VRV-0421-F

Warning • Ask a qualified installer or contractor to install this product. Do not try to install the product
yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or
explosion.

General Catalogue
• Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
• Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
Notice • About harmonics, since this product is equipped with an inverter, harmonics will be generated. If
local laws require the suppression of harmonics on the building, please take harmonic suppression
measures on the electrical equipment side. Please contact your local sales company for details.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to
install the outdoor unit close to the sea shore, contact your local distributor.

VRV is a trademark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trademark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

Specifications, designs and other content appearing in this brochure are current as of October 2020 but subject to change without notice.
©All rights reserved 10/20 AK

Cooling Only 50 Hz

PCTVMY2009 Cooling Only 50 Hz


Exceeding Boundaries with Contents

Innovative Energy Savings New Products Information


VRV Development History
VRV User Benefits
3
5
7
VRV Overview 9
First launched in Japan in 1982, the Daikin VRV system has been embraced by world markets for over 35 years.
VRV X Series 13
Daikin proudly introduces the advanced VRV system. By combining the technologies of VRV,
VRT and VAV, we have attained both energy savings and comfortable air conditioning. VRV A Series 31
VRV S High Seasonal Efficiency Series 49
VRV IV S Series 63
VRV IV Q Series 71
VRV IV W Series 85
VRV WS Series 99
+ VRT + VAV VRV IV Heat Recovery Hot Water System
Indoor Unit Overview
109
123
VRV Indoor Units Type
VRV
X series / A series FXFSQ-A Round Flow Cassette with Sensing 125
movie FXFQ-A Round Flow Cassette 131
FXZQ-A Compact Multi Flow Cassette 135
FXCQ-A Double Flow Cassette 137
FXKQ-MA Corner Cassette 139
FXDSQ-A 3D Airflow Duct with Sensing 141
FXDQ-PD/ND Slim Duct (Standard) 143
FXDQ-SP Slim Duct (Compact) 144
FXSQ-PA Middle Static Pressure Duct 145
FXMQ-PA Middle-High Static Pressure Duct 147
FXMQ-P High Static Pressure Duct 149
FXUQ-A 4-Way Flow Ceiling Suspended 151
FXHQ-MA/A Ceiling Suspended 152
FXAQ-A Wall Mounted 153
FXLQ-MA Floor Standing 155
FXNQ-MA Concealed Floor Standing 156
Energy savings & comfort FXVQ-N Floor Standing Duct 157
FXB(P)Q-P Clean Room Air Conditioner 159
• Uniting VRV, VRT and VAV technologies
Residential Indoor Units Type
• Quiet operation
FDKS-EA/C(A) Slim Ceiling Concealed Duct 161
FTKS-D/B/F Wall Mounted 162
Design flexibility & easy installation BPMKS-A BP Units 163
Air Handling Unit 164
• Automatic refrigerant charge function
Air Treatment Equipment 165
• Varied lineup of models
Control Systems 181
Precision Piping Method 195
High reliability Option List 199
• Refrigerant cooled PCB Daikin Engineering Supports 213
*VRV is a trademark of Daikin Industries, Ltd.
• Double backup operation
• Heavy anti-corrosion model

1 2
New Products Information
Air Treatment Equipment Page
169

Heat Reclaim Ventilator with DX-coil


VKM-GC Series
Indoor Air Quality (IAQ) improvement VRV Outdoor Units

Page
49 by adding fresh outdoor air
VKM-GC
Heat reclaim ventilator + Heat exchanger
The ideal air conditioning system → Comfortable air supply Indoor Unit Indoor Unit

Presentation Air conditioning and outdoor air


for residential houses, Movie
processing can be accomplished Return
small offices and shops using a single system. Air
Air-Conditioning Air
Air
Supply

Higher energy efficiency Energy savings


VRT Smart Control & comfort
Quiet operation
Stylish Remote Controller Page
181

RSUQ-A
A complete redesigned controller focused to enhance user experience

Design
High performance flexibility of
& reliability installation
BRC1H61W (White) BRC1H61K (Black)

Two attractive colors to match any interior


Extended operation range up to 52°C The high external static pressure of 40 Pa enables
Compact, measures only 85 x 85 mm
High voltage shield PCB installation in small installation spaces where the airflow
Easy setting via Bluetooth App with smartphone
Automatic refrigerant charge function direction needs to be diverted to avoid short circuits.
(for Installer/Facility manager)
Low height casing design
Improved setback function to keep hotel room comfortable
Increased actual piping length up to 120 m

Compact Multi Flow Cassette Page


135 Precision Piping Method Page
195

A revolution in piping works for VRV system!


Quiet, compact, designed for user comfort
Non-brazing work Header Pack Daikin Gas Tight Joint
Compact & Elegant Design Save installation time (Packaged Refnet Headers) (Fire free connection for piping)
Fully-flat integration in standard architectural without special skills
ceiling tiles
Efficiency & Comfort
Two optional intelligent sensors improve
energy efficiency and comfort. BHF-RHP6Z

BDGTA

FXZQ-A Save time using quick flare Hot work permit is not necessary
nut connection

3 4
VRV Development History
*VRV is a trademark of Daikin Industries, Ltd.
To meet the needs of the times, we've been continuously developing
technologies as the leading air conditioning manufacturer in the world. VRV A MAX
Heavy anti-corrosion
VRV IV
Cooling only / Heat pump VRV A series

VRV K Plus series VRV II MA series


VRV IV
Heat Recovery Hot Water System
VRV G series
Heat pump

VRV III-C series VRV III Q series


Low outdoor temp. Replacement use VRV X MAX
VRV-WII area use Heavy anti-corrosion
VRV H series series
VRV D series Made possible to connect VRV L series
Cooling only to BMS using the DIII-NET Adopted the new R-407C
refrigerant

1982 1988 1992 1996 2000 2004 2006 2008 2011 2014 2016 2018 2020

1984 1990 1995 1999 2002 2005 2007 2010 2012 2015 2017 2019

VRV F series VRV G series VRV K series VRV KA series


Cooling only Heat recovery VRV-WIII series VRV III VRV IV S series VRV IV W series VRV X series
The 1st Generation Connection to residential Water cooled system
indoor unit series
VRV II-S series VRV III-S series

VRV S
VRV C series High Seasonal Efficiency Series
Cooling only

VRV II M series VRV III series


Adopted the new R-410A VRV Multi function series VRV IV VRV IV Q series VRV WS series
VRV series released in 1982
refrigerant Cooling/heating, hot water supply Heat recovery Replacement use Water cooled system

The birth of innovative products that changed the history


of air conditioning technology UAE
Saudi Arabia
Bahrain
• 2.5-year development term Jordan
Oman
• Completion of development in May, 1982 Qatar
• Technical award of Japan Society of Refrigerating & Air-conditioning Engineers in 1983
Italy Netherlands
France Poland
Germany Portugal
Spain Finland Middle East North America
Russia Greece Europe
UK Hungary
Asia USA
Austria Ireland Mexico

Expansion of the country of sale Belgium


Bulgaria
Croatia
Romania
Serbia
Slovakia
Japan
China
Canada
Puerto Rico

Sales companies well established


Korea
Cyprus Sweden Africa Taiwan
Czech Switzerland
Lithuania Turkey South America
Macedonia Ukraine
South Africa India Cambodia
Oceania Brazil

in more than 70 countries


Algeria Vietnam Myanmar
Burkina Faso Argentina
Thailand Maldives Australia
Egypt Chile
Indonesia Nepal Fiji
Ivory Coast Colombia
Malaysia Seychelles New Caledonia
Senegal Panama
Singapore Pakistan New Zealand
Sudan Peru
Philippine Sri Lanka Tahiti
5 6
VRV User Benefits
For USERS

Comfortable environment
• VRT Smart operation maintains the indoor temperature BP unit
and ensures a comfortable environment.
For property OWNERS Min.
sound level
22 dB(A)
Residential indoor units
• Residential indoor units can be connected and it is possible
to realise quiet operation.

Energy saving & comfortable environment • By remotely installing an BP unit, the noise
• VRT Smart greatly reduces the energy by of refrigerant passing though the piping can be reduced.
optimising the capacity according to heat load,
especially during low-load operation.

• Comfortable indoor environment is maintained


at the time. For CONSULTANT
and DESIGN OFFICES

Varied lineup of models


• With various types of indoor units available, comfortable airflow is ensured in every space.
Efficient space utilisation Cooling tower VRV
Long piping provides more flexible system design
• When construct a large-scale air conditioning • Maximum equivalent piping length between indoor and outdoor unit is 190 m.
system on a single refrigerant system, space for • Maximum height difference is 90 m.
CADXpress
air conditioning is drastically reduced.
Compatible with engineering software
• Daikin provide the software, the simulation results, and drawing materials to support the building
• Even with a 20-storey building all of the Garage
information modeling (BIM) currently entering the mainstream in construction industries. CADXpress
outdoor units can be installed on the rooftop.
Energy efficient
• Achieves your green building solution by Daikin’s innovative
energy-saving technology.
High reliability Refrigerant
piping
• Refrigerant cooled PCB
Daikin’s unique refrigerant cooling helps maintain
high cooling capacity even during high outdoor Print circuit
temperatures.
For INSTALLERS
board

• Double backup operation


Unit backup & Compressor backup ensure R-410A
continuous operation. • Heavy anti-corrosion model
The heavy anti-corrosion
models can provide Automatic refrigerant charge function
Emergency
operation durable operation at • Automates the charging of proper refrigerant amount to contribute to optimised operation efficiency,
humid and seaside areas. higher quality and easier installation.
Also, outdoor unit can
be installed from 0 m Lightweight and compact large-capacity single units
from coastline. • Easy to install and can be transported in elevators.
Malfunction
Malfunction
Emergency Simple piping, easy wiring
operation • The REFNET piping system and DIII-NET system simplify refrigerant piping and control wiring installation.

7 8
Wide Variety of Series Models From residential houses to large buildings,
and from newly constructed to renovated buildings,

to Supply Total Air Solutions


VRV system meets a wide range of air conditioning needs
and supplies total air solutions.

Page Page
13 71
Heavy anti-corrosion New heights in energy efficiency For quick & high quality replacement use
model
during actual operation
RXUQ-AW The VRV X series features new models specially developed for higher VRV IV Q series, a replacement VRV unit, can be installed using existing refrigerant piping, so renovation
efficiency. All compressors used in outdoor units are new scroll of the air conditioning system can be carried out quickly and smoothly. This minimises inconveniences to
compressors designed to enhance energy efficiency. activities and users in the building.
Lineup
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 Lineup

RXUQ-A Single outdoor units


RQQ-T HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Double outdoor units Standard Type
3-phase 4-wire system, 3-phase 4-wire system,
380-415 V/380 V, 50/60 Hz Triple outdoor units 380-415 V/380 V, 50/60 Hz Space Saving Type

Page Page
31 85
Heavy anti-corrosion Saves space and delivers Water cooled system suitable for tall multi-storied buildings
model
excellent performance
The VRV A series achieves high efficiency in a design that is more Water cooled VRV IV W series utilises water as a heat source. The temperature of heat source water can be
RXQ-AW
compact and lightweight. It also offers comfort, easy installation, and from 10°C to 45°C, and outdoor air temperature does not affect cooling capacity. The outside unit is
high reliability to meet the needs in various buildings. compact and saves space in the machine room.
Lineup
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
RXQ-A Single outdoor units
RWEYQ-T Lineup

3-phase 4-wire system, Double outdoor units


3-phase 4-wire system, HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
380-415 V/380 V, 50/60 Hz Triple outdoor units 380-415 V/380 V, 50/60 Hz Cooling Only

Page Page
49 99
Especially designed for residential houses, Water cooled system suitable for residential houses
small office and shops
New VRV S High Seasonal Efficiency series achieves higher energy efficiency with a variety of function for Water cooled VRV WS series outside units are designed to be compact and lightweight, and single phase
comfort and high performance. A wide range of options for installation location and application are easily power supply enables simplified installation in residential applications.
achieved by the low height casing, long piping length and other features.

Lineup

RSUQ-A HP 4 5 6 7 8 9 RWXQ-A Lineup


Cooling Only
1-phase, 220-240 V/220 V, 50/60Hz HP 4 5 6
4-6 HP: 1-phase, 220-240 V/220-230 V, 50/60 Hz
7-9 HP: 3-phase, 380-415 V/380 V, 50/60 Hz Cooling Only

Page Page
63 109
Especially designed for residential houses, Comfortable air conditioning and energy-efficient
small offices and shops hot water heating
VRV IV S series aims to provide sufficient capacity, along with the compact size required by residential This energy-efficient, multifunction system recovers waste heat generated by air conditioning, as energy to
houses, small offices and shops. Outdoor units are designed to be slim and space saving to suit your needs. heat water. It is suitable for different business applications and provides flexible combination of VRV IV
indoor units achieving comfort and aesthetic.
Lineup
Lineup HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
RXMQ-A/B HP 4 5 6 RWHQ-T / HWHQ30A High-COP Type
4 HP: 1-phase, 220-230 V/220 V, 50/60 Hz Cooling Only Standard Type
3-phase 4-wire system,
5-6 HP: 1-phase, 220-240 V/220-230 V, 50/60 Hz 380-415 V/380 V, 50/60 Hz Space Saving Type

9 10
Wide Range Indoor Unit Lineup
Create Comfortable Airflow
VRV indoor units New lineup Residential indoor units with connection to BP units
20 25 32 40 50 63 71 80 100 125 140 200 250 400 500
Category

25 35 50 60 71
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP
Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500
Capacity Index 25 35 50 60 71
Round Flow Cassette
FXFSQ-AVM
with Sensing
Ceiling Mounted Cassette

FDKS-EAVMB
Round Flow Cassette FXFQ-AVM Slim Ceiling Concealed Duct
(700 mm width type)

Compact Multi FDKS-C(A)VMB


FXZQ-AVM
Flow Cassette (900/1,100 mm width type)

Double Flow Cassette FXCQ-AVM FTKS-DVM

Corner Cassette FXKQ-MAVE


Wall Mounted FTKS-BVMA
3D Airflow Duct with
FXDSQ-AVM
Sensing
FTKS-FVM
FXDQ-PDVE
(with drain pump)
Note: For indoor units connectability, please refer to the indoor unit product lineups under individual outdoor unit series.
FXDQ-PDVET (700 mm width type)
(without drain pump)
Slim Duct (Standard)
Ceiling Concealed Duct

FXDQ-NDVE
(with drain pump)

FXDQ-NDVET (900/1,100 mm width type)


(without drain pump)

Slim Duct (Compact) FXDQ-SPV1

Middle Static
FXSQ-PAVE
Pressure Duct

Middle-High Static Pressure Duct FXMQ-PAVE

High Static Pressure Duct FXMQ-PVM

Outdoor-Air Processing Unit FXMQ-MFV1

4-Way Flow Ceiling


Ceiling Suspended

FXUQ-AVEB
Suspended

FXHQ-MAVE
Ceiling Suspended
FXHQ-AVM

Wall Mounted FXAQ-AVM

Floor Standing FXLQ-MAVE


Floor Standing

Concealed Floor Standing FXNQ-MAVE

FXVQ-NY1
Floor Standing Duct
FXVQ-NY16
(high static pressure type)

FXBQ-PVE
Clean Room Air Conditioner
FXBPQ-PVE

Heat Reclaim Ventilator


VKM-GCVE Airflow rate 500-950 m3/h
with DX-Coil

Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h

Air Handling Unit AHUR 6–120 HP

Note: For indoor units connectability, please refer to the indoor unit product lineups under individual outdoor unit series.

11 12
VRV X Series

Greater energy savings during low-load operation

VRV X Series
Daikin’s VRV X series raised the standard of energy efficiency.
New Heights in Energy Efficiency
The key to innovative
During Actual Operation Cooling Only
energy savings
6 HP –60 HP
(16 kW) (168 kW)
Load factor of 50% or less

Operation period
accounts for 80% of annual
Increased efficiency operation period.
during low-load operation.

* Data source
• Number of properties connected to the Air
Conditioning Network Service System: 42 projects
• Number of outdoor unit systems: 535 systems
• Data collection period: 8:00-18:00, weekdays 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
(excluding public holidays), from July 2015 to June
2016 in office buildings in Singapore. Load factor for the rated capacity

Higher Energy Efficiency Ratio (EER) for 10 HP

9 8.84 8.42
8.19

Cooling Operation EER


Annual power 8 7.37
consumption
7 6.43

Single outdoor units


20%
Lower
6
5
5.69
5.08
4.45
4
RXUQ6-20AYM 3
0
Double outdoor units 30% 40% 50% 60% 70% 80% 90% 100% Load
* Simulation conditions:
RXUQ12-40AMYM • Location: Bangkok, Thailand
Conventional model New model
• System: Outdoor unit (10 HP) x 1
Indoor unit (2 HP, Round Flow with Sensing type) x 5
Triple outdoor units • Operation time: 8:00-20:00 5 days/week
RXUQ18-20AM1YM • Outdoor units: New model: RXUQ10A (VRV X series)

RXUQ42-60AMYM Conventional model: RXQ10T (VRV IV)

* Cooling operation conditions:


• Indoor temperature of 27ºCDB, 19ºCWB, and outdoor temperature of 35ºCDB.

13 14
VRV X Series
Advanced Technologies
Advanced technologies for greater energy savings

VRV X Series
+ VRT + VAV
By uniting advanced software and hardware technologies for greater energy savings during actual
operation and combining the technologies of VRV, VRT and VAV, we have attained both energy savings
and comfortable air conditioning.

Software technology VRT Smart Control Hardware technology New Scroll Compressor
Fully Automatic Energy-saving Refrigerant Control
VRT Smart New Scroll
Control Function Compressor
movie movie

Optimally supply only for the needed capacity of indoor units Refrigerant leakage is minimized during low-load operation
• Reduces compressor load and minimizes operation loss so it is energy saving • Refrigerant leakage is
New compressor
• Controls capacity according to load to ensure a constant room temperature for greater comfort. minimized by a back pressure
Conventional compressor
control mechanism that
increases the efficiency

Compressor efficiency
during low-load operation.
Room temperature and
set temperature
The back pressure control mecha-
nism increases the efficiency during
low-load operation.

Coordinated control * Graph shown above is for illustration purposes only. Load factor

Back pressure control mechanism

Calculate
Determine the target Compressor New intermediate pressure mechanism
・Indoor airflow rate
refrigerant temperature speed control
・Target refrigerant temperature The pressure on the orbiting scroll is optimised
according to operating conditions. As a result,
the orbiting scroll has been stabilised to
* For the classification of indoor units (VRT smart control and VRT control), refer to the indoor unit lineup.
increase efficiency during low-load operation.

Intermediate pressure
adjustment port

15 16
VRV X Series
Advanced Technologies
Automatic refrigerant charge function

VRV X Series
Contribute to optimised operation efficiency, higher quality and easier installation.
Advanced oil temperature control
Standby power needed for preheating refrigerator oil was reduced up to 65.4% Optimised operation efficiency
to save energy when the air conditioner is stopped.
* Operation calculation conditions: VRV X series 14 HP
65.4% Reduction
This function prevents a capacity shortage
or energy loss due to excessive
Automatic Refrigerant
Charge Function
movie
Location: Singapore
Operation time: 08:00–18:00 on weekdays or insufficient refrigerant.
Optimised Operation
Cooling

Higher efficiency is provided during rated operation Efficiency capacity

EER at 100% operation load


VRV IV VRV X SERIES
4.95
5
4.65
4.45
4.41 4.32 4.29 4.23
Cooling operation EER

4.07 3.95 3.91


4
3.80 3.78
3.74
Insufficient Excessive
3.46 refrigerant charge refrigerant charge
3.25
3.11
3
Optimal refrigerant Refrigerant
amount charge amount

0
6 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP

Higher quality and easier installation


Cooling operation conditions : Indoor temperature of 27°CDB 19°CWB, and outdoor temperature of 35°CDB.

The automatic refrigerant charge function automates the charging of the proper
Extended operation range up to 49°C refrigerant amount and the closing of shut-off valves by simply pressing a switch after pre-charging.

Cooling Outdoor temperature (°CDB)

10 20 30 40 49°C 1 Calculation of necessary refrigerant 2 Pre-charge of refrigerant 3 Start of automatic refrigerant


amount from design drawing charge operation

Note: When outdoor temperature falls below 10℃, the thermostat shuts OFF,
the outdoor unit stops, and operation switches from cooling to fan
VRV X Series
operation.
Automatic Refrigerant Charge

R-410A

I-demand function Total of 11 levels


Less Power consumption More

100%
Peak power cut-off can be accomplished according
to each user situation. Can be set in
70% 5% increments
* Set on the PCB of the outdoor unit.

50% ・Automatic completion by proper refrigerant amount


40% ・Monitoring refrigerant charging is unnecessary
・No recalculation of charge amounts due to minor design changes locally

0%
Time * There are conditions in the range of ambient temperature in which the automatic refrigerant charge can be used. Refer to the installation manual for details.
* When set to 70% demand * The refrigerant amount that can be automatically charged may differ from the additional refrigerant amount that is provided from calculations, but there are
no problems in performance and quality.

High external static pressure


VRV X series outdoor unit has been achieved high external static pressure up to 78.4 Pa.
17 18
VRV X Series
Comfort & Reliability
Comfort

VRV X Series
Nighttime quiet operation function Load % Outer rotor DC motor (ODM) Conventional Motor
ODM(Outer Type) UNIQUE

Operating sound dB(A) (Inner Type)


The nighttime quiet operation function Only Daikin has adapted an ODM HIGH TORQUE
Rotor
Rotor
automatically suppresses the nighttime with the feature of stable rotation and with low energy
operating sound by reducing operation Peak in the outdoor volumetric efficiency. F

capacity to maintain the quiet environ- 100% temperature F


MORE efficient
ment of the neighborhood.
Three selectable modes are available 8 hrs*1 10 hrs*2
depending on the required level. 50%

Function of information display by luminous digital tube 7-segment digital display

VRV X series utilises a bright 7-segment digital display to


56 dB(A)
convey operational status and facilitate simple installation
Night and after-sales service.
*1. Initial setting is 8 hours. Can be selected from 6, 8 and 10 hours.
*2. Initial setting is 9 hours. Can be selected from 8, 9 and 10 hours.
quiet mode
*3. In case of 10 HP outdoor unit. Displays system operation
information directly
Notes: • This function is available in setting at site.
• The operating sound in quiet operation mode is the actual
Min. 40 dB(A)*3
40 dB(A)
value measured by our company.
• The relationship of outdoor temperature (load) and time SMT* packaging technology Computer control board surface adopting SMT packaging technology
shown above is just an example. 8:00 12:00 16:00 20:00 0:00 4:00 8:00
Night mode STARTS Night mode ENDS • Improves the anti-clutter performance. SMT packaging material
• Protects your computer boards from the adverse
effects of sandy climates and humid weather.
*SMT: Surface mounted technology
Computer control board

Reliable and stable technology


Automatic sequencing operation
High reliability at high ambient temperature Priority Priority
Priority 1 2 3 3 1 2 2 3 1
PCB

Power Module Automatic Automatic


Heat Refrigerant Jacket sequencing sequencing
Refrigerant
Refrigerant Stage 1 Stage 2 Stage 3

Using refrigerant to cool the inverter power Double backup operation functions
module helps minimise the size of the electronic Unit backup operation function Compressor backup operation function
components, and this results in reduction of
Malfunction Emergency Emergency
airflow resistance and high efficiency of the heat operation operation
exchanger. Malfunction
* For single outdoor unit
system RXUQ14-20AYM
models. On-site settings are
Control board failure ratio at stable operation is reduced. required using the PCB of the
outdoor unit.

This enables Ease of maintenance


Can provide maintenance
• Suitability for high ambient temperatures feature* without shutting down
• Miniaturization of electronic components the whole VRV system.

* Field setting is required. This feature does not apply


to residential indoor unit connection. For more
information, please contact Daikin sales office. Area A Area B Area C

19 20
VRV X Series
Flexible System Design
More options for installation location

VRV X Series
Long piping length
The long piping length provides more design flexibility, which can match even large-sized buildings.

Installation for VRV indoor units only Installation for mixed combination of VRV and residential indoor units
Between the outdoor branch
and the last outdoor unit
Max. total
piping length 1000 m Max. 13 m Max. total
Between the outdoor units piping length 250 m
VRV: VRV indoor unit
Max. 5 m RA: Residential indoor unit

Max. actual
piping length
Between BP unit
Max. level difference Max. actual Max. level difference between the and indoor unit
165 m between the outdoor units piping length outdoor unit and the BP units
and the indoor units Max. 15 m
Max. equivalent *2 100 m 40 m BP unit
piping length 90 m
Max. equivalent
piping length
190 m Max. level
120 m difference
between 15 m
RA RA
Max. level difference
Max. level difference
Between the first indoor between the indoor units BP unit BP unit between the outdoor unit
branch and the farthest and the indoor unit
indoor unit 30 m 50 m
*1 Max. level difference
Max. 90 m Between the first indoor between the indoor
RA units
branch and the farthest
VRV indoor unit RA
Max. level difference 15 m
*1 between the BP unit
Max. 50 m and the indoor unit
Note: The above is just a schematic diagram.
5m
Actual piping length (Equivalent) 165 m (190 m)
Total piping length 1000 m
Maximum allowable piping length VRV
Between the first indoor branch and the farthest indoor unit 90 m*1
Note: The above is just a schematic diagram.
Between the outdoor branch and the last outdoor unit (Equivalent) 10 m (13 m)
Between the outdoor units (Multiple use) 5m
Maximum allowable level difference Between the indoor units 30 m
Between the outdoor units and the indoor units 90 m*2
When a mixed combination of VRV and residential indoor units is connected
*1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. The VRV X series is easy to extend to 90 m by lessening
the conditions from conventional VRV IV models. Be sure to refer to the Engineering Data Book for details of these conditions and requirements.
Actual piping length (Equivalent) 100 m (120 m) *1. If the piping length between the first
*2. When level differences are 50 m or more, the diameter of the main liquid piping size must be increased. If the outdoor unit is above the indoor unit, a dedicated setting
indoor branch and BP unit or VRV
on the outdoor unit is required. Refer to the Engineering Data Book and contact your local dealer for more information.
Total piping length 250 m indoor unit is over 20 m, it is necessary
to increase the gas and liquid piping
Between BP unit If indoor unit capacity index < 60. 2 m–15 m size between the first indoor branch
Maximum allowable and indoor unit and BP unit or VRV indoor unit. If the
piping length If indoor unit capacity index is 60 and 71. 2 m–8 m
piping diameter of the sized up piping
Between the first indoor branch and the farthest BP unit or exceeds the diameter of the piping
50 m*1
Connection ratio Conditions of VRV indoor unit connection capacity
Minimum allowable
between the first indoor branch and the farthest VRV indoor unit before the first indoor branch kit, then
the latter also requires a liquid piping
and gas piping size up. Please refer to
Between outdoor unit and the first indoor branch 5m Engineering Data Book for details.
Connection capacity piping length
FXSQ FXAQ
at maximum is 200%. Applicable Other VRV indoor Between the indoor units 15 m
VRV indoor units unit models*1 Between BP units 15 m *When a mixed combination of VRV and
FXMQ-PA
residential indoor units is connected or
Connection ratio FXDQ FXB(P)Q
Maximum allowable Between the outdoor unit If the outdoor unit is above. 50 m when only residential indoor units are
level difference and the indoor unit If the outdoor unit is below. 40 m connected, connection ratio must be

50%– 200% 200%


50% to 130%. Refer to page 25 for

200%
Single outdoor units Between the outdoor unit and the BP unit 40 m outdoor unit combination details.
Double outdoor units 160% Between the BP unit and the indoor unit 5m

Triple outdoor units 130%


*1 For the FXF(S)Q25 and FXVQ models, maximum connection ratio is 130% for the entire range of
outdoor units.
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced
Total capacity index of the indoor units in all the indoor units.
Connection ratio = *Refer to page 25 for outdoor unit combination details.
Capacity index of the outdoor units

21 22
VRV X Series
Anti-corrosion Technology
Heavy anti-corrosion model

VRV X Series
Maximize lifespan The new model resists corrosion by salt,
maintains performance,
A third party tested the corrosion resistance and greatly reduces life cycle costs.
(ISO 9227: salt spray tests) of the reinforced fins
and casing for ISO 12944: 2018 Category C5 and •Total life cycle cost
RXUQ6-20AYMW ion
ros
RXUQ12-60AM(1)YMW
confirmed them to be at very high (VH) levels. Cor eriod
p
ISO 12944-6:2018 : Paints and varnishes – Corrosion protection
of steel structures by protective paint systems n
Built for sio
Category C5 : Industrial areas with high humidity and o rro iod
Seaside aggressive atmosphere and coastal areas
with high salinity
C e
p
r

Level VH : Very high (equivalent to an expected life of


25 years *)
ISO 9227 : Corrosion test in artificial atmospheres-Salt Initial cost Replacement Time
spray tests
Maximize anti-corrosion and performance * This number of years is not the warranty period of the product.
Product life depends on installation location and operating conditions.
Standard model

Outer casing 4-layer coating


Multi coating for extreme durability Top clear special coating Built for seaside
Top coat metallic special coating
The hot-dip Zinc-Aluminum-Magnesium alloy Powder middle coating Previous model: Anti-corrosion : Heavy Anti-corrosion
coated sheet is optimised for even greater Primer base coating
durability with an additional four-layer coating Hot-dip zinc-aluminum-magnesium alloy coated steel sheet Building
Can be installed
Building
combination. right by the sea

Sea wind outdoor unit Sea wind outdoor unit


Anti-corrosion verification by accelerated test Salt Spray Test CASS Test

Although the previous anti-corrosion model is Previous model VRV X MAX Previous model VRV X MAX
rusted, the VRV X MAX outer casing shows no
Sea Sea
signs of corrosion in either test. 0 – 1000m
* The cross cut was made in order to simulate a severe case of coating damage
Must be installed at least 300 m away from the sea in a Must be installed where the unit does not get into contact
and corrosion (not from regular usage).
location not in direct contact with sea wind. with seawater.

: Corrosion : No corrosion : Corrosion : No corrosion 300 - 1,000 m 0 – 1,000 m

Standard model
CASS Test
VRV X MAX
Specifications of anti-corrosion model
Heat exchanger (Fin)
Item Parts Standard model
Anti-corrosion technology
Hot-dip zinc-aluminum-magnesium alloy-coated steel sheet + Primer
The aluminum fins on VRV X MAX are 1 Sheet metal casing Outer casing Hot dip zinc coated sheet + powder coating base coating + Powder middle coating + Top coat metallic special
coating (metallic brown) + Top clear special coating
manufactured with thicker anti-corrosion layer
2 Discharge grille • Protection net Low Density Polyethylene (LDPE) coating
including an additional two-layer coating.
: Corrosion : No corrosion 3 Fasteners SWCH + zinc-nickel plating SUS410 + zinc-nickel plating

Corrosion resistance coating* 4 Heat exchanger Copper tube + Standard aluminum fin Copper tube + Anti-corrosion aluminum fin
Aluminum fin + High corrosion resistance aluminum fin +
Primer base coating*
High performance technology 5 Aluminum fin Aluminum fin + Hydrophilic anti-corrosion Primer base coating (outside area only) + Corrosion resistance coating
High corrosion resistance aluminium fin (outside area only)

New aluminum fins are 21% thicker Aluminium fin


Hot-dip zinc-aluminum-magnesium
* outside area only 6 Heat exchanger end plate Hot dip zinc coated sheet + corrosion resistance polyurethane coating
to maintain performance. alloy-coated steel sheet without coating

Fan motor stand • Electric box •


Achieves both anti-corrosion 7 Inner casing sheet metal
Galvanized iron sheet Hot dip zinc coated sheet + corrosion resistance polyurethane coating
Automated fin coating line and high efficiency
8 Fan • Fan motor Resin fan + resin casing motor
To prevent differences in coating thickness caused by manual application, the additional fin coatings are 9 Pressure vessel (oil separator) Hot rolled sheet steel + painting Hot rolled sheet steel + Double rust inhibitor
coating with additional touch-up paint
performed on the latest automated assembly line, maintaining high precision and quality.
10 Printed circuit board Both side resin coating Expanded both side resin coating

23 24
VRV X Series
Outdoor Unit Lineup
VRV X Series

VRV X Series
The outdoor unit capacity is up to 60 HP (168 kW) in increments of 2 HP.

Lineup For mixed combination of VRV and residential indoor units


HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 Total capacity index of connectable indoor units*2
Capacity Maximum number of
Model name* 1
kW HP index Combination (%)*2
Single outdoor units connectable indoor units
50% 100% 130%
VRV X
Double outdoor units RXUQ6AYM(W) 16.0 6 150 75 150 195 9
SERIES
RXUQ8AYM(W) 22.4 8 200 100 200 260 13
Triple outdoor units
RXUQ10AYM(W) 28.0 10 250 125 250 325 16
RXUQ12AYM(W) 33.5 12 300 150 300 390 19
RXUQ14AYM(W) 40.0 14 350 175 350 455 22

Outdoor unit combinations RXUQ16AYM(W)


RXUQ18AYM(W)
45.0
50.0
16
18
400
450
200
225
400
450
520
585
26
29
RXUQ20AYM(W) 56.0 20 500 250 500 650 32
Notes: *1. Only single outdoor unit (RXUQ6-20AYM(W)) can be connected.
For connection of VRV indoor units only *2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.

Capacity Outdoor unit multi Total capacity index of Maximum number of


HP kW Model name Combination
index connection piping kit*1 connectable indoor units*2 connectable indoor units*2
6 16.0 150 RXUQ6A RXUQ6A – 75 to 195 (300) 9 (15)
8 22.4 200 RXUQ8A RXUQ8A – 100 to 260 (400) 13 (20)
10 28.0 250 RXUQ10A RXUQ10A – 125 to 325 (500) 16 (25)
12 33.5 300 RXUQ12A RXUQ12A – 150 to 390 (600) 19 (30)
14 40.0 350 RXUQ14A RXUQ14A – 175 to 455 (700) 22 (35)
16 45.0 400 RXUQ16A RXUQ16A – 200 to 520 (800) 26 (40)
18 50.0 450 RXUQ18A RXUQ18A – 225 to 585 (900) 29 (45)
20 56.0 500 RXUQ20A RXUQ20A – 250 to 650 (1,000) 32 (50)
12 32.0 300 RXUQ12AM RXUQ6A + RXUQ6A 150 to 390 (480) 19 (24)
14 38.4 350 RXUQ14AM RXUQ6A + RXUQ8A 175 to 455 (560) 22 (28)
16 44.8 400 RXUQ16AM RXUQ8A + RXUQ8A BHFP22P100 200 to 520 (640) 26 (32)
18 50.4 450 RXUQ18AM RXUQ8A + RXUQ10A 225 to 585 (720) 29 (36)
20 55.9 500 RXUQ20AM RXUQ8A + RXUQ12A 250 to 650 (800) 32 (40)
18 48.0 450 RXUQ18AM1 RXUQ6A × 3 225 to 585 (585) 29 (29)
BHFP22P151
20 54.4 500 RXUQ20AM1 RXUQ6A × 2 + RXUQ8A 250 to 650 (650) 32 (32)
22 61.5 550 RXUQ22AM RXUQ10A + RXUQ12A 275 to 715 (880) 35 (44)
24 67.0 600 RXUQ24AM RXUQ12A × 2 300 to 780 (960) 39 (48)
26 73.5 650 RXUQ26AM RXUQ12A + RXUQ14A 325 to 845 (1,040) 42 (52)
28 78.5 700 RXUQ28AM RXUQ12A + RXUQ16A 350 to 910 (1,120) 45 (56)
30 83.5 750 RXUQ30AM RXUQ12A + RXUQ18A 375 to 975 (1,200) 48 (60)
BHFP22P100
32 89.5 800 RXUQ32AM RXUQ12A + RXUQ20A 400 to 1,040 (1,280) 52 (64)
34 96.0 850 RXUQ34AM RXUQ14A + RXUQ20A 425 to 1,105 (1,360) 55 (64)
36 101 900 RXUQ36AM RXUQ16A + RXUQ20A 450 to 1,170 (1,440) 58 (64)
38 106 950 RXUQ38AM RXUQ18A + RXUQ20A 475 to 1,235 (1,520) 61 (64)
40 112 1,000 RXUQ40AM RXUQ20A × 2 500 to 1,300 (1,600) 64 (64)
42 117 1,050 RXUQ42AM RXUQ12A × 2 + RXUQ18A 525 to 1,365 (1,365)
44 123 1,100 RXUQ44AM RXUQ12A × 2 + RXUQ20A 550 to 1,430 (1,430)
46 130 1,150 RXUQ46AM RXUQ12A + RXUQ14A + RXUQ20A 575 to 1,495 (1,495)
48 135 1,200 RXUQ48AM RXUQ12A + RXUQ16A+ RXUQ20A 600 to 1,560 (1,560)
50 140 1,250 RXUQ50AM RXUQ12A + RXUQ18A + RXUQ20A 625 to 1,625 (1,625)
BHFP22P151 64 (64)
52 146 1,300 RXUQ52AM RXUQ12A + RXUQ20A × 2 650 to 1,690 (1,690)
54 152 1,350 RXUQ54AM RXUQ14A + RXUQ20A × 2 675 to 1,755 (1,755)
56 157 1,400 RXUQ56AM RXUQ16A + RXUQ20A × 2 700 to 1,820 (1,820)
58 162 1,450 RXUQ58AM RXUQ18A + RXUQ20A × 2 725 to 1,885 (1,885)
60 168 1,500 RXUQ60AM RXUQ20A × 3 750 to 1,950 (1,950)
Notes: *1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
*2. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double outdoor units, and 130%
for triple outdoor units. Refer to page 21 for notes on connection capacity of indoor units.

25 26
VRV X Series
Indoor Unit Lineup
Enhanced range of choices

VRV X Series
Indoor units subject to Indoor units subject to
VRV indoor units New lineup VRT
smart VRT smart control VRT VRT control Residential indoor units with connection to BP units
20 25 32 40 50 63 71 80 100 125 140 200 250 400 500 25 35 50 60 71
Category

Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 Capacity Index 25 35 50 60 71
Round Flow Cassette VRT
FXFSQ-AVM smart
with Sensing FDKS-EAVMB VRT
Ceiling Mounted Cassette

(700 mm width type)


Slim Ceiling Concealed Duct
Round Flow Cassette FXFQ-AVM VRT
smart
FDKS-C(A)VMB VRT
(900/1,100 mm width type)
Compact Multi VRT
Flow Cassette FXZQ-AVM smart
FTKS-DVM VRT

Double Flow Cassette FXCQ-AVM VRT


smart

Wall Mounted FTKS-BVMA VRT


Corner Cassette FXKQ-MAVE VRT

3D Airflow Duct with FTKS-FVM VRT


FXDSQ-AVM VRT
Sensing
FXDQ-PDVE VRT Note: BP units are necessary for residential indoor units. Only single outdoor unit (RXUQ6-20AYM(W)) can be connected.
(with drain pump) smart
FXDQ-PDVET VRT
(without drain pump) smart (700 mm width type)
Slim Duct (Standard)
FXDQ-NDVE VRV indoor units combine with residential indoor units, all in one system.
Ceiling Concealed Duct

VRT
(with drain pump) smart
FXDQ-NDVET
(without drain pump)
VRT
smart (900/1,100
width type )
mm
VRV indoor unit only system

Slim Duct (Compact) FXDQ-SPV1 VRT

Middle Static VRT


FXSQ-PAVE smart
Pressure Duct

Middle-High Static Pressure Duct FXMQ-PAVE VRT


smart
VRV indoor units only
High Static Pressure Duct FXMQ-PVM VRT Max. • If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control.
smart
64 indoor
units • If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, VRT smart control and VRT control are disabled.
Outdoor-Air Processing Unit FXMQ-MFV1

4-Way Flow Ceiling Residential indoor unit and VRV indoor unit mix system
Ceiling Suspended

FXUQ-AVEB VRT
Suspended

FXHQ-MAVE VRT
Ceiling Suspended BP unit
FXHQ-AVM VRT

Wall Mounted FXAQ-AVM VRT


smart
Residential indoor units VRV indoor units
Floor Standing FXLQ-MAVE VRT Max. • BP units are necessary for residential indoor units. Only single outdoor unit (RXUQ6-20AYM(W)) can be connected.
32 indoor
Floor Standing

units • If a system has both residential indoor units and VRV indoor units, the system is operated under VRT control.
Concealed Floor Standing FXNQ-MAVE VRT

FXVQ-NY1 VRT Residential indoor unit only system


Floor Standing Duct
FXVQ-NY16 VRT
(high static pressure type)

FXBQ-PVE VRT
BP unit BP unit
Clean Room Air Conditioner
FXBPQ-PVE VRT

Heat Reclaim Ventilator


with DX-Coil
VKM-GCVE Airflow rate 500-950 m3/h Residential indoor units only
Max. • BP units are necessary for residential indoor units. Only single outdoor unit (RXUQ6-20AYM(W)) can be connected.
Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h
32 indoor
units • If a system has only residential indoor units, the system is operated under VRT control.

Air Handling Unit AHUR 6–120 HP

27 28
VRV X Series
Outdoor Units
VRV X Series

VRV X Series
Specifications

MODEL RXUQ6AYM(W) RXUQ8AYM(W) RXUQ10AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ12AMYM(W) RXUQ14AMYM(W) RXUQ16AMYM(W) RXUQ18AMYM(W) RXUQ20AMYM(W) RXUQ18AM1YM(W) RXUQ20AM1YM(W) RXUQ22AMYM(W) RXUQ24AMYM(W) RXUQ26AMYM(W)
— — — — — — — — RXUQ6AYM(W) RXUQ6AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ6AYM(W) RXUQ6AYM(W) RXUQ10AYM(W) RXUQ12AYM(W) RXUQ12AYM(W)
Combination units — — — — — — — — RXUQ6AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ10AYM(W) RXUQ12AYM(W) RXUQ6AYM(W) RXUQ6AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ14AYM(W)
— — — — — — — — — — — — — RXUQ6AYM(W) RXUQ8AYM(W) — — —
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 54,600 76,400 95,500 114,000 136,000 154,000 171,000 191,000 109,000 131,000 153,000 172,000 191,000 164,000 186,000 210,000 229,000 251,000
Cooling capacity
kW 16.0 22.4 28.0 33.5 40.0 45.0 50.0 56.0 32.0 38.4 44.8 50.4 55.9 48.0 54.4 61.5 67.0 73.5
Power consumption kW 3.23 4.82 6.29 7.81 9.46 11.4 12.8 14.8 6.46 8.05 9.64 11.1 12.6 9.69 11.3 14.1 15.6 17.3
Capacity control % 23-100 19-100 13-100 12-100 11-100 9-100 7-100 11-100 10-100 9-100 8-100 7-100 8-100 7-100 6-100
Casing colour Ivory white (5Y7.5/1) (Metallic brown 1
) Ivory white (5Y7.5/1) (Metallic brown 1
)
Type Hermetically sealed scroll type Hermetically sealed scroll type
Compressor
Motor output kW 2.4×1 3.4×1 4.2×1 5.2×1 (3.4×1)+(2.9×1) (3.4×1)+(3.9×1) (3.7×1)+(4.3×1) (4.9×1)+(4.2×1) (2.4×1)+(2.4×1) (2.4×1)+(3.4×1) (3.4×1)+(3.4×1) (3.4×1)+(4.2×1) (3.4×1)+(5.2×1) (2.4×1)+(2.4×1)+(2.4×1) (2.4×1)+(2.4×1)+(3.4×1) (4.2×1)+(5.2×1) (5.2×1)+(5.2×1) (5.2×1)+(3.4×1)+(2.9×1)
Airflow rate m3/min 119 178 191 218 268 297 119+119 119+178 178+178 178+191 119+119+119 119+119+178 178+191 191+191 191+218
Dimensions (H×W×D) mm 1,657×930×765 1,657×1,240×765 (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×1,240×765) (1,657×930×765)+(1,657×930×765)+(1,657×930×765) (1,657×1,240×765)+(1,657×1,240×765)
Machine weight kg 185 (195 1
) 215 (235 1
) 275 (295 1
) 291 (316 1
) 185+185 (195+195 1 ) 185+215 (195+235 1 ) 185+185+185 (195+195+195 1 ) 215+215 (235+235 1 ) 215+275 (235+295 1)
Sound level dB(A) 54 56 58 59 62 65 57 58 59 60 59 60 61 62
Operation range °CDB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 6.4 6.6 8.3 8.5 9.7 9.8 11.7 6.4+6.4 6.4+6.6 6.6+6.6 6.6+8.3 6.6+8.5 6.4+6.4+6.4 6.4+6.4+6.6 8.3+8.5 8.5+8.5 8.5+9.7
Piping Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing) 12.7 (Brazing) 15.9 (Brazing) 19.1 (Brazing)
connections Gas mm 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 34.9 (Brazing)

MODEL RXUQ28AMYM(W) RXUQ30AMYM(W) RXUQ32AMYM(W) RXUQ34AMYM(W) RXUQ36AMYM(W) RXUQ38AMYM(W) RXUQ40AMYM(W) RXUQ42AMYM(W) RXUQ44AMYM(W) RXUQ46AMYM(W) RXUQ48AMYM(W) RXUQ50AMYM(W) RXUQ52AMYM(W) RXUQ54AMYM(W) RXUQ56AMYM(W) RXUQ58AMYM(W) RXUQ60AMYM(W)
RXUQ12AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W)
Combination units RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W)
— — — — — — — RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W)
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 268,000 285,000 305,000 328,000 345,000 362,000 382,000 399,000 420,000 444,000 461,000 478,000 498,000 519,000 536,000 553,000 573,000
Cooling capacity
kW 78.5 83.5 89.5 96.0 101 106 112 117 123 130 135 140 146 152 157 162 168
Power consumption kW 19.2 20.6 22.6 24.3 26.2 27.6 29.6 28.4 30.4 32.1 34.0 35.4 37.4 39.1 41.0 42.4 44.4
Capacity control % 5-100 4-100 4-100 3-100 2-100
Casing colour Ivory white (5Y7.5/1) (Metallic brown 1 ) Ivory white (5Y7.5/1) (Metallic brown 1
)
Type Hermetically sealed scroll type Hermetically sealed scroll type
Compressor (3.4×1)+(2.9×1)+ (3.4×1)+(3.9×1)+ (3.7×1)+(4.3×1)+ (4.9×1)+(4.2×1)+ (5.2×1)+(5.2×1)+ (5.2×1)+(5.2×1)+ (5.2×1)+(3.4×1)+(2.9×1)+ (5.2×1)+(3.4×1)+(3.9×1)+ (5.2×1)+(3.7×1)+(4.3×1)+ (5.2×1)+(4.9×1)+(4.2×1)+ (3.4×1)+(2.9×1)+(4.9×1)+ (3.4×1)+(3.9×1)+(4.9×1)+ (3.7×1)+(4.3×1)+(4.9×1)+ (4.9×1)+(4.2×1)+(4.9×1)+
Motor output kW (5.2×1)+(3.4×1)+(3.9×1) (5.2×1)+(3.7×1)+(4.3×1) (5.2×1)+(4.9×1)+(4.2×1)
(4.9×1)+(4.2×1) (4.9×1)+(4.2×1) (4.9×1)+(4.2×1) (4.9×1)+(4.2×1) (3.7×1)+(4.3×1) (4.9×1)+(4.2×1) (4.9×1)+(4.2×1) (4.9×1)+(4.2×1) (4.9×1)+(4.2×1) (4.9×1)+(4.2×1) (4.2×1)+(4.9×1)+(4.2×1) (4.2×1)+(4.9×1)+(4.2×1) (4.2×1)+(4.9×1)+(4.2×1) (4.2×1)+(4.9×1)+(4.2×1)
Airflow rate m3/min 191+218 191+268 191+297 218+297 268+297 297+297 191+191+268 191+191+297 191+218+297 191+268+297 191+297+297 218+297+297 268+297+297 297+297+297
Dimensions (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Machine weight kg 215+275 (235+295 1) 215+291 (235+316 1
) 275+291 (295+316 )
1
291+291 (316+316 1
) 215+215+291 (235+235+316 1
) 215+275+291 (235+295+316 1
) 215+291+291 (235+316+316 1
) 275+291+291 (295+316+316 1
) 291+291+291 (316+316+316 1
)
Sound level dB(A) 62 63 66 67 68 65 66 67 68 69 70
Operation range °CDB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 8.5+9.8 8.5+11.7 9.7+11.7 9.8+11.7 11.7+11.7 8.5+8.5+11.7 8.5+9.7+11.7 8.5+9.8+11.7 8.5+11.7+11.7 9.7+11.7+11.7 9.8+11.7+11.7 11.7+11.7+11.7
Piping Liquid mm 19.1 (Brazing) 19.1 (Brazing)
connections Gas mm 34.9 (Brazing) 41.3 (Brazing) 41.3 (Brazing)
Notes: Specifications are based on the following conditions; Note: 1. Models with (W) are the outdoor units with anti-corrosion specifications. For details, refer to pages 23 - 24 for more information.
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.

29 30
VRV A Series

Greater energy savings during low-load operation


Daikin’s VRV A series raised the standard of energy efficiency.
Saves Space and

VRV A Series
The key to innovative
Delivers Excellent Performance Cooling Only
energy savings
6 HP –60 HP
(16 kW) (168 kW)
Load factor of 50% or less

Operation period
accounts for 80% of annual
Increased efficiency operation period.
during low-load operation.

* Data source 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
• Number of properties connected to the Air
Conditioning Network Service System: 42 projects Load factor for the rated capacity
• Number of outdoor unit systems: 535 systems
• Data collection period: 8:00-18:00, weekdays
(excluding public holidays), from July 2015 to June
2016 in office buildings in Singapore.

Higher Energy Efficiency Ratio (EER) for 10 HP

9
8.16

Cooling Operation EER


Annual power 8 7.78 7.57
consumption 6.77
7

14%
5.92
6
5.23
5 4.68
Single Outdoor units Lower 4.09
4
RXQ6-20AYM 3
0
30% 40% 50% 60% 70% 80% 90% 100% Load
Double Outdoor units * Simulation conditions:
RXQ18-40AMYM • Location: Bangkok, Thailand
• System: Outdoor unit (10 HP) x 1
Conventional model New model

Indoor unit (2 HP, Round Flow with Sensing type) x 5


Triple Outdoor units • Operation time: 8:00-20:00 5 days/week

RXQ42-60AMYM • Outdoor units: New model: RXQ10A (VRV A series)


Conventional model: RXQ10T (VRV IV)

* Cooling operation conditions:


• Indoor temperature of 27ºCDB, 19ºCWB, and outdoor temperature of 35ºCDB.

31 32
VRV A Series
Advanced Technologies
Advanced technologies for greater energy savings

+ VRT + VAV
By uniting advanced software and hardware technologies for greater energy savings during actual

VRV A Series
operation and combining the technologies of VRV, VRT and VAV, we have attained both energy savings
and comfortable air conditioning.

Software technology VRT Smart Control Hardware technology New Scroll Compressor
Fully Automatic Energy-saving Refrigerant Control
VRT Smart New Scroll
Control Function Compressor
movie movie

Optimally supply only for the needed capacity of indoor units Refrigerant leakage is minimized during low-load operation
• Reduces compressor load and minimizes operation loss so it is energy saving • Refrigerant leakage is
New compressor
• Controls capacity according to load to ensure a constant room temperature for greater comfort. minimized by a back pressure
Conventional compressor
control mechanism that
increases the efficiency

Compressor efficiency
during low-load operation.
Room temperature and
set temperature
The back pressure control mecha-
nism increases the efficiency during
low-load operation.

Coordinated control * Graph shown above is for illustration purposes only. Load factor

Back pressure control mechanism

Calculate New intermediate pressure mechanism


Determine the target Compressor
・Indoor airflow rate
refrigerant temperature speed control
・Target refrigerant temperature The pressure on the orbiting scroll is optimised
according to operating conditions. As a result,
the orbiting scroll has been stabilised to
* For the classification of indoor units (VRT smart control and VRT control), refer to the indoor unit lineup.
increase efficiency during low-load operation.
* The new mechanism is used in RXQ10,12,14 and 20A models.

Intermediate pressure
adjustment port

33 34
VRV A Series
Advanced Technologies
Automatic refrigerant charge function
Contribute to optimised operation efficiency, higher quality and easier installation.
Advanced oil temperature control

VRV A Series
Standby power needed for preheating refrigerator oil was reduced up to 82.7% Optimised operation efficiency
to save energy when the air conditioner is stopped.
* Operation calculation conditions: VRV A series 14 HP
82.7%Reduction
This function prevents a capacity shortage
or energy loss due to excessive
Automatic Refrigerant
Charge Function
movie
Location: Singapore
Operation time: 08:00–18:00 on weekdays or insufficient refrigerant.
Optimised Operation
Cooling
capacity
Extended operation range up to 49°C Efficiency

Cooling Outdoor temperature (°CDB)

10 20 30 40 49°C

VRV A Series
Note: When outdoor temperature falls below 10℃, the thermostat shuts OFF,
the outdoor unit stops, and operation switches from cooling to fan
Insufficient Excessive
operation.
refrigerant charge refrigerant charge

Optimal refrigerant Refrigerant


amount charge amount

I-demand function Total of 11 levels Higher quality and easier installation


Less Power consumption More

100% The automatic refrigerant charge function automates the charging of the proper
Peak power cut-off can be accomplished according refrigerant amount and the closing of shut-off valves by simply pressing a switch after pre-charging.
Can be set in
to each user situation.
70% 5% increments
* Set on the PCB of the outdoor unit.
50%
40% 1 Calculation of necessary refrigerant
amount from design drawing
2 Pre-charge of refrigerant 3 Start of automatic refrigerant
charge operation

0%
Time
* When set to 70% demand
Automatic Refrigerant Charge

High external static pressure R-410A

VRV A series outdoor unit has been achieved high external static pressure up to 78.4 Pa.

・Automatic completion by proper refrigerant amount


・Monitoring refrigerant charging is unnecessary
・No recalculation of charge amounts due to minor design changes locally

* There are conditions in the range of ambient temperature in which the automatic refrigerant charge can be used. Refer to the installation manual for details.
* The refrigerant amount that can be automatically charged may differ from the additional refrigerant amount that is provided from calculations, but there are
no problems in performance and quality.

35 36
VRV A Series
Comfort & Reliability
Comfort

VRV A Series
Nighttime quiet operation function Load % Outer rotor DC motor (ODM) Conventional Motor
ODM(Outer Type) UNIQUE

Operating sound dB(A) (Inner Type)


The nighttime quiet operation function Only Daikin has adapted an ODM HIGH TORQUE
Rotor
Rotor
automatically suppresses the nighttime with the feature of stable rotation and with low energy
operating sound by reducing operation Peak in the outdoor volumetric efficiency. F

capacity to maintain the quiet environ- 100% temperature F


MORE efficient
ment of the neighborhood.
Three selectable modes are available 8 hrs*1 10 hrs*2
depending on the required level. 50%

Function of information display by luminous digital tube 7-segment digital display

VRV A series utilises a bright 7-segment digital display to


57 dB(A)
convey operational status and facilitate simple installation
Night and after-sales service.
*1. Initial setting is 8 hours. Can be selected from 6, 8 and 10 hours.
*2. Initial setting is 9 hours. Can be selected from 8, 9 and 10 hours.
quiet mode
*3. In case of 10 HP outdoor unit. Displays system operation
information directly
Notes: • This function is available in setting at site.
• The operating sound in quiet operation mode is the actual
Min. 40 dB(A)*3
40 dB(A)
value measured by our company.
• The relationship of outdoor temperature (load) and time SMT* packaging technology Computer control board surface adopting SMT packaging technology
shown above is just an example. 8:00 12:00 16:00 20:00 0:00 4:00 8:00
Night mode STARTS Night mode ENDS •Improves the anti-clutter performance. SMT packaging material
•Protects your computer boards from the adverse
effects of sandy climates and humid weather.
* SMT: Surface mounted technology
Computer control board

Reliable and stable technology


Automatic sequencing operation
High reliability at high ambient temperature Priority Priority
Priority 1 2 3 3 1 2 2 3 1
PCB

Power Module Automatic Automatic


Heat Refrigerant Jacket sequencing sequencing
Refrigerant
Refrigerant Stage 1 Stage 2 Stage 3

Using refrigerant to cool the inverter power Double backup operation functions
module helps minimise the size of the electronic Unit backup operation function Compressor backup operation function
components, and this results in reduction of
Malfunction Emergency Emergency
airflow resistance and high efficiency of the heat operation operation
exchanger. Malfunction
* For single outdoor unit
system RXQ16-20AYM
models. On-site settings are
Control board failure ratio at stable operation is reduced. required using the PCB of the
outdoor unit.

This enables Ease of maintenance


Can provide maintenance
• Suitability for high ambient temperatures
feature* without shutting down
• Miniaturization of electronic components the whole VRV system.

* Field setting is required. This feature does not apply


to residential indoor unit connection. For more
information, please contact Daikin sales office. Area A Area B Area C

37 38
VRV A Series
Flexible System Design
More options for installation location
Long piping length

VRV A Series
The long piping length provides more design flexibility, which can match even large-sized buildings.

Installation for VRV indoor units only Installation for mixed combination of VRV and residential indoor units
Between the outdoor branch
and the last outdoor unit
Max. total
piping length 1000 m Max. 13 m Max. total
Between the outdoor units piping length 250 m
VRV: VRV indoor unit
Max. 5 m RA: Residential indoor unit

Max. actual
piping length
Between BP unit
Max. level difference Max. actual Max. level difference between the and indoor unit
165 m between the outdoor units piping length outdoor unit and the BP units
and the indoor units Max. 15 m
Max. equivalent *2 100 m 40 m BP unit
piping length 90 m
Max. equivalent
piping length
190 m Max. level
120 m difference
between 15 m
RA RA
Max. level difference
Max. level difference
Between the first indoor between the indoor units BP unit BP unit between the outdoor unit
branch and the farthest and the indoor unit
indoor unit 30 m 50 m
*1 Max. level difference
Max. 90 m Between the first indoor between the indoor
RA units
branch and the farthest
VRV indoor unit RA
Max. level difference 15 m
*1
Max. 50 m between the BP unit
and the indoor unit
Note: The above is just a schematic diagram.
5m
Actual piping length (Equivalent) 165 m (190 m)
Total piping length 1000 m
Maximum allowable piping length VRV
Between the first indoor branch and the farthest indoor unit 90 m*1
Note: The above is just a schematic diagram.
Between the outdoor branch and the last outdoor unit (Equivalent) 10 m (13 m)
Between the outdoor units (Multiple use) 5m
Maximum allowable level difference Between the indoor units 30 m
Between the outdoor units and the indoor units 90 m*2
When a mixed combination of VRV and residential indoor units is connected
*1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. The VRV A series is easy to extend to 90 m by lessening
the conditions from conventional VRV IV models. Be sure to refer to the Engineering Data Book for details of these conditions and requirements.
Actual piping length (Equivalent) 100 m (120 m) *1. If the piping length between the first
*2. When level differences are 50 m or more, the diameter of the main liquid piping size must be increased. If the outdoor unit is above the indoor unit, a dedicated setting
indoor branch and BP unit or VRV
on the outdoor unit is required. Refer to the Engineering Data Book and contact your local dealer for more information.
Total piping length 250 m indoor unit is over 20 m, it is necessary
to increase the gas and liquid piping
Between BP unit If indoor unit capacity index < 60. 2 m–15 m size between the first indoor branch
Maximum allowable and indoor unit and BP unit or VRV indoor unit. If the
piping length If indoor unit capacity index is 60 and 71. 2 m–8 m
piping diameter of the sized up piping
Between the first indoor branch and the farthest BP unit or exceeds the diameter of the piping
50 m*1
Connection ratio Conditions of VRV indoor unit connection capacity between the first indoor branch and the farthest VRV indoor unit before the first indoor branch kit, then
the latter also requires a liquid piping
Minimum allowable Between outdoor unit and the first indoor branch 5m
and gas piping size up. Please refer to
Engineering Data Book for details.
Connection capacity piping length
FXSQ FXAQ
at maximum is 200%. Applicable Other VRV indoor Between the indoor units 15 m
VRV indoor units unit models*1 Between BP units 15 m *When a mixed combination of VRV and
FXMQ-PA
residential indoor units is connected or
Connection ratio FXDQ FXB(P)Q
Maximum allowable Between the outdoor unit If the outdoor unit is above. 50 m when only residential indoor units are
level difference and the indoor unit If the outdoor unit is below. 40 m connected, connection ratio must be

50%– 200% 200%


50% to 130%. Refer to page 43 for

200%
Single outdoor units Between the outdoor unit and the BP unit 40 m outdoor unit combination details.
Double outdoor units 160% Between the BP unit and the indoor unit 5m
Triple outdoor units 130%
*1 For the FXF(S)Q25 and FXVQ models, maximum connection ratio is 130% for the entire range of
outdoor units.
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced
Total capacity index of the indoor units in all the indoor units.
Connection ratio = *Refer to page 43 for outdoor unit combination details.
Capacity index of the outdoor units

39 40
VRV A Series
Anti-corrosion Technology
Heavy anti-corrosion model
Maximize lifespan The new model resists corrosion by salt,

VRV A Series
maintains performance,
A third party tested the corrosion resistance and greatly reduces life cycle costs.
(ISO 9227: salt spray tests) of the reinforced fins
and casing for ISO 12944: 2018 Category C5 and •Total life cycle cost
RXQ6-20AYMW ion
ros
RXQ18-60AMYMW
confirmed them to be at very high (VH) levels. Cor eriod
p
ISO 12944-6:2018 : Paints and varnishes – Corrosion protection
of steel structures by protective paint systems n
Built for sio
Category C5 : Industrial areas with high humidity and o rro iod
Seaside aggressive atmosphere and coastal areas
with high salinity
C e
p
r

Level VH : Very high (equivalent to an expected life of


25 years *)
ISO 9227 : Corrosion test in artificial atmospheres-Salt Initial cost Replacement Time
spray tests
Maximize anti-corrosion and performance * This number of years is not the warranty period of the product.
Product life depends on installation location and operating conditions.
Standard model

Outer casing
4-layer coating
Multi coating for extreme durability Top clear special coating Built for seaside
Top coat metallic special coating
The hot-dip Zinc-Aluminum-Magnesium alloy Powder middle coating Previous model: Anti-corrosion : Heavy Anti-corrosion
coated sheet is optimised for even greater Primer base coating
durability with an additional four-layer coating Hot-dip zinc-aluminum-magnesium alloy coated steel sheet Building
Can be installed
Building
combination. right by the sea

Sea wind outdoor unit Sea wind outdoor unit


Anti-corrosion verification by accelerated test Salt Spray Test CASS Test

Although the previous anti-corrosion model is Previous model VRV A MAX Previous model VRV A MAX
rusted, the VRV A MAX outer casing shows no
Sea Sea
signs of corrosion in either test. 0 – 1000m
* The cross cut was made in order to simulate a severe case of coating damage
Must be installed at least 300 m away from the sea in a Must be installed where the unit does not get into contact
and corrosion (not from regular usage).
location not in direct contact with sea wind. with seawater.

: Corrosion : No corrosion : Corrosion : No corrosion 300 - 1,000 m 0 – 1,000 m

Heat exchanger (Fin) Standard model


CASS Test
VRV A MAX
Specifications of anti-corrosion model
Item Parts Standard model
Anti-corrosion technology
Hot-dip zinc-aluminum-magnesium alloy-coated steel sheet + Primer
The aluminum fins on VRV A MAX are 1 Sheet metal casing Outer casing Hot dip zinc coated sheet + powder coating base coating + Powder middle coating + Top coat metallic special
coating (metallic brown) + Top clear special coating
manufactured with thicker anti-corrosion layer
2 Discharge grille • Protection net Low Density Polyethylene (LDPE) coating
including an additional two-layer coating.
: Corrosion : No corrosion 3 Fasteners SWCH + zinc-nickel plating SUS410 + zinc-nickel plating

Corrosion resistance coating* 4 Heat exchanger Copper tube + Standard aluminum fin Copper tube + Anti-corrosion aluminum fin
Aluminum fin + High corrosion resistance aluminum fin +
Primer base coating*
High performance technology 5 Aluminum fin Aluminum fin + Hydrophilic anti-corrosion Primer base coating (outside area only) + Corrosion resistance coating
High corrosion resistance aluminium fin (outside area only)

New aluminum fins are 21% thicker Aluminium fin


Hot-dip zinc-aluminum-magnesium
* outside area only 6 Heat exchanger end plate Hot dip zinc coated sheet + corrosion resistance polyurethane coating
to maintain performance. alloy-coated steel sheet without coating

Fan motor stand • Electric box •


Achieves both anti-corrosion 7 Inner casing sheet metal
Galvanized iron sheet Hot dip zinc coated sheet + corrosion resistance polyurethane coating
Automated fin coating line and high efficiency
8 Fan • Fan motor Resin fan + resin casing motor
To prevent differences in coating thickness caused by manual application, the additional fin coatings are 9 Pressure vessel (oil separator) Hot rolled sheet steel + painting Hot rolled sheet steel + Double rust inhibitor
coating with additional touch-up paint
performed on the latest automated assembly line, maintaining high precision and quality.
10 Printed circuit board Both side resin coating Expanded both side resin coating

41 42
VRV A Series
Outdoor Unit Lineup
VRV A Series
The outdoor unit capacity is up to 60 HP (168 kW) in increments of 2 HP.
For mixed combination of VRV and residential indoor units

VRV A Series
Lineup
Total capacity index of connectable indoor units*2
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 Capacity Maximum number of
Model name*1 kW HP index Combination (%)*2 connectable indoor units
Single outdoor units 50% 100% 130%
VRV A RXQ6AYM(W) 16.0 6 150 75 150 195 9
Double outdoor units
SERIES RXQ8AYM(W) 22.4 8 200 100 200 260 13
Triple outdoor units RXQ10AYM(W) 28.0 10 250 125 250 325 16
RXQ12AYM(W) 33.5 12 300 150 300 390 19
RXQ14AYM(W) 40.0 14 350 175 350 455 22
RXQ16AYM(W) 45.0 16 400 200 400 520 26
Outdoor Unit Combinations RXQ18AYM(W) 50.0 18 450 225 450 585 29
RXQ20AYM(W) 56.0 20 500 250 500 650 32
Notes: *1. Only single outdoor unit (RXQ6-20AYM(W)) can be connected.
For connection of VRV indoor units only *2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.

Capacity Outdoor unit multi Total capacity index of Maximum number of


HP kW Model name Combination
index connection piping kit*1 connectable indoor units*2 connectable indoor units*2
6 16.0 150 RXQ6A RXQ6A – 75 to 195 (300) 9 (15)
8 22.4 200 RXQ8A RXQ8A – 100 to 260 (400) 13 (20)
10 28.0 250 RXQ10A RXQ10A – 125 to 325 (500) 16 (25)
12 33.5 300 RXQ12A RXQ12A – 150 to 390 (600) 19 (30)
14 40.0 350 RXQ14A RXQ14A – 175 to 455 (700) 22 (35)
16 45.0 400 RXQ16A RXQ16A – 200 to 520 (800) 26 (40)
18 50.0 450 RXQ18A RXQ18A – 225 to 585 (900) 29 (45)
20 56.0 500 RXQ20A RXQ20A – 250 to 650 (1,000) 32 (50)
18 50.4 450 RXQ18AM RXQ8A + RXQ10A 225 to 585 (720) 29 (36)
20 55.9 500 RXQ20AM RXQ8A + RXQ12A 250 to 650 (800) 32 (40)
22 61.5 550 RXQ22AM RXQ10A + RXQ12A 275 to 715 (880) 35 (44)
24 67.0 600 RXQ24AM RXQ12A × 2 300 to 780 (960) 39 (48)
26 73.5 650 RXQ26AM RXQ12A + RXQ14A 325 to 845 (1,040) 42 (52)
28 78.5 700 RXQ28AM RXQ12A + RXQ16A BHFP22P100 350 to 910 (1,120) 45 (56)
30 83.5 750 RXQ30AM RXQ12A + RXQ18A 375 to 975 (1,200) 48 (60)
32 90.0 800 RXQ32AM RXQ14A + RXQ18A 400 to 1,040 (1,280) 52 (64)
34 95.0 850 RXQ34AM RXQ16A + RXQ18A 425 to 1,105 (1,360) 55 (64)
36 100 900 RXQ36AM RXQ18A × 2 450 to 1,170 (1,440) 58 (64)
38 106 950 RXQ38AM RXQ18A + RXQ20A 475 to 1,235 (1,520) 61 (64)
40 112 1,000 RXQ40AM RXQ20A × 2 500 to 1,300 (1,600)
42 117 1,050 RXQ42AM RXQ12A × 2 + RXQ18A 525 to 1,365 (1,365)
44 123 1,100 RXQ44AM RXQ12A × 2 + RXQ20A 550 to 1,430 (1,430)
46 130 1,150 RXQ46AM RXQ14A × 2 + RXQ18A 575 to 1,495 (1,495)
48 135 1,200 RXQ48AM RXQ14A + RXQ16A + RXQ18A 600 to 1,560 (1,560)
50 140 1,250 RXQ50AM RXQ14A + RXQ18A × 2 625 to 1,625 (1,625) 64 (64)
BHFP22P151
52 145 1,300 RXQ52AM RXQ16A + RXQ18A × 2 650 to 1,690 (1,690)
54 150 1,350 RXQ54AM RXQ18A × 3 675 to 1,755 (1,755)
56 156 1,400 RXQ56AM RXQ18A × 2 + RXQ20A 700 to 1,820 (1,820)
58 162 1,450 RXQ58AM RXQ18A + RXQ20A × 2 725 to 1,885 (1,885)
60 168 1,500 RXQ60AM RXQ20A × 3 750 to 1,950 (1,950)
Notes: *1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
*2. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double outdoor units,
and 130% for triple outdoor units. Refer to page 39 for notes on connection capacity of indoor units.

43 44
VRV A Series
Indoor Unit Lineup
Enhanced range of choices
Indoor units subject to Indoor units subject to
VRV indoor units New lineup VRT
smart VRT smart control VRT VRT control Residential indoor units with connection to BP units
20 25 32 40 50 63 71 80 100 125 140 200 250 400 500 25 35 50 60 71
Category

VRV A Series
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 Capacity Index 25 35 50 60 71
Round Flow Cassette VRT
FXFSQ-AVM smart
with Sensing FDKS-EAVMB VRT
Ceiling Mounted Cassette

(700 mm width type)


Slim Ceiling Concealed Duct
Round Flow Cassette FXFQ-AVM VRT
smart
FDKS-C(A)VMB VRT
(900/1,100 mm width type)
Compact Multi VRT
Flow Cassette FXZQ-AVM smart
FTKS-DVM VRT

Double Flow Cassette FXCQ-AVM VRT


smart

Wall Mounted FTKS-BVMA VRT


Corner Cassette FXKQ-MAVE VRT

3D Airflow Duct with FTKS-FVM VRT


FXDSQ-AVM VRT
Sensing
FXDQ-PDVE VRT Note: BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20AYM(W)) can be connected.
(with drain pump) smart
FXDQ-PDVET VRT
(without drain pump) smart (700 mm width type)
Slim Duct (Standard)
FXDQ-NDVE
Ceiling Concealed Duct

VRT
(with drain pump) smart
VRV indoor units combine with residential indoor units, all in one system.
FXDQ-NDVET
(without drain pump)
VRT
smart (900/1,100
width type )
mm
VRV indoor unit only system
Slim Duct (Compact) FXDQ-SPV1 VRT

Middle Static VRT


FXSQ-PAVE smart
Pressure Duct

Middle-High Static Pressure Duct FXMQ-PAVE VRT


smart

High Static Pressure Duct FXMQ-PVM VRT VRV indoor units only
smart
Max. • If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control.
Outdoor-Air Processing Unit FXMQ-MFV1 64 indoor
units • If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, VRT smart control and VRT control are disabled.

4-Way Flow Ceiling


Ceiling Suspended

FXUQ-AVEB VRT Residential indoor unit and VRV indoor unit mix system
Suspended

FXHQ-MAVE VRT
Ceiling Suspended
FXHQ-AVM VRT BP unit
Wall Mounted FXAQ-AVM VRT
smart

Floor Standing FXLQ-MAVE VRT Residential indoor units VRV indoor units
Floor Standing

Max. • BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20AYM(W)) can be connected.
Concealed Floor Standing FXNQ-MAVE VRT
32 indoor
units • If a system has both residential indoor units and VRV indoor units, the system is operated under VRT control.

FXVQ-NY1 VRT
Floor Standing Duct Residential indoor unit only system
FXVQ-NY16 VRT
(high static pressure type)

FXBQ-PVE VRT
Clean Room Air Conditioner BP unit BP unit
FXBPQ-PVE VRT

Heat Reclaim Ventilator


VKM-GCVE Airflow rate 500-950 m3/h
with DX-Coil
Residential indoor units only
Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h Max. • BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20AYM(W)) can be connected.

6–120 HP
32 indoor
units • If a system has only residential indoor units, the system is operated under VRT control.
Air Handling Unit AHUR

45 46
VRV A Series
Outdoor Units
VRV A Series
Specifications

VRV A Series
MODEL RXQ6AYM(W) RXQ8AYM(W) RXQ10AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ18AMYM(W) RXQ20AMYM(W) RXQ22AMYM(W) RXQ24AMYM(W) RXQ26AMYM(W) RXQ28AMYM(W) RXQ30AMYM(W)
— — — — — — — — RXQ8AYM(W) RXQ8AYM(W) RXQ10AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W)
Combination units
— — — — — — — — RXQ10AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W)
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 54,600 76,400 95,500 114,000 136,000 154,000 171,000 191,000 172,000 191,000 210,000 229,000 251,000 268,000 285,000
Cooling capacity
kW 16.0 22.4 28.0 33.5 40.0 45.0 50.0 56.0 50.4 55.9 61.5 67.0 73.5 78.5 83.5
Power consumption kW 3.38 5.17 6.84 8.70 10.7 12.9 15.3 17.7 12.0 13.9 15.5 17.4 19.4 21.6 24.0
Capacity control % 25-100 20-100 13-100 12-100 11-100 10-100 10-100 7-100 7-100 7-100 6-100 6-100 6-100 5-100 5-100
Casing colour Ivory white (5Y7.5/1) (Metallic brown 1 ) Ivory white (5Y7.5/1) (Metallic brown 1 )
Type Hermetically sealed scroll type Hermetically sealed scroll type
Compressor (5.6×1)+(3.5×1) (5.6×1)+(4.0×1)
Motor output kW 2.3×1 3.4×1 4.5×1 5.6×1 6.4×1 (3.5×1)+(3.5×1) (4.0×1)+(4.0×1) (3.8×1)+(6.3×1) (3.4×1)+(4.5×1) (3.4×1)+(5.6×1) (4.5×1)+(5.6×1) (5.6×1)+(5.6×1) (5.6×1)+(6.4×1)
+(3.5×1) +(4.0×1)
Airflow rate m3/min 119 178 191 257 297 178+178 178+191 191+191 191+257
Dimensions (H×W×D ) mm 1,657×930×765 1,657×1,240×765 1,657×1,240×765 (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×1,240×765)
Machine weight kg 175 (180 1
) 185 (195 1
) 215 (235 1
) 260 (280 1
) 285 (310 1
) 175+185 (180+195 1
) 185+185 (195+195 1
) 185+215 (195+235 1) 185+260 (195+280 1
)
Sound level dB(A) 56 57 59 60 61 65 60 61 62 63
Operation range °CDB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 5.9 6.7 6.8 7.4 8.2 8.4 11.8 5.9+6.7 5.9+6.8 6.7+6.8 6.8+6.8 6.8+7.4 6.8+8.2 6.8+8.4
Piping Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing) 15.9 (Brazing) 19.1 (Brazing)
connections Gas mm 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 34.9 (Brazing)

MODEL RXQ32AMYM(W) RXQ34AMYM(W) RXQ36AMYM(W) RXQ38AMYM(W) RXQ40AMYM(W) RXQ42AMYM(W) RXQ44AMYM(W) RXQ46AMYM(W) RXQ48AMYM(W) RXQ50AMYM(W) RXQ52AMYM(W) RXQ54AMYM(W) RXQ56AMYM(W) RXQ58AMYM(W) RXQ60AMYM(W)
RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ14AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W)
Combination units RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W)
— — — — — RXQ18AYM(W) RXQ20AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W) RXQ20AYM(W)
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 307,000 324,000 341,000 362,000 382,000 399,000 420,000 444,000 461,000 478,000 495,000 512,000 532,000 553,000 573,000
Cooling capacity
kW 90.0 95.0 100 106 112 117 123 130 135 140 145 150 156 162 168
Power consumption kW 26.0 28.2 30.6 33.0 35.4 32.7 35.1 36.7 38.9 41.3 43.5 45.9 48.3 50.7 53.1
Capacity control % 5-100 5-100 5-100 4-100 3-100 4-100 3-100 3-100 3-100 3-100 3-100 3-100 3-100 2-100 2-100
Casing colour Ivory white (5Y7.5/1) (Metallic brown 1
) Ivory white (5Y7.5/1) (Metallic brown 1
)
Type Hermetically sealed scroll type Hermetically sealed scroll type
Compressor (6.4×1)+(4.0×1) (3.5×1)+(3.5×1) (4.0×1)+(4.0×1) (4.0×1)+(4.0×1) (3.8×1)+(6.3×1) (5.6×1)+(5.6×1) (5.6×1)+(5.6×1) (6.4×1)+(6.4×1) (6.4×1)+(3.5×1)+(3.5×1) (6.4×1)+(4.0×1)+(4.0×1) (3.5×1)+(3.5×1)+(4.0×1) (4.0×1)+(4.0×1)+(4.0×1) (4.0×1)+(4.0×1)+(4.0×1) (4.0×1)+(4.0×1)+(3.8×1) (3.8×1)+(6.3×1)+(3.8×1)
Motor output kW
+(4.0×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1) +(3.8×1)+(6.3×1) +(3.8×1)+(6.3×1) +(4.0×1)+(4.0×1) +(3.8×1)+(6.3×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1)+(4.0×1) +(4.0×1)+(4.0×1)+(4.0×1) +(4.0×1)+(3.8×1)+(6.3×1) +(6.3×1)+(3.8×1)+(6.3×1) +(6.3×1)+(3.8×1)+(6.3×1)
Airflow rate m3/min 257+257 257+297 297+297 191+191+257 191+191+297 257+257+257 257+257+297 257+297+297 297+297+297
(1,657×930×765)+(1,657×930×765)+
Dimensions (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
(1,657×1,240×765)
Machine weight kg 215+260 (235+280 )
1
260+260 (280+280 1
) 260+285 (280+310 ) 285+285 (310+310 ) 185+185+260 (195+195+280 ) 185+185+285 (195+195+310 )
1 1 1 1
215+215+260 (235+235+280 ) 1
215+260+260 (235+280+280 1
) 260+260+260 (280+280+280 1
) 260+260+285 (280+280+310 1) 260+285+285 (280+310+310 1) 285+285+285 (310+310+310 1)
Sound level dB(A) 64 66 68 65 67 65 66 68 69 70
Operation range °CDB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 7.4+8.4 8.2+8.4 8.4+8.4 8.4+11.8 11.8+11.8 6.8+6.8+8.4 6.8+6.8+11.8 7.4+7.4+8.4 7.4+8.2+8.4 7.4+8.4+8.4 8.2+8.4+8.4 8.4+8.4+8.4 8.4+8.4+11.8 8.4+11.8+11.8 11.8+11.8+11.8
Piping Liquid mm 19.1 (Brazing) 19.1 (Brazing)
connections Gas mm 34.9 (Brazing) 41.3 (Brazing) 41.3 (Brazing)
Notes: Specifications are based on the following conditions; Note: 1. Models with (W) are the outdoor units with anti-corrosion specifications. For details, refer to pages 41 - 42 for more information.
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
47 When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures. 48
VRV S High Seasonal Efficiency Series

The VRV S High Seasonal Efficiency Series concept

VRV S High Seasonal Efficiency Series


New VRV S High Seasonal Efficiency Series achieves higher energy efficiency with a variety of function
The Ideal Air Conditioning System for comfort and high performance. A wide range of options for installation location
and application are easily achieved by the low height casing, long piping length and other features.
for Residential Houses, Cooling Only
4 HP –9 HP
Small Offices and Shops (11.2 kW) (24 kW)

Presentation
Movie
Energy savings
& comfort

Design
High performance flexibility of
& reliability installation

Energy savings & comfort


Higher energy efficiency
VRT Smart Control
Quiet operation

High performance & reliability


Extended operation range up to 52°C
RSUQ4-6AVM High voltage shield PCB
RSUQ7-9AYM Automatic refrigerant charge function

Design flexibility of installation


The high external static pressure of 40 Pa enables installation in small installation spaces where the
airflow direction needs to be diverted to avoid short circuits.
Low height casing design
Increased actual piping length up to 120 m

49 50
VRV S High Seasonal Efficiency Series
Energy Savings & Comfort
Energy savings Comfort

VRV S High Seasonal Efficiency Series


High seasonal efficiency Quiet operation
The VRT Smart Control enables improvements on efficiency during low load operation, Low operation sound
achieving high seasonal efficiency.
New fan and bell mouth help enable low operation sound.
dB(A)

EER for 5 HP Cooling 4 HP 5 HP 6 HP 7 HP 8 HP 9 HP

8 New 51 51 52 58 59 60
7
7.00
6.18
6
5.36
V-cut & irregular pitch propeller fan A˚
5 4.79
Cooling EER

4
4.26 4.07 Old New
Separate

Collision

1

0 Air streams collide Air streams are smoothed around
50% 60% 70% 80% 90% 100% Load and generate loss V-cut and reduces airflow loss
Irregular blade pitch also contributes
The fan's V-cut enables streamlined and effective airflow.
S SERIES to reduced airflow noise.
A˚< B˚< C˚
Nighttime quiet operation function
The nighttime quiet operation function automatically suppresses the nighttime operating sound by
reducing operation capacity to maintain the quiet environment of the neighborhood. Three selectable
VRT Smart Control modes are available depending on the required level.
VRT Smart function is available in the VRV S High Seasonal Efficiency Series for This function is suitable for use in residential areas.
the first time. Coordination between indoor and outdoor units minimizes energy
consumption by optimising capacity to meet actual operation load. Cooling Night Quiet Mode

Room temperature and RSUQ4/5/6A Min. 40 dB(A)


set temperature Load %
RSUQ7/8/9A Min. 45 dB(A)
Operating
sound dB(A)

Peak in the outdoor


100% temperature
Coordinated control
8 hrs 10 hrs
50%

52 dB(A)

Calculate Night
Determine the target Compressor quiet mode
・Indoor airflow rate
refrigerant temperature speed control
・Target refrigerant temperature
Notes: • This function is available in setting at site.
Notes: • For the classification of indoor units (VRT smart control and VRT control), refer to pages 59 - 60.
• If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control.
Min. 40 dB(A) • The operating sound in quiet operation mode is the actual value
40 dB(A) measured by our company.
• If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, VRT smart control and VRT control are disabled.
• The relationship of outdoor temperature (load) and time shown
above is just an example.
8:00 12:00 16:00 20:00 0:00 4:00 8:00 • In case of 4-6 HP outdoor unit
Night mode STARTS Night mode ENDS

51 52
VRV S High Seasonal Efficiency Series
High Performance & Reliability
High temperature operation New swing compressor

VRV S High Seasonal Efficiency Series


Extended operation range up to 52°C High efficiency, high capacity DC inverter swing compressor
The outdoor operation temperature range is now extended to 52ºC. The new compressors offer higher performance compared New DC motor
This enables reliable operation even under high temperature conditions to that of conventional scroll compressors. (high wire-efficiency winding/
and a wider choice of installation locations. high-efficiency magnet)
High-capacity
swing structure
Cooling Outdoor temperature (°CDB)
-5 0 10 20 30 40 46 52°C Improved performance
New VRV S High Seasonal Efficiency Series The new DC motor designed with
small-diameter bearing and improved
efficiency during low-speed
Previous VRV IV S Series
operation has improved seasonal efficiency.

The refrigerant-cooled PCB and large 3-row heat exchanger


raise the maximum cooling outdoor operation temperature from 46°C to 52°C.
High voltage shield PCB (4-6 HP model only)
The high voltage shield PCB protects Max.
440 V
the electrical parts and prevents malfunctions
Refrigerant cooled PCB at the highest voltage of 440 V.
Daikin’s unique refrigerant cooling helps
maintain high cooling capacity even during * Continuous operation range is 198 to 264 V.
high outdoor temperatures.

Automatic refrigerant charge function


Contribute to optimised operation efficiency, higher quality and easier installation.

Optimised operation efficiency Optimised Operation


Cooling
New heat exchanger This function prevents a capacity shortage or energy loss due Efficiency capacity

・2-sided 3-row
・Heat exchanger area 68%UP
(4,5 HP model only)
to excessive or insufficient refrigerant.

Insufficient Excessive
refrigerant charge refrigerant charge
Keep rated cooling capacity in high outdoor
temperature up to 43°C* Higher quality and easier installation
Optimal refrigerant
amount
Refrigerant
charge amount

Rated cooling capacity can be maintained even when outdoor temperature is up to 43°C*. The automatic refrigerant charge function automates the charging of the proper refrigerant
*Rated cooling capacity for 9 HP is up to 42°C.
amount and easy start by pressing one button.
Cooling
capacity New VRV S High Seasonal Efficiency Series
1 Calculation of necessary refrigerant 2 Start of automatic refrigerant
amount from design drawing charge operation

Previous VRV IV S Series The large heat exchanger ensures Automatic Refrigerant Charge

sufficient cooling capacity even


100% in high ambient temperatures. R-410A

Outdoor ・Automatic completion by proper refrigerant amount


temperature ・Monitoring refrigerant charging is unnecessary
・No recalculation of charge amounts due to minor design changes locally
10 35 39
43* 52 (°CDB)

53 * Must use automatic refrigerant charge function. Refer to installation manual for details. 54
VRV S High Seasonal Efficiency Series
Design Flexibility of Installation
No short circuits Low height casing design

VRV S High Seasonal Efficiency Series


High external static pressure up to 40 Pa and The new design has been optimised for the VRV S High Seasonal Efficiency Series with the height
of all models reduced to only 870 mm. This low height casing design provides occupants with a clear,
automatic adjustment of external static pressure unobstructed view of the scenery.

The new VRV S High Seasonal Efficiency Series External


static pressure (Pa)
outdoor unit has been achieved high external Previous VRV IV S series
static pressure up to 40 Pa, realizing stable operation Resistance increases
when duct is
in small installation sites where the air direction Rated airflow is
installed in the site.
adjustment grille or duct is used to avoid short circuits. maintained.
maintained
3

1,430 mm
1,345 mm
The external static pressure automatic adjustment function Airflow decreases. 2
maintains rated airflow and capacity by automatically adjusting

990 mm
the external static pressure during the test operation to
870
suit the resistance of the installation site. 1 mm
Airflow (rated)

Airflow (m3/min)
4,5 HP 6 HP 8,9 HP 4-9 HP

Optimum airflow direction with the ・Ideal solution that minimises both visual and sound impact
・Can be installed in a wide variety of locations and applications
optional air direction adjustment grille ・No space required for multiple outdoor units
When discharged air is blocked by some obstacle, Wind is diverted upwards.
the optional air direction adjustment grille can
divert the airflow to one of 4 directions View from outside View from inside
(up, down, left or right) to avoid the obstacle.

Wind is diverted sideways.


Window

Outdoor
Air direction adjustment grille unit
(option)

Duct installation to stabilize the system Flange


(Field supply) Double-stacking installation possible
Duct
When the obstacle is not avoidable (Field supply) The low height casing design allows for compact
by the air direction adjustment grille, double-stacking of outdoor units to
installing a field-supplied duct maximize utilization of installation space.
can bypass the obstacle. In this way,
installation of the outdoor unit is possible
in places like behind an advertising board.

55 56
VRV S High Seasonal Efficiency Series
Design Flexibility of Installation
Increased actual piping length up to 120 m*

VRV S High Seasonal Efficiency Series


Actual piping length increased by 20% Installation on the rooftop of Installation on balconies of One outdoor unit can provide
allows for various installation! residential apartments residential apartments comfort for the whole house

Previous VRV IV S series

100 m 120 m*

Installation for VRV indoor units only Installation for mixed combination of VRV and
Max. total
piping length 300 m
residential indoor units
Max. total
piping length 300 m
VRV: VRV indoor unit
RA: Residential indoor unit
Max. actual
piping length
Max. level difference
120 m* between the outdoor units Between BP unit
and the indoor units Max. actual Max. level difference between the and indoor unit
piping length outdoor unit and the BP units
Max. equivalent
piping length 50 m Max. 15 m
120 m* 40 m BP unit

150 m Max. level difference


between the indoor units Max. equivalent
piping length
15 m Max. level
Between the first indoor
branch and the farthest
145 m difference
between 15 m
RA RA
Max. level difference
indoor unit BP unit BP unit between the outdoor unit
and the indoor unit
Max. 40 m 50 m
Max. level difference
Between the first indoor between the indoor
RA units
branch and the farthest
VRV indoor unit RA
Max. level difference 15 m
Note: The above is just a schematic diagram.
Max. 40 m between the BP unit
and the indoor unit

4 HP 5-9 HP 5m
Actual piping length (Equivalent) 120 m* (150 m) 120 m* (150 m)
Maximum allowable Total piping length 300 m 300 m
piping length
Between the first indoor branch and the farthest indoor unit 40 m 40 m VRV
Note: The above is just a schematic diagram.
Between the indoor units 10 m 15 m
Maximum allowable 4 HP 5-9 HP
Between the outdoor units If the outdoor unit is above. 50 m 50 m
level difference
and the indoor units If the outdoor unit is below. 40 m 40 m Actual piping length (Equivalent) 120 m* (145 m) 120 m* (145 m)
* Must use automatic refrigerant charge function. Total piping length 300 m 300 m
Refer to installation manual for details. 2 m–15 m 2 m–15 m
If indoor unit capacity index < 60.
Maximum allowable Between BP unit
If indoor unit capacity index is 60. 2 m–12 m 2 m–12 m
and indoor unit
piping length If indoor unit capacity index is 71. 2 m–8 m 2 m–8 m
Between the first indoor branch and the farthest BP unit or
40 m 40 m
between the first indoor branch and the farthest VRV indoor unit
Minimum allowable
Between outdoor unit and the first indoor branch 5m 5m
piping length
Between the indoor units 10 m 15 m
Between BP units 10 m 15 m
Maximum allowable Between the outdoor unit If the outdoor unit is above. 50 m 50 m
level difference and the indoor unit If the outdoor unit is below. 40 m 40 m
Between the outdoor unit and the BP unit 40 m 40 m
Between the BP unit and the indoor unit 5m 5m
* Must use automatic refrigerant charge function.
Refer to installation manual for details.
57 58
VRV S High Seasonal Efficiency Series
Indoor Unit Lineup
Wide variety of indoor units

VRV S High Seasonal Efficiency Series


Indoor units can be selected from 2 lineups, both VRV and residential indoor units, Residential indoor units with connection to BP units
to match rooms and preferences. 25 35 50 60 71
Indoor units subject to Indoor units subject to
VRV indoor units New lineup VRT
smart VRT smart control VRT VRT control Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1

20 25 32 40 50 63 71 80 100 125 140 200 250 Capacity Index 25 35 50 60 71


Category

Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP
Capacity Index
FDKS-EAVMB VRT
20 25 31.25 40 50 62.5 71 80 100 125 140 200 250
(700 mm width type)
Slim Ceiling Concealed Duct
Round Flow Cassette VRT
FXFSQ-AVM smart
with Sensing FDKS-C(A)VMB VRT
Ceiling Mounted Cassette

(900/1,100 mm width type)

Round Flow Cassette FXFQ-AVM VRT


smart
FTKS-DVM VRT

Compact Multi VRT


Flow Cassette FXZQ-AVM smart
Wall Mounted FTKS-BVMA VRT
Double Flow Cassette FXCQ-AVM VRT
smart

FTKS-FVM VRT
Corner Cassette FXKQ-MAVE VRT

Note: BP units are necessary for residential indoor units.


3D Airflow Duct with
FXDSQ-AVM VRT
Sensing
FXDQ-PDVE VRT
(with drain pump) smart
FXDQ-PDVET VRT
(without drain pump) smart (700 mm width type)
Slim Duct (Standard)
FXDQ-NDVE
Ceiling Concealed Duct

VRT
(with drain pump) smart
FXDQ-NDVET
(without drain pump)
VRT
smart (900/1,100
width type )
mm VRV indoor units only
Max. • If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control.
Slim Duct (Compact) FXDQ-SPV1 VRT 14 indoor
units • If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, VRT smart control and VRT control are disabled.

Middle Static VRT


FXSQ-PAVE smart
Pressure Duct

Middle-High Static Pressure Duct FXMQ-PAVE VRT


smart
BP unit BP unit
High Static Pressure Duct FXMQ-PVM VRT
smart

Outdoor-Air Processing Unit FXMQ-MFV1

4-Way Flow Ceiling


Residential indoor units only
Ceiling Suspended

FXUQ-AVEB VRT Max.


Suspended • BP units are necessary for residential indoor units.

FXHQ-MAVE VRT
14 indoor
units • If a system has only residential indoor units, the system is operated under VRT control.

Ceiling Suspended
FXHQ-AVM VRT

Wall Mounted FXAQ-AVM VRT


smart

Floor Standing FXLQ-MAVE VRT


Floor Standing

Concealed Floor Standing FXNQ-MAVE VRT

Floor Standing Duct FXVQ-NY1 VRT

FXBQ-PVE VRT
Clean Room Air Conditioner
FXBPQ-PVE VRT

Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h

59 60
VRV S High Seasonal Efficiency Series
Outdoor Units
VRV S High Seasonal Efficiency Series

VRV S High Seasonal Efficiency Series


Specifications Outdoor unit combinations
MODEL RSUQ4AVM RSUQ5AVM RSUQ6AVM RSUQ7AYM RSUQ8AYM RSUQ9AYM
kW 11.2 14.0 16.0 20.0 22.4 24.0

HP 4 5 6 7 8 9

Capacity index 100 125 150 175 200 215

50% 50 62.5 75 87.5 100 107.5


Total capacity
index of
Combination (%) 100% 100 125 150 175 200 215
connectable
MODEL RSUQ4AVM RSUQ5AVM RSUQ6AVM RSUQ7AYM RSUQ8AYM RSUQ9AYM indoor units
130% 130 162.5 195 227.5 260 280

Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz 3-phase, 380-415 V/380 V, 50/60 Hz Maximum number of connectable indoor units 6 8 9 11 13 14

Btu/h 38,200 47,800 54,600 68,200 76,400 81,900 Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
Cooling capacity
kW 11.2 14.0 16.0 20.0 22.4 24.0

Power consumption kW 2.49 3.44 4.10 5.46 6.61 7.21

Capacity control % 23 to 100 16 to 100 9 to 100

Casing colour Ivory white (5Y7.5/1)

Type Hermetically sealed swing type


Compressor
Motor output kW 2.0 3.1 3.5 1.9 3.2 3.8

Airflow rate m3/min 87 84 87 123 137

Dimensions (H×W×D) mm 870×1,100×460

Machine weight kg 95 98 115

Sound level dB(A) 51 52 58 59 60

Operation range °CDB -5 to 52

Type R-410A
Refrigerant
Charge kg 4.0 4.2 5.4

Liquid mm 9.5 (Flare)


Piping connections
Gas mm 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing)

Note: Specifications are based on the following conditions;


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.

61 62
VRV IV S Series

Compact & lightweight design


The Ideal Air Conditioning System
The VRV IV S series is slim and compact, with outdoor units that require minimal installation space.
for Residential Houses, Cooling Only
4 HP –6 HP
Small Offices and Shops (11.2 kW) (16.0 kW)

990 mm

VRV IV S Series
320 mm
940 mm

4 HP 5 HP 6 HP
Height 990 mm 990 mm 990 mm
Product Weight 71 kg 76 kg 78 kg
Footprint 0.30 m2 0.30 m2 0.30 m2

Energy saving

High Energy Efficiency Ratio (EER)


VRV IV S series provides greater energy saving as compared to VRV III S series.

VRV III S VRV IV S Series

4
3.89

3.8

Cooling Operation EER


3.66
RXMQ4AVE 3.6 3.55

3.4
RXMQ5-6BVM
3.2

0
4 HP 5 HP 6 HP
(11.2 kW) (14.0 kW) (16.0 kW)

*Cooling operation conditions: Indoor temp. of 27º CDB,19º CWB, and outdoor temp. of 35º CDB.

63 64
VRV IV S Series
Comfort and Simplified Installation
Quiet operation Load % Makes the long piping design possible
Operating sound dB(A)
Nighttime quiet operation function Long piping length offers flexibility in the choice of installation positions,
and simplifies system planning.
The nighttime quiet operation function Peak in the outdoor

automatically suppresses the nighttime operating


100% temperature When only VRV
sound by reducing operation capacity to maintain 8 hrs 10 hrs indoor units are connected a
the quiet environment of the neighborhood. 50% Actual piping length b c d
Three selectable modes are available depending e g
f h i
on the required level. Max. 70 m First indoor branch

VRV IV S Series
This function is suitable for use in residential areas. Max.
52 dB(A) Equivalent piping length 30 m k
Max.
Night j 15 m
quiet mode Max. 90 m

Total piping length


Min. 43 dB(A)
43 dB(A) Max. 300 m
4 HP 5,6 HP
8:00 12:00 16:00 20:00 0:00 4:00 8:00 Refrigerant piping length (Equivalent) a+b+c+d+i 50 m (65 m) 70 m (90 m)
Night mode STARTS Night mode ENDS Max. allowable piping Total piping length a+b+c+d+e+f+g+h+i 250 m 300 m
length
Notes: • This function is available in setting at site. Between the first indoor branch and the farthest indoor unit b+c+d+i 40 m 40 m
• The operating sound in quiet operation mode is the actual value measured by our
company. Between the indoor units j 10 m 15 m
• The relationship of outdoor temperature (load) and time shown above is just an Max. allowable level
example. Between the outdoor unit If the outdoor unit is above k 30 m 30 m
• In case of 4 HP outdoor unit
difference
and the indoor unit If the outdoor unit is below k 30 m 30 m

When a mixed combination of VRV


and residential indoor
Technologies for efficient and quiet operation units is connected
Actual piping length a b c d
Swing compressor Smooth air inlet bell mouth and aero e f g Max.
spiral fan Max. 70 m First indoor branch
BP o 40 m
Daikin swing compressor has integrated the Max.
h i 15 m m
Max.
rotor with the blade, completely solving the The smooth air inlet bell mouth and the aero Equivalent piping length 30 m n BP
refrigerant leakage and the wear problem spiral fan work to minimize turbulence in the j
caused by the mechanical friction between the Max. 90 m
airflow and reduce sound.
rotor and the blade, which enhances the
RA RA VRV
k
Max.
compressor efficiency and makes the compressor Total piping length l 15 m
RA VRV

more quiet and durable.


Max. 250 m RA
DC fan motor
4 HP 5,6 HP
Efficiency improved in all areas compared to Refrigerant piping length (Equivalent) a+b+c+g+k, a+b+c+d 50 m (65 m) 70 m (90 m)
conventional AC motors, especially at low Max. allowable piping Total piping length a+b+c+d+e+f+g+h+i+j+k 250 m 250 m
length
speeds. The first indoor branch - the farthest BP or VRV indoor unit b+c+g, b+c+d 40 m 40 m
If indoor unit capacity index < 60 2 m–15 m 2 m–15 m
Swing Max. & min. BP unit -
allowable piping If indoor unit capacity index is 60 h, i, j, k 2 m–12 m 2 m–12 m
compressor indoor unit
length If indoor unit capacity index is 71 2 m–8 m 2 m–8 m
Min. allowable piping length Outdoor unit - the first indoor branch a 5m 5m

Between the indoor units l 10 m 15 m


Between BP units m 10 m 15 m
Max. allowable level
Outdoor unit - If the outdoor unit is above n 30 m 30 m
difference
the indoor unit If the outdoor unit is below n 30 m 30 m
Outdoor unit - the BP unit o 30 m 30 m

65 66
VRV IV S Series
Indoor Unit Lineup
Enhanced range of choices
A mixed combination of VRV indoor units and residential indoor units can be combined
into one system, opening the door to stylish and quiet indoor units.

VRV indoor units New lineup Residential indoor units with connection to BP units
20 25 32 40 50 63 71 80 100 125 140 25 35 50 60 71
Category

Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 Capacity Index 25 35 50 60 71

Round Flow Cassette

VRV IV S Series
FXFSQ-AVM FDKS-EAVMB
with Sensing
Ceiling Mounted Cassette

(700 mm width type)


Slim Ceiling Concealed Duct
Round Flow Cassette FXFQ-AVM
FDKS-C(A)VMB
(900/1,100 mm width type)
Compact Multi FXZQ-AVM
Flow Cassette
FTKS-DVM
Double Flow Cassette FXCQ-AVM
Wall Mounted FTKS-BVMA
Corner Cassette FXKQ-MAVE

3D Airflow Duct with FTKS-FVM


FXDSQ-AVM
Sensing
FXDQ-PDVE Note: BP units are necessary for residential indoor units.
(with drain pump)

FXDQ-PDVET (700 mm width type)


(without drain pump)
VRV indoor units combine with residential indoor units, all in one system.
Ceiling Concealed Duct

Slim Duct (Standard)


FXDQ-NDVE
(with drain pump)

FXDQ-NDVET (900/1,100 mm width type)


(without drain pump)

Slim Duct (Compact) FXDQ-SPV1 BP unit

Middle Static Pressure Duct FXSQ-PAVE


Max.
Middle-High Static Pressure Duct FXMQ-PAVE 9 indoor
units

Outdoor-Air Processing Unit FXMQ-MFV1 Residential indoor units VRV indoor units
Ceiling Suspended

4-Way Flow Ceiling Suspended FXUQ-AVEB

FXHQ-MAVE
Ceiling Suspended
FXHQ-AVM

Wall Mounted FXAQ-AVM

Floor Standing FXLQ-MAVE Max.


Floor Standing

Concealed Floor Standing FXNQ-MAVE


9 indoor
units

VRV indoor units only


Floor Standing Duct FXVQ-NY1

FXBQ-PVE * Refer to page 70 for the maximum number of connectable indoor units.
Clean Room Air Conditioner
FXBPQ-PVE

Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h

67 68
VRV IV S Series
Outdoor Units
VRV IV S Series
Specifications Outdoor unit combinations
MODEL RXMQ4AVE RXMQ5BVM RXMQ6BVM
kW 11.2 14.0 16.0

HP 4 5 6
Capacity index 100 125 150
MODEL RXMQ4AVE RXMQ5BVM RXMQ6BVM
50% 50 62.5 75
Power supply 1-phase, 220-230 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz Total capacity index
of connectable Combination (%) 100% 100 125 150
Btu/h 38,200 47,800 54,600 indoor units
Cooling capacity 130% 130 162.5 195

VRV IV S Series
kW 11.2 14.0 16.0
Maximum number of connectable indoor units 6 8 9
Power consumption kW 2.88 3.83 4.51 Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.

Capacity control % 24 to 100 15 to 100

Casing colour Ivory white (5Y7.5/1)

Type Hermetically sealed swing type


Compressor
Motor output kW 1.92 3.2 3.7

Airflow rate m3/min 76 81 80

Dimensions (H×W×D) mm 990×940×320

Machine weight kg 71 76 78

Sound level dB(A) 52 53 55

Operation range °CDB -5 to 46

Type R-410A
Refrigerant
Charge kg 2.9 3.4 4.0

Liquid 9.5 (Flare)


Piping connections mm
Gas 15.9 (Flare) 19.1 (Brazing)
Note: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27° CDB, 19° CWB, Outdoor temp.: 35° CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.

69 70
VRV IV Q Series

The VRV IV Q Series concept

For Quick & High Quality


Replacement Use Cooling Only
An automatic
6 HP – 48 HP
(16 kW) (135 kW) refrigerant charge
function enables
Reusing existing high quality installation Improvement
refrigerant piping in capacity
minimizes installation and greater number
time and cost of indoor units

VRV IV Q Series
Quick, quality and economical replacement
Reuse
Simple use of existing refrigerant piping
Special equipment and work is no longer required to clean pipes. A new function automatically deals
with contamination inside piping during refrigerant charging, eliminating the work involved in cleaning.

Even applicable for non-DAIKIN systems! The Daikin low-cost upgrade solution
Reuse drain pipes
Reuse refrigerant pipes
Pipes used for R-22 will also work with VRV IV Q series.
Standard Type Space Saving Type

Reuse refrigerant branch pipes


Single outdoor units Single outdoor units There are no restrictions when upgrading from a
RQQ6-16TYM(E) RQQ18-20TYM(E) Daikin VRV system. Other VRF systems require branch
pipes withstand pressure up to 3.3 MPa.

Reuse remote control and indoor-outdoor wiring


Double outdoor units Double outdoor units
Reuse wiring when upgrading from a Daikin VRV system.
RQQ18-32TNYM(E) RQQ30-40TSYM(E) In other cases, this will depend on the cable type.

Replace indoor units


Triple outdoor units Triple outdoor units
RQQ34-48TNYM(E) RQQ42-48TSYM(E)
Replace outdoor units
* (E) : anti-corrosion model

71 72
VRV IV Q Series
Benefits of System Replacement
Automatic Design flexibility
Refrigerant charging, cleaning Significantly more compact outdoor unit enables the effective use of limited space!
and test operation done with just a single switch.
Compact design enables the effective use
The automatic refrigerant charge function automates the charging of the proper refrigerant amount
and the closing of shut-off valves by simply pressing a switch after pre-charging.
of space taken up by existing machinery
Furthermore, there is no need to clean inside piping as this is handled automatically by the VRV IV Q
unit.
* There are conditions in the range (ambient temperature, connection ratio) in which the automatic refrigerant charge can be used. Refer to the installation manual for
Conventional
VRV K PLUS series: RX20K
VRV IV Q : RQQ20T
details. The refrigerant amount that can be automatically charged may differ from the additional refrigerant amount that is provided from calculations, but there are no
20 HP outdoor unit 20 HP outdoor unit
problems in performance and quality.

VRV IV Q Series
Installation space
VRV IV Q series
Time saving Conventional solution
for Replacement use 0.95 m2
Installation space
Enables smooth replacement 1 1
58%
Refrigerant recovery and units removal Refrigerant recovery and units removal
of air conditioning 2.25 m2
with less effect on operations less space
2 Removal of existing piping 2 Reuse of existing refrigerant piping 750 mm 765 mm
and users in the building. 3,005 mm 1,240 mm
Quicker
3 Installation of new piping and wiring 3 Carry-in and installation of units

4 Carry-in and installation of units 4 Airtightness test

Conventional
5 Airtightness test 5 Vacuum drying
High external static pressure 78.4 Pa VRV K series VRV IV Q
Refrigerant charge,
6 Vacuum drying
6 Automatic refrigerant pipe cleaning,
test operation

7 Refrigerant charging and volume measurement

Quicker Quicker and higher quality


49.0 Pa 78.4 Pa
8 Test operation installation

System flexibility
Cost saving Cost details (10 HP example) An increased number of connectable indoor units in a single system
Great reduction of work cost
By the reuse of existing piping, Approx.
35% of cost down Piping 40%
–35% More indoor units can be connected in a single system,
can be realized compared enabling consolidation of existing piping!
to installing new pipes.
10%
Equipment installation 10%
10%
Conventional VRV K PLUS series: RX24–30K VRV IV Q : RQQ40–48T
Duct 20%

30 64
20%
indoor units indoor units
Refrigerant charge 10%
Up to connectable Up to connectable
10%
Removal work 10%
8%
Curing 4%
4%
Overheads 6% 3%

New pipe installation VRV IV Q series


73 74
VRV IV Q Series
Benefits of System Replacement
Enables increased capacity New technology that enables use of existing piping
VRV IV Q series for replacement use enables the system capacity to be increased without changing New tested contamination collection method
VRV IV Q series only
the refrigerant piping. For example, it is possible to install a 16 HP VRV IV Q series using the refrigerant A new method collects contamination from existing piping,
piping of an 10 HP R-22 system. eliminating compressors and electric valves malfunction.

Acid Impurities Iron powder


An acid neutraliser agent is added to A generously sized filter is provided A magnet is installed inside the
Pipe size: 28.6, 12.7 disable acids (chlorine ions), which inside the refrigerant circuit which traps accumulator where liquid refrigerant
Before replacement cause corrosion. impurities. accumulates.

10 HP
The magnet attracts iron powder to

2.5 HP×4 units Acid (chlorine ion) Refrigerant


keep the system clean.

flow

Acid Filter Accumulator


neutraliser Iron
powder
Iron powder,
etc
Reuse of existing piping

VRV IV Q Series
Impurities

Refrigerant pipe To
After replacement Pipe size: 28.6, 12.7 Magnet compressor

VRV IV Q Series
4.0 HP×4 units
16 HP
Reliable and stable technology
Replace Replace High reliability at high ambient temperatures

PCB

Power Module
Heat Refrigerant Jacket
Energy saving Refrigerant
Refrigerant
81% increase
(Compared with 8 HP model of VRV K(A) ) Using refrigerant to cool the inverter power
Higher Energy Efficiency Ratio (EER) module helps minimise the size of the
Control board failure ratio at stable operation is reduced.
5.0
VRV IV Q series delivers 4.41 4.32 electronic components, and this results in
Cooling Operation EER

4.07 reduction of airflow resistance and high This enables


highly efficient performance, 4.0 3.80 3.74
3.46 efficiency of the heat exchanger.
contributing to high energy savings. 3.25 3.11
3.0
• Suitability for high ambient temperatures
• Miniaturization of electronic components
* Cooling operation conditions: 2.0
Indoor temp. of 27º CDB, 19º CWB, and outdoor temp. of 35º CDB.

1.0 SMT* packaging technology Computer control board surface adopting SMT packaging technology

• Improves the anti-clutter performance. SMT packaging material


0
6 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP • Protects your computer boards from the adverse
effects of sandy climates and humid weather.
VRV K(A): RSX-K(A) VRV II: RX-M VRV IV Q Series
*SMT: Surface mounted technology
Computer control board

ODM (Outer Type) UNIQUE


VRT Control for optimal annual efficiency Outer Rotor DC Motor (ODM) Conventional Motor
(Inner Type)
Rotor
VRT automatically adjusts refrigerant temperature to individual building Only Daikin has adapted an ODM Rotor HIGH TORQUE
and climate requirement, thus further improving annual energy efficiency with the feature of stable rotation and with low energy
F
and maintaining comfort. volumetric efficiency.
F
MORE efficient

75 76
Guidelines for Reuse of VRV IV Q Series
Existing Refrigerant Piping
Piping limits for reuse of existing piping Reusability of existing piping for VRV IV Q series
Piping size
Type of piping Capacity Liquid Gas
Single use 6.4 9.5 12.7 15.9 19.1 22.2 12.7 15.9 19.1 22.2 25.4 28.6 34.9 41.3 54.1
6 HP X S X X X X S X X X
8 HP X S X X X X S X X X
Actual piping length 10 HP X S X X X X X S X X X
a 12 HP X X S X X X X X X X S X X
f g h 14 HP X X S X X X X X X X S X X
Max. 150 m 16 HP X X S X X X X X X X S X X
18 HP X X X S X X X X X X S X X
First indoor branch
b c d e i 20 HP X X X S X X X X X X S X X
22 HP X X X S X X X X X X S X X
24 HP X X X S X X X X X X X S X
r Main piping 26 HP
28 HP
X
X
X
X
X
X
X
X
S
S
X
X
X
X
X
X
X
X
X
X
X
X
S
S
X
X
30 HP X X X X S X X X X X X S X
32 HP X X X X S X X X X X X S X
s 34 HP X X X X S X X X X X X S X
Equivalent piping length 36 HP X X X X S X X X X X X X S
38 HP X X X X S X X X X X X X S

VRV IV Q Series
40 HP X X X X S X X X X X X X S
Max. 175 m Colours in the diagram above are merely for identifying pipes referenced with symbols such as a . 42 HP
44 HP
X
X
X
X
X
X
X
X
S
S
X
X
X
X
X X X
X
X
X
X
X
S
S
X X
46 HP X X X X S X X X X X X X S
48 HP X X X X S X X X X X X X S
< 100 X S X X X X S X X X X X X
100 ≤ X < 150 X S X X X X S X X X X X X
Multiple use 150 ≤ X < 160 X S X X X X X S X X X X
160 ≤ X < 200 X S X X X X X S X X X X
From 200 ≤ X < 290 X S X X X X X S X X X
k REFNET
290 ≤ X < 330 X X S X X X X X X S X X
Total piping length to REFNET *1
330 ≤ X < 420 X X
X
S
X
X X
X
X
X
X
X
X X X
X
S X X
420 ≤ X < 480 X S X X S X X
480 ≤ X < 640 X X X S X X X X X X S X X
Max. 300 m q 640 ≤ X < 900
900 ≤ X < 920
X
X
X
X
X
X
X
X
S
S
X
X
X
X
X
X
X
X
X
X
X
X
S
S
920 ≤ X X X X S X X X X X X X S
First 20–40 class S X X X X S X X X X X X X
indoor branch 50 class S X X X X S X X X X X X X
63-80 class X S X X X X S X X X X X X
p a f From 100–125 class X S X X X X S X X X X
REFNET 140 class X S X X X X S X X X X
First outdoor branch b to indoor unit*2 200 class
250 class
X
X
S
S
X
X
X
X
X
X
X
X
X
X
S
X S
X
X
X
X
X
X
400 class X X S X X X X X X X S X X
*The rest of indoor units are the same as for single use. X X X X X X X X X X
500 class S S
: Piping size of conventional R-22 model
: Piping size of conventional R-410A model
S : Standard piping size of VRV IV Q series
: Possible
: Standard piping size of VRV IV Q series. However, when equivalent piping length between outdoor unit and indoor unit is 90 m or more, size of main piping must be increased.
Piping length Example X : Not possible

Actual refrigerant piping length (Equivalent) 150 m (175 m) a+f+g+h+i *1 Piping between REFNETs depends on total capacity index of indoor units connected below each REFNET. It cannot exceed piping size of upstream side.
Maximum Total piping length 300 m a+b+c+d+e+f+g+h+i
*2 Piping from REFNET to indoor unit depends on the capacity of the connected indoor unit. It cannot exceed piping size of upstream side.

allowable
Between the first indoor branch and the farthest indoor unit 40 m f+g+h+i
piping length
Between the outdoor branch and the last outdoor unit (Equivalent) 10 m (13 m) k+p

Level Difference Example

Between the outdoor units (Multiple use) 5m q


Maximum Between the indoor units 15 m s
allowable
Between the outdoor units If the outdoor unit is above. 50 m r
level difference
and the indoor units If the outdoor unit is below. 40 m r

77 78
VRV IV Q Series
Outdoor Unit Lineup Indoor Unit Lineup
VRV IV Q Series
Enhanced lineup to 2 types Wide variety of indoor units
25 35 50 60 New lineup

Lineup 20 25 32 40 50 63 71 80 100 125 140 200 250 400 500

Category
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP
HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500
Standard Type
VRV IV Q Round Flow Cassette
Series FXFSQ-AVM
Space Saving Type with Sensing

Ceiling Mounted Cassette


Round Flow Cassette FXFQ-AVM
Outdoor unit combinations Compact Multi
FXZQ-AVM
Standard Type Flow Cassette

Capacity Outdoor unit multi Total capacity index of Maximum number of


HP kW Model name Combination Double Flow Cassette FXCQ-AVM
index connection piping kit*1 connectable indoor units*3 connectable indoor units*2
6 16.0 150 RQQ6T RQQ6T — 75 to 195 9

VRV IV Q Series
— Corner Cassette FXKQ-MAVE
8 22.4 200 RQQ8T RQQ8T 100 to 260 13
10 28.0 250 RQQ10T RQQ10T — 125 to 325 16
3D Airflow Duct with
12 33.5 300 RQQ12T RQQ12T — 150 to 390 19 FXDSQ-AVM
Sensing
14 40.0 350 RQQ14T RQQ14T — 175 to 455 22
FXDQ-PDVE
16 45.0 400 RQQ16T RQQ16T — 200 to 520 26 (with drain pump)

18 50.4 450 RQQ18TN RQQ8T + RQQ10T 225 to 585 29 FXDQ-PDVET (700 mm width type)
(without drain pump)
20 55.9 500 RQQ20TN RQQ8T + RQQ12T 250 to 650 32 Slim Duct (Standard)
FXDQ-NDVE

Ceiling Concealed Duct


22 61.5 550 RQQ22TN RQQ10T + RQQ12T 275 to 715 35 (with drain pump)

24 67.0 600 RQQ24TN RQQ12T × 2 300 to 780 39 FXDQ-NDVET (900/1,100 mm width type)
BHFP22P100 (without drain pump)
26 73.5 650 RQQ26TN RQQ12T + RQQ14T 325 to 845 42
28 78.5 700 RQQ28TN RQQ12T + RQQ16T 350 to 910 45 Slim Duct (Compact) FXDQ-SPV1
30 85.0 750 RQQ30TN RQQ14T + RQQ16T 375 to 975 48
32 90.0 800 RQQ32TN RQQ14T + RQQ18T 400 to 1,040 52 Middle Static
FXSQ-PAVE
34 850 425 to 1,105 55 Pressure Duct
95.0 RQQ34TN RQQ10T + RQQ12T × 2
36 101 900 RQQ36TN RQQ12T × 3 450 to 1,170 58 Middle-High Static Pressure Duct FXMQ-PAVE
38 106 950 RQQ38TN RQQ8T + RQQ12T + RQQ18T 475 to 1,235 61
40 112 1,000 RQQ40TN RQQ12T × 2 + RQQ16T 500 to 1,300 High Static Pressure Duct FXMQ-PVM
BHFP22P151
42 119 1,050 RQQ42TN RQQ12T + RQQ14T + RQQ16T 525 to 1,365 Outdoor-Air Processing Unit FXMQ-MFV1
44 124 1,100 RQQ44TN RQQ12T + RQQ16T × 2 550 to 1,430 64
4-Way Flow Ceiling

Ceiling Suspended
46 130 1,150 RQQ46TN RQQ14T × 2 + RQQ18T 575 to 1,495 FXUQ-AVEB
Suspended
48 135 1,200 RQQ48TN RQQ14T + RQQ16T + RQQ18T 600 to 1,560
Notes: *1. For multiple connection of 18 HP systems and above, the outdoor unit multi connection piping kit (separately sold) is required. FXHQ-MAVE
*2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor units. Ceiling Suspended
*3. When outdoor-air processing units and standard indoor units are connected, the total connection capacity index of the outdoor-air processing units
must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
FXHQ-AVM

Wall Mounted FXAQ-AVM


Space Saving Type
Capacity Outdoor unit multi Total capacity index of Maximum number of Floor Standing FXLQ-MAVE
HP kW Model name Combination

Floor Standing
index connection piping kit*1 connectable indoor units*3 connectable indoor units*2
Concealed Floor Standing FXNQ-MAVE
18 50.0 450 RQQ18T RQQ18T – 225 to 585 29
20 56.0 500 RQQ20T RQQ20T – 250 to 650 32 FXVQ-NY1
30 83.5 750 RQQ30TS RQQ12T + RQQ18T 375 to 975 48 Floor Standing Duct
FXVQ-NY16
32 89.5 800 RQQ32TS RQQ12T + RQQ20T 400 to 1,040 52 (high static pressure type)

34 95.0 850 RQQ34TS RQQ16T + RQQ18T 425 to 1,105 55 Heat Reclaim Ventilator
VKM-GCVE Airflow rate 500-950 m3/h
BHFP22P100 with DX-Coil
36 100 900 RQQ36TS RQQ18T x 2 450 to 1,170 58
38 106 950 RQQ38TS RQQ18T + RQQ20T 475 to 1,235 61 Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h
40 112 1,000 RQQ40TS RQQ20T x 2 500 to 1,300
42 117 1,050 RQQ42TS RQQ12T x 2 + RQQ18T 525 to 1,365
44 123 1,100 RQQ44TS RQQ12T x 2 + RQQ20T 550 to 1,430 64
BHFP22P151
46 129 1,150 RQQ46TS RQQ12T + RQQ16T + RQQ18T 575 to 1,495
48 134 1,200 RQQ48TS RQQ12T + RQQ18T x 2 600 to 1,560
Notes: *1. For multiple connection of 30 HP and above the outdoor unit multi connection piping kit (separately sold) is required.
*2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor units.
*3. When outdoor-air processing units and standard indoor units are connected, the total connection capacity index of the outdoor-air processing units
79 must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%. 80
VRV IV Q Series
Outdoor Units
VRV IV Q Series
Specifications
Standard Type

MODEL RQQ6TYM(E) RQQ8TYM(E) RQQ10TYM(E) RQQ12TYM(E) RQQ14TYM(E) RQQ16TYM(E) RQQ18TNYM(E) RQQ20TNYM(E) RQQ22TNYM(E) RQQ24TNYM(E) RQQ26TNYM(E) RQQ28TNYM(E) RQQ30TNYM(E) RQQ32TNYM(E)
RQQ8TYM(E) RQQ8TYM(E) RQQ10TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ14TYM(E) RQQ14TYM(E)
Combination units — — — — — — RQQ10TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ14TYM(E) RQQ16TYM(E) RQQ16TYM(E) RQQ18TYM(E)
— — — — — — — —
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 54,600 76,400 95,500 114,000 136,000 154,000 172,000 191,000 210,000 229,000 251,000 268,000 290,000 307,000
Cooling capacity
kW 16.0 22.4 28.0 33.5 40.0 45.0 50.4 55.9 61.5 67.0 73.5 78.5 85.0 90.0
Power consumption kW 3.63 5.18 6.88 8.82 10.7 13.0 12.1 14.0 15.7 17.6 19.5 21.8 23.7 26.1
Capacity control % 20-100 16-100 15-100 11-100 10-100 8-100 6-100 5-100

VRV IV Q Series
Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Compressor (3.4X1)+ (3.4X1)+ (4.1X1)+ (5.2X1)+ (5.2X1)+(2.9X1)+ (5.2X1)+(3.6X1)+ (2.9X1)+(3.3X1)+ (2.9X1)+(3.3X1)+
Motor output kW 2.4X1 3.4X1 4.1X1 5.2X1 (2.9X1)+(3.3X1) (3.6X1)+(3.7X1)
(4.1X1) (5.2X1) (5.2X1) (5.2X1) (3.3X1) (3.7X1) (3.6X1)+(3.7X1) (4.4X1)+(4.0X1)
Airflow rate m³/min 119 157 165 178 233 233 157+165 157+178 165+178 178+178 178+233 233+233
Dimensions (H×W×D) mm 1,657X930X765 1,657X1,240X765 (1,657X930X765)+(1,657X930X765) (1,657X930X765)+(1,657X1,240X765) (1,657X1,240X765)+(1,657X1,240X765)
Machine weight kg 185 195 285 185+195 195+195 195+285 285+285
Sound level dB(A) 55 56 57 59 60 61 60 61 62 63 64
Operation range ºCDB -5 to 49 -5 to 49
Type R-410A R-410A
Refrigerant
Charge kg 5.9 6.0 6.3 10.3 10.4 5.9+6.0 5.9+6.3 6.0+6.3 6.3+6.3 6.3+10.3 6.3+10.4 10.3+10.4 10.3+10.5
Piping Liquid mm 9.5(Brazing) 12.7(Brazing) 15.9(Brazing) 19.1(Brazing)
connections 22.2(Brazing) 28.6(Brazing) 28.6(Brazing) 34.9(Brazing)
Gas mm 19.1(Brazing)

Space Saving Type

MODEL RQQ34TNYM(E) RQQ36TNYM(E) RQQ38TNYM(E) RQQ40TNYM(E) RQQ42TNYM(E) RQQ44TNYM(E) RQQ46TNYM(E) RQQ48TNYM(E) MODEL RQQ18TYM(E) RQQ20TYM(E)
RQQ10TYM(E) RQQ12TYM(E) RQQ8TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ14TYM(E) RQQ14TYM(E)
Combination units RQQ12TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ14TYM(E) RQQ16TYM(E) RQQ14TYM(E) RQQ16TYM(E) Combination units — —
RQQ12TYM(E) RQQ12TYM(E) RQQ18TYM(E) RQQ16TYM(E) RQQ16TYM(E) RQQ16TYM(E) RQQ18TYM(E) RQQ18TYM(E)
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 324,000 345,000 362,000 382,000 406,000 423,000 444,000 461,000 Btu/h 171,000 191,000
Cooling capacity Cooling capacity
kW 95.0 101 106 112 119 124 130 135 kW 50.0 56.0
Power consumption kW 24.5 26.5 29.4 30.6 32.5 34.8 36.8 39.1 Power consumption kW 15.4 18.0
Capacity control % 5-100 4-100 3-100 Capacity control % 10-100 8-100
Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Type Hermetically Sealed Scroll Type

Compressor
(5.2X1)+(2.9X1)+ (5.2X1)+(3.6X1)+ (2.9X1)+(3.3X1)+ (2.9X1)+(3.3X1)+ Compressor
(4.1X1)+(5.2X1)+ (5.2X1)+(5.2X1)+ (3.4X1)+(5.2X1)+ (5.2X1)+(5.2X1)+
Motor output kW (3.3X1)+(3.6X1)+ (3.7X1)+(3.6X1)+ (2.9X1)+(3.3X1)+ (3.6X1)+(3.7X1)+ Motor output kW (4.4X1)+(4.0X1) (4.6X1)+(5.5X1)
(5.2X1) (5.2X1) (4.4X1)+(4.0X1) (3.6X1)+(3.7X1)
(3.7X1) (3.7X1) (4.4X1)+(4.0X1) (4.4X1)+(4.0X1)
Airflow rate m³/min 165+178+178 178+178+178 157+178+233 178+178+233 178+233+233 233+233+233 Airflow rate m³/min 233 268

Dimensions (H×W×D) mm (1,657X930X765)+(1,657X930X765)+ (1,657X930X765)+(1,657X930X765)+ (1,657X930X765)+(1,657X1,240X765)+ (1,657X1,240X765)+(1,657X1,240X765)+


Dimensions (H×W×D) mm 1,657X1,240X765
(1,657X930X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765)
Machine weight kg 195+195+195 195+195+195 185+195+285 195+195+285 195+285+285 285+285+285 Machine weight kg 285 320
Sound level dB(A) 63 64 65 66 Sound level dB(A) 62 65
Operation range ºCDB -5 to 49 -5 to 49 Operation range ºCDB -5 to 49
Type R-410A R-410A Type R-410A
Refrigerant Refrigerant
Charge kg 6.0+6.3+6.3 6.3+6.3+6.3 5.9+6.3+10.5 6.3+6.3+10.4 6.3+10.3+10.4 6.3+10.4+10.4 10.3+10.3+10.5 10.3+10.4+10.5 Charge kg 10.5 11.8
Piping Liquid mm 19.1(Brazing) 19.1(Brazing) Piping Liquid mm 15.9(Brazing)
connections Gas mm 34.9(Brazing) 41.3(Brazing) 41.3(Brazing) connections Gas mm 28.6(Brazing)
Notes: 1. Models with (E) are the outdoor units with anti-corrosion specifications. Please refer to Engineering Data Book for details.
2. Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27° CDB, 19° CWB, Outdoor temp.: 35° CDB, E quivalent piping length: 7.5 m, Level difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
81 During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. 82
When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
VRV IV Q Series
Outdoor Units
VRV IV Q Series
Specifications
Space Saving Type

MODEL RQQ30TSYM(E) RQQ32TSYM(E) RQQ34TSYM(E) RQQ36TSYM(E) RQQ38TSYM(E) RQQ40TSYM(E) RQQ42TSYM(E) RQQ44TSYM(E) RQQ46TSYM(E) RQQ48TSYM(E)
RQQ12TYM(E) RQQ12TYM(E) RQQ16TYM(E) RQQ18TYM(E) RQQ18TYM(E) RQQ20TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ12TYM(E)
Combination units RQQ18TYM(E) RQQ20TYM(E) RQQ18TYM(E) RQQ18TYM(E) RQQ20TYM(E) RQQ20TYM(E) RQQ12TYM(E) RQQ12TYM(E) RQQ16TYM(E) RQQ18TYM(E)
— — — — — — RQQ18TYM(E) RQQ20TYM(E) RQQ18TYM(E) RQQ18TYM(E)
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 285,000 305,000 324,000 341,000 362,000 382,000 399,000 420,000 440,000 457,000
Cooling capacity
kW 83.5 89.5 95.0 100 106 112 117 123 129 134
Power consumption kW 24.2 26.8 28.4 30.8 33.4 36.0 33.0 35.6 37.2 39.6
Capacity control % 6-100 5-100 4-100

VRV IV Q Series
Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Compressor (5.2×1)+(4.4×1)+ (5.2×1)+(4.6×1)+ (3.6×1)+(3.7×1)+ (4.4×1)+(4.0×1)+ (4.4×1)+(4.0×1)+ (4.6×1)+(5.5×1)+ (5.2×1)+(5.2×1)+ (5.2×1)+(5.2×1)+ (5.2×1)+(3.6×1)+(3.7×1)+ (5.2×1)+(4.4×1)+(4.0×1)+
Motor output kW
(4.0×1) (5.5×1) (4.4×1)+(4.0×1) (4.4×1)+(4.0×1) (4.6×1)+(5.5×1) (4.6×1)+(5.5×1) (4.4×1)+(4.0×1) (4.6×1)+(5.5×1) (4.4X1)+(4.0×1) (4.4×1)+(4.0×1)
Airflow rate m³/min 178+233 178+268 233+233 233+268 268+268 178+178+233 178+178+268 178+233+233

Dimensions (H×W×D) mm (1,657×930X765)+(1,657×1,240X765) (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765) (1,657×930×765)+(1,657×930×765)+ (1,657×930×765)+(1,657×1,240×765)+


(1,657×1,240×765) (1,657×1,240×765)
Machine weight kg 195+285 195+320 285+285 285+320 320+320 195+195+285 195+195+320 195+285+285
Sound level dB(A) 64 66 65 67 68 65 67 66
Operation range ºCDB -5 to 49 -5 to 49
Type R-410A R-410A
Refrigerant
Charge kg 6.3+10.5 6.3+11.8 10.4+10.5 10.5+10.5 10.5+11.8 11.8+11.8 6.3+6.3+10.5 6.3+6.3+11.8 6.3+10.4+10.5 6.3+10.5+10.5
Piping Liquid mm 19.1(Brazing) 19.1(Brazing)
connections Gas mm 34.9(Brazing) 41.3(Brazing) 41.3(Brazing)
Notes: 1. Models with (E) are the outdoor units with anti-corrosion specifications. Please refer to Engineering Data Book for details. • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
2. Specifications are based on the following conditions; During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise to the
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.

83 84
VRV IV W Series

Water Cooled System Suitable


for Tall Multi-Storied Buildings Cooling Only
• Water cooled system does not require
6 HP – 36 HP
(16 kW) (101 kW)
to exchange heat with outdoor air Cooling tower (closed type)

• Outside units can be installed indoors.


• The air conditioning operation is stable even
when the outdoor air temperature is high
Indoor unit
Refrigerant
piping

• Individual air conditioning is achieved Water piping


via on-demand operation in each room.
• The length of the refrigerant piping can
be minimized by installing outside units
in proximity to indoor units.
• As refrigerant piping is connected to
indoor units, it reduces the risks of

VRV IV W Series
indoor water leakage. Outside unit

High installation
Design flexibility
flexibility

Design flexibility
No balcony required

High-rise buildings Condominiums and Underground shopping


Single outdoor units
Compact outside units can be detached houses malls and subway
RWEYQ6-12TYM easily installed in the machine We offer an extensive lineup of As heat exchanging with
rooms on each floor. It is small capacity outside units as outdoor air is not required,
Double outdoor units adaptable to high-rise buildings. well as connectable residential individual air conditioning can
RWEYQ14-24TYM indoor units. be easily provided.

r pipe ter pipe


Wate Wa
Triple outdoor units
RWEYQ26-36TYM
Water inflow
Water outflow
Refrigerant liquid pipe
Refrigerant gas pipe
Min. 300 mm
Celling height
Min. 3,200 mm

(100-300 mm)

(300-400 mm)
ipe
in p
Dra
* Only for the purpose of illustration.

85 86
VRV IV W Series
Water Cooled VRV IV as a Retrofit Solution
A flexible system convenient for expansion/renovation
Problems with existing water systems can Easy Installation
Individual air conditioning comfort can be realized when
be solved with minimal construction work. and where it is actually required.

Indoor installation solves the puzzle Independent control provides greater comfort and convenience.
of proper placement of outdoor units Each indoor unit can be Large meeting room: Office: 26°C, General manager office: 27°C,
It is possible to place the outside unit inside the building, it makes easier independently controlled and OFF high air volume low air volume
to adapt to different type of buildings and open to various kinds of adjusted according to each
creative building exteriors. tenant’s individual needs for
temperature and air volume. Meeting room Office

Based on cooling condition


Part of the old system can be retained Cost Saving
The water cooled VRV IV W series can Retained cooling
tower
retain the cooling tower and boiler of the Higher efficiency with partial load
old system during renovation, effectively

VRV IV W Series
Actual conditions of the floor
keeping costs down. During actual operation, the load of an air
conditioning system changes according to
variations in weather conditions outside
and indoor unit operation rates. Daikin’s
advanced DC inverter technology and
Before renovation After renovation advanced refrigerant control technology
boasts a higher efficiency under partial
*System diagram
load than in the rated operating
conditions.
The compact outside units facilitate the renovation process Space Saving
Air conditioning of the meeting
room is normally switched off

• The outside units are conveniently


compact so transport by elevator is Cooling tower Cooling tower
Saving more
possible. It also effectively simplifies space for
installation. This also saves a great deal other purposes Flexibly satisfies conditions for working overtime and times of insufficient load
of time and labor. Each indoor unit can be independently controlled and adjusted according to each tenant’s individual
• The modular design enables a free and needs for temperature and air volume.
flexible configuration of the outside
• Inconvenient transportation procedures are eliminated.
units. Also can save space for other • Operation for each indoor unit can be precisely and individually set.
Garage
purposes.
Outside units take up a
disproportionately large amount of
Example of air conditioning control for different rooms of the same floor
Can save space
space for installation.
8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00

Workdays During normal work hours, the building's central air conditioner is used
During overtime hours,
the water cooled
Office
Floor by floor renovation without disturbing other tenants Flexible Renovation
VRV IV W series operates

The water cooled VRV IV W series is utilised to meet overtime work needs
Because equipment can be replaced in Renovation in
phases, installation adapts to the phases is possible. Weekends At weekends, the water cooled VRV IV W series operates
renovation plans of the customers and Phase 1
General manager's office
ensures that work performed on some Pump The water cooled VRV IV W series is utilised to meet weekend work needs
Phase 2
floors and zones will not affect other Cold
Pump Phase 3
tenants. source
supply Both the building's central air conditioner
Cooling and the water cooled VRV IV W series operate
tower Meeting Room
Cold
Plate heat * System diagram
source
back-flow exchanger When a large number of people are present, the water cooled VRV IV W series can work
to supplement insufficient capacity of the building's central air conditioner
Water cooled VRV IV W series
87 88
VRV IV W Series
Easy Installation & Energy Saving
Compact and lightweight Enhanced lineup

Compact
Design

1,000 mm

Footprint :
0.43 m 2 Wider capacity
range from 6 to 36 HP
146 kg
Product Weight : 550 mm
(*For 6 HP, 8 HP)
780 mm 6 HP, 8 HP, 10 HP, 12 HP

VRV IV W Series
6, 8, 10, 12 HP 14, 16, 18, 20, 22, 24 HP 26, 28, 30, 32, 34, 36 HP

DTA104A62
Enhanced usability
Interlocking
Centralised interlocking function
Centralised interlocking input operate by using RWEYQ6TYM RWEYQ10TYM RWEYQ14TYM RWEYQ20TYM RWEYQ26TYM RWEYQ32TYM
an external control adaptor (DTA104A62). RWEYQ8TYM RWEYQ12TYM RWEYQ16TYM RWEYQ22TYM RWEYQ28TYM RWEYQ34TYM
RWEYQ18TYM RWEYQ24TYM RWEYQ30TYM RWEYQ36TYM

Energy saving
Control wiring
(external-to-external transmission wiring) Higher Energy Efficiency Ratio (EER) VRT control for optimal annual efficiency
Cooling Operation EER VRT automatically adjusts refrigerant
temperature to individual building and climate
VRV III W series
VRV IV W Series 18% requirement, thus further improving annual
Increase
16% energy efficiency and maintaining comfort.
Using one external control adaptor circuit 6.20 Increase
6.00 5.80
board makes centralised interlocking input to
multiple units within the same water system 5.00 5.16
4.57
possible.
4.00

3.00

2.00

1.00

0
6 HP 8 HP 10 HP 12 HP
*Cooling : Indoor temp.: 27ºCDB, 19ºCWB/inlet water temp.: 30ºC,
Equivalent piping length: 7.5 m, Level difference: 0 m.

89 90
VRV IV W Series
Flexible System Design
Long piping length
Installation for VRV indoor units only Installation for residential indoor units only

Actual piping length Actual piping length


Single use Single use only
Max. 120 m Max. 100 m

a
Equivalent piping length f g h Equivalent piping length b
a e Max.
o 40 m
Max. 140 m First indoor branch b c d e Max. 120 m First indoor branch BP unit
i
n 50 m
Max. h i Max.
m 15 m
r BP unit
Total piping length Total piping length
RA RA

VRV IV W Series
Max.
Max. 300 m s Max. 200 m Max. k P 5m
l 15 m RA
RA: Residential indoor unit
RA
*Colours in the diagram above are merely for identifying pipes referenced with symbols such as a . *Colours in the diagram following are merely for identifying pipes referenced with symbols such as a .

Actual Equivalent Actual Equivalent


Example Example
piping length piping length piping length Example piping length
Refrigerant piping length 120 m a+f+g+h+i 140 m Max. Refrigerant piping length 100 m a+b+k 120 m
Max. Total piping length 300 m a+b+c+d+e+f+g+h+i — allowable Total piping length 200 m a+b+e+h+j+k —
allowable piping length
Between the first indoor branch and the farthest indoor unit 90 m*1 f+g+h+i — Between the first indoor branch and the farthest indoor unit 50 m*1 b+k —
piping length
Between the first outside branch and the last outside unit 10 m k+p 13 m Max. and min. If indoor unit capacity index < 60 2 m - 15 m h,i,j,k —
Between BP unit and
Between the outside units (multiple use) 2m q — allowable If indoor unit capacity index is 60 2 m - 12 m h,i,j,k —
Max. piping length indoor unit
Between the indoor units 15 m s — If indoor unit capacity index is 71 2m-8m h,i,j,k —
allowable
level difference Between the outside units If the outside unit is above. 50 m r — Between the outside unit If the outside unit is above. 50 m n —
and the indoor units If the outside unit is below. 40 m r — and the indoor unit If the outside unit is below. 40 m n —
Max.
*1 No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. The VRV IV W series is easy to extend to 90 m by Between the indoor units 15 m l —
lessening the conditions from conventional VRV III W models. Be sure to refer to the Engineering Data Book for details of these conditions and requirements. allowable
level difference Between the outside unit and the BP unit 40 m o —
Between BP units 15 m m —
Between the BP unit and the indoor unit 5m p —
*1. When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased.
Please refer to Engineering Data Book for details.

Multiple use

q
First
indoor branch

p a f
First outdoor branch b
*The rest of indoor units are the same as for single use.

91 92
VRV IV W Series
Advanced Technologies Outside Unit Lineup
VRV IV W Series
High efficiency compressor to achieve a SMT* packaging technology
high performance Lineup
• Improves the anti-clutter performance.
The reluctance DC motor uses 2 • Protects your computer boards from the
different types of torque, adverse effects of sandy climates and humid Capacity HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
neodymium magnet and weather. Range
16.0 22.4 28.0 33.5 38.4 44.8 50.4 56.0 61.5 67.0 72.8 78.4 84.0 89.5 95.0 101
kW
reluctance torque. It generates *SMT: Surface mounted technology VRV IV W SERIES
more power with a smaller
electric power and saves energy. Computer control board surface adopting SMT packaging
technology

SMT packaging material


Reluctance DC motor

Outside unit combinations


Computer control board
For connection of only VRV indoor units
Capacity Total capacity index of Maximum number of
HP kW Model Combination

VRV IV W Series
index connectable indoor units*2 connectable indoor units

16.0 150 RWEYQ6T RWEYQ6T × 1 75 to 195 9


Minimize performance degradation from Function of information display 6
8 22.4 200 RWEYQ8T RWEYQ8T × 1 100 to 260 13
refrigeration oil in all stages of operation by luminous digital tube 10 28.0 250 RWEYQ10T RWEYQ10T × 1 125 to 325 16
12 33.5 300 RWEYQ12T RWEYQ12T × 1 150 to 390 19
Surplus oil is stored in the Oil separator VRV IV W series utilises a 7-segment digital display
14 38.4 350 RWEYQ14T*1 RWEYQ6T + RWEYQ8T 175 to 455 22
receiver and automatically bright 7-segment digital
Compressor 16 44.8 400 RWEYQ16T*1 RWEYQ8T × 2 200 to 520 26
controls the amount of display to convey 18 50.4 450 RWEYQ18T*1 RWEYQ8T + RWEYQ10T 225 to 585 29
refrigeration oil in the operational status and 20 56.0 500 RWEYQ20T*1 RWEYQ10T × 2 250 to 650 32
refrigerant cycle. facilitate simple 22 61.5 550 RWEYQ22T*1 RWEYQ10T + RWEYQ12T 275 to 715 35
This prevents a reduction in installation and after-sales 24 67.0 600 RWEYQ24T*1 RWEYQ12T × 2 300 to 780 39
performance for heat service. Displays system operation 26 72.8 650 RWEYQ26T*1 RWEYQ8T × 2 + RWEYQ10T 325 to 845 42
exchanger. information directly 28 78.4 700 RWEYQ28T*1 RWEYQ8T + RWEYQ10T × 2 350 to 910 45
New oil receiver 30 84.0 750 RWEYQ30T*1 RWEYQ10T × 3 375 to 975 48
32 89.5 800 RWEYQ32T*1 RWEYQ10T × 2 + RWEYQ12T 400 to 1,040 52
34 95.0 850 RWEYQ34T*1 RWEYQ10T + RWEYQ12T × 2 425 to 1,105 55
101 900 RWEYQ36T*1 RWEYQ12T × 3 450 to 1,170 58
Automatic sequencing operation 36
*1. An outside unit multi connection piping kit (option) is necessary for multiple connections of 14 HP systems and above.
Priority Priority *2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outside units.
Priority 1 2 3 3 1 2 2 3 1
For connection of only residential indoor units
Total capacity index of connectable indoor units*2
Automatic Automatic Capacity Maximum number of
sequencing sequencing Model name*1 kW HP Combination (%)*2
index connectable indoor units
50%* 2
100% 130%
Stage 1 Stage 2 Stage 3
RWEYQ6T 16.0 6 150 75 150 195 9
RWEYQ8T 22.4 8 200 100 200 260 13
RWEYQ10T 28.0 10 250 125 250 325 16
Auto-restart technology RWEYQ12T 33.5 12 300 150 300 390 19
power supply *1. Only single outside unit (RWEYQ6-12T) can be connected.
Power interruption Keep a record of the recovers Restore itself back into the *2. Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outside unit.

during normal operation operating mode adopted recorded operating status

Refrigerant pressure detection technology


• Utilizes temperature sensors to detect the system’s operating status.
• Employs high and low pressure sensors to carry out quick, comprehensive and accurate detection of
the refrigerant status.
93 94
VRV IV W Series
Indoor Unit Lineup
Enhanced range of choices
VRV indoor units New lineup Residential indoor units with connection to BP units
20 25 32 40 50 63 71 80 100 125 140 200 250 400 500 25 35 50 60 71
Category

Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 Capacity Index 25 35 50 60 71
Round Flow Cassette
FXFSQ-AVM
with Sensing FDKS-EAVMB
Ceiling Mounted Cassette

(700 mm width type)


Slim Ceiling Concealed Duct
Round Flow Cassette FXFQ-AVM
FDKS-C(A)VMB
(900/1,100 mm width type)
Compact Multi FXZQ-AVM
Flow Cassette
FTKS-DVM
Double Flow Cassette FXCQ-AVM

Wall Mounted FTKS-BVMA


Corner Cassette FXKQ-MAVE

3D Airflow Duct with FTKS-FVM


FXDSQ-AVM
Sensing
FXDQ-PDVE Note: BP units are necessary for residential indoor units. Only single outside unit (RWEYQ6-12T) can be connected.
(with drain pump)

VRV IV W Series
FXDQ-PDVET
(without drain pump)
(700 mm width type)
Slim Duct (Standard)
FXDQ-NDVE
Ceiling Concealed Duct

(with drain pump)

FXDQ-NDVET
(without drain pump) (900/1,100
width type )
mm

Slim Duct (Compact) FXDQ-SPV1

Middle Static
FXSQ-PAVE
Pressure Duct
Max.
VRV indoor units only
Middle-High Static Pressure Duct FXMQ-PAVE
58 indoor
units
High Static Pressure Duct FXMQ-PVM

Outdoor-Air Processing Unit FXMQ-MFV1

4-Way Flow Ceiling


Ceiling Suspended

FXUQ-AVEB
Suspended

FXHQ-MAVE
Ceiling Suspended
BP unit BP unit
FXHQ-AVM

Wall Mounted FXAQ-AVM


Max.
Floor Standing FXLQ-MAVE Residential indoor units only
19 indoor
Floor Standing

units
Concealed Floor Standing FXNQ-MAVE
*Refer to page 94 for the maximum number of connectable indoor units.
FXVQ-NY1
Floor Standing Duct
FXVQ-NY16
(high static pressure type)

Heat Reclaim Ventilator


VKM-GCVE Airflow rate 500-950 m3/h
with DX-Coil

Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h

Air Handling Unit AHUR 6–120 HP

95 96
VRV IV W Series
Outside Units
VRV IV W Series
Specifications

MODEL RWEYQ6TYM RWEYQ8TYM RWEYQ10TYM RWEYQ12TYM RWEYQ14TYM RWEYQ16TYM RWEYQ18TYM RWEYQ20TYM RWEYQ22TYM RWEYQ24TYM
– – – – RWEYQ6TYM RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM
Combination units
– – – – RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM RWEYQ12TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 54,600 76,400 95,500 114,000 131,000 153,000 172,000 191,000 210,000 229,000
Cooling capacity
kW 16.0 22.4 28.0 33.5 38.4 44.8 50.4 56.0 61.5 67.0
Power consumption kW 2.58 3.86 5.43 7.33 6.44 7.72 9.29 10.9 12.8 14.7
Casing colour lvory white (5Y7.5/1) lvory white (5Y7.5/1)
Dimensions (H × W × D) mm 1,000 × 780 × 550 (1,000 × 780 × 550) × 2
Type Hermetically sealed scroll type Hermetically sealed scroll type
Compressor
Motor output kW 1.9 2.8 3.7 4.7 1.9 + 2.8 2.8 × 2 2.8 + 3.7 3.7 × 2 3.7 + 4.7 4.7 × 2
Liquid 9.5 (Flare) 12.7 (Flare) 12.7 (Flare) 15.9 (Flare) 19.1 (Flare)
Refrigerant piping 28.6 (Brazing)
Suction gas *1 mm 19.1 (Brazing) 22.2 (Brazing)
connections
High and low pressure gas 19.1*2 (Brazing) 22.2*2 (Brazing) 28.6*2 (Brazing)
Water inlet PT1 1/4B intenal thread (PT1 1/4B) × 2 intenal thread

VRV IV W Series
Water piping
Water outlet PT1 1/4B intenal thread (PT1 1/4B) × 2 intenal thread
connections
Drain outlet PS1/2B intenal thread (PS1/2B) × 2 intenal thread
Machine weight (Operating weight) kg 146 (148) 147 (149) 146 × 2 (148 × 2) 146 + 147 (148 + 149) 147 × 2 (149 × 2)
Sound level dB(A) 49 50 51 53 53 54 55 56
Operation range (Inlet water temp.) °C 10 to 45 10 to 45
Capacity control % 23-100 19-100 23-100 19-100
Type R-410A R-410A
Refrigerant
Charge kg 3.5 4.2 3.5 + 3.5 3.5 + 4.2 4.2 + 4.2

MODEL RWEYQ26TYM RWEYQ28TYM RWEYQ30TYM RWEYQ32TYM RWEYQ34TYM RWEYQ36TYM


RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM Notes:
1. Specifications are based on the following
Combination units RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM RWEYQ12TYM conditions:
RWEYQ10TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM RWEYQ12TYM RWEYQ12TYM • Cooling: Indoor temp.: 27ºCDB, 19ºCWB / inlet
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz water temp.:30ºC, Equivalent piping
length: 7.5 m, Level difference: 0 m.
Btu/h 248,000 268,000 287,000 305,000 324,000 345,000
Cooling capacity • Sound level: Anechoic chamber conversion
kW 72.8 78.4 84.0 89.5 95.0 101 value, measured at a point 1 m in
Power consumption kW 13.2 14.7 16.3 18.2 20.1 22.0 front of the unit at a height of 1.5
m.
Casing colour lvory white (5Y7.5/1) lvory white (5Y7.5/1) During actual operation, these
Dimensions (H × W × D) mm (1,000 × 780 × 550) × 3 (1,000 × 780 × 550) × 3 values are normally somewhat
higher as a result of ambient
Type Hermetically sealed scroll type Hermetically sealed scroll type
Compressor conditions and oil recovery mode.
Motor output kW 2.8 × 2 + 3.7 2.8 + 3.7 × 2 3.7 × 3 3.7 × 2 + 4.7 3.7 + 4.7 × 2 4.7 × 3 When there is concern for noise to
Liquid 19.1 (Flare) 19.1 (Flare) the surrounding area such as
Refrigerant piping residences, we recommend
Suction gas *1 mm 34.9 (Brazing) 34.9 (Brazing) investigating the installation
connections
High and low pressure gas 34.9*2 (Brazing) 34.9*2 (Brazing) location and taking soundproofing
Water inlet (PT1 1/4B) × 3 intenal thread (PT1 1/4B) × 3 intenal thread measures.
Water piping 2. This unit cannot be installed in the outdoors.
Water outlet (PT1 1/4B) × 3 intenal thread (PT1 1/4B) × 3 intenal thread Install indoors (Machine room, etc).
connections
Drain outlet (PS1/2B) × 3 intenal thread (PS1/2B) × 3 intenal thread 3. Hold ambient temperature at 0 – 40ºC and
humidity at 80%RH or less. Heat rejection from
Machine weight (Operating weight) kg 146 × 2 + 147 (148 × 2 + 149) 146 + 147 × 2 (148 + 149 × 2) 147 × 3 (149 × 3) 147 × 3 (149 × 3) the casing: 0.51 kW / 6 - 8 HP / hour, 0.58 kW / 10
Sound level dB(A) 55 56 57 58 - 12 HP / hour.
Operation range (Inlet water temp.) °C 10 to 45 10 to 45 4. Connectable to closed type cooling tower only.
*1: In the case of cooling only system, suction gas
Capacity control % 21-100 20-100 19-100 19-100 pipe is not used.
Type R-410A R-410A *2: In the case of cooling only system.
Refrigerant • Be sure to refer to the Engineering Data Book for
Charge kg 3.5 + 3.5 + 4.2 3.5 + 4.2 + 4.2 4.2 + 4.2 + 4.2 4.2 + 4.2 + 4.2
facility design.

97 98
VRV WS Series

Easy Installation & Energy Saving


Compact and lightweight
Water Cooled System Suitable for
Residential Houses Cooling Only
4HP –6 HP Compact

0.35 m
(11.2 kW) (16 kW)
Footprint : 2 Design

1,000 mm
Product Weight :
(For 4/5 HP) 110 kg
Product Weight :
(For 6 HP) 111 kg
450 mm
780 mm

Service space (Single installation)

450 mm 100 mm
Service access from the front with minimal space
required at rear of the condenser (100 mm)

VRV WS Series
700 mm
Front
Water piping
space

20 mm 780 mm 20 mm

Energy saving
Higher Energy Efficiency Ratio (EER) VRT control for optimal annual efficiency
Cooling Operation EER VRT automatically adjusts refrigerant
RWXQ4-6AXVE temperature to individual building and climate
6.00 requirement, thus further improving annual
5.49 energy efficiency and maintaining comfort.
5.00 4.90
4.70
4.00

3.00

2.00

1.00

0
4 HP 5 HP 6 HP
*Cooling : Indoor temp.: 27ºCDB, 19ºCWB/inlet water temp.: 30ºC,
Equivalent piping length: 7.5 m, Level difference: 0 m.

99 100
VRV WS Series
Flexible System Design
Long piping length
Installation for VRV indoor units only Installation for residential indoor units only
Actual piping length Actual piping length
Max. 90 m Max. 70 m

Equivalent piping length Equivalent piping length


Single use Max. 120 m Single use only Max. 90 m

Total piping length Total piping length

Max. 250 m Max. 100 m


a
f g h a b
e o 15 m
Max.
First indoor branch
First indoor branch b c d e BP unit

i Max. h i m 15 m
Max.
n 30 m
r BP unit

RA RA
Max.
k

VRV WS Series
Max.
s l P 5m
15 m RA
RA: Residential indoor unit
RA
*Colours in the diagram above are merely for identifying pipes referenced with symbols such as a . *Colours in the diagram following are merely for identifying pipes referenced with symbols such as a .

Actual Equivalent Actual Equivalent


Example Example
piping length piping length piping length Example piping length
Max. Refrigerant piping length 90 m a+f+g+h+i 120 m Max. Refrigerant piping length 70 m a+b+k 90 m
allowable Total piping length 250 m a+b+c+d+e+f+g+h+i — allowable Total piping length 100 m a+b+e+h+j+k —
piping length Between the first indoor branch and the farthest indoor unit 40 m f+g+h+i — piping length Between the first indoor branch and the farthest indoor unit 40 m b+k —
Max. Between the indoor units 15 m s — Max. and min. If indoor unit capacity index < 60 2 m - 15 m h,i,j,k —
Between BP unit and
allowable Between the outside units allowable If indoor unit capacity index is 60 2 m - 12 m h,i,j,k —
30 m r — piping length indoor unit
level difference and the indoor units If indoor unit capacity index is 71 2m-8m h,i,j,k —
Between the outside unit
If the outside unit is above. 30 m n —
and the indoor unit
Max. l —
Between the indoor units 15 m
allowable
Between the outside unit and the BP unit 15 m o —
level difference
Between BP units 15 m m —
Between the BP unit and the indoor unit 5m p —

101 102
VRV WS Series
Advanced Technologies

Tube-in-Tube Type Heat Exchanger Easy maintenance


Refrigerant lines spiraling around the water circuit in a counter flow design delivers superior heat The electrical components and the major components
exchange. are designed in a way that they can be accessed from
front for maintenance.

Lower risk of
blockage

Tube in tube structure for simple installation and maintenance Delivers optimal
performance
Built in water flow switch
Better tolerance
for water quality! Mechanical water flow switch is built into the system to enhance system reliability.

Use of copper pipes enhances tolerance against corrosive effects of chloride ions Reed contact

Magnet
For activating the

VRV WS Series
reed contact

Refrigerant cooling technology Magnet


For generating the
paddle reset force

Paddle System Pin


PCB Reacts to flow

Power Module
Heat Refrigerant Jacket
Refrigerant
Refrigerant

The main heat generating parts (inverter power module) in the electric component
is adopted to reduce the size of the refrigerant cooling technology.

Standard water strainer


A standard water strainer is equipped so it reduces the additional cost and installation
time at field. The new filter also has less pressure drop at higher water flows.
Control board failure ratio at stable operation is reduced.
* Refer to page 108 for water strainer specification details.

This enables

• Suitability for high ambient temperatures


• Miniaturization of electronic components

103 104
VRV WS Series
Indoor Unit Lineup
Enhanced range of choices
VRV indoor units New lineup Residential indoor units with connection to BP units
20 25 32 40 50 63 71 80 100 125 140 25 35 50 60 71
Category

Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 Capacity Index 25 35 50 60 71
Round Flow Cassette
FXFSQ-AVM
with Sensing FDKS-EAVMB
Ceiling Mounted Cassette

(700 mm width type)


Slim Ceiling Concealed Duct
Round Flow Cassette FXFQ-AVM
FDKS-C(A)VMB
(900/1,100 mm width type)
Compact Multi FXZQ-AVM
Flow Cassette
FTKS-DVM
Double Flow Cassette FXCQ-AVM

Wall Mounted FTKS-BVMA


Corner Cassette FXKQ-MAVE

3D Airflow Duct with FTKS-FVM


FXDSQ-AVM
Sensing
FXDQ-PDVE Note: BP units are necessary for residential indoor units.
(with drain pump)

FXDQ-PDVET
Ceiling Concealed Duct

(without drain pump)


(700 mm width type)
Slim Duct (Standard)
FXDQ-NDVE
(with drain pump)

FXDQ-NDVET
(without drain pump) (900/1,100
width type )
mm

VRV WS Series
Slim Duct (Compact) FXDQ-SPV1

Middle Static
FXSQ-PAVE
Pressure Duct
Max.
VRV indoor units only
Middle-High Static Pressure Duct FXMQ-PAVE
9 indoor
units
4-Way Flow Ceiling
Ceiling Suspended

FXUQ-AVEB
Suspended

FXHQ-MAVE
Ceiling Suspended
FXHQ-AVM

Wall Mounted FXAQ-AVM

BP unit BP unit
Floor Standing

Floor Standing FXLQ-MAVE

Concealed Floor Standing FXNQ-MAVE

Floor Standing Duct FXVQ-NY1 Max.


Residential indoor units only
7 indoor
units

*Refer to page 108 for the maximum number of connectable indoor units.

105 106
VRV WS Series
Outside Units
VRV WS Series
Specifications Outside Unit Combinations

Total capacity index of connectable indoor units


Capacity Maximum number of
Model name kW HP Combination (%)
index connectable indoor units
50% 100% 130%
RWXQ4A 11.2 4 100 50 100 130 6
RWXQ5A 14.0 5 125 62.5 125 162.5 8
RWXQ6A 16.0 6 150 75 150 195 9
MODEL RWXQ4AXVE RWXQ5AXVE RWXQ6AXVE Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outside unit.
Power supply 1-Phase, 220-240 V/220 V,50/60 Hz
Btu/h 38,200 47,800 54,600
Cooling capacity
kW 11.2 14.0 16.0
Power consumption
Casing colour
kW 2.04 2.86
Ivory white (5Y7.5/1)
3.40
Standard Water Strainer Specifications
Dimensions (H×W×D) mm 1,000×780×450
Specifications
Type Hermetically sealed swing type
Compressor 4 HP, 5 HP 6 HP
Motor output kW 1.92
Nominal diameter DN25 DN32
Refrigerant piping Liquid 9.5 (Flare)
mm Nominal pressure 1.6 MPa 1.6 MPa
connections Suction gas 15.9 (Flare)
Work temperature -25°C - 70°C -25°C - 150°C
Water inlet PT1B internal thread PT1 1/4B external thread
Water piping Mesh size 0.12 mm 0.23 mm & 0.5 mm (dual layer mesh)
Water outlet PT1B internal thread PT1 1/4B external thread
connections
Drain outlet PS1/2B internal thread

VRV WS Series
Machine weight (Operating weight) kg 110 (113.5) 111 (114.5)
Sound level dB(A) 31 36 39
Operation range (Inlet water temp.) °C 15 to 40 (Range for continuous operation)
Capacity control % 33-100
Type R-410A
Refrigerant
Charge kg 2.4 2.7 2.8
Rated water flow (Range of water flow) L/min 38 (19 to 57) 49 (24.5 to 73.5) 55 (27.5 to 82.5)
Note :1. Specifications are based on the following conditions ;
· Cooling : Indoor temp. : 27ºCDB, 19ºCWB / inlet water temp. :30ºC, Equivalent piping length : 7.5 m, Level difference : 0 m.
· Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing
measures.
2. This unit cannot be installed in the outdoors. Install indoors (Machine room, etc).
3. Hold ambient temperature at 0-40˚C and humidity at 80% RH or less.
Heat rejection from the casing: 0.28 kW/4 HP /hour, 0.31 kW/5 HP /hour, 0.35 kW/6 HP /hour

107 108
VRV IV Heat Recovery Hot Water System

Air conditioning combined


with hot water supply – Compact system
Comfortable Air Conditioning and
Outdoor unit
Energy-efficient Hot Water Heating Cooling Only
6 HP – 60 HP
(16 kW) (168 kW)

Air conditioning Serpentine heat


indoor unit exchanger unit

The system can be used in


combination with other water
Hot water storage tank heaters depending on the
required amount and
temperature of hot water.

VRV IV Heat Recovery Hot Water System


Flexible combination
Extremely energy-efficient
of VRV IV indoor units
energy source
achieves comfort and aesthetic

High-COP Type Standard Type

Double outdoor units Single outdoor units


RWHQ12-16THYM RWHQ6-16TYM AIR HOT WATER
CONDITIONING SUPPLY
Triple outdoor units Double outdoor units
RWHQ18-50THYM RWHQ18-32TNYM
Triple outdoor units
RWHQ34-60TNYM
Energy to supply hot water – Cost-effective
Space Saving Type
Hot water temperature – Up to 65 °C
Single outdoor units
RWHQ18-20TYM
Can be used in combination with other water heaters depending on the required amount and
Double outdoor units temperature of hot water.
RWHQ22-40TSYM
Triple outdoor units
RWHQ42-50TSYM
109 110
VRV IV Heat Recovery Hot Water System
Innovative and Reliable System
The energy-ef f icient system recovers waste heat
as energy to heat water Example on usage of VRV IV Heat Recovery
Hot Water System for residence
Waste heat from air conditioning (which usually In a sample family model of 3 adults and 3 children,
Family composition 2 showers / person / day

released into the ambience) is recovered to heat water the waste heat generated by air conditioning is sufficient
50 L 50 L
X

to supply hot water for everybody’s showers. 3 adults 3 children = 12 showers (600 L (39˚C))
In a conventional system, This system recovers waste heat from air
Time
waste heat from air conditioning is released conditioning to heat water.
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4
into the ambience. ON OFF ON
VRV Heat load
70%
Hot air discharge Lower hot air discharge Generally, all air conditioners
50% are not in operation during the day
because parents are working.
30%
OFF
Hot water
supply pattern
150L

0L
Hot
Circulating Water Water Temp. 60˚C
Pump Storage
Tank

VRV IV Heat Recovery Hot Water System


When cooling, if the temperature drops in the storage water heater,
the unit starts water heating operations by using the waste heat.
40˚C
Ambient air Ambient air 25˚C
Air conditioner load conditions / Operation time: 16 hours/day
Water-heating load
Tank capacity: 200 L
Boiling temperature: 25˚C to 60˚C (tap water)

The serpentine heat exchanger unit recovers heat Amount of hot water per person per time (standard): 50 L/shower (39˚C) (water dispensed: 10 L/min.; shower time: 5 min./shower)
Amount of water required in tank to dispense 39˚C hot water
No electric heater consumption
(Water heating by the use of waste heat)
The proprietary Serpentine The high-temperature, 4000

Annual power consumption [kWh]


Compact, Heat Exchanger achieves excellent high-pressure refrigerant
lightweight Comparison between VRV IV Heat Recovery
heat exchange efficiency. pipe is coiled around
design
the water pipe.
Hot Water System and electric heater 3000

Refrigerant out
Because waste heat is used to heat water, annual electricity 2000 94%
3,986 kWh reduction
consumption can be reduced approximately 94%
Water in compared with consumption for separate operation 1000
234 kWh
Water pipe
Water out
of air conditioning and an electric water heater.
(Outlet) 0
Refrigerant leakage
Electric heater VRV IV Heat Recovery
does not contaminate
Refrigerant pipe Hot Water System + water pump
water.
Water pipe (Outlet)
(Inlet) Refrigerant pipe
(Inlet)
Refrigerant in
VRV IV Heat Recovery Hot Water controller
Convertible Remote Controller
Main Remote Control & Sub Remote Controller are both convertible and interchangeable.
Anti-Bacteria
Increased energy efficiency of the outdoor unit By default, this would be activated every Monday morning at 2am, heating storage water up to 60°C for
10 minutes.
The waste heat from air conditioning is transferred to heat water. This mechanism reduces the amount
of heat processed by the outdoor unit, resulting in better operation efficiency. The EER for VRV IV Heat Vacation Mode
Recovery Hot Water has increased from 4.41 to 4.50, compared with the conventional VRV IV. This disables all other functions, except for anti-bacterial mode.
Auto Restart
When power supply is restored after a failure, the system would revert to the last
Reducing short circuits operational function.
Safety-Error Code
The temperature of exhaust heat from the outdoor unit is lower, minimising in ambient temperature If thermistors or communication line are faulty, as a safety precaution, operation
increase. In the event of a short circuit, capacity reduction is minimised. of the electric heater is disabled. BRCS82
111 112
VRV IV Heat Recovery Hot Water System
Indoor Unit Lineup
Enhanced range of choices
A mixed of stylish and quiet VRV type indoor units and residential type indoor units
can be combined into one system.

VRV indoor units New lineup Residential indoor units with connection to BP units
20 25 32 40 50 63 71 80 100 125 140 200 250 400 500 25 35 50 60 71
Category

Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 Capacity Index 25 35 50 60 71
Round Flow Cassette
FXFSQ-AVM
Ceiling Mounted Cassette

with Sensing
FDKS-EAVMB
Round Flow Cassette FXFQ-AVM (700 mm width type)
Slim Ceiling Concealed Duct
Compact Multi
Flow Cassette FXZQ-AVM FDKS-C(A)VMB
(900/1,100 mm width type)

Double Flow Cassette FXCQ-AVM


FTKS-DVM
Corner Cassette FXKQ-MAVE

3D Airflow Duct with


FXDSQ-AVM Wall Mounted FTKS-BVMA
Sensing
FXDQ-PDVE
(with drain pump)

VRV IV Heat Recovery Hot Water System


FXDQ-PDVET FTKS-FVM
(700 mm width type)
(without drain pump)
Slim Duct (Standard)
Ceiling Concealed Duct

FXDQ-NDVE
(with drain pump)

FXDQ-NDVET (900/1,100 mm width type)


(without drain pump)

Slim Duct (Compact) FXDQ-SPV1

Middle Static Pressure Duct FXSQ-PAVE

Middle-High Static Pressure Duct FXMQ-PAVE

High Static Pressure Duct FXMQ-PVM

Outdoor-Air Processing Unit FXMQ-MFV1


4-Way Flow Ceiling
Ceiling Suspended

FXUQ-AVEB
Suspended
FXHQ-MAVE
Ceiling Suspended
FXHQ-AVM

Wall Mounted FXAQ-AVM

Floor Standing FXLQ-MAVE


Floor Standing

Concealed Floor Standing FXNQ-MAVE

FXVQ-NY1
Floor Standing Duct
FXVQ-NY16
(high static pressure type)

FXBQ-PVE
Clean Room Air Conditioner
FXBPQ-PVE

Heat Reclaim Ventilator


VKM-GCVE Airflow rate 500-950 m3/h
with DX-Coil
Heat Reclaim Ventilator VAM-GJVE Airflow rate 150-2000 m3/h

Air Handling Unit AHUR 6–120 HP

Note: BP units (BPMKS967A2/3) are necessary for residential indoor units.

113 114
VRV IV Heat Recovery Hot Water System
Outdoor Units
VRV IV Heat Recovery Hot Water System
Specifications
High-COP Type

MODEL RWHQ12THYM RWHQ14THYM RWHQ16THYM RWHQ18THYM RWHQ20THYM RWHQ22THYM RWHQ24THYM RWHQ26THYM RWHQ28THYM RWHQ30THYM RWHQ32THYM RWHQ34THYM RWHQ36THYM RWHQ38THYM RWHQ40THYM
RWHQ6TYM RWHQ6TYM RWHQ8TYM RWHQ6TYM RWHQ6TYM RWHQ6TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ12TYM RWHQ12TYM
Combination units RWHQ6TYM RWHQ8TYM RWHQ8TYM RWHQ6TYM RWHQ6TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ12TYM RWHQ14TYM RWHQ12TYM RWHQ14TYM
— — — RWHQ6TYM RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ14TYM RWHQ14TYM RWHQ14TYM RWHQ14TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 109,000 131,000 153,000 164,000 186,000 207,000 229,000 248,000 267,000 286,000 305,000 327,000 348,000 365,000 389,000
Cooling capacity
kW 32.0 38.4 44.8 48.0 54.4 60.8 67.2 72.8 78.3 83.9 89.4 95.9 102 107 114
Power consumption kW 7.10 8.68 10.3 10.7 12.2 13.8 15.4 17.5 19.2 21.3 23.0 24.9 26.7 28.7 30.5
Capacity control % 10-100 7-100 6-100 5-100 4-100
Casing colour Ivory white(5Y7.5/1) Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Compressor (2.4x1)+ (2.4x1)+ (3.4x1)+ (2.4x1)+(2.4x1)+ (2.4x1)+(2.4x1)+ (2.4x1)+(3.4x1)+ (3.4x1)+(3.4x1)+ (3.4x1)+(3.4x1)+ (3.4x1)+(3.4x1)+ (3.4x1)+(4.1x1)+ (3.4x1)+(5.2x1)+ (3.4x1)+(5.2x1)+ (3.4x1)+(2.9x1)+(3.3x1)+ (5.2x1)+(5.2x1)+ (5.2x1)+(2.9x1)+(3.3x1)+
Motor output kW
(2.4x1) (3.4x1) (3.4x1) (2.4x1) (3.4x1) (3.4x1) (3.4x1) (4.1x1) (5.2x1) (5.2x1) (5.2x1) (2.9x1)+(3.3x1) (2.9x1)+(3.3x1) (2.9x1)+(3.3x1) (2.9x1)+(3.3x1)
Airflow rate m3/min 119+119 119+157 157+157 119+119+119 119+119+157 119+157+157 157+157+157 157+157+165 157+157+178 157+165+178 157+178+178 157+178+233 157+233+233 178+178+233 178+233+233
(1,657x930x765)+ (1,657x930x765)+ (1,657x930x765)+ (1,657x930x765)+
Dimensions (HxWxD) mm (1,657x930x765)+(1,657x930x765) (1,657x930x765)+(1,657x930x765)+(1,657x930x765) (1,657x930x765)+(1,657x930x765)+(1,657x930x765) (1,657x930x765)+ (1,657x1,240x765)+ (1,657x930x765)+ (1,657x1,240x765)+

VRV IV Heat Recovery Hot Water System


(1,657x1,240x765) (1,657x1,240x765) (1,657x1,240x765) (1,657x1,240x765)
Machine weight kg 185+185 185+185+185 185+185+200 185+200+200 185+200+285 185+285+285 200+200+285 200+285+285
Sound level dB(A) 58 59 60 61 61 62 63 64
Operation range °CDB 15 to 49 15 to 49
Type R-410A R-410A
Refrigerant
Charge kg 6.4+6.4 6.4+6.4+6.4 6.4+6.4+6.5 6.4+6.4+6.8 6.4+6.5+6.8 6.4+6.8+6.8 6.4+6.8+10.3 6.4+10.3+10.3 6.8+6.8+10.3 6.8+10.3+10.3
Piping Liquid mm 12.7(Brazing) 15.9(Brazing) 19.1(Brazing)
connections
(Indoor unit) Gas mm 28.6(Brazing) 34.9(Brazing) 34.9(Brazing) 41.3(Brazing)
Piping Inlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 3) 19.1(Brazing x 3)
connections
(Heat exchanger unit) Outlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 3) 19.1(Brazing x 3)

Standard Type

MODEL RWHQ42THYM RWHQ44THYM RWHQ46THYM RWHQ48THYM RWHQ50THYM MODEL RWHQ6TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ14TYM RWHQ16TYM
RWHQ14TYM RWHQ14TYM RWHQ14TYM RWHQ16TYM RWHQ16TYM
Combination units RWHQ14TYM RWHQ14TYM RWHQ16TYM RWHQ16TYM RWHQ16TYM Combination units — — — — — —
RWHQ14TYM RWHQ16TYM RWHQ16TYM RWHQ16TYM RWHQ18TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 409,000 427,000 444,000 461,000 478,000 Btu/h 54,600 76,400 95,500 114,000 136,000 154,000
Cooling capacity Cooling capacity
kW 120 125 130 135 140 kW 16.0 22.4 28.0 33.5 40.0 45.0
Power consumption kW 32.4 34.5 36.6 38.7 41.1 Power consumption kW 3.55 5.13 7.22 8.93 10.8 12.9
Capacity control % 4-100 3-100 Capacity control % 20-100 16-100 15-100 11-100 10-100
Casing colour Ivory white (5Y7.5/1) Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Type Hermetically Sealed Scroll Type
Compressor (2.9x1)+(3.3x1)+(2.9x1)+ (2.9x1)+(3.3x1)+(2.9x1)+ (2.9x1)+(3.3x1)+(3.6x1)+ (3.6x1)+(3.7x1)+(3.6x1)+ (3.6x1)+(3.7x1)+(3.6x1)+ Compressor
Motor output kW Motor output kW 2.4x1 3.4x1 4.1x1 5.2x1 (2.9x1)+(3.3x1) (3.6x1)+(3.7x1)
(3.3x1)+(2.9x1)+(3.3x1) (3.3x1)+(3.6x1)+(3.7x1) (3.7x1)+(3.6x1)+(3.7x1) (3.7x1)+(3.6x1)+(3.7x1) (3.7x1)+(4.4x1)+(4.0x1)
Airflow rate m3/min 233+233+233 Airflow rate m /min
3
119 157 165 178 233
Dimensions (H×W×D) mm (1,657x1,240x765)+(1,657x1,240x765)+(1,657x1,240x765) Dimensions (H×W×D) mm 1,657x930x765 1,657x1,240x765
Machine weight kg 285+285+285 Machine weight kg 185 200 285
Sound level dB(A) 65 66 Sound level dB(A) 55 56 57 59 60 61
Operation range ºCDB 15 to 49 Operation range ºCDB 15 to 49
Type R-410A Type R-410A
Refrigerant Refrigerant
Charge kg 10.3+10.3+10.3 10.3+10.3+10.4 10.3+10.4+10.4 10.4+10.4+10.4 10.4+10.4+10.5 Charge kg 6.4 6.5 6.8 10.3 10.4
Piping Liquid mm 19.1(Brazing) Piping Liquid mm 9.5(Brazing) 12.7(Brazing)
connections connections
(Indoor unit) Gas mm 41.3(Brazing) (Indoor unit) Gas mm 19.1(Brazing) 22.2(Brazing) 28.6(Brazing)
Piping Inlet pipe mm 19.1(Brazing x 3) Piping Inlet pipe mm 19.1(Brazing)
connections connections
(Heat exchanger unit) Outlet pipe mm 19.1(Brazing x 3) (Heat exchanger unit) Outlet pipe mm 19.1(Brazing)
115 116
Notes: Specifications are based on the following conditions; •Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise to the
surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
VRV IV Heat Recovery Hot Water System
Outdoor Units
VRV IV Heat Recovery Hot Water System
Specifications
Standard Type

MODEL RWHQ18TNYM RWHQ20TNYM RWHQ22TNYM RWHQ24TNYM RWHQ26TNYM RWHQ28TNYM RWHQ30TNYM RWHQ32TNYM RWHQ34TNYM RWHQ36TNYM RWHQ38TNYM RWHQ40TNYM RWHQ42TNYM RWHQ44TNYM RWHQ46TNYM
RWHQ8TYM RWHQ8TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ14TYM RWHQ14TYM RWHQ14TYM RWHQ10TYM RWHQ12TYM RWHQ8TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ14TYM
Combination units RWHQ10TYM RWHQ12TYM RWHQ14TYM RWHQ14TYM RWHQ14TYM RWHQ14TYM RWHQ16TYM RWHQ18TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ14TYM RWHQ16TYM RWHQ14TYM
— — — — — — — — RWHQ12TYM RWHQ12TYM RWHQ18TYM RWHQ16TYM RWHQ16TYM RWHQ16TYM RWHQ18TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 172,000 191,000 213,000 232,000 251,000 273,000 290,000 307,000 324,000 345,000 362,000 382,000 406,000 423,000 444,000
Cooling capacity
kW 50.4 55.9 62.4 68.0 73.5 80.0 85.0 90.0 95.0 101 106 112 119 124 130
Power consumption kW 12.4 14.1 15.9 18.0 19.7 21.6 23.7 26.1 25.1 26.8 29.4 30.8 32.6 34.7 36.9
Capacity control % 8-100 7-100 6-100 5-100 5-100 4-100 3-100
Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Compressor (3.4x1)+ (3.4x1)+ (3.4x1)+(2.9x1)+ (4.1x1)+(2.9x1)+ (5.2x1)+(2.9x1)+ (2.9x1)+(3.3x1)+ (2.9x1)+(3.3x1)+ (2.9x1)+(3.3x1)+ (4.1x1)+(5.2x1)+ (5.2x1)+(5.2x1)+ (3.4x1)+(5.2x1)+ (5.2x1)+(5.2x1)+ (5.2x1)+(2.9x1)+(3.3x1)+ (5.2x1)+(3.6x1)+(3.7x1)+ (2.9x1)+(3.3x1)+(2.9x1)+
Motor output kW
(4.1x1) (5.2x1) (3.3x1) (3.3x1) (3.3x1) (2.9x1)+(3.3x1) (3.6x1)+(3.7x1) (4.4x1)+(4.0x1) (5.2x1) (5.2x1) (4.4x1)+(4.0x1) (3.6x1)+(3.7x1) (3.6x1)+(3.7x1) (3.6x1)+(3.7x1) (3.3x1)+(4.4x1)+(4.0x1)
Airflow rate m3/min 157+165 157+178 157+233 165+233 178+233 233+233 233+233 165+178+178 178+178+178 157+178+233 178+178+233 178+233+233 233+233+233
(1,657x1,240x765)+
(1,657x930x765)+ (1,657x1,240x765)+ (1,657x1,240x765)+ (1,657x930x765)+(1,657x930x765)+ (1,657x930x765)+(1,657x930x765)+ (1,657x930x765)+(1,657x1,240x765)+
Dimensions (HxWxD) mm (1,657x930x765)+(1,657x1,240x765) (1,657x1,240x765)+
(1,657x930x765) (1,657x1,240x765) (1,657x1,240x765) (1,657x930x765) (1,657x1,240x765) (1,657x1,240x765)

VRV IV Heat Recovery Hot Water System


(1,657x1,240x765)
Machine weight kg 185+200 185+285 200+285 285+285 285+285 200+200+200 185+200+285 200+200+285 200+285+285 285+285+285
Sound level dB(A) 60 61 62 63 64 64 63 64 65 66
Operation range °CDB 15 to 49 15 to 49
Type R-410A R-410A
Refrigerant
Charge kg 6.4+6.5 6.4+6.8 6.4+10.3 6.5+10.3 6.8+10.3 10.3+10.3 10.3+10.4 10.3+10.5 6.5+6.8+6.8 6.8+6.8+6.8 6.4+6.8+10.5 6.8+6.8+10.4 6.8+10.3+10.4 6.8+10.4+10.4 10.3+10.3+10.5
Piping Liquid mm 15.9(Brazing) 19.1(Brazing) 19.1(Brazing)
connections
(Indoor unit) Gas mm 28.6(Brazing) 34.9(Brazing) 34.9(Brazing) 41.3(Brazing)
Piping Inlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 2) 19.1(Brazing x 3)
connections
(Heat exchanger unit) Outlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 2) 19.1(Brazing x 3)

Standard Type Space Saving Type

MODEL RWHQ48TNYM RWHQ50TNYM RWHQ52TNYM RWHQ54TNYM RWHQ56TNYM RWHQ58TNYM RWHQ60TNYM MODEL RWHQ18TYM RWHQ20TYM RWHQ22TSYM RWHQ24TSYM
RWHQ14TYM RWHQ14TYM RWHQ16TYM RWHQ18TYM RWHQ18TYM RWHQ18TYM RWHQ20TYM RWHQ10TYM RWHQ12TYM
Combination units RWHQ16TYM RWHQ18TYM RWHQ18TYM RWHQ18TYM RWHQ18TYM RWHQ20TYM RWHQ20TYM Combination units — — RWHQ12TYM RWHQ12TYM
RWHQ18TYM RWHQ18TYM RWHQ18TYM RWHQ18TYM RWHQ20TYM RWHQ20TYM RWHQ20TYM — —
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 461,000 478,000 495,000 512,000 532,000 553,000 573,000 Btu/h 171,000 191,000 210,000 229,000
Cooling capacity Cooling capacity
kW 135 140 145 150 156 162 168 kW 50.0 56.0 61.5 67.0
Power consumption kW 39.0 41.4 43.5 45.9 48.5 51.1 53.7 Power consumption kW 15.3 17.9 16.2 17.9
Capacity control % 3-100 Capacity control % 10-100 8-100
Casing colour Ivory white (5Y7.5/1) Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Type Hermetically Sealed Scroll Type
Compressor (2.9x1)+(3.3x1)+(3.6x1)+ (2.9x1)+(3.3x1)+(4.4x1)+ (3.6x1)+(3.7x1)+(4.4x1)+ (4.4x1)+(4.0x1)+(4.4x1)+ (4.4x1)+(4.0x1)+(4.4x1)+ (4.4x1)+(4.0x1)+(4.6x1)+ (4.6x1)+(5.5x1)+(4.6x1)+ Compressor
Motor output kW Motor output kW (4.4x1)+(4.0x1) (4.6x1)+(5.5x1) (4.1x1)+(5.2x1) (5.2x1)+(5.2x1)
(3.7x1)+(4.4x1)+(4.0x1) (4.0x1)+(4.4x1)+(4.0x1) (4.0x1)+(4.4x1)+(4.0x1) (4.0x1)+(4.4x1)+(4.0x1) (4.0x1)+(4.6x1)+(5.5x1) (5.5x1)+(4.6x1)+(5.5x1) (5.5x1)+(4.6x1)+(5.5x1)
Airflow rate m /min
3
233+233+233 233+233+268 233+268+268 268+268+268 Airflow rate m /min
3
233 268 165+178 178+178
Dimensions (H×W×D) mm (1,657x1,240x765)+(1,657X1,240x765)+(1,657x1,240x765) Dimensions (H×W×D) mm 1,657x1,240x765 (1,657x930x765)+(1,657x930x765)
Machine weight kg 285+285+285 285+285+320 285+320+320 320+320+320 Machine weight kg 285 320 200+200
Sound level dB(A) 66 67 68 69 70 Sound level dB(A) 62 65 61 62
Operation range ºCDB 15 to 49 Operation range ºCDB 15 to 49
Type R-410A Type R-410A
Refrigerant Refrigerant
Charge kg 10.3+10.4+10.5 10.3+10.5+10.5 10.4+10.5+10.5 10.5+10.5+10.5 10.5+10.5+11.8 10.5+11.8+11.8 11.8+11.8+11.8 Charge kg 10.5 11.8 6.5+6.8 6.8+6.8
Piping Liquid mm 19.1(Brazing) Piping Liquid mm 15.9(Brazing)
connections connections
(Indoor unit) Gas mm 41.3(Brazing) (Indoor unit) Gas mm 28.6(Brazing) 34.9(Brazing)
Piping Inlet pipe mm 19.1(Brazing x 3) Piping Inlet pipe mm 19.1(Brazing) 19.1(Brazing x 2)
connections connections
(Heat exchanger unit) Outlet pipe mm 19.1(Brazing x 3) (Heat exchanger unit) Outlet pipe mm 19.1(Brazing) 19.1(Brazing x 2)
117 118
Notes: Specifications are based on the following conditions; • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise to the
surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
VRV IV Heat Recovery Hot Water System
Outdoor Units
VRV IV Heat Recovery Hot Water System
Specifications
Space Saving Type

MODEL RWHQ26TSYM RWHQ28TSYM RWHQ30TSYM RWHQ32TSYM RWHQ34TSYM RWHQ36TSYM RWHQ38TSYM RWHQ40TSYM RWHQ42TSYM RWHQ44TSYM RWHQ46TSYM RWHQ48TSYM RWHQ50TSYM
RWHQ8TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ16TYM RWHQ18TYM RWHQ18TYM RWHQ20TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM RWHQ12TYM
Combination units RWHQ18TYM RWHQ16TYM RWHQ18TYM RWHQ20TYM RWHQ18TYM RWHQ18TYM RWHQ20TYM RWHQ20TYM RWHQ12TYM RWHQ12TYM RWHQ16TYM RWHQ18TYM RWHQ18TYM
— — — — — — — — RWHQ18TYM RWHQ20TYM RWHQ18TYM RWHQ18TYM RWHQ20TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Btu/h 247,000 268,000 285,000 305,000 324,000 341,000 362,000 382,000 399,000 420,000 440,000 457,000 478,000
Cooling capacity
kW 72.4 78.5 83.5 89.5 95.0 100 106 112 117 123 129 134 140
Power consumption kW 20.4 21.8 24.2 26.8 28.2 30.6 33.2 35.8 33.2 35.8 37.1 39.5 42.1
Capacity control % 7-100 6-100 5-100 4-100 3-100
Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Compressor (3.4x1)+(4.4x1)+ (5.2x1)+(3.6x1)+ (5.2x1)+(4.4x1)+ (5.2x1)+(4.6x1)+ (3.6x1)+(3.7x1)+ (4.4x1)+(4.0x1)+ (4.4x1)+(4.0x1)+ (4.6x1)+(5.5x1)+ (5.2x1)+(5.2x1)+ (5.2x1)+(5.2x1)+ (5.2x1)+(3.6x1)+(3.7x1)+ (5.2x1)+(4.4x1)+(4.0x1)+ (5.2x1)+(4.4x1)+(4.0x1)+
Motor output kW
(4.0x1) (3.7x1) (4.0x1) (5.5x1) (4.4x1)+(4.0x1) (4.4x1)+(4.0x1) (4.6x1)+(5.5x1) (4.6x1)+(5.5x1) (4.4x1)+(4.0x1) (4.6x1)+(5.5x1) (4.4x1)+(4.0x1) (4.4x1)+(4.0x1) (4.6x1)+(5.5x1)
Airflow rate m3/min 157+233 178+233 178+268 233+233 233+268 268+268 178+178+233 178+178+268 178+233+233 178+233+268

(1,657x930x765)+(1,657x930x765)+ (1,657x930x765)+(1,657x1,240x765)+
Dimensions (HxWxD) mm (1,657x930x765)+(1,657x1,240x765) (1,657x1,240x765)+(1,657x1,240x765) (1,657x1,240x765)+(1,657x1,240x765)
(1,657x1,240x765) (1,657x1,240x765)

VRV IV Heat Recovery Hot Water System


Machine weight kg 185+285 200+285 200+320 285+285 285+320 320+320 200+200+285 200+200+320 200+285+285 200+285+320
Sound level dB(A) 63 64 66 65 67 68 65 67 66 67
Operation range °CDB 15 to 49 15 to 49
Type R-410A R-410A
Refrigerant
Charge kg 6.4+10.5 6.8+10.4 6.8+10.5 6.8+11.8 10.4+10.5 10.5+10.5 10.5+11.8 11.8+11.8 6.8+6.8+10.5 6.8+6.8+11.8 6.8+10.4+10.5 6.8+10.5+10.5 6.8+10.5+11.8
Piping Liquid mm 19.1(Brazing) 19.1(Brazing)
connections
(Indoor unit) Gas mm 34.9(Brazing) 41.3(Brazing) 41.3(Brazing)
Piping Inlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 2) 19.1(Brazing x 3)
connections
(Heat exchanger unit) Outlet pipe mm 19.1(Brazing x 2) 19.1(Brazing x 2) 19.1(Brazing x 3)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode. When there is concern for noise
to the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.

119 120
VRV IV Heat Recovery Hot Water System
Outdoor Units
VRV IV Heat Recovery Hot Water System
Serpentine heat exchanger unit (HWHQ30A)

Single Heat Exchanger Unit Double Heat Exchanger Unit


Model Name Model Name
( RWHQ-TYM, HWHQ30A ) RWHQ6TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ14TYM RWHQ16TYM RWHQ18TYM RWHQ20TYM ( RWHQ-TYM, HWHQ30A ) RWHQ6TYM RWHQ8TYM RWHQ10TYM RWHQ12TYM RWHQ14TYM RWHQ16TYM RWHQ18TYM RWHQ20TYM
+HWHQ30A +HWHQ30A +HWHQ30A +HWHQ30A +HWHQ30A +HWHQ30A +HWHQ30A +HWHQ30A +HWHQ30Ax2 +HWHQ30Ax2 +HWHQ30Ax2 +HWHQ30Ax2 +HWHQ30Ax2 +HWHQ30Ax2 +HWHQ30Ax2 +HWHQ30Ax2

Rated inlet temperature °C 40 Rated inlet temperature °C 40


Rated water flow L/min 10 Rated water flow L/min 20 (10 × 2)

Range of inlet temperature °C 20-65 Range of inlet temperature °C 20-65

Range of water flow L/min 5-20 Range of water flow L/min 10-40 (5-20 × 2)

Rated Hot-water capacity *1 kW 3.2 3.3 3.3 3.5 3.7 4.0 4.2 4.4 Rated Hot-water capacity *1 kW 5.4 5.6 5.6 5.9 6.2 6.8 7.1 7.4
Machine weight kg 27 Machine weight kg 54 (27 × 2)

Diameter of Refrigerant pipe (Gas) mm 19.1 (Braze) Diameter of Refrigerant pipe (Gas) mm 19.1 (Braze) × 2

Diameter of Refrigerant pipe (Liquid) mm 19.1 (Braze) Diameter of Refrigerant pipe (Liquid) mm 19.1 (Braze) × 2

Diameter of water pipe (Inlet) mm 25.4 (Screw) Diameter of water pipe (Inlet) mm 25.4 (Screw) × 2

Diameter of water pipe (Outlet) mm 25.4 (Screw) Diameter of water pipe (Outlet) mm 25.4 (Screw) × 2

Piping length (max) m 2 (5) Piping length (max) m 2 (5)

VRV IV Heat Recovery Hot Water System


Design pressure (Water side) MPa 0.5 Design pressure (Water side) MPa 0.5

Loss of Head *2 m 0.2 Loss of Head *2 m 0.2

Casing colour Ivory white (5Y7.5/1) Casing colour Ivory white (5Y7.5/1)

Dimensions (H×W×D) mm 446 × 306 × 765 Dimensions (H×W×D) mm (446 × 306 × 765) + (446 × 306 × 765)

Notes: It is necessary to satisfy the water standard of Daikin for the water that is used. In the case that the water standard is not satisfied, special measures are required. Notes: It is necessary to satisfy the water standard of Daikin for the water that is used. In the case that the water standard is not satisfied, special measures are required.
Please contact your local sales office for details. Please contact your local sales office for details.
*1: [ Cooling ] Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Inlet water temperature 40°C, Water flow 10L/min, Indoor load 100%, Outdoor-Heat Exchanger Unit 2m. *1: [ Cooling ] Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Inlet water temperature 40°C, Water flow 10L/min,Indoor load 100%, Outdoor-Heat Exchanger Unit 2m.
*2: Water flow 10L/min. *2: Water flow 10L/min.

Pipe length restriction of VRV IV Heat Recovery Hot Water System Pipe length restriction of VRV IV Heat Recovery Hot Water System
Serpentine heat exchanger unit Serpentine heat exchanger unit

Serpentine heat Outdoor unit Outdoor unit Serpentine heat Outdoor unit Outdoor unit
exchanger unit exchanger unit

Piping Piping
B A B A

A Piping A Piping

C
Indoor side Indoor side
(as with VRV IV) (as with VRV IV)

Max. allowable piping length A Between outdoor unit and heat exchanger unit length 5m Max. allowable piping length A Between outdoor unit and heat exchanger unit length 5m

Max. allowable level difference B Between outdoor unit and heat exchanger unit level 3m Max. allowable level difference B Between outdoor unit and heat exchanger unit level 3m

Max. allowable level difference C Between heat exchanger units 3m

121 122
INDOOR UNIT LINEUP 4-Way Flow Ceiling
Suspended Type
Slim and stylish design, optimum air distribution,
installation without ceiling cavity
Ceiling Suspended Type
Slim body with quiet and wide airflow.
Wall Mounted Type
Stylish flat panel design harmonised
with your interior décor.

Daikin offers a wide range of indoor units including both VRV Page Page Page

and residential models responding to variety of needs of our customers 151 152 153
that require air-conditioning solutions.
FXHQ-MAVE

FXUQ-AVEB FXAQ-AVM

VRV indoor units FXHQ-AVM

Round Flow Cassette with Round Flow Cassette Type Compact Multi Flow Cassette Type Floor Standing Type Concealed Floor Standing Type Floor Standing Duct Type
Sensing Type 360° airflow for improved comfort Quiet, compact, and designed for user comfort Suitable for perimeter zone air conditioning Suitable for perimeter zone air conditioning Large airflow type for large spaces.
Comfort and energy savings by sensing functions

Page Page Page Page Page Page


125 131 135 155 156 157

FXFSQ-AVM FXFQ-AVM FXVQ-NY1


FXZQ-AVM FXLQ-MAVE FXNQ-MAVE FXVQ-NY16
(high static pressure type)

Double Flow Cassette Type Corner Cassette Type 3D Airflow Duct with Sensing Type Clean Room Air Conditioner Air Handling Unit
Thin, lightweight, and easy to install Slim design for flexible installation 3D airflow with sensing function Suitable for hospitals and other clean spaces Integrate your air handling unit
in narrow ceiling spaces for comfort and energy savings in a total solution for large size spaces such
as factories and large stores.

Page Page Page Page Page


137 139 141 159 164

FXCQ-AVM FXKQ-MAVE FXDSQ-AVM FXBQ-PVE


FXBPQ-PVE AHUR

Slim Duct (Standard) Type Slim Duct (Compact) Type Middle Static Pressure Duct Type Residential indoor units with connection to BP units
Slim design, quietness and ideal for drop-ceilings Slim and compact design for easy and Middle static pressure and slim design
flexible installation allow flexible installations. Slim Ceiling Concealed Duct Type Wall Mounted Type
Slim and smooth design suits your shallow ceiling Stylish flat panel harmonises with your interior décor
Page Page Page
143 144 145
Page Page
161 162
FXDQ-PDVE(T)

FXDQ-SPV1 FXSQ-PAVE
FDKS-EAVMB FTKS-DVM
FXDQ-NDVE(T) FDKS-C(A)VMB FTKS-BVMA
FTKS-FVM

Middle-High Static Pressure Duct Type High Static Pressure Duct Type Outdoor-Air Processing Unit
Middle and high static pressure
allows for flexible duct design.
High static pressure allows
for flexible duct design.
Combine fresh air treatment
and air conditioning,
supplied from a single system.
Air treatment equipment
Page Page Page Heat Reclaim Ventilator with Heat Reclaim Ventilator
147 149 166 DX-Coil Page Page
169 173

FXMQ-PAVE FXMQ-PVM FXMQ-MFV1


VKM-GCVE VAM-GJVE

123 124
VRV Indoor Units
Round Flow Cassette with Sensing Type
FXFSQ-A

Comfort and energy saving by sensing functions Auto airflow function Comfort
*When human is not detected for 5 minutes, the unit automatically returns to controlling the flaps for an unoccupied room.

Daikin advanced sensing technology When human presence not detected. When human presence detected.
Direct Airflow (default: OFF) Deliver cool air to users
dual sensors Cooling Dry

Comfort and energy saving by sensing functions

Optimal air direction by “Auto” Optimal air direction Swing


Infrared presence sensor by “Auto” (narrow)
Detecting the presence
of people in 4 areas
C
B D Sensing sensor mode Energy saving
Infrared floor sensor A
Detecting the average
temperature of indoor floor Sensing sensor low mode (default: OFF)
When there are no people in a room, the set temperature is shifted automatically.

Example • Cooling setpoint: 26°C


• Shift temperature: 1.0°C
• Shift time: 30 min.
• Limit cooling temperature: 30°C

Comfort and energy saving preventing over cooling Comfort 28 28°C


27 27°C

Indoor Units
Sensors detecting human presence and temperatures near the floor provide comfortable 26 26°C 26°C
spaces without uneven temperatures.

Setpoint (°C)
Automatically
Occupied Unoccupied reverts when
Without sensing function With sensing function people return.

Cooling

30°C near ceiling 30°C near ceiling Time


too After After
cold 30 min another 30 min

20°C near floor 24°C near floor Sensing sensor stop mode (default: OFF)
Based on preset user conditions, the system automatically stops operation if the room is unoccupied.
Even when room temperature is detected at 30°C, the floor To prevent an excessive drop in temperature, room temperature is
temperature may be as low as 20°C, causing the feet area to be calculated at 27°C when people are in the vicinity. *Adjustment is possible for shift time and set temperature by local setting.
cold.

125 126
VRV Indoor Units
Round Flow Cassette with Sensing Type
Circulation airflow* Individual airflow direction control
* Applicable when wired remote controller BRC1E63 is used.

Configurations of circulation airflow


Comfortable air conditioning for all room layouts and conditions
Circulation airflow cools the entire room to deliver comfort that never feels cold.
Cooling Easy setting is possible with a wired remote controller

During 2-way horizontal flow


Airflow direction can be individually adjusted
for each air discharge outlet to deliver optimal air distribution.

Hot Position 0
outdoor (Fixed airflow to highest position) No individual setting
Airflow effectively avoids blowing air directly on people. air
(Auto airflow)

Individual airflow settings


Cool air moves down along the Cools by airflow blocking out No individual setting (Auto airflow)
walls and to every corner of the room. hot air near windows and walls. Position 0 (Highest point)
Position 1
Position 2
Position 3
Position 4 (Lowest point)
Swing

Individual settings are possible as stated above.

Position 4
Comfort without cold air pockets at floor level. Swing (Up/down) (Fixed airflow to the lowest position)

Comparison Conditions
Room size: Width 7.5m x depth 7.5m x height 2.6m
Indoor unit capacity: 71 class
Outdoor air temperature: 35°C
Airflow rate and air direction: high / swing
4-way cassette (Swing)
30.0
29.0
28.0
27.0
Comfort is provided to the entire room
26.0
25.0
by individual setting corresponding to 4-way flow conditions.
24.0
23.0
22.0
21.0

Indoor Units
20.0
Swing
Circulation Airflow reduce uneven temperatures Swing is set for meetings near No individual setting
(2-way horizontal + 4-way swing) the windows.
(Auto airflow)
30.0
29.0
28.0
27.0
26.0
25.0
24.0
Approx. 5% 23.0
22.0
energy savings* 21.0 Position 0
20.0 The airflow is at the highest
* Calculated under the following comparison conditions: Large blow is provided setting (Position 0)
When the average temperature at a height of 0.6m
to meeting areas near windows. for people who dislike air
above the floor reaches set temperature. (26°C) blowing directly on them.
Operation (at start)
Performs repeatedly
Airflow
direction
changes

When the target No individual setting


temperature is reached, (Auto airflow) Blow reduced for areas
normal operation with few people.
Cools areas around Cools entire room Cools areas around Cools entire room
walls using using 4-way walls using using 4-way (all-round flow) begins.
2-way horizontal flow swing flow 2-way horizontal flow swing flow

127 128
VRV Indoor Units
Round Flow Cassette with Sensing Type
Other functions
Comfort Panel (Option)
From All-round flow to 2-way flow, various airflow patterns available.

All-round flow 3-way flow L-shaped 2-way flow Opposite 2-way flow

Standard panel with sensing Standard panel with sensing


BYCQ125EEF (Fresh White) BYCQ125EEK (Black)

(E.g., installed in middle of ceiling) (E.g., installed near a wall) (E.g., installed in a corner) (E.g., installed in a long room)
4-way flow also possible.

Suitable for high ceilings Specifications


MODEL FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM
Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level. Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600
Cooling capacity
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Power consumption kW 0.028 0.035 0.056 0.061 0.092 0.164 0.170 0.194
Casing Galvanised steel plate

Quick and easy installation Airflow rate (H/HM/M/ML/L)


m3/min
cfm
13/12.5/11.5/11/10
459/441/406/388/353
17/13.5/12.5/12/11 23/20.5/19/14.5/11 23.5/21/20/16/13.5 24.5/22/20.5/20/15 33.5/30.5/27/23.5/21 34.5/31.5/28.5/25.5/23 35.5/32.5/29.5/26.5/23
600/477/441/424/388 812/724/671/512/388 830/741/706/565/477 865/777/724/706/530 1,183/1,077/953/830/741 1,218/1,112/1,006/900/812 1,253/1,147/1,041/935/812
Sound level (H/HM/M/ML/L) dB(A) 30/29.5/28.5/28/27 35/29.5/29/28/27 38/35/34.5/29.5/27 38/36/35.5/31.5/28 39/37/36/35.5/31 44/41/38/35/33 45/42.5/39.5/37/35 46/43.5/40.5/38/35
850 mm
Installable in tight ceiling spaces Dimensions (H×W×D)
Machine weight
mm
kg 19
256×840×840
24 22 25
298×840×840
26

Min. of 261 mm* ceiling space when using standard panel. 175 mm
Piping
Liquid (Flare) 6.4 9.5

connections Gas (Flare) mm 12.7 15.9


* For FXFSQ25-80A models.
Drain VP25 (External Dia. 32/Internal Dia. 25)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Drain pump is equipped as standard accessory with 850 mm lift. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Indoor Units
Panel (Option) Function List
Easy maintenance Just open the suction grille! Model BYCQ125EEF (Fresh White) Wired Wireless
Remote controller
Dimensions(H×W×D) mm 50×950×950 BRC1E63 BRC7M634F(K)
Standard
Drain pan and drain water check panel
with
Weight kg 5.5 Dual sensors *1 —
Drain outlet Model BYCQ125EEK (Black) Direct airflow *1 —
sensing
The condition of the drain pan and drain water can be (with rubber plug) Dimensions(H×W×D) mm 50×950×950 Sensing sensor low mode *1 —
Weight kg 5.5 Sensing sensor stop mode *1 —
checked by removing the suction grille and drain plug. Note: For inquiries concerning auto
Circulation airflow —
grille panel installations, please
contact your local dealer or Individual airflow direction control —
Daikin representative. Switchable 5 step fan speed
Auto airflow rate
Auto swing
Swing pattern selection
Cleanliness High ceiling application —
*1. Applicable when sensing panel is installed.

Silver ion anti-bacterial drain pan


Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
* Drain pan should be changed once every two to three years.

Filter has anti-mould and antibacterial treatment

129 130
VRV Indoor Units
Round Flow Cassette Type
FXFQ-A
Individual airflow direction control
* Applicable when wired remote controller BRC1E63 is used.

360° airflow for improved comfort


Comfortable air conditioning for all room layouts and conditions
Easy setting is possible with a wired remote controller
Circulation airflow*
Airflow direction can be individually adjusted
for each air discharge outlet to deliver optimal air distribution.
Configurations of circulation airflow
Circulation airflow cools the entire room to deliver comfort that never feels cold. Position 0
(Fixed airflow to highest position) No individual setting
Cooling (Auto airflow)
During 2-way horizontal flow Individual airflow settings
No individual setting (Auto airflow)
Position 0 (Highest point)
Hot Position 1
outdoor
Airflow effectively avoids blowing air directly on people. air Position 2
Position 3
Position 4 (Lowest point)
Cool air moves down along the Cools by airflow blocking out Swing
walls and to every corner of the room. hot air near windows and walls.
Individual settings are possible as stated above.

Position 4
Swing (Up/down) (Fixed airflow to the lowest position)

Comfort without cold air pockets at floor level.


Comparison Conditions
Room size: Width 7.5m x depth 7.5m x height 2.6m
Indoor unit capacity: 71 class
Outdoor air temperature: 35°C Comfort is provided to the entire room
Airflow rate and air direction: high / swing
4-way cassette (Swing) by individual setting corresponding to 4-way flow conditions.
30.0
29.0
28.0
27.0

Indoor Units
26.0
25.0
24.0 Swing
23.0
22.0
Swing is set for meetings near No individual setting
21.0 the windows.
20.0 (Auto airflow)
Circulation Airflow reduce uneven temperatures
(2-way horizontal + 4-way swing)
30.0
29.0
28.0
27.0
26.0
25.0
24.0
Approx. 5% 23.0 Position 0
22.0 The airflow is at the highest
energy savings* 21.0
20.0 Large blow is provided setting (Position 0)
to meeting areas near windows. for people who dislike air
* Calculated under the following comparison conditions:
When the average temperature at a height of 0.6m blowing directly on them.
above the floor reaches set temperature. (26°C)

Operation Performs repeatedly


(at start) Airflow
direction
changes

When the target No individual setting


temperature is reached, (Auto airflow) Blow reduced for areas
with few people.
Cools areas around Cools entire room Cools areas around Cools entire room
normal operation
walls using using 4-way walls using using 4-way (all-round flow) begins.
2-way horizontal flow swing flow 2-way horizontal flow swing flow

131 132
VRV Indoor Units
Round Flow Cassette Type
Other functions
Comfort Decoration Panel (Option)
From All-round flow to 2-way flow, various airflow patterns available. Standard panel Auto grille panel (option)
Grille and air filter cleaning can be performed
All-round flow 3-way flow L-shaped 2-way flow Opposite 2-way flow without need for a stepladder by lowering the
grille.

Standard panel Standard panel A dedicated remote controller for the auto grille panel (BRC16A2) is
BYCQ125EAF (Fresh White) BYCQ125EAK (Black) included. Operation is not possible using BRC1E63.

(E.g., installed in middle of ceiling) (E.g., installed near a wall) (E.g., installed in a corner) (E.g., installed in a long room) New designer panel
4-way flow also possible.
Designer choice has been given a boost with the
increase in number of new types of decoration panels.
Suitable for high ceilings
FLAT
Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level. Flatter styling:
Suction panel grid
texture smoothed.

Designer panel CLEAN


Clean-cut form:
Quick and easy installation BYCQ125EAPF (Fresh White)
Soiling is hard to see
on smart-looking panel. Wireless RC
850 mm

Close to ideal styling Grille panel can be lowered


Installable in tight ceiling spaces 175 mm
New designer panel
ROUND to a maximum of 3.9 m.
Subtle distinction:
BYCQ125EBSF (Fresh White)
Min. of 261 mm* ceiling space when using standard panel. around suction inlets
silvering is a tasteful touch.
* For FXFQ25-80A models
Specifications
Drain pump is equipped as standard accessory with 850 mm lift. MODEL FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXFQ80AVM FXFQ100AVM FXFQ125AVM FXFQ140AVM
Power supply 1-phase, 220 -240 V/220-230 V, 50/60 Hz
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600
Cooling capacity
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Power consumption kW 0.029 0.036 0.040 0.063 0.096 0.158 0.178 0.203
Casing Galvanised steel plate

Indoor Units
m3/min 13/12.5/11.5/11/10 17/13.5/13/12/11 18/17/13.5/12.5/11 21/20/16/15/13.5 22.5/21.5/21/20/15 32/29/26/23/21 33/30.5/28/25.5/21 35.5/32.5/29.5/26.5/23
Easy maintenance Just open the suction grille!
Airflow rate (H/HM/M/ML/L)
cfm 459/441/406/388/353 600/477/459/424/388 635/600/477/441/388 741/706/565/530/477 794/759/741/706/530 1,130/1,024/918/812/741 1,165/1,077/988/900/741 1,253/1,147/1,041/935/812
Sound level (H/HM/M/ML/L) dB(A) 30/29.5/28.5/28/27 35/29.5/29/28/27 35/33.5/29.5/28.5/27 36/35.5/31.5/31/28 37/36.5/36/35.5/29.5 43/40.5/37.5/35/33 44/41.5/39/36.5/33 46/43.5/40.5/38/35
Dimensions (H×W×D) mm 256×840×840 298×840×840
Drain pan and drain water check Machine weight kg 19 22 25 26
Drain outlet Liquid (Flare) 6.4 9.5
The condition of the drain pan and drain water can be (with rubber plug) Piping
Gas (Flare) mm 12.7 15.9
connections
checked by removing the suction grille and drain plug. Note: For inquiries concerning auto
Drain VP25 (External Dia. 32/Internal Dia. 25)
grille panel installations, please Notes: Specifications are based on the following conditions;
contact your local dealer or • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Daikin representative. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Cleanliness Decoration Panel (Option) Function List


Model BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black) Wired Wireless
Standard Remote controller
panel Dimensions(H×W×D) mm 50×950×950 BRC1E63 BRC7M635F(K)
Silver ion anti-bacterial drain pan Weight kg 5.5 Circulation airflow —
Model BYCQ125EAPF (Fresh White) Individual airflow direction control —
Prevents the growth of slime, bacteria, and mould that cause odours and clogging. Designer
panel Dimensions(H×W×D) mm 97×950×950 Switchable 5 step fan speed
* Drain pan should be changed once every two to three years. Weight kg 6.5 Auto airflow rate
Auto Model BYCQ125EBSF (Fresh White) Auto swing
grille Dimensions(H×W×D) mm 105×950×950 Swing pattern selection
panel
Weight kg 8 High ceiling application —
Filter has anti-mould and antibacterial treatment

133 134
VRV Indoor Units
Compact Multi Flow Cassette Type
FXZQ-A

Quiet, compact, and designed for user comfort

Compact & elegant design


• Fully-flat integration in standard architectural ceiling tiles, leaving
only 8 mm 8 mm
• Remarkable blend of iconic design and engineering excellence
with an elegant finish in white

• The newly designed panel integrates fully within one ceiling tile
enabling lights, speakers and sprinklers to be installed in the
adjoining ceiling tiles. Specifications
MODEL FXZQ20AVM FXZQ25AVM FXZQ32AVM FXZQ40AVM FXZQ50AVM
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling capacity

Efficiency & comfort


kW 2.2 2.8 3.6 4.5 5.6
Power consumption kW 0.043 0.045 0.059 0.092
Casing Galvanised steel plate
m³/min 8.7/7.5/6.5 9.0/8.0/6.5 10.0/8.5/7.0 11.5/9.5/8.0 14.5/12.5/10.0
Dual sensors (Option) Airflow rate (H/M/L)
cfm 307/265/229 318/282/229 353/300/247 406/335/282 512/441/353
Sound level (H/M/L) dB(A) 32.0/29.5/25.5 33.0/30.0/25.5 33.5/30.0/26.0 37.0/32.0/28.0 43.0/40.0/33.0
• Two optional intelligent sensors improve energy efficiency and
Sound power (H) dB(A) 49 50 51 54 60
comfort.
Dimensions (H×W×D) mm 260×575×575 (For depth add 63 mm for electrical box)
Machine weight kg 15.5 16.5 18.5
• An optional presence and floor sensor kit can be fitted to the
Liquid (Flare) 6.4
cassette for draught prevention, energy-saving operation and to Piping
Gas (Flare) mm 12.7
provide optimal control of airflow. connections
Drain VP20 (External Dia. 26/Internal Dia. 20)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Individual airflow direction control *1 • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

Indoor Units
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

• Airflow direction can be individually adjusted for each air discharge outlet to deliver optimal air
distribution.
*1. This function can only be set via wired remote controller BRC1E63. Panel (Option)
Panel type Grid ceiling panel

Auto swing (up/down)


Possibility to select automatic vertical moving of the air discharge flaps for efficient air and temperature Appearance

distribution throughout the room.

Model BYFQ60CAW
Colour White (N9.5)

Cleanliness Dimensions (H×W×D)


Weight
mm
kg
46×620×620
2.8

Ceiling soiling prevention


Prevents air from blowing against the ceiling to prevent ceiling stains.

135 136
VRV Indoor Units
Double Flow Cassette Type
FXCQ-A
Easy maintenance
Thin, lightweight, and easy to install in narrow ceiling spaces
• The flap parts are easy to clean because it is hard to condensate and get dirty.
• Check contamination in drain pan by simply removing suction grille and panel.

Stylish design • Adjuster pockets mount at four corners of the unit enable to adjust
the main unit without removing the panel.

• Stylish unit blends easily with any interior.


Adjuster Pocket
• The flat flaps close entirely when the unit is not
operating and there are no air intake grilles visible.
Drain socket part
• Depth of all units is 620 mm, ideal for narrow spaces
Flexible installation
• Drain pump is equipped as standard accessory with 850 mm lift.
Comfort
Individual airflow direction control*1
Cleanliness
• Airflow direction can be individually adjusted
for each air discharge outlet to Individual airflow settings
deliver optimal air distribution.
Silver ion anti-bacterial drain pan
No individual setting (Auto airflow)
*1. The function can only be set via BRC1E63. • Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
Position Position 0 (Highest point) * Drain pan should be changed once every two to three years.
Position 1
Position 2
Position 3 Filter has anti-mould and antibacterial treatment
Position 4 (Lowest point)
Swing
Individual settings are possible as stated above.

Position 0 Swing
(Fixed airflow to highest position) (Up / Down) Specifications
MODEL FXCQ20AVM FXCQ25AVM FXCQ32AVM FXCQ40AVM FXCQ50AVM FXCQ63AVM FXCQ80AVM FXCQ125AVM

Indoor Units
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 30,700 47,800
Cooling capacity
5-step & auto airflow control kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0
Power consumption kW 0.031 0.039 0.041 0.059 0.063 0.090 0.149
Casing Galvanised steel plate
• Control of airflow rate has been improved from 3-step to 5-step. Auto airflow rate is newly available.
m3/min 10.5/9.5/9/8/7.5 11.5/10.5/9.5/8.5/8 12/11/10.5/9.5/8.5 15/14/13/11.5/10.5 16/15/14/12.5/11.5 26/24/22.5/20.5/18.5 32/29.5/27.5/25/22.5
Airflow rate (H/HM/M/ML/L)
cfm 371/335/318/282/265 406/371/335/300/282 424/388/371/335/300 530/494/459/406/371 565/530/494/441/406 918/847/794/724/653 1,130/1,041/971/883/794
Sound level (H/HM/M/ML/L) dB(A) 32/31/30/29/28 34/33/31/30/29 34/33/32/31/30 36/35/33/32/31 37/36/35/33/31 39/38/37/35/32 42/40/38/36/33 46/44/42/40/38
Dimensions (H × W × D) mm 305×775×620 305×990×620 305×1,445×620
Suitable for high ceilings Machine weight kg 19 22 25 33 38
Liquid (Flare) 6.4 9.5
• Even in spaces with high ceilings maximum 3.5 m, a comfortable airflow is carried down to the floor level. Piping
connections
Gas (Flare) mm 12.7 15.9
Drain VP25 (External Dia. 32/Internal Dia. 25)
Model BYBCQ40CF BYBCQ63CF BYBCQ125CF
Panel Colour Fresh white (6.5Y 9.5/0.5)
(Option) Dimensions (H×W×D) mm 55×1,070×700 55×1,285×700 55×1,740×700
300 Power consumption comparison (Cooling)
278 Weight kg 10 11 13

Energy saving
Power consumption (W)

Notes: Specifications are based on the following conditions;


216 • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
200 • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
157 149
• Power consumption is significantly 132 132
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

reduced by specially developed small tube 100 95 90


81
heat exchanger and DC fan motor. 59 63
31 39 41
0
20 25/32 40 50 63 80 125
Model class
Conventional model: FXCQ-M New model: FXCQ-A
137 138
VRV Indoor Units
Corner Cassette Type
FXKQ-MA

Slim design for flexible installation

Slim design
• Slim body needs only 220 mm space above the ceiling. If you use a panel spacer (option),
the unit can be installed in the minimum space of 195 mm.

Min.195 mm

Panel spacer
20 mm

Flexible installation
• Front discharge is possible with an air discharge unit (option), which allows the installation in
the drop-ceiling or sagging wall.

Main body Main body

Specifications
Downward discharge MODEL FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz
Air discharge grille Btu/h 9,600 12,300 15,400 24,200
Cooling capacity
Air discharge grille (Option) (Option) kW 2.8 3.6 4.5 7.1
Power consumption kW 0.066 0.076 0.105
Casing Galvanised steel plate
m3/min 11/9 13/10 18/15
Airflow rate (H/L)
cfm 388/318 459/353 635/530

Indoor Units
220 V 38/33 40/34 42/37
Set for front discharge using a suspended ceiling. Downward discharge is shut off and air is blown straight out Sound level (H/L) dB(A)
(front discharge). 240 V 40/35 42/36 44/39
Dimensions (H×W×D) mm 215×1,110×710 215×1,310×710
Machine weight kg 31 34
• Drain pump is equipped as standard accessory with 500 mm lift. Liquid (Flare) 6.4 9.5
Piping
Gas (Flare) mm 12.7 15.9
connections
Drain VP25 (External Dia. 32/Internal Dia. 25)
Model BYK45FJW1 BYK71FJW1
Panel Colour White (10Y9/0.5)
(Option) Dimensions(H×W×D) mm 70×1,240×800 70×1,440×800
Weight kg 8.5 9.5
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

139 140
VRV Indoor Units
3D Airflow Duct with Sensing Type
FXDSQ-A

3D airflow with sensing function for comfort and energy savings Comfort and energy saving preventing over cooling
Cooling

Comfort 30°C near ceiling


3D airflow Room temperature is
calculated as 27°C in the area which
is in the vicinity of the person.
The wide coverage of the airflow angle
creates a comfortable 3D airflow.
• Horizontal & Vertical direction can be adjusted freely by 24°C near floor
the remote controller settings as to provide 3D airflow to
every corner of the room.
Sensing sensor mode Example • Cooling setpoint: 26°C
• Shift temperature: 1.0°C
• Can freely select 5 positions and swing mode for each • Shift time: 30 min.
up/ down and left/right direction with remote controller. Sensing sensor low mode (default: OFF) • Limit cooling temperature: 30°C

• When there are no 28 28°C


people in a room, the 27 27°C
26 26°C 26°C
set temperature is

Setpoint (°C)
shifted automatically. Automatically
Occupied Unoccupied reverts when
60

Horizontal Cooling range people return.


°

flaps of swing

Vertical flaps 45° 45°

After After Time


30 min another 30 min
5-step & auto airflow control
• Control of airflow rate can be selected from 5-step and Auto to provide comfortable airflow.
Sensing sensor stop mode (default: OFF)
• Based on preset user conditions, the system automatically stops operation if the room is unoccupied.

Indoor Units
*Adjustment is possible for shift time and set temperature by local setting.

Installation flexibility Specifications


Only 450 mm MODEL FXDSQ20AVM FXDSQ25AVM FXDSQ32AVM FXDSQ40AVM FXDSQ50AVM FXDSQ63AVM

Slim design 200 mm


Power supply
Cooling capacity
Btu/h 7,500 9,600
1-phase, 220-240/220-230 V, 50/60 Hz
12,300 15,400 19,100 24,200
kW 2.2 2.8 3.6 4.5 5.6 7.1
• Slim and compact design with a height of only 200 mm and the depth Power consumption *1 kW 0.028 0.029 0.032 0.049 0.054
of only 450 mm which is suitable to install in limited spaces. Casing Galvanized steel plate
* Panel dimensions are not included.
Airflow rate (H/HM/M/ML/L) m3/min 8.7/8.1/7.6/7.0/6.5 9.0/8.5/8.0/7.5/7.0 10.0/9.3/8.6/7.9/7.2 12.0/11.2/10.5/9.7/9.0 15.0/14.0/13.0/11.5/10.5 19.0/17.0/15.0/13.0/11.5
External static pressure Pa 10-0 *2
Sound level (H/HM/M/ML/L)*1 *3 dB(A) 31/29/27/26/24 31/29/27/26/24 34/32/30/29/27 39/37/35/33/31 39/37/35/33/30
Dimensions (H×W×D) mm 200×700×450 200×900×450 200×1,100×450

Daikin advanced sensing technology Machine weight

Piping
Liquid (Flare)
Gas (Flare)
kg

mm
17
6.4 (flare)
12.7 (flare)
20 23
9.5 (flare)
15.9 (flare)
connections
Drain PVC26 (External Dia. 26 / Internal Dia. 20)
Dual sensors 3D Auto
swing
Dimensions (H×W×D)
Colour
mm 180×722×70
Fresh white
180×922×70 180×1,122×70

panel Weight kg 1.0 1.5 2.0


Infrared presence sensor Notes: Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 5 m, Level difference: 0 m.
The presence sensor detects where people are and adjusts the airflow direction •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
accordingly. •Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Infrared floor sensor *1: Values are based on external static pressure of 10 Pa.
*2: External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”. (Factory setting is 10 Pa )
The sensor detects the floor temperature and automatically adjusts operation of the
*3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
indoor unit to reduce the temperature difference between the ceiling and the floor.

141 142
VRV Indoor Units
Slim Duct (Standard) Type Slim Duct (Compact) Type
FXDQ-PD / ND FXDQ-SP

Slim design, quietness and ideal for drop-ceilings Slim and compact design for easy and flexible installation

Comfort Installation flexibility


• Control of the airflow rate can be selected from 3-step • Slim and compact design with a height of only 200 mm
control and Auto. Auto airflow rate control can be and the depth of only 450 mm which is suitable to
selected with wired remote controller. install in limited spaces.

• Low operation sound level: down to 23 dB(A)


200 mm
Great for
residential use
Only 450 mm

Installation flexibility 700 mm*


*For FXDQ20-32SP models

• Only 200 mm in height, this model can be


Great for
installed in rooms with as little as 240 mm in hotel use!
height for the ceiling space between the

600 mm
FXDQ20-32PD FXDQ40/50ND
drop-ceiling and ceiling slab. 240 mm
200 mm and 450 mm
200 mm 200 mm above 700 mm
• FXDQ-PD and FXDQ-ND models are available in
two types to suit different installation Ceiling
conditions. Only 700 mm 900 mm Side view Top view

FXDQ-PD/NDVE: with a drain pump (750 mm lift) as a standard accessory


FXDQ-PD/NDVET: without a drain pump
*1,100 mm in width for the FXDQ63ND model. • Drain pump is equipped as standard accessory with 750 mm lift.

Specifications Specifications
with drain pump FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE MODEL FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1
MODEL
without drain pump FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET Power supply 1-phase, 220-240 V, 50 Hz
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity

Indoor Units
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1 Power consumption 1
kW 0.072 0.075 0.078 0.180 0.196
Power consumption Casing Galvanised steel plate
(FXDQ-PD/NDVE) 1 kW 0.086 0.089 0.160 0.165 0.181
m3/min 8.7/7.6/6.5 9.0/8.0/7.0 10.0/9.0/8.0 15.0/13.0/10.5 20.0/16.0/12.5
Airflow rate (HH/H/L)
Power consumption cfm 307/268/229 318/282/247 353/318/282 530/459/371 706/565/441
kW 0.067 0.070 0.147 0.152 0.168
(FXDQ-PD/NDVET) 1 External static pressure Pa 30-10 2 50-20 2 40-20 2
Casing Galvanised steel plate Sound level (HH/H/L) 1 3
dB(A) 33/31/29 34/32/30 35/33/31 37/35/33
m3/min 8.0/7.2/6.4 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0 Dimensions (H×W×D) mm 200×700×450 200×900×450 200×1,100×450
Airflow rate (HH/H/L)
cfm 282/254/226 371/335/300 441/388/353 583/512/459 Machine weight kg 17 20 23
External static pressure Pa 30-10 2
44-15 2 Liquid (Flare) 6.4 9.5
Piping
Sound level (HH/H/L) 1 3 dB(A) 28/26/23 28/26/24 30/28/26 33/30/27 33/31/29 connections Gas (Flare) mm 12.7 15.9
Dimensions (H×W×D) mm 200×700×620 200×900×620 200×1,100×620 Drain VP20 (External Dia. 26/Internal Dia. 20)
Machine weight kg 23 27 28 31 Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 5 m, Level difference: 0 m.
Liquid (Flare) 6.4 9.5
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Piping Gas (Flare)
connections
mm 12.7 15.9 • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
Drain During actual operation, these values are normally somewhat higher as a result of ambient conditions.
VP20 (External Dia. 26/Internal Dia. 20)
*1: Values are based on the following conditions: FXDQ20-32SP: external static pressure of 10 Pa; FXDQ40-63SP: external static pressure of 20 Pa.
Notes: Specifications are based on the following conditions; *2: External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”.
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (Factory setting is 10 Pa for FXDQ20-32SP models and 20 Pa for FXDQ40-63SP models.)
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) *3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Values are based on the following conditions: FXDQ-PD: external static pressure of 10 Pa; FXDQ-ND: external static pressure of 15 Pa.
*2: External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting is
10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND models.)
*3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).

143 144
VRV Indoor Units
Middle Static Pressure Duct Type
FXSQ-PA
Comfort
Middle static pressure and slim design allow flexible installations
• Control of the airflow rate can be selected from 3-step control. Auto airflow rate control can be
selected with wired remote controller.

Installation flexibility • Lower sound level: down to 28 dB(A)


Separate drain pipe and inspection opening

Slim design Easy maintenance


• With a height of only 245 mm, • Inspection and cleaning is facilitated by separating the drain pipe
installation is possible and inspection opening and by the drain pan maintenance check hole.
even in buildings with 245 mm
narrow ceiling spaces. Drain pan
maintenance
check hole

Standard DC drain pump Cleanliness


• DC drain pump is equipped as standard accessory
with 850 mm lift. Silver ion anti-bacterial drain pan
• Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
Air conditioner Joist
Bottom suction possible * Drain pan should be changed once every two to three years.

• Bottom suction is possible which facilitates installation and Air suction Filter has anti-mould and antibacterial treatment
maintenance. Wiring connections and maintenance of control box ceiling

can be done from under the unit with an optional shield plate for side plate.
Specifications
MODEL FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz

Design flexibility
Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6
Power consumption kW 0.058*1 0.066*1 0.101*1 0.075*1
Adjustable external static pressure Casing Galvanised steel plate

Adjustable external static pressure


30 Pa* 150 Pa
m3/min 9/7.5/6.5 9.5/8/7 15/12.5/10.517/14.5/11.5
Airflow rate (H/M/L)
cfm 318/265/230 335/282/247 530/441/371 600/512/406
• Using a DC fan motor, the external static pressure can be External static pressure Pa 30-150 (50) *2 50-150 (50) *2
* 30 Pa–150 Pa for FXSQ20-40PAVE Sound level (H/M/L) dB(A) 33/30/28 34/32/30 36/33/30 34/32/29
controlled within a range of 30 Pa* to 150 Pa.

Indoor Units
50 Pa–150 Pa for FXSQ50-125PAVE Notes:
50 Pa–140 Pa for FXSQ140PAVE Dimensions (H×W×D) mm 245×550×800 245×700×800 245×1,000×800
Specifications are based on the following
Machine weight kg 25 27 35 conditions;
Liquid (Flare) 6.4 • Cooling: Indoor temp.: 27°CDB, 19°CWB,
Piping Outdoor temp.: 35°CDB, Equivalent

Easy installation
Gas (Flare) mm 12.7 piping length: 7.5 m, Level difference: 0
connections
Drain VP25 (External Dia. 32/Internal Dia. 25) m.
• Capacity of indoor unit is only for
MODEL FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE reference. Actual capacity of indoor unit
is based on the total capacity index. (See
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Engineering Data Book for details.)
“Airflow rate auto adjustment function” at field setting Cooling capacity
Btu/h 24,200 30,700 38,200 47,800 54,600 • Sound level: Anechoic chamber
conversion value, measured at a point
(local setting by remote controller) kW 7.1 9.0 11.2 14.0 16.0
1.5 m downward from the unit centre.
Duct resistance at Power consumption kW 0.106*1 0.126*1 0.151*1 0.206*1 0.222*1 During actual operation, these values
designing system Casing Galvanised steel plate are normally somewhat higher as a
*This function can only be set via wired remote controller.
rpm 1 result of ambient conditions.
Actual duct m3/min 21/17.5/14.5 23/19.5/16 32/27/22.5 37/31.5/26 39/33.5/28
resistance Airflow rate (H/M/L)
Various adjustments are required rpm 2 cfm 741/618/512 812/688/565 1,130/953/794 1,306/1,112/918 1,377/1,183/988 *1: Power consumption values are based
Field setting
External static pressure (ESP)

without “airflow rate (Due to excess or deficiency of Pa 50-150 (50) *2 50-140 (50) *2 on conditions of rated external static
External static pressure
Design Installation airflow) e.g. Duct re-construction, pressure.
auto adjustment function” Sound level (H/M/L) dB(A) 36/32/29 37.5/34/30 39/35/32 42/38.5/35 43/40/36
Motor replacement, Damper *2: External static pressure can be
replacement, etc. Dimensions (H×W×D) mm 245×1,000×800 245×1,400×800 245×1,550×800 modified using a remote controller
that offers thirteen (FXSQ20-40PA),
Machine weight kg 35 37 46 47 52
rpm 7 System eleven (FXSQ50-125PA) or ten
Field setting Innovating operation Liquid (Flare) 9.5 (FXSQ140PA) levels of control. These
with “airflow rate Function! Piping values indicate the lowest and highest
Design Installation Gas (Flare) mm 15.9
auto adjustment function” rpm 8 connections possible static pressures. The rated
Drain VP25 (External Dia. 32/Internal Dia. 25) static pressure is 50 Pa.
by remote controller

<Mechanism>
1. During field setting, power input of DC fan is detected. Rated airflow Airflow
2. External static pressure is estimated from power input of DC fan because PCB
of FXSQ-PA has table of external static pressure vs. power input of DC fan. Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated airflow.
3. Actual duct resistance is calculated according to 1 and 2. (Refer to Engineering Data Book for details)
4. Fan speed is automatically adjusted to produce rated airflow. ”Airflow rate auto adjustment function” should be used at field setting only.

145 146
VRV Indoor Units
Middle-High Static Pressure Duct Type
FXMQ-PA
Cleanliness
Middle and high static pressure allows for flexible duct design Silver ion anti-bacterial drain pan
Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
*Drain pan should be changed once every two to three years.

Design flexibility Filter has anti-mould and antibacterial treatment


Using a DC fan motor, the external static pressure can
be controlled within a range of 30 Pa* to 200 Pa*.

Adjustable external static pressure


Specifications
30 Pa* 200 Pa MODEL FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
*30 Pa – 100 Pa for FXMQ20PA-32PA
*30 Pa – 160 Pa for FXMQ40PA Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling capacity
*50 Pa – 200 Pa for FXMQ50PA-125PA kW 2.2 2.8 3.6 4.5 5.6
*50 Pa – 140 Pa for FXMQ140PA
Power consumption kW 0.056 *1 0.060 *1 0.151 *1 0.128 *1
Casing Galvanised steel plate

Easy installation Airflow rate (HH/H/L)


m3/min
cfm
9/7.5/6.5
318/265/230
9.5/8/7
335/282/247
16/13/11
565/459/388
18/16.5/15
635/582/530
External static pressure Pa 30-100 (50) *2 30-160 (100) *2 50-200 (100) *2
“Airflow rate auto adjustment function” at field setting Sound level (HH/H/L) dB(A) 33/31/29 34/32/30 39/37/35 41/39/37
Duct resistance at
(local setting by remote controller) designing system Dimensions (H×W×D) mm 300x550x700 300x700x700 300x1,000x700
rpm 1 Machine weight kg 25 27 35
*This function is not available with FXMQ140PAVE. Actual duct
*This function can only be set via wired remote controller. rpm 2 resistance Liquid (Flare) 6.4
Piping
External static pressure (ESP) mm 12.7
Gas (Flare)
Field setting Various adjustments are required connections
without “airflow rate (Due to excess or deficiency of Drain VP25 (External Dia. 32/Internal Dia. 25)
Design Installation airflow) e.g. Duct re-construction,
auto adjustment function”
Motor replacement, Damper
replacement, etc.
rpm 7 System
operation MODEL FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
Field setting Innovating Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
rpm 8
Design Installation
with “airflow rate Function! Btu/h 24,200 30,700 38,200 47,800 54,600
auto adjustment function” Cooling capacity
by remote controller
kW 7.1 9.0 11.2 14.0 16.0
Power consumption kW 0.138 *1 0.185 *1 0.215 *1 0.284 *1 0.405 *1
<Mechanism> Rated airflow Airflow Casing Galvanised steel plate

Indoor Units
1. During field setting, power input of DC fan is detected.
2. External static pressure is estimated from power input of DC fan because PCB of Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated
m3/min 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 46/39/32
Airflow rate (HH/H/L)
FXMQ-PA has table of external static pressure vs. power input of DC fan. airflow. (Refer to Engineering Data Book for details) cfm 688/618/565 883/794/706 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
3. Actual duct resistance is calculated according to 1 and 2. ”Airflow rate auto adjustment function” should be used at field setting only.
4. Fan speed is automatically adjusted to produce rated airflow. External static pressure Pa 50-200 (100) *2 50-140 (100) *2
Sound level (HH/H/L) dB(A) 42/40/38 43/41/39 44/42/40 46/45/43
• All models are only 300 mm in height and the weight of the FXMQ40-140PA has been reduced. Dimensions (H×W×D) mm 300×1,000×700 300×1,400×700

• Drain pump is equipped as standard accessory with 700 mm lift. Machine weight kg 35 45 46
Liquid (Flare) 9.5
Piping
Gas (Flare) mm 15.9
connections

Comfort Drain

Notes: Specifications are based on the following conditions;


VP25 (External Dia. 32/Internal Dia. 25)

• Control of the airflow rate can be selected from 3-step control and Auto. Auto airflow rate control can • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
be selected with wired remote controller. • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
• Low operation sound level: down to 29 dB(A) *1: Power consumption values are based on conditions of rated external static pressure.
*2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32PA), thirteen (FXMQ40PA), fourteen (FXMQ50-125PA) or
ten (FXMQ140PA) levels of control.
These values indicate the lowest and highest possible static pressures. The rated static pressure is 50 Pa for FXMQ20-32PA and 100 Pa for FXMQ40-140PA.

Energy saving
Separate drain pipe and inspection opening
• DC fan motor is used to realise energy-saving operation.

Easy maintenance
Inspection and cleaning is facilitated by separating the drain pipe
Drain pan maintenance
147
and inspection opening and by the drain pan maintenance check hole. check hole 148
VRV Indoor Units
High Static Pressure Duct Type
FXMQ-P
Easy maintenance
High static pressure allows for flexible duct design.
• Inspection and cleaning is facilitated by separating
the inspection opening and the drain pan maintenance check hole.
Separate inspection opening

Design flexibility
Adjustable external static pressure Drain pan maintenance
check hole

• Using a DC fan motor, the external static pressure can be


controlled within a range of 50 Pa to 250 Pa.

Adjustable external static pressure

50 Pa 250 Pa • Heat exchanger, drain pan and fan deck can be easily
accessed and removed from bottom for maintenance.

Easy installation
“Airflow rate auto adjustment function” at field setting
(local setting by remote controller) Duct resistance at
designing system
rpm 1
*This function can only be set via wired remote controller. Actual duct
rpm 2 resistance Specifications
External static pressure (ESP)

Various adjustments are required MODEL FXMQ200PVM FXMQ250PVM


Field setting
without “airflow rate (Due to excess or deficiency of Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz

Indoor Units
Design Installation airflow) e.g. Duct re-construction,
auto adjustment function”
Motor replacement, Damper Btu/h 76,400 95,500
replacement, etc. Cooling capacity
rpm 7 System kW 22.4 28.0
operation Power consumption kW 0.55 *1 0.67 *1
Field setting Innovating
rpm 8 Casing Galvanised steel plate
Design Installation
with “airflow rate Function!
auto adjustment function” m3/min 74/61/50 84/71/58
Airflow rate (HH/H/L)
by remote controller cfm 2,612/2,153/1,765 2,965/2,506/2,047

Rated airflow Airflow External static pressure Pa 50-250 (150) *2 50-250 (150) *2
<Mechanism>
1. During field setting, power input of DC fan is detected. Sound level (HH/H/L) dB(A) 42/38/35 44/40/37
Notes: ”Airflow rate auto adjustment function” can be adjusted within ±10% of rated
2. External static pressure is estimated from power input of DC fan because PCB Dimensions (H × W × D) mm 470×1,490×1,100 470×1,490×1,100
airflow. (Refer to Engineering Data Book for details)
of FXMQ-P has table of external static pressure vs. power input of DC fan.
”Airflow rate auto adjustment function” should be used at field setting only. Machine weight kg 95 105
3. Actual duct resistance is calculated according to 1 and 2.
4. Fan speed is automatically adjusted to produce rated airflow. Liquid (Flare) 9.5
Piping
connections
Gas (Flange) mm 19.1 22.2
Drain BSP1”
Notes: Specifications are based on the following conditions;

Built-in pre-filter slot • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
• To cater for easy installation of filter at site, During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1: Power consumption values are based on conditions of rated external static pressure.
a filter rail is available at the return flange. *2: External static pressure can be modified using a remote controller that offers fifteen levels of control.
These values indicate the lowest and highest possible static pressures. The standard static pressure is 150 Pa.

149 150
VRV Indoor Units
4-way Flow Ceiling Suspended Type Ceiling Suspended Type
FXUQ-A FXHQ-MA / A FXHQ32 / 63 / 100MA FXHQ125 / 140A

Slim and stylish design, optimum air distribution, Slim body with quiet
installation without ceiling cavity and wide airflow

Slim and stylish design Comfort


• Unit body and suction panel have round shapes that form a slim design, that fits various locations such • Auto swing (up and down) and louvers (left and right by hand)
as the ceilings without cavity. bring comfort to the room.
• Louver manually adjusts for straight or wide angle airflow.
• Flaps close automatically when the unit stops, which gives a simple appearance. Required installation space (mm)
30 or more 30 or more
• All models have a unified slim height of 198 mm that gives a similar impression even when models with
different capacities are installed in the same area. Installation flexibility
• Flexible installation
Comfort The unit fits more snugly into tight spaces. * Water used in the test-run can be drained from the air discharge
opening rather than from the side as was formerly the case.
• Airflow direction adjustment can be individually adjusted for each air discharge outlet to deliver • Drain pump kit (option) can be easily incorporated.
optimal air distribution. 5 directions of airflow and auto-swing can be selected with wired remote Drain pipe connection can be done inside the unit. 600 mm
controller BRC1E63. Refrigerant and drain pipe outlets are at the same opening.
• Control of the airflow rate can be selected from 3-step control. Auto airflow rate control can be • All wiring and internal servicing can be done from under the unit.
Drain pump kit
selected with wired remote controller. (built inside the unit)

New 125 / 140 models provide greater capacity for large spaces
Flexible installation 4-way flow 3-way flow L-shaped 2-way flow
• The technology of the DC fan motor, wide sirocco fan, and large heat exchanger combine
• Drain pump is equipped as a standard for greater airflow and quiet operation.
accessory with 600 mm lift.
• Sophisticated design: Flap neatly closes when not in use.
• Depending on installation site requirements
or room conditions, 2-way, 3-way and 4-way • Suitable for high ceilings: maximum 4.3 m
discharge patterns are available. • Control of airflow rate has been improved from 2-step to 3-step.
• Drain pump kit (option) includes a silver ion antibacterial agent that assists in preventing the growth
Cleanliness of slime, bacteria, and mould that cause smells and clogging.

Silver ion anti-bacterial drain pan • The rear side removable frame allows ease of access for piping work.

Indoor Units
Easier piping work
• Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
* Drain pan should be changed once every two to three years.
Specifications
Filter has anti-mould and antibacterial treatment MODEL FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE FXHQ125AVM FXHQ140AVM
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz
Specifications
Btu/h 12,300 24,200 38,200 48,000 52,900
Cooling capacity
MODEL FXUQ71AVEB FXUQ100AVEB kW 7.1 11.2 14.1 15.5
3.6
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz Power consumption kW 0.111 0.115 0.135 0.168 0.181
Btu/h 27,300 38,200 Casing White (10Y9/0.5) Sheet Metal / White
Cooling capacity
kW 8.0 11.2 Notes:
m3/min 17.5/-/14 25/-/19.5 34/26/20 36/27/20
Specifications are based on the following 12/-/10
0.090 0.200 Airflow rate (H/M/L)
Power consumption kW conditions; cfm 618/-/494 883/-/688 1,200/918/706 1,271/953/706
424/-/353
Casing Fresh white • Cooling: Indoor temp.: 27°CDB, 19°CWB,
Outdoor temp.: 35°CDB, Sound level (H/M/L) dB(A) 36/-/31 39/-/34 45/-/37 46/41/37 48/42/37
m3/min 22.5/19.5/16 31/26/21 Equivalent piping length: 7.5 m,
Airflow rate (H/M/L) Dimensions (H × W × D) mm 195×960×680 195×1,160×680 195×1,400×680 235×1,590×690
cfm 794/688/565 1,094/918/741 Level difference: 0 m.
• Capacity of indoor unit is only for Machine weight kg 24 28 33 41
Sound level (H/M/L) dB(A) 40/38/36 47/44/40 reference. Actual capacity of indoor unit is
6.4
based on the total capacity index. (See
Liquid (Flare) 9.5
Dimensions (H×W×D) mm 198×950×950 Piping
Engineering Data Book for details.) Gas (Flange) mm 12.7 15.9
connections
Machine weight kg 26 27 • Sound level: Anechoic chamber conversion
value, measured at a point 1 Drain VP20 (External Dia. 26/Internal Dia. 20)
Liquid (Flare) 9.5 m in front of the unit and 1 m Notes: Specifications are based on the following conditions;
Piping downward. During actual
Gas (Flare) mm 15.9 • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
connections operation, these values are • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Drain VP20 (External Dia. 26/Internal Dia. 20) normally somewhat higher as • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
a result of ambient conditions During actual operation, these values are normally somewhat higher as a result of ambient conditions.

151 152
VRV Indoor Units
Wall Mounted Type
FXAQ-A

Stylish flat panel design harmonised


with your interior décor

Comfort
Higher airflow
An invisible air intake at the top of the unit

• An invisible air intake at the top of the unit Specifications


• Vertical auto-swing enables efficient air and temperature distribution throughout the room. MODEL FXAQ20AVM FXAQ25AVM FXAQ32AVM FXAQ40AVM FXAQ50AVM FXAQ63AVM
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
• The louver closes automatically when the unit stops. Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
• Enhanced comfort is achieved. kW 2.2 2.8 3.6 4.5 5.6 7.1
Power consumption kW 0.040 0.040 0.040 0.050 0.060 0.100
• 5 step discharge angles can be set by remote controller. Casing Resin / White N9.5
• Discharge angle is automatically set at the same angle as previous operation when restart. Airflow rate (H/L)
m3/min 9.1/7.0 9.4/7.0 9.8/7.0 12.2/9.7 15.0/12.0 19.0/14.0
cfm 321/247 332/247 346/247 431/342 530/424 671/494
Sound level (H/L) dB(A) 33.0/28.5 35.0/28.5 37.5/28.5 37.0/33.5 41.0/35.5 46.5/38.5
Dimensions (H × W × D) mm 290×795×266 290×1,050×269
Machine weight kg 12 15
Lower sound level Liquid (Flare) 6.4 9.5
Piping
Gas (Flange) mm 12.7 15.9
• Whisper quiet in operation, with sound levels as low as 28.5 dB(A)* connections
Drain VP13 (External Dia. 18/Internal Dia. 15)

Indoor Units
*Sound level for FXAQ20-32A
Notes: Specifications are based on the following conditions;
• An ideal solution for a wide range of commercial spaces, including individual office spaces. • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Stylish design and cleanliness


• Stylish flat panel design creates a graceful harmony that enhances any interior space.
• Flat panel can be cleaned with only the single pass of a cloth across their smooth surface.
Flat panel can also be easily removed and washed for more thorough cleaning.
• Drain pan and air filter can be kept clean by mould-proof polystyrene.

Flexible installation
Height of drain-up

Indoor unit
• Drain pipe can be fitted to from either left or right sides. 1,000
mm
• Drain pump kit is available as optional accessory,
which lifts the drain 1,000 mm from the bottom of the unit.
Drain pump kit

153 154
VRV Indoor Units
Floor Standing Type Concealed Floor Standing Type
FXLQ-MA FXNQ-MA

Suitable for perimeter zone air conditioning Designed to be concealed in the perimeter skirting-wall

• Floor Standing types can be hung on the wall for easier cleaning. Running the piping from the back • The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design.
allows the unit to be hung on walls. Cleaning under the unit, where dust tends to accumulate, is
considerably easier. • The connecting port faces downward, greatly facilitating on-site piping work.

• The adoption of a fibre-less discharge grille featuring an original design to prevent condensation also • A long-life filter (maintenance free up to one year*) is equipped as standard accessory.
helps prevent staining and makes cleaning easier. *8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

• A long-life filter (maintenance free up to one year*) is equipped as standard accessory.


*8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Specifications
MODEL FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
Specifications Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
MODEL FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz kW 2.2 2.8 3.6 4.5 5.6 7.1
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 Power consumption kW 0.049 0.090 0.110
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1 Casing Galvanised steel plate
Power consumption kW 0.049 0.090 0.110
m3/min 7/6 8/6 11/8.5 14/11 16/12
Casing Ivory white (5Y7.5/1) Airflow rate (H/L)
cfm 247/212 282/212 388/300 494/388 565/424
m3/min 7/6 8/6 11/8.5 14/11 16/12
Airflow rate (H/L) 220 V 35/32 38/33 39/34 40/35
cfm 247/212 282/212 388/300 494/388 565/424 Sound level (H/L) dB(A)
240 V 37/34 40/35 41/36 42/37
220 V 35/32 38/33 39/34 40/35
Sound level (H/L) dB(A) Dimensions (H × W × D) mm 610×930×220 610×1,070×220 610×1,350×220
240 V 37/34 40/35 41/36 42/37
Machine weight kg 19.0 23.0 27.0
600×1,000×222 600×1,140×222 600×1,420×222

Indoor Units
Dimensions (H × W × D) mm
Machine weight kg 25 30 36 Liquid (Flare) 6.4 9.5
Piping
Liquid (Flare) 6.4 9.5 connections Gas (Flare) mm 12.7 15.9
Piping mm 12.7 15.9 Drain 21O.D.
Gas (Flare)
connections
Drain 21O.D. Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Notes: Specifications are based on the following conditions; • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

155 156
VRV Indoor Units
Floor Standing Duct Type
FXVQ-N

Large airflow type for large spaces

• Full-scale duct connection airflow allows for air conditioning evenly in spacious areas.

Duct connection airflow type Direct airflow type

• Adding the plenum chamber (option) allows for simple operation with direct airflow.
*Note that the operation sound increases by approximately 5dB(A). Specifications
MODEL FXVQ125NY1 FXVQ200NY1 FXVQ250NY1 FXVQ400NY1 FXVQ500NY1 FXVQ500NY16
Power supply 3-phase 4-wire system, 380–415 V, 50 Hz
• The belt drive system allows for use of air discharge outlets in various shapes as well as long ducts. Btu/h 47,800 76,400 95,500 154,000 191,000
Cooling capacity
kW 14.0 22.4 28.0 45.0 56.0
Power consumption kW 0.53 1.33 1.61 3.97 2.62 4.70
• A long-life filter (maintenance free up to one year*) is equipped as a standard accessory. Casing colour Ivory white (5Y7.5/1)
*8 hr/day, 26 day/month. For dust concentration of 0.15 mg/m3 Dimensions (H × W × D) mm 1,670×750×510 1,670×950×510 1,670×1,170×510 1,900×1,170×720 1,900×1,470×720
Machine weight kg 118 144 169 236 281 306
Sound level *1 dB(A) 52 56 60 65 62 66

• A wide range of optional accessories are available such as high-efficiency filters. Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing)
Piping
connections
Gas mm 15.9 (Brazing) 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing)
Drain mm Rp1 (PS 1B internal thread)
Air filter Type Long-life filter (anti-mould resin net)
• Outdoor air intake mode is useable as an outdoor-air processing air conditioner.

Indoor Units
Motor output kW 0.75 1.5 3.7 5.5
*When using the unit as an outdoor-air processing unit, there are some restrictions. Strictly follow the restrictions specified in the Engineering Data Book. m3/min 43 69 86 134 165 172
Fan Airflow rate
cfm 1,518 2,436 3,036 4,730 5,825 6,072

All-fresh (using outdoor air only) system Return + Outdoor air mixed system External static pressure *2 Pa 152 217 281 420 142 390
Drive system Belt drive system
Circulated air

Outside Outside
Air Air Notes: Specifications are based on the following conditions;
conditioning conditioning • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
*1: Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
Outdoor air Outdoor air It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
introduction *2: The value is the external static pressure with standard pulley.
introduction

* Air introduced from the outside and circulated air


must be mixed in the air conditioner primary side
before introduction into the air conditioner.

157 158
VRV Indoor Units
Clean Room Air Conditioner
FXB(P)Q-P
Antibacterial
Suitable for hospitals and other clean spaces Suppresses the propagation of bacteria in the duct with a proprietary antibacterial coating
The filter implements an antibacterial treatment with a new coating combining a silver-based inorganic
antibacterial material (an organic antibacterial material that is effective against germs) that prevents
Easily provides the high Select the air flow system and mould.
This enhances the antibacterial properties of the duct.
cleanliness environment installation method to match the An antibacterial treatment using a silver-based organic substance reduces mould.
required by various industries layout and purpose of the room Antibacterial fiber used in the intake filter Fan Intake filter

Daikin’s clean room air conditioners are specially Two types of clean room air conditioners are With a long-life filter employing anti-mould antibacterial fiber
designed to achieve an environment cleanliness available – an integrated unit model and a near the intake, cleaning performance is further enhanced.
class 10,000. These air conditioners easily realize a separate outlet unit model. * Please be aware that antibacterial products suppress the propagation of bacteria but do not have a
sterilizing effect. Also, mould may grow in places where dust or soot accumulates.
cleanliness-class environment and help create a It is also possible to configure the air flow system * A material for which the registered safety was verified by Japanese chemicals and dangerous
proper environment of hospitals, food and to ceiling intake or floor-level intake according to substances regulation law (Act on the Evaluation of Chemical Substances and Regulation of Their Outlet panel HEPA filter Sheet steel Intake panel
Manufacture, etc) is used for the antibacterial material. (punching metal) drain pan (punching metal)
beverage factories, electronics factories, and other the panel selected. * Periodic maintenance is required (such as cleaning the air filter and washing the inside to the unit). (antibacterial treated)
spaces that require clean air. This flexible design enables the air conditioner to
Specifications
easily adopt to any room layout or use.
Type Integrated outlet unit model Separate outlet unit model
Instances of installation by type (for a hospital) Indoor unit FXBQ40PVE FXBQ50PVE FXBQ63PVE FXBPQ63PVE
MODEL
Outlet unit Integrated with the indoor unit BAF82A63
Ceiling intake type Floor-level intake type
Type Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
(high speed contracted flow/high ceiling model) (gentle wind distribution/high cleanness class model)
Btu/h 15,400 19,100 24,200
Easy to increase the cleanness and air-conditioning effect. Cooling capacity
Features Construction work is simple and a ceiling installation is possible. kW 4.5 5.6 7.1
A low flow speed prevents drying of the affected part
Dust filtering and air-conditioning can be started immediately.
and the experience of drafts. Power consumption kW 0.31 0.45
Cleanness class*1 100,000 to 10,000 10,000 Intake filter efficiency *1 70% by gravimetric method
Outlet HEPA filter efficiency *2 99.97% by DOP method *5
Wind speed 1.0 m/s or higher Approximately 0.5 m/s
Indoor unit weight kg 140 *3 185 *3 120 *6
• Concentrated air conditioning centered directly under the unit • Total air conditioning with an emphasis on cleanliness Casing Galvanised steel plate
• Easy installation m3/min 19.5/17.5 26/22.5
Airflow rate (H/L)
Integrated cfm 688/618 918/794
Intake
outlet unit (sourced locally) Sound level (H/L) *4 dB(A) 44/42
model Dimensions (H×W×D) mm 492×1,788×1,000 492×1,788×1,300 492×1,078×1,300
Outlet unit weight kg – 65 *3
Applications: Surgery prep rooms, recovery rooms, nurse stations, etc. Applications: Operating theatres, delivery rooms, etc. Liquid (Flare) 6.4 9.5
Blow Piping
method Gas (Flare) mm 12.7 15.9

Indoor Units
• Somewhat concentrated air conditioning centered • Total air conditioning with an emphasis on cleanliness connections
directly under the outlet • Maintenance possible from a different room Drain PT1B
• Can provide air conditioning Filter(Option) HEPA filter BAFH82A50 BAFH82A63
Separate in rooms with irregular shapes Ceiling intake type Model BYB82A50C BYB82A63C BYB82A63CP
Outlet Air Panel
outlet unit unit conditioner Intake (Option) Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP
model (sourced locally)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Applications: CCU*2, sterile rooms, etc. Applications: Premature nurseries, newborn nurseries, ICU*3, etc.
*1: An intake air filter is only attached to the ceiling intake type.
*2: HEPA filter sold separately. The dust collection efficiency of HEPA filter is 99.97%. However, air may slightly leak around the filter when installing.
* 1. Cleanliness class. A scale expressing the cleanliness of air established by NASA (National Aeronautics and Space Administration). Class 10,000 represents a state *3: Weight including HEPA filter and panel.
of less than 10,000 minute particles of diameter under 0.5 μm per cubic foot. For comparison, the cleanliness of a typical office is around class 1,000,000. *4: Anechoic chamber conversion value under JIS B 8616 test conditions. Value usually increases slightly in practice due to surrounding conditions.
* 2. CCU (Cardiac Care Unit). A ward dedicated to the admission of patients with myocardial infarctions and other heart diseases. *5: The clean room air conditioner does not support DOP testing (leak test) based on GMP standards
* 3. ICU (Intensive Care Unit). A ward for the careful treatment and nursing of patients with serious illnesses, injuries, or recovering from operations. (Standards for Manufacturing Control and Quality Control for Medical Devices ) due to slight leakage at time of product installation.
*6: Weight including panel.
*In the case of an installation in an operating theatre etc. where an air conditioner malfunction may have serious consequences, please build
in redundancy with two or more outdoor units.

Prevents uncomfortable drafts with a low flow speed of


approximately 0.5 m/s
The floor-level intake system has a low flow speed of approximately 0.5 m/s.
Because the ceiling intake type provides concentrated air conditioning that blows directly under the outlet. Use the floor-level intake type in
Accordingly, please be aware of the following. the following kind of locations.

Filtration Warning • Sufficient heating may not be achieved near the floor or at locations far from the outlet.
• In the case of utilization in a hospital, some patients may be susceptible to cool drafts, so please ensure that they do not come directly under the outlet.
• Install multiple units using two or more outdoor unit systems for installations to rooms such as operating rooms where the failure of the air
• Locations in which heating of
the lower part or the entire
room is important.

Class 10,000 clean room condition achieved with a HEPA filter (sold separately)
conditioner may have serious consequences. • Locations necessitating a
• In order to maintain static pressure in a room, the indoor fan continues to operate even when an abnormality occurs due to the thermostat shutting particularly high cleanliness
off, defrost operation, protection device operation, or similar issue. factor and in which there are
• When incorporating outdoor air from the fresh air intake, install a damper or similar device to the duct routing and have it interlocked with the many people.
The low pressure-loss HEPA filter (sold separately) demonstrates superior dust filtering performance and indoor fan so that the outdoor air is shut out when the fan stops.
The air that incorporates the suction filter may flow backward and allow dust trapped in the filter to return to the room.
easily accomplishes an air cleanliness of class 10,000. • When using gas to disinfect hospital operating rooms where this unit is installed, stop operation and cover the air inlet and outlet with plastic sheets
to prevent the gas from reaching and damaging the air conditioner.
* It may not be possible to maintain cleanliness in rooms with low air tightness.

159 160
Residential Indoor Units
Slim Ceiling Concealed Duct Type Wall Mounted Type
FDKS-EA/C(A) FTKS-D/B/F

Slim and smooth design suits your shallow ceiling Stylish flat panel harmonises with your interior décor

Standard accessory

Installation flexibility
Note: Remote controllers
other than the standard
accessory wireless remote
controller cannot be used.
Great for
Only 200 mm in height, this model can be installed in hotel use! FTKS25D / FTKS35D
FDKS-EA
rooms with as little as 240 mm in height for the ceiling
space between the drop-ceiling and ceiling slab.
200 mm

FTKS50B
240 mm
Only 700 mm
Standard
accessory*

Signals from the wireless remote controller are


FTKS50F / FTKS60F / FTKS71F
transmitted to the signal receiver.

*Remote controllers other than the standard accessory wireless remote controller cannot be used.

Comfort Efficiency & comfort


• Low operation sound level: down to 29 dB(A) • Intelligent Eye with its infrared sensor automatically
• Home Leave Operation prevents large increase or decrease in the controls air conditioner operation according to human
indoor temperature by continuing operation* while someone is sleeping movement in a room. When there is no movement, it
or left the house. This means that an air-conditioned welcome awaits when someone wakes up or adjusts the temperature by 2˚C for energy savings. When you are in the room When you go out
returns. It also means that the indoor temperature can quickly return to the preferred comfort setting. • Low sound level: down to 22 dB(A)
*Home Leave Operation can be selected for any temperature from 18 to 32˚C for cooling operation.
*Home Leave Operation function must be set using the remote controller when going to sleep or leaving the house, and after waking up or returning home.
• 3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate
air to every part of a room for uniform cooling of even large spaces.
Suspension bolt*
* This function is available for FTKS50/60/71F.
Air discharge duct* Suction duct*

Indoor Units
Air filter Notes: 1. To prevent an increase of the operation noise, avoid A uniform temperature
Air discharge grille*

Cleanliness
installing the air suction grille directly below the suction is achieved throughout
chamber. the entire room.
2. Grilles, piping connections, ducts, and installation parts
AIR 240 mm should be obtained locally. Slim Ceiling Mounted Duct type
models do not have drain-up pumps.
3. The signal receiver unit must be located near the air suction Titanium Apatite Deodorising Filter
inlet, because the unit includes a sensor that detects room
Signal receiver wire Chamber Air suction grille* temperature. While the filter’s micron-level fibres trap dust, titanium apatite effectively adsorbs odours and allergens,
Length = 1,900 mm
Signal receiver AIR as well as deodorises odours.
* Locally obtained parts
*This filter is not a medical device. Benefits such as the adsorption of odours and allergens and deodorisation of odours are only effective for substances which are directly
attached to the Titanium Apatite Deodorising Filter.

Specifications
MODEL FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB Specifications
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz MODEL FTKS25DVM FTKS35DVM FTKS50BVMA FTKS50FVM FTKS60FVM FTKS71FVM
Airflow rates (H) m3/min(cfm) 8.7 (307) 9.5 (335) 10.0 (353) 12.0 (424) 16.0 (565) Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Sound levels (H/L/SL)* dB(A) 35/31/29 37/33/31 38/34/32 Front panel colour White
Fan speed 5 steps, quiet and automatic m3/min
Airflow rates (H) 8.7 (307) 8.9 (314) 11.4 (402) 14.7 (519) 16.2 (572) 17.4 (614)
Temperature control Microcomputer control (cfm)
Dimensions (H × W × D) mm 200X700X620 200X900X620 200X1,100X620 Sound levels (H/L/SL) dB(A) 37/25/22 39/26/23 44/35/32 43/34/31 45/36/33 46/37/34
Machine weight kg 21 25 27 30 Fan speed 5 steps, quiet and automatic
Liquid (Flare) 6.4 Temperature control Microcomputer control
Piping 9.5
Gas (Flare) mm 12.7 Dimensions (H × W × D) mm 283×800×195 290×795×238 290×1,050×238
connections
Drain VP20 (External Dia. 26/Internal Dia. 20) Machine weight kg 9 12
Heat insulation Both liquid and gas pipes Liquid (Flare) 6.4
Piping
External static pressure Pa 30 40 Gas (Flare) mm 9.5 12.7 15.9
connections
Note: *The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa for FDKS-C(A). Drain 18.0
Sound level values for bottom-suction operation can be obtained by adding 6 dB(A) for FDKS-EA and 5 dB(A) for FDKS-C(A). Heat insulation Both liquid and gas pipes

161 162
Air Handling Unit
BP Units Air Handling Unit
BP units for connection to residential indoor units
Integrate your air handling unit in a total solution for large size
spaces such as factories and large stores.

The BP units can be • Easy design and installation


installed inside the ceiling. The system is easy to design and install since no addi-
tional water systems such as boilers, tanks and gas
connections etc are required.

• Inverter controlled units

• Control of air temperature via standard Daikin wired


remote control for standard series AHUR
Capacity range : 6 – 120 HP

Connectable to residential indoor units


BP units allow VRV systems to be connected to Daikin’s stylish and quiet residential indoor units.

BP unit
Quiet operating sound
System overview
Expansion valves tend to create refrigerant
Min. sound
passing noise. However, this noise can be reduced level 22 dB(A)
by installing the valves in BP units. The units can
be fitted inside the ceiling or roof-space far from
an indoor unit.
Some Daikin residential indoor units also provide

Indoor Units / Air Handling Unit


minimum sound levels of just 22 dB(A).
Air handling unit

Specifications

MODEL BPMKS967A3 BPMKS967A2 Liquid pipe


Gas pipe
Daikin communication wire (F1, F2 communication)
Other communication wire

Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz


Number of ports 3 (connectable to 1-3 indoor units) 2 (connectable to 1-2 indoor units)
Power consumption W 10 Daikin air handling units can be connected to VRV systems.
Running current A 0.05 This combination can be built to order as a system. Outdoor air series is also possible. Please contact your
Dimensions (HXWXD) mm 180X294 (+356*)X350 local sales office for details.
Machine weight kg 8 7.5
3 for power supply (including earth wiring), 2 for power supply (including earth wiring),
Number of wiring connections 2 for interunit wiring (outdoor unit-BP, BP-BP), 2 for interunit wiring (outdoor unit-BP, BP-BP),
4 for interunit wiring (BP-indoor unit) 3 for interunit wiring (BP-indoor unit)

Liquid
Main
kW
9.5X1
Piping connections Branch 6.4X3 6.4X2
(Brazing) Main 19.1X1
Gas kW
Branch 15.9X3 15.9X2
Heat insulation Both liquid and gas pipes
Connectable indoor units 2.5 kW class to 7.1 kW class
Min. rated capacity of connectable indoor kW 2.5
Max. rated capacity of connectable indoor kW 20.8 14.2
Note: *Total auxiliary piping length.

163 164
Air Treatment Equipment
Air Treatment Equipment
Daikin's air treatment systems creating a higher IAQ Outdoor-air processing unit
Components of indoor air quality FXMQ-MF Series
Combine fresh air treatment and air conditioning,
supplied from a single system.
Ventilation Filtration *1
Air Conditioning Lineup
Model Name FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Air Processing *2
Capacity index 125 200 250
Airflow rate 1,080 m3/h 1,680 m3/h 2,100 m3/h

Fresh air treatment and air conditioning can be


A recent trend rapidly gaining popularity is for air treatment to be required as well as air conditioning. achieved with a single system. VRV indoor units
Daikin has a lineup of 3 products that provide adequate IAQ, according to the client’s needs. for air conditioning and an outdoor-air
processing unit can be connected to the same
refrigerant line. This results in enhanced design
flexibility.

Outdoor-Air Heat Reclaim Ventilator


Processing Unit VKM-GC Type VAM-GJ Type

Combination with VRV indoor units


Ventilation Filtration *1 Ventilation Filtration *1 Ventilation Filtration *1

Air Processing *2 Air Processing *2 Air Processing *2

Air conditioning and outdoor air processing can be accomplished using a single system.

VRV Outdoor Units

Refrigerant Piping Connectable Connectable Not connectable


Connections Wiring Connectable Connectable Connectable
with VRV systems

Air Treatment Equipment


Outdoor-Air Processing Unit
After-cool &
Available Available Not available
After-heat Control
Indoor Unit Indoor Unit
Ventilation System Air supply only Air supply & air exhaust Air supply & air exhaust
Heat Exchange Element — Energy savings obtained Energy savings obtained

High Efficiency Filter (Option) Available Available Available

PM2.5 Filter (Option) Available Not available Available


Air Outdoor
Airflow Rate 1,080 - 2,100 m3/h 500 - 950 m3/h 150 - 2,000 m3/h
Conditioning Air Supply
*1. PM2.5 filter (Option) is necessary.
*2. Refers to bringing outdoor air to near indoor temperature and delivering to a room.

Connection Conditions

• Outdoor-air processing units can be used without indoor units. The total connection capacity index must be 50% to 100% of the
capacity index of the outdoor units.
• When outdoor-air processing units and standard indoor units are combined, the total connection capacity index of the
outdoor-air processing units must not exceed 30% of the capacity index of the outdoor units.
Because connection is possible depending on conditions ever when the capacity index of outdoor-air processing units exceeds
30% of the capacity index of the outdoor units, contact your local distributor.

165 166
Air Treatment Equipment
Air Treatment Equipment
Outdoor-air processing / Discharge air temperature control Standard specifications
The unit supplies outdoor fresh air controlling discharge air temperature from the unit. Type Ceiling Mounted Duct Type
Thereby reducing the indoor air conditioning load. MODEL FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Power supply 1-phase 220-240 V, 50 Hz
Btu/h 47,800 76,400 95,500
Cooling capacity *1
Outdoor-Air Processing Unit kW 14.0 22.4 28.0
Btu/h 30,400 47,400 59,400
Heating capacity *1
Outdoor Air Supply Air (Discharge Air) kW 8.9 13.9 17.4
Power consumption kW 0.359 0.548 0.638
Casing Galvanised steel plate
Dimensions (H × W × D) mm 470 × 744 × 1,100 470 × 1,380 × 1,100
Discharge Air Temperature Motor output kW 0.380
Fan
m3/min 18 28 35
Heat Exchanger Airflow rate
cfm 635 988 1,236
* The default setting of the discharge air temperature is 18℃ for cooling operation, and 25℃ for heating operation. Using field settings, the set temperature may be changed External static pressure 220 V/240 V Pa 185/225 225/275 205/255
within the range 13-25℃ for cooling operation, and 18-30℃ for heating operation.
* While in unit protection mode and depending on outdoor air conditions, discharge air temperature may not be at the set temperature.
Air filter *2
* The fan stops in defrosting, oil returning and hot start operations due to mechanical protection control. Liquid mm 9.5 (Flare)
Refrigerant
Gas mm 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing)
• Applicable to outdoor air temperature range from –5 - 43°C.
piping
Drain mm PS1B female thread
In cooling operation, 19 - 43°C is adoptable. Machine weight kg 86 123
Sound level *3 220 V/240 V dB(A) 42/43 47/48

32
Notes: 1. The operation range shown in the graph is under the following conditions. Connectable outdoor units *4 6 HP and above 8 HP and above 10 HP and above

ty e

ty
idi iv

idi
m lat

m
Indoor and Outdoor Unit

Hu Re
Cooling 19 to 43°C

Hu
Operation range

0%
Equivalent piping length: 7.5 m,

ive
10

lat
Level difference: 0 m. (Fan mode operation between 15 and 19°C) Heating -5 to 15°C

Re
%
2. The system will not operate in fan mode when the outdoor

90
air temperature is 5°C or below.
Cooling 13 to 25°C
ur
e Range of the discharge temperature *5
at
m
pe
r
Supported Cooling
Heating 18 to 30°C
Te B)
ir Operation Range
A
or (°C
W Notes: *1. Specifications are based on the following conditions:
o
td • Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH), and discharge temp. of 18°CDB.
Ou
• Heating: Outdoor temp. 0°CDB, -2.9°CWB (50% RH), and discharge temp. of 25°CDB.
• Equivalent reference piping length: 7.5 m (0 m horizontal)
Fan tive *2. An intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter. Please mount it in the duct system of the suction side. Select
idity Rela ity
Operation Hum 20% umid a dust collection efficiency (gravity method) of 50% or more.
ive
Relat H
*3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. These values are normally somewhat higher during actual
30%
Heating
Supported operation as a result of ambient conditions.
Range
Operation *4. It is possible to connect to the outdoor unit if the total capacity of the indoor units is 50% to 100% of the capacity index of the outdoor unit.
*5. Local setting mode is not displayed on the remote controller.
–5 15 19 (33.5) 43 • This equipment cannot be incorporated into the remote group control of the VRV system.

Outdoor air temperature (°CDB)


Notes: * Linked control of this unit and the Heat Reclaim Ventilator is not supported.

Air Treatment Equipment


* This unit is intended for the treatment of outdoor air only. Not to be used for maintaining indoor air temperature. Be sure that the discharge airflow will not blow on
people directly. When outdoor-air processing is in excess, the unit switches to thermo-off mode, and outdoor air flows into the room directly.
* For outdoor ducts, be sure to provide heat insulation to prevent condensation.
* Group control of the product and standard indoor units is not supported. A separate remote controller should be connected to individual unit.
* If the unit is utilised to operate 24 hours a day, maintenance (part replacement, etc.) must be performed periodically.
Options
* Temperature setting and Power Proportional Distribution (PPD) are not possible even if the intelligent Touch Controller or the intelligent Touch Manager is installed.
* The remote controller wired to the outdoor-air processing unit must not be set as the master remote controller. Otherwise, when set to “Auto,” the operation mode
will switch according to the outdoor air conditions, regardless of the indoor temperature.
MODEL FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Operation remote controller BRC1H61W(K) / BRC1E63 / BRC2E61

Operation/control
Filtration equipment Central remote controller
Unified ON/OFF controller
DCS302CA61
DCS301BA61
Activated carbon filter Wiring adaptor for electrical appendices (1) KRP2A61
PM2.5 Filter (Option) Wiring adaptor for electrical appendices (2) KRP4AA51
Long-life replacement filter KAFJ371L140 KAF371M280
* Refer to page 178-180 for details.
Colourimetric method 65% KAFJ372L140 KAF372M280
Filters

High-efficiency filter
Colourimetric method 90% KAFJ373L140 KAF373M280
The filter removes PM2.5 particles suspended in the air, and also
Filter chamber *1 KDJ3705L140 KDJ3705L280
sulfur oxides and nitrogen oxides, providing clean air to the room.
PM2.5 filtration unit *2 BAF429A20A
• PM2.5 filter: Removes 99% or more of 2.5μm particulate matter. PM2.5 with activated carbon filtration unit *2 BAF429A20AC
• Activated carbon filter: Removes sulfur oxides and nitrogen oxides. Drain pump kit KDU30L250VE
PM2.5 filter Adaptor for wiring KRP1B61
Notes: *1. Filter chamber has a suction-type flange. (Main unit does not.)
High-efficiency filter & Long-life filter (Option) • Dimensions and weight of the equipment may vary depending on the options used.
• Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
• Some options may not be used in combination.
• High performance filters with dust collection efficiencies (JIS calorimetry) of 90% and 65% are • Operating sound may increase somewhat depending on the options used.
*2. Refer to pages 178 - 180 for details.
available as options. Long-life filter is also available.
167 168
Air Treatment Equipment
Air Treatment Equipment
Heat Reclaim Ventilator with DX-coil
Equipped with DC fan motor
VKM-GC Series
• Energy saving: Power consumption reduced by up to 51% (Class 50)
Air quality improvement by introducing fresh outdoor air • Flexible installation due to high external static pressure: Increase of up to +50 Pa (Class 80)
in the room

Power Consumption (kW) External Static Pressure (Pa)


Lineup 800 250
670 210 220
Model VKM50GCVE VKM80GCVE VKM100GCVE
620
Capacity Index 31.25 50 62.5 600 560 180 170 170
440 150
Airflow rate 500 m /h
3
750 m /h3
950 m /h
3
150
390
400
270
200
50

IAQ improvement by fresh air 0


Class 50 Class 80 Class 100
0
Class 50 Class 80 Class 100

Maintains comfortable indoor air quality (IAQ)


Current model New VKM-GC Current model New VKM-GC
by adding fresh outdoor air having nearly the
same temperature and humidity conditions as
the indoor air.
Supports both 50/60 Hz power supply
This energy-saving heat reclaim ventilator
further reduces air conditioning load.
Current model 1-phase 220-240 V, 50 Hz only

New model 1-phase 220-240 V, 50 Hz


1-phase, 220 V, 60 Hz

Heat reclaim ventilator + Heat exchanger → Comfortable air supply CO2 sensor control (Option) * Refer to page 177 for details.

Equipped with a heat reclaim ventilator and a heat exchanger,

Air Treatment Equipment


the new VKM series minimizes room temperature fluctuations. The supply air is cooled When CO2 sensor is installed, it detects the concentration of CO2 in the indoor air and the ventilation
from 29°C to 17.2°C with DX-coil. rate is controlled appropriately, reducing the air conditioning load due to ventilation.

Structure of VKM series


Outdoor Indoor PM2.5 filter (Option) * Refer to page 178-180 for details.

After heat exchange


29°C
Total heat exchange element Cooling by DX-Coil Removes PM2.5 particulate matter present in the outdoor air, as well as sulfur oxides and nitrogen
oxides, providing clean fresh air to the indoor ambient.
Exhaust Air Supply Air
To the Outdoor 32.9°C
To the Indoor 17.2°C • PM2.5 filter: Removes 99% or more of 2.5 μm particulate matter.
Return Air
• Activated Carbon filter: Removes sulfur oxides and nitrogen oxides
Outdoor Air
From the Indoor 27°C
From the Outdoor 35°C

Other characteristics
• Nighttime free cooling operation * Refer to page 174 for details.
• Stainless drain pan
• High-efficiency filter (Option)
169 170
Air Treatment Equipment
Air Treatment Equipment
Specifications
A compact unit packed with Daikin’s cutting-edge technologies.
MODEL VKM50GCVE VKM80GCVE VKM100GCVE
Heat exchanger element
Refrigerant R-410A
Outdoor Indoor
Power Supply 1 phase, 220-240/220 V, 50/60 Hz
EA Airflow Rate & External Static Pressure Airflow m3/h 500/500/440 750/750/640 950/950/820
SA
(Ultra-high / High / Low) (Note 4) Static pressure Pa 210/170/140 220/180/125 170/120/90
SA
Temperature Integrally-formed Power Consumption Heat exchange mode W 270/230/170 390/335/220 440/370/260
and humidity liner (Ultra-high / High / Low) Bypass mode W 305/260/200 390/335/220 440/370/260
RA
RA Fan Type Sirocco Fan
OA
Motor Output kW 0.21×2
Sound Level (Note 3) Heat exchange mode dB 43/40.5/39 41.5/39/37 41/39/36.5
Heat Exchanger Elements (Ultra-high / High / Low) Bypass mode dB 43/41/39 41.5/39/37 41/39/36.5
Temp. Exchange Efficiency (Ultra-high / High / Low) % 76/76/77.5 78/78/79 74/74/76.5
Exhaust Fan Cooling % 64/64/67 66/66/68 62/62/66
Damper Enthalpy Exchange Efficiency
(Ultra-high / High / Low) Heating % 67/67/69 71/71/73 65/65/69
EA
(Exhaust air to outdoors) Damper Motor Heat Exchanging System Air to Air Cross Flow Total Heat (Sensible + Latent Heat) Exchange
Heat Exchanger Element Specially Processed Non flammable Paper
OA Air Filter Multidirectional Fibrous Fleeces
(Fresh air from outdoors)
DX-coil Capacity (Cooling / Heating) (Note 1) (Note 2) kW 2.8 / 3.2 4.5 / 5.0 5.6 / 6.3
Dimensions (Height×Width×Depth) mm 387 × 1,764 × 832 387 × 1,764 × 1,214
RA
(Return air from room) Liquid mm 6.4 (Flare)
Piping Connection Gas mm 12.7 (Flare)
Air Supply Fan SA Drain PT3/4 External Thread
(Supply air to room) Machine Weight kg 92 113 115
Electronics Box (Control box) Around Unit 0°C–40°CDB, 80%RH or less
Unit Ambient Condition OA (Note 5) -15°C–40°CDB, 80%RH or less
RA (Note 5) 0°C–40°CDB, 80%RH or less
DX-coil
Notes: 1. Indoor temperature: 27°CDB, 19°CWB, Outdoor temperature: 35°CDB
2. Indoor temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB
3. The operating sound measured at the point 1.5 m below the centre of the unit is converted to that measured in an anechoic chamber built in accordance with the JIS
C 1502 conditions. The actual operating sound varies depending on the surrounding conditions (near running unit’s sound, reflected sound and so on) and is normally
higher than this value.
For operation in a quiet room, it is required to take measures to lower the sound.
For details, refer to the Engineering Data.
4. Airflow rate can be changed over to Low mode or High mode.
5. OA: fresh air from outdoor. RA: return air from room.
6. Temperature exchange efficiency is the mean value for Cooling and Heating. Efficiency is measured under the following condition: Ratio of rated external static
pressure outdoor to indoor is kept constant at 7 to 1.

Air Treatment Equipment


Air conditioning and outdoor air processing can be accomplished using a single system.
Options
VRV Outdoor Units

Item Type VKM50GCVE VKM80GCVE VKM100GCVE

Heat Reclaim Ventilator with DX Coil Remote controller * 1


BRC1H61W(K) / BRC1E63
Controlling Wiring adaptor for electrical
Outdoor Air device appendices
KRP2A61
PCB Adaptor
Exhaust Air Indoor Unit Indoor Unit For heater control kit BRP4A50
KDDM24B100
Silencer
Nominal pipe diameter mm 250
Additional White K-DGL200C K-DGL250C
Return function
Air suction / Discharge grille
Nominal pipe diameter mm 200 250
Air Air
Air-Conditioning Air Supply High efficiency filter KAF242J80M KAF242J100M
Air filter for replacement KAF241G80M KAF241G100M
1m K-FDS201E K-FDS251E
Flexible duct
2m K-FDS202D K-FDS252E
CO2 Sensor BRYC24B50M BRYC24B100M
PM2.5 filtration unit *2 BAF249A500 BAF429A20A
• When the VKM series units are connected, the total connection capacity index must be 50% to 130% of the capacity index of the PM2.5 with activated carbon filtration unit *2 BAF249A500C BAF429A20AC
outdoor units. *1. Necessary when operating a Heat Reclaim Ventilator (VKM) independently. When operating interlocked with other air conditioners, use the remote controllers of the air
conditioners.
*2. Refer to pages 178-180 for details.
171 • Please inquire concerning optional accessories not listed above. 172
Air Treatment Equipment
Air Treatment Equipment
Heat Reclaim Ventilator
VAM-GJ Series Pre-cool, Pre-heat control
Intentional delay of the start-up time
Daikin VAM series ensures fresh air intake and When the air conditioner is started up, the ventilation start-up is delayed to reduce load caused by the
energy savings outside air. This reduces power consumption of air conditioners.
Operation OFF 8:00 Operation ON 9:00
EA Operation EA Operation
OA ON OA ON

BRC301B61 (Option)
Used in case of independent operation. SA RA * The delay time can be changed using
Lineup SA RA
field settings.

VAM150GJVE VAM250GJVE VAM350GJVE


VAM500GJVE VAM650GJVE VAM800GJVE
VAM1000GJVE VAM1500GJVE VAM2000GJVE

Airflow rate: 150-2,000 m3/h Auto-ventilation mode changeover switching


Automatically determine the appropriate ventilation for each situation
Indoor temperature and the outdoor temperature are detected, and the system automatically switches
to the ventilation mode which has higher energy-saving effect.
Heat recovery ventilation with simultaneous supply and exhaust Compare temperature
and cools with outdoor air
Energy-saving
Cooling with outdoor air
Energy-saving
EA EA
OA operation OA operation

Outdoor Indoor EA
(Exhaust air to outdoors) SA RA SA RA
EA
SA HIGH Reduced
RA Indoor room Indoor room
(Return air from room) LOW temperature LOW temperature
Outdoor Outdoor
air temperature air temperature

RA OA
OA (Fresh air from outdoors)

Nighttime free cooling operation


SA Efficient use of outdoor air at night.
SA (Supply air to room)
Temperature
Rise in indoor temperature is avoided by automatically cooling the outdoor air at night, thus reducing
Integrally-formed
and humidity liner air conditioning load at the start of cooling operation on the next morning.
RA
Cooling with outdoor air 22:00 Cooling with outdoor air 3:00 *The system is automatically controlled by

Air Treatment Equipment


Operation Operation the set temperature of the VRV indoor
EA EA
OA OFF OA OFF unit.

HIGH Reduced
Indoor room SA RA Indoor room SA RA
temperature temperature
Further energy-saving ventilation by interlocking with VRV indoor unit
LOW LOW
Outdoor Outdoor
air temperature air temperature
• Pre-cool, Pre-heat control
• Auto-ventilation mode changeover switching VRV indoor unit
• Nighttime free cooling operation
• ON/OFF signal
• Cooling/Heating mode signal
CO2 sensor control (Option) * Refer to page 177 for details.

• Set temperature signal


• Ventilation signal When CO2 sensor is installed, it detects the concentration of CO2 in the indoor air and the Ventilation
rate is controlled appropriately, reducing the air conditioning load due to ventilation.

• Operating mode signal


• Filter cleaning signal
Interlocking PM2.5 filter (Option) * Refer to page 178-180 for details.
• Failure detection signal
LCD remote controller
for indoor unit Removes PM2.5 particulate matter present in the outdoor air, as well as sulfur oxides and nitrogen
oxides, providing clean fresh air to the indoor ambient.
• PM2.5 filter: Removes 99% or more of 2.5 μm particulate matter.
Heat Reclaim Ventilator • Activated Carbon filter: Removes sulfur oxides and nitrogen oxides
173 174
Air Treatment Equipment
Air Treatment Equipment
Heat Reclaim Ventilator
Specifications Options
MODEL VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE
Option List
Type VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE
Power Supply 1-phase, 220-240 V/ 220 V, 50/60 Hz Item
— KDDM24B50 KDDM24B100 KDDM24B100×2

Additional
Silencer

function
Temp. Exchange
Ultra-High 79/79 75/75 79/79 74/74 75/75 72/72 78/78 72/72 77/77 Nominal pipe mm — 200 250
Efficiency High % 79/79 75/75 79/79 74/74 75/75 72/72 78/78 72/72 77/77 High efficiency filter KAF242J25M KAF242J50M KAF242J65M KAF242J80M KAF242J100M KAF242J80M×2 KAF242J100M×2
(50/60 Hz) Air filter for replacement KAF241J25M KAF241J50M KAF241J65M KAF241J80M KAF241J100M KAF241J80M×2 KAF241J100M×2
Low 84/85 79/79 82/82 80/80.5 77/77.5 74/74.5 80.5/81 75.5/76 79/81 Flexible duct (1 m) K-FDS101D K-FDS151E K-FDS201E K-FDS251E
Ultra-High 66/66 63/63 66/66 55/55 61/61 61/61 64/64 61/61 62/62 Flexible duct (2 m) K-FDS102D K-FDS152D K-FDS202D K-FDS252E
For % — YDFA25A1
High 66/66 63/63 66/66 55/55 61/61 61/61 64/64 61/61 62/62 Silencer
Enthalpy Cooling Nominal pipe mm — 250
Exchange
Low 70/70.5 66/66 70/70 59/59.5 64/64.5 64/64.5 68.5/69 64/64.5 66/67 CO2 sensor BRYMA65 BRYMA100 BRYMA65 BRYMA100
Efficiency Ultra-High 72/72 71/71 70/70 67/67 67.5/67.5 65/65 70/70 65/65 72/72
PM2.5 filtration unit* BAF249A150 BAF249A300 BAF249A350 BAF249A500 — BAF429A20A
(50/60 Hz) PM2.5 with activated carbon
For %
BAF249A150C BAF249A300C BAF249A350C BAF249A500C — BAF429A20AC
High 72/72 71/71 70/70 67/67 67.5/67.5 65/65 70/70 65/65 72/72 filtration unit*
Heating
Navigation remote controller BRC1E63
Low 76/76.5 74/74 77/77 74/74.5 71.5/72 67.5/68 72.5/73 67/67.5 76/76
Heat Reclaim Ventilator remote
Ultra-High 125/134 137/141 200/226 248/270 342/398 599/680 635/760 1,145/1,300 1,289/1,542 controller BRC301B61
Heat
Exchange High W 111/117 120/125 182/211 225/217 300/332 517/597 567/648 991/1,144 1,151/1,315 Residential central
Power remote controller DCS303A51*1
Mode
Consumption Low 57/58 60/59 122/120 128/136 196/207 435/483 476/512 835/927 966/1,039 Centralised Central remote

Controlling device
(50/60 Hz) controlling controller DCS302CA61
Ultra-High 125/134 137/141 200/226 248/270 342/398 599/680 635/760 1,145/1,300 1,289/1,542
Bypass device Unified ON/OFF
High W 111/117 120/125 182/211 225/217 300/332 517/597 567/648 991/1,144 1,151/1,315 controller DCS301BA61
Mode
Low 57/58 60/59 122/120 128/136 196/207 435/483 476/512 835/927 966/1,039 Schedule timer DST301BA61
Wiring adaptor for electrical
Ultra-High 27-28.5/28.5 27-29/29 31.5-33/33 33-35.5/34 34-36/36 39-40.5/39.5 39.5-41.5/39.5 39.5-41.5/41.5 41.5-43.5/42 KRP2A61

PCB Adaptor
Heat appendices
Exchange High dB(A) 26-27.5/27.5 26-27.5/28 30-31.5/30 31.5-34/32 33-34.5/34 37-39.5/37.5 37.5-39.5/37.5 37.5-39.5/39.5 39-43/40 For humidifier KRP50-2
Mode Installation box for adaptor
Sound Level Low 20.5-21.5/21 21-22/21 23-25/23 25-28.5/24 27.5-29.5/28 35-37.5/34 35-37.5/34.5 35-37.5/36 36-39/39 PCB KRP50-2A90 (Mounted electric component assy of Heat Reclaim Ventilator)
(50/60 Hz) Ultra-High 28.5-29.5/29.5 28.5-30.5/30.5 33-34.5/34.5 34.5-36/35.5 35-37.5/37.5 40.5-42/41 40.5-42.5/40.5 41-43/42.5 43-45.5/44 For heater control kit BRP4A50
Bypass dB(A) 27.5-28.5/28.5 *1 For residential use only. When connect with a Heat Reclaim Ventilator (VAM),
High 27.5-29/29.5 31.5-33/31.5 33-34.5/33.5 33-35.5/35.5 38.5-40/39 38.5-40.5/38.5 39.5-41/41.5 40.5-45/42
Mode you can only switch the power ON/OFF. It cannot be used with other central control equipment.
Low 22.5-23.5/22 22.5-23/22.5 24.5-26.5/24.5 25.5-28.5/25.5 27.5-30.5/29.5 36-38.5/35.5 36-38.5/35.5 36.5-38/37.5 37.5-39.5/41 *Refer to pages 178 - 180 for details.
Casing Galvanised steel plate
Insulation Material Self-extinguishable polyurethane foam
Dimensions (H × W × D) mm 278 × 810 × 551 306 × 879 × 800 338×973×832 387×1,111×832 387×1,111×1,214 785×1,619×832 785×1,619×1,214
Machine Weight kg 24 32 45 55 67 129 157
Heat Exchange System Air to air cross flow total heat (Sensible heat+latent heat) exchange PCB adaptor for heater control kit (BRP4A50)
Heat Exchange Element Material Specially processed nonflammable paper
Air Filter Multidirectional fibrous fleeces When the installation of an electric heater is required in a cold region, this adaptor with an internal timer
Type Sirocco fan function eliminates the complicated timer connecting work that was necessary with conventional heaters.

Air Treatment Equipment


Ultra-High 150/150 250/250 350/350 500/500 650/650 800/800 1,000/1,000 1,500/1,500 2,000/2,000
Airflow Rate m3/h
High 150/150 250/250 350/350 500/500 650/650 800/800 1,000/1,000 1,500/1,500 2,000/2,000 Indoor Outdoor Notes when installing :
(50/60 Hz)
•Examine fully an installation place and specification for using the
Low 100/95 155/155 230/230 320/295 500/470 700/670 860/840 1,320/1,260 1,720/1,580
Fan EA
electric heater based on the standard and regulation of each
RA
External Static
Ultra-High 120/154 70/96 169/222 105/150 85/125 133/170 168/192 112/150 116/140 Heat Reclaim Ventilator
country.
•Supply the electric heater and safety production devices such as a
Pressure High Pa 106/131 54/65 141/145 66/52 53/67 92/85 110/86 73/72 58/32 Heater OA relay and a thermostat, etc of which qualities satisfy the standard
SA
(50/60 Hz) (Obtain locally)
Low 56/60 24/20 67/30 32/18 35/38 72/61 85/60 56/50 45/45 and regulation of each country at site.
Thermostat
(Obtain locally) •Use a non-inflammable connecting duct to the electric heater. Be
Motor Output kW 0.030 × 2 0.090 × 2 0.140 × 2 0.280 × 2 0.280 × 4 BRP4A50 (ON when the temperature sure to use 2 m or more between the electric heater and the Heat
is at or below -10°C) Reclaim Ventilator for safety.
Connection Duct Diameter mm 100 150 200 250 350 •For the Heat Reclaim Ventilator, use a different power supply
Thermostat (Obtain locally)
Unit ambient condition -15°C–50°CDB, 80%RH or less (OFF when the temperature is at or more Power supply (Obtain locally) from that of the electric heater and install a circuit breaker for
than 5°C) Relay box each.
Notes: 1. Airflow rate can be changed over to Low mode or High mode.
2. Temperature Exchange Efficiency is the mean value between cooling and heating.
3. Efficiency is measured under the following conditions:
Ratio of rated external static pressure has been maintained as follows; outdoor side to indoor side = 7 to 1.
4. In conformance with JIS standards (JIS B 8628), operating sound level is based on the value when one unit is operated, with the value converted for an anechoic
chamber. This is transmission sound from the main unit, and does not include sound from the discharge grille. Thus it is normal for the sound to be louder than the
indicated value when the unit is actually installed.

175 176
Air Treatment Equipment
Air Treatment Equipment
CO2 Sensor Optional Kit Connection for VAM / VKM Series PM2.5 filtration unit (Option) for VAM / VKM / FXMQ-MF series
The CO2 sensor controls airflow so that it best matches the changes of CO2 level in the room. Rapid urbanization has increased industrial and automobile emissions, resulting in higher PM2.5 levels.
This prevents energy losses from over-ventilation while maintaining indoor air quality with This has become the source of respiratory diseases and poses a serious threat to a long term health issue.
As the air quality has worsened, research has shown the harmful effects of PM2.5 on the health of the
optional CO2 sensor. general public.

Double-layered efficient filtration


PM2.5 filters are double-layered.
Example of CO2 sensor operation in an office room: 1. The front filter effectively removes large particles.
2. The PM2.5 filter layer contains a large amount of static electricity to capture particulate matter efficiently.
7- stage control with different airflow levels CO2 level
Airflow for ventilation
If airflow were
constant
Airflow down PM2.5
Reference
Highly Efficient

Airflow for ventilation


value
Airflow down Electrostatic
CO2 level

Dust Collection Filter


Airflow up

indicates energy savings!


Airflow up Energy wastage for ventilation is reduced.
Air conditioning load for ventilation is reduced.

9 10 11 12 13 14 15 16 17 18 19 20 21 Hours

Sales Sales
Morning Lunch Overtime
personnel leave personnel Front Filter
meetings time work
office return

Heat Reclaim Ventilator

Air Treatment Equipment


Air conditioner
Filtering PM2.5 efficiently for healthier and more comfortable environments

This filter removes 99% or more of 2.5 μm particulate matter.

PM2.5 electrostatic dust collection filter


PM2.5
Removal Rate

99%
Many people increase CO2 level: Fewer people decrease CO2 level:

Airflow up Airflow down

*Test results by the Heating, Ventilation and Air Conditioning Lab at Tongji University
Test environment: temperature 25-26°CDB, humidity 58-60%RH

177 178
Air Treatment Equipment
Air Treatment Equipment
Electrostatic dust collection filter: Daikin Electrostatic Specifications
more efficient and longer lasting effect Dust Collecting Filtration
PM2.5 filtration unit
The PM2.5 filter layer contains a large amount of static MODEL BAF249A150 BAF249A300 BAF249A350 BAF249A500 BAF429A20A
electricity to capture particulate matter efficiently,
Dimensions (H × W × D) mm 220×603×366 220×603×366 300×623×366 300×623×366 470×971×370
including those smaller than the grid mesh.
Connection Duct Diameter mm 100 150 150 200 580×348
The filter is difficult to be blocked by particles and has
Airflow Rate m3/h 150 250 350 500 2,100
good ventilation and long life span. Initial Pressure Drop Pa 34 30 31 42 less than 40
With the capturing effect of static electricity, Filter Lifetime *1 1 year
PM2.5 Filter
particles are adsorbed on the filter fabric. Filtration Efficiency *2 99% or higher
Filter Material No. *3 BAF244A300 BAF244A500 BAF424A20A
Notes: 1. Annual usage: 400 hrs/month x 12 months = 4,800 hrs
2. 99% or higher removal rate of ultra-fine particles with diameters of 2.5 μm or more.
3. Filters come with applicable filtration units with a one-year life. They can be purchased and replaced according to their model numbers.

The filter is not blocked and therefore


continuous Supply Air is guaranteed.

Long-lasting highly efficient dust


collection capacity
PM2.5 with activated carbon filtration unit
MODEL BAF249A150C BAF249A300C BAF249A350C BAF249A500C BAF429A20AC

Dimensions (H × W × D) mm 220×603×366 220×603×366 300×623×366 300×623×366 470×971×370


Connection Duct Diameter mm 100 150 150 200 580×348

PM2.5 with activated carbon filtration unit (Option) for VAM / VKM / FXMQ-MF series Airflow Rate m3/h 150 250 350 500 2,100
Total Initial Pressure Drop for PM2.5
Pa 37 35 36 51 less than 50
Extra-high performance filter against sulfur oxides and nitrogen oxides with Activated Carbon Filtration Unit

Initial Pressure Drop Pa 34 30 31 42 less than 40


Filter Lifetime *1 1 year
PM2.5 Filter
Activated Filtration Efficiency *2 99% or higher
Effective Use of Active Carbon Material to Enlarge carbon filter
Filter Material No. *3 BAF244A300 BAF244A500 BAF424A20A
the Adsorption Area Initial Pressure Drop Pa 3 5 5 9 less than 10
Activated
Filter Lifetime 1 year
Carbon Filter
As an expert in the research and development of filters, DAIKIN Filter Material No. 3 BAF244A300C BAF244A500C BAF424A20AC
has specifically selected active carbon material as the main

Air Treatment Equipment


Notes: 1. Annual usage: 400 hrs / month × 12 months = 4,800 hrs.
substance to constitute the filter against sulfur oxides and 2. 99% or higher removal rate of ultra-fine particles with diameters of 2.5 µm or more.
3. Filters come with applicable filtration units with a one-year life. They can be purchased and replaced according to their model numbers.
nitrogen oxides. The material’s usable pore surface is fully
exploited, thus extending the filter’s durability.

Notes: Surface area of active carbon: 700 m2/g


Given a newspaper page of 40.6 cm wide by 54.6 cm long,
each gram of active carbon has a surface area of 3,000 newspaper pages.

Intelligent Identification, Super-effective Adhesion Unidentified Gases

The special substance added in the pores of active carbon can


exclusively target sulfur oxide and nitrogen oxide gases and stick
to them without blocking other unidentified gases. This ensures
long durability of the filter.

Note: The figures are based on in-house tests under the following lab conditions:
temperature 22 to 25°CDB, humidity 35 to 40% RH, air flow rate 0.2 m/s.

Adhesives

179 180
Control Systems
Control Systems
Individual control systems for VRV systems
Stylish remote controller (Option) Navigation remote controller (Wired remote controller) (Option)

A complete redesigned A series of user friendly


controller focused to functions that can be
enhance user experience individually selected
BRC1E63 BRC1F61
BRC1H61W (White) BRC1H61K (Black) (Only for FXDSQ series)

Sleek and stylish design User-friendly interface Energy saving


• Combines refinement and simplicity • Just three buttons and a large-figure display Setpoint range set
• Echoes the distinct blue circle and simplicity of • Customisable display • Avoids excessive cooling by limiting the min. and max. set temperature.
design • Direct access to basic functions (ON/OFF, • Convenient for use at a place where any number of people may operate it.
• Two attractive colours to match any interior Operation mode, Temperature setting, Airflow
• Compact, measures only 85 x 85 mm rate, Airflow direction) Setpoint auto reset
ON/OFF
• Even if the set temperature is changed, the new set temperature returns to the
previous preset value after a preset duration of time.
SIMPLE VIEW Customisable example
• Period selectable from 30, 60, 90, or 120 min.

Off timer
• Period can be preset from 30 to 180 minutes in 10-minute increments.

Convenience
Easy and direct access
to main functions
Setback (default: OFF)
• Maintains the room temperature in a specific range during unoccupied period by temporarily starting
air conditioner that was turned OFF.

Fan speed Louvre setting Weekly schedule


Mode selection
(cooling, fan only, etc.) • 5 actions per day can be scheduled for each day of the week.
• The holiday function will disable schedule timer for the days that have been set
as holiday.
Easy setting via Bluetooth App with smartphone (for Installer / Facility manager) • 3 independent schedules can be set. (e.g. summer, winter, mid-season)

Keep hotel room comfortable

Control Systems
Auto display off
• Period can be preset from 10, 30, 60 minutes, and OFF. Initial setting is 30 minutes.
• Improved setback function by setting the lower
temperature limit in cooling mode.
Comfort
Individual airflow direction
• Airflow direction can be individually adjusted for each air discharge outlet.

Shorter installation time <App screen image>


5-step airflow control
• Airflow rate can be selected from 5-step control.
• Easy to create multiple remote control and field settings via App
• Prepare a setting in advance at the office and immediately send it to the on-site remote controller Auto airflow rate
• Save and reuse settings • Airflow rate is automatically controlled.
181 182
Control Systems
Control Systems
Individual control systems for VRV systems
Simplified remote controller (Option)
Wide variation of remote controllers for VRV indoor units
Easy operation with MODEL FXFSQ FXFQ FXZQ FXCQ FXKQ FXDSQ FXDQ FXSQ FXMQ FXUQ FXHQ FXAQ FXL(N)Q FXVQ FXB(P)Q

new intuitive design Stylish remote controller


(BRC1H61W / BRC1H61K)

Simple operation Navigation remote controller


(BRC1E63)
Using only six buttons, users have direct access to basic functions.
Navigation remote controller
This enables them to easily set comfort to their preference. (BRC1F61)
BRC2E61 • ON/OFF
Simplified remote controller
• Operation mode (BRC2E61)
• Temperature setting
Wireless remote controller*
• Airflow rate (5-step & Auto)* (Installed type signal receiver unit)
• Up and down airflow direction (5-step & Swing)*
Wireless remote controller*
• ON/OFF timer (Separate type signal receiver unit)
* The number of airflow steps and availability of auto airflow
rate and swing mode depend on the type of indoor unit. *Refer to page 211 for the name of each model.

Intuitive design The wired remote controller supports a wide range of control functions
• By using pictograms, the user-friendly interface enables convenient
In all the series of VRV, Cool/Heat changeover in the same refrigerant circuit can be changed by the remote
and easy operation. •Control of Cool/Heat controller of the indoor unit.
changeover

Compact size •Group control


Equipment One remote controller can control the
• Measuring only 85 x 85 mm, the new remote controller is Outdoor related to the operation of max.16 indoor units at the
unit same time.
extremely compact and complements any interior design. central control

Wireless remote controller (Option)


Indoor unit
Remote controller
Remote controller

• The wireless remote controller is supplied in a set with a signal


receiver.
Remote
• Signal receiver unit of installed type is contained inside decoration controller
panel or indoor unit.
• Shape of signal receiver unit differs according to the indoor unit. Forced OFF
Signal receiver unit Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of input
(Installed type)
FXF(S)Q series.

Control Systems
Heat Reclaim
• Backlight LCD of new wireless remote controller Remote
Ventilator
BRC-M series Remote controller Remote
controller
Remote controller controller Remote
controller

Control by Remote control Control for Expansion of


Pressing the backlight button 1 two remote controllers 2 3 the combined operation 4 system control
helps operating in dark rooms.
The indoor unit can be The wiring of remote controller The operation of Heat Reclaim The system can be expanded to
connected by the two remote can be extended to max. 500 m Ventilator can be controlled by add several controllers, such as
controllers, for example one in and it is possible to install the the remote controller of the BMS, Forced OFF input and etc.
• A compact signal receiver unit (separate type) to be mounted into the room and the other one in remote controllers for different indoor unit. Of course, the
Signal receiver unit
(Separate type)
a wall or ceiling is included. the control room, which can indoor units in one place. remote controller can display the
control the operation of indoor time to clean the filter.
unit freely. (The last command
* Wireless remote controller and signal receiver unit are sold as a set.
* Refer to page 211 for the name of each model.
has a priority.) Of course, the
BRC-C, E series
group control by two remote
183 controllers is also possible. 184
Control Systems
Control Systems
Integrated building monitoring system
DIII-NET Line

The high speed transmission of DIII-NET enables more advanced control of the VRV system, providing BACnet®/Ethernet or LONWORKS
®

Network Communication Line The DIII-NET system provides for:


you with enhanced comfort. • Close control and monitoring by integrating a wide variety of
Contact Signal Line
air-conditioners in the entire building.
RS485 Modbus Line
®
• Saves the in-building cabling using non-polar, two-wire cables. Easier wiring
work with tremendously fewer wiring errors.
• Additional setups readily up and running. An extendable cabling up to 2 km
in total.
Building Control System • Different control equipment flexibly joined in the system for hierarchical
risk diversification.
• Daikin's total heat exchangers and other devices under integral control.
Controllers for Centralised Control
VRV

(DCS601C51)
Heat Reclaim Ventilator

(DCM601A51)

Via internet
Residential central
remote controller D -NET Interface Adaptor for SkyAir Series
(DCS303A51) (High Speed Multiple SkyAir
(DTA112BA51)
Transmission)
Via internet

ACC Centre Control /Connection Interface * No adaptor is required for some


indoor units.
Air Conditioning Network Service System
(There are restrictions in applicable areas and release DIII-NET, Daikin’s unique Central Control Adaptor Kit
Unification adaptor Packaged
times, therefore please consult us separately for details.) high speed multiple (DTA107A55)
for computerised control Air-conditioner
(Optional Maintenance Service) transmission system,
(DCS302A52)
links air conditioners
and various other
building equipment — in
Home Automation
accordance with Interface Adaptor for DIII-NET use
Master Controller
applications, scale and (KRP928BB2S)
Home Automation conditions — and
Interface Adaptor transmits vast amounts Residential Air-conditioner
BMS (DTA116A51) of information between
them.
(Obtain locally)

Control Systems
Interface for use in BACnet® Di unit (DEC101A51)
Dio unit (DEC102A51) Building services equipment
(DMS502B51)
• Electrical equipment
• Supply water and drainage equipment
• Automatic fire alarm
• Parking equipment
• Lift
• Ventilation equipment
Interface for use in LONWORKS ®
• Lighting
(DMS504B51) • Crime and fire prevention equipment
VRV

Caution: Limitation may apply to some models and functions. Please contact your local sales office for details.
Consultation is necessary before employing this control system. Please contact your local sales office before
making a purchase.
Wiring adaptor
for electrical appendices Note: BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE). LONWORKS® is a trademark of Echelon Corporation registered in the United States and
(KRP2A61/62/51/53)
other countries. Modbus® is a registered trademark of Schneider Electric S.A.

185 186
Control Systems
Control Systems
Advanced control systems for VRV systems
For energy saving & comfort
intelligent Touch Manager maximises the advantages of VRV features
DCM601A51
intelligent Touch Manager is an advanced multi-zone controller that provides the most cost-effective
way to control and monitor the Daikin VRV system.
The 10.4" LCD touch screen is easy to use with three different screen views to include the floor plan
Various types of equipment in a building
layout view, icon view and list view and menus for system configurations.
can be controlled by a single controller. It is also easy to use with standardized remote Web Access from your PC.
It can manage a total of 650 management points consisting of up to 512 Daikin indoor unit groups
(up to 1024 indoor units) along with building equipment control / monitoring with Digital Inputs /
Output (Di/Dio), Analog Inputs / Output (Ai/Ao) and Pulse input (Pi) optional devices.
One touch selection enables flexible control of equipment
in a building. Schedule the operation time for each application. Define the setpoint range that users can change.

With Remote controller


Individual air-conditioning control Office:
Reception:
This heat is killing me.
9:00-17:00
The flexible control achieved by the VRV system 8:00-18:00 Very cold.
precisely meets different air conditioning needs Admin:
8:30-17:00
in each room (e.g. offices, conference rooms, Machine room:
16°C
24 hours
hotel rooms).

Manager room:
8:00-20:00 With Control System
Set point range 22°C - 28°C
Common area:
9:00-17:00 It can not
Meeting room: Why? be set
No schedule below this Oh! Cool.

Setting the I-demand function and nighttime


Lighting control DALI-compatible 22°C
quiet operation function is also possible.
DALI-compatible LED lighting systems can be
controlled and monitored. Lighting control is Turn the unit OFF if a user didn’t. Reset setpoint regularly.
enhanced through an interlock function with air
conditioners and other functions.

Change to 20°C
Stop Start

24ºC
Working hours Turn ON again by remote controller, Power consumption saved
(Scheduled) forgot to turn OFF, and left. by control system

Control Systems
20ºC
Power consumption saved
by control system
Air-conditioning control for large spaces 8:00 17:00 18:30 8:00 8:00 10:00 18:00 8:00

Air handling units can also be controlled. Large


Turn off Automatically turn OFF
spaces, such as entrance halls and shopping as scheduled to cut wasteful operation
Set at 24°C Reset to 24°C
malls, can be easily controlled to ensure comfort.
External contact demand control function

Building equipment control This function automatically controls outdoor and indoor unit capacity based on contact signals sent from
demand controller (field supply) etc. to save power consumption during peak hours.
Various types of equipment
other than air conditioners, • You may set 3 levels that can be switched by ON/OFF signal 3 contacts
Demand D -NET Line
of 3 contacts
including ventilators, fans, and • Control settings are pre-set for each level
Controller
Pump Fan (field supply)
pumps, can also be controlled. • Outdoor unit: I-demand function for peak power cut-off
187 Indoor unit: Set temperature shift, Forced thermostat OFF 188
DCM601A51
Control Systems
Control Systems
Lighting control (Option) Tenant management
In addition to switching lights on and off, advanced lighting control, Reporting the power consumption of VRV system for each tenant (PPD* Option)
such as illuminance adjustment, can be achieved With the PPD function, power consumption can be calculated for each indoor unit (Option)
DALI-compatible
Connection to DALI-compatible lighting control system Please contact your local sales office for details. The energy consumption is proportionally
calculated for each indoor unit. The data can
Simple wiring (daisy chain) enables management of LED lighting by the intelligent Touch Manager. be used for energy management and Operational information
Various air conditioning and lighting control is enabled through the interlock with occupancy sensors calculation of air conditioning usage fees for of individual indoor units
and illuminance sensors. respective tenants. Tenant A
HIGH
Operation duration
Air conditioning and lighting for which power consumption is high can be Room temperature
Operational information of individual indoor Expansion valve
efficiently controlled to promote energy conservation and cost reduction! opening ratio
Lighting control achieved by units are monitored, based on distribution of Tenant B
power consumption of outdoor units. LOW
the intelligent Touch Manager DCM601A51 + DCM002A51*

m from
Automatic calculation of
System Daikin’s PPD keeps track of power

er
total power consumption of

et
distribution for each indoor unit. It performs

W nal
[Operation] individual indoor units

e k ig
h
th se s
• Switch-on/switch-off operation air conditioning billing calculations quickly Tenant C

l
MEDIUM

Pu
• Illuminance (1–100%) control and automatically. Tenant B
Tenant A Tenant C
DCM009A51
• Various illuminance patterns can be registered
(BACnet® Client option) LAN
• Registered pattern can be selected from It is easy to output PPD data.
intelligent Touch Manager PPD data is output in CSV format to a PC or USB Total power consumption
kWh meter
WAGO I/O system memory device and can be freely processed and
[Monitoring] BACnet® DALI BUS managed. *PPD (Power Proportional Distribution) is Daikin’s proprietary calculation method.
DALI module
• Switch-on/switch-off status monitoring controller 753-647
• Lighting abnormality monitoring 750-831

• Illuminance monitoring
DALI LED driver
Sensor Air conditioning bills can be issued by one click (PPD* Option)
• DALI occupancy sensor monitoring LED light (occupancy /
• DALI illuminance sensor monitoring illuminance) Electricity bills can be easily calculated for each tenant (Option)

The power consumption of VRV controlled


by the intelligent Touch Manager can be Internet / Ethernet
Overview of control easily managed for each tenant using a PC. HUB
Invoice

• Up to 5 DALI modules can be connected to a single BACnet® controller. The electricity bill settings facilitate billing SVMPC1 Invoice Invoice

• Up to 64 DALI LED drivers (64 addresses) can be connected to a single DALI module. work through easy calculation and User’s PC

• 64 DALI addresses can be freely assigned to up to 16 groups using a single DALI module. issuance of VRV electricity bills.
(Each group corresponds to a management point of the intelligent Touch Manager.)
• Up to 16 scenes can be set to a single DALI module. Main functions
• Up to 12 sensors (occupancy, illuminance) can be connected to a single DALI module. • Register tenants DCM601A51 + DCM002A51*
• DALI BUS simplifies wiring and setting work by daisy chain wiring and automatic address setting. • Set the electricity unit price for 5 time zones
• Calculate power consumption and electricity charge
for each tenant
• Show aggregation results in the specified period for
Easy maintenance and energy saving by lighting control each tenant
• Output the results (Printout and CSV file) Tenant registration screen Setup screen VRV electricity bill screen

Control Systems
Case 1 Case 2 Case 3
*PPD (Power Proportional Distribution) is Daikin’s proprietary calculation method.

Switch-on / switch-off and Occupancy sensors are used to Lighting abnormalities (e.g. Effective service functions offered to tenants
illuminance are controlled eliminate both wasteful lighting burned-out bulbs) can be Smartphone will be a remote controller of VRV system (Option)
based on a schedule to cut and air conditioning. checked on the intelligent
wasteful power consumption. When a room is unoccupied, Touch Manager screen. Users can operate and check the status of For buildings VRV Smartphone Remote Controller
the air conditioning stops and VRV system from their smartphones via Up to 1024 indoor units can be controlled. VRV Indoor unit
• Failing to switch
off lights is prevented. the lighting is switched off. WiFi. Just add SVMPC2 to
this system
It is not necessary to move where a remote
OFF OFF
Lighting maintenance
controller is located with this feature.
becomes easier and quicker. VRV system in other rooms can be VRV
SVMPC2
operated, and their status can be checked. Outdoor unit
LAN cable DCM601A51
It is also possible to check if air
• Optimal illuminance
The layout screen enables quick conditioners in other rooms remain You can control
VRV system from
identification of specific locations.
reduces energy. switched on etc., helping achieve energy WiFi router Smartphone anywhere through WiFi

189 saving. 190


Control Systems
Control Systems
intelligent Touch Manager system overview
Air conditioning network service system

Preventive maintenance
Up to 512 groups
(1024 indoor units) The intelligent Touch Manager can be connected to Daikin’s own Air Conditioning Network Service
System for remote monitoring and verification of operation status for VRV system. By its ability to
Air Conditioning Up to 650 predict malfunctions, this service provides customers with additional peace of mind.
Network Service System
management points
Enhanced convenience with link to the Air Conditioning Network Service System
The intelligent Touch Manager connects seamlessly to Daikin’s 24-hour Air Conditioning Network Service System.
One D -NET system
Max. 64 indoor unit groups (128 indoor units) ACC centre
iTM Plus Adaptor Personnel at the centre monitor the occurrence of malfunctions
100Mbps Max. 64 indoor unit groups Trouble
Ethernet and track their cause via the Internet.
Advance malfunction warnings help prevent the sudden
occurrence of problems later.
Even malfunctions difficult to identify Air Conditioning Network Service System*
USB Di/Pi port can be monitored remotely.
Flash drive Repair
Max. 64 indoor unit groups
Di/Pi Line Allows dispatching of service engineers Enable prompt repairs as service engineers know
without a call from customers. the cause of the problem beforehand.
Web Access via
Internet *Because of restrictions in applicable areas and release times, please consult a Daikin representative separately for details.

Max. 64 indoor unit groups


KRP
928BB2S
Daikin offers a variety of control s ystems

Web Access
Convenient controllers that offer more freedom to administrators
via LAN Up to 7 Adaptors
Ease of use and expanded control functions
Fire alarm kWh meter Residential A/C
WAGO I/O up to 30 nodes
The user-friendly controller features colours, multilingual function, and
icons in the display for ease of understanding. A wide variety of control
methods can be accommodated, permitting administrators to monitor and
BACnet® / IP operate the system even when they are away from the controller.
DCS601C51

Connect VRV system to your BMS via BACnet® or LONWORKS®


Air Handling Unit Pump Fan Sensor Keycard switch
3rd party
BACnet® controller Compatible with BACnet® and LONWORKS®, BACnet® LONWORKS®
Seamless connection Facilitating the network
the two leading open network between VRV system integration of VRV system
WAGO I/O system communication protocols, Daikin offers and BACnet® open and LONWORKS®
BACnet® controller DALI module
interfaces that provide a seamless connection network protocol.
750-831 753-647 between VRV system and your BMS. DMS502B51 (Interface for use in BACnet®) DMS504B51 (Interface for use in LONWORKS®)

Notes: 1. BACnet is a registered trademark of American Society of Heating, Refrigerating


®

Dedicated interfaces make Daikin air conditioners and Air-Conditioning Engineers (ASHRAE).
freely compatible with open networks 2. LONWORKS® is a trademark of Echelon Corporation registered in the United States
and other countries.

Control Systems
DALI BUS
Smartphone will be a remote controller of VRV system (Option)
Operation from
DALI LED driver
a smartphone
Sensor For house VRV Smartphone Control System
LED light (occupancy / illuminance)
SVMPR2:
for controlling 64 units
Up to 64 indoor units can be controlled. VRV Indoor unit
or DALI BUS
Smartphone SVMPC2: Just add SVMPR2 to
for controlling 1024 units this system
WiFi router DALI LED driver
or Sensor
LED light (occupancy / illuminance)
Tenant billing
SVMPR2
VRV
DALI BUS Outdoor unit
LAN cable

DALI LED driver You can control Monitor Control


Web Access SVMPC1 Sensor VRV system from
via LAN LED light (occupancy / illuminance)
anywhere in your house
WiFi router Smartphone through WiFi
191 192
Control Systems
Control Systems
Home automation interface adaptor
The VRV system can be operated from the home automation system. VRV tablet and smartphone controller: SVMPC1

The SVMPC1 is easy to install, and enables monitoring and operation of VRV systems via tablets and
Image to use home automation interface adaptor DTA116A51 smartphones. It is optimal for centralized management of VRV systems in small buildings or on individual
floors of a building.
Up to 16 indoor units can be individually controlled.
Simple and easy smart control

VRV Indoor unit


• SVMPC1 is easy to install. Just add Up to 64 indoor units can be controlled.
VRV Indoor unit
DTA116A51 to outdoor unit and connect it SVMPC1
to controller.
• Thanks to user-friendly screen, anyone can
operate easily.
DTA116A51
WiFi
router VRV
Outdoor unit

Other Home
Home Automation VRV Indoor unit
Appliances
Use of Modbus® protocol Master Controller

RS485 Modbus® Protocol Internet

Wire length is up to 500 m Television


• Set point range limitation and setback
VRV Outdoor unit
function achieve energy saving and VRV
Outdoor unit
Simple installation comfortable air-conditioning.
The VRV outdoor unit and home automation Compatible with Electric curtains • Daily air-conditioning operation is
Up to 2 units can be DTA116A51* an existing unit. automatically done by schedule function It is easy to check if You can control
connected One adaptor system can be connected simply by using
this dedicated adaptor. with annual calendar. units have not VRV system from
requires for a house
Lighting • Quick notification of malfunction by e-mail been switched off, anywhere through
*A separate power supply for Home Automation Interface Adaptor is necessary. equipment to support quick maintenance. etc. WiFi
It may not be installed inside some outdoor unit models.

Functions Functions
Category Function Detail
Monitor Control
Main screen
Status monitoring On/Off, Setpoint, Operation mode, Fan step, Flap, Error, Error code, Room Temperature
On/Off On/Off status of indoor units On/Off On/Off control of indoor units Manual operation On/Off, Setpoint, Operation mode, Fan step, Flap, Scene Control
Cooling, Heating, Fan, Dry, Auto Cooling, Heating, Fan, Dry, Auto Setpoint range limitation* Cool setpoint min/max, Heat setpoint min/max
Operation mode Operation mode
(depend on indoor unit capability) (depend on indoor unit capability) Off timer* Off timer on/off, Off timer duration (5min – 12h, every 5min)
Setpoint Setpoint of indoor units Setpoint Cooling/Heating setpoint Automatic Setback operation* Setback setpoint range (Cool: 24-35°C, Heat: 10-20°C)
Room temperature Suction temperature of indoor units Swing, Stop, Flap direction control
Fan direction Action registration: Time, On/Off, Setpoint, Operation mode, Fan step, Flap, Off timer on/off, Setback setpoint
Schedule*
Swing, Flap direction (depend on indoor unit capability) Calendar setting: set by date or day of the week
Fan direction
(depend on indoor unit capability) Fan volume L, M, H (depend on indoor unit capability) Interlock Interlock operation depend on equipment status
Fan volume L, M, H (depend on indoor unit capability) Filter sign reset Reset filter sign of indoor units System setting Language, Password setting, User administration*, Point setting*
Forced off status Forced off status of indoor units * Only admin user can set.
Error Malfunction, Warning with Error code Specifications
Filter sign Filter sign of indoor units
Retrieve system information Category Specification Detail
Communication status Communication normal/error of indoor units D -NET address of connected indoor units Connectable Number of indoor units Max 64
Connected indoor units
can be retrieved. units Number of DTA116A51 Max 1
Indoor unit capabilities such as operation mode, Number of Tablet/Smartphone Max 20
Indoor unit capabilities Connectable

Control Systems
fan control, setpoint HV can be retrieved. Device type iPad, iPhone, Android tablet, Android Phone, Windows Tablet, Windows Phone, Windows PC, Mac
device
Web browser Firefox, Chrome, Safari

VRV Smartphone Control System


Multi site management system by using SVMPC1: MSMPN1
VRV Smartphone Control System can be realized by SVMPR1 which is a new product to utilize DTA116A51. Function
The MSMPN1 enables monitoring and operation of all
VRV Indoor unit VRV system connected via SVMPC1 on each site. All site information show on a MSM screen.
Just add Monitoring Connection status, A/C operation status,
SVMPR1 Headquarters MSMPN1
Site Site Error status, Energy consumption etc.
Operation All SVMPC1 function can use on MSM screen.
SVMPR1 DTA116A51

Internet VRV Indoor unit


LAN cable
SVMPC1
You can control VRV from
anywhere in your house
VRV Outdoor unit through WiFi WiFi DTA116A51

WiFi router router


VRV
Smartphone Monitor Control Outdoor unit

193 * Modbus® is a registered trademark of Schneider Electric S.A. WiFi router 194
Precision Piping Method
Precision Piping Method
Non-brazing / Save installation time A smarter way to connect refrigerant piping
Pipes can be joined easily & quickly without brazing and any special tools.
HEADER PACK
Time Saver using Quick Flare Nut Connection
Space Saving with Compact Design
Connects up to 4 and 6 indoor units

HEADER PACK
Packaged Refnet Headers

Daikin Gas Tight Joint


Safe connection without a flame (in brazing work)

Daikin Gas Tight Joint Time saver with easy fitting installation
Less labour intensive
Fire free connection for piping

Innovative problem solving for VRV refrigerant piping installation

Precision Piping Method


Reliability Installation Safety
improvement improvement improvement

Easy piping Faster work Flameless installation


installation that anyone with simplified installation without welding for safe,
can do using basic tools worry-free work

195 196
Precision Piping Method
Precision Piping Method
HEADER PACK Simple & Quick! Daikin Gas Tight Joint
Suitable luxions residence Evolutionally advanced feature
Easy piping connection / Reduction of connection points Easy installation Excellent sealing mechanism
Easy installation by elimination of refnet joints No need for brazing tools or installation skills
Quick piping anyone can do with two spanners
Refnet joint ×5 Double sealing
IDU Proof pressure 4.3 MPa
Brazing 1 2 3 4 5 6 (-45°C through +130°C)

HEADER PACK
IDU
1 2 3 4 5 6
Flare

Connect by Easy Quick flare nut


Daikin Gas installation connection DAIKIN Gas Tight Joint HEADER PACK
Tight Joint
Leverage method
or flare The pull-out resistance is more than 4 times (17.2 MPa)

• Installation time saving 1/3 of conventional • Connectable up to 4 & 6 IDU Authorised standards
• Easy to install No brazing work
• Safety No fire in the building ISO 14903 SGBP (Singapore Green Building Council)
• Space saving Low silhouette only 14 cm height Certification of international standards Proof of • Certificate Number SGBP 2019-2405
safety and reliability • Green Mark compatible products
4 port type 6 port type

HEADER PACK Lineup Matching for various piping sizes


HP Outdoor unit side Indoor unit side (Flare) Indoor unit total Dimension (mm)
(VRV System)
Model name
Liquid / Gas (mm) Port Liquid / Gas (mm) capacity index H D W
Standard joints (Connecting the same pipes)
9.5 / 15.9 Large ×1 9.5 / 15.9 Dimension (mm ) Weight / PC
6 BHF6RHP6Z 4 150 135 143 559 Figure MODEL
(Flare) Small ×3 6.4 / 12.7 ND AF L (g)
9.5 / 15.9 Large ×2 9.5 / 15.9 L
6 BHF6ARHP6Z 6 150 135 143 623 BDGTA06 6.4 19.0 46.2 106
(Flare) Small ×4 6.4 / 12.7

ND
AF
9.5 / 19.1 Large ×3 9.5 / 15.9
6·8 BHF8RHP6Z 6 200 135 143 623 BDGTA09 9.5 22.0 51.4 139
(Daikin Gas Tight Joint) Small ×3 6.4 / 12.7
9.5 / 22.2 Large ×3 9.5 / 15.9 BDGTA12 12.7 23.8 82.3 170
10 BHF10RHP6Z 6 290 135 143 623
(Daikin Gas Tight Joint) Small ×3 6.4 / 12.7 BDGTA15 15.9 29.7 82.8 236
L
12.7 / 28.6 Large ×3 9.5 / 15.9
12 · 14 · 16 BHF16RHP6Z 6 420 135 143 623 BDGTA19 19.1 35.0 85.5 327
(Daikin Gas Tight Joint) Small ×3 6.4 / 12.7
BDGTA22 22.2 38.0 93.5 401

Precision Piping Method


ND
AF
BDGTA28 28.6 45.0 99.5 546
Dimensions (Top view) BDGTA34 34.9 51.1 101.5 686
BHF6RHP6Z BHF6ARHP6Z,BHF8/10/16RHP6Z
BDGTA41 41.3 58.3 103.5 881
517 580
Suspension bolt Pitch Suspension bolt Pitch

Asymmetry joints (Connecting different size pipes)


Suspension

Suspension
bolt Pitch

bolt Pitch
178

178
D
D

Dimension (mm ) Weight / PC


Figure MODEL
ND1 ND2 AF1 AF2 L (g)

L BDGTA1209 12.7 9.5 24.0 22.0 62.4 158

W W BDGTA1512 15.9 12.7 29.7 23.8 83.2 220


ND1

ND2
AF2
AF1

BDGTA2219 22.2 19.1 38.0 35.0 87.4 362


BDGTA2825 28.6 25.4 45.0 41.8 94.4 510

197 198
Option List
Option List
Outdoor units

Type RXUQ12A(W) RXUQ12AM(W) RXUQ18AM1(W) Type


RXUQ6A(W) RXUQ14A(W) RXUQ14AM(W) RXUQ20AM1(W) RXQ6A(W) RXQ12A(W) RXQ18A(W) RXQ18AM(W)
No. RXUQ8A(W) RXUQ16A(W) RXUQ16AM(W) RXUQ22AM(W) No. RXQ8A(W) RXQ14A(W) RXQ20A(W) RXQ20AM(W)
RXUQ10A(W) RXUQ18A(W) RXUQ18AM(W) RXQ10A(W) RXQ16A(W) RXQ22AM(W)
Item
Item RXUQ20A(W) RXUQ20AM(W)
KHRP26M22H, KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H
KHRP26M22H, KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H Distributive REFNET header
1 (Max. 4 branch) (Max. 8 branch) (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Distributive REFNET header piping
1 (Max. 4 branch) (Max. 8 branch) (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
piping REFNET joint KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26A72T
REFNET joint KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26A72T 2 Outdoor unit multi connection piping kit — BHFP22P100
2 Outdoor unit multi connection piping kit — BHFP22P100 3 Active filter unit BACF22E5
3 Active filter unit BACF22E5
Type RXQ24AM(W) RXQ34AM(W) RXQ42AM(W) RXQ52AM(W)
Type RXUQ24AM(W) RXUQ34AM(W) RXUQ42AM(W) RXUQ52AM(W) RXQ26AM(W) RXQ36AM(W) RXQ44AM(W) RXQ54AM(W)
RXUQ26AM(W) RXUQ36AM(W) RXUQ44AM(W) RXUQ54AM(W) No. RXQ28AM(W) RXQ38AM(W) RXQ46AM(W) RXQ56AM(W)
No. RXUQ28AM(W) RXUQ38AM(W) RXUQ46AM(W) RXUQ56AM(W) RXQ30AM(W) RXQ40AM(W) RXQ48AM(W) RXQ58AM(W)
RXUQ30AM(W) RXUQ40AM(W) RXUQ48AM(W) RXUQ58AM(W) Item RXQ32AM(W) RXQ50AM(W) RXQ60AM(W)
Item RXUQ32AM(W) RXUQ50AM(W) RXUQ60AM(W)
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive REFNET header
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H 1 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive REFNET header piping
1 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
piping REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T 2 Pipe size reducer KHRP26M73TP, KHRP26M73HP
2 Pipe size reducer KHRP26M73TP, KHRP26M73HP 3 Outdoor unit multi connection piping kit BHFP22P100 BHFP22P151
3 Outdoor unit multi connection piping kit BHFP22P100 BHFP22P151 4 Active filter unit BACF22E5
4 Active filter unit BACF22E5

REFNET joint
REFNET joint (KHRP26A22/33/72/73T)
(KHRP26A22/33/72/73T)
Option PCB
Option PCB Type RXQ6A(W) RXQ14A(W) RXQ18AM(W) RXQ26AM(W)
Type RXUQ10A(W) RXQ8A(W) RXQ16A(W) RXQ20AM(W) RXQ28AM(W)
RXUQ12AM(W) No.
RXQ10A(W) RXQ18A(W) RXQ22AM(W) RXQ30AM(W)
RXUQ12A(W)
RXUQ14AM(W) RXQ12A(W) RXQ20A(W) RXQ24AM(W)
RXUQ6A(W) RXUQ14A(W) RXUQ18AM(W) Item
No. RXUQ16AM(W)
RXUQ8A(W) RXUQ16A(W) RXUQ20AM(W) 1 DIII-NET expander adaptor DTA109A51
RXUQ18AM1(W)
RXUQ18A(W) 2 External control adaptor DTA104A61
RXUQ20AM1(W)
Item RXUQ20A(W)
3 Home Automation Interface Adaptor DTA116A51
1 DIII-NET expander adaptor DTA109A51 4 Option plate for control adaptor — BKS26A*1 — BKS26A*1
2 External control adaptor DTA104A61
3 Home Automation Interface Adaptor DTA116A51 Type
4 Option plate for control adaptor — BKS26A*1 — BKS26A*1 RXQ32AM(W) RXQ40AM(W) RXQ48AM(W) RXQ56AM(W)
RXQ34AM(W) RXQ42AM(W) RXQ50AM(W) RXQ58AM(W)
No.
RXQ36AM(W) RXQ44AM(W) RXQ52AM(W) RXQ60AM(W)
Type RXUQ22AM(W) RXUQ32AM(W) RXUQ42AM(W) RXUQ52AM(W) RXQ38AM(W) RXQ46AM(W) RXQ54AM(W)
RXUQ24AM(W) RXUQ34AM(W) RXUQ44AM(W) RXUQ54AM(W) Item
No. RXUQ26AM(W) RXUQ36AM(W) RXUQ46AM(W) RXUQ56AM(W) 1 DIII-NET expander adaptor DTA109A51
RXUQ28AM(W) RXUQ38AM(W) RXUQ48AM(W) RXUQ58AM(W) 2 External control adaptor DTA104A61
Item RXUQ30AM(W) RXUQ40AM(W) RXUQ50AM(W) RXUQ60AM(W) 3 Home Automation Interface Adaptor DTA116A51
1 DIII-NET expander adaptor DTA109A51 4 Option plate for control adaptor BKS26A *1
2 External control adaptor DTA104A61
Note: *1. This plate is necessary for each adaptor marked .
3 Home Automation Interface Adaptor DTA116A51
4 Option plate for control adaptor BKS26A*1
Note: *1. This plate is necessary for each adaptor marked .

Option List
199 200
Option List
Option List
Outdoor units Outdoor units
Standard Type
Type Type RQQ6T(E) RQQ12T(E)
No. RSUQ4A RSUQ5A RSUQ6A RSUQ7A RSUQ8A RSUQ9A
Item No. RQQ8T(E) RQQ14T(E)
Item
RQQ10T(E) RQQ16T(E)
1 Header pack BHF6RHP6Z, BHF6ARHP6Z, BHF8RHP6Z
KHRP26M22H, KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H
REFNET header
1 Distributive piping (Max. 4 branch), (Max. 8 branch) (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
2 REFNET header KHRP26M22H (Max. 4 branch) , KHRP26M33H (Max. 8 branch) REFNET joint KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26A72T

3 REFNET joint KHRP26A22T KHRP26A22T, KHRP26A33T


Type RQQ18TN(E) RQQ24TN(E)
4 Drain plug BKP082A41 RQQ30TN(E)
No. RQQ20TN(E) RQQ26TN(E)
RQQ32TN(E)
Item
RQQ22TN(E) RQQ28TN(E)
5 Air direction adjustment grille KPW082A41
KHRP26M22H, KHRP26M33H KHRP26M22H, KHRP26M33H,
(Max. 4 branch) (Max. 8 branch), (Max. 4 branch) (Max. 8 branch)
REFNET header
KHRP26M72H KHRP26M72H, KHRP26M73H
1 Distributive piping (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Option PCB
KHRP26A22T, KHRP26A33T,
Type
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
KHRP26A72T, KHRP26A73T
No. RSUQ4A RSUQ5A RSUQ6A RSUQ7A RSUQ8A RSUQ9A
Item 2 Pipe size reducer — KHRP26M73TP, KHRP26M73HP
3 Outdoor unit multi connection piping kit BHFP22P100
1 DIII-NET expander adaptor DTA109A51

2 External control adaptor DTA104A61


Type RQQ34TN(E) RQQ38TN(E) RQQ42TN(E) RQQ46TN(E)
No.
Item RQQ36TN(E) RQQ40TN(E) RQQ44TN(E) RQQ48TN(E)
3 Home Automation Interface Adaptor DTA116A51
REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
1 Distributive piping (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
4 Option plate for control adaptor BKS26B *1 BKS26C *1 REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
2 Pipe size reducer KHRP26M73TP, KHRP26M73HP
Note: *1. This plate is necessary for each adaptor marked .
3 Outdoor unit multi connection piping kit BHFP22P151

Type
No.
Item
RXMQ4A RXMQ5B RXMQ6B Space Saving Type
1 Header pack BHF6RHP6Z, BHF6ARHP6Z, BHF8RHP6Z Type RQQ18T(E)
No.
2 REFNET header KHRP26M22H (Max. 4 branch), KHRP26M33H (Max. 8 branch) Item RQQ20T(E)
3 REFNET joint KHRP26A22T KHRP26M22H, KHRP26M33H, KHRP26M72H
REFNET header
1 Distributive piping (Max.4 branch) (Max.8 branch) (Max.8 branch)
4 Central drain plug KKPJ5G280
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
5 Fixture for preventing overturning KKTP5B112

Type RQQ30TS(E) RQQ36TS(E)


RQQ42TS(E) RQQ46TS(E)
No. RQQ32TS(E) RQQ38TS(E)
RQQ44TS(E) RQQ48TS(E)
Item
RQQ34TS(E) RQQ40TS(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
REFNET header
1 Distributive piping (Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
2 Pipe size reducer KHRP26M73TP, KHRP26M73HP
3 Outdoor unit connection piping kit BHFP22P100 BHFP22P151

Option List
201 202
Option List
Option List

High-COP Type
Type RWEYQ14T RWEYQ26T Type RWHQ12TH
RWEYQ6T RWEYQ16T RWEYQ28T No. RWHQ14TH
No.
RWEYQ8T RWEYQ18T RWEYQ30T Item RWHQ16TH
RWEYQ10T RWEYQ20T RWEYQ32T
RWEYQ12T RWEYQ22T RWEYQ34T KHRP26M22H, KHRP26M33H, KHRP26M72H
REFNET header
RWEYQ24T RWEYQ36T 1 Distributive piping (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Item
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
KHRP25M33H (Max. 8 branch), 2
KHRP25M33H (Max. 8 branch), KHRP25M72H (Max. 8 branch),
Outdoor unit multi connection piping kit BHFP22P100
KHRP25M33H (Max. 8 branch), KHRP25M72H (Max. 8 branch), KHRP25M73H (Max. 8 branch), 3 Hot water controller box BRCM82
REFNET header KHRP26M22H (Max. 4 branch), KHRP26M22H (Max. 4 branch), KHRP26M22H (Max. 4 branch), 4 Hot water remote controller BRCS82
KHRP26M33H (Max. 8 branch) KHRP26M33H (Max. 8 branch), KHRP26M33H (Max. 8 branch),
1 Distributive piping KHRP26M72H (Max. 8 branch) KHRP26M72H (Max. 8 branch),
Type RWHQ18TH RWHQ24TH RWHQ30TH
KHRP26M73H (Max. 8 branch)
No. RWHQ20TH RWHQ26TH RWHQ32TH
KHRP25A22T,KHRP25A33T,
KHRP25A22T, KHRP25A33T, Item RWHQ22TH RWHQ28TH RWHQ34TH
KHRP25A22T, KHRP25A33T, KHRP25A72T, KHRP25A73T,
REFNET joint KHRP25A72T, KHRP26A22T,
KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26M22H, KHRP26M33H,
KHRP26A33T, KHRP26A72T
KHRP26A72T, KHRP26A73T (Max. 4 branch) (Max. 8 branch) KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
REFNET header
2 Outside unit multi connection piping kit — BHFP22MA56 BHFP22MA84 KHRP26M72H (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
1 Distributive piping
3 External control adaptor DTA104A62 (Max. 8 branch)
4 Strainer kit BWU26A15, BWU26A20 KHRP26A22T,KHRP26A33T,
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
KHRP26A72T
2 Pipe size reducer — KHRP26M73TP, KHRP26M73HP
3 Outdoor unit multi connection piping kit BHFP22P151
4 Hot water controller box BRCM82
Type 5 Hot water remote controller BRCS82
No.
Item RWXQ4A RWXQ5A RWXQ6A
KHRP26M22H, KHRP26M33H Type RWHQ36TH RWHQ40TH RWHQ44TH RWHQ48TH
Distributive REFNET header No.
1 (Max. 4 branch) (Max. 8 branch) Item RWHQ38TH RWHQ42TH RWHQ46TH RWHQ50TH
piping
REFNET joint KHRP26A22T KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
REFNET header
1 Distributive piping (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
2 Pipe size reducer KHRP26M73TP, KHRP26M73HP
3 Outdoor unit multi connection piping kit BHFP22P151
4 Hot water controller box BRCM82
5 Hot water remote controller BRCS82

Option List
203 204
Option List
Option List
Outdoor units VRV indoor units
Standard Type Round Flow Cassette with Sensing Type
Type RWHQ6T RWHQ12T Type FXFSQ25A FXFSQ50A FXFSQ100A
No. RWHQ8T RWHQ14T No. FXFSQ32A FXFSQ63A FXFSQ125A
Item RWHQ10T RWHQ16T Item FXFSQ40A FXFSQ80A FXFSQ140A
KHRP26M22H, KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H Standard panel with Fresh white BYCQ125EEF
Distributive REFNET header
1 (Max. 4 branch) (Max. 8 branch) (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) sensing Black BYCQ125EEK
piping
REFNET joint KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26A72T Decoration Fresh white BYCQ125EAF *
2 Hot water controller box BRCM82 1 Standard panel
panel Black BYCQ125EBSF *
3 Hot water remote controller BRCS82
Designer panel 1 Fresh white BYCQ125EAPF *
Auto grille panel 2, 3 Fresh white BYCQ125EBSF *
Type RWHQ18TN RWHQ24TN RWHQ30TN
For usage of 3-, 4-way flow KDBH551C160
No. RWHQ20TN RWHQ26TN RWHQ32TN 2 Sealing material of air discharge outlet 4
RWHQ22TN RWHQ28TN For usage of 2-way flow KDBH552C160
Item
3 Panel spacer KDB55J160F
KHRP26M22H, KHRP26M33H, KHRP26M22H, KHRP26M33H,
(Max. 4 branch) (Max. 8 branch) (Max. 4 branch) (Max. 8 branch) Chamber Without T-duct joint KDDP55C160 (Components: KDDP55C160-1, KDDP55C160-2) 8
REFNET header
Distributive KHRP26M72H KHRP26M72H, KHRP26M73H 4 Fresh air intake kit type 5,6 With T-duct joint KDDP55C160K (Components: KDDP55C160-1, KDDP55C160K2) 8
1 (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
piping Direct installation type 7 KDDP55X160A
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T KHRP26A22T, KHRP26A33T, (Colorimetric method 65%) KAF556D80 KAF556D160
KHRP26A72T, KHRP26A73T High-efficiency filter unit 9
5
(Including filter chamber) (Colorimetric method 90%) KAF557D80 KAF557D160
2 Pipe size reducer — KHRP26M73TP, KHRP26M73HP
3 Outdoor unit multi connection piping kit BHFP22P100 (Colorimetric method 65%) KAF552D80 KAF552D160
6 Replacement high-efficiency filter 9, 10
4 Hot water controller box BRCM82 (Colorimetric method 90%) KAF553D80 KAF553D160
5 Hot water remote controller BRCS82 7 Filter chamber KDDFP55C160
8 Replacement long-life filter KAF5511D160
Type RWHQ34TN RWHQ42TN RWHQ50TN RWHQ58TN 9 Replacement long-life filter (Auto grille panel) KAF5512D160
RWHQ36TN RWHQ44TN RWHQ52TN RWHQ60TN 10 Ultra long-life filter unit (Including filter chamber) 9 KAF555D160
No.
RWHQ38TN RWHQ46TN RWHQ54TN 11 Replacement ultra long-life filter 9, 10 KAF550D160
Item RWHQ40TN RWHQ48TN RWHQ56TN
12 Branch duct chamber 4 KDJP55C80 KDJP55C160
REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H 13 Insulation kit for high humidity 9, 11 KDTP55K80A KDTP55K160A
Distributive
1 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
2 Pipe size reducer KHRP26M73TP, KHRP26M73HP
3 Outdoor unit multi connection piping kit BHFP22P151
4 Hot water controller box BRCM82 Round Flow Cassette Type
5 Hot water remote controller BRCS82
Type FXFQ25A FXFQ50A FXFQ100A
No. FXFQ32A FXFQ63A FXFQ125A
Item FXFQ40A FXFQ80A FXFQ140A
Fresh white BYCQ125EAF *
Space Saving Type Decoration
Standard panel
Black BYCQ125EAK *
1
Type RWHQ18T panel Designer panel 1 Fresh white BYCQ125EAPF *
No.
Item RWHQ20T Auto grille panel 2, 3 Fresh white BYCQ125EBSF *
REFNET header
KHRP26M22H, KHRP26M33H, KHRP26M72H For usage of 3-, 4-way flow KDBH551C160
Distributive 2 Sealing material of air discharge outlet
1 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) 4

piping For usage of 2-way flow KDBH552C160


REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
2 Hot water controller box BRCM82
3 Panel spacer KDB55J160F
3 Hot water remote controller BRCS82 Chamber Without T-duct joint KDDP55C160 (Components: KDDP55C160-1, KDDP55C160-2) 8
4 Fresh air intake kit type 5,6 With T-duct joint KDDP55C160K (Components: KDDP55C160-1, KDDP55C160K2) 8
Type RWHQ24TS RWHQ30TS RWHQ36TS Direct installation type 7 KDDP55X160A
No. RWHQ22TS RWHQ26TS RWHQ32TS RWHQ38TS High-efficiency filter unit 9 (Colorimetric method 65%) KAF556D80 KAF556D160
5
Item RWHQ28TS RWHQ34TS RWHQ40TS (Including filter chamber) (Colorimetric method 90%) KAF557D80 KAF557D160
KHRP26M22H, KHRP26M33H, (Colorimetric method 65%) KAF552D80 KAF552D160
(Max. 4 branch) (Max. 8 branch) KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H 6 Replacement high-efficiency filter 9, 10
REFNET header (Colorimetric method 90%) KAF553D80 KAF553D160
Distributive KHRP26M72H (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
1 (Max. 8 branch) 7 Filter chamber KDDFP55C160
piping
KHRP26A22T, KHRP26A33T, 8 Replacement long-life filter KAF5511D160
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T KAF5512D160
KHRP26A72T 9 Replacement long-life filter (Auto grille panel)
2 Pipe size reducer — KHRP26M73TP, KHRP26M73HP 10 Ultra long-life filter unit (Including filter chamber) 9 KAF555D160
3 Outdoor unit multi connection piping kit BHFP22P100 11 Replacement ultra long-life filter 9, 10 KAF550D160
4 Hot water controller box BRCM82 12 Branch duct chamber 4 KDJP55C80 KDJP55C160
5 Hot water remote controller BRCS82
13 Insulation kit for high humidity 9, 11 KDTP55K80A KDTP55K160A
Notes: 1. When installing designer panel, body height (ceiling required dimension) is 42 mm higher than standard panel. Designer panel cannot operate 2 and 3 way flow.
Type RWHQ42TS RWHQ48TS 2. A dedicated wireless remote controller (BRC16A2) for the auto grille panel is included for lowering and raising the suction grille.
No. RWHQ44TS RWHQ50TS 3. When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than standard panel.
Item RWHQ46TS 4. Circulation airflow is not available with this option.
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H 5. When installing a fresh air intake kit (chamber type), two air outlet corners are closed.

Option List
Distributive REFNET header 6. It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit.
1 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
piping Introducing higher quantities will increase the operating sound and may also influence temperature sensing.
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T 7. The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when more fresh air is necessary.
2 Pipe size reducer KHRP26M73TP, KHRP26M73HP 8. Please order using the names of both components instead of set name.
3 Outdoor unit multi connection piping kit BHFP22P151 9. This option cannot be installed to designer panel and auto grille panel.
4 Hot water controller box BRCM82 10. Filter chamber is required.
Hot water remote controller BRCS82 11. Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH.
5
*These panels do not contain the sensing function.
205 206
Option List
Option List
VRV indoor units
Options of Round Flow Cassette with Sensing & Round Flow Cassette Compact Multi Flow Cassette Type
Type
Options required for specific operating environments No. Item FXZQ20A FXZQ25A FXZQ32A FXZQ40A FXZQ50A
1-1 Grid ceiling panel BYFQ60CAW
1-2 Sensor kit for grid ceiling panel BRYQ60AAW
2 Replacement long life filter KAF441C60
Ultra long-life filter unit Fresh air intake kit 1, 2 3 Fresh air intake kit KDDQ44XA60
Even in dusty environments where the air Using this kit, a duct can be connected to take in
conditioning is constantly operating, the ultra outdoor air. There are two chamber types that
long-life filter only has to be cleaned once a have intake in two places: with T-duct joint and Double Flow Cassette Type
year. without T-duct joint. No. Item
Type FXCQ20A FXCQ25A FXCQ32A FXCQ40A FXCQ50A FXCQ63A FXCQ80A FXCQ125A
Filter chamber 1 Decoration panel BYBCQ40CF BYBCQ63CF BYBCQ125CF
(Can be used with high-efficiency filter) Outside 65 % KAF532C50 KAF532C80 KAF532C160
2 High efficiency filter *1
Ultra long-life filter 90 % KAF533C50 KAF533C80 KAF533C160
3 Filter chamber for bottom suction KDDFP53B50 KDDFP53B80 KDDFP53B160
4 Long life replacement filter KAF531C50 KAF531C80 KAF531C160
Dusty area: annual filter change
Note: *1. If installing high efficiency filter, filter chamber is required.
*For dust concentration of 0.3 mg/m3 (Requires separately sold Air purifier.)
1 year (Approx. 5,000 hr): About 15 hr/day x 28 day/month x 12 month/year
Ordinary store or office: filter change every 4 years
*For dust concentration of 0.15 mg/m3
4 years (Approx. 10,000 hr): About 8 hr/day x 25 day/month x 12 month/years x 4 years
The units can be installed in the following Corner Cassette Type
different ways: Type FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA
No. Item
High-efficiency filter unit Chamber type (without T-duct joint) 3, 4, 5 1 Panel related Decoration panel BYK45FJW1 BYK71FJW1
KDDP55C160 Air inlet and air discharge
Flexible duct 2 Long life replacement filter KAFJ521F56 KAFJ521F80
Available in two types: 65% and 90% (obtained locally) outlet related

colorimetry. T-duct joint

Suction chamber
(obtained locally)
3D Airflow Duct with Sensing Type
Filter chamber
(Can be used with ultra long-life filter) Intake duct
Connection chamber (obtained locally) Type
No. Item FXDSQ20A FXDSQ25A FXDSQ32A FXDSQ40A FXDSQ50A FXDSQ63A
High-efficiency filter (duct length: 4 m max.)
1 Flexible duct BFD37B40 BFD37B50 BFD37B63

Insulation kit for high humidity Chamber type (with T-duct joint) 3, 4, 5 Slim Duct (Standard) Type
Please use if you think the temperature and KDDP55C160K Flexible duct
No. Item Type FXDQ20PD FXDQ25PD FXDQ32PD FXDQ40ND FXDQ50ND FXDQ63ND
humidity inside the ceiling exceeds 30°C and RH 1 Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63
T-duct joint
80%, respectively.
Suction chamber
Intake duct
Top panel insulation(1)
Connection chamber (obtained locally) Middle Static Pressure Duct Type
(duct length: 4 m max.)
Top panel insulation(2) Type FXSQ20PA FXSQ50PA
FXSQ100PA
Top panel insulation(3) No. FXSQ25PA FXSQ40PA FXSQ63PA FXSQ140PA
FXSQ125PA
•Insulation for decoration panel Item FXSQ32PA FXSQ80PA
•Side panel insulation
Direct installation type 6 65% KAF632C36 KAF632C56 KAF632C80 KAF632C160 KAF632B160B
1 High efficiency filter *1
•Suspension bracket insulation 90% KAF633C36 KAF633C56 KAF633C80 KAF633C160 KAF633B160B
KDDP55X160A 2 Filter chamber (for rear suction) *1 KDDFP63B36 KDDFP63B56 KDDFP63B80 KDDFP63B160 KDDF63B160B
Panel spacer 3 Long-life filter *1 KAF631C36 KAF631C56 KAF631C80 KAF631C160 KAF631B160B
4 Service panel (Fresh white) KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F
Use when only minimal space is available 5 Air discharge adaptor KDAP25A36A KDAP25A56A KDAP25A71A KDAP25A140A KDAP25A160A *2
Duct flange
between drop ceilings and ceiling slabs. (with insulation material) 6 Shield plate for side plate KDBD63A160 —
Intake duct Notes: *1. If installing high efficiency filter and long-life filter to the unit, filter chamber is required.
Note: Some ceiling constructions may (obtained locally) *2. This option is a set of KDAP25A140A and KDBHP37A160.
hinder installation. Contact your
Daikin Dealer before installing
your unit. Middle-High Static Pressure Duct Type
40mm
Panel spacer Notes: 1. Use of options will increase operating sound. Type FXMQ20PA FXMQ50PA FXMQ100PA
2. Connecting ducts, fan, insect nets, fire dampers, air filters, and other No. FXMQ25PA FXMQ40PA FXMQ63PA FXMQ125PA
parts should, as required, be obtained locally.
Item FXMQ32PA FXMQ80PA FXMQ140PA
Sealing material of air discharge outlet 3. When a local-obtained fan is used, an interlock with air conditioner is
necessary. Optional PCB (BRP11B62) is required for interlocking. 65% KAF372AA36 KAF372B56 KAF372B80 KAF372B160
1 High efficiency filter
4. When installing a fresh air intake kit (chamber type), two air outlet 90% – KAF373B56 KAF373B80 KAF373B160
By using this option, 2-way, 3-way, or 4-way corners are closed. 2 – KDDF37AA56 KDDF37AA80 KDDF37AA160
Filter chamber
flow can be selected. 5. It is recommended that the volume of outdoor air introduced through
the kit is limited to 10% of the maximum airflow rate of the indoor
3 Long life replacement filter – KAF371B56 KAF371B80 KAF371B160
4 Long life filter chamber kit – KAF375B56 KAF375B80 KAF375B160

Option List
unit. Introducing higher quantities will increase the operating sound
Branch duct chamber and may also influence temperature sensing. 5 Service panel (Fresh white) KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F
6. The volume of fresh air for direct installation type is approximately 1% 6 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
This chamber lets you connect a round flexible of the indoor unit airflow.
The chamber type is recommended when more fresh air is necessary.
duct to the air discharge opening at any time
after the original installation.
207 208
Option List
Option List
VRV indoor units
High Static Pressure Duct Type Clean Room Air Conditioner
No. Type FXMQ200P FXMQ250P No. Type FXBQ40P FXBQ50P FXBQ63P FXBPQ63P
Item Item
1 8mm pre-filter BAFL501A250 1 Outlet unit — BAF82A63
2 30mm long life replacement filter BAFL502A250 2 Filter HEPA filter BAFH82A50 BAFH82A63
65% BAFM503A250 3 Ceiling intake type BYB82A50C BYB82A63C BYB82A63CP
3 High efficiency filter Panel
90% BAFH504A250 4 Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP
4 Filter chamber (long life filter, high efficiency filter) BDD500A250 5 Outside air intake duct flange KDFJ82A80
5 Drain pump kit BDU510A250VM
6 Insulation kit for high humidity BDT520A250

Residential indoor units with connection to BP units


4-Way Flow Ceiling Suspended Type Slim Ceiling Concealed Type
No. Type FXUQ71A FXUQ100A
Item Type
1 Sealing material of air discharge outlet KDBHP49B140 No. FDKS25EA FDKS35EA FDKS25CA FDKS35CA FDKS50C FDKS60C
2 Decoration panel for air discharge KDBTP49B140 Item
3 Replacement long-life filter KAF5511D160 1 Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63

Ceiling Suspended Type Wall Mounted Type


No. Item Type FXHQ32MA FXHQ63MA FXHQ100MA FXHQ125A FXHQ140A Type
No. FTKS25D FTKS35D FTKS50B FTKS50F FTKS60F FTKS71F
1 Drain pump kit KDU50N60VE KDU50N125VE KDUP50P160
Item
2 Replacement long-life filter KAFJ501D56 KAFJ501D80 KAFJ501D112 KAF501B160
1 Titanium apatite deodorising filter*1 KAF970A46 KAF971B42
3 L-type piping kit (for upward direction) KHFP5M63 KHFP5M160 KHFP5N160
Note: *1. Filter is a standard accessory. It should be replaced approximately 3 years.
4 Fresh air intake kit — KDDQ50A140

BP Units for Connection to Residential Indoor Units


Wall Mounted Type No. Type BPMKS967A2 BPMKS967A3
Item
No. Item Type FXAQ20A FXAQ25A FXAQ32A FXAQ40A FXAQ50A FXAQ63A 1 REFNET joint KHRP26A22T
1 Drain pump kit K-KDU572EVE Note: A single BP unit does not require a REFNET joint. 2 BP units require only 1 REFNET joint, and 3 BP units require only 2 REFNET joints.

Precision Piping Method


Floor Standing Type HEADER PACK
No. Item Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA No. Item HP 6 6 6–8 10 12–16
1 Long life replacement filter KAF361L28 KAF361L45 KAF361L71 1 HEADER PACK BHF6RHP6Z BHF6ARHP6Z BHF8RHP6Z BHF10RHP6Z BHF16RHP6Z
Daikin Gas Tight Joint
No. Item Type Connecting the same pipes Connecting different size pipes
Concealed Floor Standing Type BDGTA06, BDGTA09, BDGTA12 BDGTA1209, BDGTA1512
No. Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA 1 Daikin Gas Tight Joint BDGTA15, BDGTA19, BDGTA22
Item BDGTA2219, BDGTA2825
BDGTA28, BDGTA34, BDGTA41
1 Long life replacement filter KAF361L28 KAF361L45 KAF361L71

Slope-free Drain Kit


Floor Standing Duct Type HEADER PACK Maximum length of on-site drain piping L (m)

No. Item Type FXVQ125N FXVQ200N FXVQ250N FXVQ400N FXVQ500N Type Models For short piping For long piping
1 Replacement long life filter KAF261M140 KAF261M224 KAF261M280 KAF261N450 KAF261N560 (KKWP55A1601) (KKWP55A1602)
2 Ultra long-life filter — KAFSJ9A400 KAFSJ9A560 Round Flow Cassette with Sensing FXFSQ-AVM
3 Front suction base flange KD-9A140 KD-9A200 KD-9A280 KD-9A400 KD-9A560 Round Flow Cassette FXFQ-AVM
4 Front suction Suction grille KDGF-9A140 KDGF-9A200 KDGF-9A280 KDGF-9A400 KDGF-9A560 Ceiling Mounted Cassette Compact Multi Flow Cassette *1 FXZQ-AVM 6 Please refer to its
Discharge and Suction

5 filter chamber Filter Replacement long-life filter *1, 2, 3 KAF-91B140 KAF-91B200 KAF-91B280 KAF-91B400 KAF-91B560 Double Flow Cassette
for high chamber Replacement high 65% *1, 3 FXCQ-AVM installation manual
6 KAF-92B140 KAF-92B200 KAF-92B280 KAF-92B400 KAF-92B560 Single Flow Cassette
efficiency filter for high efficiency filter
7 efficiency 90% *2, 3 KAF-93B140 KAF-93B200 KAF-93B280 KAF-93B400 KAF-93B560 Middle Static Pressure Duct FXSQ-PAVE
8 filter *1, 2 Filter chamber *1, 2 KDDF-9A140 KDDF-9A200 KDDF-9A280 KDDF-9A400 KDDF-9A560 Ceiling Concealed Duct
Middle-High Static Pressure Duct FXMQ-PAVE 4
9 Plenum chamber *4 KPCJ140A KPC5J KPC8J KPCJ400A KPC15JA
Note: *1. For Compact Multi Flow Cassette type units, a VP pipe and reducing socket (procured on site) are required for connecting to the drain hose of the indoor unit and
10 Pulley for plenum chamber *4 KPP8JA KPP9JA KPP10JA — the Slope-free Drain kit. Contact your local representative for more information.
11 Fresh air intake kit KD106D10 KDFJ906A560
12 Rear suction kit KDFJ905B140 KDFJ905B200 KDFJ905B280 KDFJ905B400 KDFJ905B560

Option List
13 Discharge grille for plenum side KD101A10 KD101A20
14 Wood base KKWJ9A140 KWF1G5P KWF1G8P KKWJ9A400 KWF1G15
15 Vibration isolating frame K-ABSG1406A K-ABSG1407A K-ABSG1408A K-ABSG1409A K-ABSG1410A
Notes: *1. When ordering a filter chamber for high efficiency filter (65%), please order with all the respective parts.
*2. When ordering a filter chamber for high efficiency filter (90%), please order with all the respective parts.
*3. When replacing with a new filter, please order the replacement filters with the corresponding filter model name.
*4. Use the plenum chamber and pulley for plenum chamber in combination.
209 210
Option List
Option List
Control systems New Design
System configuration
Operation control system optional accessories Remote sensor No. Item Model No. Function
BRCS01A-1(4)(5)(6) • Up to 16 groups of indoor units (128 units) can be easily controlled using the
For VRV indoor unit use 1 Residential central remote controller DCS303A51 *2 large LCD panel. ON/OFF, temperature settings and scheduling can be
No. Type FXFSQ-A FXFQ-A FXZQ-A FXCQ-A FXKQ-MA FXDSQ-A FXDQ-PD FXDQ-SP FXSQ-PA controlled individually for indoor units.
Item FXDQ-ND
2 Interface adaptor for residential indoor units KRP928BB2S • Adaptors required to connect products other than those of the VRV System to
1 Stylish remote controller BRC1H61W (White) / BRC1H61K (Black) — BRC1H61W (White) / BRC1H61K (Black)
3 Interface adaptor for SkyAir-series DTA112BA51 *3 the high-speed DIII-NET communication system adopted for the VRV System.
2 Navigation remote controller BRC1E63 * 5
BRC1E63 BRC1F61 * 5
BRC1E63 4 Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55 * To use any of the above optional controllers, an appropriate adaptor must be
3 Simplified remote controller — BRC2E61 — BRC2E61 5 Wiring adaptor for other air-conditioner DTA103A51 installed on the product unit to be controlled.
4 Wireless remote controller BRC7M635F (Fresh White) BRC7M531W (for grid ceiling panel) BRC7M66 BRC4C63 BRC4M66 BRC4C66 • Up to 1024 units can be centrally controlled in 64 different groups.
BRC7M635K (Black) 6 DIII-NET expander adaptor DTA109A51 • Wiring restrictions (max. length: 1,000m, total wiring length: 2,000m, max.
Adaptor for wiring
5-1 (operation status output) BRP11B62 — BRP11B61 — BRP11B62 number of branches: 16) apply to each adaptor.
5-2 Adaptor for wiring — KRP1C14A KRP1B61 — • Demand control of individual or multiple systems.
6-1 External control adaptor DTA104A61
6-1
Wiring adaptor for
— KRP2A62 KRP2A51 KRP2A61 — KRP2A53 — KRP2A61
• Low noise option for individual or multiple systems.
electrical appendices (1)
Wiring adaptor for • When installing DTA109A51, DTA104A61 into outdoor units of 10 HP (VRV X) /
6-2 KRP4AA53 KRP4AA51 KRP4AA51 — KRP4A54 — KRP4AA51 6-2 Mounting plate BKS26A
electrical appendices (2) 14 HP (VRV A) or larger.
Remote sensor
7 (for indoor temperature) BRCS01A-5 BRCS01A-6 BRCS01A-1 BRCS01A-4 BRCS01A-1 BRCS01A-4 7-1 Multi tenant unit for Indoor (24 V free type) BRP114A61 *4, 5 • Use in multi tenant buildings where one tenant shuts off the breaker of the indoor unit.
8
Installation box for
KRP1H98A *2, 3 KRP1BB101 *4 KRP1C96 *2, 3 — KRP1BB101 *4 — KRP4A98 *2, 3 • Max. length from outdoor unit to last indoor unit per 1 outdoor adaptor is 200 m.
adaptor PCB 7-2 Multi tenant unit for Outdoor (24 V free type) BRP114A62 *4
External control
• 8 indoor units can be connected per 1 outdoor adaptor.
9 adaptor for outdoor unit DTA104A62 DTA104A61 DTA104A61 — DTA104A53 — DTA104A61
Multi tenant unit
• Use when extending transmission length with the multi tenant option.
10 for Indoor (24 V free type) BRP114A61 — BRP114A61 • Can add Max. 3 booster units to 1 system.
7-3 Multi tenant unit Booster (24 V free type) BRP114A63 *4
• Total transmission length is Max. 800 m.
• Total connectable indoor units is Max. 32 units.
No. Item
Type FXMQ-PA FXMQ-P FXUQ-A FXHQ-MA FXHQ-A FXAQ-A FXLQ-MA FXVQ-N *7 FXBQ-P
FXNQ-MA FXBPQ-P Notes: 1. Installation box for adaptor must be obtained locally. 3. No adaptor is required for some indoor units.
1 Stylish remote controller BRC1H61W (White) / BRC1H61K (Black) 2. For residential use only. Cannot be used with other 4. Because the maximum transmission length varies according to actual installation conditions and
centralised control equipment. diameter of wiring used, please confirm by a dedicated simulator.
2 Navigation remote controller BRC1E63 BRC1E63 *5 BRC1E63 BRC1E63 *6 BRC1E63
5. Installation box is necessary for adaptor BRP114A61. Please refer to option list for each indoor unit.
3 Simplified remote controller BRC2E61 Building management system
4 Wireless remote controller BRC4C66 BRC7CB59 BRC7EA66 BRC7M56 BRC7M676 BRC4C64 — BRC4C64 No. Item Model No. Function
Adaptor for wiring
5-1 (operation status output) BRP11B62 — BRP11B61 — BRP11B62 — BRP11B62 intelligent Touch • Air-Conditioning management system that can be controlled by a
1 Basic Hardware DCS601C51
5-2 Adaptor for wiring — KRP1C13A — KRP1C67 — Controller compact all-in-one unit.
intelligent Touch DIII-NET plus
6-1
Wiring adaptor for
KRP2A61 KRP2A61 — KRP2A62 — KRP2A61 KRP2A61 KRP2A62 *8 KRP2A61 1-1
Controller
Hardware
adaptor
DCS601A52 • Additional 64 groups (10 outdoor units) is possible.
electrical appendices (1) Option
6-2
Wiring adaptor for
electrical appendices (2) KRP4AA51 KRP4AA51 KRP4AA53 KRP4AA52 KRP4AA51 KRP4AA51 — KRP4AA51 1-2 Software Web software DCS004A51
• VRV system that is connected to intelligent Touch Controller can be
Remote sensor operated from the user's PC via a web page.
7 (for indoor temperature) BRCS01A-4 BRCS01A-6 BRCS01A-4 BRCS01A-1 BRCS01A-4 BRCS01A-6 BRCS01A-1
Installation box for
1-3 Electrical box with earth terminal (4 blocks) KJB411A • Wall embedded switch box.
8 KRP4A97 *2, 3 — KRP1BA97 KRP1CA93 *3 KRP1D93A *3 KRP4B93 *2, 3 —
adaptor PCB
2 Basic Hardware
intelligent Touch
DCM601A51
• Air-conditioning management system that can be controlled by
9
External control adaptor
for outdoor unit DTA104A61 DTA104A61 — DTA104A62 DTA104A61 DTA104A61 DTA104A62*8 DTA104A61 Manager touch screen.
10
Multi tenant unit for
BRP114A61 — BRP114A61 — 2-1 Hardware iTM plus adaptor DCM601A52
• Additional 64 groups (10 outdoor units) is possible.
Indoor (24 V free type)
External control adaptor
Max. 7 iTM plus adaptors can be connected to intelligent Touch Manager.
11 — KRP6A1*8 —
for cooling / heating iTM power • Power consumption of indoor units are calculated based on operation
12 Remote controller with key — KRCB37-1 — 2-2 proportional DCM002A51 status of the indoor unit and outdoor unit power consumption measured by
intelligent Touch distribution kWh metre.
Notes: 1. Installation box is necessary for each adaptor marked . 6. Since the control panel is equipped as standard, use the option of BRC1E63 for 2 Manager
2. Up to 2 adaptors can be fixed for each installation box. remote control system. 2-3 Option Software iTM energy • Building energy consumption is visualised.
DCM008A51
3. Only one installation box can be installed for each indoor unit. 7. When using BRC1H61W(K), BRC1E63 or BRC2E61, be sure to remove the control panel navigator Wasted air-conditioning energy can be found out.
4. Up to 2 installation boxes can be installed for each indoor unit. and since BRC1H61W(K), BRC1E63 and BRC2E61 cannot be stored inside the indoor 2-4 BACnet® client DCM009A51 • BACnet® equipment can be managed by intelligent Touch Manager.
5. Some functions can be set only via the wired remote controller unit, please place it separately. 2-5 HTTP Interface DCM007A51 • Interface for intelligent Touch Manager by HTTP
BRC1E63 or BRC1F61. They cannot be set via other remote controllers. 8. Remove the group control adaptor which is a standard equipment before mounting 2-6 SVMPR2 • VRV Smartphone Control System for residence
Please refer to each indoor unit and remote controller page for KRP2A62, KRP6A1 and DTA104A62. KRP2A62, KRP6A1 and DTA104A62 cannot be
function details. mounted to the same indoor unit at the same time.
2-7 Hardware SVM series *1 SVMPC2 • VRV Smartphone Remote Controller for building
2-8 SVMPS1 *5 • Tenant Billing System with PPD
2-9 VRV Smartphone Control System SVMPR1 • VRV Smartphone Control System for residence with DTA116A51.
VRV outdoor unit 2-10 VRV Tablet and Smartphone Controller SVMPC1
• VRV Tablet and Smartphone Controller for small size building or
residence with DTA116A51.
Adaptor for wiring (operation status output) 2-11 Multi Site Management System by using SVMPC1 MSMPN1 • MSM can control all VRV units via SVM system on multi site.
By installing it in the indoor unit with a simple wire connection, Ventilation Fan Adaptor 2-12 Di unit DEC101A51 • 8 pairs based on a pair of ON/OFF input and abnormality input.
this adaptor takes out the operating signals for the indoor unit fan Indoor 2-13 Dio unit DEC102A51 • 4 pairs based on a pair of ON/OFF input and abnormality input.
Unit • Interface unit to allow communications between VRV and BMS.
BRP11B61 BRP11B62 and the compressor and enables the interlocking of equipment
3 Interface for use in BACnet® *2 DMS502B51 Operation and monitoring of air-conditioning systems through
such as the ventilation fan. BACnet® communication.
Example:
Air Conditioning + Ventilation • Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET
Interlocking operation of the indoor unit 3-1 Optional DIII board DAM411B51
communication ports. Not usable independently.
and ventilation fan that takes in fresh air.
Optional Di board DAM412B51 • Expansion kit, installed on DMS502B51, to provide 16 more wattmeter
3-2 pulse input points. Not usable independently.
For residential indoor unit use Communication
interface • Interface unit to allow communications between VRV and BMS.
Type 4 Interface for use in LONWORKS® *3 DMS504B51 Operation and monitoring of air-conditioning systems through LONWORKS®
No. FDKS-EA, C(A) FTKS-D, B, F communication.
Item • Use of the Modbus® protocol enables the connection of the VRV system
5 Home Automation Interface Adaptor DTA116A51
1 Remote controller Wireless type — *1 with a variety of home automation systems from other manufacturers. *6
Wiring adaptor for time clock/remote controller *2 • When installing DTA116A51 into outdoor units of 10 HP (VRV X) /

Option List
2 KRP413BB1S 5-1 Mounting plate BKS26A
(Normal open pulse contact/normal open contact) 14 HP (VRV A) or larger.
3 Remote controller loss prevention chain KKF917A4 Contact/ Unification adaptor for computerised
6 analogue signal DCS302A52 • Interface between the central monitoring board and central control units.
control
4 Interface adaptor for DIII-NET use KRP928BB2S
Notes: 1. A wireless remote controller is a standard accessory. Notes: *1. HTTP interface (DCM007A51) is also required. *4. Installation box for adaptor must be obtained locally.
2. Time clock and other devices should be obtained locally. *2. BACnet® is a registered trademark of American Society of Heating, Refrigerating and *5. PPD option (DCM002A51) for iTM is also required.
Air-Conditioning Engineers (ASHRAE). *6. Modbus® is a registered trademark of Schneider Electric S.A.
*3. LonWorks® is a trademark of Echelon Corporation registered in the United States and
211 other countries. 212
Daikin Engineering Supports
VRV design and sales proposal assistance
Daikin provides engineering supports for VRV systems. It
consists of design supports that can assist consultants and
architects, as well as sales proposal supports for air
conditioning engineers and dealers. We at Daikin provide
the software, the simulation results, and drawing materials
to support the building information modeling (BIM)
currently entering the mainstream in construction industries. CADXpress
Model selection software CADXpress
CADXpress is a flexible design software that optimises equipment selection and
CAD drawing. It can empower consultants and air conditioning engineers so they
can fully enhance their equipment selections to design the most effective, optimum
systems possible. The software also allows the choice of outdoor units based on
peak loads rather than the sum of required capacities for each indoor unit. This
CADXpress
Design assistance fine-tuning feature reduces VRV system sizes and increases efficiency.
Additionally, the CAD function enables automatic calculation of piping diameter
For consultants and architects and length without any need for CAD software.

CFD simulation to optimise outdoor unit layouts DT FLOW 2


DT FLOW 2 is a simulation software that uses computational fluid dynamics (CFD),
Combines energy efficiency and comfort aiming to optimise outdoor unit layouts right at the design stage.
When discharged air from the outdoor unit is drawn back into the suction vent, it
can short circuit the system and lead to: decrease in efficiency of cooling
CFD simulation to optimise operations, capacity shortages, operation cut-offs, and shorter lifetime for the
Heat load calculation outdoor unit. To avoid the need for expensive layout modifications once Outdoor unit Indoor unit
outdoor unit layouts
construction is complete, Daikin uses the CFD method at the early design stage.
This can help consultants and architects optimise their outdoor unit arrangement.

New software for indoor airflow simulation will be coming soon.


Design flexibility Indoor airflow simulation is a method for predicting temperature distribution and
velocity distribution of indoor environment.

Heat load calculation Model selection Drawing materials support Heat load calculation DS-HL2
DS-HL2 uses ASHRAE’s Radiant Time Series method to compute heat load for a
24-hour period on summer and winter days. The Radiant Time Series considers the
delay in heat load coming into the room through outer walls and the roof in the
form of conduction and radiation. Airflow calculation for rooms can be performed.
Detailed reports are available for different breakdown requirements. Additional
monthly calculation is also available with an advanced license tier.

Sales proposals 24-hour weather data for all major cities is based on data recorded from past years.

For air conditioning engineers and dealers


Drawing supports
CAD Symbols
Users download CAD symbol drawing materials, including 2D CAD symbols and 3D
Revit data, for VRV systems designing. The 3D Revit data contains specifications for
Daikin products, including things like capacities and electric characteristics to
Heat load calculation Model selection support Building Information Modeling (BIM).