DESCRIPTION
Selector Valves allow a single agent supply to be utilized for protection of multiple hazards, reducing the
total amount of agent and number of cylinders required.
When utilizing multiple cylinders to protect multiple hazards it is necessary to use Selector Valves to divert
the flow of agent into the activated hazard. The selector valves may be activated electronically or manually
by pneumatically connecting to the solenoid actuator provided with the selector valve.
APPROVALS:
Note: Special considerations shall be made when using a selector valve controlled system to protect adjacent hazards that • FM Approved
may simultaneously become involved in a fire.
Each Selector Valve is equipped with a Valve Position Monitor that provides a visual indication of the status
of the valve (open or closed).
The Selector Valve Assembly can be pneumatically operated by utilizing agent pressure from the fire
suppression agent piping network. A Universal Valve Operator (UVO) is installed in the piping network
(between the cylinder(s) and the selector valve assembly) to provide pressure to operate selector valve
when the UVO is either manually or electrically activated.
SPECIFICATIONS
Sizes: 1”, 1 1/2”, 2”, and 3” (25, 40, 50, and 80mm)
Material: Carbon Steel or Stainless Steel
End Type: NPT threaded ends (1”, 1 1/2”, 2”, and 3”/ 25, 40, 50, and 80mm)
Actuation Pressure: 116 psi (8 bar) minimum
ORDERING INFORMATION
Selector Valve Assembly includes:
• Selector Valve with Actuator and relief / pop-off valve
• ¼” Check Valve and ¼” NPT x ¼” JIC Adapter
• ¼” Swivel JIC End Hose Assembly – 3.0’ lg.
• Release Fitting w/ ¼” NPT (Male)
• UVO Kit
704 SW 10th Street P.O. Box 610 Blue Springs, Missouri 64013-0610 U.S.A.
Phone: 8162293405 www.fike.com
Note: Reducing bushings can be utilizes when connecting to a ½”, ¾”, 1 ¼” and 2 ½” piping network.
Allow 18” of clearance from the center line of the piping to the top of the indicator.
The Manifold Safety Disc is used to prevent entrapment of agent in closed sections of pipe. For details refer Component Spec P/N 06-631-1-6.
IG71 – 233 – XX – XX
A BC
A= 10 – 1”
15 – 1 ½”
20 – 2”
30 – 3”
B= C – Carbon Steel
S – Stainless Steel
C= D – UVO Kit
V – Valve only (not remote actuator)
2 of 3
INSTALLATION
Install the Selector Valve assembly and a tee for the UVO / Release fitting approx. 1.0 feet apart in the fire suppression agent piping
network.
Connect one end of the actuation hose (supplied with selector valve assembly) to selector valve assembly and the either to pressure port
on UVO.
Insert UVO into Release fitting and secure with Retaining Clip.
Important Note: Check UVO to ensure device is armed before inserting. The UVO should be the last component installed on the Fike
ProInert system. The following items should be completed prior to final installation of the UVO:
• Cylinder installation should be complete and secured in place
• Discharge piping installation should be complete and all bracing, brackets, etc. in place
• The discharge nozzles should be installed
• The detection & control system installation should be complete & tested – no faults shall be present