Zone CFM ........................... Peak zone sensible load Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ...................................................... 617.9 Tons Load occurs at .................................................... Jul 1500
Total coil load .................................................... 7414.2 MBH OA DB / WB ..................................................... 91.0 / 73.0 °F
Sensible coil load .............................................. 4335.1 MBH Entering DB / WB ............................................ 91.0 / 73.0 °F
Coil CFM at Jul 1500 .......................................... 73664 CFM Leaving DB / WB ............................................. 36.5 / 36.4 °F
Max block CFM at Jul 1600 ................................ 73896 CFM Coil ADP .................................................................... 30.4 °F
Sum of peak zone CFM ..................................... 70201 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.585 Resulting RH ................................................................ 26 %
ft²/Ton .................................................................. 122.8 Design supply temp. .................................................. 55.0 °F
BTU/(hr-ft²) ............................................................ 97.7 Zone T-stat Check .................................................. 2 of 4 OK
Water flow @ 10.0 °F rise ............................... 1483.75 gpm Max zone temperature deviation ................................. 1.9 °F
Actual max CFM at Jul 1600 .............................. 73896 CFM Fan motor BHP ...................................................... 550.00 BHP
Standard CFM .................................................... 73816 CFM Fan motor kW ........................................................ 410.13 kW
Actual max CFM/ft² ............................................... 0.97 CFM/ft²
31
Hourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Jaharis Center System
Project Name: Jaharis Center 12/28/2003
Prepared by: Reed Berinato 07:50PM