UL Firestop Penetration Numbering System

This document provides information on the numbering system used for UL firestop penetration systems. The first alpha character indicates if the system protects penetrations through floors or walls. The second and third characters specify the floor or wall type. Numeric characters denote the penetrating item or grouping of items. Additional details on allowable penetrating items and their corresponding number ranges are also included.

Uploaded by

fazil yoosuf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views1 page

UL Firestop Penetration Numbering System

This document provides information on the numbering system used for UL firestop penetration systems. The first alpha character indicates if the system protects penetrations through floors or walls. The second and third characters specify the floor or wall type. Numeric characters denote the penetrating item or grouping of items. Additional details on allowable penetrating items and their corresponding number ranges are also included.

Uploaded by

fazil yoosuf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

UL FIRESTOP PENETRATION NUMBERING

(Tested to UL 1479, Inspect to ASTM E-2174, CCN XHEZ)

First Alpha Character


Letter Description
C Systems intended to protect penetrations through either floors or walls
F Systems intended to protect penetrations through floors
W Systems intended to protect penetrations through walls

Second and Third Alpha Characters


Letter Description
A Concrete floors with a minimum thickness less than or equal to 5 in
B Concrete floors with a minimum thickness greater than 5 in
C Framed floors
D Steel decks in marine vessels
E Floor-ceiling assemblies consisting of concrete with membrane protection
G Cross laminated timber (CLT) floor assembly
F, H - I Not used at present time
J Concrete or masonry walls with minimum thickness less than or equal to 8 in
K Concrete or masonry walls with a minimum thickness greater than 8 in
L Framed walls
M Bulkheads in marine vessels
N Composite panel walls
O Cross laminated timber (CLT) wall assembly
P-Z Not used at present time

Numeric Characters
Numeric Range Description
0000 – 0999, 01000, 01001, 01002 etc. No penetrating item
1000 – 1999, 11000, 11001, 11002 etc. Metallic pipe, conduit or tubing
2000 – 2999, 21000, 21001, 21002 etc. Nonmetallic pipe, conduit or tubing
3000 – 3999, 31000, 31001, 31002 etc. Electrical cables
4000 – 4999, 41000, 41001, 41002 etc. Cable trays with electrical cables
5000 – 5999, 51000, 51001, 51002 etc. Insulated pipes
6000 – 6999, 61000, 61001, 61002 etc. Misc. electrical penetrants such as busducts
7000 – 7999, 71000, 71001, 71002 etc. Misc. mechanical penetrants such as air ducts
8000 – 8999, 81000, 81001, 81002 etc. Groupings of penetrants including any
combination of items listed above
9000 – 9999, 91000, 91001, 91002 etc. Not used at present time