SUN STORAGE 3Power C Series

1,500 Vdc

UP TO 3.66 MVA AT 1,500 V

THREE-PHASE TRANSFORMERLESS BATTERY INVERTER WITH AN EXTRA THERMAL


STABILITY AND A GREATER POWER DENSITY
The INGECON® SUN STORAGE 3Power C Series is a three-phase bidirectional battery inverter that can be used in
grid-connected and stand-alone systems. This one-of-a-kind battery inverter achieves a market-leading power density of
470 kW/m3, as it provides up to 3,660 kVA in just one power stack.
Latest generation electronics
The INGECON® SUN STORAGE 3Power C Series battery inverter features an innovative control unit that performs a more
efficient and sophisticated inverter control, as it uses a last-generation digital signal processor.
Liquid Cooling System (LCS)
Ingeteam has already supplied +52 GW of liquid-cooled wind power converters worldwide. It offers a greater thermal stability
and a more optimized component usage. The LCS has been designed to refrigerate the IGBTs, the power phases and the IP65
compartment. It features less moving components, so it consumes a lower amount of power and it requires less maintenance
works.
The LCS is a closed circuit supplied totally filled and purged, equipped with fast connectors with an anti-dripping system, so it
offers zero risk of particle entrance. It has been designed to avoid siphons in order to easily purge it if necessary. The coolant
used is a biodegradable glycol water mixture. There is no need of emptying the LCS in order to replace the phases, nor the
sensors.
IP65 protection
A secondary liquid cooling system is used to refrigerate the air inside the IP65-protected compartment. A water-air heat
exchanger is used for that. This compartment contains the power and control electronics, the DC fuses, the DC and AC
protections, the busbars and the power phases.
SUN STORAGE 3Power C Series
1,500 Vdc

UP TO 3.66 MVA AT 1,500 V


Three-phase transformerless battery inverter with an extra thermal
stability and a greater power density
Power converter stands both, grid-following and grid forming operating modes:

Real power related functionalities Investment deferral: Safety and quality:


Renewable resources integration: - Peak shaving. - “Un-interruptible” Power.
- Ramp limits. - Load shifting / Load following. - Grid code compliance.
- Power smoothing / firming / - Real power response improvement of - Transmission congestion relief / Power
curtailment. conventional power plants. quality - reliability.
- Time shifting. Power efficiency: Reactive power related functionalities
- Micro grids. - Time shifting.
- Voltage control (Q/V).
Grid support / Ancillary services: - Price arbitrage.
- Voltage control / protection.
- Frequency regulation. - Real power response improvement of
- Fixed power factor (QPF).
- Synthetic inertia. conventional power plants.
- Fixed reactive power output (Qref).
- Black start. - Peak shaving.
- Limitation of response of Reactive Power.
- Frequency control / protection.
- Virtual “Synchronous Machine”. Standard 5 year warranty, extendable
upon request.

Protections Optional Accessories Liquid cooling system


- Short-circuits and overloads at the - Heating kit, for operating at an ambient - LCS to refrigerate the IGBTs.
output. temperature of down to - More optimized component usage:
- Anti-islanding with automatic -30 ºC. greater thermal stability.
disconnection. - DC surge arresters type I+II. - Less moving components: lower power
- Insulation failure DC. - AC surge arresters type I+II. consumption and less maintenance
- Up to 24 pairs of fuse-holders. - DC fuses. works.
- Lightning induced DC and AC surge - Monitoring of the DC currents. - No risk of particle entrance.
arresters, type II. - Grounding kit. - Anti-corrosion protection with stainless
- Motorized DC switch. steel components
- Motorized AC circuit breaker. - LCS is used in many industries. Thus,
- Hardware protection via firmware. it is very reliable, as its components are
- Additional protection for the power stack, subject to many validation tests.
liquid cooled, IP65 rated and air cooled - Fast connectors with anti-dripping
by a closed loop. system.
- Biodegradable glycol water mixture.
- No need of emptying the LCS in order to
replace the phases, nor the sensors.

INGECON® SUN STORAGE 3660TL

+24
...

Optional
+3
+2
DC-Pre-charge

+1 AC output for
AC-Pre-charge

L1
Filter

L2 connection to
-1 L3 a MV network
-2 Inverter
-3 M M

...
-24
Optional

Size and weight (mm and kg)


2,800 kg
2,215

3,50
0
50
1,0

www.ingeteam.com
SUN STORAGE 3Power C Series
1,500 Vdc

INGECON® SUN STORAGE 3660TL

C366 C450 C578 C600 C630 C645 C660


INPUT (DC)
Battery voltage range for off-grid mode 530 - 1,300 V 646 - 1,300 V 823 - 1,300 V 853 - 1,300 V 895 - 1,300 V 916 - 1,300 V 937 - 1,300 V
Battery voltage for grid-tied mode(1) 581 - 1,300 V 708 - 1,300 V 903 - 1,300 V 937 - 1,300 V 983 - 1,300 V 1,006 - 1,300 V 1,028 - 1,300 V
Maximum voltage 1,500 V
Maximum current 3,850 A
Nº inputs with fuse-holders Up to 24
Fuse dimensions Up to 630 A / 1,500 V / aR / 100 kA (L/R 5mS) (optional)
Type of connection Connection to copper bars
Power blocks 1

INPUT PROTECTIONS
Overvoltage protections Type II surge arresters (type I+II optional)
DC switch Motorized DC load break disconnect
Other protections Up to 24 pairs of DC fuses (optional) / Reverse polarity / Insulation failure monitoring / Anti-islanding protection

OUTPUT (AC)
Discharge power @1,300 Vdc 2,028.6 kVA / 2,494.2 kVA / 3,203.7 kVA / 3,325.6 kVA / 3,491.9 kVA / 3,575 kVA / 3,658.1 kVA /
(35 ºC / 50 ºC) 1,743.3 kVA 2,143.4 kVA 2,753.1 kVA 2,857.9 kVA 3,000.8 kVA 3,072.2 kVA 3,143.7 kVA
Discharge current @1,300 Vdc
3,200 A / 2,750 A
(35 ºC / 50 ºC)
Charge power @1,300 Vdc 2,021 kVA / 2,485.6 kVA / 3,192.6 kVA / 3,314.2 kVA / 3,480 kVA / 3,562.7 kVA / 3,645.6 kVA /
(35 ºC / 50 ºC) 1,737.7 kVA 2,136.4 kVA 2,744 kVA 2,848.6 kVA 2,991 kVA 3,062.2 kVA 3,133.4 kVA
Charge current @1,300 Vdc
3,189 A / 2,741 A
(35 ºC / 50 ºC)
366 V IT 450 V IT 578 V IT 600 V IT 630 V IT 645 V IT 660 V IT
Rated voltage(2)
System System System System System System System
Frequency 50 / 60 Hz
Power Factor(3) 1
Power Factor adjustable Yes, 0 - 1 (leading / lagging)
THD (Total Harmonic Distortion)(4) <3%

OUTPUT PROTECTIONS
Overvoltage protections Type II surge arresters (type I+II optional)
AC breaker Motorized AC circuit breaker
Anti-islanding protection Yes, with automatic disconnection
Other protections AC short-circuits and overloads

FEATURES
Operating efficiency 98.9%
CEC 98.5%
Max. consumption aux. services 7,600 W
Stand-by or night consumption(5) 185 W
Average power consumption per day 2,500 W

GENERAL INFORMATION
Ambient temperature -20 ºC to +60 ºC
Relative humidity (non-condensing) 0-100% (Outdoor)
Protection class IP65(6)
Corrosion protection External corrosion protection
Maximum altitude 4,500 m (for installations beyond 1,000 m, please contact Ingeteam’s BESS sales department)
Cooling system Liquid cooling system and forced air cooling system with temperature control (400V 3 phase + neutral power supply, 50/60 Hz)
Air flow range 0 - 18,000 m3/h
Average air flow 12,000 m3/h
Acoustic emission (100% / 50% load) <57 dB(A) at 10m / <49.7 dB(A) at 10m
Marking CE
IEC 62920, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-4, IEC 61000-3-11, IEC 61000-3-12, IEC 62109-1, IEC 62109-2,
EMC and security standards
EN 50178, FCC Part 15, AS3100
Grid connection standards IEC 62116, EN 50530, IEC 61683, EU 631/2016 (EN 50549-2, CEI 0-16, NTS Spain, VDE-AR-N 4120, VDE-AR-N 4110,
Arrêté du 9 juin 2020, Terna A68), G99, South African Grid Code, Mexican Grid code, Chilean Grid Code, Ecuadorian Grid
Code, Peruvian Grid Code, IEC61727, ABNT NBR 16149, ABNT NBR 16150, IEEE 1547, IEEE1547.1, DEWA (Dubai), Abu
Dhabi Grid Code, Jordan Grid Code, Egyptian Grid Code, Saudi Arabia Grid Code, RETIE Colombia, Australian Grid Code

Notes
(1) Minimum voltage DC (VDC, min) for Vgrid,max = 1.1 p.u. and Power Factor=1. If Vgrid,max is higher than this value, the minimum voltage should be corrected as VDC, min * Vgrid,max
/ 1.1. For other DC voltage ranges, please contact Ingeteam’s BESS sales department
(2) Other AC voltages and powers available upon request
(3) For Pout>25% of the rated power
(4) For Pout>25% of the rated power and voltage in accordance with IEC 61000-3-4
(5) Consumption from Battery
(6) Except for the LC filter and the air-water heat exchanger, that are IP54.

www.ingeteam.com
Ingeteam Power Technology S.A. - Energy Ingeteam S.r.l Ingeteam Uruguay S.A.
Sarriguren (Navarra), ESPAÑA Castel Bolognese (RA), ITALIA Montevideo, URUGUAY
(+34) 94 828 80 00 (+39) 0546 651490 +59 8 2623 2805
[email protected] [email protected]

Ingeteam Power Technology S.A. - Paneles Ingeteam GmbH Ingeteam Panamá S.A.
Sesma (Navarra), ESPAÑA Düsseldorf, ALEMANIA Penonomé, PANAMÁ
(+34) 94 869 84 55 +49 (0) 211 7817 7950 (507) 66444834
[email protected] [email protected] [email protected]

Ingeteam Power Technology S.A. - Service Ingeteam a.s. Ingeteam Ltda.


Albacete, ESPAÑA Ostrava-Pustkovec, REPÚBLICA CHECA São Paulo, BRASIL
(+34) 96 724 55 04 +42(0) 59 747 68 20 (+55) 19 30 37 37 73
[email protected] [email protected] [email protected]

Ingeteam Power Technology S.A. - Technology Ingeteam Sp.zo.o. Ingeteam Ltda.


Zamudio (Bizkaia), ESPAÑA Warsaw, POLONIA Curitiba, BRAZIL
(+34) 94 403 96 00 +48 22 821 99 30 (+55) 41 32769841
[email protected] [email protected] [email protected]

Ingeteam Power Technology S.A. - Electronics Ingeteam Service s.r.l. Ingeteam Power Technology Shanghai Co., Ltd
Zamudio (Bizkaia), ESPAÑA Constanta, RUMANIA Shanghai, CHINA
(+34) 94 403 96 00 (+40) 728 993 202 +86 139 1622 4886
[email protected] [email protected]

Ingeteam Power Technology S.A. - Converters Ingeteam Bulgaria EAD Ingeteam Vietnam CO., LTD
Ortuella (Bizkaia), ESPAÑA Kavarna, BULGARIA Hanoi City, VIETNAM
(+34) 94 403 96 00
[email protected]

Ingeteam Indar Machines S.A. Ingeteam Inc Headquarters Ingeteam Power Technology SA
Beasain (Gipuzkoa), ESPAÑA Milwaukee, EE.UU. Abu Dhabi, UAE
(+34) 94 302 82 00 (+1) 414 934 4100 +971 2 207 666
[email protected] [email protected]

Ingeteam R&D Europe, S.L. Ingeteam México S.A. de C.V. Ingeteam Power Technology India Pvt. Ltd.
Zamudio (Bizkaia), ESPAÑA Ciudad de México, MÉXICO Tamilnadu, INDIA
(+34) 94 403 96 00 (+52) 55 6586 9930
[email protected]

Ingeteam SAS Ingeteam México S.A. de C.V. Ingeteam Morocco SARLAU


Labège, FRANCIA Juchitán (Oaxaca), MÉXICO Casablanca, MARRUECOS
33 (0) 5 61 25 00 00 +52 971 281 0996
[email protected] [email protected]

Ingeteam UK LTD Ingeteam SpA Ingeteam Australia Pty Ltd


East Kibride, REINO UNIDO Las Condes, Santiago CHILE North Wollongong, AUSTRALIA
+44 (0) 141 488 5290 (+56) 232 637 200
[email protected]

Ingeteam S.A.
Parque Tecnológico de Bizkaia, Ed. 106
Zamudio (Bizkaia) - ESPAÑA
(+34) 94 403 97 10
[email protected]

You might also like