Weg MDW MDWH QDW SPW RDW DWP 50023623 en
Weg MDW MDWH QDW SPW RDW DWP 50023623 en
Commercial &
Appliance Motors
Automation
Digital &
Systems
Energy
Integrated Solutions
Transmission &
Distribution
Coatings
for Electrical
Installations
Full protection
for your installation
Benefits
Guaranteed
protection for the
electrical installation
MDWP, MDWS, MDW and MDWH mini circuit breaker
line offers protection against overload and short circuit
in electric conductors, complying with the tripping characteristic
curves B, C, and D, according to standards IEC 60898 and IEC 60947-2. Developed to be used in low
voltage circuits with direct or alternating current from 2 to 125 A, the line has a short-circuit breaking capacity
up to 15 kA (127/220 Vac), according to standard IEC 60947-2. The miniature circuit breakers have a trip free
mechanism, which makes the trip independent from the handle, and circuit breaker status indication.
60
J urve B
C
The main characteristic of the miniature circuit-breaker of
Tripping time
4
J urve C
C
2
The characteristic of the miniature circuit-breaker of curve C is
the instantaneous trip for currents from 5 to 10 times above
the rated current. Therefore, they are used for the protection
0.04
of circuits with installation of inductive loads.
J urve D
C
The characteristic of the miniature circuit-breaker of curve D is
the instantaneous trip for currents from 10 to 20. Therefore, 0.02
they are used for the protection of higly inductive loads who 0.01
present a high starting current peak during the starting time, 1 1.5 3
3
4 5
5
6 10
10
30
Padlock
Rated current range ln (A) Maximum dissipated active power per pole (W)
2 ≤ In ≤ 10 2.5
In = 16 3
20 ≤ In ≤ 25 4
32 ≤ In ≤ 40 5
50 ≤ In ≤ 40 7
3
000
000
E+05 1,0E+05
105 1,0E+05
105 1,0E+05
000
50-63
50-63 AA
000 50-63 A 50-63 AA
50-63 20-40
20-40 AA
20-40 A 20-40
20-40 AA
10-16 A
10-16 A
2-6 A
2-6 A
E+04 1,0E+04
104 1,0E+04
104 1,0E+04
2-6 A 2-6
2-6 A
E+03 1,0E+03
103 1,0E+03
103 1,0E+03
E+02 1,0E+02
102 10
1,0E+02
2
1,0E+02
0,1 0,1
0.1 1 11 10 10
10 0,1
0.1 0,1 1 1 10
10
Prospective short-circuitProspective
current (kArms)
short-circuit current (kArms) Prospective short-circuitProspective
current (kArms)
short-circuit current (kArms)
Prospective short-circuit current (kArms) Prospective short-circuit current (kArms)
Accessories
Padlock
Modular accessories
Auxiliary contact block and alarm contact block
Additional functions
"T" button (Test) Reset button
Accessories
Undervoltage release
Standard
Reference Voltage Application Mounting Code
package (pc)
BS E26 MDA 24 Vac / Vdc MDWS Left side 1 14641119
BS E27 MDA 48 Vac / Vdc MDWS Left side 1 14641120
BS E68 MDA 125 Vac / Vdc MDWS Left side 1 14641121
BS D13 MDA 110 Vac MDWS Left side 1 14641122
BS D24 MDA 230 Vac MDWS Left side 1 14641123
Actuation Between 70% and 30% of the voltage at the end
Shunt release
Standard
Reference Voltage Application Mounting Code
package (pc)
BD E03 MDA 24-48 Vac / Vdc MDWS Left side 1 14641027
BD E69 MDA 100-415 Vac / Vdc MDWS Left side 1 14641118
Operation description
Alarm block Auxiliary contact block Shunt release Undervoltage release
(AL-1) (BC-1) (opening - BD) (BS)
Type Device trip indicator Opening and closing auxiliary contact Remote opening Undervoltage opening
U>
U<
Diagram
92 94 91 C2 C1 D2 D1
12 14 11
(L/+) (N/-) (L/+) (N/-)
Technical characteristics
Alarm block Auxiliary contact block Shunt release Undervoltage release
(AL-1) (BC-1) (opening - BD) (BS)
Standards IEC 60947-5-1 IEC 60947-5-1 IEC 60947-2 IEC 60947-2
Pollution degree - 3
Certification
Weight g 32 32 66 66
Accessories
Association
Signal Opening Main device
Alarm block (AL-1) Shunt release (opening - BD)
1 max or 1 max or
Auxiliary contact block (BC-1) Undervoltage release (BS)
Shunt release (opening - BD)
No 1 max or
Undervoltage release (BS)
RDWS | RDWH
1 max Alarm block (AL-1)1)
and No
1 max Auxiliary contact block (BC-1)
2 max Alarm block (AL-1) No
2 max Auxiliary contact block (BC-1) No
Notes: 1) If using 2 signaling devices, first install the AL-1 alarm block.
Ambient temperature factor for the place where the miniature circuit
breaker will be installed
The tripping characteristics and the miniature circuit breakers are affected by the ambient temperature. The following table shows the
withstand current according to the ambient temperature. When installed inside any enclosure, the temperature inside the enclosure
with all surrounding devices connected must be considered as ambient temperature, since the dissipated power of the surrounding
devices influences the temperature rise inside the enclosure. In miniature circuit breakers, the following sizing factors must be applied
when sizing the product current.
Sizing of the maximum rated current of the miniature circuit breaker according to the ambient temperature - IEC 60898-1 (Tref = 30 °C)
Ambient temperature (°C)
Rated -35 -30 -20 -10 0 10 20 30 40 50 60 70
current Curve
(A) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn)
2 B/C/D 2.60 1.30 2.52 1.26 2.46 1.23 2.38 1.19 2.28 1.14 2.20 1.10 2.08 1.04 2.00 1.00 1.92 0.96 1.86 0.93 1.76 0.88 1.71 0.85
3 B/C/D 5.20 1.30 5.04 1.26 4.92 1.23 4.76 1.19 4.56 1.14 4.40 1.10 4.16 1.04 4.00 1.00 3.84 0.96 3.76 0.94 3.52 0.88 3.30 0.82
4 B/C/D 7.80 1.30 7.56 1.26 7.38 1.23 7.14 1.19 6.84 1.14 6.60 1.10 6.24 1.04 6.00 1.00 5.76 0.96 5.64 0.94 5.28 0.88 4.94 0.82
10 B/C/D 13.20 1.32 12.70 1.27 12.50 1.25 12.00 1.20 11.50 1.15 11.10 1.11 10.60 1.06 10.00 1.00 9.60 0.96 9.30 0.93 8.90 0.89 8.52 0.85
16 B/C/D 21.12 1.32 20.48 1.28 20.00 1.25 19.20 1.20 18.40 1.15 17.76 1.11 16.96 1.06 16.00 1.00 15.36 0.96 14.88 0.93 14.24 0.89 13.63 0.85
20 B/C/D 26.40 1.32 25.60 1.28 25.00 1.25 24.00 1.20 23.00 1.15 22.20 1.11 21.20 1.06 20.00 1.00 19.20 0.96 18.60 0.93 17.80 0.89 17.03 0.85
25 B/C/D 33.00 1.32 32.00 1.28 31.25 1.25 30.00 1.20 28.75 1.15 27.75 1.11 26.50 1.06 25.00 1.00 24.00 0.96 23.25 0.93 22.25 0.89 21.29 0.85
32 B/C/D 42.56 1.33 41.28 1.29 40.00 1.25 38.72 1.21 37.12 1.16 35.52 1.11 33.92 1.06 32.00 1.00 30.34 0.95 28.60 0.89 26.75 0.84 25.02 0.78
40 B/C/D 53.20 1.33 51.20 1.28 50.00 1.25 48.00 1.20 46.40 1.16 44.80 1.12 42.40 1.06 40.00 1.00 37.85 0.95 35.61 0.89 33.21 0.83 30.97 0.77
50 B/C/D 67.00 1.34 65.50 1.31 63.00 1.26 60.50 1.21 58.00 1.16 56.00 1.12 53.00 1.06 50.00 1.00 46.24 0.92 43.33 0.87 40.23 0.80 37.35 0.75
63 B/C/D 83.79 1.33 81.90 1.30 80.01 1.27 76.86 1.22 73.71 1.17 70.56 1.12 66.78 1.06 63.00 1.00 58.19 0.92 54.16 0.86 49.80 0.79 45.79 0.73
Sizing of the maximum rated current of the miniature circuit breaker according to the ambient temperature - IEC 60947-2 (Tref = 50 °C)
Ambient temperature (°C)
Rated -35 -30 -20 -10 0 10 20 30 40 50 60 70
current Curve
(A) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn)
2 B/C/D 2.66 1.33 2.63 1.32 2.58 1.29 2.52 1.26 2.46 1.23 2.38 1.19 2.28 1.14 2.20 1.10 2.08 1.04 2.00 1.00 1.92 0.96 1.86 0.93
3 B/C/D 5.32 1.33 5.26 1.32 5.16 1.29 5.04 1.26 4.92 1.23 4.76 1.19 4.56 1.14 4.40 1.10 4.16 1.04 4.00 1.00 3.84 0.96 3.76 0.94
4 B/C/D 7.94 1.32 7.87 1.31 7.71 1.29 7.56 1.26 7.38 1.23 7.14 1.19 6.84 1.14 6.60 1.10 6.24 1.04 6.00 1.00 5.76 0.96 5.64 0.94
10 B/C/D 13.35 1.33 13.21 1.32 12.95 1.30 12.70 1.27 12.50 1.25 12.00 1.20 11.50 1.15 11.10 1.11 10.60 1.06 10.00 1.00 9.60 0.96 9.30 0.93
16 B/C/D 21.52 1.35 21.31 1.33 20.89 1.31 20.48 1.28 20.00 1.25 19.20 1.20 18.40 1.15 17.76 1.11 16.96 1.06 16.00 1.00 15.36 0.96 14.88 0.93
20 B/C/D 26.90 1.35 26.63 1.33 26.11 1.31 25.60 1.28 25.00 1.25 24.00 1.20 23.00 1.15 22.20 1.11 21.20 1.06 20.00 1.00 19.20 0.96 18.60 0.93
25 B/C/D 33.63 1.35 33.29 1.33 32.64 1.31 32.00 1.28 31.25 1.25 30.00 1.20 28.75 1.15 27.75 1.11 26.50 1.06 25.00 1.00 24.00 0.96 23.25 0.93
32 B/C/D 43.38 1.36 42.95 1.34 42.11 1.32 41.28 1.29 40.00 1.25 38.72 1.21 37.12 1.16 35.52 1.11 33.92 1.06 32.00 1.00 30.34 0.95 28.60 0.89
40 B/C/D 53.80 1.35 53.27 1.33 52.22 1.31 51.20 1.28 50.00 1.25 48.00 1.20 46.40 1.16 44.80 1.12 42.40 1.06 40.00 1.00 37.85 0.95 35.61 0.89
50 B/C/D 68.83 1.38 68.15 1.36 66.81 1.34 65.50 1.31 63.00 1.26 60.50 1.21 58.00 1.16 56.00 1.12 53.00 1.06 50.00 1.00 46.24 0.92 43.33 0.87
63 B/C/D 86.06 1.37 85.21 1.35 83.54 1.33 81.90 1.30 80.01 1.27 76.86 1.22 73.71 1.17 70.56 1.12 66.78 1.06 63.00 1.00 58.19 0.92 54.16 0.86
An alternative is to use the factors of the following table, multiple by the load current and select the rated current of the miniature
circuit breaker.
Sizing of the maximum rated current of the miniature circuit breaker according to the load current - IEC 61947-2 (Tref = 50 °C)
Ambient temperature (°C) -35 -30 -20 -10 0 10 20 30 40 50 60 70
Multiplication facotr of the
0.74 0.75 0.77 0.78 0.80 0.83 0.87 0.90 0.95 1.00 1.06 1.11
Load cureent (xIn)
Padlock
Undervoltage release1)
Miniature
Standard
Reference Voltage Timing range circuit Mounting Code
package (pc)
breakers
BS MDWH6-125 A E25 12 Vac / Vdc 0 - 3s MDWH 6~125 A Left side 1 11894563
BS MDWH6-125 A E31 220 Vac / Vdc 0 - 3s MDWH 6~125 A Left side 1 11894564
Tightening torque on the terminals 0.5 N.m
Connection capacity 1 mm²-2.5 mm²
Undervoltage release Note: 1) Limited to one auxiliary block per circuit breaker.
Padlock
C125
C100
C80
B125
B100
B80
105 105
C63
Energy limit I2t (A 2s)
C50
103 103
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
Prospective short-circuit current (kArms) Prospective short-circuit current (kArms)
D125
D100
D80
105
D63
D50
D40
Energy limit I2t (A 2s)
D32
D25
D20
D16
D10
D6
D4
104 D2
103
1 2 3 4 5 6 7 8 9 10
Sizing of the maximum rated current of the miniature circuit breaker according to the ambient temperature
MDW and MDWH Ambient temperature (°C)
Rated 10 20 30 40 50 60 70
Curve
current (A) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn) (A) (xIn)
2 B and C 2.20 1.10 2.08 1.04 2.00 1.00 1.92 0.96 1.86 0.93 1.76 0.88 1.71 0.85
4 B and C 4.40 1.10 4.16 1.04 4.00 1.00 3.84 0.96 3.76 0.94 3.52 0.88 3.30 0.82
6 B and C 6.60 1.10 6.24 1.04 6.00 1.00 5.76 0.96 5.64 0.94 5.28 0.88 4.94 0.82
10 B and C 11.10 1.11 10.60 1.06 10.00 1.00 9.60 0.96 9.30 0.93 8.90 0.89 8.52 0.85
16 B and C 17.76 1.11 16.96 1.06 16.00 1.00 15.36 0.96 14.88 0.93 14.24 0.89 13.63 0.85
20 B and C 22.20 1.11 21.20 1.06 20.00 1.00 19.20 0.96 18.60 0.93 17.80 0.89 17.03 0.85
25 B and C 27.75 1.11 26.50 1.06 25.00 1.00 24.00 0.96 23.25 0.93 22.25 0.89 21.29 0.85
32 B and C 35.52 1.11 33.92 1.06 32.00 1.00 30.34 0.95 28.60 0.89 26.75 0.84 25.02 0.78
40 B and C 44.80 1.12 42.40 1.06 40.00 1.00 37.85 0.95 35.61 0.89 33.21 0.83 30.97 0.77
50 B and C 56.00 1.12 53.00 1.06 50.00 1.00 46.24 0.92 43.33 0.87 40.23 0.80 37.35 0.75
63 B and C 70.56 1.12 66.78 1.06 63.00 1.00 58.19 0.92 54.16 0.86 49.80 0.79 45.79 0.73
70 B and C 77.70 1.11 73.50 1.05 70.00 1.00 64.40 0.92 60.20 0.86 54.60 0.78 49.52 0.71
80 B and C 88.00 1.10 84.00 1.05 80.00 1.00 74.40 0.93 69.60 0.87 60.00 0.75 51.72 0.65
100 B and C 110.00 1.10 105.00 1.05 100.00 1.00 93.00 0.93 87.00 0.87 75.00 0.75 64.66 0.65
125 B and C 137.50 1.10 131.25 1.05 125.00 1.00 116.25 0.93 108.75 0.87 93.75 0.75 80.82 0.65
Sizing factor for ambient temperature where the miniature circuit breakers
are installed
The following table shows the altitude factor for the calculation.
Sizing of the miniature circuit breaker minimum rated current based on the load current
Ambient temperature (°C) -35 -30 -20 -10 0 10 20 30 40 50 60 70
Multiplication factor of the
0.76 0.77 0.80 0.83 0.87 0.91 0.95 1.00 1.06 1.12 1.19 1.27
load current (xIn)
Sizing examples
Recommended
Ambient temperature
Condition Altitude factor Grouping factor Calculation miniature circuit
factor
breaker
Commercial three-phase photovoltaic generation, with a
29 A load and two parallel circuits, installed side by side
29 A x 1 x 1.19 x 1.25 =
at an altitude below 2,000 m, inside an enclosure below a 1 1.19 1.25 MDWH-C50-3
43.14 A
zinc roofing structure which may reach temperatures up
to 60 °C in summer
Note: this table is only for sizing circuit breakers according to the installation place. The conductors used in the electrical installation must be sized according to NBR 5410 standard for Brazil.
18 36 54 72 49.5
65.6
18 36 54 72 49
65.4
4.2
9
F
83
27
89.2
9.1
9
9
E
5.4
50.5
42.5
89.2
78
54
73.5
44
MDWH-AX
50.2
MDWH_AX1
05/06/2012
61.7
45
block (BC-1)
77
68.6
45
78.7
9
81
auxiliary contact
MDW-BC1 / BC2
89.2
45
B
MDWH (80 A...125 A)
50.5
78
mm [inches]
A
83 4 3 2 1
4 3 2 1
108
45
18
F
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência. Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
F
A4P The values shown are subject to change without prior notice. The information is for reference only.
5.4
89.2
9
9
E
94
E
92
89.2 35
44
89.2
50.5
78
61.7
68.6
D
50.2
D
50.6
MDWH-AL
MDWH_AL1
Shunt release
MDWH_BC1
05/06/2012
78
77
05/06/2012
50.2
MDWH-BC1
77
(opening — BD)
45
45
C
C
45
45
1:1
1:1
45
B
83
mm [inches]
mm [inches]
A
18
A
5.4
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência. Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
A4P The values shown are subject to change without prior notice. The information is for reference only.
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência. Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
A4P The values shown are subject to change without prior notice. The information is for reference only.
44
release (BS)
61.7
68.6
Undervoltage
www.weg.net
45
MDWP, MDWS, MDW, MDWH — dimensions (mm)
Switch-disconnectors - SIW
Note: the dimensions of these products are similar to the MDW line of miniature circuit breakers.
For drawings and dimensions, see the miniature circuit breakers section.
Accessories
Auxiliary contact blocks1) Padlock
Reference Application Type WEG code
MDW-BC1 SIW (40 to 63 A) 10261573
1 NOC
MDW-BC2 SIW (80 A, 100 A) 10261574
Technical data - auxiliary contact blocks
Padlock
Switching capacity of the AC-14 6 A/230 Vac - 3 A/400 Vac
MDW-BC1 and MDW-BC2 DC-12 2 A/60 Vdc - 1 A/125 Vdc Padlock Units per
Reference Application WEG code
contacts diameter package
DC-13 6 A/24 Vdc - 2 A/48 Vdc
MDW-PLW63 SIW (40 to 63 A) 11373980
Connection capacity 1 to 2.5 mm2 Up to 5 mm 50
Contact block MDW-PLW100 SIW (80 A, 100 A) 11373981
Tightening torque on the terminals 0.8 N.m
Weight (Kg) 0.040
Residual current
circuit breakers
Full protection of
lives and property
The residual current circuit breaker is a protection
device that monitors current leakage in electrical circuits.
Available in the two and four-pole versions, with a rated current range from 25 A to 100 A, the RDW line
features 30 mA Earth leakage detection detection to protect people or 300 mA to protect property.
Available in AC and A class, where tripping is ensured for alternating sinusoidal residual currents.
Manufactured according to IEC 61008-1.
Technical characteristics
Characteristic Unit RDWS RDWH
Class - AC A
Number of poles - 2P 4P 2P 4P
25 A 40 A 63 A 25 A 40 A 63 A
Rated current In 25 A 40 A 63 A 25 A 40 A 63 A
80 A 100 A 80 A 100 A
Sensitivity IΔn [mA] 30; 300 30; 300 30; 300 30; 300
Surge current resistance [8/20µs] 250 A (instant)
Maximum operating voltage Un ~230 V ~400 V ~230 V ~400 V
Rated making and breaking capacity Im 500 A or 10xIn (whichever is greater)
Rated residual making and breaking capacity IΔm 500 A or 10xIn (whichever is greater)
Rated conditional short-circuit current Inc 6 kA 10 kA
Rated residual conditional short-circuit current IΔc 6 kA 10 kA
Rated impulse withstand voltage Uimp 4 kV
Rated insulation voltage Ui 440 V
Frequency f 50-60 Hz
Operating temperature T -5 °C to +40 °C
Storage temperature T -40 °C to +85 °C
Maximum relative humidity % 50% @ 40°C
Mechanical life operations 5,000
Electrical life operations 2,000
Connecting cable gauge (solid or stranded) [mm²] 1 to 35
Torque [N.m] 2.5
P [mm] 67
Dimensions A [mm] 83
L [mm] 36 72 36 72
Front dimension [mm] 45
Weight kg 0.194 0.432 0.194 0.432
Mounting - DIN rail 35 mm
Standard - IEC 61008-1
Sustainability - RoHS
Note: 1) WEG residual current circuit breakers were designed to simplify the installation on panels, because they can be powered from the top or the bottom, without compromising the
technical characteristics of the components.
Accessories
Padlock
Modular accessories
Adapter contact block, auxiliary contact block and alarm block1)2)
Additional functions
"T" button (Test) Reset button
Accessories
Undervoltage release
Standard
Reference Voltage Application Mounting Code
package (pc)
BS E26 MDA 24 Vac / Vdc RDWS / RDWH Left side 1 14641119
BS E27 MDA 48 Vac / Vdc RDWS / RDWH Left side 1 14641120
BS E68 MDA 125 Vac / Vdc RDWS / RDWH Left side 1 14641121
BS D13 MDA 110 Vac RDWS / RDWH Left side 1 14641122
BS D24 MDA 230 Vac RDWS / RDWH Left side 1 14641123
Actuation Between 70% and 30% of the voltage at the end
Note: 1) T
o use accessories in the Residual Current Circuit Breaker (RDWS and RDWH), the use of the AD-1 Adapter Contact
Block is mandatory.
Shunt release
Standard
Reference Voltage Application Mounting Code
package (pc)
BD E03 MDA 24-48 Vac / Vdc RDWS / RDWH Left side 1 14641027
BD E69 MDA 100-415 Vac / Vdc RDWS / RDWH Left side 1 14641118
Note: 1) T
o use accessories in the Residual Current Circuit Breaker (RDWS and RDWH), the use of the AD-1 Adapter Contact Block
is mandatory.
Operation description
Alarm block Auxiliary contact block Shunt release Undervoltage release
AD-1 adapter contact block
(AL-1) (BC-1) (opening - BD) (BS)
U>
U<
Diagram
92 94 91 C2 C1 D2 D1
12 14 11 12 14 11
(L/+) (N/-) (L/+) (N/-)
Technical characteristics
Alarm block Auxiliary contact block Shunt release Undervoltage release
AD-1 adapter contact block
(AL-1) (BC-1) (opening - BD) (BS)
Standards IEC 60947-5-1 IEC 60947-5-1 IEC 60947-2 IEC 60947-2 Not applicable
Pollution degree - 3
Certification
Mechanical status
- Yes No Yes Yes No
indicator
Rated insulation
Ui 400 Vac 400 Vac - - 400 Vac
voltage
Number of
1 NO/NC 1 NO/NC - - 1 NO/NC
contacts
Operating
-25…+50 °C
temperature
ºC
Storage
-40…+85 °C
temperature
Weight g 32 32 66 66 36
Solid cable
mm² 1 to 4 mm²
cross-section
Stranded cable
mm² 1 to 2.5 mm²
section
Association
Signal Opening2) Connection device3) Main device
Alarm block (AL-1) Shunt release (opening - BD)
1 max or 1 max or
Auxiliary contact block (BC-1) Undervoltage release (BS)
Shunt release (opening - BD)
No 1 max or
Undervoltage release (BS)
RDWS | RDWH
AD-1 adapter contact block
1 max Alarm block (AL-1)1)
and No
1 max Auxiliary contact block (BC-1)
2 max Alarm block (AL-1) No
2 max Auxiliary contact block (BC-1) No
Notes: 1) If using 2 signaling devices, first install the AL-1 alarm block.
2) The opening accessories must be installed after the AD-1 adapter contact block and before the signaling devices.
3) To use accessories in the RDW (residual current circuit breaker), the use of the adapter is mandatory.
83
45
91
N
N 11 N
N 11
TEST
TEST TEST
TEST
NN 22 NN 22
N
N 1
1 3 5
5 N
N 1
1 3 5
5 N
N 1
1 3 5
5
TEST
TEST TEST
TEST TEST
TEST
N
N 22 4
4 66 N
N 22 4
4 66 N
N 22 4
4 66
N
N 1
1 3 5
5 N
N 1
1 3 5
5
TEST
TEST TEST
TEST
N
N 22 4
4 66 N
N 22 4
4 66
Notes: 1) A ll phase conductors, including the neutral, must be connected to the RDW / RDWH; however, the ground conductor must not be connected.
The neutral conductor at the RDWS / RDWH output must remain insulated all over the installation and must not be connected to the ground.
2)If the four-pole RDWS / RDWH is used as two-pole, the phase must always be connected to the terminal next to the N (neutral), which is the first
terminal on the left in the RDWS.
3)The voltage between the phases must not exceed 220 V.
5.4 5.4
5.4 5.4
83
45
45
45
83
83
45
83
Available in the single-phase, plug-in version for degree of protection I and II, the products of the
SPW02 and SPWC lines are protection devices against voltage surges in the power line.
Developed in versions with or without remote signaling contact, the SPW02 and SPWC lines feature
visual signaling to indicate the moment to replace the protection module, and they are divided into four
models, according to the prospective maximum discharge current (wave 8/20 µs): 12, 20, 40 and 60 kA.
Removable protection modules are supplied as replacement accessories to all the models.
The new line of SPW12 surge suppressors was developed for Direct Current (DC) applications and
can also protect your photovoltaic system against induced surges, ensuring greater and better
protection for your loads and your distributed generation system.
The surge protectors Class I are indicated for locals subject to direct and high
Removable protection
intensity strokes, typical characteristic of installations and buildings supplied module
directly by overhead distribution power lines exposed to lightning discharges.
It is recommended the installation of the surge protector class I in the input point
of the power line in the building.
For locals where the power grid is subject to indirect lightning discharges, typical
case of internal installations of homes and/or buildings supplied by embedded/
Input standard:
underground power lines, the surge protectors Class II are recommended. It is Class 1
recommended the installation on the switch board panel. Class 2
For surge suppressors Class I/II, both functions aforementioned are present in
the same product. Namely, protection against the direct and indirect effects
resulting from a lightning discharge.
Accessories
Removable protection module
Maximum discharge Rated discharge Maximum impulse Maximum
Protection Signal Protection
Reference Application current, wave current, wave current, wave continuous operating WEG Code
rating contact level (kV)
8/20 µs Imax (kA) 8/20 µs In (kA) 10/350 µs Iimp (kA) voltage Uc (V)
SPWC-M275-12 SPWC-275-12 II Yes 12 5 - 1.0 275 11402917
SPWC-M275-20 SPWC-275-20 II Yes 20 10 - 1.2 275 11402916
SPWC-M275-45 SPWC-275-45 II Yes 45 20 - 1.5 275 11402915
SPWC-M275-60/12,5 SPWC-275 60/12.5 II / I Yes 60 30 12.5 1.5 275 11402914
Note: the removable protection module is for use on the SPWC model only.
Dimensions (mm)
1 2 3 4
1 2 3 4
1 2 3 4 5 6
0,709 0,709
B
18 18
A
B
3,189
C
81
B 0,709
18
0,244
18
6.2
6,2 1,791
45.5 C 1,063
27 0,252 1,791
45.5
Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
45,5 27 6.4
6,4 45,5
2,476
62.9
2,476
62.9
62,9 62,9
SPW12 0,252
1 2 1 3 2 4 3 5 4 6 5 6
6,4 1,791
D
45,5
0,709 18 18 0,709 0,709 0,709
C 18 18 18 18 2,476
D
A 62,9
E
3,189
3,189
81
81
81
D
E
The values shown are subject to change without prior notice. The information is for reference only.
B
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência.
Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
2,126
54
F 0,252 54 0,252
6,4 1,791 6.4 1,791
SPW02-275-10...40 45,5 6,4 45.5
45,5
13/09/2019 1:1 mm [inches] 2,476 F2,476
A4
C E
62,9 62.9
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência. Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
62,9
The values shown are subject to change without prior notice. The information is for reference only.
Wiring diagrams
SPW02-275-60
SPW12-600...1100
A3
A4
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência. Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
The values shown are subject to change without prior notice. The information is for reference only.
D
The values shown are subject to change without prior notice. The information is for reference only.
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência.
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência.
Does the power line that reaches Will the neutral be grounded to the main Two wiring diagrams
2,126 include neutral?
the building equipotential busbar of the building? No3) are possible4)
54 2,126 Yes
54
No Yes2)
E
Wiring diagram 1 Wiring diagram 2 Wiring diagram 3
SPW12-600...1100
The surge protectors must be connected: SPW12-600...1100
The surge protectors must be connected: The surge protectors must be connected:
- To each phase conductor, on one side; and
19/09/2019 1:1 mm [inches]
-T o each phase conductor, on one side; -T
o each phase conductor on one
A3
- To the MEB or to the PE bar on the other side1) 19/09/2019 1:1
and mm [inches]
side; and
A3
protector
protector
protector
protector
protector
Surge
Surge
Surge
Surge
Surge
Surge
protector
protector
Surge
Surge
Surge
L2 L2 N
L3 L3
protector
protector
protector
protector
Surge
Surge
Surge
Surge
N
protector
protector
protector
protector
protector
protector
Surge
Surge
Surge
Surge
Surge
Surge
protector
Surge
PE
PE PE PEN PE MEB or MEB or
N
MEB or PE bar PE bar
PE bar
PE bar
Notes: 1) The connection to the MEB or PE bar depends on where exactly the surge protectors will be installed and how the MEB is actually implemented. Therefore, the connection
will be to the MEB when:
- The MEB is located upstream the main distribution board (with the MEB located, as it should be, in the immediate surroundings of the input point of the power line in the
building), and the surge protectors are installed onto the MEB and not on the board; or
- The surge protectors are installed on the main distribution board of the building, and the PE bar of the board accumulates the MEB function. As a result, the connection will
be done to the PE bar itself when the surge protectors are installed on the distribution board, and the PE bar of the board does not accumulate the MEB function.
2) The hypothesis configures a scheme that enters TN-C and the installation continues TN-C, or that enters TN-C and then turns into TN-S. The input neutral, necessarily PEN,
must be grounded to the MEB direct or indirectly. The passage from the TN-C to TN-S scheme, with the separation of the incoming PEN conductor into neutral conductor
and PE conductor, would be done on the main distribution board (globally, the scheme is TN-C-S).
3) The hypothesis configures three possible grounding schemes: TT (with neutral), IT with neutral and line that enters the building already in TN-S scheme.
4) There are situations in which one of the two schemes becomes mandatory, like in the case mentioned in item b of 6.3.5.2.6 (ABNT NBR 5410:2004).
- MEB - Main Equipotential Busbar
Wiring diagrams
SPW12 wiring diagram (ABNT NBR 16690:2019)
Wiring diagram + +
The DC surge suppressor comes in a three-pole configuration, in which
its poles must be connected: - -
J To the Positive conductor of the photovoltaic string on one side
protector
protector
Surge
Surge
J To the MEB or to the PE bar or to the grounding system or central pole
protector
Surge
Addiotinal protection needed for the spw protector line
It is necessary to use additional protection when the SPW installation busbar has a short circuit level above 5 kA. For those
cases, the additional protection must be provided by means of one of the following alternatives:
The additional protection must be the same or bigger than the circuit breaking capacity where the surge protection is installed considering:
J Provide the continous energy supply to the installation. In this case, the additional protection will protect the surge protector and maintain
the energy supply to the installation. It is necessary to replace the additional protection in order to keep the installed protect against new
overvoltages discharges. We suggest to use auxiliary contacts in order to indicate the occurrence of a discharge.
J Continuity of surge protection: in this case, the additional protection of the surge protector is the same protection of the installation.
When protecting the surge protector, the protection will also cut of the energy of the installation.
Accessories
Distribution bars Reference Model
Maximum
current
Number of
poles
Length Per package WEG code
Notes: 1)The distribution bar withstands a maximum current The busbars can be cut. However, the following safety recommenda-
3 2 1 1 2 3
of 100 A in case it is supplied through the center, tions must be observed:
as shown on the left. - Cut the copper busbars flush with the pins, leaving at least 3 mm of
2) The BR busbar withstands short-circuit currents plastic insulation at the ends.
Imax = 100 A compatible with the breaking capacity of the MDW 3 mm 3 mm
Plastic insulation Copper busbar
and MDWH modular circuit breakers.
Connector
Maximum Connection Tightening torque on Number Units per
Reference WEG code
current capacity the terminals of poles package
AL-BR 70 A 6 - 25 mm² 2.5 N.m 1 20 11156853
Accessories
Neutral and grounding bars
Reference Number of connections Board Mounting WEG code
BRT01-8 8 QDW02 Surface-mount and Flush-mount2) 13370756
BRN01-8 8 QDW02 Surface-mount and Flush-mount2) 13370757
BTN02-8 4+8 QDW02-8 Surface-mount and Flush-mount 11377560
BTN02-12 9+9 QDW02-12 Surface-mount and Flush-mount 11377565
BTN02-18 9+9 QDW02-18 Surface-mount and Flush-mount 11377562
BRN2) BTN02-241) 9+9 QDW02-24 Surface-mount and Flush-mount1) 11377563
BTN02-361) 9+6+9 QDW02-36 Surface-mount and Flush-mount1) 11377561
Notes: 1) F
or the surface-mount frame, the busbar bracket must be centered to ensure the fastening
of the set.
2) BRN and BRT are installed on a DIN rail of the QDW02.
BRT2) BTN3) 3) T
he BTN02 bars are installed on the structure of the QDW02, in the model indicated in the table.
Note: 1) Each blanking plate is equivalent to the width of a pole of the miniature
circuit breaker.
Technical data
Description Technical data
Rated continuous duty current (In) 125 A
Rated conditional short-circuit current (Icc) 10 kA
Rated insulation voltage (Ui) 500 V / 60 Hz
Rated operational voltage (Ue) 500 V / 60 Hz
Rated impulse withstand voltage (Uimp) 4 kV
Access Front
Mounting Flush and surface-mount
Width (mm) 136 to 341 mm
Dimensions (flush-mount frame) Height (mm) 221 to 505 mm
Depth (mm) 90 and 100 mm
Width (mm) 112 to 300 mm
Dimensions (surface-mount frame) Height (mm) 199 to 473 mm
Depth (mm) 98 mm
Flush-mount IP31
Protection rating
Surface-mount IP31
Resistance to mechanical impact IK- 05
Maximum 40 °C / Minimum -5 °C
Temperature
Average +35 °C for 24 hours
Altitude Up to 2,000 m
Applicable standards NBR IEC 60439-3:2004
Dimensions (mm)
QDW board
Capacity of
Wall-mounted Flush Recess for installation (masonry)
miniature
90
90
X
199
199
Djs X
127
127
221
127
127
221
4 125
4, 6, 8, 12 6 160
211
112
112 136
8 198
136
148
148 172
183
172
56
12 270
183 207
207 56
255
255 94.5
98 279
279
100
100 379
379
199
220
127
127
127
127
251
18
251
233
233
362
362 99
98
397
397 66
68
305
305
98
100 273
273
127
127
127
127
326
326
24
345
345
330
330
127
127
127
127
271
270 92
98
64
68
98
100 310
310
127
127
127
127
473.7
127
127
127
127
505
505
473
36
470
470
127
127
127
127
306.3
300 97 341
341
98 65.5
68
BR1
F E D C B A BR2 BR3
Los valores demostrados pueden ser cambiados sin aviso previo. La información és de referencia solamente.
17.5
1
17.5
6 6
11
11
39,370 1) 0,429
1,000 10.9
10,9 5.5 5
1000
26
26
0,587
14.9
14,9
1,000
2
1)
1000
1,0001)
0,197
5
5
0,217
The values shown are subject to change without prior notice. The information is for reference only.
5.5
5,5
Sujeito a alteração sem aviso prévio. As informações contidas são valores de referência.
3
0,709
18
18
A
Note: 1) Also supplied in the 12-pole versions.
4
DETALHE A BR1-54
BRN / BTN
31/08/2012 1:1 mm [inches]
A4
6.0
35.0
6.0
68.7
Frame 1 2 to 63
Fixed - 3
Frame 2 70 to 125
Frame 1 6 to 63
Fixed - 101)
Frame 2 80 to 125
63 16 to 63 15
125 70 to 125 20
250 150 to 250 20
Fixed -
400 300 to 400 35
630 450 to 630 35
800 700 to 800 35
160 16 to 160 18 - 80
250 100 to 250 Fixed and 18 - 80
adjustable -
400 200 to 400 35 - 65
800/1000 320 to 1,000 Adjustable 35 - 65
1600 1,250 and 1,600 - Adjustable 50 - 65
According to NBR IEC 60947-2 / Annex A, all the arrangements that have cascading characteristics are normally tested so as
to ensure the aforementioned performance. The following tables contain the possible association of circuit breakers as a
function of the system rated voltage and prospective short-circuit current. These tables indicate the maximum short-circuit
breaking capacity (Icu) that the income (C2-supply) and output (C1-load) circuit breaker association withstands.
The breaking capacities reinforced by cascading indicated in the tables are valid for output circuit breakers (C1) with 1P,
1P + N, 2P, 3P or 4P.
The association described above is not restricted to two consecutive circuit breakers, but to all the circuit breakers installed
downstream from the income circuit-breaker (C2).
We are not necessarily limited to using the circuit breakers combined in the same switchboard. They may belong to different
switchboards/panels.
Icc
Icu1 < Icc Icu2 < Icc Icu = Final short-circuit breaking capacity of the device
Figure 1
DWB160N160-3DX DWB160N160-3DX
In = 160 A In = 160 A
Icu = 30 kA @ 400 Vac Icu = 30 kA @ 400 Vac
Considering cascading, we
DWB160N50-3DX MDWH50-C3
may reduce the short-circuit
In = 50 A In = 50 A
breaking capacity of the
Icu = 30 kA @ 400 Vac Icu = 10 kA @ 400 Vac
downstream circuit breaker
and therefore, the cost.
MDWH 6 to 63 ---- 30 kA 30 kA
MDW 6 to 63 10 kA
Load circuit breaker (C1) Rated current (A) 15 to 50 60 to 100 125 to 250
MDWH 6 to 63 18 kA 22 kA 20 kA
Load circuit breaker (C1) Rated current (A) 16 to 160 16 to 160 100 to 250
MDWH 6 to 63 ---- 30 kA 30 kA
Load circuit breaker (C1) Rated current (A) 16 to 160 100 to 250 200 to 400
AGW50N 15 to 50 30 kA 36 kA 50 kA
AGW100N 60 to 100 30 kA 36 kA 36 kA
Load circuit breaker (C1) Rated current (A) 100 to 250 200 to 400
Load circuit breaker (C1) Rated current (A) 20 to 100 125; 160 200; 250 400 630
MDW 6 to 63 10 kA
Load circuit breaker (C1) Rated current (A) 15 to 50 60 to 100 125 to 250
MDWH 6 to 63 18 kA 22 kA 20 kA
Load circuit breaker (C1) Rated current (A) 16 to 160 16 to 160 100 to 250
MDWH 6 to 63 ---- 30 kA 30 kA
Load circuit breaker (C1) Rated current (A) 16 to 160 100 to 250 200 to 400
AGW50N 15 to 50 30 kA 36 kA 50 kA
AGW100N 60 to 100 30 kA 36 kA 36 kA
Load circuit breaker (C1) Rated current (A) 100 to 250 200 to 400
Load circuit breaker (C1) Rated current (A) 20 to 100 125; 160 200; 250 400 630
MDW 6 to 63 10 kA
MDWH 6 to 63 14 kA 18 kA
Load circuit breaker (C1) Rated current (A) 16 to 160 16 to 160 100 a 250
MDWH 6 to 63 ---- 25 kA 25 kA
Load circuit breaker (C1) Rated current (A) 16 to 160 100 to 250 200 to 400
AGW50N 15 to 50 30 kA 36 kA 50 kA
AGW100N 60 to 100 30 kA 36 kA 36 kA
Load circuit breaker (C1) Rated current (A) 100 to 250 200 to 400
Load circuit breaker (C1) Rated current (A) 20 to 100 125; 160 200; 250 400 630
Global presence
is essential, as much
as understanding
your needs.
Global Presence
With more than 40,000 employees Availability is to have a global support network
worldwide, WEG is one of the largest electric
motors, electronic equipments and systems
Partnership is to create solutions that suits your needs
manufacturers. We are constantly expanding
our portfolio of products and services with
expertise and market knowledge. We create Competitive edge is to unite technology and inovation
integrated and customized solutions ranging
from innovative products to complete
after-sales service.
Know More
High performance and reliable
products to improve your
production process.
Excelence is to provide a whole
solution in industrial automation that
improves our customers productivity.
Visit: www.weg.net
youtube.com/wegvideos
www.weg.net
+55 47 3276.4000