109 MINIMAX Data Sheet of Module FMZ5000 Loop AP XP

The document provides information about a fire detection and suppression control panel module that can connect up to 126 devices on two detector loops or branches. It has features for interface connection of analogue addressable detectors and modules using loop technology for fire detection systems.

Uploaded by

long yu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
268 views

109 MINIMAX Data Sheet of Module FMZ5000 Loop AP XP

The document provides information about a fire detection and suppression control panel module that can connect up to 126 devices on two detector loops or branches. It has features for interface connection of analogue addressable detectors and modules using loop technology for fire detection systems.

Uploaded by

long yu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Product Sheet I Detection

Fire detection and suppression control panels


FMZ 5000 modules/cards

FMZ 5000 Loop AP XP module Part no.: 906185


Functional module for use in all design variants of the
fire detection series FMZ 5000. Includes 2 detector loops
for connection of up to 126 devices each. Instead of a
loop, 2 branches can be connected to the module.
Any number of T branches can be connected to each loop.
The loop devices can be fire detectors, input/output
modules, control modules for sounders and loop couplers
for the operation of conventional detectors in the loop.
For use in potentially explosive atmospheres, IS-detectors
can be connected to the loop via protocol interface and
safety barriers.

Product features Application


• For the interface connection of analogue addressable For fire detection with detectors using loop technology.
detectors and modules with Loop AP protocol System monitoring by connecting switches to addressable
• The high loop current enables the operation of input modules. Control of fire protection devices via dry
multiple modules, sounders, flash lights and detectors contacts or monitored via output modules.
in a single loop Interface connection of monitored zone horns via a
sounder module. For the operation of conventional
• All settings of the module, the detectors and the detectors in the loop, these are connected to a loop coupler.
detector zones are configured using the MxSysCon The module is inserted into the panel with separate
configuration program power supply by power distribution module. The power
• No further adjustment is required supply and system communication are connected via
plug-in connections on the module enclosure.
Up to 14 modules can be used in one fire alarm panel.
Technical specifications
Operating voltage (module) 18 V - 30 V DC
Included in delivery
Quiescent current
max. 52 mA DC Module completely assembled and ready for installation in
(module-bus)
the fire alarm panel.
Supply current max. 1.440 mA DC
Loop current max. 400 mA DC
Not included in delivery
Loop voltage 27 V DC 4 Socket terminal strips FKCT 2.5/3-ST 901564
Number of loops 2 Power distribution module  904093
Number of detectors per loop 126
Max. terminal cross-section 2
2.5 mm (AWG 13) Optional accessories
-5 °C to +40 °C Programming device FMZ5000 Loop AP 904556
Ambient temperature
(+23 °F to +104 °F)
The contents of this publication are subject to modifications without notice. All rights reserved.

Relative humidity max. 95 % Application in potentially explosive


(IEC 721-3-3) no condensation
atmospheres
IP rating (EN 60529) IP 20 Only the following barriers are permitted:
Enclosure Polyamide PA6.6, green Safety barrier IS addressable 24 V  901324
Installation position vertical Loop AP protocol interface 901322

Mounting rail 35 mm DIN 46277,


Mounting
top hat profile Note
Weight 220 g (0.5 lbs) If the loops of one loop module are used for fire detection
301-420_004 / AI01 / 2018-Aug-23 / en

or controlling several extinguishing zones, the loop module


35 x 99 x 114.5 mm (WxHxD)
Dimensions AP XP redundant, part no. 906186, must be used.
1.4 x 3.9 x 4.5 inch (WxHxD)
Total cable length max. 2000 m (6562 ft) per loop
Performance Level acc. to ISO 13849 c
Approvals / marking
See panels

1/1