Flexible Busbar Tie Distance 2

The document provides guidelines for fastening insulated flexible bars in electrical switchboards. It specifies that the bars should be firmly fastened to insulating supports no more than 400mm apart. Appropriate ties must be used and should not be too thin or damaged by short circuits. Maximum distances between supports are provided for different busbar cross-sections and short-circuit currents.

Uploaded by

m.ramadan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views2 pages

Flexible Busbar Tie Distance 2

The document provides guidelines for fastening insulated flexible bars in electrical switchboards. It specifies that the bars should be firmly fastened to insulating supports no more than 400mm apart. Appropriate ties must be used and should not be too thin or damaged by short circuits. Maximum distances between supports are provided for different busbar cross-sections and short-circuit currents.

Uploaded by

m.ramadan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Power connections Insulated Flexible Bars

Fastening insulated flexible bars


Standards Good practice

1 After the connection, fasten the flexible


bars firmly on insulating supports, which
are themselves fastened every 400 mm
at most on the enclosure frame.

It is prohibited to fasten flexible bars


on metal supports.

2 Use the appropriate ties to fasten the


flexible bars. They must:
- be at least 9 mm long,
- be able to bear an 80-kilo load.
Do not use ties that are too thin or
mechanically not very resistant, which
could be damaged in case of short-circuit.

3 Do not fasten the flexible bars on sharp


edges in order not to damage the insulator.

108 version: 5.0 How to assemble an electrical switchboard


Power connections Insulated Flexible Bars

Fastening insulated flexible bars (contd.)


Standards Good practice

4 Maximum distance between rigid bar


supports and ties insulated flexible bars.
The recommended distances
between the ties must be absolutely
complied with. This distance
depends on the presumed short-
circuit current of the switchboard.
The different tables below give the
maximum distances to be kept between
supports depending on the following:
- offerings,
- electrodynamic performance,
- cross-sections of the copper
busbars used.
Note: these figures are intended to help
designers of configurations that are not
described or included in the catalogues.
5
Okken table:
115 mm centre distance between bars 70 mm centre distance between bars
No. of Dim. 50 kA/1s 100 kA/1s No. of Dim. 50 kA/1s 80 kA/1s 100 kA/1s
bars (mm) bars (mm)
1 80 x 10 580 1 40 x 10 320
2 80 x 10 500 240 50 x 10 360
3 80 x 10 590 260 80 x 10 480 225
3 120 x 10 790 280 100 x 10 560 240 150

Insulated flexible bars with devices:


Type of device Presumed Icc
N H S
50 kA 70 kA 100 kA
NSX100 ipk 19 k 22 k 24 kÂ
maximum distance 350 260 220
NSX160 ipk 19 k 22 k 24 kÂ
maximum distance 350 260 220
NSX250 ipk 21 k 24 k 26 kÂ
maximum distance 280 210 180
NSX 400 ipk 32 k 36 k 42 kÂ
maximum distance 150 120 90
NSX 630 ipk 37 k 42 k 47 kÂ
maximum distance 110 90 55

Prisma table:
Bars of thickness 5 mm Bars of thickness 10 mm
No. of Dim. Icw in kA/1s No. of Dim. Icw in kA/1s
bars (mm) 15 25 30 40 50 bars (mm) 25 30 40 50 60 65 75 85 100
1 60 x 5 800 450 400 300 1b 50 x 10 850 700 500 400 300 250
80 x 5 950 550 450 350 250 60 x 10 950 800 600 450 300 250 200
2 60 x 5 1100 650 550 400 300 80 x 10 1100 950 700 500 350 300 200
80 x 5 1300 800 650 500 400 2b 50 x 10 750 650 450 350 300 300 250
60 x 10 850 700 550 400 350 300 250 250 200
80 x 10 1050 900 650 500 450 400 350 300 200
100 x 10 1250 1050 800 600 500 450 400 350 250
120 x 10 1450 1200 900 700 600 550 450 350 250

How to assemble an electrical switchboard version: 5.0 109