6 Fire Protection System
6 Fire Protection System
MANUAL
FOR
A) Introduction
B) System Description
C) Design Data & Parameter
D) Operation Procedure
E) Maintenance Procedure
F) Sprinkler pump and control valve characteristic table
A) Introduction
B) System Description
C) Design Data & Parameter
D) Operation Procedure
E) Maintenance Procedure
F) Hosereel pump characteristic table
A) Introduction
B) System Description
C) Design Data & Parameter
D) Operation Procedure
E) Maintenance Procedure
A) Introduction
B) System Description
C) Design Data & Parameter
D) Operation Procedure
E) Maintenance Procedure
1.5) WET CHEMICAL FIRE SUPPRESSION SYSTEM
A) Introduction
B) System Description
C) Design Data & Parameter
D) Operation Procedure
E) Maintenance Procedure
A) Introduction
B) System Description
C) Design Data & Parameter
D) Operation Procedure
E) Maintenance Procedure
2) EQUIPMENT CATALOGUES
7) AUTHORITIES RECORD
9) SOFTCOPY CD
A. Introduction
Each area protected by sprinkler system shall have individual alarm valve and
other components as described above, along with flow switch, inspection test
connection and flush connection. Each of the alarm valves shall taps water from
nearest Sprinkler main.
The flow switch is provided with dry contacts for monitoring through fire alarm
system on the activation.
The sprinklers are of upright, pendent and Conventional Sprinklers and located
on branch pipes as per fire codes followed. The sprinklers have a bulb with
temperature rating of 68 deg C.
B. System Description
The Sprinkler System is designed to Ordinary Hazard III for Hawker Centre Area,
Determination of the areas/rooms to be protected by sprinkler shall comply with
SS CP52 Code: 2004.
Water flow switches are incorporated into the sprinkler system. Activation of any
one of the flow switches will result in sounding of the general alarm.
Simultaneously, a signal is transmitted by the Main Alarm Panel (located at the
first storey FCC Centre, near at FFL 1) to SCDF via the Decam line.
One number of 4-way breeching inlet for basement sprinkler tank is located at
Level 1. It’s readily accessible to SCDF in the event of emergency.
Pre-set pressure switches in the sprinkler pump room control the automatic
starting of the sprinkler pumps. In the event of fire, sprinkler bulb will break when
pre-determined operating temperature is attained and this will cause water
pressure to drop in the system. Once it reaches the pumps pre-set pressure the
jockey pump will cut-in, further drop in pressure will cause the duty sprinkler
pump to start automatically and run continuously until it is MANUALLY
STOPPED at the pump controller.
The incoming water supply from PUB mains supplies water to the
compartmented concrete sprinkler tank at Basement Sprinkler Pump Room. The
tank has a total effective water capacity of 190 m³. The tank is combined fire tank
with other stratas in the building.
C. Design Data & Parameter
Type of Temperature
K-factor Response Area
Sprinkler Rating
Hawker Centre, Toilets, Rooms and
Conventional 68 °C 80 standard
above the celing areas
1 x Full Duty Electrical driven pump of capacity OH III at 30m height has been
provided as the duty pump (Completely Setsco approved with controller)
1 x Full Duty Electrical driven pump of capacity OH III at 30m height has been
provided as the standby pump (Completely FM/UL Listed and approved with
controller)
A vertical inline jockey pump of capacity 60 L/M at 57m head is used for
pressurizing the sprinkler system
A separate test line is provided to check the pumps performance. The sprinkler
system is tapped of independently for all the areas with separate alarm valves
3. The system is pressurized upto the control valve at a pressure of on the above
table through the pressurizing unit comprising of Jockey pump.
D. Operation Procedure
Normal Mode:
The Sprinkler system network shall be always pressurized with water from the
main pipe connected to pump dischrge. The Control Valves should be always in
open condition and the flushing line valve (2” gate valve) should be always in
closed condition.
Fire Mode:
The system consists of Sprinklers, which will be heated up in Fire condition. Due
to expansion of the liquid inside the glass tube, (Part of sprinkler) will burst and
the orifice of sprinkler will be opened. Water comes out from the orifice in a
pattern and sprinkled over automatically for the Fire to be quenched.
Open the drain valve of sprinkler network and gradually open the network
isolation valve. Now the water will enter to the sprinkler network and the pressure
will increase also the water will escape through drain valve with air bubbles.
Close the drain valve after all the air bubbles is evacuated from the network.
Now the sprinkler network is fully charged and the system pressure will be equal
to the sprinkler network pressure.
Check once again for any leak or dropping of water from any part of system, and
finally put the system in automatic operation.
a) To check the sprinkler system are installed in accordance with CP52 and the
approved shop drawings.
b) To conduct hydrostatic tests from sprinkler control valve to the branch lines.
The pipework is hydrostatically tested to 200 psi for 8 hour. The control valve
assembly is to be tested separately.
Sprinkler Control Valve
a) To ensure that all valves except for drain & test valves are to remain in the
OPEN position strap and padlock in their normal operation position.
b) To conduct test at the alarm gong by allowing sufficient water to pass through
the water motor.
c) To check the pressure readings at the sprinkler control valve and to remain
steady.
d) To check that the breeching inlet and labelling glass panel are in satisfactory
condition.
b) To determine the minimum, rated and peak loads of the fire pump by
controlling the quantity of water discharged through the flow meter.
d) To stimulate operation failure for duty pump, standby pump to comes in after
few seconds delay.
c) To determine the cut-in and cut-out pressure for the jockey pump.
e) To check the cut-in time between the duty and standby pumps
f) To check that in the event the duty pump set fails to operate and the system
pressure continues to fall to present low pressure limit, the standby pump will
automatically come into operation and continue to do so until manually shut
down.
g) To confirm that the following indications at the pumps control panel are
working satisfactory:
h) To check that the sprinkler pump status (pump running and pump fails to start)
are being monitored in the MAP panel at 1st storey FCC.
E. Maintenance Procedure
Control Valve
a) Regular check to ensure all sprinkler control valves are secured in OPEN
position by means of straps and padlocks, preferably at least once a month.
b) Control valves are numbered and maintenance staff must be familiar with the
portion of the system that they control. An inspection should be made monthly
and the conditions of each valve must be recorded. The report should show
that the valves are:
● In open or close position
● Strapped and padlocked
● In good operating condition, turn easily with no leaks
● Readily accessible
c) If the valves are in unsatisfactory condition, the Maintenance Officer-In-Charge
must be notified and the condition should be corrected as soon as possible.
Valve stems should be oiled or greased at least once a year.
d) At each monthly inspection of control valves, the pressure on the system
should be recorded to make sure that the water pressure is being maintained.
The maintenance of proper pressure is important and provision should be
made to check the system gauges with an inspector’s gauge every year to
ensure reliability of readings.
d) For building extensions when new partitions or enclosures are erected, the
required extension of the sprinkler system in the new areas should be
completed promptly.
Sprinkler Heads
a) Sprinkler heads should be checked regularly to make sure that they are in
good condition, free from corrosion, not painted or whitewash and not bent or
damaged. It should be replaced when they are painted, corroded or damaged.
Piping
a) Piping should be kept in good condition and free from mechanical damage or
corrosion.
b) Sprinkler piping should not be used as support for ladders, stock or other
materials.
Pipe Hangers
a) Hangers should be kept in good shape. Broken or loose hangers should be
replaced or re-fastened.
b) Broken or loose hangers may put undue strain on pipes and fittings, causing
leaks and may interfere with proper drainage.
Monthly Test
a) Inspect all water storage tanks and drains and clean/flush out the tanks as
necessary. Check that the stop valves at tank inlets, interconnecting pipes
and pump suction pipes are secured in fully OPEN position. Verify the
operation of the automatic tank filling mechanism. Visually check that tank
contains requisite amount of water and verify the operation of float-less level
control units.
b) Check and verify that sprinkler control valves are strapped and padlocked in
open position.
c) Check and verify that the drain and test valves are secured in fully CLOSED
position.
g) The entire sprinkler system should be inspected to ensure that they are free
from damage, corrosion, grease, dust, paint or whitewash and should be
replaced when necessary.
j) At monthly inspection of the batteries for control panels for pump to ensure
fully charge condition.
Sprinkler Pump 4
CC-SP-B1-4 3 300 - -
(Stand-by Electric Pump)
A. Introduction
B. System Description
The hosereel is of double pivot type, which can swivel in both direction and is
fitted with 1” X 30-meter hose, nozzle and stopcock.
Level 3 & Level 2 Hawer center water supply to hoseeel system is served by a
set of pumps, water from the 190 cu. meter tank located at Basement.
The automatic start and stop of the hosereel pumps is controlled by pressure
switches set to a pre-set pressure. In the event of small fire, the hosereel
stopcock and nozzle are opened and cause the system pressure to drop. Once it
reaches the pre-set cut-in pressure, the duty hosereel pump will automatically
start and run continuously until the hosereel stopcock and nozzle are closed. The
system pressure will built up and the duty pump will stop-automatically once the
cut-off pressure setting is reached
The hosereel system is design to comply with the SS 575 : 2012 (CP29). At all
times the most remote hosereel which are in operation simultaneously should
give at least a flow rate of 24 litre/min with throw distance of not less than (6)
meter (20 feet).
Hosereel Electric Pump Control Panel
Make : Trident
Model : -
Starter : DOL starter
Nominal Rating
Pump
Hosereel Pump
Designation
Flow(L/min) Pressure(kPa)
Hosereel Pump 1
HP 1 72 550
(Duty Electric Pump)
Hosereel Pump 2
HP 2 72 550
(Standby Electric Pump)
D. Operation Procedure
11.1 Piping
11.4.4. This may be done with the test drain on the sensing line.
The examination should be extended to include the
condition and reliability of the electric power supply.
11.5. Procedure or Test Running of Hosereel Pumpset
The pump control panel controls the automatic starting of two (2) electrically
driven hosereel pumps.
There is also provision for manual starting of hosereel pumps by turning the
mode selector switch to manual position, each individual hosereel pumps can be
started manually using the ‘ON’ push button and can be stopped using the ‘OFF’
push button.
There is no selector switch for the two hosereel pumpsets at the controller as the
pumps is automatically change over for every starting sequence during normal
operation. This allow for fair wear and tear to the two pumps.
E. Maintenance Procedure
Monthly Test
Annual Test
Introduction
The dry riser system is one of the front line firefighting system for SCDF in the
event of emergency. It is designed and installed in accordance to SS575.
There are 4 no’s of dry riser serving the Hawker Centre Area, 2 no’s is
connected to a 4 ways breeching inlet & 2 no’s connected to a 2 ways
breeching inlet with instantaneous coupling house in steel cabinet situated at
1st storey Staircase 4 and bulk meter area for easy access in the event of
emergency.
System Description
The dry riser landing valves which form part of the system are strategically
located for easy reach during emergency and is brought into operation by
coupling the fire standby hose to the landing valve which is connected to
already pressurized pipe (with water from fire engine).
Design Data & Parameter
Fire fighting lobby 2 & Smoke stop loby 2 (Staircase 3 & Staircase 4 ) served
by 4 way breching inlet which was located at level 1 near the ST4 and Dry
Riser with DR landing valves strategically located such that all accessible parts
of the building can be adequately reached with a 2x30m Standby Hose
connected to a DR landing valve and that coverage for 1 no. DR landing valve,
Staircase 5 & Staircase 6 served by 2 way breching inlet which was located at
level 1 near the bulkmeter and Dry Riser with DR landing valves strategically
located such that all accessible parts of the building can be adequately
reached with a 2x30m Standby Hose connected to a DR landing valve and that
coverage for 1 no. DR landing valve,
DR landing valves are located in DR riser or Shaft whereas some are exposed.
Standby hose is sited in near vicinity to a DR landing valve. The standby hose
is housed in cabinet when installed in exposed areas.
Operation Procedure
The dry riser landing valves which form part of the system are strategically located at
each floor level for easy access during emergency and is brought into operation by
coupling the fire hose to the landing valve connected to a fully charge up riser pipe.
The landing valves are protected from misuse by means of straps and locks.
a) To check the dry riser system is installed in accordance to code SS575 and to
the approved drawings.
b) To conduct hydrostatic tests for dry riser system (pressure reading shall be
measured at the lowest point of the system) to 200 psi for two (2) hours.
System Earthing
Maintenance Procedure
Landing Valve
All landing valves shall be in close position with straps and locks.
The dry riser is installed with automatic air release valve at the highest point and is
checked for leakages when water is charged into the system.
b) Ensure each landing valves are strapped and locked in close position.
c) The dry riser system to be pressure tested for leakages on a yearly basis.
e) Inspect electrical earth for Dry Riser System for damage or disconnect.
1.4 ADDRESSABLE FIRE ALARM SYSTEM
Description
Addressable Fire Alarm System installed in this development consists of Main Alarm
Panel located in the FCC and Sub Alarm Panels are located at L1 FFL 1 (OR), L1
FFL2 (HC), L4 FFL (OR), L9 FFL (SR), L11 FFL (SR), L13 FFL (SR), L15 FFL (SR),
L17 FFL (OR), L21 FFL (OR), L32 FFL (OR) and L42 FFL (OR) respectively.
Main Alarm Panel is networked with Floor Sub Alarm Panels which is then connected
to various devices located throughout the protected building. These devices include
smoke sensors, manual callpoints, alarm sounders, strobe lights, sprinkler flowswitch
interfaces and other devices.
Since, HC Sub Alarm Panel is linked with Main Alarm Panel at FCC. Thus, all the
isolations and resseting of fire alarm can be controlled from both FCC and HC Sub
Alarm Panel at L1 FFL2.
Operation and
Maintenance Manual
PART 1: OPERATION MAINTENANCE
MANUAL CONTENTS
Proposed Project Glory
Tan Ka Seng
Acclaim Systems Pte Ltd
Year: 2021
OPERATION MAINTENANCE MANUAL CONTENTS
(HAWKER CENTRE) PROJECT GLORY
Operation
System Maintenance
Important Notice
Inadequate maintenance is the most common cause of fire alarm malfunctions. All panels, detectors,
devices, accessories, batteries and system wiring should be regularly maintained and tested by the
Trained Authorized Agent following procedures supplied by the manufacturer.
All inspection shall also be made in accordance with the relevant Code of Practice of the Local
Authorities.
All replacement parts can be obtain from the Authorized Agent and must be certified to be compatible for
used with the relevant versions of Hardware & Software of the Fire Control Unit
Authorised Agent
Email : [email protected]
CONTENTS
Operation and
Maintenance Manual
PART 2: ADDRESSABLE FIRE ALARM SYSTEM
PROPOSED PROJECT GLORY
Tan Ka Seng
Acclaim Systems Pte Ltd
2021
Acclaim Systems Pte Ltd
OPERATION MAINTENANCE MANUAL CONTENTS
(HAWKER CENTRE) PROJECT GLORY
TABLE OF CONTENTS
1. ADDRESSABLE FIRE ALARM DESIGN OVERVIEW
1.1. General System Description
1.2. System Nodes Equipment Schedule and System Nodes allocation
1.3. Alarm Management
1.4. DEVICES LIST
The Ziton ZP3 is a complete intelligent fire alarm system that complies with the requirements of our
Local Authorities. All Fire Control Units are tested to comply with the latest Code of Practices.
The ZP3 system consists of a Main Alarm Panel located in the FCC which is networked with Floor Sub
Alarm Panels which is then connected to various devices located throughout the protected building.
These devices include smoke sensors, manual callpoints, alarm sounders, strobe lights, sprinkler
flowswitch interfaces and other devices.
All Fire Sprinkler Pumps, Sprinkler Control Valves, and other Fire Protection Equipment Status are
also interfaced with the Fire Alarm System for annunciation.
Also connected are Fire Interlocking to other Essential Equipment which includes the MV Systems,
One Way Voice Communications, Lift Homing Devices, EM Locks and other required connections.
A Master Mimic are provided beside the Main Alarm Panel to annunciated via LEDs indicators the
status of all Fire Protection Equipment Status, Floor Fire Fault Activation, Flowswitch Alarms,
Callpoints Activation.
A Floor Mimic are provided beside each floor comprising of a silkscreen diagram of the floor plan
with LED indicators indicating the location of any Fire Activation on a Zonal Basis.
A Fire System PC based Management System (Ziton Maestro) will be provided at the FCC for the
Management and Monitoring of the Complete Fire Systems installed
Addressable Fire Alarm System installed in this development comprise of the following components:
Equipment Description Make / Model Qty
Main Alarm Panel at FCC ROOM 1STY, SUB ALARM PANEL AT
Ziton ZP3 En54 Fire Alarm
L1 FFL-2 (HC) 2 NOS
Panel
Floor Mimic Panel at HAWKER CENTRE LEVEL 2 AND HAWKER
Mimic Panel 2 NOS
CENTRE LEVEL 3.
Master Mimic panel at FCC ROOM 1STY Master Mimic Panel 1 NOS
Node
No/Charger
Location Remarks
No/ Mimic
panel No
MAP (P1) 1STY FCC ROOM Main Alarm Panel
Upon the Activation of any of the Fire Sensors like Sprinkler Flowswitches, Callpoints, Smoke
Detectors, FM200 Fire Suppression System, Smoke Control System, the occupants will be alerted of
the situation by means of:
All the above Audible and Visual Signals will be activated upon the activation of any one of the Fire
Sensors.
All the Activated Alarms can be silenced from the Main Alarm Panel located in the Fire Command
Centre. There will be no 3 minute “Silence Delay” as the Fire Alarm System have been connected to
the Approved Public Address System for Voice Instructions.
After investigation and removal of the cause of the Alarm Activation, the Fire Alarm System can be
normalized from the Main Alarm Panel at the Fire Command Centre, by resetting the System.
(Note that if the source of the Alarm has not been removed and the system is resetted, the system
will go back into alarm.)
(Note that all essential equipment that was activated into Fire Mode will have to be resetted
separately)
(Note that all essential equipment that was activated into Fire Mode will have to be resetted
separately)
Device Tested
REMARKS
(Address)
Device Tested
REMARKS
(Address)
Device Tested
REMARKS
(Address)
2.1. Introduction
The ZP3 is a sophisticated intelligent fire detection system, designed for the protection of both small
and large buildings, as well as very large multi-building sites. It uses a modular design which allows
scalability from single panel systems, through to large multi-panel networked systems. A range of
hardware and software is available which allows purpose-made applications for all commercial and
industrial sites.
ZP3 is an analogue addressable system based upon the Ziton ZP operating system. It utilizes advanced
fire and smoke sensing techniques, with intelligent software which accurately recognizes real fires, and
provides early warning. Precision algorithms identify and, in most cases, eliminate false alarms. The
location of a fire is accurately identified.
The ZP3 system supports sensors, callpoints, and other devices, providing a high degree of flexibility. A
system comprises one or more ZP3 control panels, connected to fire and smoke sensors, and other
equipment to provide all the necessary functions.
Modular hardware includes remote indicator panels, mimic panels, local and remote inputs and outputs
for interfacing to third-party equipment, and interfaces to computer-based monitoring and building
management systems. Highly configurable software allows virtually any system requirement to be
simply programmed as required. The ZP3 system is suitable for both new buildings and existing
installations.
The complete system is actively monitored on a continuous basis, and provides complete reliability at all
times. Self-maintenance and diagnostics are built-in.
ZP3 fire alarm panels are available in 1, 2 and 4 loop versions, supporting up to 508 sensors per panel.
Built-in peer-to-peer networking capability allows up to 32 panels and over 16000 sensors to be
connected together, providing scalability from small to very large systems.
The complete ZP3 system is designed to comply with those parts of European Standard EN54 which
have been published. ZP3 panels comply with EN54 (parts 2 and 4), and sensors comply with EN54
(parts 5, 7, and 8). Other parts of the system comply with the appropriate parts of relevant National
Standards, such as BS5839.
The ZP3 system incorporates a wide range of features and capabilities. These are described in detail
later in this manual. The following is a list of the basic features available.
The ZP3 incorporates the proven ZP system of automatic contamination adjustment for each sensor.
This recalibrates each sensor as it becomes contaminated, and provides a constant sensitivity even
when sensors are dirty.
Each sensor is individually adjustable for sensitivity, including different sensitivities for day and night
operation.
Selectable alarm verification allows the time integration of each sensor to be set. Analogue sensors
provide pre-alarm, alarm, service, and diagnostic alarms.
Each panel supports up to 50 zones, optionally 128. Built-in zone LED’ s display up to 50 zones, and
extender panels provide LED display up to 128 zones.
Each panel has the capability for 896 programmable inputs and outputs, which can be located with
the panel, or remotely via serial connection.
Flash memory retains all programming and data, even if the panel is powered-down.
2.2.1. Operation
The panel incorporates a simple and effective operator interface with 160 character LCD display.
Together with zone LED’s and function LED’s, these indications give a clear and unambiguous
indication of all alarms and reports. All control functions are menu driven, and three access levels
are protected by codes. A “help” button provides quick access to operating instructions.
A full range of single and combination analogue addressable sensors, including wired and radio
sensors, is supported. Manual call-points meet UK preferences, and respond in 3 seconds. A range of
input and output interface units allows the connection of third-party equipment to the addressable
ZP-loop.
A range of maintenance features simplifies and improves system maintenance. These include status
reports, contamination and near-service reports, operational statistics, and a “zone walk-test” and
“sounder-test”. The systems have the ability to manually, or automatically by time, disable zones or
individual points for maintenance purposes.
Automatic diagnostics continuously monitor the system for correct operation. Features include
automatic checking of wiring and points, corrupt data detection, disconnection of faulty or corrupt
zones, automatic testing of sensor operation, and verification of sensor/zone location. Sensors are
automatically subjected to a self-test at regular intervals, and vital elements of the system, such as
the software configuration data and running data are verified every hour.
In addition to the ZP-loop devices, a range of accessories and peripheral devices is available to
provide all the elements of a complete system. These include remote display panels, mimic panel
drivers, addressable relay output boards, addressable monitored sounder output boards,
addressable input boards, communication ports RS232 and RS485, remote I/O cabinets, and other
equipment.
Day/Night control provides separate programmes for day and night modes. Different sensor
sensitivity, alarm selection, alarm evaluation delays, and fire brigade response can be configured.
2.2.8. Configuration
The ZP3 peer-to-peer network enables up to 256 standalone systems to be integrated to provide
system-wide alarm reporting, coordinated evacuation, cause-and-effect functionality, and control,
for large systems and multi-building sites.
The ZP3 is a complete intelligent fire detection system designed to protect life and property. It will
detect the presence of a fire or smoke, raise local and remote alarms, indicate accurately the location of
the fire, call the fire brigade, and activate building systems to prevent the spread of smoke, gases, and
fire. It can also activate automatic fire extinguishing systems.
The ZP3 system consists of a central panel which is connected to various devices located throughout the
protected building. These devices include fire and smoke sensors, manual callpoints, alarm sounders,
local and remote indicating panels, graphics display computers, led mimic panels, and other devices.
Also connected are interface connections to other building systems, and connections to a fire brigade,
or other remote manned centre.
Sensing devices are grouped into zones, and programmed with text-labels to indicate their location.
The control panel continually checks every fire and smoke sensor, callpoint, and other devices, attached
to the ZP-loop, every 2 seconds. The precision data collected is analysed to indicate the amount of
smoke, heat and combustion products in the proximity of devices. This information is constantly
updated because of the active scanning process by the ZP3 panel. This provides an accurate picture of
the area being monitored by the sensors, enabling intelligent decisions to be made on the presence or
not of fire, smoke, or invisible products-of-combustion.
After making a decision that a fire exists, the ZP3 system initiates an alarm at the control panel, displays
the exact location by means of illuminated LED's and LCD text-display, and illuminates the led on the
initiating sensors or callpoints. It also issues pre-programmed commands to operate area sounders, call
the fire brigade, activate building controls such as air-conditioning shut-down, and other actions. In
addition it commands remote devices to display the location and status of alarms, and to carry out
programmed control functions. Very high power processing capability allows any configuration to be
programmed. In large multi-panel systems, panels communicate with each other, display alarms from
other areas, and carry out commands issued by other panels.
The complete system is actively monitored on a continuous basis. Self-maintenance and diagnostics are
built-in, and all sensors and devices, as well as field wiring, are continuously checked for correct
operation. Any faults found are automatically reported.
Although each system is unique, the basic principles of operation apply, and this manual describes the
ZP3 operating principles. In order to fully understand your particular system, obtain a copy of the
system specification and become familiar with how the system is designed to react in the event of a fire
alarm.
The following is a simple schematic of a ZP3 fire detection system. This schematic shows a single ZP3
panel, together with some of the sensors, callpoints, sounders, and remote display panels which
constitute the make-up of a typical system.
The operation of the complete system is done by means of the controls and indicators on the panel
fascia. In some systems, the operator will control the system not from the panel fascia, but from a
Remote Display Unit. This is identical to the control panel, but is usually located in some other area,
such as a control room. It is effectively a "repeater" which operates in the same manner as the fire
panel. The following illustration shows the layout of the ZP3 fascia.
bottom line a "pointer" will be illuminated above the common "Fault" indicator. The alarm
will display by zone or by category.
Help Button
Pressing the "Help" button displays on-screen operating instructions for the ZP3 panel. These
instructions can be scrolled through using the up/down "more" keys.
Accept Button
After receipt of an alarm, pressing the "Accept" button causes the illuminated indicators to go
steady, and silences the panel buzzer. When a fire alarm is accepted the buzzer gives a "chirp" every
30 seconds; when other alarms are accepted, the buzzer remains silent.
Reset Button
Pressing the "Reset" button clears all alarms from the system, and restores the panel to a normal
non-alarm condition. All alarms displayed are removed, and all illuminated indicators are switched
off. Sounders are switched off, and the remote manned centre alarm is restored to a "no-alarm"
condition. If any sensors, callpoints, or other devices are still sensing a fire or smoke, or a fault, then
the panel go back into an alarm condition.
On this indicator the system is categorized, on the left side, into different elements, as follows:
System The panel and the complete system, including the CPU.
Zone A grouping of sensors, or other line devices.
Point A single line device, such as a sensor, callpoint, or sounder, etc.
Sounders Alarm devices, including electronic sirens, bells, etc.
Remote Alarm Alarm to a Remote Manned Centre (RMC), such as a Fire Brigade.
Extinguishing System An automatic fire extinguishing system.
The status indicators have been categorized by column as shown in the illustration above, and the
following conditions are indicated.
Power On Indicates that the ZP3 panel has power, either from the mains or from the standby
battery.
Active Indicates that a sounder, remote alarm or extinguishing system has been activated.
Fault Indicates that a fault condition has been detected on a device or output. A “System-
Fault” indicates that a major fault exists in the panel.
Disabled Indicates that a device or output has been deliberately disabled.
Delayed Indicates that the activation of a sounder, remote alarm, or extinguishing system has
occurred, but that the actual operation of the output is in a delayed state.
Pre-Alarm Indicates that a zone or sensor is in a pre-alarm condition.
Test Indicates that the panel is in a test mode, which can be initiated either manually or
automatically.
2.6.1. Overview
Alarms are displayed on the panel fascia, and the fascia of remote display panels, audibly by means
of a built-in panel buzzer, and visually by means of illuminated LED indicators and descriptive text on
the LCD display. The following is a summary of how each type of alarm is displayed.
Fire Alarms
These are shown by means of the common FIRE led's, the zone LED's, and the LCD text display. The
operation of functions arising from the fire alarm, such as sounders, control outputs, remote
manned centre alarms, etc, are shown by means of status indicators.
Fault Alarms
These are shown by means of the common FAULT led's and the LCD text display. The operation of
functions arising from the fault alarm, such as control outputs, remote manned centre alarms, etc,
are shown by means of illuminated status indicators.
Disabled Alarms
When zones, sensors, or sounders are manually disabled, or automatically disabled by time, these
events are shown by means of the common DISABLED led's, and the LCD text display. The LCD
display can be cleared with the reset button, but as long as the devices remain disabled, the
common disabled indicator will be illuminated. Details of which types of devices are disabled are
indicated by illuminated status indicators.
Other Alarms
Alarms which do not fall into any of the above three categories (for example, "pre-alarms") are
shown by means of the common INFO led's and the LCD text display. Where applicable, details of
the alarms are shown by means of illuminated status indicators.
A fire alarm will display on the panel as described below. The actions carried out upon receipt of a
fire alarm will depend upon the fire alarm procedures at the organization where the alarm occurred.
The following are generic guidelines only.
Operator Action
Accept the alarm by pressing the "Accept" button. This will silence the panel buzzer, and cause the
flashing alarm indicators to go steady. The panel buzzer will "chirp" intermittently every 30 seconds
to remind you of the alarm. Do not press "reset" or the "silence alarms".
Identify the zone from which the alarm originated. Check the area (zone) to ascertain the extent of
the problem. For example, telephone the zone fire marshal, or send someone to the area.
During this time the sounders in the area will be sounding. Only when you are sure that the situation
is under control, or that the people from the area have been evacuated, press the "silence alarms"
button to silence the building sounders. If the sounders were switched-off inadvertently, press the
"sound alarms" button to switch the sounders on.
After the alarm, restore the device which initiated it (for example, remove smoke, or replace the
glass in a callpoint), and then press the "reset" button. The system will restore to normal.
Serious faults: A system fault which takes the complete system out of
operation, such as a processor failure, requires
immediate action.
Part-system faults: A fault which takes a small part of the system out of
action, for example a damaged cable, or a mains failure
where the batteries will operate the system for the rest
of the day, needs to be repaired within the same day.
Service reports: A condition which reports as needing attention, for
example a dirty sensor, does not affect the immediate
operation of the system, and can be attended to at the
next routine service.
Operator Action
Accept the alarm by pressing the "Accept" button. This will silence the panel buzzer, and cause the
flashing alarm indicators to go steady. Do not press the "reset" button.
Call maintenance personnel to rectify the fault. Record the action taken in the logbook.
After the fault has been rectified, press the "reset" button. The system will restore to normal.
2.7.3. Disablement
Zones, sensors, callpoints, sounders, control outputs, and remote manned centre alarms can be
manually disabled for maintenance or other purposes. When disabled, the condition reports, as
described below. Disablement is normally carried out by maintenance personnel, and can only be
done with a level 2 access. In certain cases, where a specific part of a system is regularly disabled at
certain times (for example, a meeting room which allows smoking), the system is sometimes setup
to allow the operator to carry out the disablement, usually with a keyswitch.
Types of Disablement
Disablement of the system fall into two main categories:
Devices: These are input devices such as zones, sensors, manual
callpoints, etc. Provided the number of devices is sufficiently
small, and the relevant staff is aware of the situation and
keeping it under control, this situation is usually considered
acceptable.
Sounders and RMC: Disabling of sounders or the remote manned centre alarms is
considered very serious, and some authorities do not approve
of this practice. If sounders are disabled for any reason, they
must be re-enabled as soon as possible.
Operator Action
To view disabled zones press the "Disabled" button. The screen will show disabled or partly-disabled
zones; scroll with the up/down "more" buttons to view all. Status LED indicators will indicate the
category of devices which are disabled.
If a fire alarm occurs whilst sounders are disabled, press the "Restore Disabled Alarms" button. This
will restore any disabled sounders, as well as the remote manned centre alarm.
Types of Alarm
The following are the types of alarm which will be reported in the "Info" category.
Operator Action
Accept the alarm by pressing the "Accept" button. This will silence the panel buzzer, and cause the
flashing alarm indicators to go steady. Do not press the "reset" button. The type of alarm will
determine the action to be taken. For example, a "Pre-Alarm" could indicate a small quantity of
smoke, and might require prompt attention. Record the action taken in the logbook. After the alarm
has been attended to, and the source of the alarm removed, press the "reset" button. The system
will restore to normal.
2.8.1. Introduction
The panel has built in software functions for carrying routine operator functions and system checks.
These functions are accessed via the operator menu, using the panel keypad. This section describes
these functions, and how to use them.
When using a menu, the LCD screen displays the menu items in place of any alarms or events that
would normally indicate on the screen.
The operator menu is used for a number of functions. These are setting the time and date, to
identify which version of software is installed in the panel, and to test the fascia illuminated LED
indicators, and to test the keypad. It allows reports of the status of the system, or individual devices,
to be viewed or printed. It also allows previous alarms to be viewed or printed.
Access to the menus is via the panel keypad. Details of the keypad are described below.
Operator Menu
The main menu is the entry point to all of the user operator accessible software functions. The main menu is invoked
by pressing the MENU key. The display will then show the following:
Press key 1 to enter the Operator Menu. The following screen will appear.
The menu name is displayed on the top line, and the menu items are shown with numbers alongside. Menu items are
selected by pressing the numeric key that matches the item number. Selecting a menu item may cause another menu
to be called up or may carry out a particular function. The operator may be prompted to enter, via the keypad, required
information.
Any menu can be cancelled and the previous menu presented by pressing the ESC key. The ESC key is used to
cancel or abort the current activity and return to that preceding it.
The menu system can be exited completely by pressing the HOME key, which returns the panel to its normal operation
display. In order to prevent a system from being inadvertently left in a menu, a time-out is built into the menu system.
The time is from the last time a key was pressed. In menu selection, the time-out is approximately 45 seconds, and if a
software function has been started and not completed, then it is 12 minutes.
The operator menu structure is shown below, displayed as a menu tree. Items that are grouped together are
options that appear together on a menu, and items that are open-ended implement a software function.
Date The current date in the system is shown. Enter the new date in
DDMMYYYY format, and press ENTER.
Time The current time in the system is shown. Enter the new time in 24-
hour HHMM format and press ENTER.
Reports to Display
Point status This option allows the status of any device attached to the panel Z-
loops to be viewed on the LCD screen. The report will show the type,
sensitivity, zone and condition of the point.
Software version This option displays on the LCD screen the software number and
version used by the panel.
Archives This allows the operator to view on the LCD screen previous alarms
and events which are stored as "archives" in the panel. The panel
automatically stores the last 1000 events, together with the date and
time of each. The menu allows the events to be selected by date, and
viewed accordingly. Use the up/down scroll buttons to display the
next/previous archived message.
System status This option displays status information of outputs and points. Options
are available to limit the report to disabled points, or Gas Control units.
Reports to printer
Archives This allows a printout of previous alarms and events which are stored
as “archives" in the panel. The panel automatically stores the last 1000
panel events, together with the date and time of each event. The
menu allows the events to be selected by date.
Point status This option allows the status of any device attached to the panel Z-
loops to be printed. The report will show the type, sensitivity, zone and
condition of the point. The printer can also be stopped from here.
Stop printer Use of this menu option will terminate the current print operation.
Lamptest
Keypad test
2.9.1. Introduction
The owner of a fire detection system is responsible for ensuring that it is correctly maintained so
that it is in a proper working condition at all times. This will involve arranging for the system to be
checked, tested and serviced as described in this manual.
The maintenance procedures described are Ziton recommendations. There may be additional
requirements or regulations imposed by local authorities. When there is a conflict, then the local
authority regulation should be followed.
Regular procedures
The recommended maintenance procedures can be divided into the following categories:
Daily checks
Weekly checks
Quarterly services
Annual services
The daily and weekly checks require no technical knowledge and can often be carried out by the
panel operator, or in-house maintenance staff. It is important for the person carrying out the testing
to be aware of which building functions or remote alarms will be activated by the system when an
alarm occurs.
The quarterly and annual services should be carried out by an authorized Ziton servicing company,
usually under maintenance contract. These services are not the responsibility of the operator or in-
house maintenance technician, and are not covered in this section of the manual.
Repair of Faults
The system operator and in-house maintenance personnel should have the telephone number of the
outside company contracted for maintenance, so that they can call them if a major fault develops
which is beyond the capability of the in-house people.
Record Keeping
The operator should maintain a log book at the control panel, into which a record of all alarms,
events, checks, tests, and repairs are entered.
Routine Checks
The following are the details of the daily and weekly checks that must be carried out to ensure that
the system is operational at all times.
Important
Occupants of the building and anyone receiving remote alarm signals, such as the fire department,
should be informed prior to the test. They must also be informed when the test is complete. No
alarms should be activated before notification has taken place. Any external systems that are
connected to the fire system, such as fire extinguishing systems, air-conditioning systems, or lifts,
should be temporarily disabled while testing is in progress. It is essential that all disconnected or
disabled systems be reconnected at the end of testing.
Daily checks
Check that only the Green Power-on indicator is illuminated. All other LED's should be off and the
panel should be silent. The display should show the time and date only.
If the panel is indicating a fault alarm, contact the maintenance staff and arrange for the fault to be
rectified.
Maintain the logbook up-to-date. Check that all faults recorded in the log book the previous day
have been attended to.
Check that the correct time and date are displayed. If not, then correct the time/date.
Weekly Checks
Check that all LED’ s are operational by carrying out a lamp-test.
Operate at least one device (fire sensor or callpoint) in a zone. The zones should be rotated to
ensure that they will all be tested over time.
Check that the required sounders operate.
If the system is connected to a remote manned centre, check the alarm was received.
If the fire system controls the operation of auxiliary equipment, check that this did occur.
Accept the alarm, and press the “Silence Alarms” button. Check that the sounders silence.
Reset the system.
If the panel has a printer, check that it recorded the events correctly. Check that it has sufficient
paper, and that the print ribbon is not dry. Verify that the paper feeds correctly.
Make sure that the panel exterior is clean by lightly polishing with a dry cloth.
Important: If any defects are discovered during the routine testing, they should be recorded in the
log book and action taken to have them corrected.
-OPERATION MANUAL-
O&M - KIDDE WHDR Wet Chemical Extinguishing System Pg 1 of 4
1. GENERAL
The KIDDE WHDR Wet Chemical Extinguishing System is designed and has been tested to
provide fire protection for commercial cooking operations covering the hood, ducts, plenum and
appliances. KIDDE WHDR Systems are a pre-engineered type as defined in NFPA 17A –
Standard for Wet Chemical Extinguishing Systems.
The KIDDE WHDR Series is a listed pre-engineered fire extinguishing system. The WHDR
system is listed with Underwriters Laboratories, Inc. – USA per UL 300 fire test specification;
Underwriters Laboratories of Canada, Inc. per ULC/ORD 1254.6 – 1995 and Loss Prevention
Certification Board – UK per LPS 1223 rev. B.
The KIDDE WHDR Series Pre-Engineered System consists of mechanical and electrical
components. The system is composed of an agent cylinder/discharge valve charged with APC
Agent and a KRS-50 Control Box. The KIDDE WHDR system uses a liquid chemical called
Potassium Acetate Carbonate (APC) as its agent. APC, a solution of potassium carbonate in
water, suppresses fires through a process involving the followings:
• Saponification of surface grease (turning it into combustion-resistant soup),
• Cooling effects of water vaporization,
• Inerting effects of resultant steam formation, and
• Interruption of the chemical chain reaction of combustion.
O&M - KIDDE WHDR Wet Chemical Extinguishing System Pg 2 of 4
2. SYSTEM LAYOUT
4) Fusible
2) ‘KIDDE WHDR’ Link
Wet Chemical 3) KRS-50
Cylinder Control
Box
1) Manual
Pull Station
5) Discharge
Nozzles
SYSTEM BRIEF
1) Manual Pull Station : The device that allows the system to be manually
discharged either at the hazard or from a remote location.
5) Discharge : The device used to deliver a specific quantity, flow and Nozzles
discharge pattern of fire suppression agent to a specific
appliance, duct size or plenum size
O&M - KIDDE WHDR Wet Chemical Extinguishing System Pg 3 of 4
3. OPERATION
The KIDDE WHDR Wet Chemical Extinguishing System operates either automatically if
actuated by a detector or manually if actuated by a manual pull station.
The KIDDE WHDR Wet Chemical Extinguishing System suppresses fire in commercial cooking
equipment by spraying APC liquid agent in a predetermined manner onto the cooking
appliances and into exhaust ducts, filters and plenum areas. The primary means of fire
suppression is either by saponification of surface grease or by cooling the surface of oils and
hot metal surfaces with fine droplets of agent, reducing the temperature of the oil and appliance
below the auto-ignition point.
IN CASE OF FIRE
Assessing the fire situation, if the breakout of the fire size is small and be able to be
suppressed, extinguish the fire by means of a portable fire extinguisher.
Else, by automatic means, the fusible link shall separate; release the tension in the cable upon
reaching its designed temperature to cause the KIDDE WHDR series Automatic Wet Chemical
Extinguishing System to discharge.
For a manual discharge, proceed to activate the remote manual pull station by
1) Break off the safety tag,
2) Pull away the smaller ring pin
3) Pull out the bigger ring lever to manually discharge the APC liquid agent.
DO NOT GO CLOSE to the cooking area upon discharge of the APC liquid agent. Exit the
kitchen upon activation of the KIDDE WHDR Wet Chemical Extinguishing System.
O&M - KIDDE WHDR Wet Chemical Extinguishing System Pg 4 of 4
4. MAINTENANCE
4.1 Introduction
To ensure continuous reliability of the KIDDE WHDR Series Automatic Wet Chemical
Extinguishing System, regular testing and servicing shall be carried out. Only trained and
competent personal are allowed to performance the routine testing and maintenance.
2) Conduct a visual check on the entire distribution network piping, nozzles and seals to
verify that they have not been altered or damaged.
3) It is recommended that all fusible links to be replaced every 6 months. Links that do not
need replacing must be thoroughly cleaned before being put back into service. Any
fusible link found to be damaged, painted or having excessive grease must be replaced
regardless of age.
4) The agent cylinder assembly must be checked for proper pressure (within the green pie
OPERABLE RANGE on pressure gauges)
1. No Exceptions Taken
1. No Exceptions Taken
13/08/2018
7/8/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
13/08/2018
7/8/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
13/08/2018
7/8/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
04/07/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
04/07/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
04/07/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
13/08/2018
7/8/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
04/07/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
13/08/2018
7/8/2018
23/10/2018
(SQM)
Digitally signed
by Jackie
DN: cn=Jackie,
o=RSP,
ou=Architect,
email=jackie_me
[email protected],
c=US
Date: 2018.12.03
12:25:03 +08'00'
06/12/2018
9/11/2018
Please seek consensus from Architect on
aesthectic related
Subject to actual
sample approval.
Actual locations for
use to be
discussed. Should
be at BOH.
Subject to actual
sample approval.
Actual locations for
use to be
discussed. Should
be at BOH.
Note that the breeching inlet is
inside a compartment. Please
check how to interface with the
GFRC panel.
Note that the breeching inlet is
inside a compartment. Please
check how to interface with the
GFRC panel.
Provide proper
mountiing.
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
23/10/2018
(SQM)
1. No Exceptions Taken
29/08/2018
13/8/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
04/07/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
04/07/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
22/09/2018
6/9/2018
12/11/2019
IFA TO BECA
10/12/2019
BECA
19122019
: FIRE PROTECTION, PLUMBING, SANITARY & GAS
SERVICES
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
BECA COMMENT:
20/10/2018
(SQM)
17/11/2018
30/10/2018
1. No Exceptions Taken
BECA COMMENT:
ENSURE SPRINKLER PUMP NAMING
TALLIES WITH DRAWINGS AS SELECTION
FOR L50 JOCKEY PUMP IS CALLED SJP-6
WHEREAS THE SCHEMATIC SHOWS
SJP-7
17/11/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
24/07/2018
16 July 2018
To forward to RSP/BECA IFA
08/09/2018
01/10/2018
6/9/2018
1. No Exceptions Taken
01/10/2018
CONTRACTOR SUBMISSION REVIEW
Review does not constitute acceptance or approval of design
details, calculations, analyses, test method or materials
developed or selected by the contractor and does not relieve the
contractor from compliance with contractual obligation.
1. No Exceptions Taken
08/08/2018
16 July 2018
Acknowledgement Letter
TEAM DESIGN CONSULTANTS
120 LOWER DELTA ROAD
#07-02 CENDEX CENTRE
SINGAPORE 169208
1. We have received your application made with respect to the above-mentioned project.
2. Based on the amount computed and declared by you in the application form, kindly make payment of $ 180.00
for the plans approval fee within four weeks from the date of this letter, failing which, your application will be
rejected automatically by our computer system. Please note that SCDF will verify the plan fee declared by you
subsequently and inform you and the applicant if there is any shortfall.Your application will only be processed
after full payment of plan fee has been received.
3. As part of our efforts to encourage e-Payment for applications made to SCDF, payments for plans approval fee
can be made online at www.scdf.gov.sg (Credit Card, GIRO) or through NETS, Cash Card and JAV (for
Ministries). Cheque payment is acceptable only for projects with plans approval fees not less than $1000. An
application will only be processed after the cheque has been cleared.
Yours sincerely
MOHAMMED SAIF ESRAR VINOD KUMAR
for Commissioner
Singapore Civil Defence Force
27 28 29 30 31 32 33 34 35 36 37
8500 8500
10200 8500 8500 8500 8500 8500 8500 6050
DR1/HR DR1/HR
U
KRS
2200
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET
V
CHEMICAL CYLINDER CHEMICAL CYLINDER 4.73 LITRES. CAP. WET CHEMICAL CYLINDER 4.73 LITRES. CAP. WET CHEMICAL CYLINDER 4.73 LITRES. CAP. WET CHEMICAL CYLINDER CHEMICAL CYLINDER
CHEMICAL CYLINDER CHEMICAL CYLINDER CHEMICAL CYLINDER
KRS
KRS
C E N T R E 4.73 LITRES. CAP. WET
H A W K E R
CHEMICAL CYLINDER
KRS
DR1
W
KRS
KRS
KRS
5310
4.73 LITRES. CAP. WET
CHEMICAL CYLINDER
27 28 29 30 31 32 33 34 35 36 37
8500 8500 10200 8500 8500 8500 8500 8500 8500 6050
2200
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
KRS
4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET
V
4.73 LITRES. CAP. WET
CHEMICAL CYLINDER CHEMICAL CYLINDER 4.73 LITRES. CAP. WET CHEMICAL CYLINDER 4.73 LITRES. CAP. WET CHEMICAL CYLINDER 4.73 LITRES. CAP. WET CHEMICAL CYLINDER CHEMICAL CYLINDER
CHEMICAL CYLINDER CHEMICAL CYLINDER CHEMICAL CYLINDER
KRS
KRS
4.73 LITRES. CAP. WET
CHEMICAL CYLINDER
H A W K E R C E N T R E
9565
PROPOSED ADDITIONS OF FIRE SUPPRESSION SYSTEM
4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET
CHEMICAL CYLINDER CHEMICAL CYLINDER TO PROPOSED AMENDMENT TO PROPOSED ERECTION OF A
KRS
KRS
KRS
KRS
KRS
4.73 LITRES. CAP. WET 4.73 LITRES. CAP. WET (DOWNTOWN CORE PLANNING AREA)
CHEMICAL CYLINDER CHEMICAL CYLINDER
5290
4.73 LITRES. CAP. WET
CHEMICAL CYLINDER
LOCATION PLAN
X 2ND STOREY PLAN
3RD STOREY PLAN
PART OF KITCHEN LAYOUT PLAN AT 2ND STOREY
PART OF KITCHEN LAYOUT PLAN AT 3RD STOREY
LEGENDS
FIRE
ANSUL
PULL
Wet Chemical Cylinder
IN CASE OF
ANSUL TYPICAL INTERLOCKING DIAGRAM WHEN FIRE OCCURS, PULL THE MANUAL RELEASE STATION. THE
SCALE N.T.S. TENSION WILL BE RELEASED THUS ACTIVATING THE C02 CARTRIDGE
IN THE CONTROL BOX, SENDING PRESSURE TO ACTIVATE THE
CYLINDER VALVE AND RELEASE THE AGENT TO SUPPRESS THE
FIRE.
Ø12.7mmGI-B PIPE
m
GI-B
Ø12.7 Ø12.7
PIP
Ø12.7mm E
4.73 LITRES. CAP.
Ø12.7mm
SCALE 1:10
SINGAPORE 339263
Attn : SEAH CHEE KIEN
TFP FOR PHASE 3(FINAL) COMPRISING: A) BASEMENT BIN CENTRE 2; B) 1ST STOREY PARKLAND, SR
SHUTTLE LIFT LOBBY AND HAWKER CENTRE ESCALATOR; C) 2ND TO 3RD STOREY HAWKER CENTRE;
D) 6TH TO 8TH STOREY CARPARK; E) 9TH STOREY SERVICED APARTMENTS AND ROOF GARDEN; F)
10TH - 16TH STOREY SERVICED APARTMENTS; G) 17TH - 20TH STOREY SKY TERRACES AND 20TH
STOREY CEILING VOID SPACE; H) 51ST STOREY RESTAURANT, LIFT LOBBY, TOILETS AND ROOF
TERRACE; I) UPPER 51ST STOREY, ROOF AND UPPER ROOF.
1. We are pleased to inform you that your project has been granted a Temporary Fire Permit (TFP).
2. The TFP has been issued subject to the provisions of the Fire Safety Act particularly to your compliance with
the conditions given in the Annex.
Yours sincerely
SINGAPORE 307906
Note : The TFP/FSC is approved based on Qualified Person’s written declaration that the plans for the project are in compliance with fire
safety requirements, as well as the Registered Inspector (s) being satisfied that the fire safety works have been carried out in accordance with
the approved fire safety plans, the relevant codes of practice, the Act and any regulations made thereunder.
TFP ANNEX
Conditions
Note : The occupation of a premises without a valid Fire Safety Certificate is in contravention of the Fire Safety Act and the owner is liable for
court prosecution.
REPUBLIC OF SINGAPORE
SINGAPORE CIVIL DEFENCE FORCE
DESCRIPTION OF PROJECT:
PROPOSED ERECTION OF A 51-STOREY COMMERCIAL DEVELOPMENT WITH A BASEMENT AND COMPRISING SHOPPING /
HAWKER CENTRE (AIR SPACE LOT) / SERVICE APARTMENT / OFFICE / MULTI-STOREY CAR PARK AND ANCILLARY FACILITIES ON
LOTS 00505N & 00660X-PT, TS 01 AT MARKET STREET / CHULIA STREET / CHURCH STREET
TFP FOR PHASE 3(FINAL) COMPRISING: A) BASEMENT BIN CENTRE 2; B) 1ST STOREY PARKLAND, SR SHUTTLE LIFT LOBBY AND
HAWKER CENTRE ESCALATOR; C) 2ND TO 3RD STOREY HAWKER CENTRE; D) 6TH TO 8TH STOREY CARPARK; E) 9TH STOREY
SERVICED APARTMENTS AND ROOF GARDEN; F) 10TH - 16TH STOREY SERVICED APARTMENTS; G) 17TH - 20TH STOREY SKY
TERRACES AND 20TH STOREY CEILING VOID SPACE; H) 51ST STOREY RESTAURANT, LIFT LOBBY, TOILETS AND ROOF
TERRACE; I) UPPER 51ST STOREY, ROOF AND UPPER ROOF.
APPROVED PLANS(S):
This Temporary Fire Permit is granted subject to the conditions given in the Annex.
2 Date : Date :
CONCEALED SPRINKLER HEAD SINGAPORE 068912
TEL: +65 6713 2888 FAX: +65 6713 2999
35
As-Built drawing verified and vetted by:
80
SIDE WALL SPRINKLER HEAD
ARCHITECTS RSP ARCHITECTS PLANNERS & ENGINEERS (PTE) LTD.
Client/Consultant site staff Consultant's representative 1 KALLANG JUNCTION #03-01
SINGAPORE 339263
Name : Name : Tel : +65 6737 7544 Fax : +65 6291 7809
Signature : Signature :
FS FLOW SWITCH
STRUCTURAL ARUP SINGAPORE PTE. LTD.
5850
5850
CONSULTANT
Appointment : Appointment : 10 HOE CHIANG ROAD #26-01 KEPPEL TOWERS
HOSEREEL DRUM SINGAPORE 089315
Q TEL: +65 6411 2500 FAX: +65 6411 2501
Ø1 TE R P
SINGAPORE 150168
00 F PE
RA 0 D F/B
DRY RISER LANDING VALVE
16
Date : Date : TEL: +65 6377 9293 FAX: +65 6274 0788
DR /B FI
Ø1 TE
50
0 D
D
PIP
RA
0
EF
M&E BECA CARTER HOLLINGS & FERNER (S.E. ASIA) PTE. LTD.
IRE
I
CONSULTANT
SH STANDBY HOSE 1 GATEWAY DRIVE #12-01 WESTGATE TOWER
R
Ø5 A &
E
P SINGAPORE 608531
0 H T/B
F/
R P (BY
TEL: +65 6220 7588 FAX: +65 6225 6937
DOUBLE STANDBY HOSE
IPE GR
80
2SH
65
M&E SQUIRE MECH PTE. LTD.
ø 32 ENGINEER
AV
2nd Storey 2nd Storey 1 KALLANG JUNCTION #03-01
ITY
ø 32
STROBE LIGHT
)
109.900FFL SINGAPORE 339263
109.900FFL
6
ø3
TEL: +65 6378 5533 FAX: +65 6291 7809
2
FIR TIN
ø 32
QUANTITY
EX
E GU
ALARM BELL SURVEYOR ARCADIS SINGAPORE PTE. LTD.
ø 32
7
ø3
20
ø3
1 MAGAZINE ROAD #05-01 CENTRAL MALL
2
Ø6
ISH
80
2
SECTION B-B M N
ø3
2
5
SINGAPORE 059567
ER
SP
ø 40
TEL: +65 6222 3888 FAX: +65 6224 7089
SECTION A-A MANUAL CALL POINT
KP
2 2
ø3 ø3
IPE
80
ø3
3
ø3
27
55
66
2
2
F/A
LANDSCAPE
COEN DESIGN INT. PTE. LTD.
2
8
00
23 305
&T
1 : 50 0
ø 32
CONSULTANT
ø3 2
ø4
/B
1 : 50 2 2
MIMIC PANEL
ø3
ø3 MM 67 UBI ROAD 1 #06-10/11 OXLEY BIZHUB
(O
ø 40
35
2
R)
SINGAPORE 408730
17 785 ø 40 TEL: +65 6844 9888 FAX: +65 6844 9555
27
1 ø100
ø 32
20
0
HR
ø40
SUB ALARM PANEL
0
ø4 SAP
ø3
82
KEY PLAN
2
ø40
ø40
ø32
FIRE EXTINGUISHER
FIR XTIN
E
E GU
L ø32
SMOKE DETECTOR
ISH
S
00
ø32
9
ER
75
75
ø32
00
10 WET CHEMICAL CYLINDER
ø32
ø32
ø32
ø3 0 ø40 ø32
ø4
K 2
0
ø50
15
ø4
80
2
Ø5
ø3
0
0
J
ø 10
HR
30
2 ø1
PIP
00
51
ø3
E
H
F/A
ø3
Ø6
0
ø4
&
2 ø4
5
0
T/B
2
SP
ø3
2 ø3
FO
K
ø4
2
PIP
MI 0mm
RC
ø3
ø4
MI
EF
38
C(
0
N
C (W
0
ø3
70
ø4
/A
BY
2
PA )x1
ø3 2 2
23
NE 00
ø3
G RA
L mm
VFIAT
DY
2
30
) (C
ø3 ø3
ø3
2
ø3
12
2 2
C)
(D
2
ø3
)x5
ø3
10
mm
2
G
2
ø3
(H
ø3
32
)
2
Ø1
ø ø3
50
2
Ø1
ø3
2
WR E TR
2
50
70
ø3
FL
FI
FIR
S1
62
PIP ANS
OW
FIR 0 PK
a
E F FE
M
ø3
E E SPK PIP
Ø1 50 S
P
SW
2
/A R P
5
XT PI E F/
ITC
Ø1
2
ø3
SH
& T IPE
ING PE
ø3
HR
H(
2
Ø1
/B(
UIS F/B & T/A
OR L 1
ø3
S
00
BY F/B
2
HE R
)
SP
2
SP
GR & T
ø3
2
R/
R OM ROM
ø3
K
AV /A
WR
DR
ITY
0
11
/
AIN 2
ø4
HR
5m R
ø3
/CC
50 P_O
FA
PIP
CV
)
D
m)
BG
CR
P:6 PK
EF
ø3
-L1 UM
FS
(C
F
(BO 100 S
X CHIT 09/04/2021 AS-BUILT DRAWING
C)
2
-2- P F
/A
0
v oi
T PL
FL
23
&T
Ø3
ø4
)
EL
S
(
d
P
CC
(S L
Ø
2
FO R C
2
EC
2
/B 2
ø3
R
CBRG
2
SP
)P
Ev
REV BY DATE DESCRIPTION
2
) ( SA
00
R O V (O
ø3
ø3
ø3
ac
KD
75
ø4 R)
SR
R
Li f
RA
26
)
t
0 (O
IN 13
PL
2
DSPL'S INITIAL REVIEW
v oi
0
P
2
ø3
2
ø4
IPE
ø3
F
2
7
SA
d
2
R)
ø3
27
ø3
ø3
0
T/B
ø4
CHECKED
wt
PL
0
0
ø5
ø4
5
28
Ø1 E EX PIP F/A
2
ø3
ISSUED WITH COMMENTS
ø3
2
00
ø3
2
PL
FIR
2
DR
2
ø3
ø3
ø3
8
PIP UIS
Ø1 50 H
.9 0
0
REJECTED, RESUBMIT
ø4
0
109
00 R P
MI
E T HE
19
80 CC
TIN E T/ (O
ø4
Ø
PL
D-
m)
DR IP
L
P:4 R_
/A
0
FF
G
RIS
ø4
6
0m
10
(C
(BO 100 D
E
12
C)
10
LI F
CONSULTANT REVIEW
FIR XTIN
R
T
E
ø4
B ( R)
PL
E
E GU
60
LO
CO REA
PL
CC
LO
BB
0
12
APPROVED
MP CTI
P
ø4
PL TME VAL
12
W-
)
0
2
S
Y
ø4
ø3
CP
A R ON
RIS
4 NT VE
v oi
10200
2
ISH
32
ø3
d
3
APPROVED WITH COMMENTS
ER
ø
L I FT
S
FF
8500
FO (60
LO
L
BB
R 0
DR
REJECTED, RESUBMIT
10
LIG OR)
PL
Y
3.6
HT
CL
11
HR
INL (CC ø
0
HR
CP
Ø50 HR PIPE T/A (HC)
1
Ø1 OP:5
x1
IGH ) 50
TE R)
PL 0)
00
00 62
2
L1
TIN
(B
S
2
(O
S
SP 5m
Ø100 DR PIPE F/B & T/A (CC) COMBINED STATUS
ø3
PL
EL C)
KP m)
00
EL )
EC
ø4
16
_O
V
ø1
S
FIRE EXTINGUISHER
(C
T
S
APPROVED FOR SUBMISSION TO ARCHITECT
(S
0
R
PL
(BOP:5802mm)
R
Ø50ø HR_HC
CL
EL
10
EC (
S
2
2
EL )ø50
(S
ø3
APPROVED NO SUBMISSION TO ARCHITECT
PL
V
CP
R
S
CH R)
(O
HR
PU
)
2
W
ø3
BL
1
STALL 1
S
PL
STALL 2
IC
2
U REJECTED, RESUBMIT
PL OR)
ø3 2
17
TE )
LIF
/G
S
L2
TS
A
HIG
(O
ø32
S
SR
ø3
R
H-
ø3
TE R)
6
2
RIS
EL C)
PL
L
ARCHITECT'S REVIEW (RSP, NIPEK)
2
S
E
V
SR
(O
1
S
(H
LI F
97 CC
FF
PL
MA 32
T
m)
Ø5 50 W
APPROVED
L
P: 4 R _
EL R)
LE
SECTION A-A
V
PL
LO
ø
18
0m
TE C) (H
0H
10
(CO 100 D
TO
BB
L
Ø1
15
3.6
(O
R P PIP
(H
Ø25 CONDUIT PIPE
IL E
0
Y
PL S (H
ø4
110
0
T
IPE E F/
Ø
APPROVED WITH COMMENTS
/ E C)
GA C)
Ø5
14
R
T/B A (C
ø40
2
0
ø3
5
ø40
SR
S
ø6
SP
LE
(C
C
C) )
KP
PL
1
PL
Ø3
IPE
19
ø32
2
C
14
2
2
2
F/A
SP
HT
ø3
ø3
ø3
ø32
SECTION B-B
KP
ø40
&T
ø40
IPE
/B(
ø32
0
110
OR
ø4
0
F/A L 13
ø4
2
)
ø5
ø3
&T
0
AS - BUILT
2
P
Ø50 HR_HC
ø40
ø32
/B
ø3
(COP:5104mm)
ø50
SECTION A-A FEMALE FAMILY
ø32
TOILET ROOM
v oi
110
ø40
MAIN CONTRACTOR
STALL 22
ø32
ø3
ø50
ø32
ø40
ø40
v oi
ø32
d
SECTION B-B
110 Ø25 CONDUIT PIPE STALL 26
)
(COP:5530mm
HAWKER TRAY RETURN
Ø50 HR_HC
15 AREA ø32 SPECIALIST SUB-CONTRACTOR:
ø32
CONSUMER
ø32
v oi
d
SWITCHROOM ø40
APP ENGINEERING PTE LTD
ø32
ø32ø32
ø32
CERT. NO. : 2000-1-0221
ø65
ø50
S S ISO 9001 : 2015
11 TOH GUAN ROAD EAST
TER #05-01 APP ENTERPRISE BUILDING
ROOM SINGAPORE 608603
TEL: 6425 6633 FAX: 6425 6636
ø40
S
EMAIL : [email protected]
ø32
CERT. NO. :OHS-45001-2019-0031
ISO 45001 : 2018
ø32
9/4/2021 12:27:14 PM
ø32
ø32
ø32 ø40 ø40 DRAWING TITLE
7200 9000 7500 7500 ø32
GL APP TF SD ++ 02 110 X
PROJECT TITLE
27 CapitaSpring
12 28 LEGEND PROPOSED ERECTION OF A 51-STOREY COMMERCIAL
29 DEVELOPMENT WITH A BASEMENT AND COMPRISING
SHOPPING / HAWKER CENTRE (AIR SPACE LOT)/
13 30 EXPOSED SPRINKLER HEAD SERVICED APARTMENT / OFFICE / MULTI-STOREY
31 CARPARK AND ANCILLIARY FACILITIES ON LOTS
32 CUT-OFF SPRINKLER HEAD
00505N & 00660X-PT, TS 01 AT MARKET STREET /
CHULIA STREET / CHURCH STREET (DOWNTOWN
8500
33 CORE PLANNING AREA)
Q 34 UNDER BEAM SPRINKLER HEAD
10200
35 CLIENT
U 8500 ROYAL FLASH SPRINKLER HEAD CL OFFICE TRUSTEE PTE. LTD.
8500
ø32
36 168 ROBINSON ROAD #24-01 CAPITAL TOWER
SINGAPORE 068912
ø65
ø65
ø50
8500 37 CONCEALED SPRINKLER HEAD TEL: +65 6713 2888 FAX: +65 6713 2999
8500
ø32
ø50
ø40
ø40
ø40 ARCHITECTS RSP ARCHITECTS PLANNERS & ENGINEERS (PTE) LTD.
Ø40 SPKP_HC ø40
ø32
8500 SIDE WALL SPRINKLER HEAD 1 KALLANG JUNCTION #03-01
(BOP:5861mm) ø32
2
(COP:5861mm)
Ø65 SPKP_HC
ø3
Ø32 SPKP_HC
(BOP:6121mm)
6050 FS FLOW SWITCH
ø50
ø65 STRUCTURAL ARUP SINGAPORE PTE. LTD.
ø32
ø50
ø32
Ø32 SPKP_HC
(BOP:6378mm)
ø40 CONSULTANT
ø32
ø40 10 HOE CHIANG ROAD #26-01 KEPPEL TOWERS
HOSEREEL DRUM
ø32
ø40
ø40
ø65
ø32
DOUBLE SLAB
ø32
ø32
FOR DOUBLE
DOUBLE SLAB
ø32
SINGAPORE 150168
ø32
ø32
ø40 FOR DOUBLE SLAB SPK PIPE F/B FOR STILL NEVER
ø32
DO ON DRY RISER LANDING VALVE TEL: +65 6377 9293 FAX: +65 6274 0788
ø32
ø40 SLAB SITE
ø32 DOUBLE SLAB ø32
ø32 ø40 SPK PIPE F/B FOR ø32 M&E BECA CARTER HOLLINGS & FERNER (S.E. ASIA) PTE. LTD.
ø32
ø50
ø40 Ø32 SPKP_CC STANDBY HOSE
ø32
ø40 ø40 SH 1 GATEWAY DRIVE #12-01 WESTGATE TOWER
ø32
ø32
ø40
ø32
ø40 Ø32 SPKP_HC
ø50
(BOP:5814mm) ø40 SINGAPORE 608531
(BOP:6237mm) ø40 SPK PIPE F/B FOR TEL: +65 6220 7588 FAX: +65 6225 6937
ø65
ø65
ø40
ø40 ø40
ø32 ø50 ø50 DOUBLE SLAB 2SH DOUBLE STANDBY HOSE
ø40
ø32 ø50 ø40 M&E SQUIRE MECH PTE. LTD.
ø32
ø65
ø40 SPK PIPE F/B FOR ø40 ENGINEER
Ø50 SPKP_HC DOUBLE SLAB ø32 1 KALLANG JUNCTION #03-01
Ø40 SPKP_HC
ø40 SINGAPORE 339263
(BOP:6238mm) STROBE LIGHT
ø40
(BOP:5728mm) ø32 ø32 TEL: +65 6378 5533 FAX: +65 6291 7809
ø50
ø32
ø40
QUANTITY
ø32
(COP:6123mm)
Ø32 SPKP_HC
ø32
Ø32 SPKP_HC
(BOP:6238mm)
SINGAPORE 059567
Ø32 SPKP_HC
ø32
(BOP:6328mm)
TEL: +65 6222 3888 FAX: +65 6224 7089
ø32
SPK PIPE F/B FOR MANUAL CALL POINT
ø40
DOUBLE SLAB LANDSCAPE
COEN DESIGN INT. PTE. LTD.
ø32
CONSULTANT
DOUBLE SLAB ST 67 UBI ROAD 1 #06-10/11 OXLEY BIZHUB
ø32
MIMIC PANEL
ø32
ILL NEVER DO ON SIT MM
ø32
E SINGAPORE 408730
TEL: +65 6844 9888 FAX: +65 6844 9555
ø32
SPK PIPE F/B FOR
ø32
DOUBLE SLAB
ø40
T FIRE EXTINGUISHER
ø32
ø40 ø40
ø32 ø32
S SMOKE DETECTOR
S
WET CHEMICAL CYLINDER
X
27 12
2ND STOREY DOUBLE SLAB
28 2
N
1 : 150
29
13 30
Q
8500 31
Ø50 HR PIPE T/A (HC) 8500 32
Ø100 DR PIPE F/B & T/A (CC) 10200 33
FIRE EXTINGUISHER
8500 34
(BOP:5802mm)
Ø50ø HR_HC
HR
STALL 1
FIRE
EXTINGUISHER
8500 35
STALL 2
ø3 2 STALL 3 8500 36
TE R)
STALL 4 STALL 5
37
L2
ø32
8500
ø3
STALL 6
2
STALL 7
m)
FIRE
P: 4 R _
0m
ø40
2
ø40
S
ø3
(H
S
LE
ø40
ø32
STALL 13
C
ø32 CHECKED
(
STALL 14 E
ø32
ø32 ø32
ø32
ø32
STALL 16
ø32
R
ø3
ø40
ø32
ø32
ø32
ø32
ø32
STALL 17
ø40
STALL 18
ø32
ø32
ø32
ø40
ø32
ø32
ø40
ø32
HR
ø40
(CC)
REJECTED, RESUBMIT
ø40
ø32
FAD
ø50
2
ø50
(CC)
HL
ø5
ø3
ø32
FAD
ø32 ø40
ø32
ø50
2335
ø40
0
ø32
ø32
ø32
ø32
ø50
1195
ø40
ø32
Ø100ø SPKP_HC
ø32
(BOP:6260mm)
ø32
ø50
Ø100 SPKP_HC
U
ø32
ø32 2045
ø50
ø32
ø32
ø32
ø50
ø32
ø32
ø40
ø32
ø32
TO
ø40
ø50
ø40
2200
ø32
ø32
(TO BE VESTED
ø50
ø32 ø32
Ø100 SPKP_HC
ø32
ø40
ø32
STALL 21 ø50 ø40 APPROVED WITH COMMENTS
ø40
ø32
(COP:4877mm) ø40 ø40
ø32
STALL 22 ø40 STALL 19
ø50 STALL 20
V
ø32
STALL 23 Ø100 SPKP_HC CONDUIT PIPE
ø32
ø32
ø50
STALL 24 ø40 ø32 REJECTED, RESUBMIT
ø40
ø32
ø40
ø40 (COP:5231mm) ø50 COMBINED STATUS
ø40 ø32
ø40
ø32 ø50
ø100
STALL 26 Ø25 CONDUIT PIPE SPK
Ø100 SPKP_HC
ø50
ø40
SAP
ø32
FIRE EXTINGUISHER
)
STALL 28
ø32
Ø25mm CONDUIT PIPE ø32
(COP:5530mm
ø323350
TRAY RETURN
ø32
Ø50 HR_HC
S
ø32 Ø150 DR PIPE F/B & T/A
P
(HC)
ø32
DR1/HR
S
ø32
END CA
(COP:5231mm)
ø40
ø40 ø32
ø50
REJECTED, RESUBMIT
ø32
ø32
ø100
9565
ø50
ø32
ø65
BG
ø32
ø50
ø65
775
HR
ø40
ø32
ø32
TER
ø40
ø65 CENTRAL WASH
FAD(CC)
ø40
ø40
ø32
ø50
ø40
ø40
ø40
ø40
FL 3 / ø32 APPROVED
ø32
ø65
ø65 SL1
ø32
ø32 Evac
ø65
ø32
ø32
ø32
ø32
ø32
ø6
ø32
ø40
ø32
ø32
ø32
5
Lift
ø50
ø32
ø32
RW
ø40
ø32
ø32 REJECTED, RESUBMIT
ø32
ø32
ø32 ø50
ø65
ø32
ø40
ø32 ø40
ø40 ø32 ø40 FINAL COMBINED STATUS
ø32
ø32
ø32
ø40 ø32
W
ø32
ø32
void ø40 ø32
ø32
ø32
ø40 ø32
ø40
ø32
T
ø32 ø32 ø32
ø32 AS - BUILT
ø32
ø32
FIRE ø32 FIRE
ø32 ø32 planter
EXTINGUISHER EXTINGUISHER
(Type A)
ø32
ø40
ø32
ø40
S FIRE
ø32
ø32 MAIN CONTRACTOR
EXTINGUISHER
FIRE
EXTINGUISHER AS - BUILT DRAWING
X As-Built drawing certified correct and accurate:
Main Contractor's representative Sub-Contractor's representative
SPECIALIST SUB-CONTRACTOR:
Name : Name :
9/4/2021 3:12:08 PM
DRAWING TITLE
Name : Name :
Appointment : Appointment :
DATE SCALE
09/04/2021 As indicated
Company Stamp Company Stamp
DRAWN CHECKED
CHIT CHIT RUKSHAN
PROJECT ORIGINATOR DISCIPLINE TYPE ZONE STOREY NUMBER REV
Date : Date :
GL APP TF SD ++ 02 111 X
PROJECT TITLE
LEGEND CapitaSpring
Ø32 SPK PIPE AS - BUILT DRAWING PROPOSED ERECTION OF A 51-STOREY COMMERCIAL
S EXPOSED SPRINKLER HEAD DEVELOPMENT WITH A BASEMENT AND COMPRISING
SHOPPING / HAWKER CENTRE (AIR SPACE LOT)/
As-Built drawing certified correct and accurate:
4th Storey
123.900FFL Main Contractor's representative Sub-Contractor's representative
1 CUT-OFF SPRINKLER HEAD
SERVICED APARTMENT / OFFICE / MULTI-STOREY
CARPARK AND ANCILLIARY FACILITIES ON LOTS
Name : Name : 00505N & 00660X-PT, TS 01 AT MARKET STREET /
35
2 UNDER BEAM SPRINKLER HEAD CHULIA STREET / CHURCH STREET (DOWNTOWN
80
Signature : Signature :
Appointment : Appointment :
CORE PLANNING AREA)
ROYAL FLASH SPRINKLER HEAD
Company Stamp Company Stamp HIGHER K- FACTOR (K115) CLIENT
CL OFFICE TRUSTEE PTE. LTD.
ROYAL FLASH SPRINKLER HEAD 168 ROBINSON ROAD #24-01 CAPITAL TOWER
EN AP
D
SINGAPORE 068912
90
CONCEALED SPRINKLER HEAD
00
TEL: +65 6713 2888 FAX: +65 6713 2999
Date : Date :
Q
As-Built drawing verified and vetted by: SIDE WALL SPRINKLER HEAD
ARCHITECTS RSP ARCHITECTS PLANNERS & ENGINEERS (PTE) LTD.
Client/Consultant site staff Consultant's representative ø3 3 1 KALLANG JUNCTION #03-01
SINGAPORE 339263
Name : Name :
2
ø3 ø40 4 FS FLOW SWITCH
Tel : +65 6737 7544 Fax : +65 6291 7809
70
ø3 2 ø40
0
2 ø40 ø32 STRUCTURAL
Signature : Signature : ø3 CONSULTANT
ARUP SINGAPORE PTE. LTD.
2 ø32
FIR
ø32 10 HOE CHIANG ROAD #26-01 KEPPEL TOWERS
HOSEREEL DRUM
EE
Appointment : Appointment :
P ø32
80
XT
SINGAPORE 089315
IN
65
Ø5
TEL: +65 6411 2500 FAX: +65 6411 2501
GU
0
ø3
HR
ø3
ISH
2
FIR
68
2
PIP GUI
E
Company Stamp Company Stamp ø3
00
WET RISER LANDING VALVE
EE
STRUCTURAL MEINHARDT (SINGAPORE) PTE. LTD.
R
ø3
ET
2 2
XT
ø 32 ENGINEER
/B
5850
IN
FO
168 JALAN BUKIT MERAH CENTRAL #09-01 SURBANA ONE
ø 32
RO
5
SH
SINGAPORE 150168
ø3
R(
ø3 ø32
ER
2 DRY RISER LANDING VALVE TEL: +65 6377 9293 FAX: +65 6274 0788
2
BY
2 ø3
Date : Date :
GR
ø3
A
ø 32
BECA CARTER HOLLINGS & FERNER (S.E. ASIA) PTE. LTD.
VIT
M&E
6
20
Y)
CONSULTANT
ø 32
ø3
STANDBY HOSE
80
ø3
Ø6 SH 1 GATEWAY DRIVE #12-01 WESTGATE TOWER
2
80
ø3
MN
5S 2
2
66
PK 2 ø3 SINGAPORE 608531
PIP 2 TEL: +65 6220 7588 FAX: +65 6225 6937
ø 32 ø3
7
ø3
27
E 2 DOUBLE STANDBY HOSE
ø3
ø3 ø3
ø 40
2
T/B
00
2SH
2
2
(O M&E SQUIRE MECH PTE. LTD.
ø3 2
R) 0 ENGINEER
4 0 ø4
ø3
ø 32
ø 40 1 KALLANG JUNCTION #03-01
ø3
2
ø
ø 40
ø3
0
STROBE LIGHT
2
SINGAPORE 339263
82
2
8
27
0 TEL: +65 6378 5533 FAX: +65 6291 7809
20
ø3 ø4
2 ø40
HR
ø3
QUANTITY
ø40
ALARM BELL ARCADIS SINGAPORE PTE. LTD.
2
ø3
SURVEYOR
2
2
ø40
ø3
1 MAGAZINE ROAD #05-01 CENTRAL MALL
3rd Storey ø3
ø32
SINGAPORE 059567
00
116.900FFL 2 TEL: +65 6222 3888 FAX: +65 6224 7089
L
(BOP:3639mm)
ø3 MANUAL CALL POINT
75
ø32
2
Ø50 HR_OR
2
ø3
LANDSCAPE
75
COEN DESIGN INT. PTE. LTD.
ø32
ø3
ø32
0m R
00
CONSULTANT
97 P_O
2
2
ø3
MIMIC PANEL
m)
ø3 14 MM 67 UBI ROAD 1 #06-10/11 OXLEY BIZHUB
P:7 PK
0
45
ø4
2
(BO 100 S
ø3 void SINGAPORE 408730
E 2 TEL: +65 6844 9888 FAX: +65 6844 9555
Ø
CA ND
ø32
ø3
Ø6 R F
SECTION C-C
ø32
ø32
P 2 FIRE EXTINGUISHER
5 S UT
FO
0 KEY PLAN
ø4
PK UR
Ø ø40 ø32
2 K ø3 ø3
ø32
PP EP
2 (BO 100 S 2
9
ø3
15
IPE RO
0
30
0
2
26 P:61 PKP SMOKE DETECTOR
80
1 : 50 ø4 S
51
ø3
49 _O
2
32 32
V
mm R
10
ISI
ø ø 2
J ) ø3
ON
2
ø3 ø3 WET CHEMICAL CYLINDER
m
2
vo
&
vo
H
id
id
e
ø3
ø4
sh
2
2 2
ø3
0
ø3
aft
70
ø3
ø3
2 0 2 S CONCEALED SMOKE DETECTOR
2
ø4
23
ø4
32 ø3
0
ø3
ø4
ø
vo
ø3 0
0
ø4
id
2
30
ø4
2 2
ø3 ø3
0
12
ø4
ø3
MI 0mm
ø3
MI
2
38
C (W
2
25
PA )x1
FA
33
ø3
2
D(
NE 00
2 2 2
ø3
ø3
ø3
CC
2
ø3
2
ø3 ø3
L mm
ø3
2
)
2
2
ø3
ø3
ø3
ø1
2
ø3
G
FIR
00
2
00
70
FIR XTIN
2
(D
ø3 2
EH
ø1
Ø5 RAVØ W E T GUIS
pr
ø3
)x5
62
ø3
E
E GU
es
2
0 ITYR
OS
ø3
10
G 50
2 1 TI/RBE
su
1
ø3
2
HR ) PIP ANS HER
vo
mm
E
15
ø3
riz
FL
id
2 PR 0Ø
PIP E F
at
2
(H
OW
ø3 2
50
11
ISH
ø3
ion
FI
)
ø3 OV SP
E F /A & R P
2
&
Ø EXT
SW
2
F
ER
ISI KP
FIR IN
ø3
59
ø3
/A
M
ø3
P
ITC
ON PIP
FIR XTIN
& T T/B ( E F/
2
20
N
2
vo
Ø1 50 S PR
H(
2
EF
/B
E
E
ø3
R
SH
ø3
id
5
OR
ø5
HR
FO Y GR
2
Ø1 0
0 S PK P DRA
ø3 UR
TE R)
)
0
26
R C AV
ø3
2
PK IP IN
FE
GU
TU
L
2
ø3
Ø1 B
ø3
S
2
SP
B
2
(O
C(
RE
ISH
PIP E F/ PIP FL 1
5
S
2
0
2
2
T/
ø6
2
BY TY)
R/
ø3
FL
ø3
IP
ø3
ER
E
S
WR
ø3
27
/
ø3 2
HR
I
50
A
F
00
EL )
S
2
2 ø3
RO
ø3
ø1
B
V
2
FS
(S
T E R)
ø4
2
ø3
28
ø3
ø4
M UMP
ø3
FA
S
ø3
00
R
L1
ø3
CV ø F
2
0
D(
2
ø3
(O
F
ø6
0
M
75
(H C
ø3 2
CC
2
ø4
(C) L P
3-2 32 OR
2
P
T P
ø3
C)( L
EL
TE )
)
S
0
EL R)
2
S
1F
FL c Li
ø3
ø3
F
2
ø4
ø3
Ø
E
L
EC
4m R
SR
2
ø3
&
(S
OR V
(BO 100 S
2
Ev
13 P_O
2
ø3
2 ft
(O
EL R)
ø3
)
S
0
ø3
a
EC (
16
ø4
OR
m)
2
S
ø4 2
P:6 PK
2
(S
(S A
2
ø3
lift ft
ø3 P:6 PK
C
CH R)
ø3 0 ø3
R)
ø3
(BO 150 S
sh
2 32 P_O
2
32
ø4
2
2
a
0 ø3
ø4
(O
90
S
ø4
2
0m R ø
0
0
ø3
R)
Ø
PL
0
lift ft
00
EL C)
ø4
0
vo
m)
0
S
ø3
SA
S
EC
ø4
id
2
ø1
sh
12
GA R)
E
ø3
2
(C
2
ø4
ø3
OM
a
CA ND 00 ø3
ING
S
2
(O
2
RO
ø3
5
vo
HT
ø6
P
ø5
ø5
0
id
PR ALVEDR
LI G
R
ø4
ø3
lift ft
CH R)
0
VE
0
EA
V Ø32
ø3
ø5
2
sh
SE
W
E
S
2
2
ø3
(O
CT IN P
AR
a
ø3
2
ø3
ø3
TE TRE
2
IO
SP
ø6
lift ft
CE
NA
N
S
2
ø3
0
ø3 ø3
ø3
A
5
sh
ø4
NT LIFT
EL )
ø3
2
a
2 S
V
ø3
ø3
SE LOB
13
(O
0
IPE
ø4
2
2
2
E
ø4
ø5
RV
S
75
ø3
HT
Z2
ø4
IC BY
T/B
lift
ø3
2
E
0 REV BY DATE DESCRIPTION
ø3
sh
ø3
lift ft
ø3
ø3
2 ø1
ø3
0
af t
S
2
2
ø4
sh
2
2
00
35
2
ø3
0
ø3
a
ø5
CP
80
5
0
00
2 Ø1
ø6
ø3
ø4
ø3
ø1
ø6 00
lift
ø3
50
2
3
ø3
2
ø3
vo
5
sh
DR
D
2
2
2 8500
ø1
FIR H RAV
2
id
ø3
ø3
af t
2
5
ø3 PIP CHECKED
0
ø6
E E R P ITY
0
Ø5 Y G
S
ø4
ø5
S
2 E
0
XT IPE )
lift
(B
ø3
0
F/B
ø1
ø4
DR
lift ft
IN
sh
LIG CC)
ø3
2
00
ø3
GU T/B
ISSUED WITH COMMENTS
af t
HR
2
sh
05
HT
2
CP
vo
2
ø3
00
2
a
ISH FO
ø3
S
HR
I NG ( C
id
ø3
2
LIG C)
ø3
29
(
2
2
ø3
ø3
ø1
ø1
lift
ø3
ø3
ø3
TE R)
2
0
ER R O
2
HT
Ø50 HR PIPE F/B
2
2
ø4
00
sh
L1
0
S
ø3 (HC) REJECTED, RESUBMIT
ING
ø5
(O
lift ft
ø3
af t
S
2 Ø100 DR PIPE
sh
2
EL R)
ø4 F/B
EL C)
V
ø3
R
lift ft
0 S
(S
2
EC
0
ø4
lift
ø3
ø4
S
sh
(C
FIRE EXTINGU
C
vo
ø3
Ø1 OP:6
sh
0
a
ø3
id
EL R)
2
af t
2
ø4
5
ø4
ø4
S
ø3
2
(B
EC (S
87 CC
0 S 460
3000
CP
ø3 S
00 32
lift
EL )
(S
0
0
(C
70
m)
P:5 R_
PK mm
2
sh
V
ø3
2
CH R)
HR
APPROVED
SP 4m
(O
7m
ø3
1
47
lift ft
af t
(BO 150 W
ø3
P_ )
2
ø3
W
ø3
R
2
sh
CL ROO
S
2
KP m )
ø3
OR
2
ø3
89 HC
2
U
2
2 ø32
ø3
TE R)
a
ø3
2
EA M
ø4
ø3
PL OR)
m)
ø3 2
ø3
Ø
2
P:4 R_
ø3
L2
_O
NE
2
/G
ø3
0m
(O
2 ø3 S
lift
(BO 50ø H
2
STALL 1
RS
DC
ø4
AS
R
(
2
ø32
sh
ø3 ø4 S
ø4
2
0
af t
EN
ø3
ø3
ø4
ø4 0
Ø
2
2 0 STALL 2
lift
REJECTED, RESUBMIT
ø3
EL C)
2
lift ft
0
2
5 0
2
ø32
sh
TE )
V
ø3
52
ø65
2
ø3
sh
lift ft
(H
af t
ø3
L
S
(O
a
0
ø3
40
sh
2
ø4
ø5
R
lift
2
ø3
a
ø3
2
2
14 0
ø3
0
ø3
EL R)
sh
2
ø4
S
ø32
ø3
2
ø3
TE C) (HC
ø3
EC
COMBINED STATUS
af t
L
(O
2 Ø
2
ø4
(H
0
ø3
2
(CO 150 S
ø40
5
0
ø4
ø3
PL S
2
ø6
ø32
ø3
/
Ø5
lift ft
ø3
GA )
P:6 PK
0
2
00
sh
0
ø4
ø3
lift ft
60
EL C)
SP
2
57 P_O
a
ø40
0
ø40
ø3
ø3 S
sh
EC
ø4
KP
82
(H
a
2
B ø5
2
2
Ø3
vo
2
IPE
sh
m)
MA
ø3 35
2
ø3
2
ø3
ø3 ø3
ø3
id
ø3
ø3
ø3
a
ø32
2
LE
2 00
0
ø5 120
2
T/B
2
2
SP
ø3
ø4
2
ø3
ø3
8m R
HT
REJECTED, RESUBMIT
TO
0
Ø1 HR
KP
0
(O
ø3
ø32
9 9 P_ O
ø3
2
ø4
I LE
Ø5
50 PIP
R)
ø40
ø3
ø32
IPE
2
ø32
2
T
0
m)
ø3
WR E
2
ø3
0
0
S
P:5 PK
0
ø3
ø4
F/A shaf
ø4
2
ø40
ø4
ø4
ø40
2
ø3
PIP T/B (
ø32
(CO 150 S
ø3
ø3 2
l&ift t
ø4
ø3 Ø100ø SPKP_HC ARCHITECT'S REVIEW (RSP, NIPEK)
0
ø3
2
ø5
E F OR
T/B
ø32
ø3 2
0
ø5
ø3
ø3
2
ø3
2
ø5
2
ø3
/A )
0
2
ø3
0
2
ø40
ø4
2
ø3
2
ø5
(C
2
ø3
ø3
APPROVED
2
2
2
ø50
C)
ø3
ø3
ø3
ø3 2
2
ø40
0
Ø100 SPKP_HC
ø3
ø3
(COP:5259mm)
ø5
2
ø40
(COP:4738mm)
ø3
ø3
0
ø3
ø32
0
ø32
2
ø4
ø5
2
ø3
ø3
Ø1 OP:5
m
ø3
2
00 70
vo
(B
0
2
&
2
ø3
2
0
ø5
id
SP 0m
ø3
sh
FEMALE TOILET
ø3
ø4
2
ø3
ø3
0
2
2
2
ø3
aft
ø5
REJECTED, RESUBMIT
2
KP m)
ø3
ø3
2
2
ø3
2 SECTION C-C
ø3
ø50 ø32
2
ø3 ø32
_O
ø3
ø3
2
75
2
2
0
ø3
2
32 35
ø3
R
ø3
ø4
2 ø32
ø3
76
2
2
ø 120 STALL 21
ø32
0
2
0
0
ø3
ø3
ø4
ø4
2
2
Ø100 SPKP_HC
ø3
ø3
ø32
0
32
ø40
(COP:5191mm)
ø4
2
Ø1 OP:6
ø32
2
2
0
ø3
Ø25mm COND
4m R
Ø50 HR_OR
ø3
ø3
0
ø4
0
00 32
ø3
ø4
(C
0
ø3
ø3
ø32
2
ø4
ø3
ø3
ø32
2
ø3
0
ø4
A
SP 4m
(BOP:4890mm)
2
2 STALL 25
m)
ø3
ø4
AS - BUILT
0
ø3
2
ø32
P:6 PK
0
2
ø4
ø3
KP m )
2 ø3 ø32
ø32
0
ø3
ø32
vo
ø32
STALL 26
ø32
(CO 150 S
2
ø4
ø32
id
_O
2
ø3
0
2
ø3
ø3
ø4
ø3
ø3 ø40
0
R
ø40
0
ø4
ø32
ø32
2
ø32
ø4
ø32
Ø
ø3
ø32
0
0
ø 32
ø3
ø4
ø3
2
ø5
0
2
2
ø4
ø3
ø32
ø4
ø3
2
2
2
ø3
2
ø3
ø3
ø3
ø3 ø3 ø32
2
2
ø40
ø3
ø3
ø50
2 ø40
ø32
2 ø32 ø32 ø32
ø32 ø32
ø32
MAIN CONTRACTOR
ø32
2
ø32
2
2
ø32
ø3
ø32
HR
ø3
2
ø3
ø32
ø32
ø40
ø3
END CAP
ø4
ø50
ø32 ø32
ø3
S S
2
0
ø3
ø3 ø3
2
HR
ø40
2
ø50
0
ø32
2
2 2
ø3
ø4
ø3
Ø100 SPKP_OR
ø32
MANAGER
2
ø3
ø32
ø3 HC METERING
ø3
2
2
ø3
2
2
ø3
2
2
ø3
ø32
ROOM
ø3
(COP:5815mm)
ø3
ø3
Ø150ø SPKP_OR
ø32
KIOSK STORE
2
2
ø3
ø3
ø32
2
2
ø32
(COP:6553mm)
ø32
ø3
ø3
ø3
ø3
ROOM
ø32
ø32
ø100
ø32
ø3 2
ø40
ø32
ø32
ø32
0
00
2
2
ø4
2
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø1
ø3
2
ø3
T
2
ø40
ø3
ø3
ø3
ø3
2
ø32
2
2
ø3
ø3
ø3
ø3
ø3 SPECIALIST SUB-CONTRACTOR:
2
2
2 ø40
2
FFL 116.95
ø3
ø3
ø3 ø32
ø3
2 ø3
ø3
2
2 ø32 ø32 ø32 APP ENGINEERING PTE LTD
X
CERT. NO. : 2000-1-0221
2 Ø150 SPKP_OR 11 TOH GUAN ROAD EAST ISO 9001 : 2015
9/4/2021 2:18:24 PM
14 S DRAWING TITLE
1 1 : 150 DRAWN
09/04/2021
CHECKED
As indicated
GL APP TF SD ++ 03 120 X
PROJECT TITLE
27 CapitaSpring
12 28
Q 29
PROPOSED ERECTION OF A 51-STOREY COMMERCIAL
DEVELOPMENT WITH A BASEMENT AND COMPRISING
13 LEGEND SHOPPING / HAWKER CENTRE (AIR SPACE LOT)/
30 SERVICED APARTMENT / OFFICE / MULTI-STOREY
31 CARPARK AND ANCILLIARY FACILITIES ON LOTS
8500 32 EXPOSED SPRINKLER HEAD 00505N & 00660X-PT, TS 01 AT MARKET STREET /
10200 33 CHULIA STREET / CHURCH STREET (DOWNTOWN
1420 34 CUT-OFF SPRINKLER HEAD CORE PLANNING AREA)
8500
ø32 8500
35
36 UNDER BEAM SPRINKLER HEAD CLIENT
ø50 8500 37 CL OFFICE TRUSTEE PTE. LTD.
ø50 8500 ROYAL FLASH SPRINKLER HEAD 168 ROBINSON ROAD #24-01 CAPITAL TOWER
SINGAPORE 068912
ø50 ø32 ø40
ø32 8500 TEL: +65 6713 2888 FAX: +65 6713 2999
ø32
ø32
2
ø50
ø32
8500 CONCEALED SPRINKLER HEAD
ø3
ø32
ø40 Tel : +65 6737 7544 Fax : +65 6291 7809
ø65
ø32
ø32
ø32
ø40
ø65
605 U
SINGAPORE 089315
ø32
DOUBLE SLAB
ø32
TEL: +65 6411 2500 FAX: +65 6411 2501
SPK PIPE F/B FOR
ø40 HOSEREEL DRUM
ø32
ø65
ø32 DOUBLE SLAB ENGINEER
DOUBLE SLAB SPK PIPE F/B FOR ø40 168 JALAN BUKIT MERAH CENTRAL #09-01 SURBANA ONE
ø32
ø32
ø32
DOUBLE SLAB STALL 20
V WET RISER LANDING VALVE SINGAPORE 150168
ø32
ø32
ø50
ø50
ø50
SPK PIPE F/B FOR ø50 ø32 ø32
ø32 M&E BECA CARTER HOLLINGS & FERNER (S.E. ASIA) PTE. LTD.
ø40
ø32
DOUBLE SLAB
SPK PIPE F/B FOR ø32 ø32
DRY RISER LANDING VALVE CONSULTANT
ø32 1 GATEWAY DRIVE #12-01 WESTGATE TOWER
ø65 DOUBLE SLAB SPK PIPE F/B FOR SINGAPORE 608531
DOUBLE SLAB TEL: +65 6220 7588 FAX: +65 6225 6937
ø32
ø40
SH STANDBY HOSE
ø50
ø32
ø50
ø40 ø40
ø32
M&E
ENGINEER
SQUIRE MECH PTE. LTD.
SPK PIPE F/B FOR
ø32
ø50
2SH 1 KALLANG JUNCTION #03-01
DOUBLE SLAB
ø32 ø32 SINGAPORE 339263
ø32
ø32
(BOP:6083mm)
ø32 ø32 TEL: +65 6378 5533 FAX: +65 6291 7809
DOUBLE SLAB SPK PIPE F/B FOR ø40
ø50
STROBE LIGHT
Ø150 DR
DOUBLE SLAB
ø32
ø32 QUANTITY
ARCADIS SINGAPORE PTE. LTD.
ø32
ø32 ø32 SURVEYOR
ø32
SPK PIPE F/B FOR 1 MAGAZINE ROAD #05-01 CENTRAL MALL
ø32
ø32
ø32
DOUBLE SLAB ALARM BELL SINGAPORE 059567
TEL: +65 6222 3888 FAX: +65 6224 7089
ø32
ø50
ø32 ø150 LANDSCAPE
COEN DESIGN INT. PTE. LTD.
ø32
ø40 MANUAL CALL POINT CONSULTANT
ø40
ø40 ø50
W 67 UBI ROAD 1 #06-10/11 OXLEY BIZHUB
SINGAPORE 408730
ø32
TEL: +65 6844 9888 FAX: +65 6844 9555
MM MIMIC PANEL
T ø32 KEY PLAN
FIRE EXTINGUISHER
S Ø150 DR PIPE T/A
S SMOKE DETECTOR
X WET CHEMICAL CYLINDER
27
12 28 3RD STOREY DOUBLE SLAB
2
29 1 : 150
13 30
35
80
8500 31
Q 8500 32
33
N
Ø50 HR PIPE F/B 10200
Ø100 DR PIPE
(HC)
F/B Ø25mm CONDUIT PIPE 8500
34
FIRE EXTINGU
ISHER 8500
35
HR FIRE EXTINGU
ISHER 36
8500
37
89 HC
ø32
m)
P:4 R_
ø32
8500
Ø
STALL 2 ø32
ø32
ø65
FIRE
ø32
ø32 STALL 10
ø32
E
2
ø40
STALL 7 STALL 11
ø32
FOR OR (BY GR
ø32
ø32
ø32
ø32 AVITY)
ø40
ø32
ø32
ø32 FIRE EXTINGU
ø32
ø32
ø32
ø32
ø32
ISHER
ø32
(BOP:4839mm) 135
ø32 ø40 Ø50 HR PIPE F/A FOR REV BY DATE DESCRIPTION
ø40
ø32
(CC)
OR (BY GRAVITY)
ø32
FAD
ø50 STALL 18
HR
ø32
10mm)
ø32
(CC)
STALL 13
FAD
ø32
ø32
ø32
Ø150 DR_HC
ø40
ø32
ø40
STALL 15
ø32
ø32
ø32
STALL 14
CH (HC)
:4835
ø32
ø32
ø32
ø32
Ø50 HR_OR
ø32
ø40
ø32
ø40
(BOP23
ø40 ø32 STALL
ø32
17
ø40
ø32 CHECKED
ø50
ø32
ø40
ø32
ø40
FLOW SW IT
ø50
FOR CONTINUATION PLEASE REFER TO
ø40
Ø100 SPKP_HC
ø32
ø32
(COP:4738mm)
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø50
2050
ø32
ø32
ISSUED WITH COMMENTS
ø32
ø32
ø32
2200
ø40
ø32
DWG NO. : GL/APP/TF/SD/++/03/120 X
1440
ø40
ø32
ø32
ø40
ø50
ø32
(BOP:5259mm)
ø32
1665
ø32
ø32
ø32
Ø150 SPKP_HC
ø32
ø40
ø32
ø32
ø32
ø32 STALL 20 ø32
ø32
ø32
ø32
ø32
STALL 21
V
ø32
(COP:5259mm) (BOP:5259mm)
ø50
ø32
ø50
ø50
STALL 22
ø32
Ø100 SPKP_HC
STALL 23
ø32
(COP:5191mm)
ø32
ø3
ø100 ø32
Ø25mm COND 2 ø32 MIMIC PANEL
ø32
ø32
ø32
UIT PIPE ø40 ø40
ø40
APPROVED
ø50
ø32
ø50 ø32 ø40
ø32
ø32
ø32
ø40
ø32
ø32
STALL 25 SAN
FS
SAN
ø32
ø32
ø40
ø32
ø32
ø40
ø40
SPK
ø32
(CC)
ø32
ø32
FAD
ø32
ø32
(HC)
ø32
P
ø50 ø50 Ø25mm CONDUIT PIPE (HC) ø32 FOR CONTINUA ø32 Ø100 SPKP_HC
END CA
Ø100ø SPKP_HC CONDUIT PIPE 285 TI
ON PLEASE RE Ø100 SPKP_HC
ø32
ø32 ø32
ø32
ø32
ø40
(BOP:5191mm) UBLE SLAB
ø32
S
ø50
(HC)
S
UIT PIPE T/B ø40
ø32
FFL116.85
ø40
ø50
ø50
ø32
ø40
ø32
ø65
ø32
ø32
ø32
DR1
ø32
ø32
ø40
CENTRAL WASH
ø32
9565
ø32
ø40
ø32 Ø100 SPK DRAIN PIPE T/B ø32
775
ø40
ø50
HR
ø40
ø32 ø32
ø32
W Ø100 SPKP_HC
ø32
ø32
ø32
ø32
) (BOP:5224mm) ø100
ø40
ø32
ø32
ø32
ø32
ø32
ø32
ø50
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32
ø32 REJECTED, RESUBMIT
ø32
ø40
ø32
ø32
RW
ø32
ø32
ø40
ø32
ø50
ø32
ø40
ø32
ø32
ARCHITECT'S REVIEW (RSP, NIPEK)
ø32
ø40 ø40
ø50
ø32
ø32
ø32 ø32 APPROVED
ø32
ø32
ø40
ø32
ø32
FIRE
W
ø32
ø40 ø40
ø32
ø32
ø32 EXTINGUISHER APPROVED WITH COMMENTS
ø32
FIRE ø32
ø32
T ø32
ø32
EXTINGUISHER REJECTED, RESUBMIT
ø32
ø32
FFL 116.95
ø32
FIRE
ø32
EXTINGUISHER FINAL COMBINED STATUS
S ø32
AS - BUILT
FIRE
EXTINGUISHER X
MAIN CONTRACTOR
AS - BUILT DRAWING
3RD STOREY PART 2 OF 2 As-Built drawing certified correct and accurate:
1 1 : 150
Main Contractor's representative Sub-Contractor's representative
SPECIALIST SUB-CONTRACTOR:
Name : Name :
9/4/2021 2:58:18 PM
DRAWING TITLE
Name : Name :
Appointment : Appointment :
DATE SCALE
09/04/2021 As indicated
Company Stamp Company Stamp
DRAWN CHECKED
CHIT CHIT RUKSHAN
PROJECT ORIGINATOR DISCIPLINE TYPE ZONE STOREY NUMBER REV
Date : Date :
GL APP TF SD ++ 03 121 X