB CB 1 VC
SD
P
DS RD
150MM Ø PVCSDP 150MM Ø PVCSDP 150MM Ø PVCSDP
L/S-1 L/S-2 L/S-3
150MM Ø PVCSDP 150MM Ø PVCSDP
L/S-5
150MM Ø PVCSDP
L/S-6 L/S-7
TO DRAINAGE
( VERIFY)
DS RD H
C CB 15 DS RD
0M
150B MØ
LENGTH MM DS RD PV
ØP CS
VC D
SD CB P 15 DS
P150CB
A MM
Ø
0M
MØ
PV
CS
PV DS RD
A B C D E F G CS
DP1
50M CB
D
CBP
TO
( V DRAI
B MØ
P
ER NA
IFY GE
)
VC DS
SD RD
LEGEND: C
1P50
MM C
ØPB
2
SDP- (150 MM Ø PVC ) STORM DRAINAGE PIPE VC
1 CATCH BASIN LAYOUT P-1
SD
P15 DS RD
RD - (75MM Ø PVC ) ROOF DRAIN
P-1 SCALE 1:150 M 2 C
S A
D
0M
M ØP C
VC B
DS - (75MM Ø PVC ) DOWN SPOUT
CA TC SD
P15
0M
DS RD
LE HB F
M ØP
VC CB
TR
IC
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR CATCH BASIN LAYOUT,
DETAIL OF CATCH BASIN,
ENGINEERING ASST. P-1 13
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF DETAIL OF SECTION,
JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO CATCH BASIN ISOMETRIC
PREPARED: SHARYN C. SUPEÑA 1 1 15
CALINOG, ILOILO GIZA P. PLAZA ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
GENERAL NOTES LEGEND
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH THESE SYMBOL DESCRIPTION
PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS OF THE LATEST
11W LED CEILING PINLIGHT
EDITION OF THE PHILIPPINE ELECTRICAL (PEC). THE RULES AND REGULATION
OF THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE
PB 150W IP65 LED FLOODLIGHT
2 2
LOCAL POWER COMPANY. THE ELECTRICAL WORKS SHALL BE UNDER
IMMEDIATE SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER. 50W IP65 LED FLOODLIGHT
2. THE ELECTRICAL SERVICE IS 1-PHASE, 2-WIRE, 230 V AC, 60 Hz. S 1-GANG SWITCH
1
a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONDUIT
b. LIGHTING POWER - POLYVINYL CHLORIDE CONDUIT Scde 3-GANG SWITCH
BRANCH CKT., & AUXILIARY SCH. 40
S3w 3-WAY SWITCH
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN"
CIRCUIT BREAKER
UNLESS OTHERWISE INDICATED IN THE PLAN. THE MINIMUM SIZE OF WIRE
FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE 3.5mm² AND
3
DUPLEX CONVENIENCE OUTLET
INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL BE 15mmØ
TRADE/NOMINAL SIZE. MDP
MAIN DISTRIBUTION PANEL BOARD
5. ALL OUTLET BOXES SHALL BE GALVANIZED GUAGE NO. 16 DEEP TYPE WITH PB PANEL BOARD
FACTORY KNOCKOUTS.
M SERVICE METER
2
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE
FOR THE PARTICULAR LOCATION AND PURPOSE OF USAGE. SERVICE ENTRANCE
SPARE 5 20 20 6 SPARE
4 ONE LINE
ONE LINEDIAGRAM
DIAGRAM
2 SCHEDULE OF LOADS W/ BACKUP COMPUTATION E-1
E-1
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: CONCURRED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CY 2024 DPWH INFRASTRUCTURE PROGRAM VOLTAGE DROP MA. LANI J. GALLEGO
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR
CALCULATION,
SCHEDULE OF LOADS W/
ENGINEERING ASST. E-1 14
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF BACK UP COMPUTATION,
PREPARED: RYAN B. SEROJANO JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO ELECTRICAL PLAN,
ONE LINE DIAGRAM,
1 1 15
CALINOG, ILOILO ENGINEER II OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER BARANGAY CAPTAIN
GENERAL NOTES, LEGEND RYAN B. SEROJANO
ENGINEER II DATE DATE DATE DATE DATE
L. MEDIANA
PROJECT NAME AND LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
BASED ON ROAD SAFETY DESIGN MANUAL
CY 2024 DPWH INFRASTRUCTURE PROGRAM
REGIONAL OFFICE VI DETAILED ENGINEERING DESIGN PLAN FOR BILLBOARD: D.O.21 SERIES OF 2017, PB 15
ILOILO 2ND DISTRICT ENGINEERING OFFICE CONSTRUCTION (COMPLETION) OF MULTI- PURPOSE BUILDING OF DPWH BILLBOARD REVISED GUIDELINES ON THE INSTALLATION OF JERMAIN CEM L. DEQUILLA EDUARD B. OREN ALLAN REY R. PAJIMNA
BALABAG, DUMANGAS, ILOILO BARANGAY IMPALIDAN, CALINOG, ILOILO 1 1 15
CALINOG, ILOILO PROJECT BILLBOARDS OIC-CHIEF, PLANNING AND DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER DISTRICT ENGINEER