0% found this document useful (0 votes)
17 views

Overhead Line Design - Load Case Condition Energex

Uploaded by

tosikur rahman
Copyright
© © All Rights Reserved
Available Formats
Download as PDF or read online on Scribd
0% found this document useful (0 votes)
17 views

Overhead Line Design - Load Case Condition Energex

Uploaded by

tosikur rahman
Copyright
© © All Rights Reserved
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 1
3.5 Load case conditions The following tables provide the wind pressure, ambient temperature and load factors to be used in earch 14Pa | oC 1 14 10, - - a 1OPa | 15°C 1 15 15 20 - it 0.25 Max isc 14 1.25 125 1.25 (Broken Wire [checks against Wind see note 2) 1. Design wind pressure will depend on terrain category, line security level and microburst considerations. see Table 3. 2, Failure containment case shall llow for phase and OHEW conductors to be broken in accordance with ‘Clause 3.3.8, causing a worstcase out-of-balanoe load on both termination and intermediate structures. Additionally, for stayed structures, a failure containment load case is required for all conductors attached ‘and the stay wire removed. In dispibution systems using pin or post insulators with wire ties or equivalent fixing, and relatively flexible ‘structures and foundations, itis not necessary to design supports for the RSL_ For tension and terminal ‘distribution pole supports consideration shall be given for the RSL 3. Designers are to add notes to their design drawings indicating, where required, the need for temporary ‘construction stays. Consideration for conductor stringing and construction staging is required when developing supports for this laad case. 4. "0 rofers to dynam loads due tp personnel and equipment.that may be applied tothe pole or poke top hardware during construction/maintenance, see AS/NZSTO00, 5. Forotherload eases, e.g. snow andice, seismic, torsional loading, and maxirmum wind uplif, see ASINZS7000.

You might also like