109 MINIMAX Data Sheet of Module FMZ5000 Loop AP XP
The document provides information about a fire detection and suppression control panel module that can connect up to 126 devices on two detector loops or branches. It has features for interface connection of analogue addressable detectors and modules using loop technology for fire detection systems.
109 MINIMAX Data Sheet of Module FMZ5000 Loop AP XP
The document provides information about a fire detection and suppression control panel module that can connect up to 126 devices on two detector loops or branches. It has features for interface connection of analogue addressable detectors and modules using loop technology for fire detection systems.
Functional module for use in all design variants of the fire detection series FMZ 5000. Includes 2 detector loops for connection of up to 126 devices each. Instead of a loop, 2 branches can be connected to the module. Any number of T branches can be connected to each loop. The loop devices can be fire detectors, input/output modules, control modules for sounders and loop couplers for the operation of conventional detectors in the loop. For use in potentially explosive atmospheres, IS-detectors can be connected to the loop via protocol interface and safety barriers.
Product features Application
• For the interface connection of analogue addressable For fire detection with detectors using loop technology. detectors and modules with Loop AP protocol System monitoring by connecting switches to addressable • The high loop current enables the operation of input modules. Control of fire protection devices via dry multiple modules, sounders, flash lights and detectors contacts or monitored via output modules. in a single loop Interface connection of monitored zone horns via a sounder module. For the operation of conventional • All settings of the module, the detectors and the detectors in the loop, these are connected to a loop coupler. detector zones are configured using the MxSysCon The module is inserted into the panel with separate configuration program power supply by power distribution module. The power • No further adjustment is required supply and system communication are connected via plug-in connections on the module enclosure. Up to 14 modules can be used in one fire alarm panel. Technical specifications Operating voltage (module) 18 V - 30 V DC Included in delivery Quiescent current max. 52 mA DC Module completely assembled and ready for installation in (module-bus) the fire alarm panel. Supply current max. 1.440 mA DC Loop current max. 400 mA DC Not included in delivery Loop voltage 27 V DC 4 Socket terminal strips FKCT 2.5/3-ST 901564 Number of loops 2 Power distribution module 904093 Number of detectors per loop 126 Max. terminal cross-section 2 2.5 mm (AWG 13) Optional accessories -5 °C to +40 °C Programming device FMZ5000 Loop AP 904556 Ambient temperature (+23 °F to +104 °F) The contents of this publication are subject to modifications without notice. All rights reserved.
Relative humidity max. 95 % Application in potentially explosive
(IEC 721-3-3) no condensation atmospheres IP rating (EN 60529) IP 20 Only the following barriers are permitted: Enclosure Polyamide PA6.6, green Safety barrier IS addressable 24 V 901324 Installation position vertical Loop AP protocol interface 901322
Mounting rail 35 mm DIN 46277,
Mounting top hat profile Note Weight 220 g (0.5 lbs) If the loops of one loop module are used for fire detection 301-420_004 / AI01 / 2018-Aug-23 / en
or controlling several extinguishing zones, the loop module
35 x 99 x 114.5 mm (WxHxD) Dimensions AP XP redundant, part no. 906186, must be used. 1.4 x 3.9 x 4.5 inch (WxHxD) Total cable length max. 2000 m (6562 ft) per loop Performance Level acc. to ISO 13849 c Approvals / marking See panels