Liebert CRV: In-Row Cooling Solution

The document discusses Liebert CRV, an in-row cooling solution for data centers. It addresses changing needs in data centers like higher heat densities, variable heat loads, and more precise temperature control. Liebert CRV uses direct expansion or chilled water cooling directly at the server rack. Key features include variable capacity compressors or chilled water valves for modulating capacity, EC fans for variable airflow, and controls to precisely manage temperature and humidity. It is presented as a flexible solution capable of satisfying various data center layouts and cooling requirements.

Uploaded by

garis24b
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views

Liebert CRV: In-Row Cooling Solution

The document discusses Liebert CRV, an in-row cooling solution for data centers. It addresses changing needs in data centers like higher heat densities, variable heat loads, and more precise temperature control. Liebert CRV uses direct expansion or chilled water cooling directly at the server rack. Key features include variable capacity compressors or chilled water valves for modulating capacity, EC fans for variable airflow, and controls to precisely manage temperature and humidity. It is presented as a flexible solution capable of satisfying various data center layouts and cooling requirements.

Uploaded by

garis24b
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 25

LIEBERT ® CRV

In-Row Cooling Solution

19-FEB-2019
WHAT HAS CHANGED IN DATA CENTERS?

Higher Heat Densities


Higher Cooling Densities required
Variable Heat Loads
Cooling Capacity Modulation required
Variable Airflows
Fan speed modulation required
More Precise Control
Air Temperature control at the server inlet required

We Need Products that can Satisfy these Requirements!

Preliminary planning document, subject to consultation, negotiation or other local legal requirements 2
FROM THE SERVER TO THE RACK
TO THE DATA CENTER ROOM

Vertiv has different solutions available for any rack and Data Center layout

• One of the solutions is to place the cooling unit next to the server
and the IT rack
• Thermal Management units have the capability to adapt to the
servers’ needs in terms of air flow and air temperature
LIEBERT CRV – ROW BASED COOLING
▪ DX and CW Version
▪ 300 and 600 mm wide frame
▪ Wide Range: 4 basic capacities in DX and 5 in CW version
▪ High Efficiency:
▪ EC Fans
▪ Inverter driven scroll compressor on the 300mm frame
▪ Digital Scroll on the 600 mm frame
▪ High Density Applications: up to 10kW/Rack in open architecture
▪ Rich features: Humidifier, Re-heat, ATS, and more…
Direct Expansion (DX) Chilled Water (CW)

CR012RA CR025RA CR020RA/W CR035RA/W CR030RC CR052RC CR060RC CR040RC CR050RC


kW 13.6 22.2 23.4 36.4 39.2 54 57.0 46.6 58.0
Humidity
No Yes Yes Yes Yes No Yes Yes No
Control
Width 300 mm Frame 600 mm Frame 300 mm Frame 600 mm Frame
Rating Conditions: DX – 38 °C, 22% RH, 35 °C Outdoor temperature; CW – 38 °C, 22% RH, 7/12 °C CW Temperature

*Additional Notes 4
PRODUCT POSITIONING - FEATURES

Liebert CRV
Fully Featured Thermal Management Unit

• Cooling
• Humidification / Dehumidification
• Reheating
• Up to F5 filtration class
• Air Discharge Baffles
• Dual Power Supply with ATS
LIEBERT® CRV CW – MAIN FEATURES

EC Fans Fully Featured


• Variable air flow • With humidifier and reheat
• High Efficiency • Dual Power supply with ATS
• Low Power Consumption • Internal Condensate pump
• Quiet Operation • Air Discharge Baffles

VertivTM ICOMTM Control Variable Capacity Compressor


• Vertiv ICOM control with 6 • Cooling Capacity modulation
control modes • High Efficiency
• Up to 20 rack temperature • Quick adaptation to changing
detection points heat loads
• Easy integration to BMS • Low Power consumption
• Large Coldfire Display

Preliminary planning document, subject to consultation, negotiation or other local legal requirements 6
LIEBERT® CRV DX – MAIN FEATURES

EC Fans Fully Featured


• Variable air flow • With humidifier and reheat
• Energy Saving • Dual Power supply with ATS
• Quiet Operation • Internal Condensate pump
• High Efficiency • Air Discharge Baffles

VertivTM ICOMTM Control CW Valve


• Vertiv ICOM control with 6 • 2-Way or 3-way Chilled Water
control modes valve
• Up to 20 rack temperature • Precise control thanks to 0-10V
detection points Actuator
• Easy integration to BMS
• Large Coldfire Display

Preliminary planning document, subject to consultation, negotiation or other local legal requirements 7
DX VERSIONS: DIGITAL SCROLL COMPRESSOR –
MODULATING CAPACITY
Only 600 mm
Digital Scroll Compressor models
modulates the capacity thus
guarantees the right temperature

Main Features Benefits for Customer


• Low energy consumption
• Cooling Capacity quickly adopts to
• Allows scalable IT infrastructure
changing heat loads
• Ideal for applications with variable heat
• Low power input
loads
• High Efficiency
• Longer compressor lifetime
DX VERSIONS: DC INVERTER SCROLL COMPRESSOR
COOLING CAPACITY MODULATION
Only 300 mm
DC Inverter Scroll Compressor models
Modulates the cooling Capacity thus guarantees the right
temperature

Main Features Benefits for Customer


• Cooling Capacity quickly adopts to changing • Low energy consumption
heat loads • Allows scalable IT infrastructure
• High efficiency on full and partial load • Ideal for applications with variable heat loads
• Low Inrush Current • Longer compressor lifetime
• Quiet Operation • Downsized UPS and Gensets
DX VERSIONS: ELECTRONIC EXPANSION VALVE

All DX models

Main Features Benefits for Customer

• More precise superheating control • Energy savings thanks to lower


• Allows lower condensing condensing temperatures
temperatures • Better control of the refrigeration
system
CW VERSION: CHILLED WATER VALVE

0-10V Chilled Water Valve


For precise cooling capacity control

• 3-way or 2-way CW valve


• 0-10V Valve actuator for precise water flow control
• Top / bottom CW piping connections for easy adaptation to any site
CW VERSION: CHILLED WATER COIL

High Efficiency CW Coil


For the best heat transfer

• Coil designed to achieve highest efficiency


• Tube-fins design
• Hydrophylic fin treatment to minimize water carryover
• No droplet separator required
• Low air and water side pressure drop
• Dehumidification allowed on the whole range
TECHNOLOGY EMPLOYED

The Entire Range


AIRFLOW MODULATION

EC Fans
Deliver always just the required air flow

Main Features Benefits for Customer

• Variable airflow to meet server requirements • Low energy consumption


• High Efficiency • Quick adoption to server airflow needs
• Low noise • Suitable for open as well as closed architecture
• Emergency Airflow • Highest availability
EMERGENCY AIRFLOW FOR HIGHEST AVAILABILITY 600 mm
models
⚫ When the Liebert CRV is operating at 100% of its catalog capacity, both fans are only spinning at partial
speed.

100% Rating Max Fan Speed Extra Airflow


CRV 20kW 4172 m3/h 4905 m3/h 18%
CRV 35kW 5500 m3/h 6806 m3/h 23%
CRV 40kW 5650 m3/h 6548 m3/h 16%

⚫ Benefits:
• In the event of a fan failure, the functioning fan will increase to max speed to help compensate for the
lost fan. Plus, when multiple Liebert CRV units are Teamworked together, the other units will also
assist the impaired unit

• The unit will automatically ramp to max fan speed when the room is overheated.
Example: Heat soaked, post-power failure condition. Extra airflow provides extra capacity to return to the room
set point FASTER.
FIELD ADJUSTABLE MODULAR BAFFLES
Getting the air where it needs to be – close to the IT Available for the
equipment Entire Range

Air discharge
to the left

Air discharge to
Readjust baffles as cooling needs the right
and room layout changes
Air discharge to
both sides
VERTIVTM ICOMTM CONTROL

Vertiv ICOM Control


takes care of IT racks

• 6 Control Modes
• Up to 10 rack-installed temperature sensors per unit
• Graphical User Interface for local control and integration to Network Management System
• Teamworking – Unit to unit communication for highest availability and performance
optimization
SENSORS

CR012; 25; 30 CR020; 35; 40; 50; 60


• Each unit is as standard equipped
• Each unit is as standard equipped from
from the factory with:
the factory with: o 1 x Return Air temperature and
o 1 x Return Air temperature and humidity humidity sensor
sensor o 1 x Supply Temperature Sensor
o 1 x Supply Temperature Sensor o 3 x Rack temperature sensor
o 1 x Rack temperature sensor Rack Sensor o Leak detection sensor available as
Rack Sensor o 1 x Leak detection sensor an accessory

• Max number of Rack • Max number of Rack


temperature sensors temperature sensors
connected to 1 unit connected to 1 unit
DX units CW units
DX/CW units
10 6
10

*Additional Notes 18
SIX CONTROL MODES

Six control modes to independently match the server heat load and airflow as
server operations change

Cooling Capacity
(via Digital Scroll Compressor or CW Valve)
Sensors Supply Air Remote Rack Return Air
Airflow (via Factory
Supply Air Setting
Variable Speed
Default with
EC Plug Fans) Remote Rack rack sensors

Return Air Traditional

= Available
= Recommended With and Without Containment

Preliminary planning document, subject to consultation, negotiation or other local legal requirements 19
EASY INSTALLATION - TOP AND BOTTOM CONNECTIONS
FOR ALL MEDIA
Piping

All media can be connected from top or from bottom


• CW or DX piping
• Humidifier piping
• Condensate piping (condensate pump for top connection)

Piping
CONDENSATE MANAGEMENT AND
DUAL POWER SUPPLY
ATS location in
⚫ Condensate pump available for all models 600 mm models

⚫ Dual power supply alternate available for all models


except for CR012 and CR025
– 600 mm models have ATS located in a box on the top of the unit
– 300 mm models have internal ATS
EASY SERVICE AND MAINTENANCE

⚫ All service and Maintenance can be done through the front or the back side of the unit
⚫ No Side access required

Access from the front


through the front door

Access from the back,


through the back door
TYPICAL APPLICATIONS

Small data centers


Server Rooms
• Raised Floor not required

Combination with
• Open or closed architecture

Smart Aisle
• Heat densities up to 10 kW / Rack
in Open Architecture
LIEBERT® CRV - SUMMARY

Liebert® CRV is suitable both for new and existing buildings:

• With or without raised floor


• With or without humidity control
• Addressed in particular for data centers from 1 to 30 racks
• Heat load up to 10 kW / rack (open architecture)
• Typically for rooms from 5 to 100 m2 room space
Air diffuser can be adjusted on site for left, right or both air distribution hands for the best
cooling effect
Space saving frame – High cooling capacity from a small footprint
SmartAisleTM ready – Easy integration into cold aisle containment