RSLogix Gateway Config
RSLogix Gateway Config
NT 50 Gateway
RSLogix5000
Web: http://www.hilscher.com
List of Revisions
Index Date Version Chapter Revision
0 Jan. 2015 1 All Created
Table of Contents
1 Document Scope .....................................................................................................4
2 Example System......................................................................................................4
3 NT 50 Configuration ................................................................................................4
3.1 NT 50 Setup ....................................................................................................5
3.2 EtherNet/IP configuration .................................................................................6
4 RSLogix5000 Configuration .....................................................................................7
4.1 Add New Module .............................................................................................7
4.2 Module Properties............................................................................................9
4.3 RSLogix Download and Run ............................................................................9
1 Document Scope
The intention of this documentation is to show the user how to configure a
Gateway such as NT 50 or NT 100 or NB 100 to communicate with a
Rockwell 1769-L32 processor module using RSLogix5000. This document
will not cover the entire scope of the RSLogix5000 software and it is
expected that the user is familiar with this software and the 1769 controller
connected to it.
2 Example System
The example system used in our configuration example consists of the
following devices.
• 1769-Power Supply
• 1769-L32E Processor
• 1769-QB16 (Not used in example)
• 1769-IQ16 (Not used in example)
• End Cap
• RSLogix5000 Software
• NT 50
The NT 50 Gateway device is connected to the L32E via Ethernet hub/switch
or directly using a cross over Ethernet cable. IP address and subnet mask
must be within the range to communicate.
3 NT 50 Configuration
The NT 50 Gateway adaptor is configured by using the SYCON.net on the
DVD delivered with the product. Please insert this DVD and install the
software. After the install of the software the first step will be to configure the
Gateway. This is done as follows.
3.1 NT 50 Setup
4 RSLogix5000 Configuration
The configuration of the 1769-L32E will be done by using RSLogix5000.
Open this application and create a new project that matches the system
1769 configuration.
In RSLogix5000 under the I/O Configuration folder right click on the 1769-
L32E module and select New Module. The following screen should appear.
RSLogix Select Module Type Dialog Box
Configure the IP Address of the Gateway which was done previously in the
SYCON.net parameters. Our example device is set to 10.0.0.101.
Connection parameters should follow the example. Please note that the input
area size is four(4) bytes or two words more than what was configured
SYCON.net. The additional four bytes or two words contain status
information about the EIP adapter. The definition of this information can be
found in the EIP Adapter manual. Input assembly instance is always 101 and
output assembly instance is always 100. The configuration assembly
instance is set to 1 and 0 size.
After completing the configuration of the new module download the project to
the CompactLogix PLC and go to Run mode. The LEDs on the NT 50
Gateway should be in a solid green state. This indicates that the PLC and
the adapter are communicating properly.