ASCE 7-05 Errata
ASCE 7-05 Errata
Errata
This document containing the errata to ASCE 7-05 is periodically updated and posted on
the SEI website at www.SEInstitute.org The errata are organized by date in descending
order (most recent to furthest past) hence regular users of this document need only review
the errata posted since their previous use. This document will be continuously updated as
additional errata are identified.
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
Most recent errata posting: May 3, 2007
Third errata posting: October 3, 2006
Second errata posting: September 15, 2006
First errata posting: January 6, 2006
MEAN ROOF HEIGHT, h: The average of the roof eave height and the height to the highest
point on the roof surface, except that, for roof angles of less than or equal to 10°, the mean roof
height shall be the roof eave heave height.
Rℓ = RB setting η = 4.6n1 E B/ Vz
(remove the symbol “E” – it was included by mistake)
Change the title of Figure 6-18D from “Troughed Free Roofs” to “Free Roofs” as it applies to
monosloped, pitched and troughed free roofs. Also, in the title block change “ λ = 0°, 180° ” to
read “ γ = 90° .”
6. Notation:
L : horizontal dimension of roof, measured in the along wind direction, ft. (m)
h : mean roof height, ft. (m). See Figures 6-18A, B or C for a graphical depiction of this dimension.
γ : direction of wind, degrees
θ : angle of plane of roof from horizontal, degrees
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
Revise the illustration in the upper left-hand corner to correctly identify the
location of the zones. Correct illustration is provided below:
3
2
1
2
3
Change the title of Figure 6-19B from “Monoslope Free Roofs” to “Pitched Free Roofs.”
Dimension "a" for Figures 6-19B and 6-19C is as shown in Figure 6-19A. Please also see Note 6
below.
The value of Cf for h/D=25 and Round (D√qz >2.5), Very rough (D'/D = 0.08) is 1.2, not 0.2 as
shown.
6. Loads due to ice accretion as described in Chapter 10 Section 11 shall be accounted for.
The dashed line for “Unobstructed Slippery Surfaces”, Ct = 1.1 should begin at 10° degrees, not at
15° as presently drawn.
Add a support symbol ▲, between second and third support symbol in Case 1, similar as shown in
Case 2 and Case 3.
For the middle loading diagram, change the title to “Unbalanced W ≤ 20 ft with roof rafter
system”
(The “less than” symbol should be a “less than or equal to” symbol”)
Revise Table 7.2 heading as shown below – “Exposure of roofa” applies to all
three columns:
Exposure of Roofa
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
4. Ordinary plain 14.2 and 14.2.3.1 1½ 2½ 1½ NL NP NP NP NP
concrete shear
walls
5. Intermediate precast 14.2 and 14.2.3.5 4 2½ 4 NL NL 40k 40k 40k
shear walls
6. Ordinary precast 14.2 and 14.2.3.3 3 2½ 3 NL NP NP NP NP
shear walls
7. Special reinforced 14.4 and 14.4.3 5 2½ 3½ NL NL 160 160 100
masonry shear
walls
8. Intermediate 14.4 and 14.4.3 3½ 2½ 2¼ NL NL NP NP NP
reinforced masonry
shear walls
Systems 9 thru 12 omitted for brevity.
13. Light-framed walls 14.1, 14.1.4.2, 6½ 3 4 NL NL 65 65 65
sheathed with and 14.5
wood structural
panels rated for
shear resistance or
steel sheets
14. Light-framed walls 14.1, 14.1.4.2, 2 2½ 2 NL NL 35 NP NP
with shear panels and 14.5
of all other
materials
15. Light-framed wall 14.1, 14.1.4.2, 4 2 3½ NL NL 65 65 65
systems using flat and 14.5
strap bracing
B. BUILDING FRAME
SYSTEMS
Systems 1 thru 4 omitted for brevity.
5. Special reinforced 14.2 and 14.2.3.6 6 2½ 5 NL NL 160 160 100
concrete shear
walls
6. Ordinary reinforced 14.2 and 14.2.3.4 5 2½ 4½ NL NL NP NP NP
concrete shear
walls
7. Detailed plain 14.2 and 14.2.3.2 2 2½ 2 NL NP NP NP NP
concrete shear
walls
8. Ordinary plain 14.2 and 14.2.3.1 1½ 2½ 1½ NL NP NP NP NP
concrete shear
walls
9. Intermediate precast 14.2 and 14.2.3.5 5 2½ 4½ NL NL 40k 40k 40k
shear walls
10. Ordinary precast 14.2 and 14.2.3.3 4 2½ 4 NL NP NP NP NP
shear walls
Systems 11 thru 22 omitted for brevity.
12.4.3.2 Load Combinations with Overstrength Factor. Where the seismic load effect with
overstrength, Em, defined in Section 12.4.3 is combined with the effects of other loads as set forth
in Chapter 2, the following seismic load combination for structures not subject to flood or
atmospheric ice loads shall be shall be used in lieu of the seismic load combinations in either
Section 2.3.2 or 2.4.1:
12.10.2.1 Collector Elements Requiring Load Combinations with Overstrength Factor for
Seismic Design Categories C through F. In structures assigned to Seismic Design Category C,
D, E, or F, collector elements (see Fig. 12.10-1), splices, and their connections to resisting
elements shall resist the load combinations with overstrength factor of Section 12.4.3.2.
Revise item 8 as follows – also see errata posting on January 6, 2007 below:
8. For buildings with a diaphragm that is not flexible, the distance between the center of rigidity
and the center of mass parallel to each major axis shall not exceed 15 percent of the greatest
width of the diaphragm parallel to that axis. In addition, the following two equations shall be
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
satisfied for each major axis direction:
m n
e1 2 m
∑ k1i d12i + ∑ k 2 j d 22 j ≥ 2.5(0.05 +
i =1 j =1 b1
)b1 ∑ k1i
i =1
(Eq. 12.14-2A)
m n
e2 2 m
∑k
i =1
1i d12i + ∑ k 2 j d 22 j ≥ 2.5(0.05 +
j =1 b2
)b2 ∑ k1 j
j =1
(Eq. 12.14-2B)
(Note: the subscripts on “d” in both equations and for the third summation in 12.14-2B were
incorrect in the January 6th errata posting.)
13.1.1 Scope. This chapter establishes minimum design criteria for nonstructural components
that are permanently attached to structures and for their supports and attachments. Where
the weight of a nonstructural component is greater than or equal to 25 percent of the
effective seismic weight, W, of the structure as defined in Section 12.7.2, the component
shall be classified as a nonbuilding structure and shall be designed in accordance with
Section 15.3.2.
Revise Exception 5 as shown below – also see errata posted on September 15,
2006 below:
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
Chapter 13, Section 13.5.6.2.2, page 147:
d. For ceiling areas exceeding 2,500 ft2 (232 m2), a seismic separation joint or full height
partition that breaks the ceiling up into areas not exceeding 2,500 ft2 shall be provided unless
structural analyses are performed of the ceiling bracing system for the prescribed seismic
forces that demonstrate ceiling system penetrations and closure angles provide sufficient
clearance to accommodate the anticipated lateral displacement. Each area shall be provided
with closure angles in accordance with item 2 item b and horizontal restraints or bracing in
accordance with item 3 item c.
e. Except where rigid braces are used to limit lateral deflections, sprinkler heads and other
similar type penetrations that do not behave integrally with the ceiling system in the lateral
direction shall have a 2 in. (50 mm) oversize ring, sleeve, or adapter through the ceiling tile to
allow for free movement of at least 1 in. (25 mm) in all horizontal directions. Alternatively, a
swing joint that can accommodate 1 in. (25 mm) of ceiling movement in all horizontal
directions is permitted to be provided at the top of the sprinkler head extension.
14.3.1 Reference Documents. The design, construction, and quality of composite steel and
concrete components that resist seismic forces shall conform to the applicable requirements of
1. ACI 318 excluding Chapter 22
2. AISC LRFD AISC 360
3. AISC Seismic AISC 341
K zd
∆K = ( K 33,u − K 33,d ) F∆K ( x ) (C6-8)
K 33,d
− ( K 33 , d − K 33 , u ) 2 − 2.3
x0 = c3 × 10 (The constant c3 needs to be added) (C6-10)
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
[Ref. C7-43] Tobiasson, W. (Apr. 1999). “Discussion of Ref. C7-5642 C7-42. J. Struct. Engrg.
(ASCE), 125(4), 470–471.
[Ref. C7-55] Isyumou Isyumov, N., and Mikitiuk, M. (June 1992). “Wind tunnel modeling of
snow accumulation on large roofs.” In Proc. 2nd International Conf. Snow Engrg. Santa Barbara,
CA.
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
Chapter C8, page 338:
Flow rate, Q, for the secondary drainage, 12 in. (305 mm) wide channel scupper:
Q = 0.0104 Ai Q = 0.0104 A i (C8-1)
3
Q = 0.0104(11,500)(1.5) = 179 gal/min (0.0113 m /s)
Tanks or vessels supported Use values for the appropriate structure type in the
on structural towers similar 15.5.5 categories for building frame systems and moment resisting
to buildings frame systems listed in Table 12.2-1 or Table 15.4-1.
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
AWWA D100
Sections 15.4.1, 15.7.7.1, 15.7.9.4, 15.7.10.6, 15.7.10.6.2
Welded Steel Tanks for Water Storage, 2005 2006
*ICC-ES AC 156-04
Section 13.2.5
Acceptance Criteria for Seismic Qualification Testing of Nonstructural Components, 2000
Seismic Qualification by Shake-table Testing of Nonstructural Components and Systems, 2004
NFPA 59A
Section 15.4.8
Production, Storage, and Handling of Liquefied Natural Gas (LNG), 2005 2006
The 2005 edition of ASCE 7 continues to utilize spectral response seismic design maps that reflect
seismic hazards on the basis of contours. These maps were developed by the United States
Geological Survey (USGS) and were updated for the 2005 edition. The USGS has also developed
is developing a companion software program that calculates spectral values for a specific site
based on a site’s longitude, latitude, and site soil classification. The calculated values are based on
the data used to prepare the maps in Section 22.0. The spectral values may be adjusted for Site
Class effects using the Site Classifications Procedure in Section 20.0 and the site coefficients in
Section 11.4. Longitude and latitude for a given address can be found at a variety of Web sites.
The software program should be used for establishing spectral values for design because the maps
found in ASCE 7 and at Web sites are at too large a scale to provide accurate spectral values for
most sites. Upon its completion, the The software program will be included is available on the
CD-ROM version of ASCE 7-05, and it may also be accessed at the USGS Web site at
eqhazmaps.usgs.gov, or through the SEI Web site at www.seinstitute.org Upon its completion, the
availability of the software program will be widely advertised however, as of this writing, it is
unknown when the program will be available.
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
In the second equation for Rl on the right hand side of the equation for etta the
“E” should not be in the equation as shown below:
Chapter 12:
Table 12.2-1: Design Coefficients and Factors for Seismic Force-Resisting Systems
C3
Intermediate Steel Moment 12.2.5.6, 12.2.5.7, 12.2.5.8,
Corrected 4.5 3 4 NL NL 35h NPh NPi
Frames 12.2.5.9, and 14.1
In Red
G2
Intermediate steel moment
Corrected 14.1 1½ 1¼ 1½ 35 35 35h NP h NP i
frames
In Red
G3
Ordinary steel moment frames 14.1 1¼ 1¼ 1¼ 35 35 NP NPh, i NPh, i
Printed
G3
Corrected Ordinary steel moment frames 14.1 1¼ 1¼ 1¼ 35 35 NPh NPh NPi
In Red
System B11 – ΩO is 2½ not 2; The change in BLUE reflects an error in the original posting of this errata –
not an error in the printed document. Our apologies.
System C3 – remove footnote i for SDC D;
System G2 – remove footnote i for SDC E and remove footnote h for SDC F;
System G3 – add footnote h for SDC D, remove footnote i for SDC E and remove footnote h for SDC F.
--`,`,,```,```,,,`,,````````,
D, E, F
Irregular structures with T < 3.5 Ts and P P P
having only horizontal irregularities
type 2, 3, 4, or 5 of Table 12.2-1 12.3-1
or vertical irregularities type 4, 5a or
5b of Table 12.3-1 12.3-2
Chapter 13:
4. Mechanical and electrical components in Seismic Design Categories D, E, or and F where the
component importance factor, Ip, is equal to 1.0 and either both of the following conditions apply:
a. flexible connections between the components and associated ductwork, piping, and conduit
are provided, or and
b. components are mounted at 4 ft (1.22 m) or less above a floor level and weigh 400 lb (1780
N) or less.
5. Mechanical and electrical components in Seismic Design Categories D, E, and F where the
component importance factor, Ip, is equal to 1.0 and both of the following conditions apply:
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
a. Flexible connections between the components and associated ductwork, piping, and
conduit are provided, and
b. The components weigh 20 lb (89 N) or less or, for distribution systems, weighing 5 lb/ft
(73 N/m) or less.
The word “or” should be added to the second listing of items as follows:
a. 1.3 times the force in the component and its supports due to the prescribed forces.
b. The maximum force that can be transferred to the anchor by the component and its supports.
Table 15.7-3: The heading of the third column of Occupancy Category should be “IV” not “III”
API
American Petroleum Institute
1220 L Street
Washington, D.C. 20005-4070
API 650
Sections 15.4.1, 15.7.8.1, 15.7.9.4
Welded Steel Tanks For Oil Storage, 10th Edition, Addendum 4, 2005 2006.
ASCE/SEI
American Society of Civil Engineers
Structural Engineering Institute
1801 Alexander Bell Drive
Reston, VA 20191-4400
ASCE 19
Section 14.1.1, 14.1.7
Structural Applications for Steel Cables for Buildings, 2002 1996.
The equation reference in last sentence should be changed from C5-2 to C5-3 as
follows:
The recommended value for use in Eq. C5-2 C5-3 is therefore 0.03 s.
In the heading, upper right hand corner, the “q” should be “θ” so that the heading reads:
In the heading of the table for Wind Direction, the “g” should be “γ” so that the
heading reads:
The dimension Dc in the upper right-hand diagram is measured from the upper
corner of the rectangle on the left side to the lower corner on the right side as
shown below:
Dc
Remove two horizontal lines and indent two headings for clarity. Properly
Structure Type Ct x
Moment resisting frame systems in which the frames resist 100
percent of the required seismic force and are not enclosed or
adjoined by components that are more rigid and will prevent the
frames from deflecting where subjected to seismic forces:
0.02 0.75
All other structural systems
(0.0488)a
a
- metric equivalents are shown in parentheses
Remove the units in two places in the first paragraph as shown below:
12.8.4.2 Accidental Torsion. Where diaphragms are not flexible, the design shall include
the inherent torsional moment (Mt) (kip or kN) resulting from the location of the structure
masses plus the accidental torsional moments (Mta) (kip or kN) caused by assumed
displacement of the center of mass each way from its actual location by a distance equal
to 5 percent of the dimension of the structure perpendicular to the direction of the applied
forces.
Where earthquake forces are applied concurrently in two orthogonal directions, the
required 5 percent displacement of the center of mass need not be applied in both of the
orthogonal directions at the same time, but shall be applied in the direction that produces
the greater effect.
9. For buildings with a diaphragm that is not flexible, the distance between the center of rigidity
and the center of mass parallel to each major axis shall not exceed 15 percent of the greatest
width of the diaphragm parallel to that axis. In addition, the following two equations shall be
satisfied for each major axis direction:
m n
e1 2 m
∑ k1i d i2 + ∑ k 2 j d 2j ≥ 2.5(0.05 +
i =1 j =1 b1
)b1 ∑ k1i
i =1
(Eq. 12.14-2A)
∑ k1i d i2 + ∑ k 2 j d 2j ≥ 2.5(0.05 +
i =1 j =1 b2
)b2 ∑ k1i
2
i =1
(Eq. 12.14-2B)
k1i is the lateral load stiffness of wall “i” or braced frame “i” parallel to major axis 1
k2j is the lateral load stiffness of wall “j” or braced frame “j” parallel to major axis 2
d1i is the distance from the wall “i” or braced frame “i” to the center of rigidity, perpendicular
to major axis 1
d2j is the distance from the wall “j” or braced frame “j” to the center of rigidity, perpendicular
to major axis 2
e1 is the distance perpendicular to major axis 1 between the center of rigidity and the center of
mass
b1 is the width of the diaphragm perpendicular to major axis 1
e2 is the distance perpendicular to major axis 2 between the center of rigidity and the center
of mass
b2 is the width of the diaphragm perpendicular to major axis 2
m is the number of walls and braced frames resisting lateral force in direction 1
n is the number of walls and braced frames resisting lateral force in direction 2
Eqs. 12.14-2A and B need not be checked where a structure fulfills all the following
limitations:
1. The arrangement of walls or braced frames is symmetric about each major axis direction,
2. The distance between the two most separated lines of walls or braced frames is at least 90
percent of the dimension of the structure perpendicular to that axis direction, and
3. The stiffness along each of the lines considered for item 2 above is at least 33 percent of the
total stiffness in that axis direction.
Chapter C Appendix C
Serviceability Considerations
the computer as a design tool, the use of stronger a fraction of the nominal loads.
(but not stiffer) construction materials, the use of
lighter architectural elements, and the The response of the structure to service loads
uncoupling of the nonstructural elements from normally can be analyzed assuming linear elastic
the structural frame, may result in building behavior. However, members that accumulate
systems that are relatively flexible and lightly residual deformations under service loads may
damped. Limit states design emphasizes that require examination with respect to this long-
serviceability criteria (as they always have been) term behavior. Service loads used in analyzing
are essential to ensure functional performance creep or other long-term effects may not be the
and economy of design for such building same as those used to analyze elastic deflections
structural systems [Refs. CC-1, CC-2, CC-3]. or other short-term or reversible structural
behavior.
There are three general types of unserviceability
that may be experienced: Serviceability limits depend on the function of
the building and on the perceptions of its
1. Excessive deflections or rotation that occupants. In contrast to the ultimate limit
may affect the appearance, functional states, it is difficult to specify general
use or drainage of the structure, or may serviceability limits that are applicable to all
cause damaging transfer of load to non- building structures. The serviceability limits
load supporting elements and presented in Sections CC.1.1, CC.1.2, and
attachments. CC.1.3 provide general guidance and have
2. Excessive vibrations produced by the usually led to acceptable performance in the past.
activities of building occupants, However, serviceability limits for a specific
mechanical equipment, or the wind, building should be determined only after a
which may cause occupant discomfort careful analysis by the engineer and architect of
or malfunction of building service all functional and economic requirements and
equipment. constraints in conjunction with the building
3. Deterioration, including weathering, owner. It should be recognized that building
corrosion, rotting, and discoloration. occupants are able to perceive structural
deflections, motion, cracking, or other signs of
In checking serviceability, the designer is possible distress at levels that are much lower
advised to consider appropriate service loads, the than those that would indicate that structural
response of the structure, and the reaction of the failure was impending. Such signs of distress
building occupants. may be taken incorrectly as an indication that the
building is unsafe and diminish its commercial
Service loads that may require consideration value.
include static loads from the occupants and their
possessions, snow or rain on roofs, temperature CC.1.1 Vertical Deflections Excessive vertical
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---
distress in the form of wide cracks has been "Wind drift design of steel-framed
caused by restraint of thermal, shrinkage, and buildings: state of the art." J. Str. Div.,
prestressing deformations. Designers are ASCE 114(9): 2085–2108.
advised to provide for such effects through relief [CC-8] Freeman, S. (1977). "Racking tests of
joints or by controlling crack widths. high rise building partitions." J. Str.
Div., ASCE 103(8): 1673–1685.
CC.5 Durability Buildings and other [CC-9] Bachmann, H. and Ammann, W.
structures may deteriorate in certain service (1987). "Vibrations in structures."
environments. This deterioration may be visible Structural Engineering, Doc. 3e,
upon inspection (weathering, corrosion, staining) International Assoc. for Bridge and Str.
or may result in undetected changes in the Engr., Zurich, Switzerland.
material. The designer should either provide a [CC-10] Ellingwood, B. (1989). "Serviceability
specific amount of damage tolerance in the guidelines for steel structures." AISC
design or should specify adequate protection Engr. J. 26(1): 1–8.
systems and/or planned maintenance to minimize
the likelihood that such problems will occur. [CC-11] ANSI (1983). “American National
Water infiltration through poorly constructed or Standard Guide to the Evaluation of
maintained wall or roof cladding is considered Human Exposure to Vibration in
beyond the realm of designing for damage Buildings (ANSI S3.29-1983)." Am.
tolerance. Waterproofing design is beyond the Nat. Stds. Inst., New York.
scope of this standard. For portions of buildings [CC-12] Murray, T. (1991). "Building floor
and other structures exposed to weather, the vibrations." AISC Engineering J. 28(3):
design should eliminate pockets in which 102–109.
moisture can accumulate.
[CC-13] Allen, D.E. and Rainer, J.H. (1976).
References "Vibration criteria for long-span floors."
[CC-1] Ad Hoc Committee on Serviceability Canadian, J. Civil Engr. 3(2): 165–173.
--`,`,,```,```,,,`,,````````,``-`-`,,`,,`,`,,`---