0% found this document useful (0 votes)
218 views

PSC-12M - Installation Instructions

The document provides installation instructions for the Siemens Model PSC-12M 12 Amp Power Supply. The PSC-12M supplies 24VDC power to fire safety systems and has a built-in battery charger capable of charging up to 100AH batteries. It can switch to standby batteries during power outages. The power supply mounts in the back of a fire safety control panel enclosure and has terminals for connections, LED indicators, and a reset switch.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
218 views

PSC-12M - Installation Instructions

The document provides installation instructions for the Siemens Model PSC-12M 12 Amp Power Supply. The PSC-12M supplies 24VDC power to fire safety systems and has a built-in battery charger capable of charging up to 100AH batteries. It can switch to standby batteries during power outages. The power supply mounts in the back of a fire safety control panel enclosure and has terminals for connections, LED indicators, and a reset switch.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Installation Instructions

Model PSC-12M
12 Amp Power Supply

INTRODUCTION The Model PSC-12M from Siemens Industry, Inc., is a high current power supply that
provides the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
system with primary regulated 24VDC. It is rated at 12A and has a built-in charger that
is capable of charging up to
100AH batteries. It also has a
microprocessor-controlled
transfer circuit that allows
the PSC-12M to switch
the system power to
stand-by batteries during
loss or reduction of the
AC power.

The PSC-12M incorpo-


rates a replaceable 20 Amp
fuse on the battery input. It
provides connection to a
tamper switch and Voltage Selector Switch

terminal tie points for


system signals.
Figure 1
The PSC-12M communi- PSC-12M 12 Amp Power Supply
cates directly to the
PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3
(Cerberus PRO Modular) to report fault conditions and allows the PMI/PMI-2/PMI-3
(XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular) to query the status of the power supply. It has 1 common alarm relay, 1
common trouble relay, and 2 programmable relays. The common alarm and common
trouble relays are defaulted to activate when the degrade ALARM bus or degrade
TROUBLE bus is asserted.

The PSC-12M mounts at the back of the enclosure of the FireFinder-XLS/Desigo Fire
Safety Modular/Cerberus PRO Modular system and occupies one location on the
studs in the backbox or on the optional FireFinder-XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular Mounting Plate, CAB-MP.

Features The PSC-12M features are as follows:

• AC power input 120VAC - 240VAC @ 60Hz / 50Hz


• Off-line Switch Mode Power Converter
• Power Factor Correction
• Built-in Battery Charger
• Total Output power of 5A@24VDC (Continuous), 12A@24VDC (Alarm)

Siemens Industry
Industry,, Inc.
A6V12021370_enUS_b Smar
Smartt Infrastruct ure
Infrastructure
• Two separate power output terminals: one power limited terminal with 4A
max @ 24VDC capacity and one non-power limited terminal with 12A max
@ 24VDC capacity (total not to exceed 12A)
• Both output terminals have over current protection.
• Auto resettable current protection circuits for overload and short circuit
• Access to CC-5/CC-2 System bus
• Supplies 6.2VDC @ 2A (power limited) to the system bus
• Supplies 24VDC @ 2A (power limited) to the system bus (subject to a 12A
total current limit)
• Communicates via HNET protocol
• Provides termination for the tamper switch
• One common alarm relay, one common trouble relay and two program-
mable relays with 2A ratings

OPERATION The PSC-12M occupies one network address in the HNET network and has three
functional components: the Controller, the Main Power Module, and the Interface Board.

The Controller component (with a build-in battery charger) monitors the status of the
PSC-12M Power Supply (ground fault conditions, loss of network communication,
24VDC terminal overload and the status of the battery). This information is relayed to
the User Interface, where applicable, and is communicated to the PMI/PMI-2/PMI-3
(XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular) for system reporting. The Controller also allows the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) to
query the state of the power supply. It also provides the control of the relays.

The degrade ALARM bus and degrade TROUBLE bus will override the command that
is sent by the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular),
FCM2041-U3 (Cerberus PRO Modular) to the Alarm and Trouble relays.

The Controller also monitors and maintains the battery. This circuitry utilizes three
charge modes, depending upon the state of the batteries: Bulk (Full) Charge Current
Absorption, and Float (maintenance) State. It monitors the batteries and determines
which of the charging modes to activate.

The PSC-12M's Main Power Supply component has an Off-line switch mode power
converter and power factor correction. It is designed to take voltage inputs of
120VAC-240VAC at 60Hz/50Hz.

The Interface Board provides diagnostics LEDs, system connections and the terminal
connections on the PSC-12M.

Terminal Blocks The PSC-12M has one reset switch, one battery disconnect switch, one 20A fuse (for
battery reversal protection), seven LEDs, three HNET address switches, four terminal
connections, and two 60 pin flat ribbon cables as shown in Figure 2.

The LED's and switches located at the top of the module are defined as follows:

Siemens Industry, Inc. 2 A6V12021370_enUS_b


Smart Infrastructure
RESET - Pushing the reset switch re-initializes the
POWER LIMITED
TAMPER
SWITCH
OUTPUT
(24VDC @ 4A)
PSC-12M operation.
FMT REMOTE

POWER - (Green) Normally ON. When illuminated,


RISER LVM
TB1 +
_

1
P5
1 6 1 2 indicates that the PSC-12M is powered
TB3 from the AC mains. When flashing, indicates
that the PSC-12M is powered from the battery.
7 12
GROUND
FAULT P10 REMOTE CAN
SUPERVISION LVM NETWORK
CONNECTION
MODULE FAIL - (Yellow) Normally OFF. When illuminated,
indicates that the module microprocessor has
failed.

HNET FAIL - (Yellow) Normally OFF. When illuminated,


indicates that HNET communication with the
PSC-12M has terminated.
+ +

GND FAULT - (Yellow) Normally OFF. When illuminated,


indicates that the PSC-12M has detected either a
negative or positive ground fault on its outputs.

24V 12A FAIL - (Yellow) Normally OFF. When illuminated,


TO PSX-12, TO PSX-12, indicates that the 24VDC nonpower limited
PSX-12M PSX-12M
OR CC-5/CC-2 OR CC-5/CC-2 output has a trouble condition or the PSC-12M
has disconnected the 24VDC output due to
current overload or short circuit.

24V 4A FAIL - (Yellow) Normally OFF. When illuminated,


F1 indicates that the 24VDC power limited output
BATTERY P9
TB2 P12 has a trouble condition or the PSC-12M has
_ 19 24
disconnected the 24VDC power output due to
CONNECTION + GND
1 2 N

+ TB4
_ 13 18 H current overload or short circuit.

BATTERY STATUS - (Green/Yellow/Flashing Yellow) When


NON- POWER RELAY OUTPUTS AC
LIMITED OUTPUT (2A @ 30VDC/ CONNECTION
(24VDC @ 12A Max.) 120VAC (.6PF) (INPUT)
illuminated Green, it indicates that the battery is
Figure 2 properly connected to the Power Supply. It
Terminal Blocks, Controls and Indicators illuminates Yellow when there is no battery
connected (or battery voltages are below 14V) to
NOTE: terminal P9 and it flashes Yellow if the Battery
Positive and negative ground fault detected at: Disconnect switch was pressed.
<20K ohms for TB3 terminals 1,2
<20K ohms for TB4 terminals 1,2
<30K ohms for TB1 terminals 10,11 BATTERY DISCONNECT - Pressing (1 second) and releasing this button
<20K ohms for TB1 terminals 4,5 inhibits transfer to battery if AC is removed. The
<30K ohms for TB1 terminals 1,2
battery status LED will blink yellow. Removing AC
<1.5K ohms for TB1 terminals 7,8
in this state will power down the system. There is
no need to disconnect the battery cable.

HNET - The 3 Rotary Switches located directly below the


LEDs are used to set the HNET network address of
the PSC-12M.

VOLTAGE SELECTION SWITCH - Located on the right side of the power supply
(see Figure 1) selects the AC voltage source.

Siemens Industry, Inc. 3 A6V12021370_enUS_b


Smart Infrastructure
The Installer must always activate the Battery Disconnect Switch and wait for the Battery
Status LED to flash Yellow before physically removing the battery cable.

F1 A 20 Amp Mini Blade Fuse (P/N A5Q20010590) is pre-installed to

protect the battery from reverse polarity.

The terminal blocks of the PSC-12M are defined as follows (See Figures 2, 3 and 4.

TB1 Terminals 1, 2 and 3 provide connection to the FMT riser.

Terminals 4, 5 and 6 provide an output to the monitor speaker in a


remotely mounted LVM.

Terminals 7, 8 and 9 provide an input from the microphone of a remotely


mounted LVM.
LVM
FMT MONITOR
RISER SPEAKER Terminals 10, 11 and 12 provide external CAN network connection.

+ – S + – S
TB2 Relay outputs; 1 for Alarm, 1 for Trouble and 2 User-programmable relays
that are set to NOT USED in ZEUS by default. These outputs are rated 2A
1 6
@ 30VDC/ 120VAC (0.6 PF).
TB1
7 12 Under normal system operation, the alarm and trouble relays are
+ – S + – S controlled by the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire
LVM CAN Safety Modular), FCM2041-U3 (Cerberus PRO Modular). However, if the
MICROPHONE HNET fails (and an initiating card cannot communicate with the PMI/
PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular),
S = SHIELD TIE POINT.
CONNECT AT ONE FCM2041-U3 (Cerberus PRO Modular), the initiating card will control the
PSC-12M ONLY. ALARM and TROUBLE relays. The User programmable relays are acti-
Figure 3 vated by the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety
TB1 Wiring Diagram Modular), FCM2041-U3 (Cerberus PRO Modular) output logic as pro-
grammed by the Zeus tool. When the system is operating normally,
these relays are controlled by the output logic only. (See Figure 4.)

PROGRAMMABLE TB3 24VDC Power Limited Output Terminal. This terminal output is limited to
4A. When it is exceeded, it will shut down, light the 24V 4A Fail diagnos-
USER USER
RELAY 2 RELAY 1 tic LED and send a fault condition to the PMI/PMI-2/PMI-3 (XLS),
OUTPUT OUTPUT
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO
NO NC C NO NC C Modular).
19 24
This output is normally connected to remote modules. This
TB2 output is power limited to NFPA 70 per 760. All wiring must be in
13 18
accordance with Article 760 of NEC or local building codes. (See Figure 2.)
NO NC C NO NC C

Output Voltage: 24VDC +10%, -15%


TROUBLE ALARM
Output Current: 4A max
RELAY RELAY
OUTPUT OUTPUT TB3-1: (+) terminal
TB3-2: (-) terminal
DEDICATED

Figure 4
TB2 Wiring Diagram

Siemens Industry, Inc. 4 A6V12021370_enUS_b


Smart Infrastructure
TB4 24VDC Non-Power Limited Output Terminal. This terminal is non-power
limited and can supply up to 12A. When the current draw is exceeded, it
shuts down, lights the 24V 12A Fail LED and sends a fault condition to the
PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular),
FCM2041-U3 (Cerberus PRO Modular).

This output is normally connected to the input terminals of the CC-5.


This output must remain within the enclosure or within 20 feet in rigid
conduit. All wiring must be in accordance with Article 760 of NEC or
local building codes. (See Figure 2.)

Output Voltage: 24VDC +10%, -15%


Output Current: 12A max
TB4-1: (+) terminal
TB4-2: (-) terminal

The total cumulative sum of the 24VDC output (power limited + non-power limited)
must not exceed 12A. Over-current draw will initiate a PSC-12M shut down.

The main AC power line must be turned OFF prior to installation.

P5 Connects the HTSW-1 Tamper Switch to the PSC-12M to determine the


position of the panel door. The door position status is then transmitted
to the system bus. (See Figure 2.)

This circuit is intended for 24 hour circuit monitoring and is configured by


the Zeus tool. Refer to HTSW-1 Installation Instructions, P/N 315-033350.

There can be only one Tamper Switch connection per enclosure.

P9 Connects the back-up battery to the PSC-12M. Battery size has to be


calculated to ensure that the battery size can support the system load
during battery back-up condition. Refer to the Zeus battery calculations in
the tools folder to determine the required battery size of the system.

Always apply AC power first followed by the battery.

P10 Set the jumper on P10 to the ENABLE (left-hand) position to enable
ground fault supervision.

P12 AC input connector from the Power Supply Filter Assembly (PSFA),
or Power Termination Board (PTB), P1/P2.

Siemens Industry, Inc. 5 A6V12021370_enUS_b


Smart Infrastructure
2x60-pin Connects the PSC-12M to the system. It is a straight- through connection
between the two connectors and provides the 24VDC rated at 2A and
6.2VDC rated at 2A that powers the CC-5/CC-2 modules. It also
contains all the communication signals and system signal bus that is neces-
sary for the proper operation of the system.
These connectors are power limited. If the PSC-12M is located in a
different row in the enclosure, an optional extended ribbon cable, Model BCL
(P/N 599-633997), must be used.
If the PSC-12M is located to the left of a CC-5 or CC-2 an optional longer rib-
bon cable is required between the PSC-12M and the CC-5 or CC-2. Model
CBL-8 (P/N S54400-K8-A1) must be used.
Output Voltages: 24VDC , 6.2VDC
Max Current : 2A @ 24VDC, 2A @ 6.2VDC

PRE-INSTALLATION The PSC-12M installation kit has the following components:

INSTALLATION KIT COMPONENTS

PSC-12M / PSFA Kit PSX-12M PSFA (Only)


Four #10-32 1/2" Phillips Screws Four #10-32 1/2" Phillips Screws
(for PSC-12M) (for PSX-12M)

Four #10 Hex Nuts (for PSFA) Four #10 Hex Nuts

AC Wire Assembly, AC Wire Assembly,


P/N 600-134264 P/N 600-134264
Battery Wire Assembly, Battery Wire Assembly,
P/N 465-633943 P/N 465-633943
Battery Cable Conversion Kit 60-pin Flat Ribbon Cable,
P/N 545-634222 P/N 555-133036

Table 1

The following parts are optional:


• If the PSC-12M is not located in the same row in the backbox (or on the same
optional CAB-MP) as the CC-5, an extended 60 pin flat ribbon cable, Model BCL (P/N
599-633997) from Siemens Industry, Inc., is required.

• If the PSC-12M is located farther than 12 inches from the PSFA/PTB the
500-634879-PSC-CBL-24 Extension Cable is required.
If the PSC-12M is located to the left of a CC-5 or CC-2 an optional longer ribbon
cable is required between the PSC-12M and the CC-5 or CC-2. Order model
CBL-8 (P/N S54400-K8-A1).
The following components must be set prior installing the module in the enclosure:

Verify that the dedicated circuit breaker for the PSC-12M is turned OFF at the mains.

• Network Address Switch: Set the three-digit HNET network address for
the PSC-12M using the three rotary dial address switches located below the
LEDs on the front panel. (Refer to Figure 2 for the location of the switches.)
The address for the PSC-12M must be the same as the address selected for
it in the Zeus Programming Tool. To set the address, turn the pointers on
each of the three dials to the numbers for the selected address. For ex-
ample, if the address is 123, set the pointer for the HUNDREDS dial to “1” ,
set the pointer for the TENS dial to “2”
, and set the pointer for the ONES dial
to “3” . The range of allowable addresses is from 001 to 251 (leading zeros
must be used).
• Voltage Selector Switch: If the AC input is 220/240VAC, you will need to
set the red switch on the right side of the unit (see Figure 1) to the 220 po-
sition.
Siemens Industry, Inc. 6 A6V12021370_enUS_b
Smart Infrastructure
INSTALLATION

Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)

For 220/240VAC installation, check the Voltage Selector Switch before installing the
Power Supply.

The PSC-12M mounts on studs in the backbox or on the optional Mounting Plate
(CAB-MP). The Mounting Plate may be located either inside or outside of the enclo-
sure to perform this installation procedure. If the Mounting Plate is located inside the
enclosure you will have to gain access to it by opening
the enclosure Inner and Outer doors. If the
Mounting Plate is located outside of the enclosure,
POSITION 1 POSITION 2 POSITION 3 POSITION 4
place it in front of you so that the word “TOP” is at
the top and away from you.
TOP THREADED POSTS

TOP
The PSC-12M can occupy any position in the backbox
or on the mounting plate, but it should be installed in
the row and position that is located directly above the
PSFA to which it is connected. (Refer to Figures 5 and
7). When the PSC-12M is mounted correctly on the
optional Mounting Plate it will be flush on the top,
CAB-MP bottom, and right with the Mounting Plate and the
mounting screw holes of the PSC-12M will align with
the threaded posts.

1.Install four 10-32 screws in the threaded posts at


the mounting position. Screw each of the 10-32
BOTTOM THREADED POSTS
screws into the threaded posts 5-6 turns.

POSITION 1 POSITION 3 POSITION 4


2.Place the PSC-12M over the four screws on the
POSITION 2
Mounting Plate and slide it down or towards you to
Figure 5 rest on the four screws. (Refer to Figure 6.) When
Location Of The PSC-12M On The Optional CAB-MP the PSC-12M is in the correct position it will be flush
with the top, bottom and right side of the Mounting
Plate.
3.Tighten the four screws.

Siemens Industry, Inc. 7 A6V12021370_enUS_b


Smart Infrastructure
SLIDE DOWN UNTIL
FLUSH ON TOP,
RIGHT, AND BOTTOM

PSC-12M
CAB-MP

Figure 6
Mounting The PSC-12M On The Optional CAB-MP

WIRING The PSC-12M has removable terminal blocks and connectors at the top and bottom
of the module. The terminals and connectors at the top of the PSC-12M are power
limited. The terminals and connectors at the bottom of the PSC-12M are non-power
limited. (Refer to Figure 7.)

Use a separate or dedicated circuit breaker and run the earth ground from a suitable
source to the PSC-12M. Check local requirements.

Conduit is not an acceptable Earth Ground Conductor.

/ PTB

Figure 7
PSC-12M Wiring In The CAB Enclosures

Siemens Industry, Inc. 8 A6V12021370_enUS_b


Smart Infrastructure
Wire in accordance with local codes and Article 760 of the NEC, NFPA latest edition.
In compliance with NEC, all power limited fire protective signaling conductors must
be separated a minimum of a 1/4" from all of the following wiring located within a
control panel:

• Electric light
• Power
• Class 1 or non-power limited fire protective signaling conductor
Refer to the CAB2-BB Installation Instructions, P/N 315-033009-1 for wiring require-
ments to comply with NEC codes.

Battery Connections When BTX-1, BTX-2 or BTX-3 batteries are required, connect them to the system
with the Battery Cable Conversion Kit, P/N 545-634222, following the steps listed
below.

1. Using the 12 in. long wire assembly, connect the two batteries together, as
shown in Figure 7. Secure each end of the assembly to the battery with a
10-32 x 3/4” screw and lock nut.
2. Attach the quick disconnects to the positive and negative battery terminals
with the 10-32 x 3/4” screws and lock nuts supplied.
3. Attach the red battery wire to the quick disconnect on the positive terminal
and the black battery wire to the quick disconnect on the negative terminal.

QUICK
DISCONNECT
(2 PLACES)

10-32 X 3/4” -
SCREWS
(4 PLACES)

+ 12 IN. LONG
WIRE ASSEMBLY
-

LOCK NUT
(4 PLACES)

BTX-1, BTX-2 OR BTX-3


BATTERIES

Figure 8
Wiring BTX-1/-2/-3 Batteries To The PSC-12M

Siemens Industry, Inc. 9 A6V12021370_enUS_b


Smart Infrastructure
Power Supply Load and Battery Calculations

The PSC-12M power supply load and battery size calculations are performed by the
Zeus tool based on the equipment in the physical view. Once all of the equipment is
inserted into the physical view for each enclosure and a successful compile is
performed, the results of the calculations are shown in the report view.

From the Tools menu, select Report Generation and then select System Power &
Battery Calculation Report. The report contains power supply loading and battery size
results for each enclosure. This report can be printed for a permanent record.

Battery Power Use 12 AWG for battery connection.

Battery backup is required for compliance to UL864. The PSC-12M can charge a
battery up to 100 amp hours. (15 amp hours is the minimum size for the PSC-12M.)

These battery models are UL listed for use with the FireFinder-XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular system:

• BP-61—24V, 15 AH
• BTX-1—a set of 12V, 31 AH
• BTX-2—a set of 12V, 75 AH
• BTX-3—a set of 12V, 100AH

Select the battery that meets or exceeds the final calculated battery amp hour rating.
Use an external battery box, SIEMENS Model CAB-BATT, P/N 500-633917, with the
BTX-2 and BTX-3 models.

Battery System Electrical Rating:


Input Voltage: 24VDC +10%, -15%
Input Current: 15A max.
Minimum Battery size: 15AH
Maximum Battery size : 100AH
Battery Max Charge Current: 5A (full charge mode)

Siemens Industry, Inc. 10 A6V12021370_enUS_b


Smart Infrastructure
ELECTRICAL RATINGS
120VAC @ 50/60Hz
Input Voltage 220VAC @ 50/60Hz
240VAC @ 50/60Hz
3.5A Max. @ 120VAC
Input Current 2.5A Max. @ 220VAC
2.0A Max. @ 240VAC

24V Back Plane Current 2A Max.

Power Limited: 4A Max.


Screw Terminal 24V Current
Non-Power Limited: 12A Max.

6.2V Back Plane Current 2A Max.

150mA +
24V Standby Current
20mA per active relay

Output Power

8V peak to peak max.


Each HNET/XNET and CAN
Network Pair 75mA max.
(during msg transmission)

Table 2

COMPATIBILITY:
The PSC-12M is compatible with the PSFA or the PTB.

Siemens Industry, Inc. 11 A6V12021370_enUS_b


Smart Infrastructure
CYBER SECURITY DISCLAIMER

Siemens provides a portfolio of products, solutions, systems and


services that includes security functions that support the secure
operation of plants, systems, machines and networks. In the field of
Building Technologies, this includes building automation and control,
fire safety, security management as well as physical security
systems.

In order to protect plants, systems, machines and networks against


cyber threats, it is necessary to implement – and continuously
maintain – a holistic, state-of-the-art security concept. Siemens’
portfolio only forms one element of such a concept.

You are responsible for preventing unauthorized access to your


plants, systems, machines and networks which should only be
connected to an enterprise network or the internet if and to the
extent such a connection is necessary and only when appropriate
security measures (e.g. firewalls and/or network segmentation) are
in place. Additionally, Siemens’ guidance on appropriate security
measures should be taken into account. For additional information,
please contact your Siemens sales representative or visit https://
www.siemens.com/global/en/home/company/topicareas/future-of-
manufacturing/industrial-security.html.

Siemens’ portfolio undergoes continuous development to make it


more secure. Siemens strongly recommends that updates are
applied as soon as they are available and that the latest versions are
used. Use of versions that are no longer supported, and failure to
apply the latest updates may increase your exposure to cyber
threats. Siemens strongly recommends to comply with security
advisories on the latest security threats, patches and other related
measures, published, among others, under

https://www.siemens.com/cert/en/cert-security-advisories.htm.

Siemens Industry, Inc. Siemens Canada, Ltd.


Smart Infrastructure 1577 North Service Road East Document ID A6V12021370_enUS_b
Parsippany, NJ Oakville, Ontario
L6H 0H6 Canada

You might also like