Identification and Coloring of Insulated Conductors and Cables Rules 4-024, 4-026, and 4-032 Issued May 2022 Scope
Identification and Coloring of Insulated Conductors and Cables Rules 4-024, 4-026, and 4-032 Issued May 2022 Scope
Bulletin 4-5-14
Identification and coloring of insulated conductors and cables
Rules 4-024, 4-026, and 4-032
Scope
Consumer’s services
Rule 4-024 1) requires that all insulated neutral conductors up to and including No. 2
AWG, in any location, be identified by a continuous white covering, or by three
continuous white strips along the entire length of the conductor.
Rule 4-026 requires that insulated neutral conductors larger than No. 2 AWG to either
be continuously identified or be suitably labelled or marked at each end at the time of
installation. Marking shall be permitted to be white paint, white sleeving, white tape, or
other equivalent means.
Rule 4-024 4) permits insulated neutrals of any size in multi conductor cables to be
permanently identified at each accessible point in the circuit by the use of white paint,
white sleeving, white tape, or other equivalent means.
Safety Note
There was a near miss reported where the neutral and a phase conductor were
interchanged accidentally at the supply connection point to a consumer’s service.
Historically, utilities have used white to identify one of the phase conductors in their
systems, which can potentially lead to errors when a consumer’s service is connected to
a supply authority system.
Although not required by the Code, it is considered good practice to bare the
consumer’s neutral conductor at the weather head on three phase services to reduce
the likelihood of a utility worker treating the white conductor as a phase conductor.
Rule 4-032 requires that insulated bonding or grounding conductors up to and including
No. 2 AWG in size to have a continuous outer finish that is either green or green with
one or more yellow stripes.
In sizes larger than No. 2 AWG the conductor is permitted to be labelled or marked in a
permanent manner with a green colour or green colour with one or more yellow stripes
at each end and at each point where the conductor is accessible. Paint, sleeving, tape,
or other equivalent means are acceptable.
Note
Where tape is used outdoors for identification of conductors at a supply connection
point or similar location, “Weather Resistant” tape shall be used.
Where there are longer lengths of cable at larger enclosures such as switchboards a
minimum of 150 mm of conductor shall be identified at the points of connections.
Question
Why are some non metallic sheathed cable (NMSC) jackets coloured blue, some red,
some yellow, some white, etc?
Answer
The colouring of the jacket of non-metallic sheathed cable is not mandated by the Code.
Some cable manufacturers are colour coding the jackets of cables intended for different
purposes as a marketing tool. White is intended for general purpose circuits, blue is
intended for AFCI circuits, yellow for 20 amp kitchen circuits, and red for 240 volt
circuits. Inspectors will check the wire size (gauge) rather than the cable jacket colour to
ensure the correct wire has been used for the connected load.
Figure B2
NMSC
b) 120 V equipment as per OESC 4-032, it is permitted to use a cable with red and
black conductor provided that any exposed portion of the coloured conductor is
permanently changed at each accessible point in the circuit by white paint,
sleeving, tape, or equivalent means (see Figure B3).
Figure B3
NMSC
Note
When tape is used for marking of conductors it shall be applied as per CSA C22.2 No.
197 PVC insulating tape states: “The tape is intended to be applied in layers, each layer
being half-lapped...”