Water Strainer Control Panel Submittal
Water Strainer Control Panel Submittal
Submittal for
Strainer Control Panel
Prepared by:
Your Company
Your Address
Panel Job: 2013-252
Table of Contents
D. Drawings
E. Bill of Materials
IEC Style Door Mounted Disconnect Switches – Type N
Class 9421
The 9421 Type N is an IEC-style door-mounted disconnect switch with onboard fusing for Class CC and Class J fuses.
The switch is UL Listed and CSA certified, and provides service entrance spacing, 100 kA withstandability and Type 2
coordinated protection when used with Square D and Telemecanique starters in accordance with fuse selection tables.
Each installation will require a disconnect switch, handle, and shaft.
Class 9421 Disconnect Switches
Maximum Horsepower Ratings Switch
Disconnect 1 Phase AC 3 Phase AC DC Fuse Selection
Switch Size Type Price
115 V 230 V 200 V 230 V 460 V 575 V 125 V 250 V
2 3 7.5 7.5 15 20 3 5 Unfused NC1 $ 140.00
Class 9421
Disconnect Switch 30 A .75 2 5 5 10 10 2 3 30 A Class CC NC2 153.00
2 3 7.5 7.5 15 20 3 5 30 A Class J NC3 167.00
3 10 15 15 30 50 5 10 Unfused ND1 169.00
60 A
3 10 15 15 30 50 5 10 60 A Class J ND3 216.00
Disconnect
Switch Size Type Price Auxiliary Contacts
Shaft and Terminal Shieldp NTS30 $ 10.60
Auxiliary Contact
Shorting Links Disconnect Kit
30 A CC Fuse Cover t NCF30 15.80
Switch Size
J Fuse Cover NJF30 21.10 Type Price
Terminal Shieldp NTS60 15.80 SPDT N.O. Inner NAX10 $ 36.90
60 A
J Fuse Covert NJF60 21.10 SPDT N.O. Outer NBX10 36.90
30 A, 60 A
Auxiliary Contact Shielda NXSH 10.60 DPDT 2 N.O. Inner NAX20 53.00
p Terminal shield for line or load side. DPDT 2 N.O. Outer NBX20 53.00
OPERATING MECHANISMS AND
t 30 A CC fuse cover and 60 A J fuse cover are also used for non-fusible
applications. NOTE: Each installation requires a disconnect switch, handle, and
a 2 per package shaft. Further, the first auxiliary contact block that is used
must be an inner block (maximum is 1 inner and 3 outer
blocks).
DISCONNECT SWITCHES
E F
A B C D
1&2 3 1&2 3
NC 4.33” 3.82” 4.45” 4.65” 3.73” 5.25” 4.20” 5.70”
ND 5.62” 5.14” 5.36” 6.1” 4.90” 5.06”
7
Line Terminals B
Up to four auxiliary C
blocks may be fitted
D
Terminal Shields
and
Fuse Covers
For additional information, reference Catalog Number 9420CT9701 or D-Fax™ Number 1500.
LOW-PEAK® LP-CC
Time-Delay Fuses
Class CC – 600 Volt, ⁄Ω™ to 30 Amps
Dimensional Data General Information:
LP-CC LOW-PEAK Yellow™ Fuse
• A superior all-purpose, space-saving branch circuit fuse
that meets most protection requirements up to 30 amps.
• Very compact; physical size is only ⁄‹Ω£™∑ ≈ 1⁄Ω™∑ (10.3mm ≈
1.5" ((0.031) 38.1mm) with rejection tip.
(38.1mm)
• The unique yellow color makes it easy to tell that the correct
fuse type is installed.
• Faster response to damaging short-circuit currents and
higher interrupting rating than mechanical overcurrent
protective devices.
.41" ((0.005)
(10.3mm) 200,000 Ampere Interrupting Rating
• Maximum interrupting rating for available fault current in
today's large capacity systems.
• Helps ensure that future growth will not obsolete the system.
Catalog Symbol: LP-CC Dual Characteristics
• Time-delay to avoid unwanted fuse openings from surge
Time-Delay, Current-Limiting
currents.
Ampere Rating: ⁄Ω™ to 30 Amperes
• Fast speed of response under short-circuit conditions for a
AC Voltage Rating: 600 Volts (or less) high degree of current-limitation.
Interrupting Rating: 200,000A RMS Sym. • ADVANTAGE: The LOW-PEAK ® fuse can be sized close
Agency Approvals: to full load ratings for maximum overload and short-circuit
U.L. Listed, Std. 248-4, Class CC, Guide JDDZ, File E4273 protection.
CSA Certified, C22.2 No. 248.4, Class 1422-02, File 53787 • ADVANTAGE: Can be used where either a time-delay or
DC Voltage Rating: 300 Volt DC (or less) a fast-acting fuse is needed, making selection easier and
⁄Ω™-2⁄Ω¢A and 20-30A, 20,000 AIR, U.L. 198L reducing spare fuse inventories for substantial cost reduction.
150 Vdc or less 3-15A, 20,000 AIR, U.L. 198L
Superior Motor Protection
Catalog Numbers • For protection of small horsepower motor circuits.
LP-CC-⁄Ω™ LP-CC-1⁄Ω™ LP-CC-3 LP-CC-6 LP-CC-12
• Proper sizing can provide Type “2” coordinated protection
LP-CC-flΩ¡º LP-CC-1flΩ¡º LP-CC-3¤Ω¡º LP-CC-6⁄Ω¢ LP-CC-15
for NEMA and IEC motor controllers.
LP-CC-°Ω¡º LP-CC-1°Ω¡º LP-CC-3⁄Ω™ LP-CC-7 LP-CC-20
• Motors receive maximum protection against burnout from
LP-CC-1 LP-CC-2 LP-CC-4 LP-CC-7⁄Ω™ LP-CC-25
overloads and single phasing.
LP-CC-1⁄Ω• LP-CC-2⁄Ω¢ LP-CC-4⁄Ω™ LP-CC-8 LP-CC-30 Current-Limiting Effects
LP-CC-1⁄Ω¢ LP-CC-2⁄Ω™ LP-CC-5 LP-CC-9 — Prospective Short- *Let-Through Current (Apparent RMS Symmetrical)
LP-CC-1›Ω¡º LP-CC-2°Ω¡º LP-CC-5flΩ¡º LP-CC-10 — Circuit Current 1⁄Ω¢A 2°Ω¡ºA 15A 20A 25A 30A
1,000 100 135 240 305 380 435
3,000 140 210 350 440 575 580
Carton Quantity and Weight
5,000 165 255 420 570 690 710
Ampere Carton Weight*
10,000 210 340 540 700 870 1,000
Ratings Qty. Lbs. Kg.
20,000 260 435 680 870 1,090 1,305
0-30 10 .193 .088
30,000 290 525 800 1,030 1,300 1,520
*Weight per carton.
40,000 315 610 870 1,150 1,390 1,700
Fuseblock Catalog Numbers 50,000 340 650 915 1,215 1,520 1,820
Screw Pressure 60,000 350 735 1,050 1,300 1,650 1,980
No. of Screw Pressure Box Quick- Quick- 80,000 390 785 1,130 1,500 1,780 2,180
Poles Terminal Plate Terminal Connect Connect
100,000 420 830 1,210 1,600 2,000 2,400
1 BC6031S BC6031P BC6031B BC6031SQ BC6031PQ
200,000 525 1,100 1,600 2,000 2,520 3,050
2 BC6032S BC6032P BC6032B BC6032SQ BC6032PQ
*RMS Symmetrical Amperes Short-Circuit
3 BC6033S BC6033P BC6033B BC6033SQ BC6033PQ NOTE: To calculate Ip (Ipeak) multiply IRMS value ≈ 2.3.
• Fibre tube.
• For circuits with high inrush currents.
• Formerly designated 5AB.
• Fusetron® Dual-Element fuse.
1.5"
(Ⳳ0.031)
(38.1mm)
Fuseblock Catalog Numbers
Poles Terminal Type
Screw With Pressure Plate Box
Quick Connect w/Quick Connect Lug
1 BM6031SQ BM6031PQ BM6031B
.41"
(Ⳳ0.004) 2 BM6032SQ BM6032PQ BM6032B
(10.3mm)
3 BM6033SQ BM6033PQ BM6033B
CC-TRON¤ FNQ-R
Time-Delay Fuses
Ú‹‰£“∑ ≈ 1Ú‰“∑, 600 Volt, Ú‰¢ to 30 Amps
Dimensional Data
General Information:
• The Bussmann CC-TRON® (FNQ-R) was designed to meet
the needs of control circuit transformer protection.
• Current-limitation protects down stream components
1.5" against damaging thermal and magnetic effects of short-
(50.031)
(38.1mm) circuit currents.
• Rejection feature. FNQ-R fuses meet the U.L. 508, para-
graph 19.2.4 requirement that control circuit fuses used in
equipment listed for use with more than 10,000 ampere
available must have an adequate interrupting rating and
.41" must be rejection type.
(50.005)
(10.3mm) • High inrush time-delay. Control circuit transformers can
experience inrush currents up to 85 times their full-load
current rating. FNQ-R fuses can be sized according to
NEC and U.L. requirements and still allow the high inrush
Catalog Symbol: FNQ-R currents, with significantly more time-delay than the U.L.
Time-Delay minimum value of 12 seconds at 200% for Class CC fuses.
Application: Circuit Transformer Protection • Melamine tube. Nickel-plated brass endcaps.
Ampere Rating: ⁄Ω¢ to 30 Amperes Maximum Acceptable Rating of Overcurrent Device*
Voltage Rating: 600 Volts AC (or less)† Maximum Rating of Overcurrent
Interrupting Rating: 200,000A RMS Sym. (U.L.) Rated Primary Protective Device Expressed As A
Agency Approvals: Current Percent of Transformer Primary
(Amperes) Current Rating
U.L. Listed, Std. 248-4, Class CC, Guide JDDZ, File E4273
Less than 2A 500**
CSA Certified, Class CC CSA, Class 1422-01, 2A to less than 9A 167
File 53787–HRC-MISC 9A or more 125
†12-30 amp is 300 Vdc and 10 KAIC. *U.L. 508, Table 19.3.
**300% for other than motor control applications.
Dimensions–Type TF Only
VA Key
Figure A B C Dq E F Gf SLOT
I II III
25 VA ... ... 3 3.09 3.00 4.00 3.84 2.00 2.50 4.20 .20 x .38
... ... 25 VA 3 4.00 3.43 4.00 4.80 2.00 2.50 4.20 .20 X .48
50 VA 25 VA ... 3 3.09 3.00 4.00 3.84 2.00 2.50 4.20 .20 x .38
... ... 50 VA 3 4.19 3.43 4.25 4.99 2.38 2.81 4.45 .20 X .48
75 VA 50 VA ... 3 3.34 3.38 4.25 4.09 2.38 2.81 4.45 .20 X .48
... 75 VA ... 3 3.59 3.75 4.55 4.34 2.88 3.13 4.75 .20 x .38
... ... 75 VA 3 4.88 3.75 4.55 5.68 2.88 3.13 4.75 .20 x .38
100 VA ... ... 3 3.34 3.38 4.25 4.09 2.38 2.81 4.45 .20 X .48
... ... 100 VA 3 4.88 3.75 4.55 5.68 2.88 3.13 4.75 .20 x .38
150 VA 100 VA ... 3 3.59 3.75 4.55 4.34 2.88 3.13 4.75 .20 x .38
200 VA 150 VA ... 3 3.59 3.75 4.55 4.34 2.88 3.13 4.75 .20 x .38
250 VA ... 150 VA 3 5.25 3.75 4.55 6.05 2.88 3.13 4.75 .20 x .38
300 VA 200 VA 200 VA 3 4.70 4.50 5.10 5.50 2.56 3.75 5.30 .20 x .38
350 VA 250 VA 250 VA 3 5.09 4.50 5.10 5.89 3.00 3.75 5.30 .20 x .38
... 300 VA ... 3 5.09 4.50 5.10 5.89 3.00 3.75 5.30 .20 x .38
... ... 300 VA 3 5.46 4.50 5.10 6.26 3.56 3.75 5.30 .20 x .38
500 VA 350 VA ... 3 5.46 4.50 5.10 6.26 3.56 3.75 5.30 .20 x .38
... ... 350 VA 3 5.46 4.50 5.10 6.26 3.56 3.75 5.30 .20 x .38
750 VA 500 VA 500 VA 3 5.66 5.25 5.73 6.46 3.43 4.38 5.93 .28 X .56
1000 VA 750 VA 750 VA 3 6.04 5.25 5.73 6.84 4.31 4.38 5.93 .28 X .56
1500 VA 1000 VA 1000 VA 3 5.81 7.06 7.46 6.61 4.13 5.81 7.66 .28 X .56
2000 VA 1500 VA 1500 VA 3 7.04 7.06 7.46 7.84 4.56 5.81 7.66 .28 X .56
q Dimensions with FINGERSAFE® covers installed.
f Dimensions with fuse pullers installed.
c SF41 can be installed on the following voltage codes: D1, D5, D24, D3, D4,
D51, D2, D23, D14, D25, D20, D95, D19.
Factory Installed Secondary Fuse Clips
How to Order:
D1:240 x 480-120
To Order Specify: Catalog Number
UL/CSA VA CE VA Catalog Number Price
50 50 9070T50D1SF41 $ 40.30 k Class Number Class Type Voltage Code
100 100 9070T100D1SF41 52.00 k Type Number
k Voltage Code 9070 TF500 D1
150 150 9070T150D1SF41 55.00
250 160 9070T250D1SF41 79.00 k Field Fuse Option
9070 FB-3B
12
FINGERSAFE is a Registered
Trademark of Square D Company
or related companies.
0 0
— — — — — — — 2 2 LC1D40008 b 296.00 353.00
3 7.5 15 15 40 40 50 3 LC1D50 234.00 291.00
0 1 1
5 10 20 20 50 50 65 3 LC1D65 322.00 379.00
80
— — — — — — — 4 0 LC1D65004 b 446.00 503.00
0 0
— — — — — — — 2 2 LC1D65008 b 446.00 503.00
LC1D093
IEC CONTACTORS AND
Table 18.2: D-Line Overload Relays — Ambient Compensated, Bi-Metallic Direct Mount
Class 10 with Class 10 without Class 20 with Class 20 without
Current Setting For Direct Mounting Single Phase Single Phase Single Phase Single Phase $ Price
Range Amperes to LC1 ttt Sensitivity Sensitivity Sensitivity Sensitivity
0.10–0.16 LRD01 LR3D01 — —
0.16–0.25 LRD02 LR3D02 — —
0.25–0.40 LRD03 LR3D03 — —
LC1D115 0.40–0.63 LRD04 LR3D04 — —
0.63–1 D09–D32 LRD05 LR3D05 — — 60.00
1–1.6 LRD06 LR3D06 — —
1.6–2.5 LRD07 LR3D07 — —
2.5–4 LRD08 LR3D08 LRD1508 LR3D1508A1
4–6 LRD10 LR3D10 LRD1510 LR3D1510A1
5.5–8 D09–D32 LRD12 LR3D12 LRD1512 LR3D1512A1
7–10 D09–D32 LRD14 LR3D14 LRD1514 LR3D1514A1
9–13 D12–D32 LRD16 LR3D16 LRD1516 LR3D1516A1
62.00
12–18 D18–D32 LRD21 LR3D021 LRD1521 LR3D1521A1
16–24 D25–D32 LRD22 LR3D22 — —
17–25 D25–D32 — — LR3D1522A1
23–32 D25–D32 LRD32 LR3D32 — —
23–28 D25–D32 — — LRD1530 LR3D1530A1
73.00
25–32 D25–D32 — — LRD1532 LR3D1532A1
LRD22
30–38 D32 LRD35 LR3D35 — —
17–25 D40–D80 LRD3322 LR3D3322 LR2D3522 LR3D3522
23–32 D40–D80 LRD3353 LR3D3353 LR2D3553 LR3D3553
30–40 D40–D80 LRD3355 LR3D3355 LR2D3555 LR3D3555 107.00
37–50 D50–D80 LRD3357 LR3D3357 LR2D3557 LR3D3557
48–65 D50–D80 LRD3359 LR3D3359 LR2D3559 LR3D3559
55–70 D65–D80 LRD3361 LR3D3361 LR2D3561 LR3D3561
63–80 D65–D80 LRD3363 LR3D3363 LR2D3563 LR3D3563 127.00
80–104 D80 LRD3365 — — —
80–104 D115–D150 LRD4365 — — —
95–120 D115–D150 LRD4367 — — — 362.00
110–140 D150 LRD4369 — — —
STARTERS
4 LC1F7804 9940.00
— 450 800 900 800 1000 3 LC1F800 6676.00
18
300–500 F265–F500 LR9F7379b LR9F7579b 737.00
380–630 F400–F630 LR9F7381b LR9F7581b 905.00
a Complete part number by adding coil voltage code from table below. For example: LC1F115G7. All contactors (except F780) include 1 N.O. coil
interlock contact.
b When mounting overload relays LR9F5●57 to LR9F5●71 directly beneath the contactor, supporting the relays with a mounting plate is recommended.
With overload relays LR9F7●75 to LR9F7●81, use of a support mounting plate is mandatory.
c IEC standard 60947-4 specifies the following trip times when the overload relay senses 7.2 times the setting current:
Class 10 — between 4 and 10 seconds
Class 20 — between 6 and 20 seconds
d Interconnection kit LA7F407 is required to mount an LR9F●71 to an LC1F185.
Table 18.7: Coil Voltage Codes for AC and DC Voltages for F800 (includes built-in surge supressor)
Volts AC/DC 24 48 110 120 127 208 220 240 277 380 415 440 480 575 600 660
50/60 HZ — — FW FW FW — MW MW — QW QW QW — — — —
f Scale range is expanded between 0.1 and 0.6 seconds on the dial for more accurate settings at the lower end of the range.
g With switching time of 40 ms ± 15 ms between the opening of the N.C. contact to the closing of the N.O. contact.
Catalog number
Front snap-on to be completed
Application Price
mounting onto by the code corresponding
to the coil voltage
LCk/LPk D09 to D65 For silent operation and energy conservation LA6DK10ih $74.
LC1 D80 to D150 For silent operation and energy conservation LA6DK20ih 74.
LP1 D80
h Does not include internal coil clearing contact.
Volts 12 24 32/36 42/48 60/72 100 110/127 200/208 220/240 380/415 440/480 500/600
AC or DC J B C E EN K F L M Q R S
For additional information, reference Catalog #8502CT9901R2/01 or D-FAX™ #5497, 5498, 5799, 5500, 5501, 5502.
Accessories
Standard Catalog
Description For use with Price
Packaging Number
Pre wiring kit allows direct connection of the N.C. contact LC1D09 through D18 10 LAD7C1 $ 8.70
of relay LRD01–D32 or LR3D01–D32 to the contactor LC1D25, D32 10 LAD7C2 8.70
Stop button locking device All relays except LRD01–D32, LR3D01–D32 and LR9D 10 LA7D901 2.20
LRD01–D32, LR3D01–32 1 LAD703b 43.70
Remote stop/tripping or electrical resetc
LA7D901 All relays except LRD01–D32, LR3D01–D31 1 LA7D03b 43.70
Reset by flexible cable 500 mm (19.6 in.) LRD01–D32 1 LAD7305 100.00
b Part number to be completed by adding coil voltage code. IEC STYLE CONTACTORS
AC 50/60 Hz Jd B E F M Q N
DC J B E F M ... ...
c The time that the LA7D03 can remain energized depends on its rest time; 1 s pulse wth 9 s rest time; 5 s pulse with 30 s rest time; 10 s pulse with
90 s rest time; maximum pulse duration of 20 s with rest time of 300 s. Consumption on inrush and sealed : < 100 VA
d Not available for LRD01-D32, LR3D01-D32.
16
Body/Mounting Collar
For use with Catalog Number $ Price
Contact block or light module ZB5AZ009 5.40
Contact Blocks
ZB5AZ009 Spring terminal connections (1)
Contacts for standard applications
N/O N/C
1 – ZBE1015 18.00
Single
ZBE1015 – 1 ZBE1025 18.00
1 – ZB5AZ1015 24.00
Contact blocks
– 1 ZB5AZ1025 24.00
Single with body/mounting collar
2 – ZB5AZ1035 42.00
– 2 ZB5AZ1045 42.00
Light Modules
Spring terminal connections (1)
Color of
Description Supply voltage Catalog Number $ Price
ZB5AZ1015 light source
White ZBVJ15 57.00
Green ZBVJ35 57.00
12 Vac/Vdc Red ZBVJ45 57.00
Orange ZBVJ55 57.00
Blue ZBVJ65 57.00
White ZBVB15 57.00
Green ZBVB35 57.00
Integral LED
24 Vac/Vdc Red ZBVB45 57.00
(to combine with
heads for integral LED) Orange ZBVB55 57.00
TM
Blue ZBVB65 57.00
White ZBVG15 57.00
Green ZBVG35 57.00
110–120 Vac Red ZBVG45 57.00
Orange ZBVG55 57.00
Blue ZBVG65 57.00
White ZBVM15 57.00
Green ZBVM35 57.00
230–240 Vac Red ZBVM45 57.00
Orange ZBVM55 57.00
Blue ZBVM65 57.00
(1) Additonal blocks cannot be attached to the back of these contact blocks or light modules.
01 - white 3 - maintained
ZB5AD3
03 - green
ZB5AD• 04 - red 3 - momentary to center
ZB5AD5
05 - yellow
3 - momentary from
06 - blue left to center ZB5AD7
(example ZB5AD204) 3 - momentary from
right to center ZB5AD8
2 - momentary from
right to left ZB5AJ4
3 - maintained
ZB5AJ3
3 - momentary to center
ZB5AJ5
ZB5AJ3
3 - momentary from
left to center ZB5AJ7
3 - momentary from
right to center ZB5AJ8
2 - momentary from
ZB5AG6
ZB5AG• right to left
ZB5AG0
ZB5AG3
3 - maintained ZB5AG5
ZB5AG9
ZB5AG09
3 - momentary from
left to center ZB5AG1
3 - momentary
to center ZB5AG7
ZB5AG8
3 - momentary from
right to center
ZB5AG08
85
04/2005 © 1999-2005 Schneider Electric All Rights Reserved
Push Buttons & Operator Interface - XB5 22 mm Double Insulated
Non-Illuminated Operators
White ZB5AA1
ZB5AA0 Black ZB5AA2
Green ZB5AA3
Flush Red ZB5AA4
Yellow ZB5AA5
Blue ZB5AA6
Grey ZB5AA8
White ZB5AA18
Green ZB5AA38
ZB5AA5 Flush with transparent cap,
Red ZB5AA48
for insertion of legend ●
Yellow ZB5AA58
Blue ZB5AA68
White ZB5AL1
Black ZB5AL2
Green ZB5AL3
Extended
Red ZB5AL4
Yellow ZB5AL5
81
04/2005 © 1999-2005 Schneider Electric All Rights Reserved
Push Buttons & Operator Interface - XB5 22 mm Double Insulated
Illuminated Operators
Green ZB5AW333
Red ZB5AW343
Yellow ZB5AW353
ZB5AW313
Blue ZB5AW363
Green ZB5AW533
Red ZB5AW543
Yellow ZB5AW553
Blue ZB5AW563
Red ZB5AA48
Yellow ZB5AA58
Blue ZB5AA68
Red ZB5AW143
Yellow ZB5AW153
Blue ZB5AW163
Red ZB5AW443
Yellow ZB5AW453
Blue ZB5AW463
Clear ZB5AW473
Green ZB5CW333
Red ZB5CW343
Yellow ZB5CW353
ZB5CW113
Blue ZB5CW363
Green ZB5CW133
Red ZB5CW143
Yellow ZB5CW153
Blue ZB5CW163
Only use with light modules for a BA 9s incandescent bulb, neon or LED
Green ZB5AW33
Red ZB5AW34
Yellow ZB5AW35
Blue ZB5AW36
ZB5AW33 Clear ZB5AW37
Green ZB5AW13
Red ZB5AW14
Yellow ZB5AW15
Blue ZB5AW16
Clear ZB5AW17
89
04/2005 © 1999-2005 Schneider Electric All Rights Reserved
Timers RE11/RE48/REXL
Refer to Catalog 9050CT0001
www.schneider-electric.us
Table 23.120: RE11 Modular Timers—17.9 mm wide (Multi-function, dual function or single function)
Functions Supply Voltages Rated Current Catalog Number $ Price
Solid state output
On delay 24–240 Vac/Vdc 0.7A RE11LAMW 54.00
Interval 24–240 Vac 0.7A RE11LHBM 51.00
Off delay with control contact 24–240 Vac 0.7A RE11LCBM 62.00
RE11LHBM Asymmetrical repeat cycle 24–240 Vac 0.7A RE11LLBM 89.00
Multi-function 24–240 Vac 0.7A RE11LMBM 74.00
Timing ranges: 0.1–1 s, 1–10 s, 0.1–10 min, 1–10 min, 0.1–1 hr, 1–10 hr, 10–100 hr
Conforming to standards IEC 61812-1, EN 50081-1/2, EN 50082-1/2, LV directives (73/23/EEC + 93/68/EEC (CE marking) +
EMC directive (89/336/EEC + IEC 60669-2-3)
cULus File: E173076 CNN: NRNT
Approvals File: E173076 CNN: NRNT7
23
Table 23.121: RE48 Panel Mount Timers (For required socket, refer to the catalog section)
RELAYS AND TIMERS
Table 23.122: REXL Miniature Plug-in Timers (For required socket, refer to the catalog section)
4 pole 2 pole
Function Rated
Supply Voltages Current Catalog Number $ Price Current Rated Catalog Number $ Price
Table 23.3: Miniature relays with LED without Push Button (sold in lots of 10)
Number and type of contacts - Thermal current (Ith)
2 C/O -12 A Res. 3 C/O - 10 A Res. 4 C/O - 8 A Res.
Coil Voltage Catalog Number $ Price ea. Catalog Number $ Price ea. Catalog Number $ Price ea.
12 Vdc RXM2AB3JD 6.80 — — RXM4AB3JD 7.50
24 Vdc RXM2AB3BD 6.80 — — RXM4AB3BD 7.50
48 Vdc RXM2AB3ED 6.80 — — RXM4AB3ED 7.50
23
Table 23.4: Miniature relays with low level contacts, Table 23.6: Miniature relays with low level contacts,
without LED (sold in lots of 10) with LED without Push Button
Number and type of contacts - Thermal current (Ith)
(sold in lots of 10)
4 C/O -3 A Res. Number and type of contacts - Thermal current (Ith)
Table 23.8: Miniature relays with LED without Push Button (sold in lots of 100)
Number and type of contacts - Thermal current (Ith)
2 C/O - 12 A Res. 4 C/O - 8 A Res.
$ Price $ Price
Coil Voltage Catalog Number Catalog Number
ea. ea.
24 Vdc RXM2AB3BDTQ 6.80 RXM4AB3BDTQ 7.50
24 Vac RXM2AB3B7TQ 6.80 RXM4AB3B7TQ 7.50
230 Vac RXM2AB3P7TQ 6.80 RXM4AB3P7TQ 7.50
23
Mounting adapter for DIN rail All relays RXZE2DA .84
Mounting adapter for mounting directly to a panel All relays RXZE2FA .57
All relays (sheet of 108 markers) RXZL520 .05
Clip-in markers
All sockets except RXZE2M114 RXZL420 .05
199-DR4 0.05 R
Heavy Duty (1.2)
Symmetrical Rail
35 mm x 15 mm
3.28' (1 m) long 1.38 0.94
Zinc-Plated, Yellow 5 (35.0) (24.0)
Chromated Steel
EN50022 0.09
0.04 (2.4)
(1.0)
DIN #3 0.59
(15.0)
1492-DR7 ➋
Symmetrical Rail 30°
2.80
35 mm x 7.5 mm (71.0)
2.80" (71.0 mm) high 1.87
3.28' (1 m) long (47.5)
0.84
Angled 30° 2 (21.3)
Zinc-Plated,
Chromated Steel 1.13
(28.7)
DIN #3
For mounting rail details, see Cat. No. 199-DR1
➊ Dimensions shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
➋ 0.218" (5.5 mm) x 0.50" (12.7 mm) slotted mounting holes every 3" (76.2 mm) starting 1.69" (42.9 mm) from end.
12-174
Bulletin 1492
Screw Connection Terminal Blocks
Standard Feed-Though Blocks, Continued
Bulletin 1492
Screw Connection Terminal Blocks
Grounding Blocks, Continued
1492-JG6 1492-JG10
10
11
12
13
Visit our website: www.ab.com/catalogs
Preferred availability cat. nos. are printed in bold 12-23
24" 8"
STRAINER T-1
CONTROL PANEL
MAIN FD-MD
T-F6
T-F5
T-F4
G-1
X2
BACKWASH VALVE
OPEN CLOSED
XF HF H1
LP-2 LP-3
MAN-OFF-AUTO OPEN-CLOSE
RCT CR CR CR
INIT
~/+
COM
NO NO NO
S-1 S-2
120V NC NC NC
24" STRAINER
CR-BWO CR-BWC CR-HDP
C-S1
RCT-BW
COIL COIL COIL
RUNNING HIGH DP
~/-
NO
NC
COM COM COM
COIL
NO
NC
LP-1 LP-4
RESET
STOP
STOP START
R B G-2
OL-S1
P-1
14
10
12
13
15
16
17
18
20
19
11
21
P-2
4
3
9
NEMA 4X 304SS WHITE
POWDER COATED ENCLOSURE
PANEL TO BE UL LISTED (usUL, cUL) NOTES:
INDUSTRIAL CONTROL PANEL 1) CONTROL PANEL
UL508A FILE NO E109698 TO BE UL LISTED
DATE
REV DATE PURPOSE: BY CHKD DESIGNED FOR:
ENCLOSURE LAYOUT
JW 2/13 YOUR CUSTOMER WATER FILTRATION SYSTEM
DATE
DRAWN
STRAINER CONTROL PANEL
JW 2/13 THIS DRAWING, AND ALL REPRESENTED DATA, ARE THE PROPERTY
DATE
OF THE NAMED COMPANY IN THE TITLE BLOCK. THIS DRAWING DRAWING SET: SHEET:
CHECKED
SHALL NOT BE REPRODUCED, COPIED, OR DISCLOSED EXCEPT FOR
CK 2/13 MAINTENANCE PURPOSES BY THE USING CUSTOMER.
2013-252 STRAINER PANEL 1 OF 4
480Y/277V-3PH 60 Hz 3.5 FLA GND
SCCR 5KA RMS SYMMETRICAL AT 480V
CAUTION: FOR USE ON A SOLIDLY L1/224 L2/224
GROUNDED WYE SOURCE ONLY
200 250
G
L1 L2 L3
FD-MD
201 251
F1 F2 F3 MAIN FUSED
DISCONNECT
F-1A F-2A F-3A
6A 6A 6A
T1 T2 T3
202 252
203 253
204 254
L1
205 255
L2
L3
L1
206 256
L2
207 257
210 L3 T3 L3 T3 260
212 262
T-1
T-F4 T-F5
H4 H2 H3 H1
213 263 #14 AWG GRN
L2 480V L1
#14 AWG BLK 3A 3A
500VA
TB1 T-F6 TB1 TB1
H 120V N
214 264 H N G
XF
X1 X2
6.25A
#14 AWG RED #14 AWG WHT
217 267
218 268
219 269
220 270
221 271
222 272
223 273
224 274
L1/250 L2/250
H/300 N/300
225 275
DATE
REV DATE PURPOSE: BY CHKD DESIGNED FOR:
POWER SCHEMATIC
JW 2/13 YOUR CUSTOMER WATER FILTRATION SYSTEM
DATE
DRAWN
STRAINER CONTROL PANEL
JW 2/13 THIS DRAWING, AND ALL REPRESENTED DATA, ARE THE PROPERTY
DATE
OF THE NAMED COMPANY IN THE TITLE BLOCK. THIS DRAWING DRAWING SET: SHEET:
CHECKED
SHALL NOT BE REPRODUCED, COPIED, OR DISCLOSED EXCEPT FOR
CK 2/13 MAINTENANCE PURPOSES BY THE USING CUSTOMER.
2013-252 STRAINER PANEL 2 OF 4
H/274 N/274 H/324 N/324
LP-2 LP-2
CR-BWO
3500 3501
300 350 9 5 12 11 X1 R X2 BACKWASH VALVE
350 XO 350
120V OPEN
354
H
H/266 22 21
-PTT/120 OX
301 351
LP-3 LP-3
CR-BWC
H
3520 3521
302 352 9 5 12 11 X1 G X2 BACKWASH VALVE
352 XO 352
120V CLOSED
358
H 352
H/266 22 21
-PTT/120 OX
H
303 353
VLV-BW
N
305 13 14 12 11 X1 R X2 RUNNING 355 F
TB1 CLS
3571
307 357 11 12 11 12 8 3
356 OOX 356 OX CMD
362
TB1 COM OPN TB1 CR-BWC
352 315
3550
308 358 3 C B 5 A1 A2 BACKWASH VALVE
120V STD CLOSED RELAY
309 359 A
CLS
367
STRAINER RUNNING STRAINER HIGH
STATUS CONTACT DP STATUS CONTACT RCT-BW 360
TB1 TB1 S-1
3570 3620
312 15 17 362 31 32 A1 A2 BACKWASH TIMER
OOX 120V STD RCT-BW
SEE NOTE 1 SEE NOTE 1 357
ZELIO TIMER RE11-RLMU
SET FROM FACTORY
313 363 AS INSTANT ON
2 MIN ON TIME
(BACKWASH VALVE OPEN)
30 MIN OFF TIME
(BACKWASH VALVE CLOSED)
314 364
DPS-1
N
CR-BWO TB1 CR-BWC TB1 TB1 TB1
3150 3151 3152 3153 C NO
315 12 8 18 12 8 20 365 9 10
354 358
BACKWASH VALVE BACKWASH VALVE
TB1 OPEN STATUS CONTACT TB1 CLOSED STATUS CONTACT TB1
NC
316 19 21 366 11
LP-4 LP-4
3671
318 368 SP 2 12 11 X1 A X2 HIGH DP
7 PSID XO 120V ALARM
H
H/266 22 21
-PTT/120 OX
319 369
DIFF PRESSURE SWITCH
320 370
321 371
322 372
323 373
NOTES:
1) #16 YELLOW WIRE, THIS WIRING TO
BE PROTECTED BY A 10AMP OR LESS
324 374 FUSE OR CIRCUIT BREAKER. CONTACT
RATING 277VAC 6AMP , 28VDC 8AMP
MAX
H/350 N/350
325 375
DATE
REV DATE PURPOSE: BY CHKD DESIGNED FOR:
CONTROL SCHEMATIC
JW 2/13 YOUR CUSTOMER WATER FILTRATION SYSTEM
DATE
DRAWN
STRAINER CONTROL PANEL
JW 2/13 THIS DRAWING, AND ALL REPRESENTED DATA, ARE THE PROPERTY
DATE
OF THE NAMED COMPANY IN THE TITLE BLOCK. THIS DRAWING DRAWING SET: SHEET:
CHECKED
SHALL NOT BE REPRODUCED, COPIED, OR DISCLOSED EXCEPT FOR
CK 2/13 MAINTENANCE PURPOSES BY THE USING CUSTOMER.
2013-252 STRAINER PANEL 3 OF 4
FIELD CONNECTIONS
TB1
FD-MD TB1 TB1
4 11 14
VLV-BW STRAINER RUNNING
INCOMING POWER
COM OPN STATUS CONTACT
3 E D 10 15
480Y/277V-3PH 60 Hz 3.5 FLA
SCCR 5KA RMS SYMMETRICAL AT 480V
DPS-1
TB1
C NO
F BRAY SERIES 70 9 16
BW VALVE
CLS DIFF PRESSURE SWITCH
1.4A STRAINER HIGH
OPN DP STATUS CONTACT
CAUTION: FOR USE ON A SOLIDLY NC
G
GROUNDED WYE SOURCE ONLY 6 2 1 17
CMD NEU
CLS TB1
C NO
8 3 12 18
T1 480V 3 C B 13 19
002.20A
TB1
T3 5 21
G 7
DATE
REV DATE PURPOSE: BY CHKD DESIGNED FOR:
FIELD CONNECTIONS
JW 2/13 YOUR CUSTOMER WATER FILTRATION SYSTEM
DATE
DRAWN
STRAINER CONTROL PANEL
JW 2/13 THIS DRAWING, AND ALL REPRESENTED DATA, ARE THE PROPERTY
DATE
OF THE NAMED COMPANY IN THE TITLE BLOCK. THIS DRAWING DRAWING SET: SHEET:
CHECKED
SHALL NOT BE REPRODUCED, COPIED, OR DISCLOSED EXCEPT FOR
CK 2/13 MAINTENANCE PURPOSES BY THE USING CUSTOMER.
2013-252 STRAINER PANEL 4 OF 4
Your Company
Project Name: Water Filtration System Job No: 2013-252 Bill of Material
Panel Name: Model A Strainer Control Panel Typical of 1 Panel(s)
Page 1 of 2
Your Company
Project Name: RWater Filtration System Job No: 2013-252 Bill of Material
TB- 20 AB 1492-J10 J 1 TIER,TERMINAL,0.39 IN
TB- 2 AB 1492-JG10 J 1 TIER,TERMINAL,0.39 IN,GROUND
TB- 1 AB 1492-EBJ3 J 1 TIER,END BARRIER,FOR J3/J4/J10
TB- 4 AB 1492-EAJ35 ACC,END ANCHOR
Page 2 of 2