(Full) Lab Report 1
(Full) Lab Report 1
Remarks:
Checked by:
Date:
Hydrodynamics of a Packed Column
(Wet Column Pressure Drop)
Amirul Azwan bin Armee (2019406066), Ahmad Akif bin Md Ghazali (2019295124), Aizah binti Jamarudin (2019207276), Alia
Natasya binti Mohamad (2019614908), Ayu Baiduri binti Hasmizam (2019612686), Nur Maryam Shahida binti Mohd
Rahipuddin (2019268736)
Abstract— The aim of this experiment is to Packed columns are used for distillation, gas
examine the air pressure drop across the column absorption and liquid-liquid extraction. The gas-
as a function of air flow rate for different water liquid contact in a packed column is continuous, not
flow rates through the column. For water stage-wise, as in a plate column. The liquid flows
flowrates of 1 L/min, 2 L/min, and 3 L/min, the down in the column over a packing surface and the
pressure drop was recorded every 2 minutes at air vapor moves counter-currently, up the column. In the
flowrates of 20 L/min, 40 L/min, 60 L/min, 80 counter-current two-phase flow of gas and liquid, a
L/min, 100 L/min, 120 L/min, 140 L/min, 160 pressure drop occurs in the packed column. It is
L/min, and 180 L/min. The experiment will important to know the pressure drop in the gas phase
continue until it reaches the point of flooding, and in single- and two-phase counter-current flow
the water flow rate will be changed to 2 L/min and through random or structured packings, in order to
3 L/min respectively. From the experiment, we can assess the operating mode of packed columns.
conclude that if the air flowrate increases, the (Jerzy Maćkowiak, 2009) The towers are also known
pressure drop also increases. According to the as scrubbers.
result, the theoretical pressure drop of this
experiment is 7.083 mm H20/m while experimental A long vertical column used in industry for absorbing
value is 25.49 mm H20/m. This experiment's gases. The gas is introduced at the bottom of
percentage error for water flow rate at 1 L/min the column and the absorbing liquid, often water,
is12.5%, while there is no percentage error for passes in at the top and falls against the counter
water flow rate at 2 L/min and 3 L/min. Flooding current of gas. (Oxford) Flooding is brought about by
is high at 1 L/min water flowrate compared to 2 excessive vapour flow, causing liquid to be entrained
L/min and 3 L/min based on experimental result. in the vapour up the column. At this point the
A higher flooding point would result a large entire column is filled liquid and the gas now has to
pressure drop and packings in the column will be bubble through the liquid in the packing voids.
damaged. The experiment was successfully
completed, and objectives were achieved.
II. OBJECTIVES
Keywords—abstract, introduction, objectives, The objectives of the experiment are to examine the
theory, material and apparatus, procedures, air pressure drop across the column as a function of
results and calculations, discussion, conclusion, air flow rate for different water flow rates through the
recommendations, references, two column format, column, to plot the graph of column pressure drop
Times New Roman, size 10, APA style, packed against the air flow rate in log – log graph, to obtain
column, absorption column. the pressure drop from the generalized correlation
chart as in Appendix and to compare the experimental
value and the correlated value.
I. INTRODUCTION
Absorption, or gas absorption, is a unit operation used
in the chemical industry to separate gases by washing III. THEORY
or scrubbing a gas mixture with a suitable liquid. One Gas absorption is a mass transfer process where more
or more of the constituents of the gas mixture than one species is removed from a gaseous stream
dissolves or is absorbed in the liquid and can thus be by dissolution in a liquid. The component extracted
removed from the mixture. (Manuel Laso, Urs von from the vapour stream is known as solute of the
Stockar, 2017) solution meanwhile the component extracting the
solute is known as solvent. The carrier gas is the
insoluble component exist in the gas which is not Operating Line Equation
absorbed by the solvent. Variations in composition are constant from one end
to the other in a packed absorption column. The
Gas-Liquid Equilibrium material balances for the portion of the column above
A Gas-Liquid Equilibrium is considering the system an arbitrary segment, as shown in Figure 3, are
where a gaseous component A is in equilibrium with similar to the single stage equilibrium phase. The
both air and water at a given temperature. The subscript for component A, on the other hand, is
equilibrium relationship between the partial pressure, omitted because it is the only component that is
pA in the gas phase and the composition, xA in the moved between phases.
liquid phase can often be expressed by a straight line
Henry’s Law equation at low concentrations.
[Equation 1]
[Equation 2]
[Equation 3]
[Equation 4]
A line drawn with the slope of (–kxa / kya) from the Figure 7 Limiting liquid to gas ratio
operating line will intersect the equilibrium line at the
Since the driving forces for mass transfer become
interface composition (xi, yi). This is shown in Figure
zero at point B1 at the bottom of the column, an
4.
infinitely high packed absorption column is required
at this limiting condition. To achieve the required
change in the outlet gas composition in a specific
column, the liquid flow rate must be higher than this
minimum.
[Equation 8a]
[Equation7a]
[Equation 8b]
[Equation 7b]
Where is the logarithmic mean of
The mass transfer is said to be liquid film regulating
when these two coefficients are approximately the
same magnitude and m is much greater than 1.0. For In general, there are four kinds of transfer units based
CO2 in water at 20°C and 1 atm, Henry's Law on individual or overall driving forces:
coefficient is 1430, which equals the value of m. On
the other hand, when a gas's solubility in a liquid is Gas film: and [Equation 9a]
very high, the value of m is very small, and the mass
transfer is said to be gas film regulating. Liquid film: and [Equation 9b]
Overall gas: and [Equation 9c]
Limiting Gas to Liquid Ratio Overall liquid: and [Equation 9d]
The inlet gas flow, VB, and its composition, yB, are
usually known in an absorption phase. The absorption
column's outlet gas concentration, yT, is also fixed as Pressure Drop in Packed Columns
a criterion, and the inlet liquid concentration, xT, is Fluid friction between the packings causes the
also determined by the process specifications. The pressure drop in a packed column. Figure 9 shows the
amount of liquid flow entering the system, LT, must pressure drop per unit packing depth against the gas
be calculated. flow rate, Gy (mass per hour per unit empty column
cross sectional area), in logarithmic coordinates.
Absorption Column
Procedures
Filled the receiving vessel B2 through the charge port
with 50L of water by opening valve V3 and V5.
Closed valve V3. Opened valve V10 and valve V9
slightly. Observe the flowed of water from vessel B1
through pump P1. Switch on pump P1, then slowly
opened and adjust valve V11 to give a water flow rate
of around 1 L/min. Allowed the water to entered the
top of column K1, flowed down the column and
Figure 10 Generalized correlation for pressure drop accumulate at the bottom until it overflows backed
in packed columns (1 in.H2O/ft = 817 Pa/m) into vessel B1. Opened and adjust valve V11 to give
a water flow rate of 1.0 L/min into column K1.
Opened and adjust valve V1 to give an air flowed rate
IV. MATERIAL & APPARATUS of 20 L/min into column K1. Observe the liquid and
gas flowed in the column K1, and record the pressure
Material dropped across the column at dPT-201. Repeated
Water steps 6 to 7 with different values of air flow rate, each
time increasing by 20 L/min after 2 minutes while
Apparatus maintaining the same water flow rate. Repeated steps
5 to 8 with different values of water flowed rate, each Table 5: Log Pressure Drop and Log Air Flowrate
time increasing by 1.0 L/min by adjusting valve V11. Value (Experimental).
F*=Flooding
F*=Flooding
F*=Flooding
Sample Calculation for Cross Sectional Area of
Packed Column
Cross-sectional Area, Ac
=
=
= 0.005 m2
=
Figure 11 : Graph Log Pressure Drop vs Log Air
Flow Rate = 0.0779 kg/m2s
From the graph, it shows the log pressure drop
increases as the log air flowrate increases. Also Sample Calculation for Liquid Mass Velocity, 𝐆𝐱
indicates as air flowrate increases, the pressure drop Liquid mass velocity, Gx
increases. For the 1 LPM water flowrate, the data of
=
the experimental shows a huge pressure drop
comparing to the theoretical data. This is also
happened on the 2 LPM water Flowrate but for 3 =
LPM water flowrate, the pressure drop of the
experimental data shows a slightly drop comparing = 3.32 kg/m2s
with the theoretical data.
Sample Calculation for Capacity Parameter, y-
VII. CALCULATION axis
Given,
y-axis =
Data for Theoretical Pressure Drop Calculations:
=
ΔPTheory = 7.083 mm H20/m
= 0.8032 x 10-6 m2/s
Sample Calculation for Pressure Drop Units, liquid. The pressure drop is higher, but still
mBar to mm H2O/m proportional to the square of the gas velocity (Kiefer,
2021). Hence, flooding occurs faster than the lower
: water flow rates.
VIII. DISCUSSION
The purpose of this experiment is to examine the air
pressure drop across the column as a function of air
flow rate for different water flow rates through the
column. This experiment results are shown in the log-
log graph. In the first experiment by using 1 L /min of
water flow rate, the air flow rate is regulated to 20 L
Figure 13
/min with an addition of 20 L/min for the next results
until 180 L/min for each 2 min. The data of the
It is proven that the experimental data is valid as it
pressure drop is collected until flooding occurs. Then,
shows the same pattern of data.
the experiment is proceed with the next water flow
rate which are 2 L /min and 3 L /min. Although the relationship of pressure drop and the air
flow rate is proportional in each theoretical and
experimental data, there is a slight error occurred. For
1 L / min of water flow rate, the theoretical flooding
air flow rate occur at 160 L/min. Meanwhile, the
experimental flooding air flow rate occur at 140 L
/min. Hence, the percentage error is around 12.5%.
This happens due to error occur during controlling the
water from exceeding the entrance of the gas flow
rate at the bottom of the column. For the 2 L/min and
3 L/min of water flow rate, the theoretical and
experimental flooding air flow rate both at the same
rate. For 2 L /min and 3L/min, The flooding air flow
rate is 120 L/min and 80 L/min respectively.
X. RECOMMENDATION
There are a few recommendations that can be made to
enhance the experiment in order to come up with a
better results. First of all, it is advisable to constantly
check the valve controlling the level of water flowing
back to the water reservoir to get more accurate
reading. We can also change the air with other inert
gases to observe the behavior of pressure drop. Next,
avoid trapped air by ensuring the level of water is
higher than the bottom of reservoir. Besides that,
check all the valves are closed before using the
column.
XI. REFERENCES