TCH KB12260
TCH KB12260
The KB Standard series consists in VRLA batteries - AGM technology (Absorbent Glass
Mat), with a design life of 6 - 8 years and it is designed for general applications such
as UPS, telecommunications and electrical applications.
125
Φ12
M5
5
176
Performance Characteristics
55
Nominal Voltage 12V 138.5 F13-BP TERMINAL
166
Dimensions Length (mm / inch) 166±1.5 / 6.54
Width (mm / inch) 176±1.5 / 6.93 Applications
Height (mm / inch) 125±1.5 / 4.92
Total Height (mm / inch) 125±1.5 / 4.92 Alarm systems Marine equipment
Approx Weight (Kg / lbs) 7.40 / 16.31 Cable television Medical equipment
Design Life Communications Equipment Micro processor based office machines
Terminal M5 Control Equipment Portable cine & Video lights
Container Material A.B.S. UL94-HB, UL94-V0 Optional. Computers Solar powered systems
Electronic Cash Registers Telecommunications systems
Rated Capacity 26.0Ah / 1.30 (20hr, 1.75V / cell, 25ºC / 77ºF)
Electric Test Equipment Television & Video recorders
20.11Ah / 6.70A (3hr, 1.75V / cell, 25ºC / 77ºF)
(1hr, 1.60V / cell, 25ºC / 77ºF) Emergency lighting systems Toys
15.09h / 15.09A
Fire & Security Uninterruptible power supply systems
Max. Discharge Current 7.8A (5s)
Internal Resistance Approx 12mΩ
Geophysical equipment Vending machines
Operating Temp. Range Discharge : -20 ~ 60ºC (-4 ~140ºF)
Charge : 0 ~ 50ºC (32 ~ 122ºF) Certifications
Storage : -20 ~ 60ºC (-4 ~ 140ºF)
25ºC± 5ºC
Charge Current Max. 5.4A
Cycle Use Voltage: 14.6V ~ 14.8V at 25ºC (77ºF)
Standby Use Voltage: 13.7V ~ 13.9V at 25ºC (77ºF)
Capacity affected by Temperature 40ºC (104ºF) 103% Discharge Current vs. Discharge Voltage
25ºC (77ºF) 100%
0ºC (32ºF) 86%
Self Discharge Fully charged Kaise Standard Series batteries may be Final discharge 1,75V 1,70V 1,60V
stored for up to 6 months at 25ºC (77ºF) and then a voltage V/CELL
freshening charge is required. For higher temperatures the Discharge current (A)≤0.2C 0.2 <C(A)<1.0C (A)≥1.0C
time interval will be shorter. (A)
Discharge Constant Current (Amperes) at 25ºC (77ºF) Discharge Constant Power (Watts per cell) at 25ºC (77ºF)
Volts/cell 5min 10min 15min 30min 1h 3h 5h 10h 20h Volts/cell 5min 10min 15min 30min 1h 3h 5h 10h 20h
1.80V 61.86 47.74 36.84 23.05 13.06 6.499 4.419 2.430 1.287 1.80V 110.8 87.25 68.25 43.61 25.14 12.62 8.640 4.802 2.547
1.75V 70.45 52.74 39.90 24.12 13.58 6.706 4.536 2.461 1.300 1.75V 123.5 94.73 72.88 45.17 25.99 12.97 8.837 4.858 2.570
1.70V 78.63 57.62 42.87 25.23 14.10 6.913 4.653 2.494 1.316 1.70V 134.9 101.7 77.20 46.78 26.81 13.32 9.034 4.916 2.598
1.65V 87.15 62.59 45.77 26.40 14.57 7.106 4.777 2.532 1.332 1.65V 146.1 108.4 81.21 48.45 27.54 13.63 9.243 4.985 2.627
1.60V 93.72 66.23 47.88 27.50 15.09 7.332 4.905 2.564 1.354 1.60V 155.4 112.6 83.70 49.45 28.36 14.00 9.454 5.039 2.665
(Note) The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
KB12260 12V 26Ah
100
0.16 2.30
2.00
0.14 Charge Voltage 2.25
80
0.12 2.20 1.84
60 0.10 2.15 0.1C
After 50% Discharge 0.25C 0.17C 0.05C
1.68
0.08 After 100% Discharge 2.10 0.55C
40 3C 1C
0.06 2.05 1.52
0.04 2.00
20
1.36
0.02 Charge Current 1.95
0 0.00 1.90 0
0 2 4 6 8 10 12 14 16 18 20 22 24 1 2 3 5 7 10 20 40 60 2 4 6 8 10 20
min h
Charging Time(h)
Life Characteristics of Cyclic Use Effect of Temperature on Long Term Float Life
10
Life Expectancy (y ears)
0
0 10 20 30 40 50
Temperature(℃)
120 100
100 A 0℃
0 .0 5 C 80
Capacity (% )
Capacity (% )
80
A
0 .2 5 C 60
10℃
60
0 .5 5 C A 20℃
40
40 40℃ 30℃
20
20
0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature(℃) Storage Time(months)
IMPORTANT NOTE: The specifications presented herein are subject to revision without notice.
2023/V1/R
Contacto
[email protected]
PANASONIC EVOLTA EL FUTURO DE LAS PILAS
www.tempelgroup.com
Tempel Group en el mundo
BARCELONA · MADRID · VALENCIA · BILBAO · SEVILLA · LISBOA · PORTO · BUENOS AIRES · LIMA
[email protected] BARCELONA
SANTIAGO DE CHILE· ·MADRID
BOGOTÁ ·· SÃO
VALENCIA
PAULO ·· MÉXICO
BILBAODF ·· CIUDAD
SEVILLADE PANAMÁ
· LISBOA · PORTO · QUITO
· MONTEVIDEO
www.tempelgroup.com
BUENOS AIRES · SANTIAGO DE CHILE · BOGOTÁ · SÃO PAULO · LIMA · MEXICO DF