iXP2 Manual V1.3 202006 EN
iXP2 Manual V1.3 202006 EN
XGT PANEL
iXP2 Series
Safety Precautions
► Safety precaution is classified into ‘Warming’ and ‘Caution’ and their meanings are as
follows.
Warning Violating the instruction may result in serious personal injury or death.
product damage.
► The indicated illustrations on the product and in the manual have the fallowing meanings.
► After reading the instruction manual, keep it handy for quick reference.
1
Safety Precautions
Design Precautions
Warning
► Install a safety circuit external to the HMI to protect the whole control system in case of
external power supply trouble.
Serious trouble may occur to the entire system due to erroneous output/operation of the HMI.
Design Precautions
Caution
► In/output signal or communication cable should be at least 100mm apart from High-
voltage/power wires.
Otherwise, it may cause erroneous output/operation.
Installation Precautions
Caution
► Use the HMI in an environment that meets the general specification contained in this
manual or datasheet.
Otherwise, it could result in electric shock, fire, erroneous operation or deterioration.
► In case of much vibration in the installed environment, be sure to insulate the HMI from
direct vibration.
Otherwise, it could result in electric shock, fire, erroneous operation.
► Be sure not to let foreign substances such as conductive debris inside the product.
Otherwise, it could result in electric shock, fire, erroneous operation.
► Do not touch the conductive part of the HMI. It may cause an electric shock,
which may cause malfunction.
2
Safety Precautions
Wiring Precautions
Warning
► Be sure to turn off the HMI and external power before wiring.
Otherwise, it may result in an electric shock or damage to the product.
Caution
► Wire correctly by checking each of the product’s rated voltage and terminal layout.
Otherwise, it may result in fire, electric shock or erroneous operation.
► Be sure not to let any foreign substances such as wiring debris inside the module.
Such debris may cause fire, damage or erroneous operation.
► Tighten the crimp terminal to the specified torque, and crimp the external
connection connector using the specified tool or solder it correctly.
3
Safety Precautions
Warning
► Do not touch the terminals while power is on.
Otherwise, it may cause electric shock or erroneous operation.
► Turn off the HMI and external power when cleaning or tightening the terminal.
Otherwise, it may cause electric shock or erroneous operation.
► Do not charge, disassemble, heat, short circuit, solder, etc. other battery.
Mishandling the battery may cause overheating, crack, fire and may result in injury or fire.
Caution
► Do not disassemble PCB from the product case or modify the product.
Otherwise, it may result in fire, electric shock or erroneous operation.
► When mounting or removing the HMI from the panel, be sure to shut off all
power
being used by the system. It may cause electric shock, malfunction.
► Use cellular phone or walky-talky at least 30cm away from the HMI.
Otherwise, it may result in erroneous operation.
Disposal Precaution
Caution
► When disposing of this product or battery, treat it as industrial waste.
Otherwise, it may cause poisonous pollution or explosion.
4
Revision History
Revision History
'
※ The number of User’s manual is indicated the right side of the back cover.
ⓒ LS ELECTRIC Co., Ltd2018 All Rights Reserved.
5
Contents
6
Contents
7
Contents
8
Chapter 1 Overview
Chapter 1 Overview
Chapter2 System Configuration It describes features and system configurations for each XGT Panel.
Performance
Chapter 3 It describes XGT Panel and system configuration for each XGT Panel.
Specifications
It describes the installation, wiring and precautions for reliability of the PLC
Chapter4 Installation and Wiring
system.
XGT Panel Menu
Chapter 5 It describes the XGT Panel Menu.
Explanation
It describes the way to backup recipes, logging and other files by using
Chapter 6 Backup files by using
storage devices.
storage devices
It describes inspection categories and methods for long-term normal
Chapter 7 Maintenance
operation of the HMI system.
EMC Standard
Chapter 8 It describes the system configuration for EMC standards.
Certification
Appendix 1 Troubleshooting It describes a variety of error contents and measures.
Notes
This manual does not explain XP-Builder or PLC connections. Please refer to the related manual for these functions.
1-1
Chapter 1 Overview
1.2 Features
The XGT Panel has the following features.
USB Memory
XP-Builder
USB Loader
Cable
RS-232C/Ethernet
1-2
Chapter 1 Overview
1-3
Chapter 1 Overview
1-4
Chapter 1 Overview
1.3 Terminology
XP-Remote Software used to remote monitor and control the XGT Panel -
Abbreviation of Real Time Clock, It is used to call general IC that contains the
RTC -
clock function.
AC voltage Voltages whose charge flow and direction change periodically with time
Electric shock The current flows in the human body, causing injury or shock.
Failure to observe the instructions may cause dangerous situations that may
Caution Caution
result in serious injury or damage to property or property damage.
Failure to observe the instructions may cause dangerous situations that may
Warning Warning
result in death or serious injury.
As a general precaution, when you need to observe the instructions given in
Caution mark
the user's manual
1-5
Chapter 1 Overview
iXP2 -
(A) (B)(C)(D) (E)
1-6
Chapter 2 System Configuration
4
2
2-1
Chapter 2 System Configuration
iXP2-1200A
10
11
5 6 7 8 9
5 PE connector PE connection
ON
A
1 2 3 4
<Setting switch>
Battery cover, RS-422/485 termination resistance On
A Side.
Reset switch, No. 1/2 (Default)
9
Backup battery,
B Side. RS-422/485 termination resistance Off
Setting switch
A Side. O/S Download
No. 3
B Side. Nand Flash booting(Default)
A Side. Backup Battery On
No. 4
B Side. Backup Battery Off(Default)
<Reset S/W>
System reset switch. Pressing the switch will reset the system.
10 SD Card Logging / Recipe / Alarm / Project data backup and transfer
2-2
Chapter 2 System Configuration
12 13 14 15 16 17 18
Note
(1) The surface of the touch panel must be kept clean at all times.
- Foreign objects (water, oil, etc.) on the touch panel may cause malfunction.
(2) Touching the front of the touch panel may cause malfunction.
- Be careful that conductive objects do not touch the touch panel.
(3) The switch No. 1/2 of the setting switch must be set in the same direction.
- If switches 1 and 2 are set in different directions, communication problems may occur.
(4) Refer to the communication manual for details on communication connection.
(5) Please refer to Chapter 10 for installation details.
(6) For explosion-proof products
- Can open front USB cover using star wrench
- Front USB can only be used as a maintenance function
2-3
Chapter 2 System Configuration
To use XGT Panel, you must create project data in XP-Builder and transfer it to XGT Panel.
USB Memory
XP-Builder
USB Loader
Cable
RS-232C/Ethernet
If project data can not be transferred using communication, you can transfer data using USB storage device or SD card.
Please refer to Chapter 5 and XP-Builder User's Guide for more information.
USB Memory
SD
Card
Note
(1) It is recommended to use Ethernet rather than RS-232C.
(2) Refer to the communication manual for how to make the Ethernet cable.
(3) Refer to XP-Builder manual for project transfer method.
2-4
Chapter 3 Standard Specification
5≤f<9 Hz - 3.5mm
9≤f≤150 Hz 9.8m/s2 -
Vibration
5 10 times each
resistance
Continuous vibration in X, Y and Z IEC 61131-2
direction
frequency acceleration amplitude
5≤f< 9 Hz - 1.75mm
9≤f≤150 Hz 4.9m/s2 -
* Maximum shock acceleration: 147m/s2 (15G)
6 Shock endurance * Duration time: 11ms IEC 61131-2
* Pulse wave: half sine pulse (3 times each in X, Y and Z directions)
Square wave AC: ± 1,500V LS
Impulse noise DC: ± 1,000V ELECTRIC
Electrostatic
IEC 61131-2
Discharge ± 4 kV (contact discharge), ± 8 kV (air discharge)
IEC 61000-4-2
Immunity
Electromagnetic
IEC 61131-2
Radiated 80 ~ 1,000 MHz, 10 V / m
IEC 61000-4-3
Noise Emissions
7
Immunity
Fast Category Power module Communication interface
IEC 61131-2
Transient
IEC 61000-4-4
/ Burst noise Voltage 2 kV 1 kV
Communication
Category AC power DC power supply
interface
Surge IEC 61131-2
2kV (LG) 1kV (LG)
Voltage 1 kV
1 kV (LL) 0.5 kV (LL)
8 Environment Free from corrosive gases and excessive dust -
3-1
Chapter 3 Standard Specification
Note
3-2
Chapter 3 Standard Specification
3-3
Chapter 3 Standard Specification
3-4
Chapter 3 Standard Specification
Note
(1) Caution in power connection
- With AC power applied to DC power device, it may cause product damage or fire. Please pay a special
attention to connection.
(2) PE Connection
- For the device PE, please use PE terminal.
(3) Battery discharge-prevention DIP switch
- In order to prevent the battery discharge, turn off the DIP switch No.4.
To use backup function, please turn on DIP switch No. 4.
(4) Battery Operation and Life
- Battery is used for RTC (date/time) when the power of device is off. Battery is not consumed with power
applied.
(5) LCD Backlight Replacement
- Please replace LCD if you want to replace LCD backlight.
(6) Protection standard
- XGT Panel is designed by IP66 Standard in front parts. Ingress Protection (IP) is based on the IEC 60529
Standard for degrees of protection provided by enclosures. But XGT Panel does not guarantee from all
installation environment. When installing panels, make sure that dust and moisture are not brought in. For
more details on installation, See Chapter 4.Installation and Wiring.
- It complies with the following specifications.
IEC 60079-0:2011
EN 60079-0:2011
IEC 60079-15:2010
EN 60079-15:2010
IEC 60079-31:2013
EN 60079-31:2013
3-5
Chapter 3 Standard Specification
(3) For the PLC Ethernet communication cable use of the S.STP cable is recommended. If the S.STP cable
cannot be used due to the environmental conditions, it may result in communication abnormalities and noise in more
than one module.
3-6
Chapter 3 Standard Specification
Transmission
Type Used frequency (MHz) Purpose
speed (Mbps)
Category 1 Audio frequency 1 Telephone network (2Pair)
Note
(1) The categories that are commercially available in Korea and globally are categories 3, 5, En-Cat.5 and CAD.6.
Category 4 is now defunct following the category 5 appearances, and category 7 is a STP structure that is in the
development phase worldwide
3-7
Chapter 4. Installation and Wiring
4.1 Installation
This machine has high reliability regardless environment. But for reliability and stability, be careful the followings
4-1
Chapter 4. Installation and Wiring
Note
(1) Waterproof and dustproof standard
(a) IP66 Standards
1) The protection standards of XGT Panel have been designed to meet the IP66 test conditions,
in accordance with the degrees of protection provided by enclosures of IEC60529.
As this machine installed at the panel, it is not guaranteed with all installation environment even
though its protection standards for the front parts are satisfied.
2) IP66 rating guarantees the enclosure is dust proof (6) and protected against jets of water (6).
3) IP20 rating guarantees protection from solid foreign objects of above 12mm diameter proof (2),
but it does not guarantee protection from water ingress.
(b) Notice
1) In the environment where the protection grade of XGT Panel is exceeded or not satisfied,
the damage of the device or malfunction can occur due to the failure of protecting the product.
2) Since the protection grade of XGT Panel is the water-proof/dust-proof standards, it cannot be
protected from oil, corrosive gas and metal particles.
3) In case when Gasket is damaged by chemicals and continuous vibration, its water-proof/dust-proof
effect can be weakened.
4) In case when installing the panel, make sure that dust and water are not brought in panels.
4-2
Chapter 4. Installation and Wiring
This section describes the precautions for handling the XGT Panel from opening to installation.
Before installing the XGT Panel on the panel, it must be manufactured on the panel as shown in the table below.
Unit: [mm]
X
100 Z
100
100
4-3
Chapter 4. Installation and Wiring
Unit: [mm]
100
100
100 100
100
Note
(1) In order to be less affected by electromagnetic waves (radiation noise) or heat generated by other control devices,
Required.
(2) Install it considering the wiring of power and communication cables.
(3) When the panel cut dimensions are outside the reference tolerance (0 ~ + 1mm) when making the panel, the gap
between the gasket and the panel. The contact area may be reduced, and the waterproof and dustproof effect may be
weakened.
(4) When mounting the product on the panel, use gasket for waterproof and dustproof. The XGT Panel basically has a
waterproof and dustproof gasket is equipped.
(5) If the surface of the panel on which the XGT Panel is mounted is uneven, there is a gap between the XGT Panel and the
panel, or dust may penetrate. Particularly, depending on the material (steel, aluminum, acrylic, etc.) of the panel, This may
require installation environment review. Also check that the gasket and panel are in close contact. It is absolutely
necessary.
(6) If the condition of the gasket is contaminated or damaged due to deterioration at the time of installation or after a certain
period of use, the waterproof and dustproof effect care should be taken because it can be significantly weakened, and if a
gasket needs to be replaced, contact your nearest dealer or service. Please contact the center.
(7) In case of explosion-proof equipment, it should be installed in the environment with pollution degree 2 or less according to
KS IEC 60664-1.
(8) Install the front of the explosion-proof product in a place protected from the inflow of liquid in order to maintain the
explosion-proof performance after installation in accordance with the requirements of the obligatory safety certificate notice
of the protection device (Ministry of Employment and Labor Notice 2013-54)
When installing the product on the panel, use gasket for waterproof and dustproof. The XGT Panel is basically equipped with
a waterproof and dustproof gasket.
4-4
Chapter 4. Installation and Wiring
(4) Fixing
Fix the XGT Panel using the brackets on the panels as shown below.
(The bracket is included in the product.)
Fixed Bracket
Panel
Note
(1) During installation, XGT Panel should be closely contacted to the panel not to have any gap. In the
environment requiring water-proof/dust-proof effect, install and fix a bracket on a slope.
(2) The bracket should be fixed symmetrically(Up-Down, Left-Right). In case when it is not fixed
symmetrically, there could be a gap between the panel and XGT Panel.
(3) When fixing the bracket, it should be installed perpendicularly to the panel, and the required bracket
screw torque is 6.7kgf ㆍ cm. Depending on the material type of the panel, the torque value can be
different. The standard screw torque for each bolt size is followed. If it is fixed with the power more than
the required screw torque, the touch malfunction or weakening of water-proof/dust-proof can happen due
to the deformation of XGT Panel.
4-5
Chapter 4. Installation and Wiring
Be sure to remove the film attached to the panel to protect the front sheet when it is shipped from the factory.
Note
(1) Remove the protection film attached to the front of this machine. Due to the deformation of the
protection film, the touch malfunction or wrong input can occur. It is recommended to use a special
protection sheet to protect the front sheet. In case of purchasing the protection sheet, contact the
agency or a sales office close by.
Loosen the fixing bracket screw and remove the bracket from the XGT Panel.
Press the Anti-drop lock as shown below and then slowly push it forward to remove it from the panel.
Note
(1) If the device is forcibly remove from the panel without anti-drop lock, the product may be damaged.
(2) Be careful not to drop the product when removing the device from the panel.
4-6
Chapter 4. Installation and Wiring
4.2 Wiring
Caution
► Connecting AC power to a device that uses DC power may cause product damage or fire.
Be careful of connection.
► 'XXD' is a product using DC 24V and 'XXA' is a product using AC100-240.
Be sure to check the polarity of the back of the product before use.
► The equipment shall be installed in an enclosure which maintains an ingress protection rating protection
rating of at least IP64 and meets the enclosure requirements of IEC 60079-0 and IEC 60079-15, IEC
60079-31.
► Transient protection shall be provided that is set at a level not exceeding 140 % of the peak rated voltage
value at the supply terminals to the equipment.
► The equipment shall only be used in an area of not more than pollution degree 2, as defined in
IEC 60664-1.
► Plugs and sockets shall not be separated while an explosive atmosphere may be present.
► The equipment presents a potential electrostatic hazard. Clean only with a damp cloth.
► Install in a vertical direction only.
4-7
Chapter 4. Installation and Wiring
Type Cable specification (Unit: ㎟) Wire Type Thermal Resistance Screw Torque
Note
(1) For installations where there is voltage drop, it is recommended to use stranded wire with a cross
sectional area greater than 2 ㎟.
(2) It is recommended that cable connections are twisted and secure. Short cable runs are also
recommended between the point of supply and the XGT panel.
(3) For safety reasons it is recommended that you use color coded outer sheaths on the conductors to
aid safe terminations.
L N PE + - PE
Power
Supply
a a
b b
Note
(1) When the power fluctuation is larger than the specified value range, use a constant voltage transformer.
(2) When there is a lot of noise in the power supply, use an insulation transformer.
(3) Momentary power failure for stable data backup when power on / off. Please use.
(4) “a” is external earth, “b” is internal earth.
4-8
Chapter 4. Installation and Wiring
For XGT Panel power supply, I / O devices and power devices, separate the power supply system as shown below.
HMI
Main Noise
power
Power Filter
PE
Others
Note
Do not bring the power line of the XGT Panel close to the main circuit (high voltage, high current) line or I / O signal
line. Possible 100mm Install at an interval of more than two.
Use the surge absorber as shown in the figure below to prevent surge such as lightning.
XGT Panel
E1
E2
Note
(1) Separate grounding (E2) of the XGT Panel of ground surge absorber (E1).
(2) Select the surge absorber so that the surge absorber does not exceed the maximum allowable voltage even when
the power supply voltage rises to a maximum please give it to me.
4-9
Chapter 4. Installation and Wiring
When there is concern about noise penetration, use an insulation shield transformer or a noise filter.
Be sure to twist the wiring of the input power supply as short as possible and do not let the wiring of the shielding transformer or
noise filter pass through the duct.
When using a magnetic contactor (MC) for AC / DC, it is recommended to use Ferrite Core at the power input terminal.
EX) Apply a ferrite core to the power terminal as shown in the figure.
L N PE
Ferrite Core
(CU1130B, E-TECH)
(CU1330G, E-TECH)
(ZCAT3035-1330, TDK)
(1) This XGT Panel has enough noise countermeasures, so it can be used without grounding except when there is a lot of noise.
However, when grounding, please refer to the following.
(3) When dedicated grounding is not possible, use common ground as shown in Fig.
(4) Ground wire is 2 mm2 or more. If possible, place the grounding point near the XGT Panel to shorten the length of the ground
wire.
Note
If the grounding condition is bad or connected as in (C), the XGT Panel may malfunction or communication failure
may occur. Be sure to check grounding.
4-10
Chapter 4. Installation and Wiring
(1) Connect the cable tie through the external interface cable fixing hole on the back of the unit.
(2) Tighten the cable tie firmly so that the external interface cable does not come off by external force.
Caution
► External interface cable anchors are an important factor in maintaining explosion proof performance.
If it is not installed as described above, it may cause explosion due to spark due to abnormal connection of
cable. Therefore, please be sure to familiarize yourself with the above instructions.
4-11
Chapter 5 XGT Panel Menu Explanation
This chapter describes how to set the environment such as XGT Panel time setting, Ethernet connection setting, backlight setting.
If you press the [Settings] button on the XGT Panel main screen, you can set the environment of XGT Panel.
After booting the XGT Panel after turning on the power, the XP-Runtime main screen is displayed. Functions of each menu are as
follows.
Menu Meaning Details Note
Backlight Setting
Touch Setting
DateTime Setting
Environment Setting
Configuration menu of
Settings Ethernet Setting Refer to 5.1 Settings
XGT Panel
Buzzer Setting
Sound Setting
XP-Remote Setting
Goto MainMenu
Screen
Touch
Backup Memory/
Flash Memory
Diagnostics function of
Diagnostics USB Memory Refer to 5.2 Diagnostics
XGT Panel
Serial
SD Card
Touch Sensitivity
Goto MainMenu
5-1
Chapter 5 XGT Panel Menu Explanation
구분 의미 세부 항목 비고
Settings
PLC setting menu SHOW INFO
Refer to
PLC Information connected with Program Monitor
5.3 PLC Information
XGT Paenl OK
N:1 Settings
Refer to
Update XGT Panel For updating XGT Panel XGT Panel Update
5.4 Update XGT Panel
Project Download
It is for using Project Upload
Refer to
Storage Function the storage devices XGT Panel Update
5.5 Storage Function
used in XGT Panel Select USB
Cancel
5-2
Chapter 5 XGT Panel Menu Explanation
5.1 Settings
Press the [Backlight Settings] button on the [System Configuration] screen to go to the setup screen as follows.
5-3
Chapter 5 XGT Panel Menu Explanation
[Backlight setting]
Menu Explanation
Brightness Backlight Brightness can be adjusted.
Do not turn off backlight Backlight power is always on.
If you do not touch for a certain period of time, the backlight automatically turns
Turn off backlight after idle time
off.
Turn off after The backlight turns off after the set time (in minutes).
5-4
Chapter 5 XGT Panel Menu Explanation
You can adjust the sensitivity of the touch according to the type of gloves according to the work environment during touch operation. If
you press [Touch Setting] on the System Configuration screen as shown below, the setting window will be activated and you can set
the sensitivity according to the type of glove. You can set the sensitivity of the touch by user setting.
If you select the [PreDefined] option, the optimal sensitivity is set immediately when using bare hands, cotton gloves, rubber coated
cotton gloves, or water proof. If you want to adjust the sensitivity in detail, you can select [User Custom] option. In this case, you can
adjust the sensitivity in eight steps
[Touch setting]
5-5
Chapter 5 XGT Panel Menu Explanation
In [Gesture Function], you can select whether or not to use the function using the finger gesture. If checked, PAN and Flick operation
enables screen changing and data list search (history alarm view, logging viewer, file explorer, etc).
Note
(1) By default, XGT Panel has touch setting. If the touch position error is large, Please contact us for action.
(2) If touch glass breakage occurs, it may cause touch operation problem.
(3) Touch glass may cause touch malfunction due to water droplets.
In this environment, please disable the gesture function
5-6
Chapter 5 XGT Panel Menu Explanation
You can set the date and time of XGT Panel by pressing [DateTime Setting] button on [System Configuration] screen as follows.
2017
Today: 4/23/2017
[Date / Time Setting]
Note
Date / time view and setting are also available in the device information view of the communication setting dialog of XP-Builder.
For more information,See the XP-Builder User's Guide .
5-7
Chapter 5 XGT Panel Menu Explanation
If you press the [Environment Setting] button on the [System Configuration] screen to go to the setup screen as follows.
(1) Screen
5-8
Chapter 5 XGT Panel Menu Explanation
Menu Explanation
If you select [Show always], the title bar displays when a pop-up window is displayed on
the screen. You can select and move the title bar of the pop-up window. If you select [Hide
Window’s title bar : Show always] the title bar will not be displayed when a pop-up window is displayed on the
always screen, and you will not see it when you click the window screen blank.
/Hide always If you uncheck [Show always], [Hide always], the title bar will not be displayed when the
pop-up window is displayed on the screen, and the title bar will appear when you click the
window screen blank.
Smoothly handle the edge of each stroke when the letter is displayed. To do this, you can
choose between Anti-aliasing and ClearType. Generally, applying ClearType is more
Smooth edges of fonts : poetic, but Anti-aliasing may be better, depending on the font type and font size. Smooth
Anti-aliasing/ ClearType font display by selecting one of the two increases the load on the system, especially as the
font size increases, it may have a performance impact on functions such as flow alarms.
This feature is available on iXP, iXP2 and later models
After rebooting XGT Panel or downloading edit data,
Goto screen
You will switch. If you disable this setting,
after boot up
Button to move to the screen.
When I start the screen, I do not cache the image in advance,
It does not appear. However, if you select this option, the initial screen may appear
Quick start somewhat late.
There is. In particular, if the screen contains animation objects,
It may take a few seconds. The next screen transition is fast.
If you choose [Drawing takes precedence], the screen that you have already entered
when switching the screen will display the image/value based on the data that was last
displayed at that time. Then read the actual device value and display the image/value
Drawing takes again. If the screen is entering for the first time, it will behave the same as when [Drawing
precedence takes precedence] is deselected.
If you deselect [Drawing takes precedence] when switching the screen, read the actual
device value and display the image/value. This may take some time to switch screens
depending on the network situation or PLC response rate.
In order to exit to the standby screen during screen monitoring,
Do not show menu bar The window (menu bar) does not appear. If this is the case,
You need to configure and use a special switch to exit the screen.
Enable Arabic text
Enables the right-to-left language.
Display (right-> left)
Set startup screen The screen corresponding to the number entered at the start of monitoring is displayed.
(2) General
5-9
Chapter 5 XGT Panel Menu Explanation
Menu Explanation
Hide mouse cursor Mouse cursor does not appear after scrolling.
Buzzer On / Off You can set whether buzzer is used or not.
Buzzer test You can test the buzzer.
XGT Panel starts monitoring the images used on the screen to speed up the screen
operation.
It will be loaded into memory before use. By the way,
If a positive image is used, due to memory space constraints, all
The image will not load. In this case, if the screen is not yet loaded
Images are loaded, and there is not enough space, so unused images are retrieved from
Low Memory Mode
memory
The operation to delete may be repeated, and the screen switching operation may be
slowed down. In this situation
Low Memory Mode "is recommended. In Low Memory Mode, you do not load the image
before monitoring, but use only the original source of the image used in the project, which
results in less memory usage and less load to load and delete images into memory.
Ensures the order of operation when entering values by bit switch, word switch, multi-
switch, etc. when [Async mode] is deselected. In other words, when 1, 2, 3 actions are
performed by multiple switches or overlapped switches, 2 is performed when 1 action is
completed, and 3 is performed only when 2 is completed. Therefore, if there is no
response from the target controller in Operation 1, the actions 2 and 3 are also delayed
even if the controller is different.
Async mode
When [Async mode] is selected, the value is entered by bit switch, word switch, multi-
switch, etc. without ensuring order. In other words, when 1, 2, 3 actions are performed by
multiple switches or overlaid switches, each action can be completed in the order of 2, 1
and 3 depending on the network situation or controller response speed. Although the
order is not followed, it has the advantage of operating quickly for the rest of the controllers
even if some of them do not respond.
5-10
Chapter 5 XGT Panel Menu Explanation
When XGT Panel starts, it turns off USB power On to initialize the connected device.
Reset USB power
The initial setting is On, and if the USB recognition speed is slow or not well recognized
after boot up
Uncheck, power on again and try again.
When you start monitoring by selecting [Start] menu on the XGT Panel main screen,
It buffers the used image and shows the progress of the operation. (fast
Show progress Do not show progress if you make a start setting). At this time,
on the bottom If you check the [Show Lower] check box, this progress will be simplified and displayed at
the bottom of the screen.
Is displayed. This option can be applied when using the default screen image.
Sets whether the 5V power output is enabled at the 9pin D-sub terminal for RS-232C
RS-232C 5V
communication.
power supply
This feature is available on iXP, iXP2 and later models.
Delete all files you've downloaded on your device. However, connecting to the device
If a password is set, you must enter the password before you can delete it. The password
is the device connection password that you enter when downloading a project, This can
be set in XP-Builder on the Device Information View tab of the Communication dialog box.
Clear SRAM memory
The files to be deleted include user project data, web server, VNC startup module, option
And data files
card Driver, RAPIEnet communication setting data, XP-Manager setting data etc. from
user PC All downloaded data is included. Set using the configuration menu of the
machine. The contents are kept uninitialized. If the menu language is not English,
A device reboot is required to delete files.
5-11
Chapter 5 XGT Panel Menu Explanation
(3) BK Image
Menu Explanation
If you select an image, the standby screen and desktop are selected after the XGT Panel
is powered on.
If [Use boot image] option is selected, images with resolutions other than XGT Panel,
It can not be used unless it is a 24bit BMP image.
When you select an image, the XGT Panel is powered on and the standby screen and
desktop are selected.
Set to image. To turn off background settings, click the Clear Background button.
Delete background image
Just press it.
If you select the Use boot image option, you cannot use it unless it is an image with a
resolution different from the XGT Panel or a 24bit BMP image.
(4) Printer
5-12
Chapter 5 XGT Panel Menu Explanation
5-13
Chapter 5 XGT Panel Menu Explanation
Menu Explanation
Displays additional printer print settings dialogs. If there is no printer information
You should download from XP-Builder with the following message.
From XP-Runtime, go to Start menu and prepare for downloading.
After using the printer, you can use the menu.
Printer Settings
5-14
Chapter 5 XGT Panel Menu Explanation
Printer Settings
Menu Explanation
Port Connection method: Displays the connection method.
Printer type Printer type: Displays the printer type.
Print direction Orientation: Set whether it is horizontal or vertical.
Print color Print color: Set whether it is color or black and white.
High quality print Print quality: Set whether to print advanced.
View additional properties: Displays additional properties.
Printer Properties
More ... If you have made any changes, check whether you want to
save it,
Go to the dialog box.
OK Save the settings.
Cancel Cancels the setting.
Diagnose connectivity: Diagnoses the connection status of
the printer. this
The functions of the printer (LK-P30, LK-P41, LK-P43)
Support. Press the button to the right of the current status
Displays a message. If the printer is off
You can turn it on, connect the cable again,
Printer Check There is.
* Message Type *
One. OK: normal
2. No Printer: Not compatible with printer
3. Cover Open: Paper cover opened
4. Paper Empty: Out of paper
Test printing: To test the printout status
Function. It prints the following information and briefly
Outputs the printing status.
5-15
Chapter 5 XGT Panel Menu Explanation
(5) HDMI
Menu Explanation
Not used HDMI function is disabled.
Clone mode The same screen is displayed on the monitor connected by HDMI.
Extended mode
Expands the screen to a monitor connected via HDMI.
(To be implemented)
Note
5-16
Chapter 5 XGT Panel Menu Explanation
If you press the [Ethernet Setting] button on the [System Configuration] screen as below, you can set the IP to use Ethernet.
You can change the IP by pressing the [Set] button for each item of IP address, Subnet Mask and Gateway.
If you click [OK] button, changed IP information will be saved. Two Ethernet ports [LAN 0] and [LAN 1] can be set respectively.
Note
For 1: 1 connection with PC, it is recommended to set as follows.
If you press the [Disable] button and reboot, the device will not use Ethernet. If this is the case,
You can get the effect. To use Ethernet again, press [Enable] button and reboot.
5-17
Chapter 5 XGT Panel Menu Explanation
[Buzzer setting]
5-18
Chapter 5 XGT Panel Menu Explanation
[Sound setting]
5-19
Chapter 5 XGT Panel Menu Explanation
You can change the settings for XP-Remote that can remotely control the XGT Panel.
[XP-Remote setting]
[Explanation of the dialog box]
Menu Explanation
Allow XP-Remote to connect Allow connection of remote XP-Remote.
Max. of XP-Remote Specify the maximum number of XP-Remote that can be connected to XGT Panel.
If there is no communication request from XP-Remote within the designated time,
communication is stopped,
Timeout value
If XP-Remote has operation authority, it recovers operation authority.
(10 seconds ~ 300 seconds)
Enable control by XP-Remote
After XGT Panel starts to monitor, operation permission status is automatically set.
after Monitor Start
Set Password You can set it to enter a password when you request a connection from XP-Remote.
Note
For details of XP-Remote, refer to the XP-Remote User's Manual.
5-20
Chapter 5 XGT Panel Menu Explanation
5.2 Diagnostics
This chapter explains the functions that can be used to diagnose communication terminal, screen and touch function of XGT Panel.
If you click the [Diagnosis] button on the main screen of XGT Panel, a menu for diagnosing each function of XGT Panel is displayed.
5-21
Chapter 5 XGT Panel Menu Explanation
[Screen Diagnostic]
Screen
Red Green Blue Black White Graph
order
5-22
Chapter 5 XGT Panel Menu Explanation
[Touch Diagnostic]
5-23
Chapter 5 XGT Panel Menu Explanation
If you press the [Backup Memory] button, you can see the diagnostic results in the confirmation window.
Note
(1) If 'NVRAM Data Access ~~ Fail' occurs, take A/S action.
(2) If 'BATTERY STATUS ~~ BAD' occurs, you have to replace the battery through A/S.
If the rear setting switch 1 is set to B, set it to ON. B is a mode without backup battery.
5-24
Chapter 5 XGT Panel Menu Explanation
Note
1. If "Read Disk Information Error!" Occurs, please contact us.
2. Space allocation of Flash Disk may depending on O/S version.
5-25
Chapter 5 XGT Panel Menu Explanation
Note
If USB memory is installed and 'Read Disk Information Error!' Occurs, remove it, insert it again and test
do it. If the error message occurs repeatedly, contact Customer Service.
5-26
Chapter 5 XGT Panel Menu Explanation
Diagnostic function for serial communication port such as RS-232C, RS-422. Press the [Serial] button to diagnose the serial
ports installed on the XGT Panel. (However, for diagnosis, loop-back terminal must be connected to each port)
[Serial Diagnostic]
5-27
Chapter 5 XGT Panel Menu Explanation
Please make RS-232C port terminal as below. (Connect pins 2 and 3.)
Pin
name function
number
One TX + Data transmission
2 TX- Data transmission
3 RX + Receive data
4 RX- Receive data
5 SG Signal Ground
6 PE PE
5-28
Chapter 5 XGT Panel Menu Explanation
Note
If 'Read Disk Information Error!' Occurs when an SD card is installed, remove it, insert it again, and test it.
If the error message occurs repeatedly, take A / S action.
5-29
Chapter 5 XGT Panel Menu Explanation
5-30
Chapter 5 XGT Panel Menu Explanation
Note
1. Touch Sensitivity is only able to check if noise is flowing into iXP2.
2. Touch Sensitivity is only supported in XP-Builder V3.00 or later.
3. When touch is input, the value around the input area is increased. If the value of the non-touch area changes drastically,
please take A/S action.
5-31
Chapter 5 XGT Panel Menu Explanation
Note
PLC connection status can be viewed only when project data is transferred to XGT Panel.
5-32
Chapter 5 XGT Panel Menu Explanation
[PLC information]
Note
- PLC communication setting screen may be different for each driver.
- Refer to individual PLC manual for PLC communication setting change contents.
5-33
Chapter 5 XGT Panel Menu Explanation
You can check the connection number, PLC manufacturer, target PLC type, connection method, IP address, and timeout time set up
for connection with PLC in XP-Builder.
[PLC information]
Item Explanation
Connection No. Displays the communication connection number. Available from 0 to 15.
Vendor Displays the manufacturer of the communication target device.
Target device Displays the communication target device.
Connection type Displays the connection method.(RS-232, RS-422, TCP/IP, ect.)
Timeout value Displays the set timeout time.
Send wait value Displays the transfer waiting time.
Displays the number of retransmissions when a timeout occurs during
Retry value
communication.
5-34
Chapter 5 XGT Panel Menu Explanation
You can check the CPU type, operation mode, status, version and scan time of our own PLC model and provide information only
when connected with PLC.
Note
PLC types that can view PLC information are as follows.
- MASTER-K CPU, FEnet, Cnet
- GLOFA-GM CPU, FEnet, Cnet
- XGK / XGB / XGI / XGR CPU, FEnet, Cnet
You can check the PLC error history of your own PLC model.
Note
The PLC types that can display the error history are as follows.
- The MASTER-K CPU has no error history.
- GLOFA-GM CPU, FEnet, Cnet
- XGK / XGB / XGI / XGR CPU, FEnet, Cnet
5-35
Chapter 5 XGT Panel Menu Explanation
You can check the PLC run / stop operation mode history of your PLC model.
Note
The following PLC types are available to view the PLC operation mode switching history.
- MASTER-K CPU does not have operation mode switching history.
- GLOFA-GM CPU, FEnet, Cnet
- XGK / XGB / XGI / XGR CPU, FEnet, Cnet
You can check the PLC power shutdown history of your own PLC type.
Note
PLC type that can view the power off history is as follows.
- MASTER-K CPU has no power off history.
- GLOFA-GM CPU, FEnet, Cnet
- XGK / XGB / XGI / XGR CPU, FEnet, Cnet
5-36
Chapter 5 XGT Panel Menu Explanation
Note
The PLC types that can view the system history are as follows.
- The MASTER-K CPU has no system history.
- Only available with the GLOFA-GM CPU (GM4C). Other CPUs have no system history.
- XGK / XGB / XGI / XGR CPU, FEnet, Cnet
5-37
Chapter 5 XGT Panel Menu Explanation
5.3.8 N: 1 Setting
XGT Panel supports N: 1 service which enables communication between several XGT Panels and one PLC. You can set details
using the [N: 1 Settings] menu.
[PLC information]
[N: 1 setting]
Note
For detailed setting and understanding of N: 1 communication, refer to XP-Builder's N: 1 communication manual.
5-38
Chapter 5 XGT Panel Menu Explanation
Note
- Program monitor modules must be installed via XP-Manager.
- LS: XGK / XGB CPU, Cnet, and Enet driver.
- You must specify the use of the program monitor in the project properties of XP-Builder.
5-39
Chapter 5 XGT Panel Menu Explanation
The functions described in this chapter are for updating the XGT Panel software. By default, XGT Panel is also optimized
when downloading project file from XP-Builder. Use this function only if you need to update only the XGT Panel in particular.
The software of the XGT Panel will need to be updated with the new version as new functions and enhancements are
added. Refer to the following procedure.
[Method]
1. Connect XGT Panel and PC.
2. Run the XP-Builder.
3-1. Click [Communication] - [XGT Panel Update].
3-2. Click Connection Setup to select the type of XGT Panel and PC connected.
3-3. Click Browse and select the XP-Runtime file.
Note
1. Do not disconnect the communication cable or turn off the device while updating the XGT Panel.
XGT Panel may not update properly and may malfunction
2. Click Update XGT Panel menu and then click MENU on XP-Runtime screen to return to XP-Runtime menu
screen.
5-40
Chapter 5 XGT Panel Menu Explanation
5.5.1 Overview
Download the project edited by the user in XP-Builder from PC or upload the project backed up in the device to PC
Uploading and updating the device are usually done by connecting USB cable or Ethernet cable to XGT Panel series.
You can do it through. In situations where this connection is not possible, you can use the storage device to proceed.
The function description for [Storage Function] is as follows.
1. If you touch [Storage Function] on the menu, the following dialog box is displayed.
Project Download To download a project from an external storage device to the XGT Panel
Project Upload To transfer project data backed up to an external storage device from XGT Panel
XGTPanel Update To update the XGT Panel Software from an external storage device
5-41
Chapter 5 XGT Panel Menu Explanation
1. When you touch [Download Project] in the storage function menu, the following dialog box is displayed.
If you want to download a project using a storage device, it must be stored in the directory in the above path.
5-42
Chapter 5 XGT Panel Menu Explanation
1. If you touch [Upload Project] in the storage function menu, the following dialog box is displayed.
3. Touch the [OK] button to transfer the project backup file in the machine to the path of the selected storage device.
4. The project backup file must be downloaded to download the project backup file when downloading the project.
If not selected, the project backup file is not stored in the device and therefore can not be transferred to the storage device.
1. If you touch [Update XGT Panel] in the storage function menu, the following dialog box will be displayed.
5-43
Chapter 5 XGT Panel Menu Explanation
If you want to update the device using an external storage device, the XGT Panel Software file is in the directory in the
above path
It must be saved.
3. Touch the [OK] button to update the device with the XGT Panel Software stored in the specified path.
5-44
Chapter 6 Backup files by using Storage Devices
This chapter describes the management functions for external storage devices that store backup data of logging, recipe, and
screen images.
(1) XGT Panel can back up logging, recipe, screen image data to USB storage device according to the settings set in XP-Builder.
(2) If there is no capacity to be backed up on the specified storage device, the existing data is deleted according to the settings
set by XP-Builder, and the backup process or backup is stopped.
(3) The XP-Builder monitors whether or not the external storage device specified as the backup device is detached.
Logging
1 (Logging Number)
YYYY.MM.BeginDay.EndDay.0
HH.BeginMinute.FF
Lhhmmss0.CSV
2 (same as lower structure 1)
Recipe
ScreenImage
6-1
Chapter 6 Backup files by using Storage Devices
6-2
Chapter 6 Backup files by using Storage Devices
6. Structure of path when Blue Screen of camera image and live image is created
(1) ‘MovieStill’ directory will be formed at the sub route directory of USB storage device.
6-3
Chapter 6 Backup files by using Storage Devices
Remark
(1) When changing device time, in case of changing current time into after time, we guarantee the normal
operation. But in case of changing current time into early time, we don’t guarantee the normal operation. In this
case, you have to delete directory including the changed hour and its lower directory for normal operation. For
example, if you change time from December 10th to December 5th, you have to delete year, month directory
created in December 10th and restart the device
(2) Sorting by project is not supported for each logging, recipe, screen image. For example, there are no.1, 2, and
3 logging groups in the project A. And in case each logging group backups the file, 1, 2, 3 directories are
created and each data is saved under each directory. Then, in case file backup occurs in the project B having
no.1, 2 logging group, backup file is created in same directory of project A. In this case, you have to sort the
backup files of project A and B based on the created time.
6-4
Chapter 6 Backup files by using Storage Devices
Remark
(1) In unknown directory or file (user file or directory), searches the oldest thing among normal backup files except
unknown directory or file.
(2) In case there is nothing except user data in now searched directory, backup operation fails. XGT Panel
can’t delete user data, at this point, operation stops.
6-5
Chapter 6 Backup files by using Storage Devices
XGT Panels monitors connection status about external storage equipment designated when setting backup path in
XP-Builder. The following figure is backup path specified in XP-Builder.
In order to use this monitoring function, you have to set about system alarm window, and then the project should be
downloaded.
6-6
Chapter 6 Backup files by using Storage Devices
In case USB storage equipment is removed during operation after setting the path for saving Logging backup file as
USB storage equipment and downloading the project into device, the designated system alarm (HS951.0) is set. In
case storage equipment is equipped again, alarm is reset.
In case USB storage equipment is removed during operation after setting the path for saving Recipe backup file as USB
storage equipment and downloading the project into device, the designated system alarm (HS951.1) is set. In case storage
equipment is equipped again, alarm is reset.
In case USB storage equipment is removed during operation after setting the path for saving Screen Image
backup file as USB storage equipment and downloading the project into device, the designated system alarm
(HS951.2) is set. In case storage equipment is equipped again, alarm is reset.
Internal address of the designated system alarm can be checked in XP-Builder as follows.
6-7
Chapter 7 Maintenance
Chapter 7 Maintenance
To keep the XGT Panel best, examine the XGT Panel.
7.1 Maintenance
Because an error may be developed by environment, the periodic maintenance is needed. You should check the following
categories once or twice every 6 months.
7-1
Chapter 7 Maintenance
Check the followings once or twice every six months and take measure.
Maintenance
Maintenance category Criterion Action
method
Surrounding
0 ~ 50 C
Temperature Measure through Modify it to meet
Surrounding Temperature the general standard.
Environment 10 ~ 85%RH
Humidity /Hygrometer Measure (Environment standard
Surrounding of corrosive gas in the panel)
No corrosive gas.
pollution degree
Unwinding, swing Move XGT Panel Fixed firmly Retighten screws
XGT Panel Use a dry cloth to
Status Dust, foreign
Visual check Not loose remove dust and
matter adhesion
foreign matter.
Retighten screw with
Looseness Not loose Retighten screws
Screwdriver
Reduce the distance
Keep the proper
between compressed Visual check Correction
Connection distance.
terminals.
status
Wind the fixed screw of
Loose connectors Visual check Not loose
connector
Retighten screw with
Loose brackets Not loose Retighten screws
Screwdriver
Check the power
AC: 100~240V Supply
Power voltage maintenance voltage of input terminal
DC: 24V power modification
of power by test
Check the total of
Check when battery is If guarantee duration is
power stoppage time
exchanged and voltage exceeded even tough
and guarantee
Battery drop is indicated. there is no battery
duration
(It is expressed voltage drop indication,
There is no battery
by system alarm) change the battery.
voltage drop indication
Check the guarantee When error occurs,
LCD Backlight maintenance Visual check
duration change the backlight.
When error occurs,
No damage or
Touch Screen error Visual check change the Touch
Scratches and Pollution
Panel
Touch status
No damage or Change the touch pad
faulty touch pad Visual check Scratches in case of
/contamination an abnormality
7-2
Chapter 7 Maintenance
Maintenance
Maintenance category Criterion Action
method
• Damage or scratches
/contamination
Front sheet damage and Replace front sheet in
Visual check nonexistent
deformation case of an abnormality
• No front
sheet deformation
7-3
Chapter 7 Maintenance
Remark
(1) Battery exchange time is expressed by alarm. System alarm is expressed when system alarm
category is set at the XP-Builder as follows.
(2) Replace Battery With Hitachi Maxell, Part No. CR2032 Only. Use of another battery may present a
risk of fire or explosion. See User Manual for safety Instructions.
WARNING: Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire.
(3) As the iXP2 model has the integrated LCD and backlight, the LCD should be replaced when the life is
over or it is out of order.
(4) One of the ESD prevention measures, please use after wiping with a damp cloth.
7-4
Chapter 8 EMC Standard Certification
EMC command is regulated on “It doesn’t produce the Strong electromagnetic waves: Emission” and “It is not
affected by electromagnetic wave from external: Immunity”. The following is describing the contents to meet the
EMC command when configuring the system by using the XGT Panel. This is a summary document for the
request and standard which our company has obtained from EMC but we don't assure that all devices
manufactured according to these contents are not suitable for the below standards. The final manufacturer needs
to finally judge about the fitness method or fitness judgment of EMC command.
8-1
Chapter 8 EMC Standard Certification
Directive:
The XGT Panel acquire the electromagnetic fitness registration (KC specification) certified by wave laboratory
under information-communication part.
A grade device
8-2
Appendix 1. Troubleshooting
Appendix 1 Troubleshooting
1. Type of Problems
It classifies problems from XGT Panel including an indicated figure, indication of the object, and problems
appeared when downloading. Refer to the following chart.
APP1-1
Appendix 1. Troubleshooting
Question Why does black screen show up when turning on the device?
Phenomenon When turning on the device, black screen shows up and the booting is impossible.
<Solution>
(1) Because the device is not set as a booting mode, the above problem can occur.
Check whether No. 5 switch at DIP switch in the back of the device is in B direction or not.
B direction is a booting mode.
When applying the option, ‘Go to Screen after boot up’, it displays “Failed to load image files”
Question
as the monitoring has not been started.
After storing images in the USB storage device and then selecting the option “Go to Screen
Phenomenon after boot up” in the start menu, in case when re-permitting the power of the equipment, the
message like “Failed to load image files” is displayed and the monitoring is not started.
<Cause>
(1) In case when it is connected with the USB storage device, the recognition of the USB is delayed.
<Solution>
(1) In case when the recognition speed is delayed due to the characteristics of the USB storage device,
remove the USB storage device and then reinstall it.
Question When the power is re-permitted, the USB storage device (or USB mouse) is not recognized.
When the USB storage device was initially installed, it was normally recognized. However, it is
Phenomenon
not recognized after the power is re-permitted.
<Causes>
(1) Due to the option of the ‘Reset USB Power’ of the equipment, there could problems in the recognition
process.
(2) Depending on the USB storage device, it may not be smoothly recognized.
APP1-2
Appendix 1. Troubleshooting
<Solution>
(1) If the power initialization option (“Reset USB Power”) of the equipment is selected, cancel the selection
and then permit the power again. The “Reset USB Power” option is an additional function to improve
the initialization of the storage device with slow recognition speed or low recognition ratio. Depending
on the characteristics of the storage device, however, the power initialization can be an obstacle to the
initialization work. Thus, depending on Phenomenon, select what has higher recognition ratio by
properly using the power initialization option.
(2) Depending on the characteristics of the storage device, it may not be recognized. Use another USB
storage device showing higher recognition ratio.
APP1-3
Appendix 1. Troubleshooting
Question When touching the screen it reacts in a different area or it may not react at all?
Phenomenon When touching the screen it reacts in a different area or it may not react at all.
<Solution>
(1) Redo Calibration setting about touch. Refer to the [Device manual Ch.4.1 Touch Calibration].
(2) It you can’t go to setting menu, connect mouse to USB port and use mouse.
<Solution>
(1) Redo environment setting for buzzer to sound. Refer to the [device manual Ch.4.7 Environment Setting].
(2) After setting to use buzzer, check whether the buzzer sounds or not in the 1)’s setting windows.
After the system alarm about the lack of system memory occurs, XGT Panel itself closes the
Phenomenon
monitoring and then moves to the start menu in unspecific time without user’s operation.
<Causes>
(1) The memory usage could be exceeding 95%.
(2) The memory usage can be a bit increased when floating pop-up windows or moving to several screens
during monitoring. In case when the number of image used for project is a lot, the memory usage can
more easily reach the limit. In this case, XGT Panel closes the monitoring by itself and then takes an
action to secure the memory again.
<Solution>
(1) In case of using vector image instead of raster image, the memory share can be reduced. In the graphic
library of XP-Builder, the image group marked as OOO_R is the raster image group while the image
group marked as OOO_V is the vector image group.
(2) In case when the monitoring is closed down due to the increase of the memory share in spite of the
image change operation, contact the A/S center close by.
APP1-4
Appendix 1. Troubleshooting
After continuously adding projects to the screen, and adding/editing objects, the operation
Question
speed has been slowed down.
After adding projects to the screen and also adding/editing objects, it feels like the operation
Phenomenon
speed of XGT Panel gets slowed down.
<Causes>
(1) The amount of image used for projects is big.
(2) In order to increase the screen operation speed, XGT Panel maintains the used images in the memory in
advance. Since the memory resource has limitation, they cannot be maintained in the memory once the
amount of image exceeds a certain limit. Whenever they are needed, thus, they are read from the file
system and then expressed on the screen. This could be the reason why the screen operation speed gets
slowed down.
<Solution>
(1) In case of using vector image instead of raster image, the memory share can be reduced. In the graphic
library of XP-Builder, the image group marked as OOO_R is the raster image group while the image
group marked as OOO_V is the vector image group.
(2) In case when there is no proper vector image, the desired image can be composed by using various
functions of figures (circle, square, straight line and etc.).
(3) Removing unnecessary background screen, the screen is composed by applying the background colors.
APP1-5
Appendix 1. Troubleshooting
The shape of object is not shown or the number or character value which has to be shown is
Question
not shown
The shape of object is not shown or the number or character value which has to be shown is
Phenomenon
not shown.
<Cause>
(1) The connection with PLC connected with each project is disconnected or NAK occurs.
<Solution>
(1) When the communication is executed at first, Check the cable connected with PLC is OK or not.
(2) If object where the offset is set is not shown, check whether address range is exceeded or not.
(3) In case that communication is not OK, when communication is abnormal, the following message shows
up in the XGT Panel.
APP1-6
Appendix 1. Troubleshooting
<Cause>
(1) This happens when digit is not correct or type is not BCD.
<Solution>
(1) When the number to be expressed exceeds the number set in the object, # is expressed. In case of this,
set the digit largely and after download again, execute program again.
(2) When the numeric display object is expressed as BCD type, the data whose type is not BCD is
expressed as ~. In case of this, adjust device value as BCD type.
(3) This phenomenon occurs at the data list object, numeric input, numeric display device, and logging
viewer.
APP1-7
Appendix 1. Troubleshooting
Question After switching the screen, the previous screen remains for a few minute
After switching the screen, when there is no background or image in the part or number
Phenomenon
indication device, the previous screen remains for a few minute because of change of part
<Solution>
(1) It is normal status. In case that multiple connection or communication is not good, when switching the
screen, the remains of previous screen can occur during the time-out hour.
Phenomenon The number under the data list shows up above data list.
<Solution>
(1) It is normal status. The folded window or part object is not included in screen, regardless of sequence of
drawing, the object changed recently is expressed at top of screen. So if possible, do not fold the object
in screen.
I downloaded the figure above the object in XP-Builder, but the object always shows up above
Phenomenon
the figure.
<Solution>
(1) It is normal status. The object always shows up above figure in the XGT Panel.
APP1-8
Appendix 1. Troubleshooting
5. Communication Problems
On the screen where the object is not many, communication works but when you move the
Phenomenon
screen where the object is many, timeout occurs.
<Solution>
(1) It occurs because timeout is set much smaller than sum of request time of communication data and
response time from PLC. In the device setting at the XP-Builder, after setting communication time out to
be big, download program and execute again.
<Solution>
(1) In case of RS-232C, check whether connection setting is normal or not in XP-Builder.
(2) In case of RS-422/485, check whether station and communication connection setting is normal or not.
(3) If 1), 2) is normal, do diagnosis about PLC-RS232C, PLC-RS485/422 at the Serial diagnosis screen of
device menu. Refer to the [Device manual ch.5.6 Serial Communication Diagnosis]
(4) If 3) is normal, check whether connection cable has error or not.
(5) In case of Ethernet, check the port and IP setting about relative PLC.
(6) In case of Ethernet, make sure that the IP and port settings for the other PLC are correct.
<Solution>
(1) If the subnets of the two Ethernet ports are the same, the initial connection may be delayed due to
the seek time.
(2) If possible, remove the Ethernet port's subnet.
APP1-9
Appendix 1. Troubleshooting
Caution
► Before trial operation of the product, be sure to check if a normal communication is available
between XGT Panel and the subject device of control
APP1-10
Appendix 1. Troubleshooting
Question When removing the USB memory equipment, device is stopped for some times.
Phenomenon This happens when doing data backup including logging, recipe.
<Solution>
(1) If possible, when monitoring XGT Panel, do not remove the memory card and after going out to the
waiting screen, execute the removing.
(2) Inescapably you have to remove it during the operation, remove when backup does not occur. If the
above phenomenon occurs, it works normally after about 10 seconds.
(3) In case of USB memory, please remove it when the LED of USB external memory is not flickering.
Question After the repeated attachment/detachment of the USB storage device, it is not recognized
It can happen when the attachment/detachment of the USB device is repeated for a short
Phenomenon
period of time.
<Cause>
(1) When the USB device is recognized or removed, it takes a certain period of time(maximum a few
seconds) to recognize it. When the storage device is quickly installed/removed, however, it cannot be
normally recognized.
<Solution>
(1) It is recognized again after waiting for about a minute. Install it again after waiting for more than a minute.
(2) When removing/reinstalling the USB device, reinstall it after waiting for around 2-3 seconds.
Caution
► If you force to remove the data during the storage of data in the external memory, file may not
be stored in a normal condition or external memory may suffer from damage.
APP1-11
Appendix 1. Troubleshooting
Phenomenon The USB or SD card is inserted but the unit does not recognize it.
<Cause>
(1) It appears when the USB memory or SD card is partitioned.
<Solution>
(1) Please format USB memory or SD card as one partition.
Caution
► If you forcefully remove the data from the external memory while it is being saved, the file may not be
saved properly or the external memory may be damaged.
8. Touch recognition
Question It recognizes that you have touched a place you do not want.
<Caution>
(1) Check the surface of the touch panel for foreign matter such as water or oil.
(2) Check if the power or communication cable is passing on the surface of the touch panel.
<Solution>
(1) Clean the surface of the touch panel using a dry cloth or a towel
(2) When cleaning the surface of the touch panel, be sure to turn off the power to prevent malfunction
(3) Be careful not to let cables run near the touch panel
Caution
► The electrostatic touch panel may cause malfunction if liquids such as water or oil get on the surface.
► If you need to clean the unit, be sure to turn off the power before cleaning.
APP1-12
Appendix 1. Troubleshooting
In case that problems occur during execution of XGT Panel including the start of device, diagnosis of device and
environment setting, project download, monitoring of control device, and error messages occur as type of box. At
this time the message indicates the code made by 4 digit number. The front 2 number indicate code of object
and work, the rear 2 number is message number. In case that the present error message is indicated as [0101],
an error message occurs when doing diagnosis about the status of NVRAM. When an error message occurs,
refer to the row’s number and sequence and find the category of reason and measure.
APP1-13
Appendix 1. Troubleshooting
APP1-14
Appendix 1. Troubleshooting
Abnormal send-
Communication status is abnormal.
XGT payload. Please
0x00 Check the connection of
Panel download project
communication cable.
again.
This message shows up when making
it newly because there is no password
XP There's not Password
0x01 setting file in the device. When making
Builder File.
it newly, it is initialized with no
password.
It make new password setting file when
there is no password setting file. But
XP Failed to Create downloading is stopped when it fails to
0x02
Builder Password File. make this file because of device error.
If this problem is repeated, Contact the
near Customer Service Center.
Communication status is abnormal.
Project Route information is not correct to save
0x26 XP
download 0x03 Invalid Backup Media. project data. If this problem is repeated,
Builder
Contact the near Customer Service
Center.
In case that the version information file
doesn’t exist in the device, that file is
made newly. In case that the device
XP Failed to Create
0x04 has error and fails to make that file,
Builder version File.
download is stopped. If this problem is
repeated, Contact the near Customer
Service Center.
There is version information file. In
case that because of error of device, it
fails to read version information,
XP
0x05 File Size Error. because the device doesn’t know
Builder
version, download is stopped. If this
problem is repeated, Contact the near
Customer Service Center.
APP1-15
Appendix 1. Troubleshooting
APP1-16
Appendix 1. Troubleshooting
APP1-17
Appendix 1. Troubleshooting
APP1-18
Appendix 1. Troubleshooting
APP1-19
Appendix 1. Troubleshooting
APP1-20
Appendix 1. Troubleshooting
APP1-21
Appendix 1. Troubleshooting
APP1-22
Appendix 1. Troubleshooting
APP1-23
Appendix 1. Troubleshooting
APP1-24
Appendix 1. Troubleshooting
APP1-25
Appendix 1. Troubleshooting
APP1-26
Appendix2. Dimensions
1. iXP2-08xxA/D
APP2-1
Appendix2. Dimensions
2. iXP2-10xxA/D
APP2-2
Appendix2. Dimensions
3. iXP2-12xxA/D
APP2-3
Appendix2. Dimensions
4. iXP2-15xxA/D
APP2-4
Appendix 3. Warranty and Environmental Policy
1. Warranty contents
One. Warranty
The warranty period for your product is 18 months from the date of manufacture.
2. Scope of warranty
Partial replacements or repairs are available for any faults that occur during the above warranty period.
However, please note that if it falls under the following, it will be excluded from the guarantee range.
(1) In case of improper condition, environment, or handling other than those specified in the instruction manual
(2) If the cause of the fault is something other than our own product
(3) If the product has been modified or repaired outside of the designated spot designated by the Company or the
Company.
(4) If the product is not intended for its original use
(5) When the product is shipped from the Company, due to unforeseen circumstances at the level of science or technology
(6) If there is no responsibility for other genius, fire, etc.
2. Environmental Policy