HUNGARY GLASS PACKAGING FACTORY INVESTMENT FIRE INSTALLATİON WORKS

Scope Fire Installation Works Document no HSCM-QC-ITP-011


BOQ no 14.06.000.0000 Inspection and Test Plan for Fire Installation Works Revision 00
ITP No ITP-002 Submittal Date
Control Category
Activity Inspection
Description Inspection Method References Acceptance Criteria
no Frequency Sub- Project
Contractor Employer
Contractor Director
1 MATERIALS
1.1 Control of pipes and paint products to be used. 100% H Certificate Check Material Submittal,Project Specification Material Submittal,Project
Specification,EN 10255

1.2 Pipe Fitting Equipment (Bolt, DObel, Rod, Profile, Clip). 100% H Certificate Check Material Submittal,Project Specification Material Submittal,Project Specification

1.3 Fire Equipments (Fire Pump, Fire Cabinet, Zone Valves, Compressor, Valves). 100% H Certificate Check Material Submittal,Project Specification,NFPA Material Submittal,Project
Specification,NFPA
2 INSTALLATİON
2.1 Pipe Installation as per approved drawings. 100% W Visual Check-Drawings Check Approved Drawing,DIN Standards,NFPA Approved Drawing,DIN Standards,NFPA

2.2 Valve and Accessory Assembly Control. 100% W Visual Check-Drawings Check Approved Drawing,DIN Standards,NFPA Approved Drawing,DIN Standards,NFPA

2.3 Hangers and support installation support spacing,ducting route,reinforcement & hangers. 100% W Visual Check-Drawings Check DIN Standards,NFPA,,Project DIN Standards,NFPA,,Project
specification,Approved Drawing,MOS specification,Approved Drawing,MOS

2.4 Fittings, Threaded Branch and Clamp Compliance Control. 100% W Certificate Check-Drawings Check DIN Standards,NFPA,,Project DIN Standards,NFPA,,Project
specification,MOS specification,MOS

2.5 Pipe Internal Cleanliness Control with Flushing Application. 100% W Visual Check, DIN Standards,NFPA,,Project DIN Standards,NFPA,,Project
specification,MOS specification,MOS

2.6 Sprinkler Installation Control Suitable for Intended Use. 100% W Visual Check-Drawings Check DIN Standards,NFPA,,Project DIN Standards,NFPA,,Project
specification,MOS specification,MOS
3 EQUIPMENT INSTALLATİON
3.1 Equipment Foundation Location Check as per Approved Drawing. 100% W Survey check-Drawings Check Approved Drawing,Project specification Approved Drawing,Project specification

3.2 Fire Equipments (Fire Pump, Fire Cabinet, Zone Valves, Compressor, Valves) Check as per Approved Drawing. 100% H Visual Check-Drawings Check Approved Drawing,Project specification Approved Drawing,Project specification

3.3 Dilatation Expansion Joint Installation Control. 100% W Visual Check-Drawings Check Approved Drawing,Project specification Approved Drawing,Project specification

3.4 Verify unit Installation is as per approved Drawing, Check Vibration pad Place Beneath the Package Equipment installation. 100% W Visual Check-Drawings Check Approved Drawing,Project specification Approved Drawing,Project specification

3.5 Fire Cabinet Model, Sheet Thickness, Lock, Paint Color etc. Compliance Check. 100% W Visual Check-Drawings Approved Drawing,Project specification Approved Drawing,Project specification
Check,Certificate Check

3.6 Fire Brigade Connection Nozzles, Cabinet Internal Sets (Tube and Hose) Assembly Control. 100% W Visual Check-Drawings Check Approved Drawing,Project specification Approved Drawing,Project specification

4 FINAL INSPECTION
4.1 Calibration of test equipment. 100% H Document Review Accredited Firm / Site Verification As Per Report

4.2 Check Orientation & Level is per IFC Drawing.Check drain system is as per approved drawing. 100% W Visual Check-Drawings Check Approved Drawing,Project specification,MOS Approved Drawing,Project
specification,MOS

4.3 Check for leak test for pipe installation. 100% W Visual Check,Sealing Check Approved Drawing,Project specification,MOS Approved Drawing,Project
specification,MOS

4.4 Control of Tightness Tests of Pipes (Pressure and tightness test shall be performed according standards.) 100% W Visual Check,Sealing Check Approved Drawing,Project specification,NFPA Approved Drawing,Project
specification,NFPA

4.5 Conducting Operational Tests, Complete Commissioning of the Entire System and Labeling. 100% H Form Check,Visual Check Approved Drawing,Project specification,NFPA Approved Drawing,Project
specification,NFPA

Preparared by Reviewed by Approved by

H= Hold Point
W= Witness point
S= Surveillance Point
T= Test point
R= Review of Records