CocaCola Cooling Specification
CocaCola Cooling Specification
TECHNICAL SPECIFICATIONS
ATLANTIC INDUSTRIES
CAIRO CONCENTRATE PLANT
COCA COLA
JUNE 2014
1
Table Of Contents
15054 - Training.
15057 - Guarantee.
15058 - Standards.
15101 - Generally.
15105 - Valves.
15107 - Strainers.
2
Table Of Contents (continue)
15110 - Workmanship Generally
15351 - Generally.
15401 - Generally.
15500 - Insulation
15501 - Generally.
15504 - Workmanship.
3
15559 - Workmanship Generally.
15600 - Control System
15601 - Generally.
15602 - Workmanship.
15603 - Electronic System.
15604 - DDC System.
15605 - Building Automation System.
15650 - Balancing, Testing and Adjusting
15651 - Generally.
15652 - Pressure Tests.
15655 - Testing of Pumps.
15656 - Testing and Adjusting of Control System.
15657 - System Performance Test.
4
15758 - Push Buttons.
15759 - Relays.
15760 - Circuit Breakers.
15761 - Motor Control Center.
15762 - Motor Control Panels.
15763 - Workmanship.
15800 - Manufacturers List
********************
5
15050 GENERAL REQUIREMENTS
------------------------------------------------
6
15052 DRAWINGS, INSTRUCTIONS AND SAMPLES
7
~052-06 SHOP AND INSTALLATION DRAWINGS: mark clearly in ink
catalogues, pamphlets and drawings for proper identification of item
proposed and indicate, with reasons, deviations from the Specification
and the Drawings.
~052-10 FURTHER DRAWINGS: during the progress of the work, submit shop-
drawings, to 1/20 or 1/10 scale, as required by the Engineer and as
specified elsewhere.
8
~052-14 MINOR CHANGES AND MODIFICATIONS may be made in layout to
prevent conflict with work of other trades or for proper execution of the
work.
~052-17 FURNISH to other trades templates, patterns, setting out plans and
shop details necessary for proper installation and coordination of
adjacent work.
9
manufacturer's list of general spare parts for every piece of equipment
with unit prices,
manufacturer's list of recommended spare parts for one year of
operation of each piece of equipment with unit prices,
detailed and simplified one line colour coded flow diagram of each
system with tag number, location and function of each valve and
instrument,
detailed and simplified colour coded as-installed wiring diagrams of
motor controllers and automatic controls with tag number, location and
function of each instrument and electrical device with description of
sequence of operation and interlocks.
10
~053-02 LABEL AND IDENTIFY equipment, instruments, controls, electrical
devices, valves etc. as to duty, service or function. Label controls and
electrical devices to indicate clearly what they control.
~053-04 LABELS: laminated Bakelite with black surface, white core and incised
lettering in English.
~053-06 TAG controls and instruments that cannot be easily identified with
Bakelite labels.
~053-07 TAG valves and controls, except equipment shut off valves located at
equipment.
11
15054 TRAINING
~056-03 NOISE LEVEL resulting from equipment and heard in the same
building or nearby buildings is not to exceed 40 decibels as measured
12
with a standard sound level meter on the 'A' scale.
15057 GUARANTEE
13
~057-05 MAINTENANCE AND OPERATION: act promptly to correct problems
arising in operation of equipment or system.
15058 STANDARDS
14
UL - Underwriters' Laboratories Inc.
15100 PIPEWORK
15101 GENERALLY
~101-01 BLACK SEAMLESS STEEL PIPE : use for the following services:
chilled/heating water
chilled water
heating water
~101-02 GALVANIZED STEEL WELDED PIPE: use for the following services:
condensate drainage
½ 65 1.22
¾ 2.65 1.58
1 3.25 2.44
1¼ 3.25 3.14
1½ 3.25 3.61
2 3.65 5.10
2½ 3.65 6.51
15
3 4.05 8.47
4 4.50 12.10
5 4.85 16.20
6 4.85 19.20
~102-04 GALVANIZED PIPES: galvanizing to be tested to BS 1387:
Appendix A.
~102-08 PIPE UNIONS to have female threaded ends and ground metal to
metal seats.
16
size, thickness, facing, drilling and pressure rating.
~102-14 GASKETS for flat face flanges to be full face ring type, with punched
holes, 1.5 mm thick asbestos composition.
~102-15 GASKETS for raised face flanges to be ring type 1.5 mm thick
asbestos composition.
~102-16 BOLTS AND NUTS: black steel to BS 4190. Lengths of bolts to allow
nuts to utilize full length of thread.
17
1 1/4 1.375 0.055
1 1/2 1.626 0.060
2 2.175 0.070
~103-01 TYPE AND RATING: Rubber tubing with annular corrugations, covered with
high tensile bronze braid, suitable for 150 psi cold water working pressure.
~103-02 ENDS: screwed for pipes 2" diameter and under and flanged for pipes over
2" diameter.
15104 VALVES
~104-02 RATING: 125 psi steam working pressure and 200 psi cold water non-shock
pressure rating.
~104-05 GATE VALVES 2" diameter and under to be screwed and have bronze body
and trim, solid wedge disc, non-rising stem and screwed bonnet.
~104-06 GATE VALVES over 2" diameter to be flanged and have cast iron body,
bronze trim, solid wedge disc, non-rising stem and bolted bonnet.
~104-07 GLOBE VALVES 2" diameter and under to be screwed and have bronze
body and trim, integral seat, revolving disc, inside screw, rising stem and
screwed bonnet.
18
~104-08 GLOBE VALVES over 2" diameter to be flanged and have cast iron body,
bronze trim, renewable seat and disc, outside screw, rising stem and bolted
bonnet.
15106 STRAINERS
~106-01 STRAINERS 2" diameter and under to be screwed, Y-type, bronze body,
250 psi working pressure rating, with 20 mesh stainless steel screen and
screwed cap with 1/2" diameter tapped hole for blowdown valve.
~106-02 STRAINERS over 2" diameter on water service to be flanged, basket type
with cast iron body, 250 psi working pressure rating with 20 mesh stainless
steel basket screen, bolted cap and 3/4" diameter tapped hole at bottom for
blowdown valve.
~107-02 VALVES: pack-less type, with flexible metal diaphragm, non-rotating bearing
plate, nylon seat disc, stainless steel opening spring, metal hand-wheel and
'O' ring seal between bonnet and valve body. Forged brass body and
bonnet, solder ends and integral support bracket, good for an operating
pressure of 250 psi and an operating temperature of 40 to 200 deg. F.
~107-03 VALVES: valve opening to be full size for maximum flow with minimum
restriction.
19
~107-04 CHARGING VALVES to have one end with flare thread, and seal cap and
chain.
~107-05 EXPANSION VALVES: thermostatic type, forged brass body, stainless steel
diaphragm, spring and pushrod, with remote bulb, capillary tube, built-in inlet
strainer and external superheat adjustment set for 10 deg. F superheat, and
correctly sized for coil capacity for efficient refrigerant distribution without
starving coil and without hunting.
~107-06 SOLENOID VALVES: forged brass body suitable for 250 psi Freon
operating pressure, solder ends, with means for manual lifting of stem and
complete with coil, coil housing and plunger.
~107-08 STRAINERS: brass body suitable for 250 psi operating pressure, solder
ends and bolted cap to permit removal of strainer screen for cleaning
without breaking the inlet and outlet connections. Screen is to be non-
corrodible metal of at least 100 mesh with net free area at least 10 times the
internal area of the liquid refrigerant pipe.
20
connections, non-porous forged brass body, 500 psi maximum working
pressure, with large, self-cleaning, crystal clear moulded sight glass, special
high temperature neoprene seal, with indication to show `full` when system
is fully charged and with provision to change colour when a moisture
condition exists.
~108-02 GENERALLY: hangers and supports to be steel with smooth flat bearing
surfaces. They are to carry the weight of piping and contents without
sagging, swaying, vibrating or deforming, and to allow free movement of
pipes due to expansion and contraction without noise or damage to piping or
structure.
~108-05 INSULATED HOT PIPES SUPPORTED FROM ABOVE: use a pipe clamp
directly on pipe with the arms of the clamp extended outside the insulation
or a clevis or pipe clamp hanger lined with insulation protection shields.
21
between vapour barrier and support to be galvanized sheet steel to fit
outside diameter of insulation and cover 180 degrees of arc, 3 mm thick for
pipes up to 5" diameter and 5 mm for pipes over 5" diameter.
~108-08 PIPE ANCHORS AND GUIDES: 3/4" diameter U-bolt to fit pipes.
~109-03 GROUP pipes together where practicable and run in straight parallel lines
close and parallel to walls, ceilings and columns.
~109-06 AIR POCKETS: install piping to avoid air pockets and dirt traps.
~109-07 AIR POCKETS: use eccentric reducers where appropriate to avoid air
pockets, with the flat of the reducer on top on water piping to permit proper
venting of the system.
22
expansion loops or expansion joints.
~109-11 JOINTS are not to be painted, varnished or otherwise coated until tested
and approved.
~109-12 JOINTS: cut pipes square and to exact length, ream cut ends with a special
tool to full inside diameter and remove chips.
~109-15 THREADED JOINTS: make with red lead on cold pipes and with graphite
ground in linseed oil on hot pipes. Apply to male thread only. Teflon tape
thread sealant may be used.
~109-16 FLANGED JOINTS: make perfectly square with pipes. Fit with ring gaskets
and assemble with steel square head machine bolts and hexagonal nuts.
~109-18 JOINTS IN BLACK PIPES 2" diameter and under to be threaded. Pipes
over 2" diameter to be welded.
23
~109-21 WELDOLETS AND THREADOLETS of forged steel may be used on black
steel pipe branch connections where branch does not exceed half the
diameter of main pipe.
~109-27 FITTINGS: changes in direction and size, branching and jointing of pipes
are to be made with regular pipe fittings. Do not bend pipe.
~109-31 GATE VALVES: do not use for throttling purposes such as regulation,
balancing or controlling. Use only for shut-off purposes, with the valve in the
fully open or fully closed position.
24
~109-32 GLOBE VALVE: use where throttling service is required.
~109-33 RELIEF VALVES: install where shown on the Drawings, with proper setting
to protect equipment and piping from over pressure.
~109-34 DRAIN VALVES: fix at all low points of piping system and where required to
completely drain system.
~109-35 SHUT-OFF VALVES: fix on branches to isolate sections of piping system for
repairs and on each side of equipment.
~109-36 MANUAL OR AUTOMATIC AIR VENTS: fix at all high points of piping
system.
~109-37 STRAINERS: install where shown on the Drawings and upstream of pumps,
control valves and other equipment that may be damaged by suspended
particles in the fluid.
~109-40 SUPPORT piping at close enough intervals to avoid air pockets and dirt
traps.
~109-41 SPANS: specified maximum spans are for straight runs of pipe.
25
seismic forces.
~109-46 FIX supports to structure with masonry expansion bolts without causing
overstress to the structure.
~109-47 FIX: provide intermediate steel where required to transfer loads to areas of
structure where they can be safely accommodated.
~109-49 MULTIPLE PIPE RUNS: where bottoms of lines are approximately at same
level, support in groups on trapeze hangers. Keep pipes in position with U-
bolts.
~109-50 HOT LINES subject to extreme thermal expansion are to be free to slide or
roll on roller supports.
26
against damage from pipe weight or movement, without affecting the firm
attachment of pipes to their supports.
~109-55 INSULATED HOT PIPES: lugs may be welded to pipes and extended
outside the insulation to a hanger attachment, or if supported from below, to
a sliding shoe or roller supports.
~109-56 INSULATED COLD PIPES WITH VAPOUR BARRIER: supports are not to
penetrate insulation. Use insulation protection shields between hanger or
support and outside of vapour barrier.
~109-57 ANCHORS: weld U-bolts to pipes at points of contact and bolt to structural
angle frame securely fixed to structure.
27
~109-59 VERTICAL PIPE: support at a minimum of every storey height.
~109-60 SUPPORT piping from ceilings with adjustable, split- ring hangers with
threaded hanger rod and ceiling flange. Support horizontal pipes run along
walls on brackets.
~109-63 HANGERS AND SUPPORTS: locate at not more than 600 mm from each
change of direction, preferably on side with longest run.
~109-64 HANGERS AND SUPPORTS on straight runs of pipe over 6 m long are to
allow for thermal movement of pipe.
~109-66 JOINTS: make by silver brazing, using 45 per cent silver brazing alloy and a
good grade of silver brazing flux. Do not bend pipe.
~109-67 VALVES: install in each refrigeration system all necessary service valves,
charging valves and safety valves, whether shown on the Drawings or not.
~109-68 SOLENOID VALVES: install in liquid line upstream of each expansion valve.
~109-69 STRAINERS: install upstream of expansion valves and other control valves
that do not have built-in strainers.
~109-70 SIGHT GLASSES: install in liquid line before the filter- drier to indicate
adequacy of refrigerant charge and existence of moisture.
28
pressure side. System is to have no loss of pressure for 4 hours. Test for
leaks with a soap solution.
~109-73 VACUUM TEST refrigeration systems after pressure test. Evacuate system
with a vacuum pump to a vacuum of 25" of mercury. System is to hold
vacuum for 24 hours.
~109-74 CHARGE refrigeration systems following vacuum test with the correct
quantity of refrigerant. Test with a halide torch to prove tightness under
actual operating conditions.
~109-75 CLEAN WATER SYSTEMS after completion by flushing with clean water.
~251-01 GENERAL
The reciprocating Air Cooled units will be completely factory
assembled including all interconnecting refrigerant piping and internal
wiring of controls, mounted on a steel base which accommodates the
air cooled condenser and compressor (s) . Unit structure will be
constructed of G90U, galvanized steel and painted with weather
resistant enamel. The unit will be shipped with pressurized nitrogen or
a full operating charge of R-407C or equal .All units will contain
separate refrigerant circuits, each with a single compressor for standby
operation. All units will be designed and constructed in accordance
with the applicable sections of the following: Air Conditioning and
Refrigeration Standard ARI 590; American Society of Heating,
Refrigeration and Air Conditioning Engineers ANSI/ASHRAE 15 Safety
Code for Mechanical Refrigeration; American Society of Mechanical
29
Engineers ASME Pressure Vessel Code; National Electrical
Code/National Fire Protection Association NFPA 70; Underwriters
Laboratory UL 1995 (200, 230 and 460-3-60); and Canadian
Standards Association.
30
pressure of the condenser coil will be 450 psig.
The unit will contain two separate refrigerant circuits and each will be
constructed of ACR copper tubing with brazed joints, and will include:
shut-off valve, liquid sight glass with moisture indicator, direct acting
maximum operating pressure thermal expansion valve, solenoid
valve and filter-drier with charging connection. The entire suction line
and liquid line between the expansion valve and the cooler will be
insulated with flexible closed cell insulation. Full operating charge of
R407C or equal and oil..
31
115-1-50أHz mounting will include primary and secondary wiring
between the transformer and the control panel.
32
15350 PUMPS
15351 GENERAL
~351-10 SHOP DRAWINGS: submit the following for approval, for each pump
prior to shipment:
33
order number, pump designation number shown on the Drawings, date
of manufacture, model number, pump size, impeller diameter, impeller
type, maximum impeller diameter pump can accommodate, rpm, flow-
head characteristic curve, consumed horsepower curve, pump
efficiency curve
~351-11 SHOP TESTS: prior to shipment of any pump submit the certified
results of the following tests:
~351-12 SHOP TESTS: test reports are to include the following information:
34
motor data: make, model number, serial number, horsepower rating,
rpm, voltage, phase, frequency, class of insulation, full load amperes,
locked rotor amperes and actual voltage and amperes at all test points
starter data: make, model number, size, heater sizes, ampere rating, line
voltage, control voltage and frequency.
~351-13 PUMP AND MOTOR BASE: align and level throughout entire length and
width of base and provide shims under base for levelling. Secure to
foundation with anchor bolts and completely grout in to provide a rigid non-
deflecting support. Realign after grouting in base and connecting pipework.
~351-14 DRAINS FOR PACKING GLANDS AND BASE: pipe to nearest floor drain.
~352-01 TYPE: horizontal, base mounted, end suction, single stage, centrifugal type,
directly connected to motor through a heavy duty flexible coupling, with
heavy gauge coupling guard.
~352-02 BASE: pump and motor to be mounted on common cast iron base
35
adequately reinforced against deflection, with drip rim, drain tapping, bolt
holes and grouting hole.
~352-04 PUMP CASING: high tensile strength close grain cast iron with smooth
waterways, register fitted and bolted to bearing frame for permanent
alignment, with bronze wear rings and tapped and plugged bottom drain and
top vent connections.
~352-05 IMPELLER: bronze, enclosed type, fitted to shaft with key and locked in
place.
~352-06 SHAFT: one piece stainless steel, sized to carry axial and radial thrust with
minimum deflection.
~352-07 MECHANICAL SEAL: Ni-resist face, carbon washer and stainless steel
metal parts.
36
15400 AIR HANDLING EQUIPMENT
15401 GENERAL
37
noise throughout their capacity range. Select to operate at minimum
noise levels determined from manufacturer's published literature.
38
15403 AIR HANDLING UNITS
~403-05 COIL : to have heavy duty coil tracks extending full width to support
coils throughout their length and to provide easy removal of coils from
coil connections side of casing. Condensate drain pan of double wall
construction is to extend under whole coil section, fixed to it and
adequately pitched to amply sized threaded drain connections on both
sides. Pan to be treated against corrosion. Stacked cooling coils to
have intermediate drain pans with drop tubes at either end to drain into
main drain pan.
39
~403-06 COIL CONSTRUCTION: to be removable cartridge type, constructed
of heavy wall seamless copper tubes to aluminium fins by mechanical
expansion and staggered in direction of air flow. Coil to be leak tested
at factory to 350 psi minimum air pressure with coil submerged in
water. Coil face area is not to exceed 2.5 meters per second coil face
velocity at specified air quantity. Coil to have number of rows and fins
per cm to satisfy required capacity at specified condition.
* Copper tube and aluminium fins coils for maximum heat transfer
efficiency.
* The condensing unit has axial fans and can be mounted externally
or internally with ducted condenser air.
The total cooling capacity of the unit shall be not less than that
mentioned in B.O.Q or greater with suitable cubic feet per minute
supply air discharge at ambient dry and wet bulb temperature as
mentioned in outdoor conditions.
40
~451-03 UNIT MAIN COMPONENTS:
COMPRESSOR(S):
41
pressure equals the losses in connected duct works – if needed- or
greater.
Evaporator air fans shall be axial type
~451-06 CONTROLS:
Controls shall be factory wired to operate on 24 volt, single phase, 50
Hz power supply.
A factory mounted multi position switch will control the unit for
continuous fan and cooling operation.
Unit shall have a 24-control circuit suitable for connection to 24-volt
remote room thermostat.
Compressor protection shall include high and low pressure switches,
current lockout and inherent over temperature protection.
42
15500 INSULATION
15501 GENERAL
43
ASTM E-84
NFPA - 225
ANSI A2.5 - 1963
or other approved international standard.
44
condensate drainage 3/4 - 6 1
refrigerant liquid
and suction lines all sizes 1 1/2
15504 WORKMANSHIP
15504-01 GENERALLY
~504-011 EXECUTE in a neat, clean, smooth workmanlike manner. Work is to be
executed by specialized, skilled workmen regularly engaged in this
type of work.
~504-012 APPLY insulation and jacketing on supply and return ducts carrying
cool air, on pipes carrying hot and cold fluids, on condensate drain
pipes and on hot and cold equipment as specified. Exhaust ducts and
fresh air ducts are not to be insulated unless otherwise specified.
~504-013 APPLY insulation in a manner to prevent air circulation within
insulation or between insulation and pipe, duct or equipment. Pipe
insulation is to fit snugly and duct insulation adhered to duct surface
with special lagging adhesive.
~504-014 APPLY insulation only after pipes, ducts and equipment have been
tested, approved and accepted.
~504-015 APPLY insulation only to surfaces that are dry and free from rust, dust,
loose scale, dirt, oil or other foreign matter.
45
~504-018 OPENINGS to have metal frames to protect edges of insulation.
~504-019 IMPERFECTIONS such as chipped edges, voids, holes or cracks to be
filled with insulation cement.
~504-021 INSULATE all pipes with preformed, rigid, sectional, pipe insulation of
thickness specified.
46
laps and butt sealing strips on longitudinal and circumferential joints
with vapour seal adhesive. Seal openings, joints, laps and end strips
with vapour barrier coating (Armoflex rubber could be used).
47
minimum 80% overall efficiency over full range
~551-04 BOILER SHELL: longitudinal joints to be double butt welded and girth
joints full fillet welded. Welds to be X- rayed and stress relieved as
required by the ASME Code.
~551-06 ACCESS DOORS to be provided at front and rear of boiler to give full
access to entire body without disconnecting electrical wiring. Doors to
be hinged, lined with high quality refractory, fully gasketted and bolted
on for complete gas-tightness.
~551-10 BOILER TRIM to include: relief valves of type and size to comply with
ASME Code requirements, 6" dial 0-200 psig range pressure gauge
with steel case and shut-off cock, cast brass 9" red reading mercury
48
thermometer with scale 30 to 240 deg. F range, separable socket well
and extended neck, float operated low water cut-off with drain valve,
boiler drain valve and stack bimetallic thermometer.
~551-11 PAINT FINISH: entire boiler, base frame and other components to be
factory painted with hard finish silicone enamel.
~551-12 TEST: unit to be fire tested at factory prior to shipment and copy of test
report furnished with boiler.
~551-13 INSPECTION: unit to be subjected to shop inspection and approval by
authorized Boiler Inspection and Insurance Company and stamped
with all identifying markings and symbols required by ASME Code.
Certified inspection report to be furnished with boiler
49
F (+/- 1 deg. C) of specified design conditions.
~601-05 INDICATING INSTRUMENTS such as pressure gauges and
thermometers are to have range such that normal readings are
indicated in middle of instrument range.
~601-06 INDICATING INSTRUMENTS installed on insulated pipes are to have
necks to extend instrument to final finished insulation surface.
~601-07 SEPARABLE SOCKET WELLS for immersion thermostats and
thermometers are to be brass, threaded and of size and length to suit
instrument and pipe.
~601-08 PRESSURE GAUGES to have brass cock on inlet.
~601-09 AUTOMATIC VALVES to have pressure ratings as noted for respective
system.
~601-10 MANUFACTURE: control instruments and appurtenances are to be
the product of one manufacturer, of latest design and as recommended
by manufacturer for control systems intended. Controls are to be
supplied for local electric current, unless noted otherwise.
15602 WORKMANSHIP
GENERAL
~602-01 INSTALL AND CONNECT controls and instruments in accordance
with manufacturer's instructions. Install in a manner and at locations to
sense accurate representative values of function controlled and to be
accessible for ease of adjustment and calibration.
~602-02 SURFACE MOUNTED CONTROLS: mounted on approved brackets
to clear final finished insulation surface.
~602-03 CONTROL VALVES: installed horizontally with motor on vertical.
direction
~602-04 CONTROL WIRING AND CONDUITS: conceal in all areas except
mechanical equipment rooms and unfinished spaces.
~602-05 WALL MOUNTED THERMOSTATS: install 1.5 m above floor level on
50
inside wall and where temperature at thermostat is not affected except
by room temperature.
~602-06 IMMERSION THERMOSTATS AND THERMOMETERS to have bulbs
inserted in brass separable socket wells installed vertically or at an
angle. Socket wells are to be installed through female threaded steel
fittings welded to pipe. Insertion depth is to suit pipe.
15603 ELECTRONIC SYSTEM
15603-01 PRESSURE INSTRUMENTS
15603-011 GAUGES
PRESSURE GAUGE PG-1: Bourdon tube type, minimum 4 inch
dial diameter, with flangeless back and 1/2 inch male threaded
bottom connection and graduated in pounds per square inch with 2
psi divisions. Gauge to have black finished cast aluminium case,
threaded black epoxy cast aluminium ring with gasketted glass face,
type 316 stainless steel spring tube, stainless steel precision
movement and micrometer adjustment on needle.
51
system conforming to specifications.
DDC controllers shall be stand alone programmable ready for
connection to central computer system via multiplexed digital
communication bus system to form building management system
[BMS]
DDC controllers shall have the facilities of local indication and
reading of values inputs and outputs also adjustment of system
parameters E.G. set points via plug-in type easy to use
service/operating terminal.
DDC controllers shall be complete with hardware and software to
perform programmable PLC and DDC functions required for cooling
control loops and all necessary interlocks, safety, and monitoring
functions. It shall contain stored-in programs in RAMS, ROMS and
eproms with integrated batteries for 10 years of data protection .
DDC controllers shall contain inputs and outputs of various types to
connect to various types of inputs and outputs such as :-
52
outputs should be in the form of 0-I, 0-II, 0-III, 0-V for step control
functions.
Analogue Output [ AO ] : Standard output signal of 0..1DVC or 4..20MA
to drive
modulating actuators.
Quantity Counter Inputs [DI ] : For connecting devices with pulse
output such as flow and energy meters.
Run Hour Inputs [ DI ] : For calculating actual running hours for devices
for maintenance purposes.
53
transmission or other parts of the system if any shall be submitted
for approval before ordering .
15604-4 BMS Functions
System shall include but not limited to :
Dynamic system pictures with presentation of process variables using
numbers, bar charts, symbols, Text .
Trend curve diagrams each with several different data elements per
system picture, blending in and out .
Dynamic system list .
Alarm monitoring with keeping of alarm journal .
Limited monitoring of analogue valves .
Logging on three printers and\or entery in a file .
Switching and positioning commands from the system pictures.
Time-dependant functions .
Time switching commands .
Time set point changes .
Different types of password protection .
Recording of historical data, plotting in tend curve form .
Export of HDB data for use in other programs .
Display of important product information on the monitored equipment
(such as spare parts information) .
Freely configurable historic database/trends .
15604-5 System Operation
Field devices and other systems monitored and or controlled are
connected to BMS system as inputs and outputs to various DDC/PLC
microprocessor based sub-stations distributed through out the building
and connected to BMS central station via multi-channel digital
communication system .Sub-stations shall have following types of
inputs/outputs as minimum requirement .
54
Digital Inputs : For connection to normally closed or normally open
contacts to indicate status or alarm conduits E.G. limit switches, level
switches, flow switches, pressure switches motor contactors auxiliary
contacts.........etc.
Digital Inputs : For quantity counters .
Digital Inputs : For hour run counters .
Analogue Inputs : For connection of various field devices such as
sensors, transducers, transmitters with industry standard signals ( 0..20
MA / 4..20 MA / 0..1VDC / 0.2..1.0 VDC / 0..10 VDC / 2..10 VDC / 0..130
OHM / 0..2000 OHM / NI 1000 / PT 1000 ) To measure variables as
temperature, pressure, flow, level, volt, current, watt.............etc.
Digital outputs : To control electric switching loads as motors, heaters,
and other electric loads. Switching can be as on\off relay output or as
multi-step switching 0-I-II / 0-I-II-III...... etc.
Analogue outputs : To provide continuous output signals 0..1VDC /
0..10VDC / 0..20MA
/ 40020MA to control proportional final control elements directly from
DDC controls.
All measured valves, status, alarm inputs...etc. shall be reported to the
central station and updated with all changes of state and alarm conditions
indicated instantly at the central station monitor and alarm printers .
All sub-stations shall function completely controlling and monitoring
electrical and mechanical equipment connected to then using built in
DDC\PLC Algorithms programmed into each sub-station to perform DDC\
PLC and BMS functions and to communicate with other sub-stations and
central station .
If central station is down or communication between sub-station central
station is lost for any reason the sub-station shall continue functioning in
a stand alone operation mode and a loss of communication shall be
55
performed at central station with time and date. Printers in addition to
printing alarms and change of states shall also be programmed to provide
various types of reports on all points of the system or specific group of
points or a single point reports shall be automatically activated on time
programs or event programs or called for via the operator . The three
system printers shall be controlled to operate as alarm printer, logs printer
and trend/graphics printer .
Sub-station shall be complete with integrated software modules to
provide building management functions such as alarm/status .
acceptance of commands with verification feed back, values,
measurement, plus metering, quantity calculation, running.
Time determination in addition to control modules both closed loop control
modules such as limit values, enthalpy control, P,PI,P-PI controllers,
hewing curve, 2point, 3point controllers, min./max. selection, root
extraction, addition subtraction, data selection ..etc.
and open loop control . modules such as step switching, summer/winter
change-over indication ....etc . Also sub-station software shall include but
not limited to time functions with date, week, year, hour, minute, and
second with calendar for working days and holidays . Substations shall be
capable of handling historical data bases for its addresses for at least 24
hours with transfer ot central station for merging with global historical data
bases. Sub-stations shall provide optimisation programs such as gree
cooling and optimum start/stop in addition to optimization and energy
management packages provided by central station . Measured values of
electrical parameters such as volt, current power, frequency ..etc. shall be
transferred to sub-station. through appropriate transducers for total power
consumption calculation and peak value control of selected loads.
56
Temperature Sensors
Duct temperature detectors shall be stem type designed
temperature measurement in air ducts with Ni or Pt sensor element.
Degree of protection shall be IP54 or higher .
Immersion temperature detectors shall be similar to duct type with
protection tube/pocket for fluid circuits . Outdoor temperature detectors
shall have Ni or Pt sensing element housed in IP55 housing . Room type
temperature detectors shall be complete with set point adjusted designed
for wall mounting with Ni or Pt sensing element .
Air Differential Pressure Switches
Air deferential pressure switches installed across bag filters and fans to
provide indication for dirty filter and broken fan belt shall have adjustable
differential pressure range of 70..600 pa, with housing protection IP-54 or
higher. The device shall be complete with all mounting and connecting
accessories .
Safety Temperature Detectors
Duct mounted stem type safety temperature controller shall be installed
after electric heaters. Set point Adjustment shall be internal . The control
action shall be single pole opener . Internal reset button.
Valve Actuators
Electric valve drive shall be supplied to control valves in modulating
control mode . Input control signal shall be continuous voltage or current
signal [0..10VDC or 0..20MA]. Supply voltage 24 VAC. Linear movement
for direct connection to valve bodies without the need to mechanical
linkages. The device shall be complete with all mounting and connecting
accessories.
DDC Controllers
DDC controls shall be with metal housing cage for better noise
protection .IP-30 or higher. DDC controllers/sub-stations shall cover all
57
points for inputs and outputs specified with extra 20% usable capacity.
15604-7 System Operation
Field devices and other systems monitored and/or controlled are
connected to BMS system as inputs and outputs to various DDC\PLC
microprocessor based sub-stations distributed through out the building
and connected to BMS central station via multi-channel digital
communication system.
Sub-stations shall have following types pf inputs/outputs.:
Digital Inputs : for connection to normally closed or normally open
contacts to indicate status or alarm conditions E.G. Limit switches, Level
switches, Flow switches, Pressure switches, motor contactors Auxiliary
contacts .....etc.
Digital Inputs : for quantity counters.
Digital Inputs : for hour run counters.
Analogue Inputs : for connection of various field devices such as
Sensors, Transducers, Transmitters with industry standard signals
( 0..20MA / 4..20MA / 0..1 VDC / 0.2..1.0 VDC / 0..10 VDC / 2..10 VDC /
0..130 OHM / 0..2000 OHM / NI1000 / PT1000 ) to measure variables as
Temperature, Pressure, Flow, Level, Volt, Current, Watt...........etc.
Digital Outputs : to control electric switching loads as Motors, Heaters,
and other electric loads. Switching can be as on/off delay output or as
muli-step switching 0-I-II / 0-I-II-III .........ets.
Analogue Outputs : to provide continuous output signals 0..10 VDC /
2..10 VDC / 0..20 MA / 4..20 MA . to control proportional final control
elements directly from DDC controllers.
All measured values, Status, Alarm Inputs....etc. Shall be reported to the
central station and updated with all changes of state and alarm conditions
indicated instantly at the central station monitor and alarm printers.
All sub-stations shall function completely controlling and monitoring
58
electrical and mechanical equipment connected to them using built in
DDC/PLC control algorithm programmed into each sub-station to perform
DDC/PLC and BMS functions and to communicate with other sub-stations
and central station. If central station is down or communication between
sub-station shall continue functioning in a stand alone operation mode
and a loss of communication is reported also return of communication
shall be reported at central station with time and date.
Printers in addition to printing alarms and change of states shall also be
programmed to provide various types of reports on all points of the
system or specific group of points or a single point reports shall be
automatically activated on time programs or event programs or called for
via the operator. The three system printers shall be controlled to operate
as alarm printer, logs printer and trend/graphics printer.
Sub-station shall be complete with integrated software modules to
provide building management functions such as alarm/status. acceptance
of commands with verification feed back, values, Measurement, pulse
metering, quantity calculation, running time determination in addition to
control modules both closed loop control modules such as limit values,
enthalpy control, P,PI,P-PI controllers, heating curve, 2Point, 3-Point
controllers , min./max. selection, roof extraction, addition, subtraction,
data selection,...etc .And open loop control modules such as step
switching, summer/winter change-over, indication.......etc.
Also sub-stations software shall include but not limited to time functions
with date, week, year, hour, minute, and second with calendar for working
days and holidays. Sub-stations shall be capable of handling historical
data bases for its addresses for at least 24 hours with transfer to central
station for merging with global historical data bases . Sub-stations shall
provide optimization programs such as gree cooling and optimum
management packages provided by central station.
59
Measured values of electrical parameters such as volt, current, power,
frequency .etc .Shall be transferred to sub-station through appropriate
transducers for total power consumption calculation and peak value
control of selected loads.
15606-013 SENSORS
ROOM TEMPERATURE SENSOR: to provide proportional single output
for electronic temperature controller. Type similar to Honeywell or
approved equal and having the following features: wall mounted
500 ohms Balco sensing element, bi-metal thermometer and
potentiometer for temperature set point adjustments
set point range 30-90 deg. F, thermometer scale 30-90 deg. F
accessories including adaptor plate for mounting on electrical wall box
and decorative finish plate.
15606-014 SUNDRIES
FLOW SWITCH FS: to shut off water when water flow through boiler
drops to preset quantity. Type similar to McDonnell and Miller or approved
equal and having the following features:
pedal vane type with single-pole, double-throw contacts
flow sensitivity adjustment stands heat up to 150 deg. F .
60
15650 TESTING, BALANCING AND ADJUSTING
15651 GENERAL
~652-04 TEST PROCEDURE: plug and blank off all openings in system and fill
slowly nitrogen. Ensure nitrogen reaches all parts of system. When
test pressure is reached close valve and monitor pressure variations.
61
~652-05 INSPECTION: with the system under pressure, inspect pipes and
joints for leaks.
~655-02 TESTS : carry out as required to test equipment for performance and
proper functioning and to demonstrate, to the Engineer's satisfaction,
that equipment meets design requirements.
62
~655-04 DATA TO BE MEASURED to be those items given on the Schedule of
Equipment and including the following: entering and leaving coil
temperatures, entering and leaving air dry bulb and wet bulb
temperature, ambient dry bulb and wet bulb temperatures, air
quantities, hot water quantities, pressure drops on air and water sides,
suction and discharge pressures, electric motor horsepower or kilowatt
input from measured voltage, current and power factor, sound levels.
~658-01 TEST SYSTEMS after they have been fully checked, balanced and
adjusted and all equipment verified to meet design requirements and
operating satisfactorily, to demonstrate to the Engineer's satisfaction
that they operate as designed and as intended.
~658-03 SCHEDULING OF TESTS: one month before date set for commencing
tests, submit for approval six copies of test procedure with tests to be
63
performed, method of testing, instruments to be used, points of
measurement and method of calculation. Date for commencing tests
to be subject to approval obtained at least 5 days before each trial test
run.
~658-04 TEST RESULTS: provide six copies for approval. Include approved
copies in the Instruction Manual.
64
15700 BUILDER'S WORK
15701 GENERALLY
~702-01 PIPE SLEEVES for pipes passing through walls, floors and roof to be
galvanized steel pipe, two nominal pipe sizes larger than pipe passing
through for bare pipes, and of sufficient size to permit pipe insulation to
pass through for insulated pipes.
65
15703 WORKMANSHIP
15703-01 EQUIPMENT BASES AND SUPPORTS
~703-015 ALIGN AND LEVEL EQUIPMENT on bases and supports over entire
length and width and shim where necessary to facilitate levelling.
~703-017 ANCHOR BOLTS: set in oversized sleeves with washers and nuts at
bottom. Bolts to project at least 6 mm above nuts when equipment is
fixed to allow for shimming. Secure during concreting.
66
~703-021 STRUCTURAL MEMBERS: do not cut without approval. Any approved
cutting to be done only as directed.
~703-022 SLEEVES to be provided for all pipes passing through walls, floors and
roofs. Locate before walls etc. are constructed and fasten securely to
prevent displacement during construction. Plug ends during
construction.
~703-023 SLEEVES to terminate flush with finished walls and ceilings and to
project 20 mm above finished floors and 250 mm above rough
concrete of roof.
15703-03 WATERPROOFING
~703-041 CLEAN equipment, material, and piping etc. inside and outside by
effective and approved methods to remove loose mill scale, blisters,
sand, plaster, paint droppings, debris, dirt, oil, grease, labels and all
foreign matter. Clean and brush work in stages as directed before
painting or concealing.
~703-043 BLACK STEEL PIPING including flanges, bolts, nuts, cast iron valves
and accessories, valve wheels and all ferrous parts are to be painted
with two coats of zinc chromate primer whether or not they are to be
67
insulated. When bare or exposed to view, they are to be further
painted with two coats of approved oil paint.
~703-046 HANGERS AND SUPPORTS including clamps, rods, bolts, nuts etc. to
be painted with two coats of zinc chromate primer and where exposed
to view with two additional coats of approved oil paint.
68
15750 ELECTRICAL WORK
15751 GENERALLY
15752 CONDUITS
~753-01 POWER WIRES AND CABLES: Single conductor wires and multi-core
cables to have high conductivity tinned copper wire conductors
insulated with PVC compound, with additional PVC sheath for multi-
core cables.
69
~753-03 CONTROL WIRES AND CABLES: provide special heat resistant
insulation or corrosion resistant sheath where required.
15755 STARTERS
~755-02 MOTOR DATA: obtain from equipment supplier before ordering any
motor starter, or check motor nameplate for full load current rating and
allowable temperature rise in order to select proper overload thermal
element for motor starter.
~755-04 CONTROL VOLTAGE for starters and control circuits is not to exceed
110 V.
70
or circuit breakers.
~755-07 AUXILIARY SUPPLY for controls, other than from main power circuit,
to be effectively isolated by auxiliary contacts on main isolator.
~755-09 STARTER TYPE A for single phase motors not exceeding 1/2 HP to
be surface or flush mounted, manual two pole toggle type, for non
reversing across the line starting, fitted with one overload element.
~755-011 STARTER TYPE C for three phase motors over 10 HP, but not
exceeding 50 HP, to be automatic star delta magnetic non reversing
type, with 3 pole overload relay and adjustable low voltage relay,
unless otherwise required by local regulations.
71
~755-014 NAMEPLATES: starters and controls to have engraved nameplates
identifying system or defining its function.
72
sheet metal enclosure to suit application.
15759 RELAYS
73
15760 CIRCUIT BREAKERS
74
sections to be easily added or removed.
75
breakers must be in OFF position before door can be opened.
76
interconnecting and interlock wiring and all devices and accessories
required for automatic or manual operation of equipment as specified
under equipment concerned.
~763-013 RIGID CONDUITS are not to terminate in nor be fastened to a motor frame
or base.
~763-016 FLEXIBLE CONDUITS: do not use in place of rigid conduit except at motor
connections, unless otherwise specified.
~763-018 CONDUITS are not to cross pipe or vent shafts, ducts or openings. They
are to be run a minimum 100 mm away from pipes of non-electrical services.
15763-02 CONTROL CIRCUITS
77
~763-021 SUBMIT FOR APPROVAL detailed control wiring diagrams and a list of
control equipment with descriptive literature. Free hand field wiring diagrams
or sketches will not be accepted.
~763-023 PROTECT CIRCUITS with high rupturing capacity fuses or circuit breakers.
Auxiliary supply for controls, other than from main power circuit, to be
effectively isolated by auxiliary contacts on main isolator.
15763-03 EARTHING
15763-04 EQUIPMENT
~763-041 STARTERS: fix detailed wiring diagram inside each enclosure cover to
clearly indicate circuits.
~763-042 STARTERS: identify control and power wires either by distinctive coloured
insulation, engraved tags or other approved method.
78
15800 LIST OF MANUFACTURES:
15801 – Units & Compressors
Carrier ( USA )
Bitzer (Germany)
Trane ( USA)
Copeland (Germany)
Or Approved equal...
15803 - Pumps
Grandfoss ( Denmark )
biral ( Swiss)
Taco ( USA )
Or Approved equal...
15804 - Evaporating Units
Carrier ( USA )
Pro-froid ( France )
Or Approved equal...
15811 - Valves & Accessories
Crane ( USA )
HONEYWELL GERMANY
Nibco ( USA )
Or Approved equal...
* Flexible Connection
Mason Industries ( USA )
Anacond ( USA )
Aeroquip Corp ( USA )
79
Or Approved equal...
* Strainers
Crane ( USA )
HONEYWELL (Germany )
Or Approved equal...
* Fittings
Anaconda American brass co. ( USA )
Muller brass co. ( USA )
Or Approved equal...
15814 - Sundries & Accessories
* Heating Equipment (Boiler)
Byworth under License of D.Balwin ( England )
Or Approved equal...
* Di-Electric Insulated Joint
Aeroquip Corp ( USA )
Capitol Mfg. ( USA )
Dresser ( USA )
Or Approved equal...
* Pressure Gauge
Achroft ( USA )
Manning, Maxwell & Moore ( USA )
Taylor instrument ( USA )
Or Approved equal...
* Refrigerant Pipe accessories
Alco ( USA )
Mueller ( USA )
80
Danfoss ( Denmark )
Or Approved equal...
15814 - Control Systems & BMS
Siemens ( SWISS )
Or Approved equal...
15814 -Electrical Components
a) Electric Motors :
Siemens ( Germany )
Or Approved equal...
b) Electric Panel Boards :
E.M.G. ( France )
ABB (SWEEDEN)
Or Approved equal...
c) Electric Cables :
Elsweedy ( Local )
Egyptian Company Cables ( Local )
Or Approved equal...
********************
81