Machine Lab III
Machine Lab III
Laboratory Report
Therefore, the main purpose of the lab session was to introduce three phase transformers
and their uses over single phase transformers.
EQUIPMENT USED
2 DC Source - 1
3 Ammeter - 2
4 Voltmeter - 2
5 Wattmeter - 1
7 Switch - 2
Theory
The fig below shows three single – phase transformer connected to work as a
start – start three – phase transformer. Note that X, Y and Z are connected
together and let us call the common point o. Similarly x, y and z are connected
together and let us cal it o’.
If the primary and secondary line voltages are V1 and V2, the primary and
secondary voltages of the individual transformers must be V 1/ 30.5 and V2 / 30.5
respectively.
Fig. below shows three single phase transformers of the windings of a single
three phase transformer connected in delta (Δ) on both primary and secondary
sides. Note that in this type of connection the phase and line voltages are equal.
The main advantage of this connection lies in the fact that the system can still
operate on 58% of it’s rated capacity even in case of failure of one of the
transformers.
Fig. below shows transformer windings where the primary side is connected in
star and the secondary is connected in delta.
Here the phase and line voltages are equal on the primary side. On the secondary
side the line voltage = 30.5 phase voltage.
This connection gives a higher secondary voltage for transmission purposes than
the connections with Δ secondaries without increasing the strain on the
insulation of the transformer. It is the connection commonly used at the
generating end of transmission lines. The neutral of the Y – connected secondary
is generally grounded.
Procedure
Assemble the circuit below. Vary the input V1 from 0.5 rated to 1.2v rated
and at each step measure the open circuit power poc, the phase voltages
and the currents IA and IC.
Connect the above circuit with the secondary sire short circuited. Increase
gradually the short circuit primary voltage so that the current on the
secondary side is about 0.5I rated, 0.75I rated and I rated. At each step
record the short circuit voltage, current and power.
Apply rated voltage to the primary and increase gradually the load current
on the secondary side by varying the resistance of the load resistor. At each
step measure the current and the secondary voltage.
Result
For Step 1:
Name plate of the transformer:
Siemens
P = 2.5kVA/2.17kVA
f = 50-60Hz
For Step 2:
Resistance of winding using ammeter/ voltmeter method becomes:
*
Note that all the values above are in Volts (V).
Transformation Ratio Y – Y connection, Y – Δ connection, Δ – Δ connection, Δ – Y
connection becomes 0.5, 0.277, 0.5 and 0.909 respectively.
For Step 4:
Open – circuit results:
Vi A1(mA) A2(A) P(W) Voc(V)
190 110 0.1 40 95
220 120 0.1 40 110
250 129 0.12 40 125
280 140 0.14 60 140
310 158 0.16 60 155
340 173 0.17 76 170
370 198 0.2 80 185
380 209 0.21 84 190
For Step 5:
Short – circuit Test:
Based upon the above graph, equivalent impedance, resistance, reactance and
short – circuit power factor of the transformer can be calculated. Hence,
Impedance, resistance, reactance and pf of the transformer become 2.43ohm,
0.25ohm, 2.41ohm and 0.377 respectively. The above result may deviate form the
one’s that were obtained during the measurement of winding resistance but they
show considerably closeness and indicate the average.
For Step 6:
Load Test:
Conclusion
This lab has tried to come up with different result that may be crucial in
determining the behavior of a three – phase transformer.
1. The winding resistance of the transformer is calculated by
ammeter/voltmeter method.
2. The three tests: no load, short – circuit and Load test. These test verify the
transformer ratio, resistance efficiency and other important results.
Even though the results are within good precision range, some may deviate
from the theory and may lead to false conclusions. But this all consideration are
taken into account. A better result may be obtained by using more accurate
equipments and a healthy transformer.