Transient Based Relays
Transient Based Relays
PAC.MARCH.2023
a Distinguished Member
not use speed for the sake of speed alone. of CIGRE, and a registered
-2000
It also uses speed to overcome problems professional engineer in the
and provide secure and dependable pro- province of Ontario. Bogdan
tection that is independent of the source -4000 has authored over 220
characteristics. technical papers and holds
Transient-based Protection History over 60 patents.
Transient-based protection responds to
300
short-lived features in the relay input cur-
Mangapathirao
rents and voltages. Fault transients are not 200
(Venkat) Mynam
powered by the sources present in the sys-
tem but by the energy stored in the system 100 received his MSEE from the
University of Idaho in 2003
components prior to the fault: transmis- 0
kV
PAC.MARCH.2023
transmission lines are as follows: Recently, we have introduced the and key relay bits for a line fault on a
Directional elements (TW32 and TW50 element as an offshoot of the 345 kV, 60 Hz line. The relay closed
TD32) for use in permissive pilot protection TW87 scheme in applications to a trip-rated output contact in 0.8 ms.
schemes lines terminating on transformers. The TW87 scheme tripped first (0.8
Underreaching distance elements When combined with the TD32 and ms) followed by the POTT scheme
(TW21 and TD21) TW32 elements, it allows sub-milli- (1.4 ms). Both of these schemes use a
Traveling-wave differential scheme second tripping without a protection direct fiber channel. During the 0.8 ms,
(TW87) channel. the line current did not change much.
Traveling-wave overcurrent element
When combined
(TW50)
In the late 1970s, Vitins, Chamia, and
3 Fault clearing time of 33 ms
Liberman proposed what is now known as
the TD32 directional element. The same re- 2000
with two-cycle searchers introduced the TD21 element for
direct tripping without the aid of a protec- 1000
tion channel.
breakers and
Their implementations (often mislabeled 0
as TW-based protection) used high-pass
filters to extract fault transients. The early
A
fast protection
implementations were restrained by the -1000
limitations of the technology available at the
channels, time (static relays). The original manufactur- -2000
ers did not follow through with new relays
transient-based when the technology improved. Nonethe-
less, a handful of utilities used these early
“traveling-wave” relays. After an initial pe-
relays clear the riod of fine tuning the filtering and settings,
they served with a good track record until 200
the last relays were decommissioned about
vast majority of a decade ago.
Also in the late 1970s, Takagi concep- 0
kV
PAC.MARCH.2023
PAC.MARCH.2023
relays have an outstanding security re- based line protection. The scheme is the remote line terminal and trips directly
cord in the field, already supported by extremely dependable and fast. The without the protection channel in 3 to 5
thousands of relay-years of service. TW32 element is moderately depend- ms. The TD21 element is designed to work
Performance able because of the poor frequency only in strong systems and is satisfactorily
Our to-date field experience with response of the present-day voltage dependable. In weak systems, such as when
the transient-based line relays leads us transformers. When the TW32 ele- only unconventional sources drive the fault
to the following observations (see Fig- ment asserts, however, it operates in current, the TD21 element does not operate
ures 3 through 6). 0.1 ms regardless of the fault and sys- by design and therefore is not a valid option
The TW87 scheme is extremely tem conditions. The TD32 element to address the wind-powered and inverter-
fast and trips on the order of 1 ms (short does all the heavy lifting and deliv- based source challenge
The faulted-phase identification logic
5 Fault clearing time of 25 ms performs exceptionally well, allowing for ex-
tremely fast single-pole tripping and reclos-
6000 ing. Identification of the faulted phase(s) in Xxxx protection
11
0
security that was required. The field experi-
-100 ence exceeded our expectations for depend-
-200 ability. The customary concerns about TWs
did not materialize. Only in a lab, faults hap-
-300 pen at the voltage zero-crossing. In real life,
-400 the insulation must be stressed with some
voltage before it breaks down. As a result,
TD32F all practical faults launch TWs. The TW87
PILOTRX scheme and the TW32 element may lose
POTT some dependability because of the poor fre-
TRIP quency response of the voltage and current
transformers and other factors related to ter-
0 ms 10 ms 20 ms 30 ms 40 ms mination impedances and overlap of TWs.
PAC.MARCH.2023
11
0
out-of-zone faults in the system.
Summary -100
Transient-based line protection is a
-200
valuable tool for solving challenges re-
lated to wind-powered generators and -300
inverter-based sources. Advancements in
electronic components, fiber communi-
cations, time synchronization, processing TD32F
power, and simulation tools allowed us to PILOTRX
design high-performance relays that have POTT
worked exceptionally well from day one. TRIP
Fault transients contain a wealth of infor-
mation. They are short lived, and protec- 0 ms 10 ms 20 ms 30 ms 40 ms
PAC.MARCH.2023