Mid Term Report
Mid Term Report
IMPLEMENTATION OF 132 KV HT
SWITCHYARD
2.3.2Mesh Substation
The general layout for a full mesh substation is shown in the schematic below.
Fig (3) Mesh Substation
The characteristics of such a substation are as follows:
O t provides a double feed to each circuit and is cheaper than double bus or
auxiliary scheme.
O Operation of two circuit breakers is required to connect or disconnect a circuit,
and disconnection involves opening of a mesh.
O Circuit breakers may be maintained without loss of supply or protection, and no
additional bypass facilities are required.
O Busbar faults will only cause the loss of one circuit breaker. Breaker faults will
involve the loss of a maximum of two circuits.
O Generally, not more than twice as many outgoing circuits as in feeds are used in
order to rationalize circuit equipment load capabilities and ratings.
2.3.3 One and a haIf Circuit Breaker Iayout
The layout of a 1 circuit breaker substation is shown in the schematic below.
Fig (4) 1 breaker scheme
The reason that such a layout is known as a 1 1/2 circuit breaker is due to the fact that
in the design, there are 9 circuit breakers that are used to protect the 6 feeders. Thus, 1
1/2 circuit breakers protect 1 feeder. Some characteristics of this design are:
O There is the additional cost of the circuit breakers together with the complex
arrangement.
O t is possible to operate any one pair of circuits, or groups of pairs of circuits.
O There is a very high security against the loss of supply.
n addition to the above schemes, there are some other alternative bus bar layouts like
the double bus, double bus with by pass isolators etc, main and transfer bus schemes
etc. These schemes are used when the additional costs incurred to install them justify
the protection required. Usually the above schemes take care of most possibilities
except when breaker maintenance is required. Schemes such as the main and transfer
bus, double bus with isolators can work even when breaker maintenance is carried out.
They transfer the load onto the other bus so that the faulty breaker does not shut down
the supply. The only constraint here is that of cost where sometimes the protection
scheme is more costly than the equipment it protects. Hence the practice of layout
selection depends on the equipment to be protected, the scheme of protection and the
economic considerations.
2.4 Switchyard Components:
2.4.1 Lightning/Surge rrestors:
The lightning arrestor is a device designed to protect electrical equipment from high
voltage surges and to limit the duration and the amplitude of the fault current.
Fig (5) Lightning/Surge Arrestors
Concept of basic insuIation IeveI(BIL):
Every device has the ability to withstand voltages up to a particular level eg
transformers, generators, circuit breakers etc. f this particular withstand voltage is
exceeded it may lead to breakdown of the equipment insulation and ultimately, the
failure of the equipment. Hence all equipment is tested and has a dry power frequency
withstand voltage as well as wet impulses withstand voltage. The basic insulation level
of the equipment determines the principle dielectric qualities of the apparatus and is
expressed for impulse tested apparatus by peak value of the 1.2/50microsecond full
wave withstand voltage. Hence the BL of all the equipment in a switchyard is
determined nowadays on the basis of the protective characteristics of the lightning
arrestors. Also the BL for various system voltages as per ndian Standards (S) has
been fixed. Generally for a 132kV yard, the BL is taken as around 650kV for a non-
effectively earthed system. These levels help in the selection of the proper equipment.
The protective devices are so selected that their flashover values are considerable
lesser than the BL of the apparatus, thereby leaving sufficient margin of protection. The
withstand or flashover values of the apparatus with this wave shape are required to be
equal or higher than the insulation levels fixed and the spark over voltage and discharge
voltage of the protective devices are required to be substantially lower than these
values so that in the event of a lightning surge the discharge occurs through the
protective device and still leaves a sufficient margin between the discharge value and
the insulation strength of the apparatus. The difference between the BL of the
insulation to be protected and the protection level of a lightning arrestor is called
"protective margin. A margin equal to 20 percent of the BL is normally considered
adequate when the arrestor is installed just close to the insulation in question.
REERENCES
O The Siemens website: www.siemens.co.in. The site provides
a thorough description of its upcoming project.
O Wikipedia-The free encyclopedia: www.wikipedia.org. The
basics of technologies like Optical Character Recognition
(OCR) were understood from references to articles on this
website.
O SNAMCS G130 Catalogue
O SNAMCS G120 Control Unit CU240S Operating
nstructions
O www.howstuffworks.com
O www.electronicsforu.com
O We have utilized data from numerous websites by searching
the net using Google's search engine.