DC Switches 2015

The document provides specifications for Telergon DC isolators for photovoltaic applications, including the ZFV32, ZFV32x2, and ZFV32EL models. The isolators are compact 4P or 8P non-polarized switches rated up to 32A and 1500V DC, with fault-make load-break operation ideal for DC systems. They have oxidation-proof contacts, IP20 or IP65 protection, and can accommodate cable sizes from 4-16mm2.

Uploaded by

Rizky N
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views

DC Switches 2015

The document provides specifications for Telergon DC isolators for photovoltaic applications, including the ZFV32, ZFV32x2, and ZFV32EL models. The isolators are compact 4P or 8P non-polarized switches rated up to 32A and 1500V DC, with fault-make load-break operation ideal for DC systems. They have oxidation-proof contacts, IP20 or IP65 protection, and can accommodate cable sizes from 4-16mm2.

Uploaded by

Rizky N
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

Telergon DC Isolators

for Photovoltaic applications


Spec Sheet: ZFV32
 Compact 4P non polarized isolator 32A rated up to 1500V DC.
 Fault-make load-break switch operation, ideal for DC systems.
 DIN profile complete with direct mounted padlockable handle.
 Terminals rated to IP20.
 Oxidation proof contacts with up to 16mm 2 cable capacity.
Application: PV array isolators.
Certification: EN 60947.3, UL 508, File E332938.
Dimensions & Ratings
Free air thermal current (Ith) 32A
Rated insulation pollution degree III (Ui) 1000V
Rated insulation pollution degree II (Ui) 1500V
Rated impulse withstand voltage (Uimp) 8kV
Ambient temperature Enclosed -40 to +45
Maximum Fuse (A) 80
Rated Conditional Short-cct Current 5kA
Rated Short-cct Making Capacity 1.7kA
Short Time Withstand (1sec) 1kA
Power Loss / pole 4.0W
Mechanical Endurance 10,000
Weight 0.2kg
Operating torque 1.7Nm
Connection torque 1.2 – 1.8Nm
Cable Size mm2 4-16

The contact ratings need to be read in conjunction with AS5033-2012


Appendix B5 for floating PV systems with transformerless inverters.
See over.

Dimensions

May 2015
Spec Sheet: ZFV32x2
 Compact 8P non polarized isolator up to 32A and up to 1500V DC.
 Fault-make load-break switch operation, ideal for DC systems.
 DIN profile complete with direct mounted padlockable handle.
 Terminals rated to IP20
 Oxidation proof contacts with up to 16mm 2 cable capacity.
Application: PV array isolators.
Certification: EN 60947.3, UL 508, File E332938.
Ratings
Free air thermal current (Ith) 32A
Rated insulation pollution degree III (Ui) 1000V
Rated insulation pollution degree II (Ui) 1500V
Rated impulse withstand voltage (Uimp) 8kV
Ambient temperature Enclosed -40 to +45
Maximum Fuse (A) 80
Max padlock shank size 5mm
Rated Conditional Short-cct Current 5kA
Rated Short-cct Making Capacity 1.7kA
Short Time Withstand (1sec) 1kA
Power Loss / pole 4.0W
Mechanical Endurance 10,000
Weight 0.4kg
Operating torque 3.4Nm
Connection torque 1.2 – 1.8Nm
Cable Size mm2 4-16
The contact ratings need to be read in conjunction with AS5033-2012
Appendix B5 for floating PV systems with transformerless inverters.
See over.

Dimensions
Dimensions in mm

May 2015
Spec Sheet: ZFV32EL
 Compact enclosed 4P non polarized isolator 32A rated up to 1500V DC.
 Fault-make load-break switch operation, ideal for DC systems.
 Padlockable handle and external mounting position.
 Oxidation proof contacts with up to 16mm2 cable capacity.
 IP65 protection and UV stabilised.
Application: PV array isolators.
Certification: EN 60947.3, UL 508, File E332938.
Dimensions & Ratings
Free air thermal current (Ith) 32A
Rated insulation pollution degree III (Ui) 1000V
Rated insulation pollution degree II (Ui) 1500V
Rated impulse withstand voltage (Uimp) 8kV
Ambient temperature Enclosed -40 to +45
Maximum Fuse (A) 80
Rated Conditional Short-cct Current 5kA
Rated Sshort-cct Making Capacity 1.7kA
Short Time Withstand (1sec) 1kA
Power Loss / pole 4.0W
Mechanical Endurance 10,000
Weight 0.2kg
Operating torque 1.7Nm
Connection torque 1.2 – 1.8Nm
Cable Size mm2 4-16
The contact ratings need to be read in conjunction with AS5033-2012
Appendix B5 for floating PV systems with transformerless inverters.
See over.

Dimensions

May 2015
ZFV32 - Technical Data
Data according to IEC 60947-3, Main Contacts Type ZFV32
VDE 0660, GB1448.3 (CCC China) Rated thermal current Ithe A 32 Making &
Rated insulation voltage Ui1) V 1000 Breaking
Rated insulation voltage Ui2) V 1500 5x
Distance of contacts (per pole) mm 8 operations
Rated operational current Ie 300V A 27 40.5
DC21A 1 pole 400V A 16 24
and A1 500V A 13 19.5
DC21B 600V A 10 15
1 800V A 5 7.5
L/R = 1ms 1000V A 2.5 3.75

2 poles in series 500V A 32 48
DC21B A2 600V A 32 48
700V A 27 40.5
800V A 23 34.5
900V A 20 30
1000V A 13 19.5
1 2
1200V A 10 15
1500V A 5 7.5

2 poles in series 500V A 58 87
+ 2 poles parallel 600V A 50 75
A2+2 700V A 27 40.5
800V A 23 34.5
1 2 900V A 20 30
1000V A 13 19.5
3 4
1200V A 10 15
1500V A 5 7.5

3 poles in series 500V A 32 48
A3 600V A 32 48
700V A 32 48
800V A 32 48
900V A 32 48
1000V A 32 48
1 2 3 1200V A 16 24
1500V A 13 19.5

3 poles in series 500V A 58 87
+ 2 poles parallel 600V A 50 75
A3 + 2 700V A 45 67.5
800V A 45 67.5
1 2 3 900V A 45 67.5
1000V A 45 67.5
4 5 6
1200V A 16 24
1500V A 13 19.5

4 poles in series 500V A 32 48
A4 600V A 32 48
700V A 32 48
800V A 32 48
900V A 32 48
1 2 3 4 1000V A 32 48
1200V A 32 48
1500V A 23 34.5

4 poles in series 500V A 58 87
+ 2 poles parallel 600V A 58 87
1) Suitable at overvoltage category I to III, pollution degree 3 A4 + 2 700V A 58 87
(standard-industry): Uimp = 8kV. 800V A 58 87
1 2 3 4 900V A 58 87
5 6 7 8 1000V A 58 87
2) Suitable at overvoltage category I to III, pollution degree 2
1200V A 50 75
(min. IP55): Uimp = 8kV. 1500V A 23 34.5

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au Ref.0614E


PV Isolators
Complies with AS/NZ 5033
(as per CEC Technical note Oct 2010)

Configuration 1

Leg 1 Leg 2
Rating per leg (2 contacts in series)
500V 600V 700V 800V 900V 1000V
32A 32A 27A 23A 20A 13A

Configuration 2

Leg 1 Leg 2 Leg 1 Leg 2

Rating per leg (1 contacts in series)


250V 300V 350V 400V 450V 500V
32A 32A 27A 23A 20A 13A
Spec Sheet: ZFV55
Features:
- Compact non polarized isolator 55A rated up to 1500V DC.
- Fault-make load-break switch operation, ideal for DC systems.
- DIN profile complete with direct mounted padlockable handle.
- Terminals rated to IP20.
- Oxidation proof contacts with up to 16mm2 cable capacity.
- Application: PV array isolators.
- Certification: IEC 60947-1 & 3

Dimensions & Ratings


Free air thermal current (Ith) 55A
Rated insulation pollution degree III (Ui) 1000V
Rated insulation pollution degree II (Ui) 1500V
Rated impulse withstand voltage (Uimp) 8kV
Ambient temperature Enclosed -40 to +45

Rated Operational Current DC21B*


(according to IEC 60947.3 and VDE 0660) 4P in Series
at 600V DC 55A
at 700V DC 55A
at 800V DC 55A
at 900V DC 55A
at 1000V DC 55A
at 1200V DC 32A
at 1500V DC 15A
Maximum Fuse (A) 125A
Rated Conditional Short-cct Current 5kA
Mechanical Endurance 10,000
Weight 0.3kg
Connection torque 2.5 - 3Nm
Cable Size mm2 2.5 - 16 (without
cable termination)
*(time constant 1ms resistive load + moderate overload)

CONNECTIONS

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au Ref.1114F


ZFV55 Series - Technical Data
Data according to IEC 60947-3 DC21B

Main Contacts Type ZFV55


Rated thermal current Ithe A 55
Rated insulation voltage Ui V 1500
Rated Operational voltage Ui V 1500
Rated impulse withstand voltage V 6kV
Tightening torque (M5 screw) Nm 2.5 - 3.0
Max cable size (flexible) mm² 16
Rated operational current Ie Voltage Making & Making &
Rating Breaking Breaking
(DC) DC21B 5 x operations
DC21B 1 pole 500V A 25.0 37.5
600V A 20.0 30.0
700V A 15.0 22.5
800V A 10.0 15.0
900V A 8.0 12.0
1
1000V A 6.0 9.0
2 pole in series 500V A 55.0 82.5
600V A 55.0 82.5
700V A 55.0 82.5
800V A 45.0 67.5
900V A 35.0 52.5
1000V A 25.0 37.5
1 2
1500V A 15.0 22.5
4 pole in series 500V A 55.0 82.5
600V A 55.0 82.5
700V A 55.0 82.5
800V A 55.0 82.5
900V A 55.0 82.5
1000V A 55.0 82.5
1 2 3 4
1500V A 15.0 22.5

Notes:

For the requirements of AS 5033 2012 Appendix B, with 2 x contacts in series in Positive (+) and
2 x contacts in series in the negative (-):

900V VOC ARRAY MAX, 4 x strings with Isc max of 8.9A (before Table 4.2 of AS 5033 2014)

1000V VARRAY MAX, 3 x Strings with Isc max of 8.9A (before Table 4.2 of AS 5033 2014)

1. If the series bridges are removed then the above ratings are not applicable.
2. VOC ARRAY MAX = VOC ARRAY + Yv (Tmin x TSTC) M (as per Clause 4.2 of AS5033 2014)

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au Ref.1114F


Spec Sheet: TFV5011
 Compact 2P non polarized isolator 50A rated up to 1000V DC.
 Fault-make load-break switch operation, ideal for DC systems.
 Padlockable handle with terminals rated to IP20.
 DIN profile for mounting in any DIN slot.
 Rotary oxidation proof contacts.
 Up to 2 x 4mm2 cables or 1 x 10mm2 fork lug.
Application: PV array isolators.
Certification: IEC 60947.3, UL 508, File E332938.
Dimensions & Ratings

Free air thermal current (Ith) 50A


Rated insulation voltage (Ui) 1500V
Rated operational voltage (Ue) 1000V
Rated impulse withstand voltage (Uimp) 6kV
Ambient temperature (Ith) -30 to +50
Rated Short-cct Making Capacity 1.4kA
Short Time Withstand (1sec) 1.0kA
Short-time withstand current (1 hour) 62.5
Mechanical Endurance 30,000
Weight 0.2kg
Operating torque 4Nm
Connection torque 1.5 – 2.0Nm
Cable Size mm2 2x4mm

The contact ratings need to be read in conjunction with AS5033-2012


Appendix B5 for floating PV systems with transformerless inverters.
See over.
)
Dimensions

L = 65.6mm

May 2015
Spec Sheet: TFV5022
 Compact 4P non polarized isolator 50A rated up to 1000V DC.
 Fault-make load-break switch operation, ideal for DC systems.
 Padlockable handle with terminals rated to IP20.
 DIN profile for mounting in any DIN slot.
 Rotary oxidation proof contacts.
 Up to 2 x 4mm2 cables or 1 x 10mm2 fork lug.
Application: PV array isolators.
Certification: IEC 60947.3, UL 508, File E332938.
Dimensions & Ratings

Free air thermal current (Ith) 50A


Rated insulation voltage (Ui) 1500V
Rated operational voltage (Ue) 1000V
Rated impulse withstand voltage (Uimp) 6kV
Ambient temperature (Ith) -30 to +50
Rated Short-cct Making Capacity 1.4kA
Short Time Withstand (1sec) 1.0kA
Short-time withstand current (1 hour) 62.5
Mechanical Endurance 30,000
Weight 0.24kg
Operating torque 4Nm
Connection torque 1.5 – 2.0Nm
Cable Size mm2 2x4mm

The contact ratings need to be read in conjunction with AS5033-2012


Appendix B5 for floating PV systems with transformerless inverters.
See over.
)
Dimensions

L = 77.5mm

May 2015
TFV50 Series - Technical Data
Data according to IEC 60947-3 DC21B

Main Contacts Type TFV Series


Rated thermal current Ithe A 50.0
Rated insulation voltage Ui V 1500
Rated Operational voltage Ui V 1000
Rated impulse withstand voltage V 6kV
Distance of contacts (per pole) mm 9.0
Rated operational current Ie Voltage Making & Making &
Rating Breaking Breaking
(DC) DC21B 5x operations
DC21B 1 pole 200V A 50.0 75.0
250V A 40.0 60.0
300V A 25.0 37.5
450V A 10.0 15.0
1
500V A 8.0 12.0
2 pole in series 400V A 50.0 75.0
500V A 40.0 60.0
600V A 25.0 37.5
850V A 10.0 15.0
1 2
1000V A 8.0 12.0
3 pole in series 400V A 50.0 75.0
500V A 50.0 75.0
600V A 50.0 75.0
800V A 32.0 48.0
900V A 25.0 37.5
1 2 3
1000V A 20.0 30.0
4 pole in series 400V A 50.0 75.0
500V A 50.0 75.0
600V A 50.0 75.0
800V A 50.0 75.0
900V A 50.0 75.0
1 2 3 4
1000V A 40.0 60.0
Fault Break Rating for 1 pole
Complies with requirements of AS5033 – Appendix B2 Clause d
Test Report No: TFV 4 Chambers_DC_2013_11_11
5x 1 pole
operations 1 600V A 11.0

Notes:
1) The TFV series has been tested to IEC 60947.3 as per the requirements of AS5033 clause
4.3.5.1
2) The “Fault Break Rating” is a requirement of AS 5033 Appendix B5. Should a switch be used to
isolate and break under these fault conditions it should be replaced to ensure guaranteed
performance.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au Ref.0614F


TFV5011 Wiring Instructions
CONNECTIONS
1 x MPPT

MPPT 1 3
1 MPPT 1

Array 1 2
4 Array 1

Note:
to be installed by a licensed electrician.
CONNECTIONS
Stranded or flex cable (without sleeves) 2 x 1.0 - 6mm²
Stranded or flex cable (with sleeves) 2 x 1.0 - 4mm²
Crimp fork lugs (width) min 6mm - max 10mm
Crimp fork lugs (thickness) min 0.5mm - max 2mm
Fork lugs 4 - 6mm² (pack of 100) GFU4*
Fork lugs 10mm² (pack of 100) ANE2U4
Fork lugs 16mm² (pack of 100) ANE3U4
Tightening torque 1.5 - 2.0Nm
*Recommended

FINAL CHECKLIST PRIOR TO ENERGISING


Check correct cable / terminal combination, APPLICATION.

Check correct terminal tightening torque applied, SCREW TENSION.

Check cable is tight in terminal, and secure.

Cable strain relief to AS3000 with no excess stress on terminals.

Switch electrical test to AS5033.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


TFV5022 Wiring Instructions
CONNECTIONS
Series 7 Inverter 2 2 x Array
Link Inverter 1 5
3 Inverter 2
Inverter 1 1
Remove
Links

8 Array 1
Array 2 6
4 Array 1
Array 2 2

Note:
to be installed by a licensed electrician.

CONNECTIONS
Stranded or flex cable (without sleeves) 2 x 1.0 - 6mm²
Stranded or flex cable (with sleeves) 2 x 1.0 - 4mm²
Crimp fork lugs (width) min 6mm - max 10mm
Crimp fork lugs (thickness) min 0.5mm - max 2mm
Fork lugs 4 - 6mm² (pack of 100) GFU4
Fork lugs 10mm² (pack of 100) ANE2U4
Fork lugs 16mm² (pack of 100) ANE3U4
Tightening torque 1.5 - 2.0Nm

FINAL CHECKLIST PRIOR TO ENERGISING


Check correct cable / terminal combination, APPLICATION.

Check correct terminal tightening torque applied, SCREW TENSION.

Check cable is tight in terminal, and secure.

Cable strain relief to AS3000 with no excess stress on terminals.

Switch electrical test to AS5033.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


TFV5022 Wiring Instructions
CONNECTIONS
7 1 x Array
5
3
1

8 Inverter
Array 6
4 Inverter
Array 2

Note:
to be installed by a licensed electrician.

CONNECTIONS
Stranded or flex cable (without sleeves) 2 x 1.0 - 6mm²
Stranded or flex cable (with sleeves) 2 x 1.0 - 4mm²
Crimp fork lugs (width) min 6mm - max 10mm
Crimp fork lugs (thickness) min 0.5mm - max 2mm
Fork lugs 4 - 6mm² (pack of 100) GFU4
Fork lugs 10mm² (pack of 100) ANE2U4
Fork lugs 16mm² (pack of 100) ANE3U4
Tightening torque 1.5 - 2.0Nm

FINAL CHECKLIST PRIOR TO ENERGISING


Check correct cable / terminal combination, APPLICATION.

Check correct terminal tightening torque applied, SCREW TENSION.

Check cable is tight in terminal, and secure.

Cable strain relief to AS3000 with no excess stress on terminals.

Switch electrical test to AS5033.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au


Data sheet:
DC-Load break switch
Model S5000 – 100A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (40 ºC) 125A


Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 8

DC Rated operational current Ie (A)


Category of
Voltage (DC)
operation
Ie
400 V DC21B 125
600 V DC21B 125
800 V DC21B 125
900 V DC21B 125
1000 V DC21B 100

Short-circuit behaviour
Short-circuit making capacity (peak value) Icm 20kA
Standards. IEC 60947-1&3 Short-time withstand current (1 sec) (rms) Icw 12kA
Conditional short-circuit current (rms value) 100kA
Quality Telergon, S.A.U. Maximum cut-off current (peak value) 33kA

IS0 9001 & 14001 Connection capacity


Bar (Thickness / Width) (mm) 7/25
2
Rigid cable (mm ) 185
Max. Connecting copper bar (mm) 25
Testing as per IEC 60947-3 Tightening torque (N·m) 13

Mechanical data
Arsenal Research Minimum number of operations (as per standard)
without load 20000
Maximum weight (4 pole molded case) (kg) 1,9

Codes
Case size (A) Poles Code Code for direct
handle
Size 1 4P S5-01254PR0 DS-EI11

Accessories: Panel handle - DS-EN11


Bridging links - DS-PI11
Protective plate - DS-CU12
Auxiliary contact - D5LAU01
Dimensions
Data sheet:
DC-Load break switch
Model S5000 – 160A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (40 ºC) 200A


Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 8

DC Rated operational current Ie (A)


Category of
Voltage (DC)
operation
Ie
400 V DC21B 200
600 V DC21B 200
800 V DC21B 180
900 V DC21B 160
1000 V DC21B 160

Standards: IEC 60947-1&3


Short-circuit behaviour
Short-circuit making capacity (peak value) Icm 20kA
Quality Telergon, S.A.U. Short-time withstand current (1 sec) (rms) Icw 12kA
Conditional short-circuit current (rms value) 100kA
IS0 9001 & 14001
Maximum cut-off current (peak value) 33kA

Connection capacity
Testing as per IEC 60947-3 Bar (Thickness / Width) (mm) 7/25
2
Rigid cable (mm ) 185
Arsenal Research Max. Connecting copper bar (mm) 25
Tightening torque (N·m) 13

Mechanical data
Codes Minimum number of operations (as per standard)
Case size (A) Poles Code Code for direct without load 20000
handle Maximum weight (4 pole molded case) (kg) 1,9
Size 1 4P S5-02004PR0 DS-EI11

Accessories: Panel handle - DS-EN11


Bridging links - DS-PI11
Auxiliary contact - D5LAU01
Protective plate - DS-CU12
Terminal shrouds – See below
Dimensions
Data sheet:
DC-Load break switch
Model S5000 – 250A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (40 ºC) 315A


Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 8

DC Rated operational current Ie (A)


Category of
Voltage (DC)
operation
Ie
400 V DC21B 315
600 V DC21B 315
800 V DC21B 280
900 V DC21B 260
1000 V DC21B 250

Standards. IEC 60947-1&3


Short-circuit behaviour
Quality Telergon, S.A.U. Short-circuit making capacity (peak value) Icm 20kA
Short-time withstand current (1 sec) (rms) Icw 12kA
IS0 9001 & 14001 Conditional short-circuit current (rms value) 100kA
Maximum cut-off current (peak value) 33kA

Testing as per IEC 60947-3 Connection capacity


Bar (Thickness / Width) (mm) 7/25
2
Arsenal Research Rigid cable (mm ) 185
Max. Connecting copper bar (mm) 25
Tightening torque (N·m) 18

Codes Mechanical data


Case size (A) Poles Code Code for direct Minimum number of operations (as per standard)
without load 20000
handle
Size 1 4P S5-03154PR0 DS-EI11 Maximum weight (4 pole molded case) (kg) 1,9

Accessories: Panel handle - DS-EN11


Bridging links - DS-PI11
Auxiliary contact - D5LAU01
Protective plate - DS-CU12
Terminal shrouds – See below
Dimensions
Data sheet:
DC-Load break switch
Model S5000 – 400A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (40 ºC) 400A


Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 8

DC Rated operational current Ie (A)


Category of
Voltage (DC)
operation
Ie
400 V DC21B 400
600 V DC21B 400
800 V DC21B 400
900 V DC21B 400
1000 V DC21B 400

Short-circuit behaviour
Short-circuit making capacity (peak value) Icm 20kA
Standards: IEC 60947-1&3 Short-time withstand current (1 sec) (rms) Icw 12kA
Conditional short-circuit current (rms value) 100kA
Maximum cut-off current (peak value) 33kA

Quality Telergon, S.A.U.


IS0 9001 & 14001 Connection capacity
Bar (Thickness / Width) (mm) 7/40
2
Rigid cable (mm ) 185
Testing as per IEC 60947-3 Max. Connecting copper bar (mm) 40
Tightening torque (N·m) 24
AIT – Austrian Institute
of Technology

Mechanical data
Codes Minimum number of operations (as per standard)
Case size (A) Poles Code Code for direct without load 20000
handle Maximum weight (4 pole molded case) (kg) 1,9
Size 1 4P S5-04004PC0 DS-EI11

Accessories: Panel handle - DS-EN11


Bridging links - DS-PI14
Protective plate - DS-CU12
Auxiliary contact - D5LAU01
Dimensions
Data sheet:
DC-Load break switch
Model S5000 – 500A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (-30 to 50 ºC) 630A

Rated insulation voltage Ui (V) 1000


Rated impulse withstand voltage Uimp (kV) 12

DC Rated operational current Ie (A)


Voltage (DC) Category of operation Ie
400 V DC21B 630
600 V DC21B 630
800 V DC21B 600
900 V DC21B 600
1000 V DC21B 500
** Please consult for other voltages and/or category of
operation

Standards. IEC 60947-1 & 3 Short-circuit behaviour


Short-circuit making capacity (peak value) Icm 26kA
Short-time withstand current (1 sec) (rms) Icw 16kA
Quality Telergon, S.A.U.
Conditional short-circuit current (rms value) 100kA
Maximum cut-off current (peak value) 39kA
IS0 9001 & 14001
Connection capacity
Bar (Thickness / Width) (mm) 2X5/40
2
Rigid cable (mm ) 2X240
Testing as per IEC 60947-3. Approvals Max. Connecting copper bar (mm) 40
Tightening torque (N·m) 24
Austrian Institute of
Technology
Mechanical data
Minimum number of operations (as per
standard) without load 10000
Maximum weight (4 pole molded case) (kg) 4,5

Codes
Case size (A) Poles Code Code for direct handle
Size 2 4P S5-06304PR0 DS-LI21

Accessories
Panel handle DS-LA21
Bridging links DS-PI21
Protective plate DS-CU22
Auxiliary contact D5LAU01

You will find detailed information about our products on our web site www.telergon.es
TELERGON, S.A.U.
DC Switch-Disconnector
Data subject to change without
S5-06304PR0 notice (printed: 19/08/2013)
Dimensions

You will find detailed information about our products on our web site www.telergon.es
TELERGON, S.A.U.
DC Switch-Disconnector
Data subject to change without
S5-06304PR0 notice (printed: 19/08/2013)
Data sheet:
DC-Load break switch
Model S5000 – 500A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (-30 to 50 ºC) 630A

Rated insulation voltage Ui (V) 1000


Rated impulse withstand voltage Uimp (kV) 12

DC Rated operational current Ie (A)


Voltage (DC) Category of operation Ie
400 V DC21B 630
600 V DC21B 630
800 V DC21B 600
900 V DC21B 600
1000 V DC21B 500
** Please consult for other voltages and/or category of
operation

Standards. IEC 60947-1 & 3 Short-circuit behaviour


Short-circuit making capacity (peak value) Icm 26kA
Short-time withstand current (1 sec) (rms) Icw 16kA
Quality Telergon, S.A.U.
Conditional short-circuit current (rms value) 100kA
Maximum cut-off current (peak value) 39kA
IS0 9001 & 14001
Connection capacity
Bar (Thickness / Width) (mm) 2X5/40
2
Rigid cable (mm ) 2X240
Testing as per IEC 60947-3. Approvals Max. Connecting copper bar (mm) 40
Tightening torque (N·m) 24
Austrian Institute of
Technology
Mechanical data
Minimum number of operations (as per
standard) without load 10000
Maximum weight (4 pole molded case) (kg) 4,5

Codes
Case size (A) Poles Code Code for direct handle
Size 2 4P S5-06304PR0 DS-LI21

Accessories
Panel handle DS-LA21
Bridging links DS-PI21
Protective plate DS-CU22
Auxiliary contact D5LAU01

You will find detailed information about our products on our web site www.telergon.es
TELERGON, S.A.U.
DC Switch-Disconnector
Data subject to change without
S5-06304PR0 notice (printed: 19/08/2013)
Dimensions

You will find detailed information about our products on our web site www.telergon.es
TELERGON, S.A.U.
DC Switch-Disconnector
Data subject to change without
S5-06304PR0 notice (printed: 19/08/2013)
Data sheet:
DC-Load break switch
Model S5000 – 630A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (40 ºC) 800A


Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 12

DC Rated operational current Ie (A)


Category of
Voltage (DC)
operation
Ie
400 V DC21B 800
600 V DC21B 800
800 V DC21B 775
900 V DC21B 700
1000 V DC21B 630

Short-circuit behaviour
Short-circuit making capacity (peak value) Icm 26kA
Standards: IEC 60947-1&3
Short-time withstand current (1 sec) (rms) Icw 16kA
Conditional short-circuit current (rms value) 100kA
Maximum cut-off current (peak value) 39kA
Quality Telergon, S.A.U.
IS0 9001 & 14001
Connection capacity
Bar (Thickness / Width) (mm) 2*5/40
2
Testing as per IEC 60947-3 Rigid cable (mm ) 2*240
Max. Connecting copper bar (mm) 240
AIT – Austrian
Tightening torque (N·m) 24
Institute of
Technology

Codes Mechanical data


Case size (A) Poles Code Code for direct Minimum number of operations (as per standard)
handle without load 10000
Size 2 4P S5-08004PC0 DS-EI21 Maximum weight (4 pole molded case) (kg) 4,5

Accessories: Panel handle - DS-EN21


Bridging links - DS-PI21
Protective plate - DS-CU22
Auxiliary contact - D5LAU01
Dimensions
Data sheet:
DC-Load break switch
Model S5000 – 850A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (40 ºC) 1250A


Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 12

DC Rated operational current Ie (A)


Category of
Voltage (DC)
operation
Ie
400 V DC21B 1250
600 V DC21B 1250
800 V DC21B 1000
900 V DC21B 870
1000 V DC21B 850

Short-circuit behaviour
Short-circuit making capacity (peak value) Icm 60kA
Short-time withstand current (1 sec) (rms) Icw 25kA
Standards. IEC 60947-1&3 Conditional short-circuit current (rms value) 72kA
Maximum cut-off current (peak value) 55kA

Quality Telergon, S.A.U. Connection capacity


Bar (Thickness / Width) (mm) 2*10/50
IS0 9001 & 14001 2
Rigid cable (mm ) 2*300
Max. Connecting copper bar (mm) 300
Tightening torque (N·m) 45
Testing as per IEC 60947-3
AIT – Austrian Institute
of Technology
Mechanical data
Minimum number of operations (as per standard)
without load 10000
Codes Maximum weight (4 pole molded case) (kg) 7,6
Case size (A) Poles Code Code for direct
handle
Size 3 4P S5-12504PC0 DS-EI31

Accessories: Panel handle - DS-EN31


Bridging links - DS-PI31
Auxiliary contact - D5LAU01
Dimensions
Data sheet:
DC-Load break switch
Model S5000 – 1250A 1000V DC21B

Electrical data (according to IEC 60947-3)

Thermal current Ith (40 ºC) 1800A


Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 12

DC Rated operational current Ie (A)


Category of
Voltage (DC)
operation
Ie
400 V DC21B 1800
600 V DC21B 1800
800 V DC21B 1500
900 V DC21B 1350
1000 V DC21B 1250

Standards. IEC 60947-1&3


Short-circuit behaviour
Short-circuit making capacity (peak value) Icm 100kA
Short-time withstand current (1 sec) (rms) Icw 50kA

Quality Telergon, S.A.U.


IS0 9001 & 14001

Connection capacity
Testing as per IEC 60947-3 Bar (Thickness / Width) (mm)
2
2*7/80
Rigid cable (mm ) --
Max. Connecting copper bar (mm) --
Arsenal Research Tightening torque (N·m) 55

Codes
Case size (A) Poles Code Code for direct Mechanical data
handle Minimum number of operations (as per standard)
Size 4 4P S5-18004PS0 DS-EI41 without load 1000
Maximum weight (4 pole molded case) (kg) 20,8
Accessories: Panel handle - DS-EN41
Bridging links - DS-PI41
Auxiliary contact - D5LAU01
Dimensions