TMS01
TMS01
Technical Information
iTHERM
MultiSens Flex TMS01
Modular direct contact TC and RTD multipoint
thermometer for Oil & Gas and Petrochemical
applications
Application
• Easy-to-use device with modular and flexible design, ready to be installed either
for direct contact measurements, or in an existing thermowell
• Specifically designed for Oil & Gas and Petrochemical processing industries
• Measuring range:
• Resistance insert (RTD): –200 to 600 °C (–328 to 1 112 °F)
• Thermocouple (TC): –270 to 1 150 °C (–454 to 2 102 °F)
• Static pressure range: Up to 100 bar (1 450 psi). Specific maximum process
pressure achievable depending on the thermometer design and process
temperature
• Degree of protection: IP66/67
Head transmitter
All Endress+Hauser transmitters are available with enhanced accuracy and reliability
compared to directly wired sensors. Easy customizing by choosing one of the
following outputs and communication protocols:
• Analog output 4 to 20 mA
• HART®
• PROFIBUS® PA
• FOUNDATION Fieldbus™
Your benefits
• Infinite 3D sensors distribution layouts for any process monitoring configuration
• High density of measuring points thanks to the possibility to mount the ProfileSens
sensor technology
• High degree of customization thanks to a modular product design for easy
installation, process integration and maintenance
• Easy integration due to inserts according standard IEC 60584, ASTM E230 and IEC
60751
• Thanks to a proper junction box support frame design, overheating of electronic is
avoided resulting in a longer product lifetime
• Compliance to different types of protection for use in hazardous locations for a
wide and easy process integration
• Possibility of sensing elements replacement
iTHERM MultiSens Flex TMS01
Table of contents
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Performance characteristics . . . . . . . . . . . . . . . . . . 12
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Shock and vibration resistance . . . . . . . . . . . . . . . . . . . . 13
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . 15
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . 15
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . 16
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Process temperature range . . . . . . . . . . . . . . . . . . . . . . 16
Process pressure range . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mechanical construction . . . . . . . . . . . . . . . . . . . . 16
Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Process connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2 Endress+Hauser
iTHERM MultiSens Flex TMS01
Measuring system Endress+Hauser offers a complete portfolio of optimized components for the temperature measuring
point – everything you need for the seamless integration of the measuring point into the overall
facility.
This includes:
• Power supply unit/active barrier
• Configuration units
• Overvoltage protection
For more information, see the brochure 'System Components - Solutions for a Complete
Measuring Point' (FA00016K/09)
Endress+Hauser 3
iTHERM MultiSens Flex TMS01
3 4 5
7 7
6 6
5 5
1 1
+ +
2 2
- 4 - 4
3 3
7 7
6 6
5 5
1 1
+ +
2 2
- 4 - 4
3 3
+
-
+
-
+
-
+
-
+
-
+
-
1 2
HAW56x
HAW56x
HAW56x
HAW56x
1 IN 2 1 IN 2 1 IN 2 1 IN 2
A0028076
1 Application example in a reactor, mounted multipoint thermometer in a locally existing thermowell with
four measurement points and four built-in transmitters or terminal blocks.
1 Device configuration with application software FieldCare
2 Commubox
3 PLC
4 Active barrier RN221N (24 VDC, 30 mA) that has a galvanically isolated output for supplying voltage to loop-
powered transmitters. The universal power supply works with an input supply voltage of 20 to 250 V DC/AC;
50/60 Hz, which means that it can be used in all international power grids.
5 Mounted multipoint thermometer in a locally existing thermowell, optionally with built-in transmitters in the
junction box for 4 to 20 mA-, HART-, PROFIBUS® PA-, FOUNDATION Fieldbus™ communication or terminal
blocks for remote wiring.
6 Surge arrester modules HAW562 for protection of signal lines and components in hazardous areas, e.g.
4 to 20 mA- , PROFIBUS® PA, FOUNDATION Fieldbus™ signal lines. More information on this can be found
in the Technical Information → 29
Equipment architecture The multipoint thermometer belongs to a range of modular product configuration for multipoint
temperature detection with a design where subassemblies and components can be managed
individually for easy maintenance and spare part ordering.
It consists of the following main sub-assemblies:
• Single point insert: Done by a metal sheathed sensing measuring element (thermocouple or
resistance), extension cables and transition bushing. When applicable, each insert can be handled
as an individual spare part that may be replaceable by untightening its compression fitting
installed onto the process connection. They can be ordered via specific standard product order
codes (e.g. TSC310, TST310) or special codes. For the specific order code please contact the
Endress+Hauser service department.
• Multiple insert: Composed of a plurality of independent metal sheated thermocouple cables in
one probe, each of them provided with its seal pot and extension cables resulting in a dual seal
insert design (Endress+Hauser ProfileSens).
• Process connection: Represented by an ASME or EN flange, it might be provided with eyebolts for
lifting the device.
• Head: It is composed of a junction box provided with its components such as cable glands, draining
valves, earth screws, terminals, head transmitters, etc.
• Neck: It is designed to support the junction box by components such as supporting rods and plates
or tube extension.
• Additional accessories: Components that can be ordered independently from the selected product
configuration, such as clips, pads, tips, spacers and plates for tag sensors.
• Thermowells: They are directly welded on the process connection, designed to guarantee higher
degree of mechanical protection and corrosion resistance for each sensor.
4 Endress+Hauser
iTHERM MultiSens Flex TMS01
In general, the system measures the temperature profile inside the process environment by means of
many sensors, jointed to a suitable process connection which ensures the right tightness levels.
Externally, the extension cables are wired into the junction box, which can be directly mounted or
remote as option.
Endress+Hauser 5
iTHERM MultiSens Flex TMS01
The modular multipoint thermometer is characterized by the following possible main configurations:
• Linear configuration
The different sensors are aligned along
the straight direction coinciding with the
longitudinal axis of the multipoint
assembly itself (linear multipoint
measurement). This configuration can be
used to install the multipoint either in an
1 existing thermowell as part of the reactor
or in direct contact with the process.
• 3D distribution configuration
For a high number of measuring points,
each multipoint cable sensor can be bent
and arranged in a three dimensional
configuration by fixing them through clips
or other equivalent accessories. This
configuration is commonly used to reach
several measurement points distributed at
different cross sections and levels. Specific
support frames can be provided and
installed on request if they are not already
available on site.
A0028362
Input
Measured variable Temperature (temperature linear transmission behavior)
RTD as per IEC 60751 Pt100 –200 to +600 °C (–328 to +1 112 °F)
Thermocouple:
Input Designation Measuring range limits
Thermocouples (TC) as per IEC Type J (Fe-CuNi) –210 to +720 °C (–346 to +1 328 °F)
60584, part 1 - using an Type K (NiCr-Ni) –270 to +1 150 °C (–454 to +2 102 °F)
Endress+Hauser - iTEMP Type N (NiCrSi-NiSi) –270 to +1 100 °C (–454 to +2 012 °F)
temperature head transmitter Type T (Cu-CuNi) –270 to +370 °C (–454 to +698 °F)
6 Endress+Hauser
iTHERM MultiSens Flex TMS01
Thermocouples (TC) - flying Type J (Fe-CuNi) –270 to +720 °C (–454 to +1 328 °F), typical
leads - as per IEC 60584 and sensitivity above 0 °C ≈ 55 μV/K
ASTM E230 Type K (NiCr-Ni) –270 to +1 150 °C (–454 to +2 102 °F) 1), typical
sensitivity above 0 °C ≈ 40 μV/K
Type N (NiCrSi-NiSi) –270 to +1 100 °C (–454 to +2 012 °F), typical
sensitivity above 0 °C ≈ 40 μV/K
Type T (Cu-CuNi) –270 to +370 °C (–454 to +698 °F), typical sensitivity
above 0 °C ≈ 43 μV/K
Output
Output signal Generally, the measured value can be transmitted in one of two ways:
• Directly-wired sensors - sensor measured values forwarded without a transmitter.
• Via all common protocols by selecting an appropriate Endress+Hauser iTEMP temperature
transmitter. All the transmitters listed below are mounted directly in the junction box and wired
with the sensory mechanism.
Family of temperature Thermometers fitted with iTEMP transmitters are an installation-ready complete solution to
transmitters improve temperature measurement by significantly increasing accuracy and reliability, when
compared to direct wired sensors, as well as reducing both wiring and maintenance costs.
PC programmable head transmitters
They offer a high degree of flexibility, thereby supporting universal application with low inventory
storage. The iTEMP transmitters can be configured quickly and easily at a PC. Endress+Hauser offers
free configuration software which can be downloaded from the Endress+Hauser Website. More
information can be found in the Technical Information.
HART® programmable head transmitters
The transmitter is a 2-wire device with one or two measuring inputs and one analog output. The
device not only transfers converted signals from resistance thermometers and thermocouples, it also
transfers resistance and voltage signals using HART® communication. It can be installed as an
intrinsically safe apparatus in Zone 1 hazardous areas and is used for instrumentation in the
terminal head (flat face) as per DIN EN 50446. Swift and easy operation, visualization and
maintenance using universal device configuration tools like FieldCare, DeviceCare or
FieldCommunicator 375/475. For more information, see the Technical Information.
PROFIBUS® PA head transmitters
Universally programmable head transmitter with PROFIBUS® PA communication. Conversion of
various input signals into digital output signals. High accuracy over the complete ambient
temperature range. The configuration of PROFIBUS PA functions and of device-specific parameters is
performed via fieldbus communication. For more information, see the Technical Information.
FOUNDATION Fieldbus™ head transmitters
Universally programmable head transmitter with FOUNDATION Fieldbus™ communication.
Conversion of various input signals into digital output signals. High accuracy over the complete
ambient temperature range. All transmitters are released for use in all important process control
systems. The integration tests are performed in Endress+Hauser's "System World". For more
information, see the Technical Information.
Advantages of the iTEMP transmitters:
• Dual or single sensor input (optionally for certain transmitters)
• Pluggable display (optionally for certain transmitters)
• Unsurpassed reliability, accuracy and long-term stability in critical processes
• Mathematical functions
• Monitoring of the thermometer drift, sensor backup functionality, sensor diagnostic functions
• Sensor-transmitter matching for dual sensor input transmitters, based on Callendar/Van Dusen
coefficients
Endress+Hauser 7
iTHERM MultiSens Flex TMS01
Power supply
• Electrical connecting cables must be smooth, corrosion resistant, easy to be cleaned and
inspected, robust against mechanical stresses, no-humidity sensitivity.
• Grounding or shielding connections are possible via ground terminals on the junction box.
1 2 3
R3 RD
R1 RD R2 R1 RD B5 BK
R1 R3
R1 W3 R1 RD
R3 R1
R3 RD R2 RD B6 BK
W5 B6 G4 W6 W4 W4 WH
W5 WH B5
W3 WH G4 YE W6 WH
4
A0045453
3 2
6
RD
5
RD
1
1 mA
4
WH
3 2
WH
A0045600
1 2
RD 6
+
RD 5
1+
+
4 -2-
WH -
WH 3
3
A0045464
8 Endress+Hauser
iTHERM MultiSens Flex TMS01
2 1 3
BK
BK RD 7
6
RD
5
1
+
2
WH 4
-
YE WH 3
4
A0045466
WH WH RD RD
2 3
2
4
GN
1
5 4 3+ -
3
3 S1 +
BK S2 +
6
!-
+
-
-
BK
A0045732
Endress+Hauser 9
iTHERM MultiSens Flex TMS01
+
-
5 4 3
1
RD
+
-
2
!
3+ -
RD
S1
3
4
4
WH
WH
1
A0045733
1 x TC 2 x TC
-
+
-
+ +
A0012700
10 Endress+Hauser
iTHERM MultiSens Flex TMS01
Head mounted transmitter TMT18x (single sensor input) 1) Head mounted transmitter TMT8x (dual sensor input) 2)
1 2 1
3
TC TC
6
7
6
1+ 5
4 1+
2-
2-
4
3
A0045467
1 Sensor input 1
2 Sensor input 2
3 Fieldbus communication and power supply
4 Display connection
Head mounted transmitter TMT7x (single sensor input) 2) Mounted field transmitter TMT162 or TMT142B 1)
1 1
6
3
4 3 2
1+
+
5 5 -
1
+ 2 4 3+
S1
3 + +
6 S2
!
+
-
- -
4 -
-2-
3
1 2
3 2 TC TC
A0045353 2 1 5 6
1 Sensor input 1
2 Sensor input 2 (not TMT142B)
3 Supply voltage for field transmitter and analog output 4 to 20 mA or fieldbus
communication
• Type J: black (+), white (-) • Type J: white (+), red (-)
• Type K: green (+), white (-) • Type K: yellow (+), red (-)
• Type N: pink (+), white (-) • Type N: orange (+), red (-)
• Type T: Brown (+), white (-) • Type T: Blue (+), red (-)
Endress+Hauser 11
iTHERM MultiSens Flex TMS01
Performance characteristics
Accuracy RTD resistance thermometer as per IEC 60751
A
- 1.0
- 1.5 B
- 2.0
- 2.5
A0045598
In order to obtain the maximum tolerances in °F, the results in °C must be multiplied by a factor
of 1.8.
Permissible deviation limits of thermoelectric voltages from the standard characteristic for
thermocouples as per IEC 60584 or ASTM E230/ANSI MC96.1:
12 Endress+Hauser
iTHERM MultiSens Flex TMS01
Response time Response time for the sensor assembly without transmitter. It refers to inserts in direct contact
with process. When thermowells are selected specific evaluation should be done.
RTD
Calculated at an ambient temperature of approx. 23 °C by immersing the insert in running water (0.4
m/s flow rate, 10 K excess temperature):
t90 5s
t90 < 10 s
Thermocouple (TC)
Calculated at an ambient temperature of approx. 23 °C by immersing the insert in running water (0.4
m/s flow rate, 10 K excess temperature):
t90 6.2 s
t90 7.5 s
t90 10.6 s
Calibration Calibration is a service that can be performed on each individual insert, either in order phase, or after
multipoint installation.
When calibration shall be performed once the multipoint is installed, please contact the
Endress+Hauser service to get full support. Together with the Endress +Hauser service any
further activity can be organised to achieve the calibration of the target sensor. In any case it is
forbidden to unscrew any threaded component on the process connection under operating
conditions = running process.
Calibration involves comparing the measured values of the sensing elements of the multipoint
inserts (DUT device under test) with those of a more precise calibration standard using a defined and
Endress+Hauser 13
iTHERM MultiSens Flex TMS01
reproducible measurement method. The aim is to determine the deviation of the DUT measured
values from the true value of the measured variable.
In case of multipoint cable sensor, temperature controlled calibration baths from
–80 to 550 °C (–112 to 1 022 °F) can be used only for the last measuring point (when NL-LMPx <
100 mm (3.94 in)) for either factory calibration or accredited calibration. Special bore through
calibration furnaces with homogeneous distribution of temperature are used for thermometer
factory calibration along the length: 200 to 550 °C (392 to 1 022 °F)
Two different methods are used for the inserts:
• Calibration at fixed-point temperatures, e.g. at the freezing point of water at 0 °C (32 °F).
• Calibration compared against a precise reference thermometer.
Evaluation of inserts
If a calibration with an acceptable uncertainty of measurement and transferable measurement
results is not possible, Endress+Hauser offers an insert evaluation measurement service, if
technically feasible.
Installation
Mounting location The installation location must meet the requirements listed in this documentation, such as ambient
temperature, protection classification, climatic class, etc.. Care should be taken when checking the
sizes of possible existing support frames or brackets welded on the reactor’s wall (usually not
included in the scope of delivery) or of any other existing frame in the installation area.
Orientation No restrictions. The multipoint thermometer can be installed either in horizontal, oblique or in
vertical configuration, related to the reactor or vessel vertical axis.
A0028440
14 Endress+Hauser
iTHERM MultiSens Flex TMS01
Installation instructions The modular multipoint thermometer is designed to be installed with a flanged process connection
into a vessel, reactor, tank or similar environment. All parts and components have to be handled
with care. During the installation phase, lifting and introduction of the equipment through the
preset nozzle, the following must be avoided:
• Misalignment with the nozzle axis.
• Any load on the welded or threaded parts due to the action of the weight of the device.
• Deformation or crushing of the threaded components, bolts, nuts, cable glands and compression
fittings.
• Bending radius of the thermowells smaller than 20 times the diameter of the thermowell.
• Friction between the temperature probes and the internals of the reactor.
• Fixing the temperature probes to the reactor's infrastructures without allowing axial displacements
or movements.
• A bending radius of the sheathed cable (inserts) smaller than 5 times the outer diameter of the
sheathed cable.
A0028441
During installation the whole thermometer must only be lifted and moved by using ropes
properly mounted on the eyebolt of the flange (1).
Environment
Ambient temperature range Junction box Non-hazardous area Hazardous area
Without mounted –40 to +85 °C (–40 to +185 °F) –40 to +60 °C (–40 to +140 °F)
transmitter
With mounted head –40 to +85 °C (–40 to +185 °F) Depends on the respective hazardous area
transmitter approval. Details see Ex documentation.
Endress+Hauser 15
iTHERM MultiSens Flex TMS01
Climate class Determined when the following components are installed into the junction box:
• Head transmitter: Class C1 according to EN 60654-1
• Multi-channel transmitter: Tested as per IEC 60068-2-30, meets the requirements regarding class
C1-C3 in accordance with IEC 60721-4-3
• Terminal blocks: Class B2 according to EN 60654-1
Electromagnetic Depending on the transmitter used. For detailed information see the related Technical Information,
compatibility (EMC) listed at the end of this document.
Process
The process temperature and process pressure are the minimum input parameters for the selection
of the right product configuration. If special product features are requested, additional data such as
process fluid type, phases, concentration, viscosity, stream and turbulences, corrosion rate have to be
considered as mandatory for the whole product definition.
Mechanical construction
Design, dimensions The overall multipoint assembly is composed of different sub-assemblies. Both linear and 3D
configurations have the same features, dimensions and materials. Different inserts are available,
based upon specific process conditions, in order to have the highest accuracy and an extended
lifetime. In addition, protecting thermowells can be selected to further increase mechanical
performances and corrosion resistance, and to allow insert replacement. Associated shielded
extension cables are provided with high resistance sheath materials to withstand different
environmental conditions and to ensure steady and noiseless signals. The transition between the
inserts and the extension cable is obtained by the usage of specially sealed bushings, ensuring the
declared IP degree protection.
16 Endress+Hauser
iTHERM MultiSens Flex TMS01
I I
H
H
A
B
L
F
MPx
L MPx
A0028080
12 Design of the modular multipoint thermometer, with frame neck on the left side or with frame neck and
covers on the right side. All dimensions in mm (in)
A, B, Dimensions of the junction box, see following figure
C
MPx Numbers and distribution of measuring points: MP1, MP2, MP3 etc.
LMPx Different immersion length of sensing elements or thermowells
I, H Encumbrance of the junction box and support system
F Extension neck length
L Overall device length
Endress+Hauser 17
iTHERM MultiSens Flex TMS01
Junction box
A
C
B
1
2
A0028118
1 Cable gland
2 Junction box
3 Frame
The junction box is suited for chemical agents environments. Sea water corrosion resistance and
extreme temperature variation stability is guaranteed. Ex e/Ex i terminals can be installed.
The multipoint thermometer can be provided of both ground terminals or shield terminals.
Please follow your plant guidelines for a proper cables connection.
Approvals ATEX, IECEx, UL, CSA, EAC approval for use in hazardous area
18 Endress+Hauser
iTHERM MultiSens Flex TMS01
Cover Hinged -
Neck extension
The neck extension ensures the connection between the flange and the junction box. The design has
been developed to ensure several mounting layouts to deal with possible obstacles and constraints
that can be met in any plant such as the reactor’s infrastructure (step ways, loading structures,
supporting skirts, stairs, etc.) and reactor thermal insulation. The neck extension design ensures easy
access for monitoring and maintaining inserts and extension cables. It guarantees a high stiffness
connection for the junction box and vibration loads. No closed volumes are present in the neck
extension. This avoids the accumulation of waste and potentially dangerous fluids coming from the
environment that can damage the instrumentation allowing continuous ventilation.
Thermocouple
Diameter in mm (in) Type Standard Hot junction type Sheath material
1x type K
2x type K
6 (0.24)
1x type J
4.5 (0.18)
2x type J IEC 60584 /ASTM Alloy600 / AISI 316L /
3 (0.12) Grounded/Ungrounded
1x type N E230 Pyrosil
2 (0.08)
2x type N
1.5 (0.06)
1x type T
2x type T
RTD
Diameter in mm (in) Type Standard Sheath material
1x Pt100 WW
3 (0.12) 2x Pt100 WW
IEC 60751 AISI 316L
6 (¹⁄₄) 1x Pt100 TF
2x Pt100 TF
Endress+Hauser 19
iTHERM MultiSens Flex TMS01
Thermowells
External diameter in mm (in) Sheath material Type Thickness in mm (in)
Weight The weight can vary depending on the configuration: Dimension and content of the junction box,
neck length, dimensions of process connection and the number of inserts. The approximate weight
of a typically configured multipoint thermometer (number of inserts = 12, flange size = 3", medium
size junction box) = 40 kg (88 lb)
Materials It refers to insert sheath, neck extension, junction box and all wetted parts.
The temperatures for continuous operation specified in the following table are only intended as
reference values for use of the various materials in air and without any significant compressive load.
The maximum operation temperatures are reduced considerably in some cases where abnormal
conditions such as high mechanical load occur or in aggressive media.
20 Endress+Hauser
iTHERM MultiSens Flex TMS01
AISI 316Ti/ X6CrNiMoTi17-12-2 700 °C (1 292 °F) • Addition of titanium means increased resistance
1.4571 to intergranular corrosion even after welding
• Broad range of uses in the chemical,
petrochemical and oil industries as well as in coal
chemistry
• Can only be polished to a limited extent, titanium
streaks can form
Process connection
3
A0028122
Endress+Hauser 21
iTHERM MultiSens Flex TMS01
Standard process connection flanges are designed according to the following standards:
ASME 1½”, 2”, 3”, 4”, 6”, 8” 150#, 300#, 400#, 600# AISI 316, 316L, 304, 304L, 316Ti,
321, 347
EN DN40, DN50, DN80, DN100, PN10,PN16, PN25, PN40,
DN150, DN200 PN63, PN100
Compression fittings
The compression fittings are welded or threaded into the flange to ensure tightness to the process
connection. Dimensions are coherent with the insert dimensions. Compression fittings comply with
the highest standards of reliability in terms of materials and performances required.
Operability
For details of operability, see the Technical Information of the Endress+Hauser temperature
transmitters or the manuals of the related operating software. → 29
22 Endress+Hauser
iTHERM MultiSens Flex TMS01
Hazardous area approvals The Ex approval applies to individual components like junction box, cable glands, terminals. For
further details on the available Ex versions (ATEX, UL, CSA, IECEx, NEPSI, EAC Ex), please contact
your nearest Endress+Hauser sales organization. All relevant data for hazardous areas can be found
in separate Ex documentation.
ATEX Ex ia inserts are available only for diameters ≥ 1.5 mm (0.6 in). For further details contact an
Endress+Hauser technician.
Certification HART The HART® temperature transmitter is registered by the FieldComm Group. The device meets the
requirements of the HART® Communication Protocol Specifications.
Certification FOUNDATION The FOUNDATION Fieldbus™ temperature transmitter has successfully passed all test procedures
Fieldbus and is certified and registered by the Fieldbus Foundation. The device thus meets all the
requirements of the following specification:
• Certified according to FOUNDATION Fieldbus™ specification
• FOUNDATION Fieldbus™ H1
• Interoperability Test Kit (ITK), up to date revision status (device certification no. available on
request): the device can also be operated with certified devices of other manufacturers
• Physical layer conformance test of the FOUNDATION Fieldbus™
Certification PROFIBUS® PA The PROFIBUS® PA temperature transmitter is certified and registered by the PNO (PROFIBUS®
Nutzerorganisation e. V.), PROFIBUS user organization. The device meets all the requirements of the
following specifications:
• Certified according to FOUNDATION Fieldbus™ specification
• Certified in accordance with PROFIBUS® PA Profile (the up to date profile version is available on
request)
• The device can also be operated with certified devices of other manufacturers (interoperability)
Material certification The material certificate 3.1 (according to EN 10204) can be requested separately. The certificate
includes a declaration related to the materials used to produce the thermometer. It guarantees the
traceability of the materials through the identification number of the multipoint thermometer.
Test report and calibration The "Factory calibration" is carried out according to an internal procedure in a laboratory of Endress
+Hauser accredited by the European Accreditation Organization (EA) to ISO/IEC 17025. A
calibration which is performed according to EA guidelines (LAT/Accredia) or (DKD/DAkkS) may be
requested separately. The calibration is performed on the inserts of the multipoint.
Material requirements Endress+Hauser can supply components according to AD 2000 W2 And W10 standards.
Welding requirements Endress+Hauser has been audited according to DIN EN ISO 3834-2:2005.
Endress+Hauser 23
iTHERM MultiSens Flex TMS01
Ordering information
Overview of the scope of delivery see the configuration table below.
Detailed ordering information is available from your Endress+Hauser Sales Center:
www.addresses.endress.com
Face • RF
• RTJ
Others on request
The values reported in the table below are indicative, based on calculations for nozzles with
standard dimensions. So the maximum number of measurement points can differ from the
maximum number of the configuration table. It depends on the dimensions of the nozzle used
on location.
1½" 3 3 1
2" 5 5 1
3" 8 8 2
4" 16 16 4
6" 30 30 11
8" 48 48 20
Insert, sensor
24 Endress+Hauser
iTHERM MultiSens Flex TMS01
Insert, sensor
Approvals Ex e / Ex ia / Ex d _______
Others on request
Endress+Hauser 25
iTHERM MultiSens Flex TMS01
Extension neck
TAG
Additional requests
Inspection certificate 3.1, short form, EN10204, (material certificate wetted parts)
Internal pressure test according to Endress+Hauser procedure, test report (in case of
thermowells)
Internal helium leak test according to Endress+Hauser procedure, test report (in case
of thermowells) 1)
External pressure test according to Endress+Hauser procedure, test report (max length
10 m)
2D dimensional drawing
Manufacturer declaration
1) (recommended)
26 Endress+Hauser
iTHERM MultiSens Flex TMS01
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code is available from your local Endress
+Hauser sales center.
Tip end Terminal closure welded at the tip end of the probe in
order to protect the insert (or the thermowell) from
aggressive process conditions and to facilitate its fixing
by means of metallic tie wraps.
A0028427
2
A0033485
1 Insert
2 Spacer
A0028783
1 Spacer
2 Guiding tube
3 Insert
Endress+Hauser 27
iTHERM MultiSens Flex TMS01
Accessories Description
1
2
A0028434
1 Thermowell
2 Spacer
1
A0028435
Accessories Description
28 Endress+Hauser
iTHERM MultiSens Flex TMS01
Documentation
• Operating manuals iTEMP temperature transmitters:
• TMT180, PC-programmable, single-channel, Pt100 (KA00118R)
• HART® TMT82, two-channel, RTD, TC, Ω, mV (BA01028T)
• PROFIBUS® PA TMT84, two-channel, RTD, TC, Ω, mV (BA00257R)
• FOUNDATION FieldbusTM TMT85, two-channel, RTD, TC, Ω, mV (BA00251R)
• Supplementary ATEX documentation:
ATEX/IECEx (Ex ia IIC): XA01647T
• Technical Information of inserts:
• Resistance thermometer insert Omnigrad T TST310 (TI00085T)
• Thermocouple insert Omnigrad T TSC310 (TI00255T)
• Multipoint temperature cable probe iTHERM ProfileSens TS901 (TI01346T)
• Technical Information application example:
HAW562 surge arresters, (TI01012K)
Endress+Hauser 29