The document provides details for designing a bi-axial isolated reinforced concrete footing for column C2 of an admin building. It includes dimensions of the column, footing, and pedestal. It specifies the grade of concrete and steel. It calculates the self-weight of the footing and soil, unfactored loads, design forces, and checks that the maximum and minimum bearing pressures are within the safe gross bearing pressure. The footing design is then shown using the maximum effective soil pressure.

Uploaded by

lagnajit das
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views

Angul Foundation C94

The document provides details for designing a bi-axial isolated reinforced concrete footing for column C2 of an admin building. It includes dimensions of the column, footing, and pedestal. It specifies the grade of concrete and steel. It calculates the self-weight of the footing and soil, unfactored loads, design forces, and checks that the maximum and minimum bearing pressures are within the safe gross bearing pressure. The footing design is then shown using the maximum effective soil pressure.

Uploaded by

lagnajit das
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

VOLTAS

DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)


Building Name COLUMN C2 OF ADMIN BUILDING
Footing Number:

COLUMN/PEDESTAL
Length (l, dim. || Z axis ) = 250 mm
global
Breadth (b, dim. || X axis) = 450 mm
X
Height of pedestal = 0m Breadth 2 m
Weight of pedestal/column = 0.00 KN

FOOTING
Footing founding level = 2m global
global Z
Top of footing Depth from ground lvl= 1.65 m Z
Foot length (L, dim. || Z axis) = 2m
Foot Breadth (B, dim. || X axis) = 2m
Thickness of footing (t1) = (highest) 350 mm global
Thickness of footing (t2) = (lowest) 350 X
Clear cover to Reinforcement = 50 mm
Main bar dia of footing = 10 mm
Effective depth of footing = 295 mm Length 2 m
Selfweight of the footing = 35.00 KN Footing Dimensions
Area of Footing(A) = 4.00 m2
Sect mod of foot about Z axis (Zz) = 1.33 m3
Sec mod of foot about X axis (Zx) = 1.33 m3

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 30 N/mm2
Grade of steel fy = 500 N/mm2

CHECK FOR GROSS BEARING PRESSURE


Safe NET bearing pressure = 150 KN/m2
Safe gross bearing pr. = 186.00 KN/m2 (net pr. + depth of foot * soil unit wt)
Unfactored load case number = 11
Axial load from output (P1) = 303.385 KN SLS
Moment about Z axis (Mz) = 0.822 KN-m SLS
Moment about X axis (Mx) = 1.57 KN-m SLS

Unit wt of soil = 18 KN/m3


Weight of soil retained above foot = 115.46 KN
Load due to filling = 28.86 KN/m2
P = (P1+soil+pedestal+foot selfwt) = 453.84 KN
Maximum bearing pressure = 115.25 KN/m2 P My Mx Safe
 
Minimum bearing pressure = 111.67 KN/m2 A Zy Zx Safe
Safe against max gross bearing pr.

DESIGN FORCES
Factored load comb. no. 11 self wt of footing &
soil wt is not
Axial load:(Pu) = 455.0775 KN considered in Pu.
Moment about Z axis (Muz) = 1.233 KN-m
Moment about X axis (Mux) = 2.355 KN-m
Maximum effective soil pressure pe max
( Pu/Area+ Muz/Zz + Mux/Zx) = 116.46 KN/m2
Minimum effective soil pressure pe min
( Pu/Area - Muz/Zz - Mux/Zx) = 111.08 KN/m2
Design of footing is done using above maximum effective soil pressure

735535544.xlsx
VOLTAS

DESIGN OF FOOTING Column C2 pA = 114 KN/m2 *


P = 303 kN SLS fck 30 N/mm 2
pB = 116 KN/m2 ###
Mx = 1 kNm SLS fy 500 N/mm 2
pc = 113 KN/m2 ###
Mz = 2 kNm SLS Z pD = 115 KN/m2 ###
H = 29 kN

350

115
Gross SBC = 186.0 kN/m2 A B ###

0.590

114
Areq. = 1.64 m 2
Mz 2 ###

0.875

0.285

114
A prov. = 4.00 m2 Safe 0.45 ###

Mx 0.822
Column /

0.25

Lz = 2.00

0.25

2.00
pmax = 116 < 186 Safe X ###

B
Pedestal

Lx =
pmin = 113 >0 Safe 115 ###

0.875
Self weight of footing = 8.8 kN/m2 Lx = 2.00

350

114
Load due to filling = 28.9 kN/m2 C D

Total downward load 37.6 kN/m2 0.775 0.775

Depth of footing at center, T1 = 350 0

350
Depth of footing at edge, T2 = 350 Ly = 2.00 350

Bearing pressure Safe A


Along Along
113 114 0.295 0.480
X - axis Z - axis
One way shear Safe Safe 114 115 115
Twoway shear (Punching shear) Safe 114
Dia of the bar, f 10 10 d/2 0.15

Required spacing 187 187

Provided spacing c/c 125 125 Safe Check for Punching shear
Net moment at face of column 23 29 kN.m per m Eff. depth at d/2 from face of column = 295 mm
Factored moment(Mu=1.5*M) 35 44 kN.m per m Influence area for twoway shear 3.59 m2
d req. 92 103 mm Shear force = 277 kN
d available 295 285 mm Perimeter of the footing @ critical sectio = 2.58 m
Mu /bd2 0.40 0.55 N/mm2 Nominal shear stress, tv = 0.55 N/mm2
Ast req. 420 420 mm2 ks = 0.5+bc = 1.00
Ast prov. 628 628 mm2 tc =0.25 sqrt(fck) = 1.37 N/mm2
% prov. 0.213 0.220 Allowble punching shear stress = ks*0.25 = 1.37 N/mm2 Safe
VOLTAS

Check for Oneway shear Check for sliding


'd' at critical section 295 285 mm
pt.at critical section 0.21 0.22 % Coefficient of friction = 0.4
S.F., V 37 45 kN per m Total downward force = 454 kN
Factored SF 56 68 kN per m Resistace force to sliding = 182 kN
tv 0.19 0.24 N/mm 2
Sliding force = 29 kN
tc 0.35 0.35 N/mm 2
Factor of safety = 6 >1.55 Safe
Safe Safe

Check for overturning


Along X-axis M Along z-axis

Overturning moment (Mz) = 1 kNm Overturning moment (Mx) = 2 kNm

Column reaction = 303.39 KN Column reaction = 303 KN

P = 454 KN P = 454 KN
Restoring Moment = 454 kNm P Restoring Moment = 454 kNm
L/2
Restoring Moment Restoring Moment
F.O.S. = F.O.S. =
Overturning moment Overturning moment
= 552 >1.55 Safe = 289 >1.55 Safe

Check for bearing


Maxm column reaction, Fy = 303 kN
Bearing stress = 2.70 N/mm^2
Allowable bearing stress(0.45fck) = 13.50 N/mm^2
Safe

Design Summary of Tapered footing


Founding Level = 2.00 m
Breadth = 2.00 m
Width = 2.00 m
Footing Size
T1 T2
Thickness =
350 mm 350 mm
Reinforcement at bottom layer
VOLTAS

in X direction = 10 dia @ 125 c/c


in Z Direction = 10 dia @ 125 c/c