1) The document provides structural design calculations for columns and foundations. It analyzes axial loads, bending moments, and reinforcement sizing for various load cases. 2) Key outputs include minimum concrete cover requirements, column design loads and moments, effective heights, reinforcement areas, and checks for axial capacity and moment strength. 3) Short and slender column conditions are identified for different sections based on calculations of effective length and slenderness ratio. Design moments are checked against various limit states as defined in design codes.

Uploaded by

rudolf
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views

Column Design

1) The document provides structural design calculations for columns and foundations. It analyzes axial loads, bending moments, and reinforcement sizing for various load cases. 2) Key outputs include minimum concrete cover requirements, column design loads and moments, effective heights, reinforcement areas, and checks for axial capacity and moment strength. 3) Short and slender column conditions are identified for different sections based on calculations of effective length and slenderness ratio. Design moments are checked against various limit states as defined in design codes.

Uploaded by

rudolf
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 14

BS8110 CALCULATIONS OUTPUT

ref.
3.2:2.1 SUB-FRAME ANALYSIS-refer to main beam
3.3 Tables Durability and Fire resistance Minimum cover to
3.3 Nominal cover for mild conditions of exposure = 20mm Internal 20 (use 30
Nominal cover for severe conditions of exposure= 40mm External 40mm
3.4 Nominal cover for 300x300 columns for 1 hr period= 20mm
Internal Column (Foundation →Roof) F2 (typical)
Axial loading and moments from analysis
Beam Column design loads Column
loads KN KN moments KN
Total Imposed Dead Top Botto
m
Load Case 1 2 1 2 1 2 1 2 1 2
Roof 24 24 54 53 195 191 3 5
9 4 4 4
21 13 46 164 133 32 58
0 3
Sw. 9 9
10 53 368 333
0
rd
3 Fl 29 29 14 13 3 5
3 0 0 6 2 8
24 11 11 132 117 32 58
9 7 7
Sw. 9 9
35 18 667 613
7 9
2nd Fl 29 29 14 13 158 154 3 5
8 0 0 6 2 8
24 11 11 132 117 35 65
9 7 7
Sw. 9 9
61 32 966 893
4 5
st
1 Fl 30 29 14 13 159 155 1 3
0 2 1 7 9 4
25 12 11 134 120
2 0 8
14 14
Foundation 87 46 127 118
s 3 2 3 2
3.8.1.6 (Foundation – first floor)
Eqn.30 Effective height l e =βl 0

Table 3.19 N- S
β=0.9 (End condition: top 1, bottom 3)
l ex =0.9 x 4.5=4.05 m
l ex 4.05
= =13.5
h 0.3
3.8.1.3 E-W
β=0.95 (End condition: top 2, bottom 3)
l ey =0.95 x 4.825=4.58 m

l ey 4.58
= =15.26>15 Slender column
b 0.3

BS 8110 Calculations Output


ref
Internal column (Foundation – 1st floor) continued
Load case 1

BS6399 Imposed = 100 + 0.8 x 773 = 718


Part 1 Dead = 1273
N= 1991kNm

3.8.3.2 M 1=0
M 2=19
M i=0.4 M 1 +0.6 M 2=0+ 0.6x19=11.4>7.6

-32
Eqn= -34 Nh
-35 M add = ¿
2000
3.8.2.4 Min.Eccentricity=0.05x300=15mm Max design mome
3,8.3.2 Max. design moment will be greatest of: 68kNm
a. M 2=19 kNm
b. M i + M add =11.4 +54.4=65.8 kNm
15
c. e minx N = x 1991 = 29.9 kNm
1000
N 1991 x 103
= =22.1
bh 300
2

6
M 65.8 x 10
= 2
=2.44
bh 300

Assume d=300-40-13=247mm
d
Use =0.8(chart
h
d 247 28) BS8110 Part 3
= =0.82
h 300 1985

100 Asc
=2.8
bh
3.8.1.1.
Asc =2420 mm 2

3.8.3.1. N bal =0.25 f cu bd =0.25x40x300x247x10−3 =741kN


Since N> N bal = try 4T25(1960mm 2 ¿
Eqn 33
N U =¿x40(300x300-1960)+0.87x460x1960)x10−3 =2369 kN

2369−1991
K= =0.23
2369 x 741

Design moment = 11.4+0.23x54.4=23.9<29.9kNm


100 Asc 100 x 1960 N
= =2 ,18 , =22.1(as before)
bh 300 x 300 bh Ok

M
From chart, 2
=1.6 , M =43.2> 29.9 kNm
BS6399 bh

Check, considering: load case 1 above 1st floor and


Eqn 36 Load case 2 and moment at 1st floor
Imposed = 100 + 0.8(514+137) = 621
Dead = 966 + 289 = 1255
Total =1876kN

M 1=0
M 2=34 kNm
M i=0+ 0.6+34+ 20.4 kNm
1876 x 54.4
M add = =51.3 kNm
1991
2369−1876
k= =0.3
2369−741

Design moment = 20.4 +0.3x51=35.8> M 2


N
=20.8
bh

100 Asc
=2.18
bh
Ok.
M
3.12.3.7 2
=2.0
bh
2.4.32. M=54>35.8 kNm

Ok.

Tie provision
161
Load =1.05(214+ )=281kN
3
3
10
As=281x = 610mm 2<1960 mm 2
460

External Column (Foundation – roof)


Axial loading and movement from analysis

Beam loads KN Column design Column moments


loads KN KN
Total Impose Dead Top Bottom
d
3.8.1.6. Load Case 1 2 1 2 1 2 1 2 1 2
Eqn.30 Level Mai 19 19 42 43 150 154 10 11
Table 3.19 n 2 7 8 5
Roof edg 99 99 99 99 98 10
e 5
Sw. 9 9
42 43 258 262
3rd Fl Mai 24 25 11 12 131 135 98 10
n 7 5 6 0 5
edg 12 12 125 125 98 10
e 5 5 5
3.8.1.3.
Sw. 9 9
15 16 523 531
3 3
2nd Fl Mai 24 25 11 12 131 135 98 10
n 7 5 6 0 5
edg 12 12 125 125 10 11
e 5 5 8 7
Sw. 9 9
27 28 788 300
4 3
BS6399 1st Fl Mai 24 25 11 11 130 134 71 76
Part 1 n 5 3 5 9
edg 12 12 125 125
e 5 5
Sw. 11 11
Foundatio 38 40 105 107 Short column
ns 9 2 4 0

Foundation – 1st floor


Effective height l e =β l 0
N-S
β=¿ 0.9 (end condition: top 1, bottom 3)
l ex =0.9 x 3.5=3.15 m
l ex 3.15
= =10.5
h 0.3

E-W
β=0.9 (End condition: top1, bottom 3)
l ey =0.9 x 3.65=3.285

BS6399 l ey 3.285
= =10.95< 15
Part 1 b 0.3

Design using load case 2


Just above 1st floor,
N=800 + 43 + 0.9(240) = 1059 kN
M = 117kNm
3
N 1059 x 10
= 2
=11.8
bh 300
6
M 117 x 10
2
= 2
bh 300
= 43

Assume d=300-50-13 = 237mm,


d 237
= =0.79
h 300

100 Asc
=2.3
bh

Asc = 2070 mm 2( 4 T 25=1960 mm2 )

Below 1st floor – foundations,


N= 1059-43 +0.8x359 = 189kN
M= 76 kNm

N
=15.4
bh

M
2
=2.81
bh

100 Asc
=1.5
bh

Asc = 1350 mm 2

Basic formulas
L D
e min = +
500 30

Pu=0.45 f cu Ac +0.67 f y A sc

A g= A c + A sc
Key points
1. Percentage of main steel = 0.8% to 6% gross c/s
2. Minimum 4 bars= rec/ 6 bars –circular
3. Transverse r/f (pitch)
- Least lateral dimensions
- 16d (small longitudinal bars)
- 300mm
4. Diameter of bar
- 0.35d
- 5mm
Steps in column design
1. Calculation of Ac by assuming A sc
2. Calculation of dimension of column, Ag
3. Calculation of dimension of main steel Ac
4. Calculation of transverse R/F

Load=1200kN
Length=3m
M20 and Fe415

Load = 12.4 kN
Factor load = 1.5 x 12.4
=18.6 kN (point)

Step 1 calculation of Ac
By assuming % of steel as 1% of gross area
1
A sc= + Ag
100
A sc=0.01 A g
A g= A c + A sc
Ac = A g −0.01 A g
A
So finally= c =0.99 A g

Step 2 calculation of dimensions of columns ( A g ¿


Pu=0.45 f cu AC +0.67 f y A sc
By substituting values
18.6x103=0.45x20x0.99 A g+0.67x415x0.01 A g
So A g=11.6905 mm2

By assuming rectangular column with area a 2


2 2
a =11.6905mm
a=3.41914 mm
Take a as 4 mm

Checking for e min


L D
e min = +
500 30

3500 400
= +
500 30
= 7 + 13,33
= 20,33>20
Hence safe

Step 3 calculation of area of main steel A sc


Pu=0.45 f cu Ac +0.67 f y A sc
A g= A c + A sc
Ac = A g −A sc
3
1800x10 =0.45 ( 20 ) ( A g −A sc ) +0.67 ( 415 ) ( A g− A sc )
=0.45(20)(153971.173)+0.67(415)
2
A sc=153971.711 mm
Take 1540 mm 2
By taking 16 mm diameter bars
2
π 16
1 bar = =201mm 2
4
1540
Number of bars = =7.661 bars
201
So take 8 bars of 16mm diameter

Step 4 calculating of R/C


- Least of
- 16d= 16 x 16 = 256 mm(centre to centre)
- Minimum lateral dimensions – 400 mm
- 300 mm

So c/c distance between ties 256 mm


Diameter of bars
0.25d- 0.25x16 = 4mm
5mm
So take 6 mm diameter bars

Given data
Number of stories = 5
Floor height = 3m
Size of primary beam = 230mm x 300mm
Size of secondary beam = 230mm x 230mm
Assume as per code
Live load on Roof slab = 1.5kNm2
Live load on floor slab = 3kN/m2
Floor finishing = 1kN/m2
Waterproofing load = 0.8 kN/m2

Load on roof slab


Thickness of slab = 125mm
Self-weight= thickness of slab x density of RCC
=0.125m x 25 kN/m2
=3.125kN/m2
=live load = 1.5 kN/m2
Floor finishes = 1kN/m2
Waterproofing =0.8kN/m2
Total load on roof = 3.125 + 1.5 + 1+ 0.8
=6.425kN/m2
Total factored load on roof = 1.5 x 6.425
=9.64 kN/m2

Load on floor slab:


Thickness of slab = 125 mm
Self-weight = thickness of slab x density of RCC
=0.125m x 25 kN/m3
= 3.124 kN/m2
Live load = 3kN/m2
Floor finishes = 1kN/m2

Total load on floor = 3.125 + 3 +1 = 7.125kN/m2


Total factored load on floor = 1.5 x 7.125 = 10.69 kN/m2
Total factored load on floor = 1.5 x 7.125 = 10.69 kN/m2

Load on the Beams:


Self-weight of Primary beam
= 0.23m x 0.3m x 25kN/m3
=1.725 kN/m

Factored self-weight of Primary Beam


=1.5 x 1.725
=2.587 kN/m

Self-weight of secondary beam


=0.23m x 0.23m x 25kN/m3
=1.322kN/m

Factored self-weight of secondary beam


=1.5 x 1.322 =1.983 kN/m

Wall loads
Height of external/internal walls= floor height – depth of beam
= 3m – 0.3m
=2.7m
Self-weight of external wall = thickness of wall x height of wall x density of
brick masonry
=0.23m x 2.7m x 20kN/m3
=12.42kNm

Factored self-weight of external wall


Self-weight of external wall
Self-weight of internal wall
=0.23m x 2.7m x 20kN/m3
=12.42kN/m

Factored self-weight of external wall


Self-weight of internal wall
Factored self-weight of internal wall
=1.5 x 12.42 = 18.63kN/m

Load transferred to column from each floor:


Area of slab surrounding the column= area of ABCD = 20m2
Length of primary beams surrounding column
1
= (length of bars inside the area)
2
=0.5(4+4+4+6)=9m

Length of secondary beam surrounding column


=0.5(length of b13)
=0.5x6=3m

Wall length under primary beams = 9m


Wall length under secondary beams = 0m

Load transferred from roof to 1st floor

Roof load (in terms of kN)


=total factored load on roof x area of roof surrounding column
=9.64kN/m2x 20m2
=192.8kN

Beam load (primary)


= factored self-weight of primary beams x length of primary beams
=2.587 x9
=23.28kN

Beam load(secondary)
Factored self-weight of secondary x length of secondary x ½
=1.983 x 3 x ½
=2.98kN

Wall load (primary)


Factored self-weight of primary walls x length of primary walls
= 18.63 x 9m
=167.7Kn
Wall load (secondary)
Total load from roof to 1st floor
= 192.8 + 23.28 + 2.98 + 167.7
= 387 kN

Load transferred from 1st floor to plinth :


Floor load (in terms of kN)
= total factored load on floor x area of floor surrounding column
=10.69 kN/m2x20m2
=213.8kN

Beam load (primary)


= factored self-weight of primary beams x length of primary beams
= 2.587 kN/m x 9m
2.98 kN

Beam load(secondary)
=factored self-weight of secondary beams x length of secondary beams x ½
=1.983kN/m x 3m x ½
=167.7 kN
Wall load (primary)=0
Factored self-weight of primary walls x length of primary walls
=18.63kN/m x 9m
167.7kN

Wall load (secondary) = 0


Total load from 1st floor to plinth
=213.8 + 23.28 +2.98 + 167.7 = 08 kN

Load transferred between plinth beam and footing (no walls and no secondary
beam):

Beam load (primary)


= factored self-weight x length of primary beams
= 2.587kN/m x 9m
=-23.38kN
= total 23.28kN

total self-weight of column


= column cross-sectional area x height of column x density of RCC
Column cross-section = 230mm x 300 mm

Height of column
= 2(floor height) + depth of plinth beam + depth of neck column
= 2(3) + (0.6) + 1
=7.6m
Total self-weight of column
=0.23m x 0.3m x 7.6m x 25 kN/m3
=13.11kN
Total load on column
=387kN + 408kN + 23.28kN + 13.11 kN
=832kN

Table
3.3.1.4

3.4.4.4

Reinforced Pad Footing


3.4.5.4 Fcu= 30 Fy =460

3.11.3.4(1 Durability
) Minimum nominal cover, moderate exposure= 25mm
3.4.5.8
Loading Dead Imposed Total kN
Internal column 1273 718 1991
design
Internal column 1273/1.4=909 718/1.6=449 1358
service

3.11.3.4(2
)
3.7.7.2
Allow 10kN/m2 extra over soil displaced by concrete and for ground flow loading
Pad area required= 1358/(200-10)=7.15 m2

Adopt 2.75×2.75×0.6 thick footing, area provided= 7.5>7.15 m2


Then U.L.S design pressure= 1991/2.752=263kNm2

Reinforcement
Moment at face of column = 263x2.75×1.2252/2=543kNm
Average d =600-40-25=535mm
312.11.2.7 M 543× 10
6

2= =0.017
F cu b d 30× 2750 ×5352

6
Ɛ 543× 10
=0.95 As = =2445mm2
d 0.95 ×460 × 0.95 ×535
3.11.3.2
ULTIMATE SHEAR
1
Minimum vc=0.34(40/ 25)3 = 0.4N/mm2

Condition 1:
1375−150−535
Shear force V@ ‘d’ from column face = 1991/2 x ( ¿ 500Kn
1375
3
500 ×10
Shear stress v @ ‘d’ from column design = = 0.34N/mm2
2750× 535
1991
Shear force V @ ‘2d’ from column face = ׿ )=112kN
2
3
112 x 10
Shear stress v ‘2d’ from column face = = 0.08N/mm2<vc
2750 x 535

Condition 2: (punching shear, usually the more critical)


V 1991× 10
3
Vmax= = = 3.1<5.0N/mm2
u0 d 4 x 300 x 535

Critical perimeter = 4(300+3+535) = 7620mm


Area within critical perimeter = (0.3+3+0.535)2=3.63m2
Shear on critical perimeter = 263(2.752-3.63) = 1034kN
3
1034 ×10
v= = 0.25N/mm2<vc
7620
cracking
clear distance = 330<750mm ok

100 A s 100 x 2445


= = 0.17<0.3%
bd 2750 x 535

Pc= 0.5x2750=1375<0.25(3c + 9d) = 0.25(3x300+9x535)=1429


Thus space bars uniformly across section, say @ 350 crs each way.