Dedicated Outdoor Air System (DOAS) Sizing Summary For VRF
Dedicated Outdoor Air System (DOAS) Sizing Summary For VRF
NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).
Cooling Heating
[kW] [kW]
Peak Coincident Indoor Unit Loads 53.3 3.0
Estimated Piping / Line Losses 0.0 0.0
Note: VRF piping / line losses are based on typical loss factors for this class of equipment. Actual line loss varies widely from one product to another.
Therefore, when selecting equipment it is critical to consult manufacturer's guidance to utilize actual line loss data.
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
V1A-FF-01 - Master Bed 1 4.2 Aug 1500 366 0.3 19.6 18.65
V1A-FF-05 - Bedroom 03 1 3.7 Jul 1500 325 0.2 14.4 22.60
V1A-FF-06 - Family Room 1 5.4 Sep 1400 475 0.4 21.7 21.90
V1A-FF-08 - Bedroom 01 1 3.9 Aug 1500 343 0.2 16.7 20.52
V1A-FF-09 - Bedroom 02 1 3.5 Jul 1500 310 0.2 14.4 21.52
V1A-GF-02 - Kitchen 1 4.6 Jul 1500 405 0.2 15.1 26.80
V1A-GF-03 - Living 1 10.5 Jul 1500 919 0.5 30.5 30.13
V1A-GF-04 - Dining 1 3.9 Aug 1500 340 0.1 17.1 19.86
V1A-GF-05 - Majlis 1 4.5 Aug 1500 397 0.3 17.8 22.30
V1A-SF-01 - Maid Room 1 3.8 Jul 1500 336 0.3 6.6 50.85
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
50
45
40
35
Load ( kW )
30
25
20
15
10
5
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for July
45000
40000
35000
30000
25000
W
20000
15000
10000
5000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day