Air-Conditioning Units and System
Air-Conditioning Units and System
To encourage sustainable development, many activities are underway as concerns both the
environmental policies of individual nations and international organisations (above all the
European Union), and specific research and development work.
Today, then, solutions to combat global warming and pollution, to live a sustainable
existence, to make our cities more liveable and our factories more efficient and virtuous all
exist: the technology is here.
CAREL has always developed and promoted evolved control systems, proposing innovative
solutions in the HVAC/R sector. These are our “high efficiency solutions”, a clear response for
environmental protection through optimised and integrated control systems, capable of
bringing significant energy savings and consequently reducing environmental impact.
These are new solutions for the market, yet the choices made are still in line with our
tradition: we have always invested in R&D, right since we first started business, and we
continued to do so despite the global recession.
These cutting-edge control solutions are now available, and their full potential is ready to
be exploited, to achieve an effective competitive advantage on the world scene and be
rewarded by the market.
Using CAREL “high efficiency solutions” today means doing something concrete to
contribute to protecting the environment. It means looking to the future with confidence.
Integrated solutions for high
efficiency units
Higher performance solutions for maximum seasonal
energy efficiency
With the European Energy Package, the EU has established targets to be met by 2020: 20%
reduction in carbon dioxide, a gas responsible for the greenhouse effect, 20% increase in
renewable sources, 20% increase in energy efficiency. The RES Directive (Renewable Energy
Sources) has defined binding national objectives for Member States.
Within this context, evaluation of the energy efficiency of air-conditioning and heating units
has evolved with the introduction of the Seasonal Performance Factor (SPF), which takes into
consideration different seasonal climatic conditions.
The new criteria for calculating efficiency require manufacturers to provide the average
seasonal performance coefficients for the units in specific reference conditions (Energy
Efficiency Ratio - EER): the factors that affect such calculations assume unit operation at part
load for a considerable amount of time. Integrated management of
To reach the predefined seasonal performance target requires the use of advanced control DC inverter compressors and
algorithms and cutting-edge technology to ensure effective control of the refrigerating unit the electronic expansion
at part loads.
valve ensures very high
Management of variable speed compressors with DC inverters, together with the use of
the electronic expansion valve in fact allows the widest heat output modulation capacity energy savings compared to a
currently available, maximising performance of the unit in response to the changing thermal traditional solution.
loads and climatic conditions throughout the year. The added possibility of exploiting serial
communication to control smart actuators (pumps, fans...) represents a further step forwards
in the development of more reliable and efficient units.
Applications 7
residential 9
air-conditioning in commercial applications 13
datacenters – precision air-conditioning 17
industrial processing 21
remote operation centre 25
Programmable controllers 29
pCO sistema 31
Unit and room terminals 39
1tool 47
Parametric controllers 49
µC sistema 51
e-dronic 55
EXV sistema 99
EXV sistema - electronic expansion valves and drivers 101
residential
pCO5+ pGD1
“pCOsistema”p.31 “Unit and room
terminals” p. 39
acqua Temperature-humidity probe th-Tune
“e-dronic” p. 55 “Sensors and protection devices” p. 67 “Unit and room terminals” p. 39
NTC probes DC inverter- power+ E2V smart NTC probes and transducers
“Sensors and “Speed controllers and “EXV sistema - electronic “Sensors and protection
protection devices” p. 67 inverters” p. 107 expansion valves and devices” p. 67
drivers” p. 101
residential
Solution for chillers/heat screw- Solution for roof-top units Solution for AHU
type pump The CAREL solution allows to manage the The CAREL application program CAREL
The CAREL solution has been developed temperature and humidity of the roof top for AHU allows adjustment of the main
around the new range of programmable unit with two circuits and 4 compressors. devices that contribute to the control of
controllers pCO5. Specific functions such as free cooling and temperature, humidity and air quality:
The application allows you to manage and free heating, optimise the operation of dampers, heat exchangers, humidifiers and
control air/water units or water/water units the unit, taking advantage of the outdoor fans. The functions are developed with
with screw-type compressors with stepless temperature while saving energy at the algorithms of the PID type, in this way the
or stepped splitters. same time. user is able to structure a fine adjustment
The maximum configuration includes a The maximum configuration includes 4 of the plant, for the various devices.
screw compressor for each circuit, up to 2 hermetic compressors (2 per circuit), 2 The application also offers maximum
circuits. resistors and an integrated or external adaptability to any type of AHU, the
The application allows the control of the humidifier . installer, in fact, can customise by changing
envelope of the main compressors on the The application also manages air quality the electrical wiring from the terminal
market (Bitzer, Refcomp and Hambell), and heat recovery. position of the inputs and outputs.
thereby ensuring the utmost reliability.
Air conditioning is one of the essential these air conditioners are equipped with
infrastructures for the operation of fans, cooling coils with direct expansion or
Information Technology equipment: chilled water, and often heater humidifiers
processing and storage devices produce to correct the temperature if it reaches a
heat which has to be removed to maintain minimum limit.
optimal operating conditions. Increasing The continuous development of
use of IT technologies in every activity technology and the constant search
has made the continuity of service for energy savings are reflected in an CAREL offers the most
imperative, often spoken of as “Mission evolution of air-conditioning solutions:
Critical” applications. The high power from monitoring the distribution of the complete and developed
installed, up to 2 kW/m2, also requires the air to the development of air conditioners
development of “Energy Saving” solutions. placed near heat sources, using motors range of solutions for
For the proper functioning of IT with permanent magnets for high air-conditioning control
equipment, the inlet air must be at a efficiency, the use of Air Handling Units
controlled temperature (typically between for freecooling, where possible and by in datacenters, a “Mission
22 and 27° C) so that the fans on the lowering the temperature with adiabatic
humidifiers (Evaporative Cooling).
Critical” application with
devices can cool the chips inside. Moisture
is also frequently controlled, since values Such a wide variety of configurations high heat disposal: flexible,
that are too low increase the probability of requires flexible control solutions, based
electrostatic discharge while any excessive on scalable, programmable controllers reliable, customisable
values accelerate corrosion or slow down and equipped with a full range of
and integrated systems
the performance processes of some accessories such as displays, sensors and
equipment. communications modules, integrated in to optimise efficiency by
The technological solution most widely a system that includes high-efficiency
used today is the so-called Computer devices such as the electronic expansion guaranteeing continuous
Room Air Conditioner (CRAC) or Close valve and drivers for brushless variable service and energy savings.
Control Units (CCU) which, installed on RPM compressors.
the perimeter, provide for cooling the air
in the room and any humidification or
dehumidification to maintain the set point;
pGDTouch pCO5+ Stand-alone speed regulators
“Unit and room “pCO sistema” p. 31 “Speed controllers and inverters” p. 107
terminals” p. 39
CRAC unit with direct expansion: power+: supply control unit CPY with integrated serial KUE
pCO5+ with valve driver The power + for handling BLDC variable The introduction of outside air and the
pCO5 + integrated two-pole driver displacement compressors represents an dehumidification produced by cooling
for an electronic expansion valve is an extremely advantageous solution for CRAC coils often requires humidification. The
ideal solution for Computing Centre air with direct expansion because it optimises KUE series of humidifiers with immersed
conditioners (CRAC units) with direct efficiency at part loads and controls the electrodes is the compact and reliable
expansion: the response speed and the CRAC supply temperature without the solution for air humidification inside
wide control range in this technology need for reheating. CRAC units. The CPY control provides
optimises superheat, keeping operating The possibility for modulation in this optimal management of the humidifier by
parameters stable under varying technology allows proportional sizing for optimising starts, transients and draining:
conditions, especially in the case of the units under normal operation with part integration with pCO5 via serial port
compressors with variable displacement loads, producing the maximum cooling means parameters can be displayed and
and multiple compressor circuits. The capacity only in a case of an anomaly set as part of control synergy.
integrated driver also allows advanced on one of the units or overheating,
control logic to optimise the transition representing a viable alternative for
and help to bring operating conditions redundancy.
within the parameters inside the envelope
defined by the manufacturer.
EXV technology is ideal in all contexts
where air-conditioning works year-round
since it makes the lowest condensing
pressure setting possible, with
considerable energy savings.
industrial processing
ChillBooster
Atomisers - evaporative
cooling
industrial processing
ChillBooster
ChillBooster is an adiabatic system that
uses air chillers and drycoolers, especially
in industrial applications where energy
savings become very high because
operation is continuous and loads are high.
ChillBooster atomises water into very fine
droplets that evaporate spontaneously,
cooling the air. The coil then comes
into contact with a stream of cooler air Temperature, pressure, and
PGD and pGD touch terminals and droplets, allowing more favourable
humidity sensors and combined
operating conditions.
Whether it involves a user interface of sensors
Additionally, the droplets that evaporate
a temperature controller or a chiller, or
from the surface of the fins actively Carel offers a complete range of sensors for
dryers for managing an entire multi-
contribute to increasing the cooling temperature, pressure and humidity.
hopper system, the series pGD and pGD
booster effect. Every single function, such as controlling
touch terminals offer a solution of high
This allows liquid coolers and condensers water or air temperature, finds a suitable
technological and aesthetic impact. This
to provide rated capacity even in periods response in the different versions available,
aspect is particularly important in industrial
of high temperatures that often coincide which are distinguished by their range
applications where ease of use for the end
with maximum load. All without expensive of measurement for the protection of
user is the decisive factor.
oversizing of systems. sensitive elements and the materials used
for the casing. There are also combined
temperature-pressure versions available.
25
remote control
maintenance
technician
energy
manager
call centre
operator
remote operation centre
pCO sistema
P+5* PCOX*
The pCO5+ controller offers specific new guarantee closing of the circuit when Compact programmable controller, just
functions for improving efficiency in no battery module was available, is no 6 DIN modules, high capacity in terms of
HVAC/R systems: longer needed; connectivity and integrated functions.
• all analogue input channels can be • more powerful and distributed control Compatible as regards both the hardware
configured as: thanks to 5 serial lines, allowing and software with the pCO family;
- digital input (voltage-free); management of smart actuators such consequently, it’s a versatile solution for all
- analogue output (PWM or 0 to 10 V); as drivers for DC inverter compressors, types of applications and requirements in
- wide selection of probes for different brushless fans (EC fans), centrifugal the HVAC/R sector.
applications (NTC, PTC, PT100, PT500, compressors, variable flow-rate pumps, There are two versions of pCO compact,
PT1000, 0 to 1 V, 0 to 5 V, 0 to 10 V, 0 to serial sensors, wireless sensors, heat which differ in terms of the number and
20 mA, 4 to 20 mA); meters, etc. type of inputs / outputs, so as to best
• integration of EVDEVO driver for control adapt to the needs of the application.
of electronic expansion valves with The new pCO5+ also guarantees perfect Possibility to interface with the most
ultracap technology, guaranteeing compatibility with the entire range of commonly-used BMS communication
stepper electronic expansion valves pCO3 and pCO5 controllers, both in terms protocols (BACnet, Modbus®, LonWorks
close in the event of power failures; of hardware (pin to pin compatible) and Modbus®, Konnex, …) by adding optional
• connectivity, providing more software, so as to protect and guarantee serial cards. pCO compact also has an
demanding designers with up to 5 serial CAREL customers’ investments. integrated, optically-isolated Fieldbus
lines, 3 of which always available and RS485 / tLAN port. It also comes with
configurable in terms of protocol (CAREL Technical specifications two USB ports (host and device), used
or Modbus®) and type (FieldBus or BMS), to upload and download the application
Power supply: 24 Vac, -15/10 % program and data logs via pendrive or
and 2 optional, again configurable in
50/60 Hz or 28 to 36 Vdc -20/10 %; direct connection to a PC.
terms of protocol (Modbus®, BACnet™,
Operating conditions: -40T70 °C, 90% RH The built-in user interface has a white
CAREL, CANbus, Konnex, LonWorks)
non-condensing positive LCD, with 132x64 dot resolution,
and physical support (RS485, Ethernet,
Degree of protection: allowing a high degree of customisation,
Can, Konnex, FTT-10). Versions are
• IP20; plus a six-button membrane keypad.
available with USB “Host” and “Device”
• front IP40
ports for programming the pCO5+
Certification: CE / UL
using a standard USB pendrive, or direct Technical specifications
Assembly: DIN rail
connection to a PC without requiring
Number of I/Os: Power supply: 24 Vac -15/10 %,
serial converters.
• analogue inputs: da 5 a 12; 50/60 Hz o 48 Vdc (36 Vmin to 72 Vmax)
• digital inputs: 13 to 28; Operating conditions: -10T60 °C, 90% RH
Integration of the above-mentioned
• analogue outputs: 9 to 16; non-condensing
functions therefore offers numerous
• digital outputs: 8 to 29. Degree of protection:
benefits to manufacturers and designers of
Serial ports: pLAN, 2BMS, 2 FieldBus • IP20;
HVAC/R systems, including:
Dimensions: • front IP40.
• reduction in the number of modules
used to create the application, as
• 13 DIN (227.5x110x60); Certification: CE / UL
configurability of the input channels
• 18 DIN (315x110x60). Assembly: DIN rail
Connections: plug-in terminals Number of I/Os:
as digital inputs or analogue outputs
means all available channels can be fully • analogue inputs: 6 to 8;
exploited; • digital inputs: 4 to 6;
• reduction in space and electrical wiring: • analogue outputs: 2 to 4;
the EXV valve driver modules, battery • digital outputs: 6 or 7.
charger modules and backup battery Serial ports: pLAN, 1BMS, 1FieldBus
modules have been replaced on the Dimensions: 6 DIN (105x110x60)
pCO5+ by the integrated EXV driver with Connections: plug-in terminals
ultracap technology;
• ultracap technology means the solenoid
valve that was previously required to
33
P+5* +
Features PCOX*A PCOX*B P+5*S P+5*M P+5*L P+5*Z
EVD EVO
Maximum flash memory capacity 4 MB 13 MB
NAND flash 32 MB 50 MB
Real Time Clock
pLAN port
tLAN port
Integrated FieldBus port
Integrated BMS port
Ready for FieldBus card
Ready for BMS card
USB programming key
Built-in pGD1 display
Black box
Max no. of analogue inputs 8 6 5 8 12 10 10
PT1000 inputs 2 2 5 8 8 8 8
PT500 inputs 5 8 8 8 8
PT100 inputs 2 3 3 4 3
PTC inputs 5 8 8 10 10
NTC inputs 8 6 5 8 10 10 10
0 to 10 Vdc inputs 4 4 5 8 11 10 10
0 to 1 Vdc inputs 6 6 5 8 10 10 10
4 to 20 mA or 0 to 20 mA inputs with 2 2 4 4 6 4 4
power supply from pCO
4 to 20 mA or 0 to 20 mA inputswith 2 2 5 8 10 10 10
external power supply
0 to 5 Vdc ratiometric inputs with power 4 4 5 6 8 6 6
supply from pCO
0 to 5 Vdc ratiometric inputs with external 4 4 5 8 10 10 10
power supply
Max no. of digital inputs 6 4 13 24 28 28 26
24 Vac/Vdc inputs 8 14 14 18 14
230 Vac/Vdc inputs 2 2 4 2
Voltage-free contact inputs 6 4 5 8 12 4 2
Fast digital inputs 1 1 4 4 4 4 4
Max no. of analogue outputs 2 4 9 12 12 16 12
optically-isolated 0 to 10 Vdc outputs 4 4 4 6 4
0 to 10 Vdc outputs 1 3 5 8 8 10 8
Optically-isolated PWM outputs 2 2 2 2 2
PWM outputs 1 1 5 8 8 10 8
Max no. of digital outputs 7 6 8 13 13 18 29
SPST relay outputs 5 4 7 10 10 13 26
SPDT relay outputs 2 2 1 3 3 5 3
Max no. of SSR outputs 2 4 1 2 2 3 2
48 Vdc power supply
standard
optional
pCO sistema
Up to 10 channels can be configured as Up to 7 communication ports available, Up to 2 integrated EVDEVO drivers for
inputs or outputs. All 10 channels can be with the most commonly-used protocols managing two Independent EXV electronic
configured to manage probes, voltage- in HVAC/R applications, for complete expansion valves.
free digital inputs and control analogue system management: pLAN, 1 BMS1, BMS2, The Ultracap module guarantees the two
outputs. FieldBus1, FieldBus2, USB host, USB device. valves close in the event of power failures,
Energy Saving. saving the cost of installing a solenoid
Up to 10 sizes of controllers to cover valve.
various different solutions in HVAC/R
applications.
GND
GND
GND
U1
U2
U1
U3
U1
U2
U2
U3
U3
NTC, PTC,
NTC,PT100,PT500,
NTC,
PTC,PTC,
PT100,PT500,
PT100,PT500,
PT1000,
PT1000,
0 PT1000,
to 1V,
0 to 1V,
0 to 1V,
0 to 5V,
0 to
0 to
5V,
0 to
10V,
05V,
to010V,
0to
to20mA,
10V,
0 to 20mA,
04toto20mA,
20mA
4 to 20mA
4 to 20mA
voltage-free
voltage-free
voltage-free
digitaldigital
inputs
digital
inputs
inputs
(standard
(standard
(standard
and fast)
and fast)
and fast)
analogue
analogue
outputs
analogue
outputs
outputs
(0 to 10
(0 V
toand
(0
10toVPWM)
10
andV PWM)
and PWM)
35
Possibility to perform actions via web, such Hardware and software compatible with
as read and write unit variables, update the two previous generations of the pCO
the application on the controller, and family: pCO5 and pCO3.
Webserver to browse custom HTML pages, No change to the layout of the electrical
send emails. panel and complete reuse of software
developed for previous projects on pCO3
and pCO5.
Applications
Applications
CAREL
pCO 3
pCO5
2005
CAREL 2007
pCO3 TODAY pCO5
2010
2005 2007 2010 TODAY
pCO sistema
OVERVIEW DRAWING +
PCOS00AKY0: start
PCOS00AKC0: CVSTDUTLF0:
PGD1/E*: smart-key, mode
1 2 3
Probes
SPKT: 4 to 20 mA pressure
transducers 0 to 5 V
ratiometric transducers
NTC/PT100/PT500/PTC/
PT1000: temperature
probes
6 E*V: electronic expansion valves
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
EVD0:
J12 J13 J14
J11 pLAN J25 BMS2 J26 FBus2
EEV controllers
J30 J29
ZigBee™
CPY: KUE*
AT*: protocol
humidifier
sensor AT*: th-Tune third party DP*: serial ADC*: clima
control
terminal devices probes terminal
boards
RS485 Modbus ®
master/CAREL master
H–
e-dronic
(*): The PCOE00TLN0 & PLD* terminals CANNOT be
MP-BUS
connected to the tLAN at the same time!
damper servo servo control
CPY: KUE* EVD*4*: PCOE00TL**: control BELIMO BELIMO
valve
humidifier EEV driver pCO tLAN I/O
control expansion PLD*: user
boards board terminal
BMS
5
CANbus status
BACnet™ MS/TP
RS485
P1 P2 P3
GND H+ H– GNX + – RS485
supervisory
6 download logs
and upload 1tool
7 pCO manager
software application
37
mode
NTC/PT1000:
temperature probes
pCO manager
DPW*: temperature &
humidity probe for civil
serial card 1
environments
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
EVD0:
J12 J13 J14
J11 pLAN J25 BMS2 J26 FBus2
J127
J9 J10
driver
1
EVD0: EEV driver PCOE0048**: pCO RS485 I/O CP: KUE* humidifier
expansion board control boards
ZigBee™
protocol
CP: KUE*
AT*: humidifier
AT*: th-Tune third party control DP*: serial ADC*: clima
sensor terminal devices boards probes terminal
3 RS485 Modbus ®
master/CAREL master
H–
status
GNX
BACnet™ MS/TP
P1
+
P2
–
P3
RS485
RS485
Modbus®
Modbus®
TCP/IP
RS485
pCO sistema
Closes the electronic expansion valve in the Provides communication with BELIMO actuators
Used to interface pCO controllers with
event of blackouts, avoiding the need to install a using the MP-BUS® protocol.
BACnet™ Ethernet™, TCP/IP, SNMP V1 V2, 2, FTP
solenoid valve. and HTTP protocols.
Electronic expansion valve drivers and Used to interface the controllers to a Konnex CANbus serial card on FieldBus or BMS
Ultracap module network. (PCOS00HBF0, PCOS00HBB0)
(EVD0*, EVD*UC0) info: [email protected]
Provides communication using CANbus
Refrigerant superheat management by protocol to the CAREL system for managing
controlling the majority of electronic expansion e-dronic fan coils.
valves with stepper motors available on the
market.
RS485 serial card on FieldBus
(PCO100FD10)
The first solution connects the smart key to a Used to interface of controllers to a LonWorks
PC’s USB port. network®. The type of interface is FTT-10 A 78
The latter two, on the other hand, connect the kbs (TP/FT-10).
pLAN port on the pCO to a PC’s USB port.
RS485 serial card
(PCOS004850)
Interface for OEM series humidifiers pCO I/O RS485 and tLAN expansion
(PCOUMI2000) cards
(PCOE004850 & PCOE00RS10; PCOE00TLN0 &
This allows fundamental parameters (water level
PCOE00TL10)
and conductivity in the cylinder, TAM current
DC/DC module
sensor) on the OEM humidifiers produced by Used to increase the number of I/Os on the pCO
CAREL to be controlled directly by pCO sistema (PCO2DCDC00)
controllers. Connection via:
controllers. The values measured by the sensors This powers the pCO controllers with 48 Vdc • RS485 protocol for distances up to 600 m;
are converted into signals read by the inputs on storage batteries, typically used in telephone • tLAN protocol for distances up to 10 m. Also
the control board. applications. DIN rail mounting by 4 DIN available for mobile phone applications
module plastic case. (shelters).
39
The structure and modularity of the pGD Design and technology Performance at competitive costs
family displays always ensure the right
The pGD Touch series interfaces represent The pGD1-pGDe series is the family of
solution for different requirements in terms
the most high-tech CAREL product interfaces with graphic LCD designed for
of performance, cost and appearance.
offering in this area. pCO sistema controllers.
The interfaces offer great versatility and
The new pGD Touch range has been
The TFT full touchscreen display with extensive customisation possibilities, while
designed for high level applications that
65000 colours and WVGA resolution, with maintaining a high aesthetic standard.
require touchscreen technology combined
on-board operating system, can manage When designing these instruments, CAREL
with an elegant design and extensive
transparency effects typical of a desktop focussed special attention on simplicity of
connectivity possibilities.
operating system, a wide library of graphic programming and quality of performance.
objects for HVAC/R applications, logs,
The pGD1-pGDe series is focused
alarms and plot trends of values. pGD1-pGDe 132x64 pixel graphic displays
on applications that require a good
can display graphic symbols of different
compromise between performance,
The touchscreen function helps the end sizes and in the main international
competitiveness and appearance.
user move easily around more complex alphabets, such as Greek, Chinese, Cyrillic
system diagrams, without losing the overall and Scandinavian languages.
The pLD series (programmable LED
view, thanks the immediate and intuitive
display) is ideal for applications where the
navigation scheme. The th-Tune series is dedicated for
main requirements of the user interface are
temperature and humidity control in
reductions in costs and the space required
pGD Touch also provides more residential or commercial environments.
for installation.
demanding manufacturers in the HVAC/R The programming knob and intuitive icons
market various possibilities for product on the display make it extremely simple
The th-Tune series room terminals have
customisation and differentiation. to use.
been designed as simplified and intuitive
interfaces, particularly suitable for end
Its attractive and modern design and
users.
extensive connectivity (including via web)
make the user interface also suitable for
residential applications.
Unit and room terminals
These graphic terminals belong to the following protocols are available: BACnet™ pGD1 and pGDe are the CAREL proposal for
new range of TFT touch screen displays MSTP and TCP/IP, and Modbus® RTU and pCO sistema user interfaces, an innovative
designed to make the user interface to the TCP/IP. This makes pGD Touch a global area series of terminals designed with semi-
pCO sistema family controllers easier and controller that can monitor and manage graphic LCDs so as to offer greater
more intuitive, including implementation a network of CAREL controllers and third versatility and possibility of customisation.
of Modbus® and BACnet™ communication party devices. When designing these terminals, CAREL
protocols as standard. The touchscreen Connectivity to the outside world allows focussed special attention on simplicity of
panel makes interaction between the user pGD Touch to offer remote access programming and quality of performance,
and the unit much easier by simplifying solutions based on web technology for while maintaining a high aesthetic
navigation between the various screens. desktop or mobile devices, as well as standard.
the gateway function to share managed The display features graphic representation
The Windows CE operating system, the variables with external systems such as on 120x32 pixels. pGD1 is available with
electronic technology used, the 65,000 BMS, using the Modbus® and BACnet™ green or white backlighting, pGDe with
colour display, the HVAC/R libraries and protocols. white backlighting.
templates offered by the Carel 1Tool Touch pGDe differs from pGD1 as concern the
Editor software, and the advanced graphic Technical specifications symbols on the buttons, which recall
functions, including transparency, mean the graphics used on the pCO5+/pCO5
the terminals can manage high resolution Power supply:
compact built-in display.
images and achieve a high aesthetic • 4.3”: 24 Vac -15/+10 % 50/60 Hz o
pGD1 and pGDe can display graphic
standard that is usually only found on 12…30 Vdc -5/+5 %;
symbols of various sizes and the main
desktop applications. • 7”, 10”, 13” : 18 to 30 Vdc -5/+5%
international alphabets.
Operating conditions:
pGD1 and pGDe also respond to the logic
pGD Touch offers additional new • 4.3”: -25T60 °C, 5 to 85% RH non-
of flexibility and ease of customisation that
integrated functions that extend potential condensing;
is the basis for the design of this series of
applications. Graphs are available in real • 7”, 10”, 13”: 0T50 °C, 5 to 85% RH non-
CAREL products, offering more demanding
time of controlled variables, which can condensing.
customers several customisation
be logged and exported to USB key for Degree of protection:
possibilities at affordable costs even for
analysis of performance, operating modes, • IP20;
limited quantities.
etc. • front IP65.
Functions available include daily, weekly Certification: CE / UL
Assembly: panel mounted Technical specifications
and monthly scheduling to automatically
control various activities, such as unit on/ Dimensions: Power supply: from power board using
off or change set point, as well as the • 4.3” : 107x147x55.8; the telephone cable (code S90CONN00*)
possibility to change screen language • 7”: 176x136x45; or from external source 18 to 30 Vdc via
during normal operation and pop-up • 10” : 276x221x42; TCONN6J000
screens for alarm signals. • 13” : 337x267x46. Operating conditions:
Serial ports: RS485 & Ethernet, number -20T60 °C, <90% RH non-condensing
pGD Touch is available in a wide range of depending on models, see summary table Degree of protection:
versions, which differ as regards display Connections: plug-in terminals • IP65 flush mounted;
size and connectivity, so as to meet all • IP40 wall-mounted.
HVAC/R application requirements. Certification: CE / UL
The range includes four display sizes, from Assembly: panel mounted and wall-
4.3” to 7”, 10” and finally 13”. mounted
The use of vectorial images in the 1tool Dimensions: 156x82x30 mm
Touch Editor software means the same Serial ports: 1 pLAN
design can be used on all four sizes. Connections: telephone connector
AT* PLD*
th-Tune is the CAREL room terminal that, Technical specifications For all those applications where cost and
together with the pCO* programmable compact dimensions represent important
Power supply:
controllers, allows users to control the aspects of the application, CAREL offers the
ATA*: 230 Vac (-15/+10 %) 50/60 Hz
temperature and humidity in residential or pLD terminal (programmable LED display)
ATC*: 24 Vac (-15/+10%), 22…35 Vdc
light commercial environments, providing in the small and large sizes, with 3 and 4
Operating conditions:
of simplified interface that is ideal for end digit display respectively.
-10T60 °C, 10 to 90% RH non-condensing
users. Compact dimensions and elegant The ease of customisation and
Degree of protection: IP20
design make it suitable for all types of programmability using the EasyTools
Certification: CE & UL
rooms, as well as being ideal both as a environment guarantee a competitive
Assembly:
simplified HMI (Human Unit Interface) for solution.
• AT*: flush mounted
heat pumps, rooftop units, AHUs, etc. and In addition, as the pLD terminal is
• AT*: wall-mounted
as zone controller display for centralised connected to the tLAN port, the use of this
Dimensions:
systems. terminal does not preclude the possibility
• flush mounted model: 86x30.55x86 mm
to connect another pGD family terminal
• wall-mounted model: 143x36x86 mm
The display integrates perfectly with (e.g. remote terminal) to the pLAN port (in
Serial ports: 1 RS485
pCO family displays, as the information this case, the two displays cannot operate
Connections: fixed terminals
displayed and settings available on th-Tune at the same time).
can be configured using 1tool, so as to
adapt to the requirements of different
applications. The RS485 serial connection Technical specifications
over Modbus® protocol means architecture
can be implemented in which multiple Power supply: 12 Vdc 8 24 Vdc
displays are connected to a controller to Operating conditions:
create synergic control logic. -20T50 °C, <80% RH non-condensing
Depending on the model, the terminal Degree of protection:
is fitted with a temperature probe or • IP65 with flush mounting
temperature and humidity probe, and Certification: CE & UL
power supply may be 230 Vac or 24 Vac/ Assembly: flush mounted
Vdc. Dimensions:
th-Tune is compatible with the main • small: 81x36x42 mm
flush mount distribution boxes available • large: 167x36x31 mm
on the market (IT, US, DE, CN). Models Serial ports: 1 tLAN
are also available with wall-mounting for Connections: crimped connector
installations where flush mount boxes
cannot be used.
Area controller
To manage multiple CAREL
or third party controllers
using the Modbus® or
BACnet™ protocols over
RS485 or Ethernet
third-party
device
Gateway
To share data with BMS
supervisory systems using
the Modbus® or BACnet™
protocols over RS485 or
Ethernet
43
"Advanced" remote
access
For control and
programming of all
functions from desktop
devices, by the manufacturer
or maintenance personnel
Unit and room terminals
ZigBee™ AT*:
protocol
third-part sensor
devices
AT*: th-Tune
Touch
terminal
24 Vac/Vdc RS485
2
1 Modbus® master
PCO*:
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
J15 J16 J17 J18
J12 J13 J14
J11 pLAN J25 BMS2 J26 FBus2
programmable
J127
J9 J10
4
4.3” USB key: download controllers
applications J30 J29
DP*: serial
probes
J1 J24 J2 J3 J4 J5 J6 J7 J8
5
SD card: logs
advanced
PCO*:
2 3a 3b application programmable
5 controllers
web download
client
J1
PCO1000WB0:
J9
J24
J10
J11 pLAN
1 pCO Web
J2
J3
C1
3a TCP/IP
NO1
J12
NO2
Modbus®
NO3
C1
J4
C4
NO4
J13
NO5
NO6
C4
TCP/IP
C7
J14
NO7
J5
3b TCP/IP
C7
NO8
C8
J15
NC8
J6
J30
C9
J16
NO9
J127
NO11
J7
C9
NO12
C12
J17
J29
NC12
J8
NO13
C13
J18
NC13
PGTA00CNV0: BMS
ZigBee™ AT*:
9 pins/3 wires adapter protocol
sensor
cable, L= 2 m third-part
devices
RS485
3 Modbus® slave
AT*: th-Tune
24 Vdc terminal
1 RS485
2 Modbus® master
+ -
PCO*:
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
J127
J9 J10
PGTA00TRF0: programmable
5
DC power supply, controllers DP*: serial
13” 10” 7” USB key: download J30 J29
probes
DIN rail mounting
PCO*: programmable
controllers
application J1
J9
web download PCO1000WB0:
J24
J10
J11 pLAN
J2
C1
NO1
Modbus®
J12
NO2
NO3
C1
J4
C4
NO4
J13
NO5
NO6
TCP/IP
C4
C7
TCP/IP
J14
NO7
J5
C7
NO8
C8
J15
NC8
1
J6
J30
C9
J16
PC/PRINTER
NO9
NO10
J127
NO11
ETHERNET
J7
C9
NO12
C12
J17
J29
NC12
J8
NO13
0V
C13
J18
NC13
24V=
USB
PLC
2 3 4 5
AUX
Unit and room terminals
PGDTMA*FR*
PGDTM1*FR*
PGDT04*F0*
PGDT07*F0*
PGDT04*FS*
PGDT07*FS*
PGD1/E*
PLD*
AT*
Features
Hardware
Flash memory 128 MB
RAM 256 MB
Colours 65000 mono- mono-
chromatic chromatic
Display size 4.3 “ 4.3 “ 7.0 “ 7.0 “ 10.4 “ 13.3 “
Type of LCD display WVGA (16:9) VGA (4:3) WVGA (16:9)
Display resolution 480 x 272 800x480 640 x 480 1280 x 800 132 x 64 predefined 3-4 digit
icons
Display backlighting LED green/white white LEDs green
LEDs LED
Type of touch screen display resistive
Number of rows 8
Number of columns 22
Buzzer
Real Time Clock lithium battery
External membrane keypad
Availability on pCOI plastic case
Integrated temperature/ temp.
humidity probes humidity
ConneDtivitZ
RS485 serial ports 1 not 1 optically- 2 not 1 optically- 2 not optically-isolated
optically- isolated optically- isolated
isolated isolated 1 not
optically-isol.
Ethernet ports 2 2 1 1
tLAN port
BACnet MS/TP® on first serial port (RS485 connector) (DB9 connector)
Modbus® on first serial port (RS485 connector) (DB9 connector)
pLAN on first serial port (RS485 connector)
Modbus® on second serial port (DB9 connector)
Web server
FTP server to upgrade software
BACnet TCP/IP
BACnet RS485
Modbus® TCP/IP
USB Host 2.0 port
SD Card
Software
Operating system Windows CE 6.0
Multilanguage (including chinese)
Programmable fonts
Alpha Blending
Bold, italics, underline
Vectorial objects
Object libraries (thermometers,
cursors,…)
Animated icons
Graphs
Alarms
Scheduler
Parameter pre-configuration
User and password
Black box
standard
optional
47
1tool
µC sistema
µC2SE
µGEO
Remote terminal
(MCH200TP00 - MCH200TW00)
This is the parametric solution for the μC2SE is the controller for units with
complete control of single circuit heat one and two circuits and up to four µC2SE
pumps with one or two compressors, compressors.
µGEO
managing the production of domestic hot It represents the technological evolution of
water and hot or cold water for the heating the μC2 series. All μC2SE series controllers µAD room terminal
or cooling system, based on the priority in fact feature microprocessors with RISC
(ADM*)
defined by the user. technology and optional real time clock,
Wiring is performed using Molex® plug-in ensuring top-of-the-range performance LCD with icons for remote wall-mounting in the
connectors, thus reducing space, and and user friendliness. The μC2SE series room as a simple user interface, with built-in
making assembly faster and easier. is available in the panel mounting temperature or temperature plus humidity
sensor and time band management, for use
version, and wiring is plug-in with Molex®
in residential or smaller commercial / service
Technical specifications connectors, reducing dimensions,
applications.
simplifying and speeding up installation.
Power supply: 24 Vac, –15/+10 %;
μC2SE ccan manage up to four hermetic
50/60 Hz
or two semi-hermetic compressors in a
Operating conditions: -10T55 °C <90% µC2SE
maximum of two circuits, as well as one
RH non-condensing
electronic valve driver per circuit. µGEO
Degree of protection: front IP65/IP40
Optimum management of air-to-water
Certification: CE, UL µAM terminal
and water-to-water chillers/HPs, air- and
Assembly: (ADE*)
water-cooled condensers, direct air/air
• µGEO: panel mounted;
units and heat pumps, rooftop units with Area controller for management of the µe-dronic
• I/O expansion: DIN rail.
free cooling by temperature. system. Automatic changeover of system
Number of I/Os:
operating mode based on requirements, energy
• analogue inputs: 8 (6 NTC inputs and 2
inputs configurable as NTC/ratiometric Technical specifications saving according to load, coordination of set
points and centralised time bands are just some
pressure probe/digital input); Power supply: 24 Vac -15/+10%, 50/60 Hz of the benefits provided by this product.
• digital inputs: 10, voltage-free contact; Operating conditions: -10T55 °C, <90% RH
• analogue outputs: 2 PWM outputs; non-condensing
• digital outputs: 10 relays with NO Degree of protection: front IP65
contact, 25 Vac 3 A res. 2 A. Certification: CE, UL µC2SE
Serial ports: tLAN, supervisor Assembly: panel mounted µGEO
Dimensions: Number of I/Os:
• µGEO: 75x33x74 mm; • analogue inputs: 4 (3 NTC inputs and 1 ON/OFF and 0 to 10 V converter
• I/O expansion: 70x110x60 mm configurable input as NTC/ratiometric (CONVONOFF0, CONV0/10A0)
Connections: tLAN, RS485 pressure probe/digital input); Condenser fan management in ON/OFF mode.
• digital inputs: 5, voltage-free contact; Switchable power control relay 10 A 250 Vac in
• analogue outputs: 1 PWM output; AC1 (1/3 HP inductive).
• digital outputs: 5 relays with NO Converts the PWM signal sent by the
contact, 250 Vac 3 A res. 2 A. corresponding relay on the controller to a
standard 0 to 10 V (or 4 to 20 mA) signal.
Serial ports: tLAN, supervisor
Dimensions: 75x33x74 mm
Connections: tLAN, RS485
µC2SE
µGEO
PSOPZKEY*:
programming
CONVONOFF*: key
PWM/digital
converter
CONV0/10A0*: CAREL PV
PWM/analogue supervisor/
converter Modbus® RTU
NTC/PT1000: MCH200485:
temperature probes remote
terminal ADM* / ADE*: AD
and µAM terminal
MCHRTF**A0: fan
speed controller
MCH200485:
remote
terminal
ADM*: µAD
SNM0000EM0: terminal
supernode
BMS CAREL PV
supervisor/
PCO10000F0: PCOS004850: RS485 PCO1000BA0:
BACnet™ MS/TP
Modbus® RTU
status RS485
P1 P2 P3
+ –
serial board
interface board
e-dronic
HYFC*
CANbus card
(HYSC00F0C0)
Expansion card with 2 triacs, 2 relays
(HYVC000M*) Microprocessor serial card for hydronic network
and advanced functions.
This is is fitted with two triacs for a 230 V
three-position servomotor. one 2 kW relay for
management of an electric heater plus 1 control
relay with voltage-free contacts.
57
This is fitted with 4 triacs for the control of 230 V Used to access a CANbus network from a
3-position servomotors. personal computer.
IR remote control fitted with LCD and 13 buttons Used to interface pCO controllers with BACnet™
Used to simply export the parameter
for local or zone programming. Ethernet™, IP, SNMP V1, 2, 3, FTP and HTTP
configuration from one e-drofan to another.
protocols.
Useful in systems with a large number of fan
info: [email protected]
coils.
Version with power supply.
IR receiver board
(HYIR*)
Universal controllers
The “infrared universale” is series is a The following sensors can be connected Panel or DIN rail mounting: all models are
range of instruments for controlling the to the “Multi-in” models: available for both classic panel installation
temperature, pressure and humidity • NTC with range –50T90 °C; with IP65 front protection, or for DIN rail
values in air-conditioning, refrigeration • NTC-HT with range –40T150 °C; mounting (4 modules).
and heating units. They can however also • PTC with range –50T150 °C;
be used in other contexts, as the voltage • PT1000 with range –50T150 °C; Backward compatibility: the list of
or current inputs can support various • PT1000 with range –199T800 °C; parameters is compatible with the
different types of sensors. In addition, the • PT100 with range –199T800 °C; previous “ir32 universale” range
PT100 probes or thermocouples have an • J/K TC with range –100T800 °C;
operating range up to 800 °C and can • Voltage: 0 to 1 V, -0.5 to 1.3 V, 0 to 10 V, 0 Other functions: 2 configurable digital
comfortably manage common oven or to 5 V rat; inputs, IR receiver and buzzer available on
furnace temperature control processes. • current: 0 to 20 mA, 4 to 20 mA. all models; some versions also feature a
The wide range of models can satisfy all The type of probe is selected by real time clock (RTC).
requirements: configuration parameter.
The models are divided into two families: Main functions include::
• the first with temperature only • PID with autotuning;
inputs, and consequently suitable for • two independent control loops;
temperature control in HVAC/R and/ • clock management for logging alarms;
or generic applications that require a • working cycles.
thermostat in the range –50T150 °C;
• the second with universal inputs (NTC, Types of outputs: relays, 0 to 10 Vdc, or
NTC-HT, PTC, PT1000, PT100, J/ TC K, control of external SSRs.
voltage and current).
%rH
The following sensors can be connected
to the “temperature only” models:
• NTC with range –50T90 °C;
Type of power supply: models are
available for mains power supply (115 to
230 Vac), or alternatively operating at 12 to
bar
• NTC-HT with range –40T150 °C;
• PTC with range –50T150 °C;
24 Vac/Vdc or 24 Vac/Vdc
°C
• PT1000 with range –50T150 °C. …and more
Universal controllers
This series of “universal” thermostats This series of controllers can connect Electronic instrument for controlling
can connect two temperature probes two universal probes (NTC, NTC-HT, PTC, ambient temperature and humidity. It
(NTC, PTC, PT1000). The second probe PT1000, PT100, J/K TC, 0 to 1 V, -0.5 to 1.3 can be used in various operating modes.
can be used for a second control loop, V, 0 to 10 V, 0 to 5 V rat., 0 to 20 mA, 4 to Special attention has been focused
independent from the first, or alternatively 20 mA) for managing common values in on advanced algorithms for heating,
for temperature compensation (summer or HVAC/R applications, as well as any other cooling or automatic operation and
heating), differential operation (difference sensor whose output is supported by the for the control of underfloor heating/
between the two temperatures), or free controller. The second probe can be used cooling and temperature compensation
cooling. They feature two digital inputs for a second control loop, independent functions. Timer and RTC clock for day and
that can be configured to manage from the first, or alternatively temperature night operation (optional, depending on
functions such as an immediate external compensation, differential operation, or the model). The remote control option
or delayed alarm, and remote ON/OFF. free cooling. They also feature two digital (by purchasing accessory IROPZ48500)
Programming is made extremely simple configurable inputs. Programming is made allows the data from the instrument to be
by the 9 selectable operating modes (e.g.: extremely simple by the 9 selectable monitored and saved using a supervisor.
direct, reverse, neutral zone, PWM, etc.). operating modes (e.g.: direct, reverse,
All controllers feature a PID algorithm neutral zone, PWM, etc.). All controllers Technical specifications
with AutoTuning and some versions are feature a PID algorithm with AutoTuning
Power supply: 24 Vac -15/10% 50/60 Hz
available with RTC (real time clock). A low and some versions are available with
1 VA, 24/32 Vdc 1 W
consumption switching power supply RTC (real time clock). A low consumption
Operating conditions:
is used on both the 12/24 Vac/Vdc and switching power supply is used on both
0T60 °C, 10 to 90% RH non-condensing
115/230 Vac versions. the 24 Vac/Vdc and 115/230 Vac versions.
Degree of protection: IP20
Certification: CE, UL
Technical specifications Technical specifications
Assembly: wall-mounted
Power supply: 115/230 Vac -15/10% 50/60 Power supply: 115/230 Vac -15/10% 50/60 Number of I/Os:
Hz 6 VA or 12/24 Vac -10/10% 50/60 Hz 4 Hz 9 VA or 24 Vac -10/10% 50/60 Hz 12 VA, • analogue inputs: room temperature
VA, 12/30 Vdc 300 mA max 24 Vdc -15/15% 450 mA max. and/or humidity and outside
Operating conditions: -10T60 °C , Operating conditions: -10T50 °C, temperature
10 to 90% RH non-condensing 10 to 90% RH non-condensing • digital inputs: 1
Front panel degree of protection: Front panel degree of protection: • analogue outputs: 1 x 0 to 10 Vdc
• panel ver.: IP65 • panel ver.: IP65 • digital outputs: 1 or 2 relays
• DIN rail ver.: IP40 • DIN rail ver.: IP40 Serial ports: 1 via external option
Certification: CE, UL (panel ver.) Certification: CE, UL Dimensions: 135x86x36 mm
Assembly: panel or DIN rail Assembly: panel or DIN rail Connections: terminals
Number of I/Os: Number of I/Os:
• analogue inputs: 2 (NTC/HT, PTC, PT1000) • analogue inputs: 2 configurable
• digital inputs: 2 • digital inputs: 2
• analogue outputs: up to 2 x 0 to 10 Vdc • analogue outputs: up to 2 x 0 to 10 Vdc
• digital outputs: 1, 2 or 4 relays • digital outputs: 1, 2 or 4 relays
Serial ports: 1 via external option Serial ports: 1 via external option
Dimensions: Dimensions:
• panel version: 76x34x75 mm • panel version: 76x34x93 mm
• DIN version: 70x110x60 mm • DIN version: 70x110x60 mm
Connections: plug-in terminals Connections: a morsetti estraibili
63
This key allows the ir33 to be programmed These have been developed to be connected
quickly, even when not powered, reducing directly to the Infrared Universale series
the risk of errors. The accessory reduces the instruments (version A). They can in any case be
number of part numbers handled, is a rapid and used with other controllers, for example with
effective tool for service operations, allowing the µchiller series.
the controller to be programmed in just a few There are two models available:
seconds, even during the testing phase at the • CONV0/10A0: cconverts the PWM signal
end of the production line. Versions are available supplied by the instrument into a standard
with battery or external power supply. analogue signal (0 to 10 Vdc or 4 to 20 mA);
• CONVONOFF0: converts the PWM signal into
an ON/OFF signal via relay.
PID - Autotuning
Real Time Clock
12/24 Vac/Vdc
to control SSR
temperature
115/230 Vac
multi-input
24 Vac/Vdc
buzzer/IR
0 to 10 V
DIN rail
digital
panel
relay
Universal thermostats
IR33V7HR20 DN33V7HR20 2 2 1
IR33V7HB20 DN33V7HB20 2 2 1
IR33V7LR20 DN33V7LR20 2 2 1
IR33W7HR20 DN33W7HR20 2 2 2
IR33W7HB20 DN33W7HB20 2 2 2
IR33W7LR20 DN33W7LR20 2 2 2
IR33Z7HR20 DN33Z7HR20 2 2 4
IR33Z7HB20 DN33Z7HB20 2 2 4
IR33Z7LR20 DN33Z7LR20 2 2 4
IR33A7HR20 DN33A7HR20 2 2 4
IR33A7HB20 DN33A7HB20 2 2 4
IR33A7LR20 DN33A7LR20 2 2 4
IR33B7HR20 DN33B7HR20 2 2 1 1
IR33B7HB20 DN33B7HB20 2 2 1 1
IR33B7LR20 DN33B7LR20 2 2 1 1
IR33E7HR20 DN33E7HR20 2 2 2 2
IR33E7HB20 DN33E7HB20 2 2 2 2
IR33E7LR20 DN33E7LR20 2 2 2 2
Universal multi-input
IR33V9HR20 DN33V9HR20 2 2 1
IR33V9HB20 DN33V9HB20 2 2 1
IR33V9MR20 DN33V9MR20 2 2 1
IR33W9HR20 DN33W9HR20 2 2 2
IR33W9HB20 DN33W9HB20 2 2 2
IR33W9MR20 DN33W9MR20 2 2 2
IR33Z9HR20 DN33Z9HR20 2 2 4
IR33Z9HB20 DN33Z9HB20 2 2 4
IR33Z9MR20 DN33Z9MR20 2 2 4
IR33A9HR20 DN33A9HR20 2 2 4
IR33A9HB20 DN33A9HB20 2 2 4
IR33A9MR20 DN33A9MR20 2 2 4
IR33B9HR20 DN33B9HR20 2 2 1 1
IR33B9HB20 DN33B9HB20 2 2 1 1
IR33B9MR20 DN33B9MR20 2 2 1 1
IR33E9HR20 DN33E9HR20 2 2 2 2
IR33E9HB20 DN33E9HB20 2 2 2 2
IR33E9MR20 DN33E9MR20 2 2 2 2
standard
Sensors and protection devices
67
CAREL offers increasingly advanced and Advantages The smoke/fire and flood detectors
complete global solutions. are small devices with auto-calibration
CAREL probes, as well as being
function, thus adapting to different
characterised by the acknowledged
For this reason, CAREL has designed environmental conditions without losing
performance that sets them apart, are very
an entire range of probes that respond activation accuracy.
versatile and can satisfy various market
to the needs of HVAC/R installers and
requirements.
manufacturers, as well as for the control of For the detection of CFCs, HFCs and CO2
CAREL’s own line of humidifiers. gas refrigerants, CAREL offers a range of
In fact, all the probes have been especially
sensors designed to satisfy requirements
designed to be compatible not only
The range envisions temperature in the industrial refrigeration and air-
with all CAREL controllers, but also with
and humidity sensors with different conditioning for supermarkets, shopping
the most commonly used standards
uses, housed in sockets, ducted, centres, and other public places.
worldwide.
residential or industrial environment,
pressure transducers, smoke, fire and
The temperature and humidity probes,
flood detectors, air quality probes,
offering a great choice between active
gas leak detectors for refrigerant
and passive technology, are available in
units, guaranteeing performance and
different operating ranges and also in
compatibility with all CAREL controllers.
specific versions for corrosive or polluting
environments.
The range has been enhanced with the
most innovative technological solutions,
The pressure transducers are available in
offering new international standards at
a ratiometric version, 0 to 5 V and 4 to 20
increasingly competitive prices.
mA, also in a sealed version (to be installed
without capillary directly onto the piping)
offering improved performance in terms of
precision.
This probes are particularly suitable for Specifically designed to measure high The ASIT* immersion probes are used in
civil and commercial environments where levels of humidity with great accuracy. cases where it is necessary to measure the
particular attention is paid to design. The range also envisions models with temperature inside cooling and heating
They are used in heating and air RS485 connection with CAREL and circuits.
conditioning systems that use ducts. The Modbus® protocol. They are particularly adaptable where the
range also envisions models with RS485 sensitive element must be in direct contact
connection with CAREL and Modbus® with the fluid being controlled.
protocol. Technical specifications
Power supply: 12/24 Vac -10/15%,
9 to 30 Vdc ±10% Technical specifications
Technical specifications Operating conditions: -10T60 °C, -20T70, Power supply: 12/24 Vac -10/15%,
Power supply: 12/24 Vac -10/15% <100% R.H. non cond. 9…30 Vdc ±10%
9 to 30 Vdc ±10% Protection rating: Operating conditions: -10T70 °C, <100%
Operating conditions: • IP55 (container); R.H. non cond.
• DPW*: -10T60 °C, <100% R.H. non cond.; • IP54 (sensor). Protection rating:
• DPD*: -10T60 °C, -20T70, <100% R.H. non Assembly: wall-mounted • IP55 (container);
cond. Number of I/Os: • IP67 (sensor).
Protection rating: • analogue outputs: -0.5 to 1 V, 0 to 1 V, Assembly: direct or with housing
• DPW*: IP30; 0 to 10 V, 4 to 20 mA Number of I/Os:
• DPD*: IP55, IP40 sensor. Serial Ports: RS485 (specific model) • analogue outputs: -0.5 to 1 V,
Assembly: Dimensions: 98x170x44 4 to 20 mA
• DPW*: wall-mounted; Connections: screw terminal board for Dimensions: 94x102x176
• DPD*: duct; cables up to 1.5 mm2 Connections: screw terminal board for
Number of I/Os: cables up to 1.5 mm2
• analogue outputs: -0.5 to 1 V, 0 to 1 V,
0 to 10 V, 4 to 20 mA
Serial Ports: RS485 (specific model)
Dimensions:
• DPW*: 127x80x30 mm;
• DPD*: 98x105x336 mm.
Connections: screw terminal board for
cables up to 1.5 mm2
The universal temperature probes are These analyse the quality of the air and The refrigerant gas detection sensor is a
used for many applications; in particular are ideal for air ventilation and handing device that indicates leaks of the most
the ASET03* version has an electronic systems in domestic and commercial areas. common gases (R22, R134a, R404a, R407c,
amplifier, protected by a container with R410a and CO2). It can be used in stand-
IP55 protection rating, which allows Main functions: alone applications, integrated with Carel
remote control up to 2oo m with 4 to 20 • measurement of air quality; controllers or with third party devices.
mA output. • quantitative analysis of contamination It envisions connection with the CAREL
by parts of polluting gases; controller via the analogue, digital output
• setting of a sensitivity threshold or via RS485 Modbus® serial connection.
Technical specifications depending on that envisioned; When a leak above a certain concentration
• for the ventilation of rooms only when is detected, the sensor informs the
Power supply: 12/24 Vac -10/15%,
necessary, contributing to a large energy controller of the alarm and locally activates
9…30 Vdc ±10%
saving. an audible and visual signal and a relay
Operating conditions: -30T90 °C or 30T150
(SPDT) at the same time. It offers the
°C, <100% R.H. non cond.
advantage of intervening immediately on
Protection rating:
gas leaks, thus preventing unit standstill
• IP55 (container); Technical specifications
and guaranteeing the safety of persons in
• IP67 (sensor). Power supply: 24 Vac/dc ±10%, 50/60 Hz the vicinity.
Assembly: directly in socket Operating conditions: 0T50 °C, Its installation ensures compliance with the
Number of I/Os: 10/90% R.H. non cond. European F-GAS and EN378 and ASHRAE
• analogue outputs: -0.5 to 1 V, 4 to 20 mA Protection rating: 15 standards.
Dimensions: 94x102x176 • IP55 (container);
Connections: screw terminal board for • IP67 (sensor)
cables up to 1.5 mm2 Technical specifications
Assembly:
• DPWQ: wall-mounted; Power supply: 12 to 24 Vac/Vdc ±20%
• DPDQ: duct 50/60 Hz
Number of I/Os: Operating conditions:
• analogue outputs: 0 to 10 V, 4 to 20 mA • semicond. ver. -20T50°C;
Dimensions: • infrared ver. -40T50°C 80% R.H. non
• DPWQ*: 95x97x30 mm; 79x81x26 mm; condensing.
• DPDQ*: 108x70x262.5 mm; Protection rating:
64x72x228.4 mm. • semicond. ver. IP41;
Connections: screw terminal board for • infrared ver. IP66.
cables up to 1.5 mm2 Assembly: wall-mounted
Number of I/Os:
• analogue outputs: configurable 0 to 5 V,
1 to 5 V, 0 to 10 V, 2 to 10 V, 4 to 20 mA;
• digital outputs: 1 amp at 24 Vac/Vdc.
Serial Ports: RS485 Modbus®
Connections: disconnectable clamps,
0.5 mm2 cable cross-section
NTC*HP*, NTC*WP*, NTC*WH*, NTC*WF*, TSN* and TSC*= NTC version PTC*
NTC*HF and NTC*HT, NTCINF*, NTC*PS* TST* and TSM*= Pt1000 version
TSOPZ= accessories (connectors, fittings,
housing…) The PTC temperature probes represent
CAREL offers a range of sensors with a possible solution for both cooling and
different features for the various controllers, CAREL offers a range of TS* series heating applications, used to measure
suitable for different applications mainly in immersion probes in NTC and Pt1000 temperature within the operating range,
the HVAC/R market sector. models, suitable exclusively for hydronic -50T100 °C and 0T150 °C.
applications.
The accuracy obtained thanks to the Quick installation, fast response of the PT100*
technical solutions used in developing the sensor an excellent price/performance
The PT100 probes represent the ideal
sensor, the reliability as a result of the tests ratio are features on which this product
solution for all applications in which it is
to which they are subjected, mean that range is based.
necessary to measure temperatures within
CAREL NTC probes are reliable transducers Connectors are available with cables,
the range from -50 to 400 °C (depending
for measuring temperature at a low cost. fittings and the socket as accessories.
on the models).
Probes for socket assembly are available
PT1*HP*, PT1*WP*, PT1*WF*, PT1*HF*,
in strips for installation on piping for
PT1*HT*; PT1*PS; TSQ*
pass-through with or without pre-heater, Technical specifications
to measure the core temperature of the The Pt1000 probes (PT1* and TSQ*) are
Operating conditions: -40T90 °C,
product, and a sensor for estimating suitable for all those applications in which
-40T120 °C
product temperature. it is necessary to measure temperatures in
Assembly: on piping
a range from -50 to 250 °C (TSQ*) and from
Dimensions:
-50 to 105 °C (PT1*), maintaining accuracy
• TSN* and TSC*: 1/8” GAS x 5 mm
Technical specifications • TST* and TSM: M14 x23 mm with 2 m
also over long distances..
Operating conditions: -50T105 °C cable
Probes for socket assembly are available
Protection rating: IP67 and IP68
in strips for installation on piping for
Assembly: depending on the model
pass-through with or without pre-heater,
Dimensions: depending on the model
to measure the core temperature of the
product, and a sensor for estimating
product temperature.
Technical specifications
Operating conditions: -50T105 °C,
-50T250 °C, -50T350 °C
Protection rating: IP65 and IP67
Dimensions: depending on the model
The pressure transducers supply an The Carel 5 V ratiometric pressure These pressure transducers supply
analogue current signal (4 to 20 mA). transducers (Sealing) have been developed a 0 to 5 V ratiometric signal (automotive
They are used particularly in refrigeration to be used in commercial refrigeration standard).
and air conditioning to measure pressure and air conditioning applications. They are They can be used in air conditioning and
in cooling circuits, but their high completely hermetic and can be installed refrigeration systems, with exception to
performance allows their use in almost all directly in contact with the piping, in those containing ammonia.
other applications. conditions with the refrigerant fluid lower Available with female connection only.
Compatible with all types of refrigerant. than the dew point ( it is not necessary
They are available with male and female to use the capillary positioned between
connection for the C series and only piping and sensor). Technical specifications
female for the D series. Available with female connection only
Power supply: 4.5 to 5.5 Vdc
Operating conditions: -40T135 °C
Protection rating: IP65
Technical specifications Technical specifications Number of I/Os:
Power supply: 8 to 28 Vdc ±20% Power supply: 5 Vdc • analogue outputs: 0.5 to 4.5 V
Operating conditions: Operating conditions: -40T125 °C Dimensions: 20x51.6 mm
• -25T80 °C (male); Protection rating: IP67 Connections: Packard
• -40T135 °C (female). Number of I/Os:
Protection rating: IP65 (IP67 with built-in • analogue outputs: 0.5 to 4.5 V
connector) Dimensions: Ø21x51 mm
Number of I/Os: Connections: Packard
• analogue outputs: 4 to 20 mA
Dimensions: depending on the model
Connections: Packard
pressure sensors
Sensors and protection devices
Differential pressure
switch
DCPD0*0*00
The combined pressure and temperature The differential pressure transducers use
transducer has been developed for a ceramic sensor that supplies a voltage
applications in the refrigeration and air or current signal that is calibrated and
conditioning sectors. The sensor-pressure compensated by temperature. They are
transducer is 0 to 5V ratiometric, while the particularly suitable for measuring low
temperature sensor is NTC. pressure values in air conditioning systems,
It offers the advantage of having a single laboratories and clean rooms (non-
component with a quicker and more corrosive air and gas)
accurate measurement. Typical use is in The main features are:
combination with a driver for electronic • compact construction;
expansion valves in refrigeration and air • easy and simple installation;
conditioning applications. • model can be configured for 4 different Anti-freeze thermostat
pressure ranges.
DCTF000320
Technical specifications Technical specifications This manages heat exchanger (evaporation
Power supply: 4.5 to 5.5 V Power supply: 15 to 36 Vdc coils) and electric heater protection for air
Operating conditions: -40T120 °C Operating conditions: 0T50 °C conditioning and refrigeration systems.
Protection rating: IP67 Protection rating: IP65 It can be used in all applications where it is
Number of I/Os: Assembly: panel necessary to control the temperature in a
• analogue outputs: 0.5 to 4.5 V and NTC Number of I/Os: certain point of the system in order to prevent it
dropping below a pre-established safety value.
10K at 25°C (non STD) • analogue outputs: 4 to 20 mA
Moreover, the thermostat offers self-protection if
Dimensions: Ø= 23.80 x 65 mm Dimensions: 70x108x73.5 mm the sensitive element should breakdown.
Connections: 4-way AMP Connections: screw terminal board for
Micro-Quadlok System connector cables up to 1.5 mm2
Airflow switch
DCFL000100
Flood detector Active probes for rooms, power supply 9 to 30 Vdc/12 to 24 Vac
DPWT010000 -10T60 °C selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
DPWT011000 -10T60 °C NTC 10 K at 25 °C
FLOE* DPWC111000 -10T60 °C 10…90% R.H. • NTC 10 K at 25 °C (temperature)
• selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
(humidity)
The flood sensor device can detect the DPWC110000 -10T60 °C 10…90% R.H. selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
presence of water in an environment. DPWC115000 -10T60 °C 10…90% R.H. • NTC 10 K at 25 °C (temperature)
It is usually used for the protection against the • 0 to 10 Vdc (humidity)
flooding of datacentres, offices, laboratories,
DPWC112000 -10T60 °C 10…90% R.H. 0 to 10 Vdc
special rooms. It is made up of a detector
(normally positioned on the electric control DPWC114000 -10T60 °C 10…90% R.H. opto-isolated RS485 serial
board) and a sensor (positioned on the point to DPWT014000 -10T60 °C opto-isolated RS485 serial
be controlled). Active probes for industrial environments, power supply 9 to 30 Vdc/12 to 24 Vac
When the water comes into contact with the
sensor, the detector immediately signals an DPPT010000 -20T70 °C selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
alamr, switching over relay status. DPPT011000 -20T70 °C NTC 10 K at 25 °C
DPPC111000 -10T60 °C 10…90% R.H. • NTC 10 K at 25 °C (temperature)
• selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
(humidity)
DPPC110000 -10T60 °C 10…90% R.H. selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
DPPC210000 -20T70 °C 0…100% R.H. selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
DPPC112000 -10T60 °C 10…90% R.H. 0 to 10 Vdc
DPPC212000 -20T70 °C 0…100% R.H. 0 to 10 Vdc
DPPT014000 -10T60 °C 10…90% R.H. opto-isolated RS485 serial
DPPC114000 -10T60 °C 10…90% R.H. opto-isolated RS485 serial
DPPC214000 -20T70 °C 0…100% R.H. opto-isolated RS485 serial
Active probes for ducts, power supply 9 to 30 Vdc/12 to 24 Vac
DPDT010000 -20T70 °C selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
Smoke and fire detector DPDT011000 -20T70 °C NTC 10 K at 25 °C
DPDC111000 -10T60 °C 10…90% R.H. • NTC 10 K at 25 °C (temperature)
• selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
SFF* (humidity)
DPDC110000 -10T60 °C 10…90% R.H. selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
The smoke and heat detectors are electronic
DPDC210000 -20T70 °C 0…100% R.H. selectable 0 to 1 V/-0.5 to 1 Vdc/4 to 20 mA
devices that can quickly detect dangerous and
sudden temperature changes or the increase in DPDC112000 -10T60 °C 10…90% R.H. 0 to 10 Vdc
fumes. Their peculiarity lies in the self-calibration, DPDC212000 -20T70 °C 0…100% R.H. 0 to 10 Vdc
i.e. the possibility to maintain the guarantee of DPDT014000 -20T70 °C opto-isolated RS485 serial
activation over time, adapting perfectly to the
DPDC114000 -10T60 °C 10…90% R.H. opto-isolated RS485 serial
different environmental conditions, without
losing sensitivity. DPDC214000 -20T70 °C 0…100% R.H. opto-isolated RS485 serial
Container protection rating: IP55 for DPD, DPP for duct and technical environment)
IP30 for DPW (wall-mounted)
Sensitive element protection rating IP30 for DPW
IP40 for DPD
IP54 for DPP
Time constant, temperature in still air 300 s
in ventilated air (3 m/s) 60 s
Time constant, humidity in still air 60 s
in ventilated air (3 m/s) 20 s
Pressure transducers
operating output constants
Models power supply: range accuracy IP
temperature signal (time)
SPKT00-R0: 0 to 5 V ratiometric - female series R
*53* 4.5 to 5.5 Vdc -40T135 °C 4.2 relative bar ±1,2% 0.5 to 4.5 V 10 ms IP65 1
*13* 4.5 to 5.5 Vdc -40T135 °C 9.3 relative bar ±1,2% 0.5 to 4.5 V 10 ms IP65 1
*33* 4.5 to 5.5 Vdc -40T135 °C 34.5 relative bar ±1,2% 0.5 to 4.5 V 10 ms IP65 1
*43* 4.5 to 5.5 Vdc -40T135 °C 17.3 relative bar ±1,2% 0.5 to 4.5 V 10 ms IP65 1
*B6* 4.5 to 5.5 Vdc -40T135 °C 45.0 relative bar ±1,2% 0.5 to 4.5 V 10 ms IP65 1
*F3* 0.5 to 5.5 Vdc -40T135 °C 20 relative bar ±1,2% 0.5 to 4.5 V 10 ms IP65 1
*E3* 0.5 to 5.5 Vdc -40T135 °C 12.8 relative bar ±1,2% 0.5 to 4.5 V 10 ms IP65 1
SPK*: 4 to 20 mA - male series C
*1000000 8 to 28 Vdc -25T80 °C -0.5 to 7 bar ±1% fs 4 to 20 mA - IP67
*240000 8 to 28 Vdc -25T80 °C -1 to 24 bar ±1% fs 4 to 20 mA - IP67
*2500000 8 to 28 Vdc -25T80 °C 0 to 25 bar ±1% fs 4 to 20 mA - IP67
*3000000 8 to 28 Vdc -25T80 °C 0 to 30 bar ±1% fs 4 to 20 mA - IP67
SPK*C*: 4 to 20 mA - female series C
*T0021C0 8 to 28 Vdc -40T135 °C -0.5 to 7 bar ±1% fs; 0T50 °C 4 to 20 mA <10 ms IP65 1
*T0011C0 8 to 28 Vdc -40T135 °C 0 to 10 bar ±1% fs; 0T50 °C 4 to 20 mA <10 ms IP65 1
*T0031C0 8 to 28 Vdc -40T135 °C 0 to 30 bar ±1% fs; 0T50 °C 4 to 20 mA <10 ms IP65 1
*T0041C0 8 to 28 Vdc -40T135 °C 0 to 18.2 bar ±1% fs; 0T50 °C 4 to 20 mA <10 ms IP65 1
*T00B1C0 8 to 28 Vdc -40T135 °C 0 to 44.8 bar ±1% fs; 0T50 °C 4 to 20 mA <10 ms IP65 1
*T00G1C0 8 to 28 Vdc -40T135 °C 0 to 60 bar ±1% fs; 0T50 °C 4 to 20 mA <10 ms IP65 1
*T00D8C0 8 to 28 Vdc -40T100 °C 0 to 150 bar ±1% fs; 0T50 °C 4 to 20 mA <10 ms IP65 1
SPK*: 4 to 20 mA - female series D
*T0021D0 8 to 28 Vdc -40T135 °C -0.5 to 7 bar ±1% fs; 0T40 °C 4 to 20 mA <10 ms IP65
*T0011D0 8 to 28 Vdc -40T135 °C 0 to 10 bar ±1% fs; 0T40 °C 4 to 20 mA <10 ms IP65
*T0041D0 8 to 28 Vdc -40T135 °C 0 to 18.2 bar ±1% fs; 0T40 °C 4 to 20 mA <10 ms IP65
*T0031D0 8 to 28 Vdc -40T135 °C 0 to 30 bar ±1% fs; 0T40 °C 4 to 20 mA <10 ms IP65
*T00B1D0 8 to 28 Vdc -40T135 °C 0 to 44.8 bar ±1% fs; 0T40 °C 4 to 20 mA <10 ms IP65
SPK*: 0 to 5 V - female series S
*T0051S0 0.5 to 4.5 Vdc -40T125 °C -1 to 4.2 bar ±1% fs; 0T50 °C 0.5 to 4.5 V <10 ms IP67
*T0011S0 0.5 to 4.5 Vdc -40T125 °C -1 to 9.3 bar ±1% fs; 0T50 °C 0.5 to 4.5 V <10 ms IP67
*T00E1S0 0.5 to 4.5 Vdc -40T125 °C -1 to 12.8 bar ±1% fs; 0T50 °C 0.5 to 4.5 V <10 ms IP67
*T0041S0 0.5 to 4.5 Vdc -40T125 °C 0 to 17.3 bar ±1% fs; 0T50 °C 0.5 to 4.5 V <10 ms IP67
*T00F1S0 0.5 to 4.5 Vdc -40T125 °C 0 to 20.7 bar ±1% fs; 0T50 °C 0.5 to 4.5 V <10 ms IP67
*T0031S0 0.5 to 4.5 Vdc -40T125 °C 0 to 34.5 bar ±1% fs; 0T50 °C 0.5 to 4.5 V <10 ms IP67
*T00B1S0 0.5 to 4.5 Vdc -40T125 °C 0 to 45 bar ±1% fs; 0T50 °C 0.5 to 4.5 V <10 ms IP67
1
with built-in IP67 connector
Sensor suitable for installation in The EP sensor (External Probe) is The SA wireless room sensor is battery-
refrigeration cabinets. The local button used inside cabinets or cold rooms to powered and is installed inside rooms to
disables the high temperature signal alarm monitor temperature in combination monitor temperature and humidity.
when the cabinet is off or being cleaned. with supervisory systems. It transmits
The sensor is ready to be installed directly temperature data measured by the two Functions implemented
inside the cabinet with its own fastening NTC probes, and the status of two digital • instant temperature;
bracket. The rear wall has metal shielding inputs, configurable as “door status” and • instant humidity;
that, combined with thermal insulation “defrost status” or for generic use. • monitoring of temperature and
inside the shell, offers better heat humidity thresholds;
insulation, eliminating the influence of the Functions implemented • battery level control in mV;
surface of the refrigerated cabinet. • instant temperature read by the two • wireless signal level control.
sensors;
Functions implemented • monitoring of temperature thresholds
• instant temperature; for high temperature (HACCP) or low Technical specifications
• product simulation temperature; temperature alarm signals;
• monitoring of temperature thresholds • battery level control in mV; Power supply: 3.6 V lithium battery
for high temperature (HACCP) or low • wireless signal level control; 2500 mAh, “AA” size
temperature alarm signals (to prevent Operating conditions: -10T60°C 80% r.H.
products from freezing); non-condensing
• disable high temperature alarm from Degree of protection: IP30
Technical specifications Assembly: wall-mounted
local “Clean” button;
Power supply: 3.6 V lithium battery Dimensions: 127x80x30 mm
• battery level control in mV and residual
2500 mAh, “AA” size
charge in mAh;
Operating conditions: 0T50°C 80% r.H.
• wireless signal level control.
non-condensing
Degree of protection: IP55
Assembly: wall-mounted
Technical specifications Number of I/Os:
Power supply: 3.6 V lithium battery • analogue inputs: 2 NTC 10 K at 25°C
2500 mAh, “AA” size • digital inputs: 2 (voltage-free contact)
Operating conditions: -40T50 °C 80% r.H. Dimensions: 94x102x40 mm
non-condensing Connections: plug-in terminals, wire size
Degree of protection: IP65 0.5 mm2
Assembly: wall-mounted on bracket
Dimensions: 83.9x71.6x34 mm
79
The SI wireless industrial sensor is battery- The CI battery-powered wireless pulse This device acquires data via the wireless
powered and is installed inside rooms to counter is a device used together with signals sent by the sensors or Routers over
monitor temperature, humidity and light energy meters to measure electricity, gas, the ZigBee™ network, and then forwards
intensity. or water consumption, without the need these over a Modbus® RTU RS485 serial
to install electrical cables. line. A CAREL supervisor (PlantVisorPRO or
Functions implemented It can manage two energy meters PlantWatchPRO) or controller can be used
• instant temperature; using two digital inputs, and is ready to manage the rTM system variables. Up to
• instant humidity; for connection of two external NTC 30 sensors can be bound to each Access
• instant light intensity; temperature probes. Closing of the Point, and a maximum of 60 when adding
• monitoring of temperature, humidity contacts on the digital inputs activates two one or more Routers. Up to 7 Access Points
and light intensity thresholds; separate pulse counters. can be connected to the same Modbus
• battery level control in mV; The number of pulses is converted to RS485 serial network, for a total of 111
• wireless signal level control. an energy value (KW, m3) by the CAREL sensors on each serial line.
supervisor or controller with special
software, so as to total and monitor energy
Technical specifications utility consumption. It can manage up to Technical specifications
two energy meters configured to send
Power supply: 3.6 V lithium battery Power supply: 12/24 Vac/Vdc ±10%;
pulse signals.
2500 mAh, “AA” size Operating conditions: 0T50°C 80% r.H.
Operating conditions: -20T70°C non-condensing
Functions implemented
80% r.H. non-condensing Degree of protection: IP55
• two separate pulse counters; Assembly: wall-mounted
Degree of protection: IP55 case, IP40
• battery level control in mV; Serial ports: RS485 Modbus®
sensor cap
• wireless signal level control; Dimensions: 94x300x40 mm
Assembly: wall-mounted
• instant temperature read by two NTC Connections: plug-in terminals, wire size
Dimensions: 94x153x40 mm
probes; 0.5 mm2
• temperature difference between NTC
probes.
Technical specifications
Power supply: 3.6 V lithium battery
2500 mAh, “AA” size
Operating conditions: 0T50°C 80% r.H.
non-condensing
Degree of protection: IP55
Assembly: wall-mounted
Number of I/Os:
• analogue inputs: 2 NTC 10 K at 25°C;
• digital inputs: 2 (voltage-free contact)
Dimensions: 94x108x40 mm
Connections: plug-in terminals, wire size
0.5 mm2
Wireless devices for monitoring temperature, humidity, light and energy
This device is used when the distance This device is used to connect Modbus® This integrates the same functions as
between sensor and Access Point exceeds RS485 instruments via radio when these the EP battery-powered sensor and the
30 m, or alternatively the number of are not accessible using cabled lines, using RO Router, and features two network
network nodes (sensors) exceeds a total a wireless connection to send data from addresses (one for the sensor and one for
of 30. A maximum of 60 Routers can be the instruments to the supervisor. the router).
installed in the wireless network, 48 of The instruments are connected locally on
which can be accessed by the supervisor. the serial line, which acquires data and Functions implemented
The Access Point automatically assigns the forwards them to the Access Point. • instant temperature read by the two
serial address in the order in which these The Access Point is physically connected sensors;
are “bound” (from 200 to 247). to the supervisor, and the instruments • monitoring of temperature thresholds
connected locally to the Router-Bridge for high temperature (HACCP) or low
devices are logically assigned to the temperature alarm signals;
main network (where the Access Point is
Technical specifications • wireless signal level control;
physically connected).
Power supply: 230 Vac -20/+10 %; This is an excellent solution for all
Operating conditions: 0T50 °C 80% r.H. refrigeration and air-conditioning
non-condensing Technical specifications
applications and others with similar needs.
Degree of protection: IP55 The device is a solution for binding Power supply: 12/24 Vac/Vdc ±10%;;
Assembly: wall-mounted all wired devices that require wireless Operating conditions: 0T50 °C 80% r.H.
Dimensions: 98x300x44 mm communicate. non-condensing
Connections: plug-in terminals, wire size It also includes the Router function. Degree of protection: IP55
0.5 mm2 Assembly: wall-mounted
Number of I/Os:
Technical specifications • analogue inputs: 2 NTC 10 K at 25°C;
• digital inputs: 2 (voltage-free contact)
Power supply: 12/24 Vac/Vdc ±10%; Dimensions: 94x300x40 mm
Operating conditions: 0T50 °C 80% r.H. Connections: plug-in terminals, wire size
non-condensing 0.5 mm2
Degree of protection: IP55
Assembly: wall-mounted
Serial ports: RS485 Modbus®
Dimensions: 94x300x40 mm
Connections: plug-in terminals, wire size
0.5 mm2
81
This integrates the same functions as the This module can be configured as a The rTM handheld is a useful device for
CI pulse counter and the RO Router, and wireless I/O actuator for managing loads installation, commissioning and service of
features two network addresses (one for and reading generic inputs. It can be CAREL ZigBee™ wireless networks for the
the pulse counter and one for the router). configured as a thermostat with heat- rTM system.
cool operating logic. When used as an I/O
Functions implemented module, the outputs are managed directly Functions implemented
• management of two separate pulse by Modbus variables (via CAREL supervisor • reading of wireless channels occupied,
counters; or controller with special software). When performed before wireless system
• wireless signal level control; used as a thermostat, it sends the I/O installation (in the fiel );
• instant temperature measurement by status to the supervisor for monitoring. It • measurement of wireless signal intensity
two NTC probes; also integrates the Router function and from Access Point or Router;
• temperature difference between NTC features two network addresses (one for • simplified opening and closing of the
probes. the I/O module - thermostat and one for wireless network during commissioning;
the router). • reset default parameters on Access Point
and Router;
Technical specifications Configured as an I/O module it • assign serial address (ID) to the BP
manages: Sensor.
Power supply: 12/24 Vac/Vdc ±10%;
• 2 digital inputs;
Operating conditions: 0T50 °C 80% r.H.
• 2 digital outputs, 1 A/24 Vac;
non-condensing
Degree of protection: IP55
• 1 analogue inputs (NTC 10 K at 25°C) Technical specifications
Assembly: wall-mounted Power supply: 1.5V “AAA” size batteries
Number of I/Os: Functions implemented Operating conditions: 0T50 °C 80% r.H.
• analogue inputs: 2 NTC 10 K at 25°C; • management of remote loads, reading non-condensing
• digital inputs: 2 (voltage-free contact) analogue and digital inputs; Degree of protection: IP40
Dimensions: 94x300x40 mm • activation of digital outputs from digital Dimensions: 72,5x167,5x28 mm
Connections: plug-in terminals, wire size input;
0.5 mm2 • thermostat management (heat – cool);
• wireless signal level control;
Technical specifications
Power supply: 12/24 Vac/Vdc ±10%;
Operating conditions: 0T50 °C 80% r.H.
non-condensing
Degree of protection: IP55
Assembly: wall-mounted
Number of I/Os:
• analogue inputs: 1 NTC 10 K at 25°C
• digital inputs: 2 (voltage-free contact)
• digital outputs: 2 (1 A, 24 Vac)
Dimensions: 118x300x40 mm
Connections: plug-in terminals, wire size
0.5 mm2
Wireless devices for monitoring temperature, humidity, light and energy
Router Actuator
Router-Bridge
RS485 Modbus®
Router-Bridge th-tune
Access Point
RS485 Modbus®
SA
Router Actuator
RS485 Modbus®
Router Actuator
Router-Bridge
Router-Bridge
energy meter
RS485 Modbus®
RS485 Modbus®
Router-Bridge
MPXPRO
MPXPRO MPXPRO
MPXPRO MPXPRO
MPXPRO
MPXPRO
MPXPRO
MPXPRO EP RS485 Modbus®
SA
SI
s®
bu
od
M
5
48
RS
ir33
Access point
us®
db
Mo
85
RS4 RS485 Modbus®
Router-Bridge
Router-Bridge
ir33
Connectivity
Connectivity is the result of CAREL’s Security CAREL devices, through the supervisory
years of experience in the design and systems, can be equipped with:
Absence of risks in transmitting
production of serial devices for controlling • differentiated access to the unit
information and exchanging important
HVAC/R units. CAREL is continuously according to whether the person
data, especially across networks that can
engaged in technological evolution in the is authorised for maintenance or
be accessed by everyone.
communications industry, paying attention supervision;
to certain fundamental concepts. • secure access via internet or VPN (virtual
private network).
Connectivity
Interfaceability and compatibility with Application example
the most widespread BMS (Building
Management Systems): BACnet™,
LonWorks®, Modbus®, Konnex, SNMP. It
thus becomes easy to:
• manage the unit remotely via modem
and Internet, even with a simple
browser;
Modbus RS485
• inform authorised personnel, wherever
CAREL RS485
Interoperability
The ability to work in distributed
intelligence and with integrated solutions,
acquiring and sharing information to and
from third party devices for:
• better unit management;
• a higher degree of efficiency of the
system (energy savings).
BACnet TCP/IP
Building
Managem
System
Connectivity
Supernode
SN*
Features SNS*M
Supernode, the programmable controller
for managing a large flow of information. Flash Memory 4 Mb
Compact (6 DIN modules) with built-in Ram 512 kb
132x64, pixel blue negative display. Nand Flash 32 Mb
The keypad, located horizontally under Real Time Clock
the display and without screen printing, Max no. serial ports 6
allows customisation of the functions for pLAN
each key (shown in the last row on the
RS485 opto-isolated/tLAN/PST-PLD
display) differentiating them from screen
to screen. Serial 1 card connector
Serial 2 card connector
Supernode has 6 serial ports: USB Master Port
• 2 integrated RS485, one of which is USB Slave Port
opto-isolated; Preset programming key
• 2 slots for BMS plug-in cards; Built-in 132x64 pixel blue negative display
• 2 USB ports (Master and Slave). Built-in 6 LED + 1 key user interface
Black box
The fast digital input that is standard on
all versions allows direct reading of energy Maximum no. inputs 7
meters. PT1000 inputs 2
Ideal as a system coordinator, access for Inputs 0 to 10V 6
two supervisory systems at the same Inputs 0 to 1V 6
time and masters with several serials Inputs 4 to 20mA or 0 to 20mA 2
ports makes it adaptable to all types of NTC inputs 6
applications and needs.
Inputs 0 to 5 Vdc, ratiometric 6
Voltage-free contact digital inputs 3
Technical characteristics
Fast digital inputs for pulse counter 1
Power supply: 24 Vac -15/10%, 50/60 Hz o Input selection via software
48 Vdc (36 Vmin to 72 Vmax)
Max no. analogue outputs 2
Operating conditions: -10T60 °C, 90% RH
non condensing 0 to 10 Vdc outputs 1
Protection rating: IP20 –Front IP40 PWM outputs (cut-off ) 1
Certification: CE / UL Max no. digital outputs 2
Assembly: DIN rail SPST relay outputs 1
I/O Number: SPDT relay outputs 1
• analogue inputs: from 6 to 8 Max no. SSR outputs 2
• digital inputs: from 4 to 6
Power supply 48 Vdc
• analogue outputs: 2
Power supply 24 Vdc
• digital outputs: 2
Serial Ports: pLAN, 2BMS, 1FieldBus standard
Dimensions: 6 DIN (105x110x60) optional
Connections: plug-in terminals
87
(*): The tLAN CANNOT be connected to PCOE00TLN0 & PLD* terminals at the same time! ZigBee™
protocol
pCO manager
RS485 Modbus®
Modbus® TCP/IP
serial card 1
Probes
SPKT*: 4 to 20 mA DPW*:
pressure probes - 0 to temperature
5 V ratiometric probes & humidity
PCOS004850:
status
BACnet™ MS/TP
P1 P2 P3
RS485
PCO1000BA0: probes for civil
RS485 serial board
GNX + – RS485
CANbus boards
BACnet™ interface
e-dronic DPP*: temperature &
humidity probes for DPD*: temperature &
PCO10000F0: LON industrial environments humidity probes for ducts
PCOS00KXB0:
boards
Konnex board
Connectivity
XML
e-mail
TCP/IP
XMLXML
XML TCP/IP
e-mail
e-mail RTU
e-mail
TCP/IP
TCP/IPTCP/IP
RS485 Modbus®
RS485
CAREL
ECHELON®, LonWorks®, and the ECHELON® logo are trademarks of ECHELON® Corporation registered in the United States and other countries.
89
FieldBus connectivity
For the purpose of communication sensors, Belimo actuators, etc. In
between controllers from different this way, the pCO sistema controller
manufacturers, CAREL offers a wide manages not only the individual unit
variety of solutions that allow pCO but also the entire air conditioning/
controllers to interface with devices cooling system.
in the field such as valves, VFDs, serial
user
interface
tLAN
16 TER
MAS tLAN
...up to
16 MASTER units F
CANbus
...5 ...2 1 ...5 ...2 1
(BMS: PCOS00HBB0, FieldBus: PCOS00HBF0)
...up to ...up to With the CANbus option, pCO controllers can be
5 SLAVE units 5 SLAVE units
connected to the CAREL system to manage fan
coils (e-drofan), thus allowing easy management
of the system and optimising comfort and
operating costs through synergy between
controllers.
F Available for both FieldBus and BMS.
RS485
(PCO100FD10)
Probes
EVD0 pCOe
Modbus®
F
TH-tune Probes
Centrifugal compressor
Power+
CAREL humidifiers
MP BUS
(PCO100MPB0)
BMS connectivity
Connecting CAREL controllers with the card that communicates with the
BMS can be done as follows: protocal used by the BMS (BACnet™,
• directly, thanks to the capacities of SNMP, LON…); A B
the pCO series system for selecting • by integrating the drivers for
the protocol to use (CAREL, managing the CAREL proprietary
Modbus®); protocol (OP® server) in the BMS.
• through the connection with a serial connect
RS485
(PCOS004850)
A B
The CAREL slave protocol is for interfacing with
PlantVisorPRO, PlantWatchPRO or OPC server
supervisor systems.
B
A B
A B A B A B
SNMP
B
XML
pCOWeb
B (PCO1000WB0)
CAREL Supernode:to create gateway solutions Third party BMS: to integrate controllers
between CAREL or Modbus® RTU and from different protocols and functions in a
Modbus® more advanced protocols or area control single monitoring system.
units.
Webgate: Gateway between the CAREL
PlantVisorPRO: to monitor CAREL protocol and a local TCP/IP network with
controllers and/or with third party SNMP v1 protocol or Webserver, with the
Modbus® RTU. possibility of customising the HTML page.
93
PP2ST* PP2ST*P*
PlantVisorPRO is the CAREL monitoring and and detailed reports, relating to system PlantVisorPRO is a scalable solution that
supervision system that allows complete variables. offers the user the possibility to activate
control and optimisation of refrigeration specific function packages according to
and air conditioning systems. KPI – Key Performance Indicator requirements.
It offers an intuitive and customisable Control of the effective controlling Below is the offering of packages for
interface for the display and configuration capacity of a device depending on the the solution and the relative functions
of the system. operating set point, the differential and any activated:
PlantVisorPRO guarantees remote access defrosting performed.
GREENRETAIL Floating Suction
to all devices connected to it via the LAN
Energy Dew Point Broadcast
or MODEM connection.
The system is available as a complete all- Analysis of CO2 emissions, power Parameter control
in-one solution: the product integrates all consumption and the cost of energy per KPI
field connections, digital inputs and output pricing zone in order to identify energy Energy
relays. optimisation areas. SAFETY Parameter control
The installation formats are defined as RemotePRO connection
follows: Simplified commissioning ModbusSlave
Version No. of Variable log Reduction of installation times in the EXTENDED Logical devices
Instruments system and control of the installation. Custom algorithm
STANDARD 90 1400 Thermodynamic debug ENERGY KPI
HYPER 300 3500 Analysis of the thermodynamic behaviour Energy
of the refrigerated counters. SAVING Floating Suction
Dewpoint Broadcast
Energy Saving Configuration propagation
Optimisation and monitoring of system Propagation of system configurations from
performance: specific functions for the one to “n” devices.
increase in installation efficiency and for
the analysis of energy consumption trends.
Alarm management
Floating Suction Pressure Control
Detection and signalling of every alarm
Automated modification of the
situation, with remote interaction for
refrigeration unit set point depending on
efficient management of maintenance and
the cooling request from the refrigerated
after-sales service operations.
counters it serves.
Parameter Control
Recording and notification of the
unauthorised modifications on critical
system parameters in order to preserve
optimum operating configuration.
PWPRO* IOM*
Refrigeration
utilities
retrofit
convenience store
service area
Refrigeration Refrigeration
utilities units
97
Air-conditioning
building
hypermarket
PlantVisorPRO is the ideal solution for large areas where there are
a large number of units and advanced control and management
are required.
remotePRO
RVSTD*
The remote supervision system allows required by the customer. be guaranteed. It offers the possibility
analysis and comparison of the data Centralised notification of alarms and to be notified immediately regarding
collected by local supervisors on each comparative analysis between the systems. any malfunctions and includes all tools
installation, using just one interface. necessary for solving problems in the field
Whatever your application, CAREL remote Data analysis directly from the office;
is a secure and reliable tool for keeping KPI comparisons for evaluation of system • RVSTDDS000 – Centralised data
systems installed in different locations operation: alarms, energy, temperature management: dedicated to whoever
under control. report. Offline reports without having to wants to support their customers with
All local supervision products offered by connect to the individual sites. comparative analyses of the different
CAREL can be connected to the remote system data. Offers reports, graphs and
supervisor: Call Centre statistical calculations on the variables
• PlantVisorPRO; transferred from the local supervisors.
Advanced tool for the management of
• PlantWatchPRO;
routine and special system maintenance.
• pCOWEB. Version No. of sites Variables
via LAN or modem connection.
Versions RVSTDDS000 50 ---
Maintenance • RVSTDDS000 – Remote Control RVSTDDM000 50 7.000
Maintenance Technician: dedicated to plugin to
Centralised control of all systems in order
the persons in charge of maintenance on activate on
to reduce management costs of the
sites where correct operation must always RVSTDDS000
sites and guarantee the level of security
remotepro
80%
The CAREL E2V smart series electronic Two families of valves with similar CAREL also offers a complete range of high
expansion valves bring together the architecture, covering a consecutive range capacity valves, where energy efficiency
renowned reliability of the CAREL E2V and of capacities, with elbow connectors, is essential and precision control is one of
the versatility of a removable cartridge, usable indifferently on the inlet or outlet. the best ways to ensure this.
plus the option of a convenient integrated Complete installation freedom is further Unrivalled tightness in closing and
sight glass. supported by that fact that the various the built-in sight glass mean separate
The motor block can be dismantled to components, stator, motor block and liquid solenoid valves and liquid indicators
simplify welding, thus preventing the risk sight glass, can be fully dismantled. are not required, while the possibility to
of overheating and damage. As well as on the E4V, the liquid sight glass completely dismantle the parts ensures
A movable element with Teflon gasket, is now also available on the E3V. Fitted with accurate welding without the risk of
plus a calibrated spring seal mechanism, moisture indicator, this is very useful for damage.
are the heart of the CAREL system that verifying correct refrigerant flow and valve On chillers and large air-conditioning units
ensures unrivalled tightness, meaning the operating conditions. having a valve that can be dismantled
valves can work with very high pressure Both E3V and E4V can operate in both means only the valve body needs to be
differentials. directions, representing the ideal handled when installing the piping, and
E2V smart also offers a removable metal solution for reverse-cycle applications by the motor and stator can be fitted later
filter to trap solid residues that may ensuring simple installation and saving on when the unit is being completed.
damage the valve or cause a decline in installation of a solenoid valve and liquid Three models of valves with inline fittings
efficiency. indicator. and copper connectors, each with an
The family of E2V smart valves comes in 8 E3V and E4V offer solutions for all needs in extended operating range:
sizes and covers a wide range of capacities: the following applications: • E5V: Ø35/35mm, up to 530 kW*
• air-conditioning: 0.3 to 58 kW (R410A, • air-conditioning: 12 to 290 kW (R410A, • E6V: Ø42/42mm, up to 890 kW*
tev= 4.4 °C, tcond= 38 °C, sc= 1K) tev= 4.4 °C, tcond= 38 °C, sc= 1K) • E7V: Ø54/54mm, up to 1850 kW*
• refrigeration: 0.15 to 38 kW (R404A, tev= • refrigeration: 8 to 260 kW (R404A, tev= (*) R134a, tev=2 °C; tcond= 45.0 °C; sc= 3
-12 °C, tcond= 45 °C, sc= 3 K). -12 °C, tcond= 45 °C, sc= 3 K).
The E2V (amily (which can comfortably Based on CAREL’s extensive experience Ultracap is the new emergency power
handle operating pressures up to 45 barg) in electronic valve drivers, EVD evolution supply device for electronic valves,
has been further extended to include a is available as a “single” and “twin” driver, the natural completion of the EVDEvo,
product developed specifically for use with the latter able to control two valves both single and twin versions, ensuring
transcritical CO2 systems. independently, with the most commonly- complete closing of the valves even when
A powerful motor, thicker walls and highly used refrigerants (see the instruction there are sudden mains power failures.
resistant materials are just some of the sheet). Simple graphics and a series of LEDs Exploiting ELDC (Electric Double Layer
reasons why these valves have achieved offer an immediate overview of operating Capacitor) technology, Ultracap can supply
record levels of performance, with status and the main driver functions. immediate, reliable and clean emergency
operating pressures and differentials that energy, representing a major step forwards
are hard to find in products made by other A powerful removable graphic display compared to conventional battery-based
manufacturers. (EVDIS**0) can be used to configure the systems, including as regards disposal of
Designed for transcritical CO2 applications, driver, providing clear and immediate used materials.
these can naturally also be used for information on operating status and Ultracap has been designed to give 10
subcritical cycles, where higher pressure allowing the controller to be started years’ trouble-free silent operation, without
resistance - exceeding 45 barg - and very the first time after selecting just four requiring periodical checks or having to
precise control are required. parameters: replace batteries.
Complete tightness guaranteed by a • refrigerant used; Ultracap means immediate energy: just 5
Teflon gasket, and continuous and regular • valve model; minutes (4 minutes for CAREL valves) after
movement are the outstanding features of • type of pressure probe; power is restored, the system is already
the E2V platform that are also available in • application (chiller, cabinet, etc.). recharged and active (in practical terms
this E2V for high operating pressures. EVD evolution can operate in stand-alone the same time the compressor takes to
E2V**C comes in five sizes, covering mode, or connected to a pCO or the restart…).
subcritical cycle cooling capacities up to PlantVisorPRO supervisor. The extreme reliability of Ultracap
20 kW (R744, tev= -10 °C, tcond= 20 °C, EVD evolution can also manage other combined with the exceptional tightness
sc= 5 K. functions in addition to superheat control, of CAREL valves, eliminates the need for
such as hot gas bypass, evaporation solenoid valves even in the most critical
Technical specifications pressure control (EPR), valve control for gas applications.
coolers in transcritical CO2 circuits. Ultracap can be connected to the EVDEvo
Limit pressure values: as well as all the pCO5 family controllers,
• maximum working pressure (MWP):
Technical specifications with extremely simple installation, just like
140 bars (2030 psi)
connecting a battery module.
• maximum operating pressure differential Power supply: 24 Vac 50/60 Hz,
(MOPD): 120 bars (1740 psi) 24 Vdc (±15%)
• PED: not applicable, group 2 fluids, art. Operating conditions: -10T60 °C, 90% RH Technical specifications
3, par. 3 non-condensing Power supply: 24 Vac 50/60 Hz,
Operating conditions: Degree of protection: IP20 24 Vdc (±15%)
• refrigerant side: -40T65 °C (-40T149 °F) Assembly: DIN rail Operating conditions: -25T50 °C, 90% RH
• installation environment: -30T50 °C Number of I/Os: non-condensing
(-22T122 °F) • inputs: 2 digital Degree of protection: IP20
Closing steps: 550 • outputs: 2 voltage-free contacts Assembly: DIN rail
Control steps: 480 Serial ports: 1 Dimensions: 70x110x60mm
Dimensions: 70x110x60 mm (4 modules DIN)
(4 modules DIN)
EXV sistema - electronic expansion valves and drivers
Ultracap Technology
ultracap
VBAT
G
G0
with ultracap
be connected
30VA 2AT
VBAT
G
other loads
G0
voltage-free
relay output for
utilities up to alarm
230 Vac signal
without ultracap
VBAT
COM 1
NO 1
1 3 2 4
G
2 AT
30VA Power Supply E XV connection Relay
G0
G
personal computer
5V
network
tLAN
GND
Rx/Tx
GND
EVDCNV00E0: OPEN
converter
CLOSE
DI1
DI2
RS485 version
S1
S2
S3
S4
GND Tx/Rx
External controller
DI1
DI2
0 to 10 V 4 to 20 mA
Modbus + RS485
1 2
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
J127
J9 J10
PCO*:
digital input
digital input (defrost)
programmable
4 to 20 mA and 0 to 5 V S1
J30 J29
controllers
ratiometric probes
J1 J24 J2 J3 J4 J5 J6 J7 J8
S2
NTC: low temperature
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
probes J9 J10
J127
PCO*:
4 to 20 mA and 0 to 5 V programmable
S3 J30 J29
controllers
ratiometric probes J1 J24 J2 J3 J4 J5 J6 J7 J8
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
probes J9 J10
J127
PCO*:
PlantVisorPRO J30 J29
programmable
J1 J24 J2 J3 J4 J5 J6 J7 J8
controllers
Condenser controller and inverters
107
To complete its range of products, CAREL pumps and compressors fitted with The use of inverters with electric motors
offers a series of modules suitable to satisfy asynchronous three phase motors and the applied on the water pumps or on fans
different particular applications of HVAC/R innovative power+, it can control BLDC/ allows modulation of load and accurate
units, for fan, pump and compressor speed BLAC brushless motors with permanent and efficient process control from an
control. magnets, which are used in new energy point of view.
In fact, optional modules are available generation compressors.
that have been specially designed, and In particular, compressor modulation
therefore optimised, for increasingly allows significant results in terms of
important functions in today’s air energy saving and at the same time
conditioning and refrigeration units. optimise operation of all unit components.
Modulation of flow rate of the refrigerant
As regards condensing pressure control, and primary fluids exploits the full capacity
the fcs range of controllers is available, of heat exchangers at reduced load and
allowing the possibility to be used in decreases compression ratio at the same
stand-alone configuration or connected to time. To exploit the modulation capacities
a controller in the pCO sistema range. of these compressors in full, the use of the
This range of controllers is available for latest generation electronic expansion
all requirements: single and three-phase valve is essential. For this reason, pCO
versions exist. sistema represents the complete system
made-to-measure for the new generation
Regarding parametric controllers, such as of high efficiency units.
the µchiller range, CAREL offers a range of
controllers with single phase power supply The range of VFD, NXL series variable
in the MCHRTF range, which are more frequency drives, is developed specifically
suitable for this type of controller. for applications with:
This speed controllers are also compatible • variable flow rate on air handling unit
with programmable pCO sistema fans;
controllers. They can manage single phase • modulation of compressor speed;
230 Vac fans with 8, 10 and 12 A current. • variable flow rate on system supply
pumps and evaporator pumps on the
The inverter represents one of the chillers;
state-of-the-art solutions regarding • control of condensing pressures on
energy saving. The CAREL inverter offer ventilation units.
can boast two product families: The
VFD NXL range, suitable for driving fans,
Speed controllers and inverters
PSD* NXL*
power+ is an inverter that can control compressor tested by CAREL can be The NXL range is available in power ratings
compressors with BLDC/BLAC brushless completed with a click, if used with the from 0.37 to 30 kW, with single-three
motors with permanent magnets without controllers of the pCO sistema. The CAREL phase power supply and three phase
the aid of a position sensor, thanks to controller not only manages the electric output, protection rating up to IP54, for all
the use of “sensorless” technology. The parameterisation of power+ but also the applications with variable capacities.
integrated functions of Power+ are complete thermodynamic control of the Control is via 0 to 10V or 4 to 20 mA
focused on controlling the compressors: compressor according to the requirements analogue signal or via Modbus® serial
• the acceleration ramp, programmable of the compressor manufacturer. communication, which can integrate
in steps, respects the requirements of the device functions with the pCO range
every application: controllers management software or the
• a PTC input guarantees heat protection Technical specifications PlantvisorPRO supervisor.
of the compressor.
Power supply:
Other advantages are: wide operating
• single-phase: 200 to 240 V 12 A or 16 A;
power+ also has an STO input (Safe range, easy installation and use, low
• three-phase: 380 to 480 V 14/18 A (50 °C)
Torque Off ), which can be used to cut-off noise emissions, high protection rating
or 22.5 A;
the compressor power supply in the against electromagnetic interference and
Operating conditions: 60 °C 95% R.H. non
event of an emergency, for example particularly compact book-like” design.
condensing
following activation of a high pressure The NXL range is the ideal solution for all
Protection rating: IP20/IP44
switch. Moreover, power+ can manage operating environments, for completion
CE UL, certification:
the compressor in an intelligent manner and integration of the range of CAREL
Assembly: panel or semi-builtin
in extreme conditions: algorithms are products in order to obtain maximum
Number of I/Os:
available for automatic reduction of the efficiency and energy saving in HVAC/R
• digital inputs: 1 STO (Safe Torque Off )
switch-over frequency or rotation speed in systems.
and 1 PTC;
order to prevent the compressor stopping
• digital outputs: 1 voltage-free contact
in high temperature conditions.
In household use, noise is limited to
configurable relay up to 240 Vac 5 A Technical specifications
Serial Ports: RS485/Modbus® Power supply:
a high frequency switch-over, up to 8
Dimensions: 164x183x265 mm max. • single-phase: 208 to 240 V from 0.37 kW
kHz. The electromagnetic compatibility
Connections: screw clamps to 1.5 kW;
(EMC), is such to allow use in the home,
also respecting the strictest standards • three-phase: 380 to 500 V from 0.55 kW
regarding harmonic emissions. to 30 kW;
Product installation is made easier by Operating conditions: -10T50°C 95% R.H.
the flat design of the electronics, as well non condensing
as availability of removable brackets for Protection rating: IP20, IP21, IP54
fixing. In this way, the heat sink necessary CE UL, certification:
to dispose of the heat up to 60°C in the Assembly: panel
environment, can be positioned behind Number of I/Os:
the control board, thus greatly reducing • analogue inputs: 2 x 0 to 10 V or
the space occupied inside the control 0 to 20 mA
board. The IP protection rating and the • digital inputs: 3 programmable
protection gasket guarantee a protection • analogue outputs: 1 x 4 to 20 mA
rating of IP44 on the heat sink side. • digital outputs: 1 NO/NC relay
power+ has also been tested with most Serial Ports: RS485/Modbus®
BLDC compressors available on the Dimensions: 195x519x237 mm max.
market: SCI (Siam Compressor Industries), Connections: screw clamps
Samsung, Hitachi, Toshiba.
The configuration of power+ for a BLDC
FCP is a speed controller for single phase The range of FCS and MCHRTF single
fans on stand-alone units with up to 2 phase controllers has been developed to
circuits. It manages the fan depending on control fan speed on condensing units
the pressure variation in the condenser depending on the signal sent from the
circuit, in order to maintain the set point controllers. In particular, the FCS range,
value, using a 0 to 5 V signal from the receives a 0 to 10 V signal, while the
ratiometric pressure transducer (SPKT*R0) MCHRTF, pCO, µchiller, ir33 universal and
positioned in the water circuit. It is used pRack range controllers, receive a PWM
on condensing units. It can manage signal.
asynchronous axial motors (specific for
the phase cut controller), on loads up Technical specifications
to 8 A/230 Vac. Available in the master/
Power supply: 4, 8, 10 and 12 A/230 Vac
slave version or power device (as current
Operating conditions: -10T50 °C
MCHRTF80A0, in IP54 version).
Protection rating: IP00
Assembly: panel
Technical specifications Number of I/Os:
Power supply: 230 Vac -15/10%, 50/60 Hz • analogue inputs: 0 to 10 V or PWM
with autosensing Dimensions: 82x107x58 mm max.
Operating conditions: -20T50 °C, <85% Connections: screw clamps for cables with
R.H. non condensing cross-section of 1.5 mm2
Protection rating: IP54
Assembly: panel
Number of I/Os:
• analogue inputs: 2 ratiometric
0 to 5 Vdc, 1 NTC 10 K at 25 °C
• digital inputs: 1 configurable
• analogue outputs: PWM
Serial Ports: RS485 (with additional
optional board)
Dimensions: 139.8x134.8x89 mm
Connections: spring clamps for cables
with cross-section of 1.5 mm2
fans
Speed controllers and inverters
The IP55 three phase range, suitable for The IP20 range, suitable for installation
outdoor environments, can be controlled on the control board, can be managed
by a 0 to 10 Vdc analogue signal or with by controllers with 0 to 10 Vdc analogue
PWM signal (phase width modulation). signal or PWM signal (phase width
The range, which envisions the control of modulation). This envisions the control of
motors with current draw of 6 to 40 A, is motors with current draw of 9 to 40 A, and
fitted with a control board, able to supply a control board, which supplies power to
power to the load, in linear or square the load, in linear or square mode, with cut
mode, with cut off, threshold, minimum off, threshold, minimum and maximum
and maximum speed functions, using the speed functions, using the trimmer on the
trimmer on the board. board.
fans
+800001001 - 2.2 - 01.09.2012
CAREL INDUSTRIES reserves the right to modify the features of its products without prior notice.