EX DELTA II 渦流流量計插入型電池動能 (英) 型錄

This document describes a battery-powered vortex flowmeter that can measure the flow of gases, liquids, and steam. It has a wide measurement range and high accuracy. It requires no external power source as it is powered by internal lithium batteries that can last up to 7 years. It has a digital display that shows integrated and instantaneous flow readings and can be mounted up to 50 meters from dispersed sensors. It has an explosion-proof construction suitable for hazardous areas.

Uploaded by

Richard Xu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views12 pages

EX DELTA II 渦流流量計插入型電池動能 (英) 型錄

This document describes a battery-powered vortex flowmeter that can measure the flow of gases, liquids, and steam. It has a wide measurement range and high accuracy. It requires no external power source as it is powered by internal lithium batteries that can last up to 7 years. It has a digital display that shows integrated and instantaneous flow readings and can be mounted up to 50 meters from dispersed sensors. It has an explosion-proof construction suitable for hazardous areas.

Uploaded by

Richard Xu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Steam Liquid Gas

Excellent Vortex Flowmeter


INSERTION Type GENERAL SPECIFICATION
BATTERY POWERED EX DELTAⅡ GS.No.GBD607E−2
PAF5 TYPE
■ GENERAL
The battery-powered EX DELTA Ⅱ is a dedicated on site
monitor with a wide variety of applications as a universal
vortex flowmeter. It has been designed to be simple to use on
the built-in battery alone.
The display monitors integrated value or instantaneous flow
and is switchable externally. A remote display unit is also
available that allows the display to be installed up to 50m
away from several dispersed sensors. This flowmeter is in
preparation of a fixed type and a hot-tap type.

■ FEATURES
1. Offers high accuracy measurement over a wide flowrange.
2. Applicable for flow measurement of gas,liquid and steam.
3. The sensor, completely isolated from wetted parts, has along
service life.
Fixed Type Hot-tap Type
4. Absence of any moving parts means that dust and mist in the
medium being measured are less likely to pose a problem.
5. Battery powered, it requires no electrical installation from an
external power source. [Uses five 3.6V lithium-metal battery
packs. Good for 7 years on a 24 hours a day continuous 7. Water proof (IP65/67) and intrinsically safety (Ex d IIB+H2T4)
operation (model integral with preamplifier), or 4 years (model construction are the most suitable to local flow monitoring
with separately mounted preamplifier) basis. sensor.
6. Totalizer flow (cumulative and resettable) and instantaneous 8. The separate type is able to monitor up to 50m away from
flow rate can be monitored by digital display. several dispersed sensors.

■ GENERAL SPECIFICATIONS
● Transmitter
Item Description
Mounting Type Fixed Type Hot-tap Type
Nominal Size to be applied 200, 250, 300, 400, 500, 600, 800, 1000, 1500, 2000mm 400, 500, 600, 800, 1000, 1500, 2000mm
Nominal Size of the Probe 50mm
Mounting Flange 100mm (4″)
Pressure Rating JIS10K, ASME/JPI150
Nominal Size of Piping: D<500mm; 0.5D D=Inner Dia.of Piping (mm)
Standard Insertion Depth
D≥500mm; 0.2D
Liquids (Water. Hot Water. Chemical Liquids)
Fluid to be Metered
Gases (Oxygen. Nitrogen. Carbon Dioxide. Compressed Air. etc.)
Steam (Saturated Steam. Super Heated Steam)
Flow range See flow range table P3, P4, P5
Air (Atm. press.): 12 to 50m/s
Velocity Range
Water: 0.6 to 6m/s
Operating Tem. Range (※1) −10 to +300℃
Maximum Operating Pres (※2) Depends on flange rating
Accuracy Within ±2% of FS
Meter Body SUS304
Materials
Bluff Body SUS304
Installation Horizontal or Vertical Horizontal
※1:Operating temperature range depends on condition of the fluid to be measured.
※2:Accuracy shall be guaranteed only for the specified actual nominal size.

http://www.oval.co.jp/english

Head Office (Tokyo): Tel. +81 3-3360-5121 Fax. +81 3-3365-8605


International Sales Division Email: [email protected]
Overseas Branch Offices: Beijing, Seoul, Singapore, Taipei
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

● Transmitter specifications
Item Description
Flowmeter integral type
Mounting
Separated type (2B (50A) pipe stand), Distance between detector and transmitter: Maximum 50 m
EMC EN 61326-1; FCC 47 CFR part 15 (applicable to integral type only)
Directives and Standards
RoHS EN 50581
Flameproof configuration
Explosionproof configuration Meter integral type: detector for separated type: Ex d IIB + H2T4
Transmitter for separated type (single): Ex d IIC T6 Gb
Waterproof configuration JIS C 0920 (IEC IP66/67), Seal: silicon
Explosionproof: −20 to + 40 ℃, 50 ℃, 60 ℃ (see explosionproof specifications (integral and separated types))
Ambient Temperature
Non-explosionproof: −40 to + 70 ℃
Ambient Humidity 5 to 100% RH. There should be no dew condensation in the housing.
Body Material Aluminum die-cast
Housing Painting Polyurethane coating (ISO 12944 compliance with category C4-M)
Painting Body: Munsell 10B8/4, Cover (front and back): Munsell 2.5PB4/10
Size: upper row 10.5 mm, lower row 7 mm, display rotation by an optical switch
(1) Resettable counter in 8 digits, (7 digits for integers + decimal)
(2) Totalizing counter in 8 digits
Display (3) Instantaneous flow rate (selectable from /day, /h, /min, /sec)
(4) Instantaneous flow rate bar graph
Low battery alarm ( ), switch operation ( ), alarms, key lock ( ), with back light

Dedicated battery: 3.6 V lithium-metal battery TL-5930/F made by TADIRAN


Transmitter integral type: 24h 7 years continuous
Power Supply
Transmitter separated type: 24h 4 years continuous
The battery life varies according to the setting, configuration and operating environment.
Dimensions W112×H133×D148mm (excluding protrusions)
All settings are saved in EEPROM. For each total back up. Data retention: 10 years or more. Parameter settings can be saved with a
Data Protection
password.
Weight Approx. 1.9 kg (including pressure-proof packing: 2.0 kg)
Wire connection port: M25 female screws
Transmission distance: maximum 50 m
Cable: 1.25mm2 or more, 3 core shielded wire, finished outer diameter: Non-explosionproof: φ13mm or less
Connection Explosionproof: φ8.5 to 11mm
(For separated type only) Connection terminal block: cross recessed machine screws M3
Pressure-tight packing:
• Transmitter side: KXB-25, 16 ORES or ORE
• Detector side: KXY-16 (common to PA25)

■ EXPLOSIONPROOF TEMPERATURE SPECIFICATIONS (INTEGRAL TYPE)


Ambient temperature Explosionproof temperature
Sensor type Explosionproof configuration
Measured fluid temperature class

−20℃ to +60℃
Insertion type sensor Ex d ⅡB+H2T4 T4
−196℃ to +130℃

■ EXPLOSIONPROOF TEMPERATURE SPECIFICATIONS (SEPARATED TYPE)


Ambient temperature Explosionproof temperature
Sensor type Explosionproof configuration
Measured fluid temperature class

Common to all sensors −20℃ to +55℃


Ex d ⅡC T6 Gb T6
Transmitter for separated type —

−20℃ to +60℃
Insertion type sensor Ex d ⅡB+H2T4 T4
−196℃ to +130℃

2
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

● Ambient Temperature Range ● Nominal Meter Factor


If the fluid temperature exceed 125°C, the allowable ambient Nominal Size of Nominal Meter
Piping mm (inch) Factor L/p
temperature range reduces as shown in the diagram below. 200 (8) 2.42
250 (10) 3.89
300 (12) 5.75
60 400 (16) 10.7
500 (20) 18.9
40
Ambient Temp. (℃)

600 (24) 27.7


20 800 (30) 49.2

0 1000 (40) 76.9


1500 (60) 173
−20
−10 50 100 150 200 250 300 2000 (80) 309
0 125
Fluid Temperature (℃)

■ FLOW RANGE
Table A, B, C, E are given value calculated from a nominal bore size. In order to determine flow range for actual piping bore
size, correction should be made according to the following equation.

Q = Q0 × (D/D0)2.........[A]
Q : Flow rate based on actual bore size. D : Actual bore size.
Q0: Flow rate based on nominal bore size. D0: Nominal bore size.

● Flow Range for Liquid in General


Select the minimum flow rate from Table A (based on specific gravity) or Table B (based on viscosity), whichever is greater.

Table A: Calculated value from specific gravity Unit: m3/h


Minimum Flow Rate
Sp.Gr.
0.5 0.6 0.7 0.8 0.9 1.0 1.1 1,2 Maximum
Nominal Size Veloci
ty (m/s
mm (inch) ) 0.90 0.82 0.76 0.71 0.67 0.64 0.61 0.58 6
200 ( 8˝) 102 93 86 80 76 72 69 66 678
250 (10˝) 158 145 134 125 118 112 107 102 1060
300 (12˝) 228 208 193 180 170 161 154 147 1520
400 (16˝) 405 370 342 320 302 287 273 262 2710
500 (20˝) 633 578 535 500 472 447 427 409 4240
600 (24˝) 911 831 770 720 679 644 614 588 6100
800 (32˝) 1620 1480 1370 1280 1210 1150 1100 1050 10800
1000 (40˝) 2530 2310 2140 2000 1890 1790 1710 1640 16900
1500 (60˝) 5690 5200 4810 4500 4250 4030 3840 3680 38100
2000 (80˝) 10200 9240 8550 8000 7540 7160 6820 6530 67800

Table B: Calculated value from viscosity Unit: m3/h


Kinematic Minimum Flow Rate
Viscosity (mm 2
Nominal Size Velocity
/s ) 1 2 3 5 10 15 20 25 30 40
(m/s)
mm (inch) 0.13 0.26 0.39 0.65 1.30 1.95 2.60 3.25 3.90 5.20
200 ( 8˝) 45 74 147 221 294 368 441 589
250 (10˝) 69 115 230 345 460 575 690 919
300 (12˝) 100 166 331 497 662 827 993 1330
400 (16˝) 177 294 589 883 1180 1470 1770 2360
500 (20˝) 276 460 919 1380 1840 2300 2760 3680
600 (24˝) 397 662 1330 1990 2650 3310 3970 5300
800 (32˝) 706 1180 2360 3530 4710 5890 7060 9410
1000 (40˝) 1110 1840 3680 5520 7360 9190 11100 14700
1500 (60˝) 2490 4140 8270 12400 16600 20700 24900 33100
2000 (80˝) 4410 7360 14700 22100 29400 3 6800 44100 58900
•In the shadowed area , determine on the basis of specific gravity (Table A).

3
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

● Flow Range for General Gases


In this table, flow rates are specified in [actual] base.
Therefore, in case of [normal] base, make it sure to convert the flow rate to [actual] condition and determine the flow
range and the nominal diameter based on this table.
Minimum Flow Rate (m3/h) Maximum Flow
Density kg 3
/m 0.38 0.7 1.2 2.0 3.6 6 11 19 34 (60) Rate (m3/h)
Nominal Size Velocit
y m/s
mm (inch) 20.3 15.0 11.8 10.0 8.2 6.9 5.7 4.7 3.9 3.2 50
200 ( 8’’) 2300 1690 1330 1130 923 778 636 530 437 362 5650
250 (10’’) 3590 2640 2080 1760 1450 1220 994 828 682 565 8830
300 (12’’) 5160 3810 3000 2530 2080 1750 1430 1200 982 813 12700
400 (16’’) 9180 6760 5330 4490 3690 3120 2550 2120 1750 1450 22600
Table C

500 (20’’) 14400 10600 8320 7020 5770 4870 3980 3320 2730 2260 35300
600 (24’’) 20700 15200 12000 10100 8310 7010 5730 4770 3930 3250 50800
800 (32’’) 36700 27100 21300 18000 14800 12500 10200 8480 6990 5780 90400
1000 (40˝) 57400 42300 33300 28100 23100 19500 15900 13300 10900 9030 141000
1500 (60˝) 129000 95100 74900 63200 51900 43800 35800 29800 24600 20400 318000
2000 (80˝) 230000 169000 133000 113000 92300 77800 63600 53000 43700 36200 565000
(Ref.) Viscosity
Type of Gases Density kg/m3 Gas Pressure (MPa (gauge)) at 20°C
of Gas
Acetylene 1.175 — — 0 0.08 0.23 0.55 0.9 1.65 — — 0.00943 (mPa·s)
Argon 1.785 — — — 0.02 0.12 0.26 0.55 1.05 2 — 0.0209
Ammonia 0.771 — 0 0.07 0.21 0.42 0.75 1.45 — — — 0.0092
Carbon Monoxide 1.250 — — 0 0.07 0.21 0.42 0.85 1.55 — — 0.0166
Ethane 1.357 — — 0 0.06 0.18 0.37 0.8 1.4 — — 0.0085
Ethylene 1.264 — — 0 0.07 0.21 0.42 0.85 1.55 — — 0.0097
Air 1.293 — — 0 0.07 0.2 0.4 0.85 1.5 — — 0.017
Table D

Oxygen 1.429 — — 0 0.05 0.1. 0.35 0.75 1.35 — — 0.0192


Hydrogen 0.0899 0.35 0.73 1.33 — — — — — — — 0.0084
Carbon Dioxide 1.977 — — — 0.01 0.1 0.23 0.5 0.95 1.7 — 0.0138
Nitrogen 1.251 — — — 0.07 0.21 0.42 0.85 1.55 — — 0.0166
City Gas 0.802 — 0 0.06 0.17 0.38 0.7 1.4 — — — 0.01
Natural Gas 0.828 — 0 0.06 0.16 0.37 0.68 1.35 — — — 0.0107
Freon-12 5.533 — — — — 0 0.02 0.12 0.27 0.56 1.1 0.0127
Propane 2.020 — — — 0.01 0.09 0.22 0.49 0.9 1.7 — 0.0075
Butane 2.703 — — — 0 0.04 0.14 0.34 0.65 1.2 — 0.0069
Methane 0.717 — 0 0.08 0.2 0.44 0.8 1.55 — — — 0.0103

●How to Determine the Minimum Flow Rate


Find a value D, follow the same column upwards and find a
value intersecting the desired diameter in Table C for the
minimum flow rate.
Example :
Find the minimum flow rate where fluid: air, temp.: 20°C, It can also be determined by calculating the actual density.
pressure: 0.5MPa (gauge), and actual bore size: 477.8mm. Actual density of air at 20°C and 0.5MPa is
Minimum flow rates at 0.4MPa and 0.85MPa of air with
respect to a bore of 500mm in Table D are 4870 m3/h and 273.15 0.101325+0.5
= 1.293 × × 7.15 kg/m 3
273.15+20 0.101325
3980 m3/h, respectively, from Table C. The minimum flow
rate at 0.5MPa can therefore be determined by proportion From Table C, the minimum flow rate at a density of
and formula [A] as follows: 6kg/m3 and bore of 500 mm is 4870 m3/h; at a density of

( 477.8
500 )
11kg/m3, it should be 3980 m3/h. The minimum flow rate at
0.85–0.5 (4870–3980)
Q mm ={3980 + }
2
× a density of 7.15kg/m3 and bore of 477.8mm therefore can be
0.85–0.4
found by proportion and formula [A] as follows:
4300m3/h

Q min ={3980 +
11–7.15
11–6
+ (4870-3980)}× (477.8
500 )
2

4300 m3/h

4
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

● Flow Range for Saturated Steam


Table E Unit: t/h
N.B.S *
Flo
200 (8˝ ) 250 (10˝ ) 300 (12˝ ) 400 (16˝ ) 500 (20˝ ) 600 (24˝ ) 800 (32˝ )
1000 (40˝ ) 1500 (60˝ ) 2000 (80˝ ) Temp. Density
Ra w
Press. te
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max °C kg/m3
MPa(gauge)
0.049 1.32 4.89 2.06 7.64 2.96 11.0 5.26 19.5 8.22 30.5 11.9 44.0 21.1 78.2 32.9 122 74.0 275 132 489 111.4 0.8653
0.098 1.50 6.37 2.35 9.94 3.38 14.3 6.00 25.4 9.38 39.7 13.5 57.3 24.0 101 37.5 159 87.4 358 150 636 120.1 1.126
0.196 1.97 9.26 3.07 14.4 4.42 20.8 7.86 37.0 12.3 57.8 17.7 83.3 31.5 148 49.2 231 111 521 197 926 133.3 1.638
0.294 2.35 12.1 3.67 18.9 5.29 27.2 9.39 48.4 14.7 75.6 21.2 108 37.6 193 58.7 302 132 680 235 1210 143.2 2.140
0.392 2.70 14.9 4.22 23.2 6.07 33.5 10.8 59.6 16.9 93.1 24.3 134 43.2 238 67.5 372 152 838 270 1490 151.4 2.635
0.490 3.03 17.6 4.73 27.6 6.81 39.7 12.1 70.7 18.9 110 27.2 159 48.4 282 75.6 442 170 994 303 1760 158.3 3.127
0.588 3.33 20.4 5.21 31.9 7.50 45.9 13.4 81.7 20.9 127 30.0 183 53.3 327 83.3 511 188 1140 333 2040 164.4 3.615
0.686 3.62 23.1 5.66 36.2 8.15 52.1 14.5 92.7 22.7 144 32.6 208 58.0 370 90.6 579 204 1300 362 2310 169.8 4.099
0.785 3.90 25.9 6.10 40.4 8.78 58.2 15.6 103 24.4 161 35.1 233 62.4 414 97.5 647 220 1450 390 2590 174.7 4.581
0.883 4.17 28.6 6.52 44.7 9.38 64.4 16.7 114 26.1 178 37.6 257 66.7 458 105 715 235 1610 417 2860 179.2 5.064
0.981 4.44 31.4 6.93 49.0 9.98 70.6 17.8 125 27.7 196 39.9 282 71.0 502 111 785 250 1760 444 3140 183.3 5.553
1.08 4.69 34.1 7.32 53.3 10.6 76.7 18.8 136 29.3 213 42.2 307 75.0 545 118 852 264 1910 469 3410 187.2 6.033
1.18 4.93 36.8 7.70 57.5 11.1 82.8 19.8 147 30.8 230 44.4 331 78.9 588 124 920 278 2070 493 3680 190.8 6.509
*N.B.S.=Nominal Size

● Flow Range for Superheated Steam


The flow range for superheated steam is determined by first finding the correction factors “a’’ and “b’’ for the minimum flow
rate and maximum flow rates from the table below and then multiplying the applicable connection diameter and pressure
readings in the flow range table of saturated steam by those correction factors.

Table F:

Fig. 1 Minimum flow rate correction factor Fig. 2 Maximum flow rate correction factor
1.00 1.00

0.90 0.90
4MPa
3MPa
2MPa 4MPa
0.80 1.5MPa 0.80 3MPa
1MPa 2MPa
0.6MPa 1.5MPa
Correction Factor

0.4MPa 1MPa
Correction Factor

0.70 0.2MPa 0.70 0.6MPa


0.1MPa 0.4MPa
0.2MPa
0.1MPa
0.60 0.60

0.50 0.50
100 150 200 250 300 100 150 200 250 300
Temp. of steam (℃) Temp. of steam (℃)

Example: Minimum flow rate


Measurement of super heated steam of pressure 0.1MPa
(gauge) and temperature 160°C in actual bore size
Q min = 9.38 × 0.93 × ( 477.8
500 )
2
8 t/h

477.8mm.
Maximum flow rate

( 477.8
500 )
From table E, minimum flow rate and maximum flow rate 2
for 0.1MPa steam with nominal bore size 500mm are Q max = 3.97 × 0.9 × 32 t/h
determined as 9.38t/h and 39.7t/h.
Correction factor “a” is determined as 0.93 from Fig. 1 and
Correction factor “b” is determined as 0.9 from Fig. 2 and
consulting from Table E and formula [A].

5
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

■ PRESSURE LOSS

● Liquid Service
ρ
ΔP= C×5 300
10
ΔP=Pressure loss (kPa)

m
ρ=Density (kg/m3)

0m
C =Pressure loss coefficient 100

m
20

0m

m
0m
25
50

m
30

0m

m
40

m
0m
0m

m
50

mm
60

0m
80

00

mm
10
10

mm
00
Pressure loss coefficient C

15

00
20
5

0.5

0.1
100 200 300 500 1000 2000 5000 2X104 5X104 105
3000 104 3X104
Flow rate (m3/h)

● Gas, Steam Service


30
ρ
ΔP= C×
100 20

ΔP=Pressure loss (kPa)


m

10
0m

ρ=Density (kg/m3)
mm
20

C =Pressure loss coefficient


m
0
0m

5
25

m
30

0m

m
40

0m

m
0m
50

m
mm
60

0m
00
80
Pressure loss coefficient C

1
mm
10

m
00

m
15

00

0.5
20

0.1

0.05

0.01
500 1000 5000 104 5? 104 105 4? 105

Flow rate (m3/h)

6
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

■ OUTLINE DIMENSIONS (Unit: mm)

● Fixed Type ● Fixed Type


Transmitter: Integral type Transmitter: Separate type
Nominal Size to be applied: 200 to 1300mm Nominal Size to be applied: 200 to 1300mm
(In case of bore size more than 1300 mm, consult factory.) (In case of bore size more than 1300 mm, consult factory.)
Ln: Height of mounting neck (std. 100 mm) Ln: Height of mounting neck (std. 100 mm)
Y : Length of insertion Y : Length of insertion
(Standard) Nominal size < 500 mm; 0.5×D (Standard) Nominal size < 500 mm; 0.5×D
Nominal size ≥ 500 mm; 0.2×D Nominal size ≥ 500 mm; 0.2×D
D = Inner dia, of piping D = Inner dia, of piping

112 103 45 44 60 55 41

φ88
φ110

L3≒634−Ln−Y

L3≒634−Ln−Y
Mounting
Mounting
flange
flange
680

673
Ln (100)

Ln (100)

Inner dia.
of piping Inner dia.
of piping
Y

Flow
φ57

Flow
φ57

25
Probe 25
76 Probe
76

● Display screen ● Separate Type transmitter

115

3 148 112

1
TOTAL (Resettable)

Instant flow rate/TOTAL 2


133
118

(Totalizing counter)

6 7
5 3
PAF5 transmitter
72

45

NO. Name
1 LCD display
2 Optical switch
3 GND terminal M4 screw
4 M25 Pressure-tight packing ※
5 Mounting bracket
6 Model code label
Explosionproof label
7
(opposite side surface)
※ In case of non-explosionproof option.

7
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

■ OUTLINE DIMENSIONS (Unit: mm)

● Hot-tap Type
Nominal Size to be applied: 400 to 2000mm

Stroke: Ls
φ355 (Ls=Ln+Y+298)

Handle

222

989
56
56

2110
400

Vent valve

Shut off valve

Face to face distance


Lv

of shut off valve: Lv


Mounting flange (Std. 229)
16

Mounting Neck
Ln

Height: Ln
(Std. 229)
Inner dia. of piping
Insertion Length: Y
Y

(0.2D Approx. or 0.5D Approx.)


Flow
φ57

46.5

76

● Mounting Direction of Transducer

8
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

■ INSTALLATION CONDITIONS
1. TYPICAL PIPING INSTRUCTIONS
It is generally required that the flow pattern of a fluid flowing in and out of an vortex flowmeter be as uniform as possible for accurate
metering performance. For this, the standard piping instructions are shown in the following table.
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant).
Straight Pipe Length
No. Piping Arrangement (L) Remarks
D: nominal diameter
L
8D For Honey Vanes L, consult OVAL.
Flow
OVAL's flow- Honey Vane L
1
straightener L
Refer to
12D
Flow GS/GCF001. (Applicable to meter size up to 24")
Flow Straightener
L
2 Reducer 15D Minimum A concentric reducer is upstream of the meter.
Flow

L
23D Minimum An elbow is upstream of the meter.
Flow

L
3 Elbow 25D Minimum Two elbows are upstream of the meter.
Flow

L
40D Minimum Two elbows are vertically upstream of the meter.
Flow

Fully Open L
Fully open
4 15D Minimum A full-open gate valve is upstream of the meter.
gate valve
Flow
Partially L A partially open gate valve, sharp orifice or
Partially open Open
5 50D Minimum something that markedly disturbs the flow pattern is
gate valve
Flow upstream of the meter.
※: "D" denotes pipeline diameter, not probe bore.
※: A short pipe section, 5D or longer is provided downsteam of the meter.
※: For pressure detection, provide the probe downstream of the flowmeter (see figure below). To avoid disturbances in the flow, temperature detection should be made downstream of
the flowmeter and, at the same time, upstream of the control valve.

● Non-full pipe
The fluid cannot be measured properly if there is an air space in
Gauge Tap the pipe. Make sure to confirm the pipe insdie is filled up with the
fluid to be measured.
2 to 7D In case of piping condition that frequently causes non-full status,
install an air release valve, for example.
● Work stage and lifting gear
Set up the work stage for maintenance and inspection.
D=Nominal size In case of hot tap type, use of lifting gear is recommended for
smooth installation.
● Pulsation
● Mounting Neck: Installing this flowmeter in a line where a roots-blower, compressor,
etc. that produce pulsating pressures are used as blowers could
Dimension of Mounting Neck subject the meter to the effects of pulsation.
If such is the case, consult factory.
Mounting flange 4″ JIS 10K The value of allowable fluctuating pressure shall be given according
φd to the following equation.
Main pipe N < 7.2ρV2 (Pa)
Ln where N: Fluctuating press. (Pa)
ρ: Density of liquid to be measured (kg/m3)
V : Minimum velocity (m/s)
● Thermal Insulation
If it is desired to thermally insulate the pipe line, simple laggings
(without mortar finished) are suggested to facilitate servicing. This
Ln: Hight of mounting neck 100mm (Std.) arrangement will permit taking off flowmeter connecting bolts
φd: Inner dia. of mountig neck φ100mm minimum (Std. 4″ sch40)
(Note) Pay particular attention for alignment of bolting
without destroying the lagging.
holes in the flange as shown in the above.

9
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

■ PRODUCT CODE EXPLANATION

Ex-proof temp. class Regulations


Explosionproof Transmitter
Process connection Transmitter configuration
Major Parts Material Display
Temp. category Output
Fluid category Communication Protcol
Probe Nominal Size Version code
Model Special
①②③④⑤⑥−⑧⑨⑩⑪⑫−⑭⑮⑯−⑱⑲⑳ − / / / Additional code

Main code

● Main code
① ② ③ Model ⑰ —
V X S EX DELTA Ⅱ Insertion Type Fixed Type ⑱ Transmitter
V X H EX DELTA Ⅱ Insertion Type Hot-tap Type F PAF5 Battery drive, no output signal
④ ⑤ ⑥ Probe Nominal Size ⑲ Transmitter configuration
0 5 0 50mm (2") 1 Integrally mounted
⑦ — 2 Separately mounted ※3
⑧ Fluid category ⑳ Display
L Liquid 1 w/Totalizer · digital indicator
G Gas  Output
S Saturated Steam Select G:Gas if specifying temperature, viscosity, and density. N No external output
K Superheated Steam Select G:Gas if specifying viscosity and density.  Communication protocol
⑨ Temp. category N Non
2 Standard (180℃ and lower)  Version code
3 High temp. (300℃ and lower) C Version: C
⑩ Major Parts Material  —
D SUS304 equivalent  Special
Z Special 0 Standard
⑪ ⑫ Process connection ※1 Z Special (special inner diameter, face-to-face dimension, etc.)
J 1 JIS10K RF (100mm) ※2
J 2 JIS20K RF (100mm) (Designed on PO issued)
J 3 JIS30K RF (100mm) (Designed on PO issued)
P 1 JPI150 RF (4″) ※2
P 3 JPI300 RF (4″) (Designed on PO issued)
A 1 ASME150 RF (4″) ※2
A 3 ASME300 RF (4″) (Designed on PO issued)
Z 9 Special
⑬ —
⑭ Explosionproof
0 Non-explosionproof
1 TIIS (PAF5)
⑮ Ex-proof temp. class
0 Non-explosionproof
4 Temp. class: T4
⑯ Regulations
0 Standard
High Pressure Gas Safety Act ※w/Material test certificate
G
(Approved product) (Designed on PO issued)
High Pressure Gas Safety Act ※w/Material test certificate
H
(Individual test) (Designed on PO issued)
High Pressure Gas Safety Act ※w/Material test certificate
J
(Completion inspection) (Designed on PO issued)
Gas Business Act ※w/Material test certificate
L
(Subject to specific welding procedure) (Designed on PO issued)
※w/Material test certificate
M Gas Business Act
(Designed on PO issued)
Electricity Business Act ※w/Material test certificate
Q
(Subject to specific welding procedure) (Designed on PO issued)
※w/Material test certificate
R Electricity Business Act
(Designed on PO issued)
※w/Material test certificate
T Fire Service Act
(Designed on PO issued)
F w/Material test certificate
※1: ASME Flange serration complies with ASME B 16.5−2003.
※2: Flange sizes other than 100mm (4") are special specification.
Hot-tap type is designed on PO issued.
※3: In separately mounted configuration, explosionproof symbol for transmitter is always Ex d IIC T6 Gb, regardless of sensor specification.

10
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

■ PRODUCT CODE EXPLANATION

Ex-proof temp. class Regulations


Explosionproof Transmitter
Process connection Transmitter configuration
Major Parts Material Display
Temp. category Output
Fluid category Communication Protcol
Probe Nominal Size Version code
Model Special
①②③④⑤⑥−⑧⑨⑩⑪⑫−⑭⑮⑯−⑱⑲⑳ − / / / Additional code

Main code

● Additional code
Header's Nominal Size ※Must choose Document
P S A 200mm Fixed Type D S J SPEC. & DWG (Approval Drawing) (Japanese)
P S B 250mm Fixed Type D S E SPEC. & DWG (Approval Drawing) (English)
P S C 300mm Fixed Type D R 0 Re-submission of SPEC. & DWG
P S D 350mm Fixed Type D C J Final DWG (Japanese)
P S E 400mm Fixed Type, Hot-tap Type D C E Final DWG (English)
D P J Strength Calculation sheet (Japanese)
P S F 450mm Fixed Type, Hot-tap Type
D P E Strength Calculation sheet (English) Unavailable for the Japan law compliant
P S G 500mm Fixed Type, Hot-tap Type
S T J Pressure test report (Japanese)
P S H 550mm Fixed Type, Hot-tap Type
S T E Pressure test report (English)
P S J 600mm Fixed Type, Hot-tap Type
S A J Airtight test report (Japanese)
P S K 650mm Fixed Type, Hot-tap Type
S A E Airtight test report (English)
P S L 700mm Fixed Type, Hot-tap Type D D J Dimensional check record (Japanese)
P S M 750mm Fixed Type, Hot-tap Type D D E Dimensional check record (English)
P S N 800mm Fixed Type, Hot-tap Type S P J Penetrant test report (Japanese) Welded part of pressure resistant vessel ※1
P S P 850mm Fixed Type, Hot-tap Type S P E Penetrant test report (English) Welded part of pressure resistant vessel ※1
P S Q 900mm Fixed Type, Hot-tap Type S M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vessel ※1
P S R 950mm Fixed Type, Hot-tap Type S M E Magnetic particle inspection (English) Welded part of pressure resistant vessel ※1
P S S 1000mm Fixed Type, Hot-tap Type S R J Radiographic inspection report (Japanese) Welded part of pressure resistant vessel ※1
P S T 1050 to 1300mm Fixed Type S R E Radiographic inspection report (English) Welded part of pressure resistant vessel ※1
P S 9 Special S U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vessel ※1
Mounting Neck ※Must choose S U E Ultrasonic inspection (English) Welded part of pressure resistant vessel ※1
P N 1 Height of mounting neck: 100mm; nozzle nominal size (connecting flange size): 100mm (4") as standard S X J PMI test report (Japanese) ※1
S X E PMI test report (English) ※1
P N 2 Height of mounting neck: 100mm; nozzle nominal size (connecting flange size): special
S S J Impact test report (Japanese) ※1
P N 3 Height of mounting neck: special; nozzle nominal size (connecting flange size): 100mm (4")
S S E Impact test report (English) ※1
P N 4 Height of mounting neck: special; nozzle nominal size (connecting flange size): special
D Y J WPS/PQR (Japanese)
Pressure-tight packing gland ※Must choose
D Y E WPS/PQR (English)
J F 0 Non
D 9 J Photo (Japanese)
J F 1 Cable O.D.: φ8.5 to 10.0 D 9 E Photo (English)
J F 2 Cable O.D.: φ10.1 to 11.0 D T J Inspection procedure (Japanese)
Category of High Pressure Gas D T E Inspection procedure (English)
H P 0 Other than High Pressure Gas Witness Test
H P 1 Toxic gas and flammable gas V 1 0 Required
H P 2 Toxic gas
H P 3 Flammable gas
H P 4 Other than toxic or flammable gas Conduit
connections
Accuracy
F 2 0 ±2.00% FS FS: rated maximum flow rate
Special test (instrumental error)
A 0 1 Dry calibration (w/Certificate) Witnessed accuracy test not applicable
Flow direction ※Must choose (See figures on the right.)
F R 0 Right to left
F L 0 Left to right
F U 0 Top to Bottom: LCD type A Separate type: electric conduit at the bottom
F D 0 Bottom to Top: LCD type A Separate type: electric conduit at the bottom
F U 1 Top to Bottom: LCD type B Separate type: electric conduit at the top (indoor use only)
F D 1 Bottom to Top: LCD type B Separate type: electric conduit at the top (indoor use only) Flow Flow
Designated special paint on body [Integral type] [Separated type]
B C 0 Corrosion proof Standard mounting position for the integral and the separated types
B A 0 Salinity and acid tolerance 120℃ and lower
B X 0 Customer designation Special
Cleansing
T W 0 Oil free and Water free treatment Hot-tap Type is special
Flow
Flow

T W 1 Oil free and Water free treatment equivalent


※1: Need not choose the item when required to implement in Japan law and regulation.
Only for items other than the legal requirement, customer can choose as special
requirement.
Integral type A Integral type B

Figure: Flow and LCD directions (both type A and B can be installed outdoors)

11
INSERTION TYPE BATTERY POWERED EX DELTA Ⅱ PAF5 TYPE GBD607E-2

■ PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE.


Fill in the blanks. Tick the boxes □ that apply.

Item Description

1. Fluid to be metered

2. Flow Range Maximum Normal Minimum □ m3/h [normal] □ m3/h [actual] □ kg/h

3. Temperature range Maximum Normal Minimum ℃

4. Pressure range Maximum Normal Minimum □ MPa [gauge]

5. Density or Sp. Gr. Density □ kg/m [normal] , □ kg/m [actual]


3 3
Sp. Gr.

6. Viscosity □ mPa·s, □ mm2/s at ℃

7. Actual inner Dia. of


Nominal size mm Actual inner Dia mm
mainline pipe

8. Type of mounting □ Fixed Type □ Hot-tap Type

9. Flow straightening □ Required (straightener and down stream pipe)


device: □ Not required (Please prepare the straightening pipe of specific length, bore and sch. no.)

10. Compensation □ Temperature and Pressure □ Pressure □ Temperature


11. Compensation
Temp. to ℃, Pressure to □ MPa [gauge]
Range
12. Compensation Ref. Ref. temp. ℃ Press. ref. □ MPa [gauge]

13. Compression coefficient:


Z (service conditions) = Zo (standard conditions) =
(in case of gas measurement)

Type: □ Integral configuration, □ Separate configuration


14. Transmitter
Explosionproof configuration: □ Non-explosionproof, □ Intrinsically safe

15. Explosionproof □ Not requested


construction □ Requested

16. Miscellaneous

The specification as of August, 2019 is stated in this GS Sheet. Specifications and design are subject to change without notice.