Upper Display
Upper Display
Enter 162 to pass
CodE Enter 162 to parameter prog. mode
SET Enter “262”
Back J, J.0: J type T/C CodE to start
K, K.0: K type T/C auto-tune
Press “Back”
t, t.0: T type T/C
to return to the Inpt Sensor Type (1)
SET S: S type T/C SET
top of
r: R type T/C
parameters “tunE”
Pt, Pt.0: Pt100
programming flashes
block Select HeAt: heating function
SET
h-C function (2) Cool: cooling function • Before starting Auto-tune, adjust H.SET.
• Auto-tune does not start in “cooling” mode.
• Process value may exceed H.Set during auto-tuning.
0 .. 50 / Heat/Cool Hysteresis (oC): • After auto-tuning, control form automatically switches
H.hys / 0.0 .. 50.0 (3) PID is active if set to 0 to PID mode.
SET C.hys o
C (for H.Hys) (oC) • Auto-tuning is stopped (interrupted) any time by
AL.tY pressing any key. In this case, the parameters before
SnS.O 1 .. 50 / auto-tuning is valid.
A.hys 0.1 .. 50.0 (3) Alarm Hysteresis (oC) • Auto-tuning may not always determine the best values
or SET o
C for your process.
SnS.F
Upper Display Factory SET Values:
H.SEt: 100 oC
Pb.C 5 .. 150 oC Proportional Band in (oC) CodE Enter “555”
SET A.SEt: 400 oC
for factory Inpt : J
reset H-C : Heat
SET
H.hys: 0 oC
SET
Ct 1 .. 200 sec Control period (sec)
A.hys: 3 oC
H.Hys “YES” / “nO” Pb.C: 30 oC
not 0 Integral Time: Ct: 4 sec
0:00 .. 30:00 In min:sec If set to 0:00, • To return to factory settings: ti: 5:00 min:sec
SET
ti min:sec Code > 555 > select “yes” >
P, PD is active (integral OFF). td: 1:00 min:sec
Press “SET” UP.L: 400 oC
Derivative Time: Lo.L: 0 oC
0:00 .. 10:00 oFFS: 0 oC
td min:sec In min:sec. If set to 0:00,
SET
P, PI is active (derivative OFF). AL.tY : rel
r.ALr: 3 oC
Upper limit value for Lo.L, C.dLY: 15 sec
Lo.L .. H.SET and A.SET. Upper Scale value P.Err: 0
SET
UP.L Upper Scale (oC) differs according to the selected C-t: 0.0 oC / min
sensor type. L.dSP: yes
Lower limit value for UP.L, o.Sht: oFF
Lower Scale ..
SET
Lo.L UP.L (oC) H.SET and A.SET. Lower Scale value SECU: AH
differs according to the selected
sensor type.
-100 .. 100 / Offset Value; Offset is directly added
SET
oFFS -100.0 .. 100.0 (3)
O
to the measured value. This feature shall
C
be used for user calibration. Normally set to 0.
Abs,rel,bnd,bn.i Alarm Type:
-Abs,-rel, Abs: Absolute -Abs: Absoloute, invert out SnS.O: Sensor failure
SET
AL.tY -bnd,-bn.i, rel: Relative -rel: Relative, invert out Continuous out
SnS.O, SnS.F bnd: band -bnd: band, invert out SnS.F: Sensor failure
AL.tY= bn.i: band inhibit -bn.i: band, invert out Flashing out
Abs,-Abs, r.ALr/ -100 .. 100 / Relative or band Alarm
SnS.O, -100.0 .. 100.0 (3)
SET Value. Displayed if AL.ty is
SnS.F b.ALr O
C
other then Abs or –Abs.
0.0 .. 300.0 If C-t is not 0, ramping starts after power on. SET value
SET
C-t o
C / min is incremented or decremented C-t degrees per minute
until SET reaches H.SEt or C.SEt.
End Prog.
(1) When sensor type is changed, Up.L, Lo.L, H.Set, A.Set, H.hys, Error Messages:
A.hys, r.Alr, b.Alr, oFFs may be set to a new value automatically, Fail: Sensor failure or sensor selection wrong
according to the selected sensor. E.FLS: Hardware failure
(2) ON-OFF control is the only option for Cooling function E.CAL: Hardware failure
(3) If sensor type is selected as Pt.0, J.0, K.0 or t.0. E.EPr: Memory failure
Gürbüzoğlu Elektronik San. ve Tic. Ltd. Şti. http://www.gemo.com.tr.
Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye e-posta: [email protected]
Tel: +90-312-3503900, Fax: +90-312-3511117
3
GEMO
PROGRAMMING HEAT SET and ABSOLUTE ALARM SET
Press 2 sec.
SET
Upper Display
Heat SET;
(Process SET)
SET H.SEt Lo.L .. UP.L oC value is
AL.tY set Lo.L .. UP.L
= rel, -rel
bnd, -bnd Displayed if Ab.AL=Yes;
bn.i, -bn.i, A.SEt Lo.L .. UP.LoC Absolute Alarm SET
SET
SnS.O, Value is set Lo.L .. UP.L
Sn.F
Prog. end
ALARM OUTPUT
AL.tY = Abs, -Abs; X = A.SEt
AL.tY = rel, -rel ; X = H.SEt + r.ALr
PV PV
X (X+A.hys) (X-A.hys) X
PV PV
A B H.SEt C D A B H.SEt C D
PV
H.SET (H.SET+C.Hys) (H.SET-H.Hys) H.SET
PID PARAMETERS
- P, PI, PD, PID is active when “H.Hys” is set to 0 (only for heating; h-C is set to ”HEAt”)
- PbC: Proportional band in oC.
- Ct: Control period for PID control. Prefer 4-10 sec.
- Ti: Integral time; Set in minutes. Determines how fast controller reacts to compensate the offset between SET point and the
process value. If set to 0, integral part is OFF. If set too low, process value may oscillate.
- Td: Derivative time; Set in minutes. If set to 0, derivative part is OFF. Determines how sensitive the controller is to changes of
the offset between SET point and the process value. If set too high, process value may oscillate or overshoot.
CLAEANING
Do not use any solvents (alcohol, thinners, benzine, acid, etc.) or corrosive substances to clean the device. Use only a dry
and clean non-abrasive cloth. Before cleaning, disconnect the power supply and mains connections.