0% found this document useful (0 votes)
14 views156 pages

Installation Manual EnUS 2508510603

Uploaded by

andrei
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views156 pages

Installation Manual EnUS 2508510603

Uploaded by

andrei
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 156

DS7200V2-EXP

Expert Programming Guide


EN Control Panel
DS7200V2-EXP | Expert Programming Guide | Contents EN | 2

Contents
1. Introduction ...............................................................................................................................................................4
1.1 Documentation Conventions.................................................................................................................................4
1.1.1 Type Styles Used.............................................................................................................................................4
1.1.2 Notes, Cautions, and Warnings.....................................................................................................................4
1.1.3 Other Conventions .........................................................................................................................................4
2. Scope of Document ..................................................................................................................................................4
3. How to Program........................................................................................................................................................5
3.1 Keypad Programming ............................................................................................................................................5
3.1.1 Installer Mode/Installer Menu ......................................................................................................................5
3.1.2 Expert/Installer Programming Modes..........................................................................................................5
3.1.3 Parameter Addresses ......................................................................................................................................5
3.1.4 Text Entry Addresses .....................................................................................................................................7
3.1.5 Exit Programming Mode ...............................................................................................................................7
4. Control Panel Programming..................................................................................................................................8
4.1 Understanding the Parameter Option Charts......................................................................................................8
4.2 Panel Wide Parameters ..........................................................................................................................................9
4.2.1 Routing Destinations ......................................................................................................................................9
4.2.2 Reporting Format Configuration.................................................................................................................10
4.2.3 Phone, Auto-Forward, and RPS Configuration .........................................................................................14
4.2.4 Global Reporting Options ...........................................................................................................................19
4.2.5 Tests................................................................................................................................................................28
4.2.6 Programming Options ..................................................................................................................................33
4.2.7 Global Open/Close Options .......................................................................................................................37
4.3 Area Wide Parameters .........................................................................................................................................48
4.4 User Interface ........................................................................................................................................................52
4.4.1 Authority Level Configuration ....................................................................................................................52
4.4.2 PIN Configuration/Installer PIN.................................................................................................................61
4.4.3 Users ...............................................................................................................................................................64
4.4.4 Keypads..........................................................................................................................................................67
4.4.5 ABC Keys and Duress Parameters .............................................................................................................71
4.4.6 RF Keypads ...................................................................................................................................................75
4.4.7 Q Button Configuration ...............................................................................................................................76
4.4.8 RF Keyfobs ....................................................................................................................................................78
4.5 Zone Parameters ...................................................................................................................................................80
4.5.1 Location Configuration ................................................................................................................................80
4.5.2 Zone Function Configuration ......................................................................................................................88
4.5.3 Global Zone Configuration........................................................................................................................103
4.6 Output Parameters ..............................................................................................................................................107
4.6.1 Global Output Configuration ....................................................................................................................107
4.6.2 Output Configuration .................................................................................................................................110
4.7 Sked Parameters..................................................................................................................................................120
4.8 Data Bus Device Parameters .............................................................................................................................123
4.8.1 RF Receiver Configuration........................................................................................................................123
4.8.2 RS-232 Module Configuration ..................................................................................................................125
4.8.3 DX8010 Telephone Module Configuration.............................................................................................126
4.8.4 DX2010 Configuration...............................................................................................................................127
4.9 Miscellaneous Programming Options ..............................................................................................................128
4.10 Network Communication ..............................................................................................................................129
4.11 DACM Configuration ....................................................................................................................................135
5. Reference Materials .............................................................................................................................................138
5.1 Control Panel Events and Reporting Formats.................................................................................................138
5.2 Glossary................................................................................................................................................................148

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | Figures EN | 3

Figures
Figure 1: Routing Destination Phone Number Configured for Basic Pager................................................................12

Tables
Table 1: Document Overview ...........................................................................................................................................4
Table 2: Reserved and Expert Addresses.........................................................................................................................6
Table 3: Key/Character Assignments ...............................................................................................................................7
Table 4: Phone Number Entry Selections ........................................................................................................................9
Table 5: Personal Dialing Format Configuration ..........................................................................................................11
Table 6: Report Tone Selections .....................................................................................................................................11
Table 7: Format Field Options ........................................................................................................................................13
Table 8: Account Number Addresses/Defaults .............................................................................................................48
Table 9: Account Number Entry Selections ..................................................................................................................48
Table 10: User Configuration ............................................................................................................................................64
Table 11: DS7446KP Keypad Icon Functions .................................................................................................................67
Table 12: RF Keypad Data Bus Addresses/Transmitter Numbers................................................................................75
Table 13: Location Configuration Parameters .................................................................................................................80
Table 14: Default Zone Function Type Selections ..........................................................................................................84
Table 15: Location Text Addresses/Defaults ...................................................................................................................86
Table 16: Zone Function Configuration Parameters .......................................................................................................88
Table 17: Single EOL Resistor Zone Configuration Options ........................................................................................89
Table 18: Tamper-wired, Zone Doubled, and No EOL Resistor Zone Configuration Options................................89
Table 19: Zone Function Type Options ...........................................................................................................................90
Table 20: On-board Zone Pulse Count Time Selections ................................................................................................94
Table 21: Off-board Zone Pulse Count Time Selections................................................................................................95
Table 22: EOL Resistor Location Pairing for Zone Doubling .....................................................................................103
Table 23: Output Configuration Parameters..................................................................................................................110
Table 24: Output Function Types ...................................................................................................................................112
Table 25: Output Mode Options.....................................................................................................................................117
Table 26: Pulse Mode Configuration ..............................................................................................................................119
Table 27: One Shot Mode Configuration.......................................................................................................................119
Table 28: Sked Configuration Parameters......................................................................................................................120
Table 29: Control Panel Events and Reporting Formats..............................................................................................138

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 1. Introduction EN | 4

2. Scope of Document
1. Introduction See Table 1 for an overview of this document and other
1.1 Documentation Conventions documents related to the DS7240V2/DS7220V2
Control Panels:
1.1.1 Type Styles Used
To help identify important items in the text, the Table 1: Document Overview
following type styles are used:
Bold text Indicates important text or terms Document Part Number Description
that you should note. User’s Guide 4998153894 Contains keypad
Italicized text Refers you to a drawing, table, or operation instructions for
the end-user. Covers use
other section of this document.
of the LCD (text) keypad
[9][8][7][6] Bracketed numbers represent keypad and the LED keypad.
keys. When next to one another, Installer’s 4998153893 Contains all wiring and
they represent the key sequence to Guide setup instructions, and
press for a particular function. For basic programming
this example, pressing the keys parameters with
shown enters the default Installer descriptions.
Troubleshooting
PIN.
information also included.
1|6 Numbers separated by a vertical bar Expert 4998153891 Contains all programming
represent output function types. This Programming parameters with
example is for Output Function Guide (this descriptions and keypad
Type 1|6: Strobe. document) programming
instructions.
1.1.2 Notes, Cautions, and Warnings Release Notes 4998153890 Contains issues with
Throughout this document there are important notes control panel that were
that address personal and/or equipment safety issues, found after printing of the
system operation issues, etc. They are set off as follows: documentation.
System 4998153887 Contains all programming
The Important Note identifies information Worksheet parameter defaults and
intended for successful operation. space to record any
default changes made
during setup of the
control panel.
The Caution Note identifies information
intended to prevent an incident that could
prohibit the functionality of the
program/equipment.

The Warning Note identifies information


intended to prevent an incident that could
prohibit the functionality of the
program/equipment and/or personal injury.
1.1.3 Other Conventions
Programming parameter titles are identified as follows:

Programming Parameter Title

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 3. How to Program EN | 5

3.1.2 Expert/Installer Programming Modes


3. How to Program • Installer Programming Mode: Installer
Programming Mode is the control panel’s default
3.1 Keypad Programming
programming mode. This mode allows the installer
3.1.1 Installer Mode/Installer Menu to access only a subset of the available
A text keypad such as the DS7447E or programming parameters. Installer Programming
DS7447V2 LCD Keypad can be used for Mode follows through the addresses shown in the
keypad programming. The DS7445i and programming section of the DS7200V2 Installer’s
DS7445V2 LED Keypads cannot be used Guide (P/N: 4998153893).
for keypad programming. • Expert Programming Mode: When the control
panel enters the Expert Programming Mode, all of
Use of the Installer PIN might be restricted. the available programming parameters can be
See Keypad Response Options on page accessed. This manual contains all of the available
70 for information on enabling/restricting programming parameters. Follow these steps to
the Installer PIN. enter the Expert Programming Mode:
There are three methods to access the control panel’s 1. Enter Installer Mode (see Installer Mode/Installer
programming mode. Choose a method from below and Menu for instructions).
follow its subsequent steps. 2. Press [7][2][4][0][#] if you are programming a
1. From a LCD (text) system keypad: DS7240V2. Press [7][2][2][0][#] if you are
programming a DS7220V2.
a. Enter the Installer’s PIN. The default Installer
PIN is 9876. See Installer PIN on page 63 for 3. Press [1][*]. The control panel enters Expert
instructions on changing the default Installer Programming Mode, and the display shows
PIN. Address 0.
b. Press [#][4][1] to enter the Installer’s Menu. 3.1.3 Parameter Addresses
c. Press the [8] key to enter the programming Data for each parameter is stored at one or more
mode. addresses. Special addresses identified as option
parameters allow you to set several options at a single
From an Installer Keypad:
address.
d. Set the Installer Keypad address to 0 (zero).
There are two parts to every address displayed across
e. Connect the Installer Keypad to the control the keypad’s top line:
panel. See “Installer Keypad” in the DS7200V2
• Adr: XXXX: The number following “Adr”
Installer’s Guide (P/N: 4998153893) for
indicates the current address displayed.
instructions.
• D=X: “X” indicates the data digit selection for the
f. Close the Installer Switch.
address currently displayed.
g. Enter the Installer PIN.
Adr: 0000 D=0
h. Press [#][4][1] to enter the Installer’s Menu.
i. Press the [8] key to enter the programming
mode. To view a specific address, enter the 4-digit address
number and then press [#].
Without an Installer’s PIN:
For example, to go to Address 0221, press the
j. Remove all power from the control panel
following keys in this order: [0][2][2][1][#].
(Mains and standby battery).
Leading zeroes can be omitted. Pressing [2][2][1][#] is
k. Close the Installer Switch.
the same as pressing [0][2][2][1][#].
l. Connect the Installer Keypad to the control
panel if you are using an Installer Keypad. Adr: 0000 D=0
0221
m. Restore all power to the control panel.
n. Locate the keypad displaying the Installer To scroll forward one address at a time, press [#]. To
Menu. scroll back one address at a time, press [*].

o. Press the [8] key.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 3. How to Program EN | 6

Follow these steps to edit the data digit entry for an Certain addresses are skipped during keypad
address: programming: Reserved addresses and Expert
1. Enter the address. addresses. Table 2 identifies these addresses.

2. Press the [#] key. • Reserved Addresses: These addresses are


reserved for future development.
3. Enter the new value (0 to 15).
• Expert Addresses: These addresses are only
4. Press the [*] key.
available when the control panel enters Expert
For example, to change the data digit for Address 0221 Programming Mode.
from 0 to 1, press the following keys in this order:
[1][*]. The new value appears on the second line of the Table 2: Reserved and Expert Addresses
display.
Adr: 0221 D=0 Keypad display before making any Reserved Addresses
changes. Current Data Digit entry
shown. DS7240V2 DS7220V2 Expert Addresses
↓ 0214-0219 0214-0219 0065
Adr: 0221 D=0 Press [1] to change Data Digit entry 0237 0237 0132-0180
1 from 0 to 1. 0274-0275 0274-0275 0222-0236
↓ 0282-0285 0282-0285 0238-0248
Adr: 0221 D=1 Press [*] to accept new Data Digit 0292-0295 0292-0295 0255-0257
entry. Display updates new entry. 0304-0307 0304-0307 0260
Follow these steps to fix an incorrect data digit entry: 0314-0317 0314-0317 0262-0273
0326-0329 0320-0363 0297
1. Press the [#] key.
0336-0339 0826-0905 0319
2. Re-enter the address you wish to program. 0348-0351 1035-1037 0341
3. Press the [#] key. 0358-0361 1128-1183 0363-0378
4. Enter the desired data digit value (0 to 15). 1035-1037 1252 0703
1252 1262 0906-1034
5. Press the [*] key.
1262 1522-1649 1038-1043
2940-2943 2418-2929 1251
2945-3405 2940-2943 1253-1261
3430-3433 2945-3405 1263-1265
3434-3441 3430-3433 2930-2939
3442-3505 3434-3441 2944
3541-3545 3442-3505 3406-3413
3554-9999 3541-3545 3507-3513
3554-9999 3515-3521
3523-3529
3531-3537
3539-3540
3886-3910
Press [#] to move forward to the next available
address. Press [*] to move back to the previous
available address.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 3. How to Program EN | 7

3.1.4 Text Entry Addresses The following keys are not used in text programming
All text entry addresses (System Text, Area Text and and produce an error tone when pressed:
Location Text) require the use of a special text- • [B]
programming mode. In this mode, the keypad keys
• [On]
display different characters depending on the number
of times the keys are pressed. See Table 3. • [Off]
A character’s order in the character selection sequence • [Perimeter Only]
indicates the number of key presses necessary to • [No Entry]
produce the character. For example, pressing the [2]
key four times produces “a.” • [Bypass]
• [System Reset]
Table 3: Key/Character Assignments

Press [1] once to clear a character space


Key Character or to enter a blank space.
0 +-0*/\[]=><#§
1 Space . 1 ? ! , @ _ & ~ : ; " ( ) ' ¿ ¡ % £ $ ¥
3.1.5 Exit Programming Mode
2 ABCabc2ÅÄÃåäáàâãαβÇç
3 DEFdef3ÉÆëéèêæ∆Φδε Press and hold [#]. The LCD keypad displays the
4 GHIghI4ïíîìΓγηι control panel’s model number and firmware revision
5 JKLjkl5Λκλ
number on the top line, and “Please Wait...” on the
bottom line. This message remains for approximately
6 MNOmno6ÖöÑñØÕøóòôõΩµνω
10 sec.
7 PQRSpqrs7ΠΣπρσ
8 TUVtuv8ÜüúùûΘΥθτυ To reduce the occurrence of false alarms at
9 WXYZwxyz9ÿΞΨξχψζ power-up (or restoration of power after a
* Moves to the address before the text block. complete loss of primary and secondary
# Moves to the address after the text block. power) or upon exiting programming mode,
A Moves cursor to the previous character position in the control panel ignores all zone alarms for
text block. approximately 60 sec while the devices
C Moves cursor to the next character position in text stabilize.
block.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 8

4. Control Panel Programming


The contents of this section are organized as in Remote Programming Software (RPS).
This section covers all of the available programming parameters. The programming section in the
DS7200V2 Installer’s Guide (P/N: 4998153893) covers the programming parameters only available
when the control panel is in the Installer Programming Mode.

This section contains programming parameter information pertaining to the DS7240V2 and DS7220V2 Control
Panels. Settings for parameters are stored at one or more addresses. For an overview of how to program the
control panel from a DS7447E or DS7447V2 Text Keypad, see Keypad Programming on page 5.
Numbers enclosed in braces, (for example, {137}) that appear throughout this document refer to the control
panel’s event numbers. See Control Panel Events and Reporting Formats on page 138 for event descriptions.
The default Installer PIN is 9876. The default PIN for User 1 is 1234. All other user PINs are not programmed by
default. See Installer PIN on page 63 and PIN, User # on page 65 for more information.
4.1 Understanding the Parameter Option Charts
The programming section of this document uses charts like the one below to identify the available selections for
option parameters.
Enter This Data Digit to Select Options
Phone Line Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Phone Line Options •
Do Not Wait for Dial Tone • • • •
“R” Function/Three-way Calling • • • •
Reserved
Phone Line Fault Requires Reset • • • •
The first option usually disables or turns off all the other options.
The data digit values (labeled 0 to 15 under the “Enter This Data Digit to Select Options” heading) are displayed
across the top of the table. Each data digit is ties to options by a “•.” To select an option, enter the corresponding
data digit value at the address programming prompt.
The option parameter’s default selection is listed above the table in bulleted form along with the option’s address
and selection range. The numbered cell that corresponds with the option’s default setting is blackened to provide a
quick visual reference. For example, the cell labeled “10” in the example above is this option parameter’s default.
Columns that are grayed out are reserved settings and should not be selected.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 9

4.2 Panel Wide Parameters


4.2.1 Routing Destinations
The control panel has two routing destinations for the routing of reports. The control panel routes by zone and
report group to the destinations. For example, you can send alarm reports for one zone to Destination 1 and for
another zone to Destination 2.
You can program two phone numbers (or IP addresses) for each destination.

Communication Fail events are by destinations and not by phone number/IP address.

For a description of the routing/dialing process, see “Dialing Attempt Tables” in the DS7200V2 Installer’s Guide
(P/N: 4998153893).

Phone Number 1 (2) for Destination 1 (2))

• Address Range:
− Phone 1, Destination 1: 0000 to 0031
− Phone 2, Destination 1: 0032 to 0063
− Phone 1, Destination 2: 0066 to 0097
− Phone 2, Destination 2: 0098 to 0129
• Default: All zeroes (0)
• Selections: 0 to 14 (see Table 4)

Table 4: Phone Number Entry Selections

Digit to be Dialed Enter at Keypad Digit to be Dialed Enter at Keypad


1 1 9 9
2 2 0 10
3 3 * 11
4 4 # 12
5 5 P (4-sec pause) 13
6 6 F (on-hook, pause, off-hook) 14
7 7 Reserved 15
8 8 T (Terminate) 0

When entering phone numbers, enter “10” ([1][0] from the keypad) to dial “0”; enter “0” to terminate
the phone number. This does not apply when entering an IP address.

Terminate telephone numbers with less than 32 digits by entering a zero (0) in the Address after the
last digit to be dialed.

The control panel can dial up to 32 digits per phone number. Each digit occupies one address. If less than 32
digits are entered into the Phone Number Address range, the control panel dials digits until it reaches a terminator
(0).
IP addresses can be entered into these addresses for network communication. See Network Communication on page
129 for more information. Firmware revision 2.10 or greater is required for network communication.
See Area # Account Number on page 48 for instructions on entering an account number.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 10

Format for Destination 1 (2)

• Address:
− Format for Destination 1: 0064
− Format for Destination 2: 0130
• Default: 2 (Contact ID)
• Selections: 2 to 4, 7, 11
− 2 = Contact ID
− 3 = SIA 300
− 4 = Basic Pager
− 7 = Personal Dialing Format
− 11 = SIA 300 with Text Blocks
This parameter selects the reporting format. All reports for this destination are sent in the format chosen here.
If you configure the control panel for network communication, you must set this parameter to Contact ID. See
Network Communication on page 129 for more information. Firmware revision 2.10 or greater is required for
network communication.

Check communications from control panel to Alarm Receiving Center (ARC) to verify that the control
panel is communicating properly in the selected reporting format.

4.2.2 Reporting Format Configuration

Personal Dialing Format

Select the Personal Dialing Format by entering “7” into the appropriate reporting format address. See Format for
Destination 1 (2) on page 10 for more information. The control panel calls a phone number where a person is
expected to answer.
The control panel starts by placing a phone call. The control panel then sends the first digit of the report, waits
one second, and then sends the second digit of the report. The control panel then waits three sec, and sends the
report again. The control panel continues to repeat the report for a total of ten times. Some reports have zero as
the second digit. In these cases, only the first digit is sent, the control panel waits approximately three sec, and
then the report is repeated.
During the three-second delay between each report, pressing [5] on the phone’s keypad acknowledges the report.
The control panel advances to the next event in the dialer queue and sends it in the same phone call, or hangs up
if there are no more events to report. The control panel send each report up to ten times or until it is
acknowledged.
If no one acknowledges the report after ten tries, the control panel hangs up and calls again. If two phone
numbers are programmed for the destination, the second phone number is called. The control panel follows the
normal event phone routing. For each event, the control panel tries five times or until the event is acknowledged.
If no acknowledge is received in the five phone calls, the control panel logs a communication failure for the
destination.
The control panel divides all possible events into Event Groups as reported to RPS. This event group selects
which report to send. The event groups are numbered 1 to 16. The following table lists the 16 possible event
groups. Table 31 details all events generated by the control panel. Not all events are transmitted in Personal
Dialing Format.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 11

• Address: See Table 5


• Default: See Table 5
• Selections: 0 to 15

Table 5: Personal Dialing Format Configuration

Event Group Address Personal Dialing Format Code Data Digit Default
1 3414 Duress 0
2 3415 Fire Alarm 1
3 3416 Non-fire Alarm 2
4 3417 Reserved 0
5 3418 Fire Trouble 5
6 3419 Non-fire Trouble 6
7 3420 Fire Restoral 0
8 3421 Non-fire Restoral 0
9 3422 RF Trouble 0
10 3423 Open/Close 0
11 3424 Installer Mode 0
12 3425 System Fault 8
13 3426 Test Report 0
14 3427 Reserved 0
15 3428 Bypass 0
16 3429 Output/User 0
Use this parameter to select the tone for the 16 different Personal Dialing Format event groups.
For each event group, the report is programmed as a value from 0 to 15. If 0 (zero) is programmed, no report is
sent and the event is a Local Only event.
See Table 6 for the two-digit report tone when the value entered is non-zero (1to15).

Table 6: Report Tone Selections

Data Digit Selection Report Tone


0 None
1 10
2 11
3 20
4 12
5 21
6 30
7 13
8 22
9 31
10 40
11 14
12 23
13 32
14 41
15 50

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 12

For example, if Data Digit Selection “5” is entered, the following report tone is transmitted (“-“ equals 1 beep): -- -.
There is a 1-second pause between the transmission of the first digit and the second digit. The second digit is
followed by a 3-second pause.
The control panel repeats the report for a total of ten times (-- - -- - -- - -- - -- - -- - -- - -- - -- - -- -)

SIA 300 with Text Blocks

The control panel sends reports using the SIA format when “3” is entered into the appropriate reporting format
address. See Format for Destination 1 (2) on page 10 for more information. An additional format (selection of “11”)
is available to include ASCII text with the SIA event codes.
If the SIA event includes a zone number as one of its parameters, and the zone represents one of the control
panel’s 40 locations, the control panel sends the zone’s programmable location text (see Location ##, Zone Text on
page 86 for more information). The event (N) block is sent first followed by the text (A) block. If there is no zone
number for the event, then no ASCII text is reported.

Basic Pager Display

Setting a Routing Destination to Basic Pager format configures the control panel to send reports to a numeric
pager. Follow these steps to use the Basic Pager format:
1. Enter the phone number for the pager in the “Phone Number 1” parameter for the Routing Destination you
have chosen as the Basic Pager Destination.
2. Set the “Format for Destination 1 (2)” parameter to Basic Pager for the Routing Destination you have chosen
as the Basic Pager Destination.
Set the routing for any reports you would like sent to the pager to the Routing Destination (1 or 2) you have
chosen as the Basic Pager destination.
Report digits are dialed as 100-ms DTMF tone pulses with 100-ms pauses between the digits.
The control panel’s Basic Pager format does not wait for an acknowledgement tone from the pager
service provider to send its report to the pager. It dials the phone number, waits 250 ms and then sends
the report. To increase the delay (pause), add delay characters as needed to the end of the phone
number. See Table 4 on page 9 for the valid phone number entries.

All information the control panel needs to format and send events to a pager is contained in Phone Number 1 (2) for
Destination 1 (2) on page 9. Figure 1 shows the phone number broken into fields.

Figure 1: Routing Destination Phone Number Configured for Basic Pager

5 5 5 1 2 3 4 P P 0 * * * 0 # 9 0

1 2 3 2 4 2
1- Digits to Dial Field: Enter the phone number for the paging service followed by any special characters
required (a pause, for example). See Table 4 on page 9for phone number entries.
2- Field Terminator: Every field must end with the terminator digit, always 0 (zero).
3- Format Field: Use this field to configure how the message appears in the pager’s display. See Table 7 on
page 13 for Format Field options.
4- End Page Field: Enter the digits that tell your paging service you are done sending your page.
The control panel dials the number you enter in the Digits to Dial Field to contact the paging service. Add one
or more pauses at the end of the number to allow the paging service time to answer the phone and prepare to
accept the message. The Digits to Dial Field ends with a Field Terminator (0).
The Format Field follows the Digits to Dial Field. It defines what information follows the account number in the
paging message. The Format Field ends with a Field Terminator (0).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 13

The End Page Field follows the Format Field. The digits you enter in this field are sent after the paging
message. For many paging services, a ‘#’ indicates the end of the paging message. The End Page Field ends with
a Field Terminator (0).

You must enter the pauses required for the paging service in the Digits to Dial Field before the Digits
to Dial field terminator.
The number of pauses required varies based on the paging service.
Test the pager to determine that you entered enough pauses to establish communications to the
paging service.

Table 7: Format Field Options

Format Field Resulting Pager Display


Empty Account, Event, Area, and Zone Numbers 1234-008-03-21
with separator characters
# Account, Event, Area, and Zone Numbers 12340080321
without separator characters
*** Account, Event, and Area Numbers with 1234-008-03
separator characters
#*** Account, Event, and Area Numbers without 123400803
separator characters
** Account and Event Numbers with separator 1234-008
characters
#** Account and Event Numbers without 1234008
separator characters
* Account Number only 1234

If the zone/user number is three digits, the leading digit is omitted. For example, “252” displays as
“52.”
Do not use alpha characters for the account number in basic pager format.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 14

4.2.3 Phone, Auto-Forward, and RPS Configuration

Integral Voice Verification Module

• Address: 0065
• Default: 0
• Selections:
− 0 = Disable Voice Verification
− 1 to 15 = Enable the Voice Verification Module and identify which output is the Voice Request output in
Area 1
This parameter enables the voice verification module. Program one of the first 15 outputs as Output Function
Type 2|10 “Voice Request.” Enter that output number (1 to 15) in this parameter. See Function, Output ## on page
112 for more information.

Set this address to 0 if the integral voice verification module is not installed.

Phone Line Options

• Address: 0131
• Default: 0
• Selections: 0 to 3, 8 to 11
Enter This Data Digit to Select Options
Phone Line Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Phone Line Options •
Do Not Wait for Dial Tone • • • •
“R” Function/Three-way Calling • • • •
Reserved
Phone Line Fault Requires Reset • • • •
This parameter consists of three options for the physical phone line.
• Do Not Wait for Dial Tone: If this option is enabled, the control panel waits three sec after going off-hook
and then starts dialing. If this option is disabled, the control panel waits up to seven sec for a dial tone. The
control panel dials when it detects the dial tone.
• “R” Function/Three-way Calling: If this option is enabled, the control panel’s “R” function/three-way
calling feature is enabled. The phone company must enable this option on the control panel’s telephone line.
• Phone Line Fault Requires Reset: If this option is enabled and a phone line fault occurs, the trouble
condition (keypad trouble message and/or tone) continues until the [System Reset] key is pressed (fix the
phone line fault first). If this option is not disabled and a phone line fault occurs, the trouble condition clears
automatically when the phone line fault is corrected. This option also applies to the Alternate Communication
Path Fault Control Input (see Options 1 for Zone Function Type 3 (24-hr Control Input) on page 97).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 15

DTMF/Pulse Dialing

• Address: 0132
• Default: 0 (DTMF)
• Selections:
− 0 = DTMF
− 1 = Pulse
This parameter selects the control panel dialing format (DTMF or Pulse). This format is used for all dialing
attempts.

Call Forwarding Auto On/Off Digits

• Address:
− Call Forwarding Auto On Digits: 0133 to 0164
− Call Forwarding Auto Off Digits: 0165 to 0180
• Default: All zeroes (0)
• Selections: See Table 4 on page 9
− Call Forwarding Auto On Digits: Up to 32 characters max
− Call Forwarding Auto Off Digits: Up to 16 characters max
This parameter configures the control panel’s Call Forwarding Auto On/Off operation.

In order to use this parameter, the premises must have Call Forwarding service from the local
telephone company. Call Forwarding Auto On/Off does not forward calls; it turns the telephone
company’s Call Forwarding service on or off by dialing digits just as the user would.
When entering phone numbers, use “10” ([1][0] from the keypad) to enter “0”; use “0” to terminate the
phone number.
Call Forwarding Auto On/Off is only available for Area 1.

If Call Forwarding Auto On/Off is enabled ([#][8][2]) and a user turns the system All On, the control panel dials
the Call Forwarding Auto On digits to activate the telephone company’s Call Forwarding service.
If Call Forwarding Auto On/Off is enabled ([#][8][2]) and a user turns the system off (from All On), the control
panel dials the Call Forwarding Auto Off digits to turn off the Call Forwarding service.
• A typical dialing sequence might be:
• Two-digit telephone company code (*21*)
• Pause
• Phone number to forward to (Example: 555-1212)
• Flash (on-hook, pause, off-hook)
• Terminate (t)
For this sequence, the entry at this parameter is *2 1 * p 5 5 5 1 2 1 2 f t.
See the DS7200V2 User’s Guide (P/N: 4998153894) for more information on Call Forwarding Auto On/Off.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 16

Remote Programming Call Back Number

• Address: 0181 to 0212


• Default: All zeroes (0)
• Selections: See Table 4 on page 9
The control panel dials this phone number (or IP address) to begin a RPS remote programming session. See
Network Communication on page 129 for complete network communication programming instructions. Firmware
revision 2.10 or greater is required for network communication.
There are three ways to use this phone number (or IP address):
1. RPS calls the control panel, which answers and determines it is RPS calling, then it disconnects and calls
RPS back.
2. When a user presses [#][4][3], the control panel calls RPS using the phone number (or IP address) entered
here.
3. The control panel can be programmed to use this phone number (or IP address) automatically at test
report time (see Automatic Test {137} Report Options on page 31 for more information).

When entering phone numbers, enter “10” ([1][0] from the keypad) to dial “0”; enter “0” to terminate
the phone number. This does not apply when entering an IP address.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 17

RPS Answer Ring Count, Answering Machine Bypass

• Address: 0213
• Default: 7 (rings)
• Selections:
− 0 = Control panel does not answer phone
− 1 to 13 = Ring Count
− 14 = Answering Machine Bypass 1
− 15 = Answering Machine Bypass 2
The ring count sets the number of rings the control panel waits before picking up and seizing the phone line for a
remote programming session, or for remote arming with a telephone (see Arming Options 1 on page 37).
The control panel does not answer the phone for remote programming or remote arming with telephone when
this parameter is set to zero (0).
This ring count is used for any control panel arming state, armed or disarmed.
The Answering Machine Bypass function can be restricted to only operate when the system is armed All On or
Perimeter Only (see Arming Options 1 on page 37). When the Answering Machine Bypass function is restricted to
only operate when the system is armed All On or Perimeter Only, the control panel does not answer the phone
for a remote arming session when it is disarmed (Off). However, [#][4][3] still initiates a remote programming
session.
Answering Machine Bypass 1
1. Call the premises; let the phone ring no more than two (2) times. Then hang up/disconnect the remote
programmer.
2. Wait at least eight sec to call back, but call back within 45 sec.
3. The control panel then picks up after the first ring.
Answering Machine Bypass 2
1. Call the premises; let the phone ring no more than four (4) times. Then hang up/disconnect the remote
programmer.
2. Wait at least eight sec to call back, but call back within 45 sec.
3. The control panel then picks up after the first ring.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 18

Phone Line Fault Response Options

• Address: 0220
• Default: 0
• Selections: 0, 1, 3, 5, 7
Enter This Data Digit to Select Options
Phone Line Fault Response Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Phone Line Supervision •
Enable Supervision (System Trouble at Keypad) • • • •
Burg Alarm & Strobe Functions, All On/Perimeter
• •
Only
Burg Alarm & Strobe Functions, Off • •
Reserved

The control panel monitors the phone line for voltage only. If the voltage drops low enough (between 1 and 3 V)
for 40 sec, it declares a phone line fault. If the phone line voltage remains above 3 V for at least 40 sec, it declares
the phone line restored. See the ”Phone Line Fault Requires Reset” option in Phone Line Options on page 14.
When enabled, the Phone Line Fault event appears at all keypads for all areas. The control panel sends a Phone
Line Restore {100} report when a phone line fault event restores.
If the phone line fails (as described above), but restores before a Comm Fail event:
1. System detects phone line fail and puts Event {99} in the log.
2. System starts dialing attempts if programmed for Phone Fail report.
3. Phone line restores before Comm fail event.
4. System sends phone line fail and phone line restore reports.
If the phone line fails (as described above), but restores after a Comm Fail event:
1. System detects phone line fail and puts report in the event in the log.
2. System starts dialing attempts if programmed for Phone Fail report.
3. Dialing attempts end with Comm fail event, phone fail report is flushed.
4. System detects phone line is restored and puts restoral report in buffer.
5. System starts dialing attempts and sends phone fail restoral and Comm restoral reports.
If an alternate communication path is enabled, the control panel can send a Phone Line Fail {99} report via the
alternate communication path when a phone line fault event occurs.
• No Phone Line Supervision: If this option is enabled, the control panel does not monitor the phone line
voltage. Phone Line Fault events do not appear at keypads. The other Phone Line Fault Response options are
also disabled if No Phone Line Supervision is selected.
• Enable Supervision (System Trouble at Keypad): If this option is enabled, the keypad displays a phone
line trouble message if a phone line fault occurs as described above. To enable the keypad to sound a trouble
tone on system troubles, see Keypad # Options on page 67 for details.
• Burg Alarm & Strobe Functions, All On or Perimeter Only: If this option is enabled, the system’s burglary
alarm and strobe function as configured when the system is armed All On or Perimeter Only if a phone line
fault occurs as described above. See Output Parameters on page 107 for burglary alarm/strobe output
configuration.
• Burg Alarm & Strobe Functions, Off: If this option is enabled, the system’s burglary alarm and strobe
function as configured when the system is off (not armed) if a phone line fault occurs as described above. See
Output Parameters on page 107 for burglary alarm/strobe output configuration.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 19

4.2.4 Global Reporting Options


These parameters configure the reporting for all areas, all zones, and all users.

Global Reporting Options

• Address: 0221
• Default: 1
• Selections: 0, 1, 3, 5, 7, 9, 11, 13, 15
Enter This Data Digit to Select Options
Global Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Local Only •
Enable Reporting • • • • • • • •
Extend Handshake • • • •
Delay Alarm Output • • • •
Burg Alarm after Two Failed Attempts • • • •

• Local Only: The control panel sends no reports.


• Enable Reporting: If this option is enabled, the control panel sends reports as programmed provided that at
least one phone number (or IP address) has been programmed for at least one Routing Destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9). Reporting options can be enabled and disabled in other
parameters. See Open/Close Reporting Options on page 39, and Area # Opening {89-96}/Closing {42-67} Reporting
Options on page 49 for more information.
• Extend Handshake: If this option is enabled, the control panel finishes dialing the ARC receiver and waits
for a ‘handshake’ tone from the receiver. The handshake is the first thing the receiver sends after answering
the phone. Typically each reporting format the receiver supports has its own handshake tone. If a receiver
supports several formats, it sounds the handshake tones one at time. Choosing this option extends the time the
control panel waits for a handshake from the ARC receiver from 45 to 60 sec.

Do not change the Extend Handshake option unless advised by Bosch Technical Service.

• Delay Alarm Output: If this option is enabled, the control panel delays burglary alarm output until
communication to the ARC receiver is complete or there are two failed dialing attempts. The delayed alarm
output functions are 1|8, 1|9 and 1|10 (see Table 25 on page 112 for descriptions of output function types). Bell
Time is not delayed, and begins at the alarm event. If Bell Time is set at three min. or less, alarm output
delayed by this option may be very short (less than 1 minute), or the alarm output may not activate at all. See
Output Parameters on page 107 for a complete description of output functions. The keypad sounder is not
delayed by this option.

Disable the Alarm Event Abort option when using the Delay Alarm Output option. See Options 1, Zone
Function ## on page 95.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 20

• Burg Alarm After Two Failed Attempts: If this option is enabled, a steady alarm output sounds after two
failed attempts to transmit a burglary alarm report from any zone when its area is armed. Alarm output is
provided even if the zone is not programmed for alarm output. Program Bell Time to at least 3 min. when
using this option. Disable this option if you want to prevent an alarm output from silent zones even when the
system fails to communicate with the receiver. This option only applies to the following output function types:
− 1|8 Alarm: All On, Perimeter Only, and Partial On (Non-Fire 24-hr alarms)
− 1|9 Alarm: Perimeter Only and Partial On Modes (Non-Fire 24-hr alarms)
− 1|10 Alarm: Controlled Zones and 24-hr Zones (Fire and Non-Fire)
See Output Parameters on page 107 for alarm configuration.

The burg alarm output activates after two failed communication attempts even if the zone is set for
silent operation.

Ack Wait Time

• Address: 0222
• Default: 5 (5 sec)
• Selections:
− 0 = 1 second
− 1 to 15 = 1 to 15 sec (1-second increments)
This parameter sets the amount of time the control panel waits for an acknowledgment tone from the ARC
receiver.

Do not change the default value unless advised by Bosch Technical Service.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 21

AC Power Supervision Options

• Address: 0223
• Default: 4
• Selections: 0 to 15
Enter This Data Digit to Select Options
AC Power Supervision Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
AC Fail Report is Tag-along • • • • • • • •
Disable AC Fail Local Annunciation (at keypad) • • • • • • • •
Enable Arm/Disarm/Bypass Tracking • • • • • • • •
Enable Internal Crystal to Keep Time • • • • • • • •
This parameter configures the control panel’s local response to AC power failure.
AC power must be failed for a maximum of 10 sec before the control panel responds to the failure. It must be
restored for a maximum of 10 sec before the control panel responds to the AC restoral. See AC Fail Report Delay
on page 34 for instructions on delaying the AC Fail Report.

The trouble tone for AC fail events sounds at all keypads in all areas. However, the trouble tone must be
silenced in each area. Silencing the trouble tone in one area does not silence it in the other areas.

• AC Tag-along: If this option is enabled, AC Fail and Restoral reports are not sent at the time of the event,
but are sent as ‘tag-along’ reports with the next report to be sent.
• Disable AC Fail Local Annunciation (at Keypad): If the control panel is only powered from a DC power
source (through battery connections), select Option 2, “Disable AC Fail Local Annunciation.” This prevents
the control panel from annunciating AC failures locally at the keypad. You must also disable AC Fail
reporting at the next parameter, “AC Fail, Low Battery Report Options.”
• Enable Arm/Disarm/Bypass Tracking: If If this option is not enabled, the control panel always powers up
in the disarmed state (Off), even if the control panel was armed before powering down. Zones that were
bypassed before powering down are not bypassed at power-up.
• Enable Internal Crystal to Keep Time: Not enabling this option keeps time by looking at the Mains AC
power. Enable this option if running on DC only (for example, if you are generating your own power or
power cycles are not consistent), otherwise leave set to default.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 22

AC Fail {1}/Low Battery {22} Report Options

• Address: 0224
• Default: 7
• Selections: 0 to 15
Enter This Data Digit to Select Options
AC Fail, Low Battery Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No AC Fail Reports, No Low Battery Reports •
AC Fail Reports • • • • • • • •
AC Restoral Reports • • • • • • • •
Low & Missing Battery and Restoral Reports • • • • • • • •
Ground Fault and Restoral Reports • • • • • • • •
AC Fail, Low Battery and Ground Fault events occur at all keypads for all areas. This parameter enables reporting
of AC power and battery supervision events, and ground fault events.

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).

The battery is considered low if the nominal voltage on its terminals drops below 12.1 V. The low battery is
considered missing if the nominal voltage on its terminals drops below 10.2 V.

System Status Report Swinger Count

• Address: 0225
• Default: 0 (Disabled)
• Selections:
− 0 = Disabled
− 1 to 15
Set this parameter to zero (0) to disable the System Status Report Swinger. System Status reports are sent as they
occur.
Entering a value from 1 to 15 enables System Status Report Swinger and sets the swinger count. Each system
status report has its own swinger counter. When the count is reached that report is no longer transmitted during
the arming cycle.
For example, if you entered 1 at this parameter, the control panel would only transmit one AC fail report, no
matter how many times AC failed and restored during the arming cycle.
Not all System Status Reports follow this Swinger Count. System Status reports that follow the count set in this
parameter are marked with an “S” in Table 31 (see page 138).
To reset the System Status Report Swinger Count, arm and then disarm the control panel.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 23

System Status Report Routing

• Address: 0226
• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
System Status reports routed by this parameter are marked with an “R” in Control Panel Events and Reporting
Formats on page 138.
Comm Fail 1 (2) reports follow System Status Reports routing. Comm Fail reports for either destination are only
sent if the other destination is the System Status Reports destination. See “Communication Failure (Comm Fail)”
for a description of the Comm Fail event, and “Dialing Attempt Tables” for the dialing sequence in the DS7200V2
Installer’s Guide (P/N: 4998153893).

Call for Service Interval

• Address: 0227, 0228


• Default: 0,0
• Selections: 00 to 99
This parameter determines the interval in weeks (7 days), (00 to 99). For example, if you enter 0,2, the control
panel waits 2 weeks (14 days) between displaying service messages.
At this interval, the keypad displays a “Call for Service” fault and/or sends a Call for Service {37} report (per the
Call for Service/System Inactive Options parameter). The display appears at all keypads in all areas. The report is sent
for Area 1 only and follows System Status Report routing.
Press [System Reset] to reset the fault in the area to which the keypad is assigned. Enter 0,0 to disable this
parameter.

System Inactive Interval

• Address: 0229, 0230


• Default: 0,0
• Selections: 00 to 99
If an area is not armed (All, Perimeter Only or Partial On) in this interval, the control panel sends a System
Inactive {136} Report for that area. A ‘System Inactive’ Display is optional, see Call for Service/System Inactive
Options on page 24 for more information.
The interval is in weeks (00 to 99). Enter 0,0 to disable this parameter.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 24

Call for Service/System Inactive Options

• Address: 0231
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Call for Service/System Inactive Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options •
Call for Service Display at Call for Service
• • • • • • • •
Interval
Call for Service Report at Call for Service
• • • • • • • •
Interval
Call for Service Display at System Inactive
• • • • • • • •
Interval
Enable Weekly Test Reminder • • • • • • • •

• Call for Service Display at Call for Service Interval: If this option is enabled, the keypad displays a “Call
for service” trouble at all keypads in all areas and/or sends a report for Area 1 at the Call for Service Interval.
Press the [System Reset] key to reset the fault in the area to which the keypad is assigned. There is no trouble
tone for the Call for Service Interval event.
• Call for Service Report at Call for Service Interval: If this option is enabled, the Call for Service {37}
Report follows System Status routing. The interval is in weeks (00 to 99). See Call for Service Interval on page
23.
• Call for Service Display at System Inactive Interval: If this option is enabled, the keypad displays a “Call
for Service” trouble at all keypads and/or sends a System Inactive {136} report for that area at the System
Inactive Interval. See System Inactive Interval on page 23.
• Enable Weekly Test Reminder: If this option is enabled, the system keypads display “System Test due,
Press 1 to test.” A reminder is generated eight (8) days after the last user test. There is no trouble tone for this
trouble reminder event. When the user presses [#][4] to view the trouble, the system displays “System Test
due, Press 1 to test.”

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 25

Log Supervision Configuration

• Address: 0232
• Default: 0 (No Log Threshold Events or Reports, No Log Overflow Events or Reports)
• Selections:
− 0 = No Log Threshold Events or Reports, No Log Overflow Events or Reports
− 1 = Overflow Event & Report {84}; Threshold Event & Report {85} at 50% full
− 2 = Overflow Event & Report {84}; Threshold Event & Report {85} at 75% full
− 3 = Overflow Event & Report {84}; Threshold Event & Report {85} at 90% full
− 4 = Overflow Event; Threshold Event at 50% full; Local Events, No Reports
− 5 = Overflow Event; Threshold Event at 75% full; Local Events, No Reports
− 6 = Overflow Event; Threshold Event at 90% full; Local Events, No Reports
The control panel can store up to 254 events in its event log (history). On startup, all of a new control panel’s log
is available for storing events. As the control panel begins storing events, the capacity for new events is reduced.
When Event 254 is stored, the control panel is 100% full. On the 255th event, it begins overwriting events
(beginning with the oldest).
RPS Remote Programming Software can access the control panel’s log. The history pointer can be reset and the
number of events in the history log would be set to 0 (zero).
To help avoid overwriting events that have not been received by RPS, this parameter configures the system for
supervision of its event log (history).
Setting this parameter to 0 disables supervision. No log threshold or overflow events are entered in the log. No log
reports are sent.
Setting this parameter to 1, 2, or 3 creates log overflow and threshold events in the log. A threshold event is
created when the control panel writes the first event to the log that exceeds the threshold (50%, 75%, or 90% full).
A threshold report reminds the ARC to access the event log with RPS, freeing log space, before the control panel
reaches 100% full (log overflow) and begins overwriting events.
If this parameter is set to 75% threshold, the threshold event reoccurs when 191 new events have occurred since
the last history pointer reset.
Overflow events are created when the log reaches 100% of capacity and begins writing over events that have not
been received by RPS.
Setting this parameter to 4, 5, or 6 creates the threshold and overflow events, but no reports are sent. The events
are local only.
Only log events (threshold and overflow) ever appear in the log. They are not system troubles. They are viewed
by pressing [#][8][5], or remotely with RPS.

Resetting the history pointer does not clear any events. The most recent 254 events are always
available.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 26

Auto On Alert Time

• Address: 0233
• Default: 3 (15 min.)
• Selections: 0 to 15 (Time = Selection x 5 min.)
Multiply the value entered in this parameter by five (5) min. to determine the duration of the Auto On Alert. The
alert sounds before the Auto On Sked to warn users to exit or extend ([#][5][1]) the auto arming.
At the Auto On time, the control panel starts exit delay. See Sked Parameters on page 120 for a complete
description of the Auto On Skeds.
If the area is armed according to the scheduled arming state (All On or Perimeter Only) during Auto On Alert
Time and then disarmed before the scheduled arming, auto arming does not occur.

Cancel Event Enabled

• Address: 0234
• Default: 0 (No Cancel Reports)
• Selections:
− 0 = No Cancel Reports
− 1 = Cancel Reports Enabled
If the Cancel Event is enabled (enter Data Digit 1 at Address 0234), a ‘Cancel Window’ starts with the initiation of
alarm events. The Cancel Window is equal to Bell Time. If the user acknowledges the alarm inside the cancel
window, a Cancel Event is created. If reporting is enabled, a Cancel {38} or Fire Cancel {39} report is sent.
If the Abort Window is enabled, the Cancel report is not sent if the user acknowledges the alarm before the Abort
Window expires. See Alarm Event Abort Window on page 106 for more information.

Call for Service Text

• Address: 1266 to 1297


• Default: Blank
• Selections: See Table 3 on page 7
All control panel text is programmed from the text keypad in a special text-programming mode. See Text Entry
Addresses on page 7 for text programming instructions.
This parameter provides 16 characters of programmable text to be displayed in the second line of the display
whenever the first line shows “Call for Service.” It is also displayed when the keypad is extinguished and the
“Extinguish Mode Displays Date” option is enabled. See Keypad Response Options on page 70 for information on the
Extinguish Mode options.
The following are possible entries for the second line of text:
• ARC phone number.
• Preferred phone number called for service.
• “Press 0 to view.” This tells users which key to press to see system trouble details. See “Call for Service Details”
in the DS7200V2 Installer’s Guide (P/N: 4998153893).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 27

Tamper Alarm/Trouble Options


• Address: 3406
• Default: 13
• Selections: 0 to 7, 12 to 15
Enter This Data Digit to Select Options
Tamper Alarm/Trouble Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Tamper Alarms, no Trouble or Restoral

Reports
Tamper Alarm when Armed • • • • • •
Tamper Alarm when Disarmed • • • • • •
Send Tamper Trouble Reports • • • • • • • •
Send Tamper Trouble Restoral Reports • • • •
This parameter configures the control panel’s response when tamper alarms occur, and whether tamper trouble
and tamper trouble restoral reports are sent. This is a global parameter that applies to both zone and non-zone
tampers, system tampers, and device tampers. It does not include user tampers.
• Tamper Alarm when Armed: If this option is enabled, a tamper condition that occurs when the control
panel is armed creates a tamper alarm response. If this option is disabled, a tamper condition that occurs
when the control panel is armed creates a tamper trouble condition.
When the control panel is armed Perimeter Only or Part On, only some of the controlled zones can create an
alarm. If this option is selected and the zone that is tampered is a Perimeter Only or Part On zone, a tamper
alarm is created. If the zone is not a Perimeter Only or Part On zone, the tamper response depends on the
setting made for the next option (Tamper Alarm when Disarmed). The non-zone tampers are always included
in the Perimeter Only or Part On zones and creates a tamper alarm if tampered.
• Tamper Alarm when Disarmed: If this option is enabled, a tamper condition that occurs when the control
panel is disarmed creates a tamper alarm response. If this option is disabled, a tamper condition that occurs
when the control panel is disarmed creates a tamper trouble condition.
If the control panel is armed Perimeter Only or Part On, the zones that are excluded from the controlled
zones respond to the tamper condition as defined by the setting of this option.
• Send Tamper Trouble Reports: If this option is enabled, a tamper report {3} is sent to the ARC when a
tamper trouble (not alarm) occurs. If this option is disabled, no report is sent.
• Send Tamper Trouble Restoral Reports: If this option is enabled, a tamper restoral report {112} is sent to
the ARC when a tamper trouble restores. If this option is disabled, no report is sent.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 28

System Alarm Reports/Output Options

• Address: 3407
• Default: 7
• Selections: 0 to 7
Enter This Data Digit to Select Options
System Alarm Reports/Output Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No System Tamper Alarm Reports, No Output •
Send System Tamper Alarm Reports • • • •
Send System Tamper Alarm Restoral Reports • •
Enable System Tamper Alarm Output • • •
Reserved

This parameter determines whether tamper alarm and alarm restoral reports are sent, and if the alarm output
operates on a tamper alarm. This parameter only applies to non-zone tampers.
• Send System Tamper Alarm Reports: If enabled, this option sends an alarm report, such as Data Bus
Device Tamper {189} alarm, to the ARC when a non-zone related tamper alarm is generated. Other non-zone
tamper alarms include Data Bus Missing Alarm {187}, Data Bus Trouble Alarm {191}, and Siren Missing
Alarm {193}.
• Send System Tamper Alarm Restoral Reports: If enabled, this option sends an alarm restoral report, such
as Data Bus Device Tamper {190} restoral, to the ARC when a non-zone related tamper condition is restored.
Other non-zone tamper alarm restorals include Data Bus Missing Alarm Restoral {188}, Data Bus Trouble
Alarm Restoral {192}, and Siren Missing Alarm Restoral {194}.
• Enable System Tamper Alarm Output: If enabled, this option activates the alarm output when a non-zone
related tamper alarm, such as Data Bus Device Tamper alarm, is generated. Other non-zone tamper alarms
include Data Bus Missing {187}, Data Bus Trouble Alarm {191}, and Siren Missing Alarm {193}.
4.2.5 Tests

System Test Configuration Options

• Address: 0244
• Default: 5
• Selections: 0 to 15
Enter This Data Digit to Select Options
System Test Configuration Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
System Test Disabled •
Test Bell • • • • • • • •
Test Strobe • • • • • • • •
Test Battery • • • • • • • •
Send Test Report • • • • • • • •
This is a global (affects all areas) option.
When the user enters the System Test key sequence ([#][4][1]) at the keypad, the system performs a self-test that
includes the options selected at this parameter. The configuration applies to all areas.
• Test Bell: If enabled, this option makes a “bell test” part of the system test. The control panel activates the
Bell Time (1|5) and Alarm Output (1|8, 1|9, 1|10, 1|11, 1|12, and 8|8) functions for three sec. See Output
Parameters on page 107 for a complete description of output functions.
• Test Strobe: If enabled, this option makes a “strobe test” part of the system test. The control panel activates
the Strobe Output function (1|6) and waits for the user to press [*] to end the test.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 29

• Test Battery: If enabled, this option makes the “battery test” part of the system test. The battery test causes
the system to run on battery power only for four min. If the battery voltage falls below 12.1 V during the four-
min. test, or if the battery is missing, the system restores AC power and displays a system trouble at all
keypads. If programmed for battery reports, the control panel sends a low battery or missing battery report.
Press [#] to end the test.
• Send Test Report: If enabled, this option makes a “communications test” part of the system test. If selected,
this option causes the control panel to attempt to send a Test {137} report when the user initiates a System
Test ([#][4][1]). If there is a system trouble present at the time of the test, the control panel sends a Test, Off
Normal {138} report. The test report follows the routing for Test Report Routing (Address 0255). If the test
communication is unsuccessful, the control panel creates a system trouble communication failure.

System Test Enable Options

• Address: 0245
• Default:
− DS7240V2: 15
− DS7220V2: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
System Test Enable Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
System Test Disabled •
Enable System Test for Area 1 • • • • • • • •
Enable System Test for Area 2 • • • • • • • •
Enable System Test for Area 3 (DS7240V2 only) • • • • • • • •
Enable System Test for Area 4 (DS7240V2 only) • • • • • • • • •
This option enables the System Test function ([#][4][1]) for each of the areas. Although the configuration of
System Test is global, the function is only enabled for keypads in the areas selected here, and only for users with
the proper authority level. See Authority Level Option 9: System Functions 1 on page 57 for more information.

If the System Test is not enabled in the previous parameter (Address 0244 is set to Data Digit 0), then
this parameter is not functional and does not need to be programmed.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 30

Walk Test Configuration Options

• Address: 0246
• Default: 8
• Selections: 0 to 15
Enter This Data Digit to Select Options
Walk Test Configuration Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Walk Test Disabled •
Start with System Test • • • • • • • •
Include Fire Zones • • • • • • • •
Include 24-hour Zones • • • • • • • •
Include Controlled Zones • • • • • • • •
When a user enters the Walk Test key sequence ([#][4][4]) at a keypad to start a walk test, the system includes the
option(s) selected in this parameter. If included, the “Start with System Test” option follows its own configuration.
See System Test Configuration Options on page 28 and System Test Enable Options on page 29. No reports are sent from
zones included in the test.

If a Zone Function type is not included, those zones remain active during the test.

A Walk Test Start {158} report, with user number, is sent at the start of the test. A Walk Test End {159} report,
with User Number 0 (zero), is sent at its conclusion.
Entering Walk Test mode starts a 20-minute timer. After 15 min. with no activity from the included zones, a
warning tone (same as Auto-arm warning) begins. After 20 min., the test automatically terminates with User
Number 0 (zero).

Any fire or 24-hour zone faulted at the termination of the test generates a trouble response, not an alarm
response. If programmed for alarm reports but not trouble reports, trouble reports are sent as part of the
trouble response only in this instance.

Walk Test Enable Options

• Address: 0247
• Default:
− DS7240V2: 15
− DS7220V2: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Walk Test Enable Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Walk Test Disabled •
Walk Test Enabled for Area 1 • • • • • • • •
Walk Test Enabled for Area 2 • • • • • • • •
Walk Test Enabled for Area 3 (DS7240V2 only) • • • • • • • •
Walk Test Enabled for Area 4 (DS7240V2 only) • • • • • • • • •
Use this parameter to choose which areas have the Walk Test function ([#][4][4]) enabled. Although the
configuration of Walk Test is global, the function is only enabled for keypads in the areas selected here, and only
for users with the proper authority level. See Authority Level Option 9: System Functions 1 on page 57 for more
information.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 31

Walk Test Start/End Report Routing

• Address: 0248
• Default: 5 (No reports, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
This is a global (affects all areas) parameter. See “Communication Failure (Comm Fail)” for a description of the
Comm Fail event , and “Dialing Attempt Tables” for the dialing sequence in the DS7200V2 Installer’s Guide
(P/N: 4998153893).

Automatic Test {137} Report Options

• Address: 0249
• Default: 0
• Selections: 0 to 4, 8 to 12
Enter This Data Digit to Select Options
Automatic Test Report Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Automatic Test Report Options •
Test Report Only if System is Armed • • • •
Defer Test Report if Other Report Sent in Test
• • • •
Interval
Test Reports for All Areas (else Area 1 only) • •
Call RPS at Test Time (after Test Report) • • • • •
Use these options to configure the Automatic Test {137} report. If “Call RPS at Test Time” is enabled, a variety of
tasks could be accomplished at this time, including downloading the log to RPS.
• Test Report Only if System is Armed: This option sends a test report only if the system is armed.
• Defer Test Report if Other Report Sent in Test Interval: If another report is sent during the test interval,
this option defers the test report until the end of the test interval.
• Test Reports for All Areas (else Area 1 only): If selected, this option generates a test report for all enabled
areas. For the DS7240V2, this option applies to Areas 1 through 4. For the DS7220V2, this option applies to
Areas 1 and 2.
• Call RPS at Test Time (After Test Report): If selected, this option calls RPS at test time after the system
sends the test report. The Remote Programming Call Back Phone Number should be programmed. See
Remote Programming Call Back Number on page 16 for more information.

Automatic Test {137} Report Time

• Address: 0250 to 0253


• Default: 0000 (Test reports disabled)
• Selections: 0 to 9
Enter the time of day for the Automatic Test. Use 24-hour format (HHMM) where midnight is 2400, noon is 1200
and 12:01 am is 0001. Enter one digit in each address so that Addresses 0250 and 0251 are the hour, and 0252
and 0253 are the minute. An entry of 0000 (the default setting) disables the Automatic Test {137} report.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 32

Automatic Test {137} Report Interval

• Address: 0254
• Default: 3 (7 Days)
• Selections:
− 0 = No Automatic Test
− 1=1H
− 2 = 1 Day
− 3 = 7 Days
− 4 = 28 Days
Enter zero (0) to disable Automatic Test {137} reporting.
The one-hour interval is incremented on the minute. For example, if you set the Automatic Test Time parameter
to 1020 (10:20 am), the Automatic Test Interval is one hour, and left programming mode at 11:10, then the
control panel sends a test report at 11:20 am (less than one hour after leaving programming mode). The next test
report would come at 12:20 pm.
The one-day, seven-day and 28-day intervals are incremented at midnight (2400). For example, if you set the
Automatic Test Time parameter to 1020 (10:20 am), the Automatic Test Interval is one day, and left programming
mode at 10:10 am, then the control panel does not send a test report until 10:20 the next day (after the one-day
interval increment at midnight).

Test Report Routing

• Address: 0255
• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
This is a global (affects all areas) parameter.
Test reports include the System Test {137}/{138} reports. The Walk Test Start {158} and Walk Test End {159}
reports follow their own routing.

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 33

4.2.6 Programming Options

Date Format and Enable PIN Trouble

• Address: 0235
• Default: 1
• Selections: 0 to 3
Enter This Data Digit to Select Options
Date Format & Enable PIN Trouble Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
MM/DD/YY Date Display • •
DD/MM/YY Date Display • •
Enable Default PIN Trouble • •
Reserved
Reserved

This parameter controls the display of the date on the keypad and logged on the printer.
This parameter can also enable the System Trouble event that is generated if the default values for the Installer
PIN and User PIN are left unchanged. See Installer PIN, on page 63, and PIN, User #, on page 65, for more
information.

If the default Installer PIN or the default User 1 PIN is changed using RPS remote programming, reset
the control panel at the end of the remote programming session.

Set this parameter to 1 (default) to do the following:


• Use DD/MM/YY date format
• Disable the system trouble message if the Installer PIN and User PIN defaults are not changed

Daylight Saving Time Calendar

• Address: 0236
• Default: 2 (European DST Calendar)
• Selections:
− 0 = No Options selected
− 1 = Australian DST Calendar
− 2 = European DST Calendar
− 3 = United States DST Calendar
This parameter determines the appropriate calendar for daylight saving adjustments.
• Australian DST Calendar: This option moves the clock ahead on the last Sunday in October and moves the
clock back on the last Sunday in March.
• European DST Calendar: This option moves the clock ahead on the last Sunday in March and moves the
clock back on the last Sunday in October.
• United States DST Calendar: This option moves the clock ahead on the first Sunday in April and moves the
clock back on the last Sunday in October.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 34

Daylight Saving Clock Advance Time

• Address: 0238, 0239


• Default: 0,2 (02:00 AM)
• Selections: 0 to 22
Addresses 0238 and 0239 select the hour that the clock is advanced.
Address 0238 holds the tens digit of the hour and Address 0239 holds the ones digit of the hour. When the local
time of the control panel matches the value entered in Addresses 0238 and 0239, an hour is added to the time. To
advance the clock at midnight when the day changes from Saturday to Sunday, enter a 0 (zero) in Addresses 0238
and 0239.

Daylight Saving Clock Reverse Time

• Address: 0240, 0241


• Default: 0,3 (03:00 AM)
• Selections: 1 to 23
Addresses 0240 and 0241 select the hour that the clock is reversed.
Address 0240 holds the tens digit of the hour and Address 0241 holds the ones digit of the hour. When the local
time of the control panel matches the value entered in Addresses 0240 and 0241, an hour is subtracted from the
time.

AC Fail Report Delay

• Address: 0242, 0243


• Default: 7, 8 (120 min.)
• Selections: 0,0 to 15,15 (0 to 255 min.)
This parameter sets the number of min. (0-255) the control panel waits before sending an AC Failure report when
an AC Failure is detected. If this parameter is set to 0 (zero), there is no delay and the report is sent immediately.
If the AC Failure condition still exists at the end of the delay period, it is logged and the report is sent. If
programmed, the AC Failure output function activates when the event is logged. If AC is restored before the delay
period ends, the event is not logged and the report is not sent. If AC restoral reports are enabled, the reports are
only sent if an AC Failure report has been sent. The restoral report is sent without delay.
Addresses 0242 and 0243 must be programmed when setting the AC Fail Report Delay. The system multiplies the
entry made in Address 0242 by 16 and adds it to the entry made in Address 0243. For example, to set the AC Fail
Report Delay time to 50 min., you would enter “3” in Address 0242 (3 x 16 = 48) and then enter “2” in Address
0243 (48 + 2 = 50). Use the formula below to calculate the delay time for this parameter.
3 (Address 0242) x 16 = 48 + 2 (Address 0243) = 50 (AC Fail Report Delay Time)
See below for commonly used time settings.
• 0,10 = 10 min. (0 x 16 = 0 + 10 = 10 min.)
• 1,14 = 30 min. (1 x 16 = 16 + 14 = 30 min.)
• 2,13 = 45 min. (2 x 16 = 32 + 13 = 45 min.)
• 3,12 = 60 min. (3 x 16 = 48 + 12 = 60 min.)
• 5,10 = 90 min. (5 x 16 = 80 + 10 = 90 min.)
• 7,8 = 120 min. (7 x 16 = 112 + 8 = 120 min.)

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 35

Remote Programming Options

• Address: 0256
• Default: 1
• Selections: 0, 1, 3, 5, 7
Enter This Data Digit to Select Options
Remote Programming Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Disable Remote Programming •
Enable Remote Programming • • • •
Enable Remote Programming Callback • •
Terminate Remote Programming Session on
• •
Alarm
Reserved

• Enable Remote Programming: If this option is enabled, the system answers the phone at the programmed
ring count for remote programming sessions. [#][4][3] can also be used to start a remote programming session
or answer the phone if Address 0213 is set to 0. See RPS Answer Ring Count, Answering Machine Bypass on page
17.
− If the programming session is completed successfully, the control panel sends a Valid Remote Access
{103} report.
− If you change the control panel parameters during the programming session, it sends a Parameters
Changed {98} report.
− If the programming session is terminated with a ‘reset panel’ from RPS, the control panel sends a Reboot
{104} report.
− If the programming session is not successfully completed, the control panel sends an Invalid Remote
Access {102} report.

Select the “Enable Remote Programming” option to ensure that the following options operate properly.

• Enable Remote Programming Callback: If this option is enabled, the system answers the phone at the
programmed ring count for remote programming sessions. If it determines that the remote programmer is
calling, it disconnects and calls the remote programmer back using the programmed call-back phone
number/IP address (Remote Programming Call Back Number on page 16). When this is enabled, [#][4][3] can also
be used to start a programming session. When a user presses [#][4][3] at the keypad, the control panel calls
RPS. If the callback to RPS is not successful, it sends a Bad Call {101} report.
• Terminate Remote Programming Connection on Alarm: If this option is enabled, an alarm on any zone
or any keypad terminates the remote programming session.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 36

Local Programming Options

• Address: 0257
• Default: 12
• Selections: 0, 1, 4, 5, 8, 9, 12, 13
Enter This Data Digit to Select Options
Local Programming Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Enable Installer Mode Reports • • • •
Reserved
Keypad Programming Enabled • • • •
PK32 (Programming Key) Enabled • • • •

• Enable Installer Mode Reports: If this option is enabled, the control panel sends the following events:
Installer Mode Start {82}, Installer Mode End {83}, and Parameters Changed {98}. If this option is disabled,
these events are only entered in the control panel’s history log.
• Keypad Programming Enabled: If this option is enabled, all control panel parameters can be programmed
from any system text keypad or an Installer Keypad. See “Installer Keypad” and “Installer Mode” in the
DS7200V2 Installer’s Guide (P/N: 4998153893).
• PK32 (Programming Key) Enabled: If this option is enabled, the PK32 Programming Key can send or
receive a program record (the control panel’s parameter settings). See “Programming Key (PK32)” in the
DS7200V2 Installer’s Guide (P/N: 4998153893).

If the “Keypad Programming Enabled” and the “PK32 (Programming Key) Enabled” options are both
disabled, you cannot access the control panel’s programming mode from a keypad. You can still
program the control panel from RPS.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 37

4.2.7 Global Open/Close Options

Arming Options 1

• Address: 0258
• Default: 0
• Selections: 0 to 7
Enter This Data Digit to Select Options
Arming Options 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Enabled •
Enable All On-No Exit • • • •
Answering Machine Bypass only when All/Perimeter
• • • •
Only On
Remote Arming with Telephone, Area 1 • • • •
Reserved

• Enable All On-No Exit: If this option is enabled and the system is turned All On and no Entry/Exit Delay
zones are faulted during Exit Delay, the system automatically shifts to Perimeter Only. Perimeter Only (not
All On) appears in the log and reports. This option can only be used if the control panel is armed with delay.
This option does not apply when arming with keyswitches or RF keyfobs.
• Answering Machine Bypass Only When All On/Perimeter Only On: If this option is enabled, the
Answering Machine Bypass function is activated at RPS Answer Ring Count, Answering Machine Bypass
parameter (see page 17). If activated there, this option can be used to restrict its function so that it only
operates when the system is All On or Perimeter Only On. The system does not answer if disarmed.
• Remote Arming with Telephone, Area 1: If enabled, this option controls the built-in telephone arming
feature for Area 1. When enabled, the control panel answers the phone on the ring count for remote
programming. The following occurs when the control panel answers the phone:
− If the control panel is All On or Perimeter Only On, it sounds three beeps and starts the handshake tone
for remote programming.
− If the control panel is Off, it sounds one short beep, waits approximately three sec and then starts the
handshake tone for remote programming (one long beep). Press and hold [5] for two sec immediately
after the first short arming beep and before the handshake tone begins.
If arming from a cell phone, quickly press [5] three times. If pressing and holding [5] for two sec from a
house (landline) phone does not produce a tone long enough to arm Area 1, retry by quickly pressing [5]
three times.
− The control panel arms if it detects a [5] key press from the telephone (All On with Delay, faulted zones
are force-armed like keyswitch arming). The control panel sounds three beeps (new armed state) and then
hangs up.

You cannot use a telephone to disarm the control panel.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 38

Arming Options 2

• Address: 0259
• Default: 12
• Selections: 0 to 15
Enter This Data Digit to Select Options
Arming Options 2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Enabled •
First Area to Open/Last Area to Close Reporting • • • • • • • •
Make Area 1 Common Area • • • • • • • •
Enable All Areas All On ([#][8][0]) • • • • • • • •
Enable All Areas All Off ([#][8][1]) • • • • • • • •

• First Area to Open {164}/Last Area to Close {165} Reporting: If this option is enabled, the system sends
one Closing {165} report when all areas are turned On and one Opening {164} report when any area is turned
Off. Opening/Closing reports must be enabled for all areas.

Enabling the “Restrict Open/Close Reports” option overrides the “First Area to Open/Last Area to
Close Reporting” option. See Area # Opening {89-96}/Closing {42-67} Reporting Options on page 49
for more information on the “Restrict Open/Close Reports” option.

All area account numbers must be the same in order to send Area 1’s account numbers. See Area
Wide Parameters on page 48 for account number programming instructions.
• Make Area 1 Common Area: If this option is enabled, all other areas are made common to Area 1. Area 1
arms when all the other areas are armed All On, and Area 1 disarms when any other area is disarmed.
• Enable All Areas All On ([#][8][0]): If this option is enabled, all areas arm when a user enters [#][8][0].
Faulted zones are force-armed. Enable all areas in which the user has the appropriate authority level.
• Enable All Areas Off ([#][8][1]): If this option is enabled, all areas disarm when a user enters [#][8][1]. This
function always requires a PIN. Enable all areas in which the user has the appropriate authority level.

Bypass/Force Arm Limit

• Address: 0260
• Default: 7
• Selections: 0 to 15
The parameter configures all areas.
This parameter sets the maximum number of zones that can be force-armed or bypassed for any one area. The
area does not arm if the number of faulted zones exceeds this limit.
Entering zero (0) allows an unlimited number of zones to be force-armed or bypassed.
The Zone Function determines which zones are bypassable.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 39

Open/Close Reporting Options

• Address: 0261
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Open/Close Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Open, Close, Exit Error, or Recent Close Reports •
Opening {89-96, 164} Reports Enabled • • • • • • • •
Closing {42-67, 165} Reports Enabled • • • • • • • •
Exit Error {18} Report Enabled • • • • • • • •
Recent Closing {19-20} Reports Enabled • • • • • • • •
This is a global parameter that affects all zones, all areas, and all PINs.

Opening and Closing reports can be restricted by area (see Area # Opening {89-96}/Closing {42-67}
Reporting Options on page 49) and by Authority Level once they are enabled and configured here.
Reporting must be enabled at the system level first (see Global Reporting Options on page 19).

• Opening Reports Enabled: If selected, this option enables Opening {89 to 96, 164} reports.
• Closing Reports Enabled: If selected, this option enables Closing {42 to 67, 165} reports.
• Exit Error: Only the Exit Error {18} report is enabled and disabled by this option. If an Entry/Exit Delay
zone (Zone Function Types 11 and 12) is violated at the end of Exit Delay, these events occur in this order:
1. Local alarm annunciation is started (keypads and alarm outputs).
2. Entry Delay starts.
3. The alarm report process begins if the system is not turned off at the end of Entry Delay. An Exit Error
{18} report is included if programmed. The Exit Error report follows the Alarm Report routing.
• Recent Closing: If this option is enabled, an Alarm Recent Closing {19 to 20} report (including the user
number) is sent for any alarm within 2 min. of the end of Exit Time.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 40

Opening/Closing Report Routing

• Address: 0262
• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
This is a global parameter that affects all zones, all areas, and all PINs.
The Exit Error {18} and Recent Closing {19 to 20} reports follow alarm routing. See “Communication Failure
(Comm Fail)” for a description of a Comm Fail event and “Dialing Attempt Tables” for a description of the
dialing sequence in the DS7200V2 Installer’s Guide (P/N: 4998153893).

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).

Exit Time Restart

• Address: 0263
• Default: 1 (Exit Time Restart)
• Selections:
− 0 = No Exit Time Restart
− 1 = Exit Time Restart
If Exit Time Restart is set to Restart (1), a violation, restoral, and second violation of an Entry/Exit Delay zone
(before the end of Exit Delay) restarts Exit Delay. One restart is allowed per arming cycle. A violation, restoral,
and second violation must all occur at the same Entry/Exit zone.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 41

Entry Delay Time 1 (2)

• Address:
• Entry Delay Time 1: 0264, 0265
• Entry Delay Time 2: 0266, 0267
• Default:
− Entry Delay Time 1: 1,14 (30 sec)
− Entry Delay Time 2: 7,8 (120 sec)
• Selections: 0,0 to 15,15 (0 to 255 sec)
Entry Delay is the time the system allows the user to turn the system off before an alarm initiates.
If the user fails to turn off the system before Entry Delay expires, an alarm event occurs. Users must enter through
a zone programmed for Entry Delay to start the Entry Delay timer.
The control panel provides two Entry Delays. Only zone function types programmed to initiate Entry Delay 1 use
the entry delay time you set at the Entry Delay Time 1 parameter. Zone function types programmed to initiate
Entry Delay 2 use the entry delay time you set at the Entry Delay Time 2 parameter.
If the system is on and a user enters through a zone assigned to Entry Delay 2, the system initiates Entry Delay 2.
If the user enters through a zone assigned to Entry Delay 1, and then through a zone assigned to Entry Delay 2,
the system does not switch from Entry Delay 1 to Entry Delay 2.
The system sounds an entry delay tone at the area’s keypad during Entry Delay.
Programming two addresses for each sets the Entry Delay Time 1 and Entry Delay Time 2 parameters. The
system multiplies the entry in the first address by 16 and adds it to the entry in the second address. For example,
to set Entry Delay Time 1 to 50 sec, you would enter 3 in the first address (3 x 16 = 48), and then enter 2 in the
second address (48 + 2 = 50). Use the formula below to calculate the delay time for programming this parameter.
3 (Address 0264) x 16 = 48 + 2 (Address 0265) = 50 (Entry Delay Time)
See below for commonly used time settings.
• 0,10 = 10 sec (0 x 16 = 0 + 10 = 10 sec)
• 1,14 = 30 sec (1 x 16 = 16 + 14 = 30 sec)
• 2,13 = 45 sec (2 x 16 = 32 + 13 = 45 sec)
• 3,12 = 60 sec (3 x 16 = 48 + 12 = 60 sec)
• 5,10 = 90 sec (5 x 16 = 80 + 10 = 90 sec)
• 7,8 = 120 sec (7 x 16 = 112 + 8 = 120 sec)
• 15,0 = 240 sec (15 x 16 = 240 + 0 = 240 sec)

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 42

Perimeter Only Mode Delay Time

• Address: 0268, 0269


• Default: 0,0 (use assigned Entry Delay)
• Selections: 0,0 to 15,15 (0 to 255 sec)
Making an entry in the Perimeter Only Mode Delay Time parameter creates an Entry Delay time that only
applies when the system is armed Perimeter Only.
If the system is Perimeter Only or Partial On and any armed zone is faulted (fire and 24-hour zones excluded), the
system starts a Perimeter Only Mode Entry Delay timer. It uses this Perimeter Only Mode timer for zones that are
assigned to either Entry Delay 1 or Entry Delay 2, and zones that are not assigned Entry Delay.
Setting the Perimeter Only Mode Delay Time to zero (0, 0) disables Perimeter Only Mode delay. When the
system is turned on Perimeter Only and 0,0 is entered for Perimeter Only Mode Delay Time, the armed entry
zones follow the Entry Delay assigned to them (Entry Delay 1 or Entry Delay 2).
Programming two Addresses sets the Perimeter Only Mode Delay Time. The system multiplies the number
entered in the first Address by 16 and adds that total with the number entered in the second Address. For
example, to set Perimeter Only Mode Delay Time 1 to 50 sec, you would enter 3 in the first Address (3 x 16 = 48)
and then enter 2 for the second Address (48 + 2 = 50). Use the formula below to calculate the delay time for
programming this parameter.
3 (Address 0268) x 16 = 48 + 2 (Address 0269) = 50 (Perimeter Only Delay Time)
See Entry Delay Time 1 (2) on page 41 for a list of commonly used time settings.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 43

Exit Delay Time 1 (2)

• Address:
− Exit Delay Time 1: 0270, 0271
− Exit Delay Time 2: 0272, 0273
• Default:
− Exit Delay Time 1: 3,12 (60 sec)
− Exit Delay Time 2: 7,8 (120 sec)
• Selections: 0,0 to 15,14 (0 to 254 sec)
Exit Delay is the time the system allows users to exit the premises. Users must leave the premises before Exit
Delay expires.
The control panel provides two Exit Delays. When a user turns the system All On or Perimeter Only On with
Delay, the system always starts Exit Delay 1. Exit Delay is set to the time you enter at the Exit Delay Time 1
parameter.
If a zone assigned to Exit Delay 2 is faulted when Exit Delay is running, the system switches from Exit Delay 1 to
Exit Delay 2 (the time you enter at the Exit Delay Time 2 parameter).
If a user force-arms an Exit Delay 2 zone, the system uses Exit Delay 2 and Entry Delay 2.
Programming two Addresses for each parameter sets Exit Delay Time 1 and Exit Delay Time 2. The system
multiplies the number entered in the first Address by 16 and adds that total with the number entered in the
second Address. For example, to set Exit Delay Time 1 for 50 sec, you would enter 3 in the first Address (3 x 16 =
48) and then enter 2 for the second Address (48 + 2 = 50). Use the formula below to calculate the delay time for
programming this parameter.
3 (Address 0270) x 16 = 48 + 2 (Address 0271) = 50 (Entry Delay Time)
See Entry Delay Time 1 (2) on page 41 for a list of commonly used time settings.
See Contact Set/Exit Delay Cancel Zone Options on page 45 and Exit Terminator Zone Options on page 45 for additional
Exit Delay options.

If Exit Delay 1 or 2 is set to 0 (zero), the area arms instantly (no Exit Delay) in the following conditions:
Arming All On:
- Both Contact Set and Exit Terminator buttons are disabled for the area.
- Arming form a Sked, keyswitch, telephone, keyfob, or RPS.
Arming Perimeter Only or Partial On: The are arms instantly – there is no Exit Delay.

Arming from a wired keypad: If either Contact Set or Exit Terminator button (or both) is enabled for the
area and Exit Delay is set to 0 (zero), Exit Delay is disabled. The keypad does not show a countdown.
The control panel does not arm until the criteria for the Contact Set or Exit Terminator is met.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 44

Tamper Reset/Arming Options

• Address: 3408
• Default: 3
• Selections: 0 to 3
Enter This Data Digit to Select Options
Tamper Reset/Arming Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Tamper Reset/Arming Options •
Allow User Reset of Tampers/Troubles • •
Allow Force Arming of Tampers/Troubles • •
Reserved
Reserved

This parameter enables user reset of a tamper or trouble condition and force arming of the control panel when a
tamper or trouble condition exists.
• Allow User Reset of Tampers/Troubles: If enabled, this option allows a user with the appropriate authority
level to reset tamper and major trouble conditions. Enable Authority Level Option 9: System Functions 1 (page 57)
and Authority Level Option 10: System Functions 2 (page 58) for each user who can reset tamper and trouble
conditions.
The following conditions are treated as major trouble conditions:
− 24-hour zone missing (DX2010 Data Bus device missing)
− Controlled zone missing (DX2010 Data Bus device missing)
− Low or missing system battery
− Telephone line fail (if programmed for user reset)
− Alternate communication path fault (if programmed for user reset)
− 24-hour zone trouble (zone programmed for trouble, not alarm)
− Controlled zone trouble (zone programmed for trouble, not alarm)
• Allow Force Arming of Tampers/Troubles: If enabled, this option allows a user with the appropriate
authority level to force arm the control panel when a tamper or major trouble condition exists. Enable
Authority Level Option 7: Force Arm/Bypass (page 56) for each user who can force arm the system when a tamper
or trouble condition occurs. If the tamper or trouble is zone-related, the zone function configuration must
have the "Can Be Bypassed or Force Armed" options enabled (see Options 2, Zone Function ## on page 99).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 45

Contact Set/Exit Delay Cancel Zone Options

• Address: 3409
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Contact Set/Exit Delay Cancel Zone Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Contact Set Arming •
Enable Contact Set in Area 1 • • • • • • • •
Enable Contact Set in Area 2 • • • • • • • •
Enable Contact Set in Area 3 (DS7240V2 only) • • • • • • • •
Enable Contact Set in Area 4 (DS7240V2 only) • • • • • • • •
This parameter selects which areas arm when an Entry/Exit Delay zone restores during Exit Delay and all zones
are normal. Each area can be individually selected to arm on contact (Exit Delay cancel zone).
Contact Set only applies when turning the system All On. If the system is turned Perimeter Only or Partial On,
the control panel only arms at the end of Exit Delay. When any Entry/Exit Delay zone (either Type 1 or Type 2)
goes from its alarm (off-normal) condition to normal, and all other zones in the area are normal or bypassed, Exit
Delay is terminated and the control panel is armed.
If a zone is faulted when the Exit zone restores, the restoral is ignored. Entry/Exit zones may or may not be
bypassed. If all Entry/Exit zones are bypassed and the Exit Delay time is set to 0 (disabled), the control panel
cannot be armed All On.

Exit Terminator Zone Options

• Address: 3410
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Exit Terminator Zone Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Terminator Arming •
Enable Exit Terminator Arming in Area 1 • • • • • • • •
Enable Exit Terminator Arming in Area 2 • • • • • • • •
Enable Exit Terminator Arming in Area 3
• • • • • • • •
(DS7240V2 only)
Enable Exit Terminator Arming in Area 4
• • • • • • • •
(DS7240V2 only)

This parameter selects which areas arm when an exit terminator button is assigned to that area. Each area can be
individually selected to arm on the activation of an exit terminator button.
Each button only arms the area to which its zone is assigned.
When Exit Delay is active, all zones are normal, and the exit terminator button is pressed, the control panel arms
immediately (see Location ##, Zone Function on page 84 for more information). The exit terminator button applies
only to All On arming, and is assigned a specific zone function. If the control panel is turned Perimeter Only or
Partial On, it only arms at the end of Exit Delay. If a zone is faulted when the button is pressed, the button is
ignored.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 46

Panel Arming Options

• Address: 3411
• Default: 0
• Selections: 0 to 7
Enter This Data Digit to Select Options
Panel Arming Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Panel Arming Options •
Enable Bad Set Operation • • • •
Panel is Disarmed during Exit Delay • • • •
Start Exit Delay with Faulted Zones • • • •
Reserved

This is a global parameter. Use it to select several different control panel arming options.
• Enable Bad Set Operation: If this option is selected, a “bad set” occurs when the Exit Delay timer expires,
and a zone is still faulted. The control panel does not arm. When a bad set occurs, all keypads in the area
sound the Last Chance tone.
The LCD keypad displays a “Failed to Arm” message and then prompts for a valid PIN to clear the display.
The LED keypad sounds the Last Chance tone and the Status LED flashes fast to indicate that a PIN entry is
required. Any control panel output configured for Bad Set activates when the bad set is detected and resets
when the PIN is entered.
When the bad set occurs, the Bad Set event {185} is placed in the log. This event follows the Opening/Closing
Report routing.
If this option is not selected, the control panel arms when the Exit Delay timer expires. A faulted zone triggers
an alarm response.
• Panel is Disarmed during Exit Delay: If this option is selected, the control panel remains disarmed until
Exit Delay is terminated. Controlled zones may be faulted, but do not cause alarms. Any zone type that
causes a trouble condition when the control panel is disarmed, or causes an alarm condition when the control
panel is armed, only creates a trouble condition. The armed LED on the keypads does not light until the Exit
Delay is terminated.
If this option is not selected, the control panel is “armed” at the start of Exit Delay. Instant controlled zones
cause an alarm if faulted. Any zone trouble that causes an alarm condition when the control panel is armed
creates an alarm condition. The armed LED on the keypads lights when Exit Delay starts.
• Start Exit Delay with Faulted Zones: If this option is selected, any faulted Entry/Exit zones or Follower
zones are ignored. The control panel proceeds with arming the area. If the zones are still faulted at the end of
Exit Delay, the control panel then generates the appropriate response. The keypad displays “Not Ready”
when a zone is faulted even though this option is selected. Instant zones always prevent control panel arming
if faulted.
If this option is not selected, any faulted zone in the set of zones to be armed prevents the area from arming.
The area must be force armed, or the faulted zones must be bypassed or restored.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 47

Verified Alarm Timer

• Address: 3412, 3413


• Default: 1,14 (30 min.)
• Selections:
− 0,0 (Disabled)
− 1,14 (30 min.) to 3,12 (60 min.)
This parameter sets the time for the Verified Alarm Timer. The amount of time entered in this parameter defines
the window of time in which two independent alarms must occur for the control panel to declare a verified alarm.
See the Glossary on page 148 for a definition of Verified Alarm.
Addresses 3412 and 3413 must be programmed when setting the Verified Alarm Timer. The system uses the
following formula to set the Verified Alarm Timer:
Address 3412 entry x 16 + Address 3413 entry = Verified Alarm Timer setting
For example, use the following steps to set the Verified Alarm Timer to 30 min.:
1. Enter “1” in Address 3412 (1 x 16 = 16).
2. Enter “14” in Address 3413 (16 + 14 = 30).
An entry of 0,0 disables the Verified Alarm Timer and Verified Alarm operation. Values from 1 to 29 operate as
30 min.. Values from 30 to 60 operate as entered (for example, with an entry of 31, the control panel declares a
verified alarm if two independent alarms occur within 31 min.). Values greater than 60 operate as 60 min..
See below for commonly used time settings:
• 1,14 = 30 min. (1 x 16 = 16 + 14 = 30 min.)
• 2,13 = 45 min. (2 x 16 = 32 + 13 = 45 min.)
• 3,12 = 60 min. (3 x 16 = 48 + 12 = 60 min.)

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 48

4.3 Area Wide Parameters


The parameters in this section configure the control panel’s areas. Each area has 16 characters of programmable
text for an area name and 16 characters of programmable area idle text, which appear on the LCD Keypad
display.
The DS7240V2 supports up to four areas. The DS7220V2 supports up to two areas.
All control panel text is programmed from the text keypad in a special text-programming mode. See Text Entry
Addresses on page 7 for text programming instructions.

Area # Account Number

• Address/Default: See Table 8


• Selections: 0 to 15 (see Table 9)

Table 8: Account Number Addresses/Defaults

Area Account # for Routing Account # for Routing Default Account #


Destination 1 Destination 2 (for both destinations)
1 Address 0276 to 0281 Address 0286 to 0291 10, 10, 10, 10, 0, 0
2 Address 0298 to 0303 Address 0308 to 0313 10, 10, 10, 10, 0, 0
3 (DS7240V2 only) Address 0320 to 0325 Address 0330 to 0335 10, 10, 10, 10, 0, 0
4 (DS7240V2 only) Address 0342 to 0347 Address 0352 to 0357 10, 10, 10, 10, 0, 0

Table 9: Account Number Entry Selections

For this Selection Press this Key For this Selection Press this Key
0 10 8 8
1 1 9 9
2 2 B 11
3 3 C 12
4 4 D 13
5 5 E 14
6 6 F 15
7 7 Terminate 0
Each area uses the account number entered here to report to the ARC receiver. Different account numbers can be
programmed for two routing destinations. See Routing Destinations on page 9 for a complete description of how the
control panel directs reports to the routing destinations.
Account numbers can contain up to six (6) digits. If less than four digits are entered, the control panel adds zeros
to the end to make a four-digit account number.
The control panel automatically truncates the account number to the maximum length supported by that format.
See Control Panel Events and Reporting Formats on page 138 for a complete description of the reporting formats
available to the control panel.
One account number digit occupies each address. Use a zero (0) to terminate the account number entry if it is less
than six digits in length.
For example, to set an account number of 1234, enter 1 2 3 4 0 (0 = Terminate).

Use “10” ([1][0] from the keypad) to enter “0.” Use “0” to terminate the account number.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 49

Area # Opening {89-96}/Closing {42-67} Reporting Options

• Address:
− Area 1: 0296
− Area 2: 0318
− Area 3 (DS7240V2 only): 0340
− Area 4 (DS7240V2 only): 0362
• Default: 1
• Selections: 0, 1, 3, 5, 7, 9, 11, 13, 15
Enter This Data Digit to Select Options
Area # Open/Close Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Open or Close Reports for Area # •
Open/Close Reports (for All On) for Area # Enabled • • • • • • • •
Restrict Open/Close Reports; Open after Alarm,
• • • •
Close on Force Arm
Open/Close Reports for Perimeter Only (and Partial
On) Mode – Must also select Open/Close Reports (for • • • •
All On)
1 Second Bell Test on Closing Rpt Acknowledgement • • • •

• Open/Close Reports for Area # Enabled: If enabled, this option configures Opening/Closing reports for
each area. This also includes the report for the Extend Auto Closing {21} event. Opening {89 to 96} and
Closing {42 to 67} reports must be enabled at the system level. Opening and Closing reports are also enabled
by authority level. Reporting must also be enabled at the system level (see Global Reporting Options on page
19).
• Restrict Open/Close Reports; Open From Alarm, Close on Force Arm: If this option is enabled, the
control panel only sends opening reports when the user disarms the system after an alarm and when Bell
Time has expired. The control panel only sends closing reports when a zone is force-armed. Force arming is
set by authority level and by zone function configuration.

Enabling the “Restrict Open/Close Reports” option overrides the “First Area to Open/Last Area to
Close Reporting” option. See Arming Options 2 on page 38 for more information on the “Restrict
Open/Close Reports” option.

• Open/Close Reports for Perimeter Only Mode: If this option is enabled, the control panel sends closing
reports when users arm the system Perimeter Only. If any zones are bypassed, bypass reports are also sent.
The control panel sends opening reports when users disarm the system. Perimeter Only arming is set by
authority level and by Zone Function configuration.
• 1 Second Bell Test on Closing Ack: If this option is enabled, outputs assigned to Alarm Output Functions
1|8, 1|9, 1|10, and 8|8 activate for one sec. See Function, Output ## on page 112 for output function
descriptions.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 50

Lock Area # Reporting

• Address:
− Area 1: 0297
− Area 2: 0319
− Area 3 (DS7240V2 only): 0341
− Area 4 (DS7240V2 only): 0363
• Default: 0 (Lock Area Disabled)
• Selections:
− 0 = Lock Area Disabled
− 1 = Lock Area Reports to Routing Destination 1
− 2 = Lock Area Reports to Routing Destination 2

This parameter locks area reporting to either Routing Destination 1 or Routing Destination 2. If you enable this
parameter for an area, all reports for that area are sent to the selected destination. Routing parameters for the
individual reports are ignored.
For example, if you set this parameter to 1, all reports in the area are sent to Destination 1. If you set this
parameter to 2, all reports in the area are sent to Destination 2.

Area Name Text

• Address: Key Character


− Area 1 Name: 1394 to 1425 0 +-0*/\[]=><#§
− Area 2 Name: 1458 to 1489 1 Space . 1 ? ! , @ _ & ~ : ; " ( ) ' ¿ ¡ % £ $ ¥
− Area 3 Name (DS7240V2 only): 1522 to 1553 2 ABCabc2ÅÄÃåäáàâãαβÇç
− Area 4 Name (DS7240V2 only): 1586 to 1617 3 DEFdef3ÉÆëéèêæ∆Φδε
4 GHIghI4ïíîìΓγηι
• Default:
5 JKLjkl5Λκλ
− Area 1: Area 1 Name Text 6 MNOmno6ÖöÑñØÕøóòôõΩµνω
− Area 2: Area 2 Name Text 7 PQRSpqrs7ΠΣπρσ
− Area 3 (DS7240V2 only): Area 3 Name Text 8 TUVtuv8ÜüúùûΘΥθτυ
− Area 4 (DS7240V2 only): Area 4 Name Text 9 WXYZwxyz9ÿΞΨξχψζ
• Selections: See Key/Character selection chart * Moves to the address before the text block.
# Moves to the address after the text block.
All control panel text is programmed from the text
A Moves cursor to the previous character position in
keypad in a special text-programming mode. See Text text block.
Entry Addresses on page 7 for text programming C Moves cursor to the next character position in text
instructions. block.
Enter up to 16 characters to describe each area. The following keys are not used in text programming
and produce an error tone when pressed: [On], [Off],
[Perimeter Only], [No Entry], [Bypass], [System Reset],
and [B].
Press [1] once to clear a character space or to enter a
blank space.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 51

Area Idle Text

• Address: Key Character


− Area 1 Idle Text: 1426-1457 0 +-0*/\[]=><#§
− Area 2 Idle Text: 1490-1521 1 Space . 1 ? ! , @ _ & ~ : ; " ( ) ' ¿ ¡ % £ $ ¥
− Area 3 Idle Text (DS7240V2 only): 2 ABCabc2ÅÄÃåäáàâãαβÇç
1554-1585 3 DEFdef3ÉÆëéèêæ∆Φδε
− Area 4 Idle Text (DS7240V2 only): 4 GHIghI4ïíîìΓγηι
1618-1649 5 JKLjkl5Λκλ
• Default: Not Ready 6 MNOmno6ÖöÑñØÕøóòôõΩµνω
7 PQRSpqrs7ΠΣπρσ
• Selections: See Key/Character selection chart
8 TUVtuv8ÜüúùûΘΥθτυ
All control panel text is programmed from the 9 WXYZwxyz9ÿΞΨξχψζ
text keypad in a special text-programming mode. * Moves to the address before the text block.
See Text Entry Addresses on page 7 for text # Moves to the address after the text block.
programming instructions. A Moves cursor to the previous character position in
This parameter provides 16 characters of text block.
programmable text for each area displayed when C Moves cursor to the next character position in text
the system is idle (no alarms, no troubles, system block.
disarmed). The following keys are not used in text programming
and produce an error tone when pressed: [On], [Off],
[Perimeter Only], [No Entry], [Bypass], [System Reset],
and [B].
Press [1] once to clear a character space or to enter a
blank space.

If the “Don’t Show Zone Status on Keypads” option is not enabled in the Keypad # Options parameter (page 67),
the text keypad displays “OK for All On” or “OK for Perimeter” across the second line. This indicates that all
zones are normal and the system is ready to arm All On or Perimeter Only. If a controlled zone is faulted, the
area idle text for this zone’s assigned area replaces the “OK for All On/OK for Perimeter” message.
If a zone not configured for Perimeter Only arming is faulted, “OK for Perimeter” replaces “OK for All On” on
the text keypad’s display. The system might be armed Perimeter Only, but cannot be armed All On until the
faulted zone is restored.
If the “Don’t Show Zone Status on Keypads” option is enabled, the area idle text displays continuously on the
second line when the keypad is idle (even if a zone is faulted).

If the “Don’t Show Zone Status on Keypads” option is selected, the default Area Idle Text (“Not
Ready”) should be changed. See Text Entry Addresses on page 7 for text entry instructions.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 52

4.4 User Interface


4.4.1 Authority Level Configuration
The Authority Level determines which functions are available to system users. Each user is assigned an authority
level. Use the parameters in this section to configure each of the four authority levels available in the control
panel.

Authority Level Option 1: All On Arming

• Address: 0364
• Default: 15
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 1: All On Arming 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required (Quick Arm) •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• [#][1]: All On with Entry Delay
• [#][1]: All On with Entry Delay, No Exit Tone*
• [#][1]: All On with No Entry Delay
• [On] Key: All On with Entry Delay
• [On] Key: All On with Entry Delay, No Exit Tone*
• [On] Key: All On with No Entry Delay
* Exit Time is doubled (up to 254 sec) when arming the system All On with Entry Delay, Silent (no Exit Tone).
If a PIN is required and not entered, the system asks for one after the function is entered.
To enable the “Quick Arm” feature, set Authority Level Option 1 to 0. A user PIN entry is not required for All
On arming.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 53

Authority Level Option 2: Perimeter Only Arming

• Address: 0365
• Default: 15
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 2: Perimeter Only Arming 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required (Quick Arm) •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• [#][2]: Perimeter Only with Entry Delay
• [#][2]: Perimeter Only with Entry Delay, No Exit Tone*
• [#][2]: Perimeter Only with No Entry Delay
• [Perimeter Only] Key: Perimeter Only with Entry Delay
• [Perimeter Only] Key: Perimeter Only with Entry Delay, No Exit Tone*
• [Perimeter Only] Key: Perimeter Only with No Entry Delay
If a PIN is required and not entered, the system asks for one after the function is entered.
Zones must be configured for Perimeter Only arming. See Options 1, Zone Function ## on page 95.
* Exit Time is doubled (up to 254 sec) when arming the system Perimeter Only with Delay, Silent (no Exit Tone).
To enable the “Quick Arm” feature, set Authority Level Option 2 to 0. A user PIN entry is not required for
Perimeter Only arming.

Authority Level Option 3: Partial On Arming

• Address: 0366
• Default: 15
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 3: Partial On Arming 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required (Quick Arm) •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• [#][3]: Partial On Arming with Entry Delay
• [#][3]: Partial On Arming with Entry Delay, No Exit Tone*
• [#][3]: Partial On Arming with No Entry Delay
If a PIN is required and not entered, the system asks for one after the function is entered.
* Exit Time is doubled (up to 254 sec) when Partial On Arming the system with Entry Delay, Silent (no Exit
Tone).
To enable the “Quick Arm” feature, set Authority Level Option 3 to 0. A user PIN entry is not required for Partial
On arming.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 54

Authority Level Option 4: Disarming the System

• Address: 0367
• Default: 15
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 4: Disarming the System 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Disarm Not Assigned (see warning below) •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts disarming of the system by authority level.

If 0 (Disarm Not Assigned) is selected for Authority Level Option 4 (Address 0367), you cannot disarm
the system from a keypad or RF keyfob. You can still disarm from a Sked, RPS, or a keyswitch.

Authority Level Option 5: One-Time Disarm

• Address: 0368
• Default: 8
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 5: One-Time Disarm 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
One-Time Disarm Not Assigned •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
If an authority level can disarm the system, use this parameter to restrict that authority level to One-time Disarm
(can only disarm the system once).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 55

Authority Level Option 6: Send Open/Close Reports

• Address: 0369
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 6: Send Open/Close
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Reports
Send Open/Close Reports for Authority Levels 1-4 •
Authority Level 1 does not send Open/Close
• • • • • • • •
Reports
Authority Level 2 does not send Open/Close
• • • • • • • •
Reports
Authority Level 3 does not send Open/Close
• • • • • • • •
Reports
Authority Level 4 does not send Open/Close
• • • • • • • •
Reports

No Open/Close reports are sent for the authority level(s) selected at this parameter.
For example, if Open/Close reports are enabled for an area and Open/Close reports are disabled for Authority
Level 1 in this parameter, the control panel sends Open/Close reports for users assigned to Authority Levels 2, 3
and 4. It does not send Open/Close reports for users assigned to Authority Level 1, even though Open/Close
reports are enabled for the area.
See the following parameters to properly enable/disable Open/Close Reporting:
• Routing Destinations on page 9
• Global Reporting Options on page 19
• Open/Close Reporting Options on page 39
• Area # Opening {89-96}/Closing {42-67} Reporting Options on page 49

If you quick arm the system, this option is ignored and closing reports are sent with user ID 255.
Opening reports are not sent.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 56

Authority Level Option 7: Force Arm/Bypass

• Address: 0370
• Default: 7
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 7: Force Arm/Bypass 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• Force Arm
• [#][0]: Selective Bypass
• [Bypass] Key
Zones must be configured for Bypass/Force Arm operation. See Options 2, Zone Function ## on page 99.

Authority Level Option 8: All Areas On/Off

• Address: 0371
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 8: All Areas On/Off 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• [#][8][0]: All On with Delay, All Areas
• [#][8][1]: Off, All Areas
Both of these functions must be enabled at the system level first. See Arming Options 2 on page 38.
For [#][8][0] to work as described, the authority level assigned to Authority Level Option 8 must match the
authority level assigned to Authority Level Option 1 (All On Arming).
For [#][8][1] to work as described, the authority level assigned to Authority Level Option 8 must match the
authority level assigned to Authority Level Option 4 (Disarming the System).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 57

Authority Level Option 9: System Functions 1

• Address: 0372
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 9: System Functions 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• View Alarm Memory ([#][4][0])
• System Test ([#][4][1])
• View System Trouble ([#][4][2])
• Remote Program ([#][4][3])1
• Walk Test ([#][4][4])
• Reset Sensors ([#][4][7]) [System Reset]2
• View Zone Trouble ([#][4][8])
1
To enable the Remote Program function, see Remote Programming Options on page 35.
2
Enable this parameter for Reset Sensor [#][4][7] for each user that can reset tamper and major trouble conditions
(see Tamper Reset/Arming Options on page 44).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 58

Authority Level Option 10: System Functions 2

• Address: 0373
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 10: System Functions 2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• Set Time and Date (send Date/Time Change {73} report) ([#][4][5])
• Change Skeds ([#][5][2]) (see Sked Parameters on page 120 for more information)
• Renew One-Time PINs ([#][5][3])
• Change (Add) Other PINs ([#][5][6])
• Delete PINs ([#][5][8])
• Set Chime Tone ([#][6][2])
• Set Chime Zones ([#][6][3])
• Set Partial On Zones ([#][6][5])
• Auto-Call Forwarding Enable, Digits to dial at All On ([#][8][3])
• Auto-Call Forwarding Disable, Digits to dial at disarm ([#][8][4])
• Reset tampers/troubles ([#][4][7]) [Also requires authority level option 9)1
• Enable Installer PIN ([#][9][2])2
1
Enable this parameter for each user that can reset tamper and major trouble conditions (see Tamper Reset/Arming
Options on page 44).
2
Set this parameter for each user who can enable the Installer PIN. For more information, see the “Restrict
Installer PIN” option in Keypad Response Options on page 70.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 59

Authority Level Option 11: Move to Area

• Address: 0374
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 11: Move to Area 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts Move to Area function ([#][5][0]) by authority level.
The Move to Area function allows the user to control multiple areas from one keypad when the system is split into
more than one area. See the DS7200V2 User’s Guide (P/N: 4998153894) for more information.

Authority Level Option 12: Extend Auto-On Time

• Address: 0375
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 12: Extend Auto-On Time 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the Extend Auto On Time function ([#][5][1]) by authority level.
The Extend Auto-On Time function delays the auto-on time by one hour if entered during the Auto-On Alert
Time. See the DS7200V2 User’s Guide (P/N: 4998153894) and Auto On Alert Time on page 26 for more information.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 60

Authority Level Option 13: System Functions 3

• Address: 0376
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 13: System Functions 3 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the following functions by authority level:
• Adjust keypad sounder volume and lighting ([#][4][9])
• Change or reset outputs ([#][5][4])
• Chime toggle Off/On ([#][6][1])
• Auto-Forward – Enable/Disable ([#][8][2])

Authority Level Option 14: Change PIN

• Address: 0377
• Default: 1
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 14: Change PIN 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Change Own PIN Not Allowed •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the PIN Change function ([#][5][5]) by authority level. The [#][5][5] function
cannot change the Installer PIN.

If 0 (zero) is selected, then no user can change their own PIN.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 61

Authority Level Option 15: View Log

• Address: 0378
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Authority Level Option 15: View Log 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No PIN Required •
Assign to Authority Level 1 • • • • • • • •
Assign to Authority Level 2 • • • • • • • •
Assign to Authority Level 3 • • • • • • • •
Assign to Authority Level 4 • • • • • • • •
This parameter enables/restricts the View Log function ([#][8][5]) by authority level.
4.4.2 PIN Configuration/Installer PIN
A Personal Identification Number (PIN) is a unique number issued at the time of installation of each system. This
PIN is required to operate the system (arm/disarm, test system, initiate functions, etc.). The PIN is not the same as
the account number.

PIN Length

• Address: 0379
• Default: 4 (4 digits long)
• Selections: 3 to 7 (3 digits min; 7 digits max)
This parameter determines the number of digits in a PIN. All user PINs and the Installer PIN follow this length.

If the PIN length is shortened after PINs are entered, duplicate PINs could be created (for example,
PINs 1235 and 1238 would both become 123).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 62

User Tamper Options

• Address: 0380
• Default: 0
• Selections: 0 to 3
Enter This Data Digit to Select Options
User Tamper Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No User Tamper Options •
User Tamper {156} Reports Enabled • •
User Tamper Activates Burg Alarm Output • •
Reserved
Reserved

A user tamper event is:


− A user entering a PIN that is not in the system (the user must enter the invalid PIN the number of times
shown in User Tamper Retry Count on page 62).
− A user entering a PIN that is in the system but does not have the authority for the desired function.
• User Tamper Reports Enabled: If enabled, this option ties User Tamper {156} reports and user tamper
activated alarm outputs to the keypad’s area. If only this option is selected and there is a user tamper event,
the text keypad in the area where the event occurs shows “Keypad locked!”
• User Tamper Activates Burg Alarm Output: If the burglary alarm output (steady alarm output) is selected
and there is a user tamper event, the text keypad where the user tamper occurred shows “Keypad locked!”
Other text keypads in the area show “Usr Tamper Alarm, Enter PIN to silence.” During the time the keypad
is locked out, any key pressed produces an error tone (for text and LED keypads). Selecting this option
specifically activates output functions 1|8, 1|9, 1|10, and 8|8. Output functions 1|8 and 1|9 only activate when
the control panel is armed. See Table 25 on page 112, for descriptions of these output functions.

User Tamper Retry Count

• Address: 0381
• Default: 4 (4 attempts)
• Selections:
− 0 = User Retry Count Disabled
− 1-15 = Number of attempts allowed before a User Tamper event occurs
Enter zero (0) to disable this parameter. The control panel creates a User Tamper event when a user enters an
invalid PIN the number of times programmed in this parameter.
For example, “5” is entered in this parameter. When an invalid PIN is entered five times, a User Tamper event
occurs.

User Tamper Lockout Time

• Address: 0382
• Default: 1 (1 minute)
• Selections: 0 to 15 (min.)
This parameter determines how long a keypad is locked out when a User Tamper event occurs (selections are in
minutes).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 63

Installer PIN

• Address: 0383 to 0389


• Default: 9876543
• Selections: 0 to 9

Do not use digits 10-15 when creating the Installer PIN or User PIN. Entering these digits makes the
PIN unusable and locks the installer out of the control panel.

The Installer PIN length is the same as all other system PINs (see PIN Length on page 61).
The default PIN length is 4 digits, which makes the Installer PIN 4 digits in length. For example, if the Installer
PIN is 7654321 and the PIN length is set to 4 digits, the Installer PIN changes to 7654.
The Installer PIN cannot disarm the system, but it can access all other functions.
The Installer PIN reports as User 0.

If the Installer PIN is left at its factory default, the control panel generates a System Trouble event if
enabled in the Date Format and Enable PIN Trouble parameter (see page 33). Make sure to change the
default value. This event is Local Only and is stored in the history buffer.
The Enable PIN Trouble option is disabled by default.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 64

4.4.3 Users
The control panel reserves the following User IDs for automated functions: 251 (control panel generated); 252
(Sked operation); 253 (remote telephone communication); 254 (RPS communication); 255 (keyswitch operation or
any local operation that does not require a PIN entry, such as Quick Arming).
See Table 10 for User parameter addresses and defaults. Defaults for User 1 are shown in (bold). Users 2-32 are
disabled by default.

Table 10: User Configuration

Personal Identification Number (PIN) Addresses Authority Area


Level
User Digit 1 Digit 2 Digit 3 Digit 4 Digit 5 Digit 6 Digit 7 Selection Selection
1 Addr 0390 Addr 0391 Addr 0392 Addr 0393 Addr 0394 Addr 0395 Addr 0396 Addr 0397 Addr 0398
(1) (2) (3) (4) (5) (6) (7) (1) (15)
2 Addr 0399 Addr 0400 Addr 0401 Addr 0402 Addr 0403 Addr 0404 Addr 0405 Addr 0406 Addr 0407
3 Addr 0408 Addr 0409 Addr 0410 Addr 0411 Addr 0412 Addr 0413 Addr 0414 Addr 0415 Addr 0416
4 Addr 0417 Addr 0418 Addr 0419 Addr 0420 Addr 0421 Addr 0422 Addr 0423 Addr 0424 Addr 0425
5 Addr 0426 Addr 0427 Addr 0428 Addr 0429 Addr 0430 Addr 0431 Addr 0432 Addr 0433 Addr 0434
6 Addr 0435 Addr 0436 Addr 0437 Addr 0438 Addr 0439 Addr 0440 Addr 0441 Addr 0442 Addr 0443
7 Addr 0444 Addr 0445 Addr 0446 Addr 0447 Addr 0448 Addr 0449 Addr 0450 Addr 0451 Addr 0452
8 Addr 0453 Addr 0454 Addr 0455 Addr 0456 Addr 0457 Addr 0458 Addr 0459 Addr 0460 Addr 0461
9 Addr 0462 Addr 0463 Addr 0464 Addr 0465 Addr 0466 Addr 0467 Addr 0468 Addr 0469 Addr 0470
10 Addr 0471 Addr 0472 Addr 0473 Addr 0474 Addr 0475 Addr 0476 Addr 0477 Addr 0478 Addr 0479
11 Addr 0480 Addr 0481 Addr 0482 Addr 0483 Addr 0484 Addr 0485 Addr 0486 Addr 0487 Addr 0488
12 Addr 0489 Addr 0490 Addr 0491 Addr 0492 Addr 0493 Addr 0494 Addr 0495 Addr 0496 Addr 0497
13 Addr 0498 Addr 0499 Addr 0500 Addr 0501 Addr 0502 Addr 0503 Addr 0504 Addr 0505 Addr 0506
14 Addr 0507 Addr 0508 Addr 0509 Addr 0510 Addr 0511 Addr 0512 Addr 0513 Addr 0514 Addr 0515
15 Addr 0516 Addr 0517 Addr 0518 Addr 0519 Addr 0520 Addr 0521 Addr 0522 Addr 0523 Addr 0524
16 Addr 0525 Addr 0526 Addr 0527 Addr 0528 Addr 0529 Addr 0530 Addr 0531 Addr 0532 Addr 0533
17 Addr 0534 Addr 0535 Addr 0536 Addr 0537 Addr 0538 Addr 0539 Addr 0540 Addr 0541 Addr 0542
18 Addr 0543 Addr 0544 Addr 0545 Addr 0546 Addr 0547 Addr 0548 Addr 0549 Addr 0550 Addr 0551
19 Addr 0552 Addr 0553 Addr 0554 Addr 0555 Addr 0556 Addr 0557 Addr 0558 Addr 0559 Addr 0560
20 Addr 0561 Addr 0562 Addr 0563 Addr 0564 Addr 0565 Addr 0566 Addr 0567 Addr 0568 Addr 0569
21 Addr 0570 Addr 0571 Addr 0572 Addr 0573 Addr 0574 Addr 0575 Addr 0576 Addr 0577 Addr 0578
22 Addr 0579 Addr 0580 Addr 0581 Addr 0582 Addr 0583 Addr 0584 Addr 0585 Addr 0586 Addr 0587
23 Addr 0588 Addr 0589 Addr 0590 Addr 0591 Addr 0592 Addr 0593 Addr 0594 Addr 0595 Addr 0596
24 Addr 0597 Addr 0598 Addr 0599 Addr 0600 Addr 0601 Addr 0602 Addr 0603 Addr 0604 Addr 0605
25 Addr 0606 Addr 0607 Addr 0608 Addr 0609 Addr 0610 Addr 0611 Addr 0612 Addr 0613 Addr 0614
26 Addr 0615 Addr 0616 Addr 0617 Addr 0618 Addr 0619 Addr 0620 Addr 0621 Addr 0622 Addr 0623
27 Addr 0624 Addr 0625 Addr 0626 Addr 0627 Addr 0628 Addr 0629 Addr 0630 Addr 0631 Addr 0632
28 Addr 0633 Addr 0634 Addr 0635 Addr 0636 Addr 0637 Addr 0638 Addr 0639 Addr 0640 Addr 0641
29 Addr 0642 Addr 0643 Addr 0644 Addr 0645 Addr 0646 Addr 0647 Addr 0648 Addr 0649 Addr 0650
30 Addr 0651 Addr 0652 Addr 0653 Addr 0654 Addr 0655 Addr 0656 Addr 0657 Addr 0658 Addr 0659
31 Addr 0660 Addr 0661 Addr 0662 Addr 0663 Addr 0664 Addr 0665 Addr 0666 Addr 0667 Addr 0668
32 Addr 0669 Addr 0670 Addr 0671 Addr 0672 Addr 0673 Addr 0674 Addr 0675 Addr 0676 Addr 0677

User 28 can be configured as the Guard Code User. See Guard Code Options on page 74 for more
information.
Users 29 to 32 can be configured as Duress Users. See Duress Reporting Options on page 73.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 65

PIN, User #

• Address: See Table 10 on page 64


• Default:
− User 1: 1, 2, 3, 4, 5, 6, 7
− Users 2-32: 15, 15, 15, 15, 15, 15, 15
• Selections: 0 to 9
Enter a PIN for each user in the PIN parameter. The PIN length parameter determines the number of digits in the
PINs.
The default PIN length is 4 digits, which makes all User PINs four digits in length. For example, if a User PIN is
7654321 and the PIN length is set to 4 digits, the User PIN changes to 7654.

Do not use digits 10 to 15 when creating a User PIN. Entering these digits makes the PIN unusable
and locks the user out of the control panel.

Authority Level, User #

• Address: See Table 10 on page 64


• Default:
− User 1: 1 (Authority Level 1)
− Users 2-32: 0 (No Authority Level assigned)
• Selections:
− 0 = No Authority Level assigned (Disabled)
− 1 = Authority Level 1 assigned
− 2 = Authority Level 2 assigned
− 3 = Authority Level 3 assigned
− 4 = Authority Level 4 assigned
This parameter assigns an authority level to each user. The authority level assigns functions to the user’s PIN and
RF keyfob. See RF Keyfobs on page 78 for a description of RF keyfobs and how to assign them to users.
Authority levels are configured as shown below. See Authority Level Configuration on page 52 to change the
configuration of authority levels.
• Authority Level 1 (Master): All options except for Option 5. A user with this authority level configuration
can arm and disarm the system, send reports, and perform all system functions except one-time disarm.
• Authority Level 2 (Unlimited): All options except for Option 5 and 14. A user with this authority level
configuration can arm and disarm the system, send reports, and perform all system functions except one-time
disarm and change PINs.
• Authority Level 3 (User): All options except for Options 5 and 8 to 15. A user with this authority level
configuration can arm and disarm the system, send reports, but can only perform a limited number of system
functions.
• Authority Level 4 (One-Time): All options except 7 to 15. A user with this authority level configuration can
arm and disarm the system (one-time only), send reports, but can only perform a limited number of system
functions and cannot force-arm or bypass zones when arming the system.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 66

Area Option, User #

• Address: See Table 10 on page 64


• Default:
− User 1:
− DS7240V2: 15 (Areas 1 to 4)
− DS7220V2: 3 (Areas 1 and 2)
− Users 2 to 32: 0 (Not assigned to an area)
• Selections: 0-15
Enter This Data Digit to Select Options
User Area Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Not Assigned to an Area •
Assigned to Area 1 • • • • • • • •
Assigned to Area 2 • • • • • • • •
Assigned to Area 3 (DS7240V2 only) • • • • • • • •
Assigned to Area 4 (DS7240V2 only) • • • • • • • •
Assigning PINs to multiple areas allows users to view and operate multiple areas from a single keypad.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 67

4.4.4 Keypads
Wired Keypads 1 to 8 are fixed at Data Bus Addresses 1 to 8. See “Keypad Addressing” in the DS7200V2
Installer’s Guide (P/N: 4998153893). All keypads (and other Data Bus devices) are fully supervised. Supervision
reports, such as missing and tamper, follow the System Status Report routing.

Keypad # Options

• Address:
− Keypad 1: 0678
− Keypad 2: 0680
− Keypad 3: 0682
− Keypad 4: 0684
− Keypad 5: 0686
− Keypad 6: 0688
− Keypad 7: 0690
− Keypad 8: 0692
• Default: 7
• Selections: 0 to 15
Enter This Data Digit to Select Options
Keypad Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Keypad Options •
Beep Keypad on System Trouble • • • • • • • •
Enable Exit Tone • • • • • • • •
Enable Area Display (DS7446KP Keypad) • • • • • • • •
Don’t Show Zone Status on Keypads • • • • • • • •

• Beep Keypad on System Trouble: If enabled, this option sounds a tone at the keypad when a System
Trouble occurs.
• Enable Exit Tone: If enabled, this option sounds the Exit Delay tone at this keypad when Exit Delay is
active.
• Enable Area Display (DS7446KP Keypad): If this option is enabled, the DS7446KP Keypad shows the
current state of each area using its four Area icons.

Table 11: DS7446KP Keypad Icon Functions

Function Condition
Icon flashes fast Area is in alarm
Icon is On Steady Area is in armed, but not in alarm
Icon flashes slow Trouble condition exists, or zone is bypassed in area
Icon is Off Area is disarmed, no alarm/trouble conditions exist, no zones are bypassed
If the “Enable Area Display” option is disabled, the DS7446KP Keypad displays the area to which it is
currently assigned if it is not in its home area. If the keypad moved to another area, the icon for the new area
lights steady. For example, if the keypad moved ([#][5][0]) to Area 1, no area icons are lit. If it moved to Area
2, the Area 2 icon turns on.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 68

• Don’t Show Zone Status on Keypads: If the “Don’t Show Zone Status on Keypads” option is not enabled in
the Keypad # Options parameter, the text keypad displays “OK for All On” or “OK for Perimeter Only” across
the second line. This indicates that all zones are normal and the system is ready to arm All On or Perimeter
Only. If a controlled zone is faulted, the Area Idle Text for this zone’s assigned area replaces the “OK for All
On/OK for Perimeter Only” message.
If a zone not configured for Perimeter Only arming is faulted, “OK for Perimeter Only” replaces “OK for All
On” on the text keypad’s display. The system might be armed Perimeter Only, but cannot be armed All On
until the faulted zone is restored.
If the “Don’t Show Zone Status on Keypads” option is enabled, the area idle text displays continuously on line
two when the keypad is idle.
LED keypads do not show zone status if this option is selected.

If the “Don’t Show Zone Status on Keypads” option is selected, the default Area Idle Text (“Not Ready”)
should be changed. See Text Entry Addresses on page 7 for text entry instructions.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 69

Keypad/Door Access Control Module (DACM) Area Options

• Address:
− Keypad/DACM 1: 0679
− Keypad/DACM 2: 0681
− Keypad/DACM 3: 0683
− Keypad/DACM 4: 0685
− Keypad/DACM 5: 0687
− Keypad/DACM 6: 0689
− Keypad/DACM 7: 0691
− Keypad/DACM 8: 0693
• Default:
− Keypad/DACM 1: 1 (Device is a keypad assigned to Area 1)
− Keypads/DACMs 2 to 8: 0 (No keypad/DACM assigned)
• Selections: 0 to 4, 9 to 12
Enter This Data Digit to Select Options
Keypad/DACM Area Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Keypad/DACM not assigned (disabled) •
Assign Keypad/DACM to Area 1 • •
Assign Keypad/DACM to Area 2 • •
Assign Keypad/DACM to Area 3 (DS7240V2 only) • •
Assign Keypad/DACM to Area 4 (DS7240V2 only) • •
Device is a Keypad • • • •
Device is a DACM • • • •

Assign only one area to each keypad. Users (PINs) can be assigned to multiple areas. The Move to Area function
([#][5][0]) allows users (PINs) assigned to multiple areas to view those areas from one keypad.
The control panel supervises the connection to the DACM. If it fails to communicate with the control panel, the
control panel sends a “Dbus Missing” {125} report.
See the documentation supplied with the DACM for complete installation, programming, addressing, and
operation instructions.

The control panel supports up to 8 DACMs. However, each DACM added to the system replaces one
keypad. If 8 DACMs are added, you cannot add a keypad. For full system control, make sure at least
one text keypad is included in the system.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 70

Keypad Response Options

• Address: 0704
• Default: 0
• Selections: 0 to 3, 6 to 11, 14, 15
Enter This Data Digit to Select Options
Keypad Response Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Keypad Response Options •
Enable Keypad Tamper Response • • • • • •
Enable Extinguish Mode • • • • • • • •
Extinguish Mode Displays Date • • • •
Restrict Installer PIN • • • • • •
This is a global parameter that affects all keypads.
• Enable Keypad Tamper Response: If this option is enabled, the control panel checks for a keypad tamper
response from each keypad. If this option is disabled, the control panel ignores the keypad tamper response.

To use this option, enable it at the control panel by setting Address 0704 to “1,” and enable the
keypad’s tamper jumper pins. See the installation instructions accompanying the keypad for information.

• Enable Extinguish Mode: If this option is enabled, the keypads extinguish when there is no activity. The
Power LED is always on, but any other LEDs are blank. The text keypad display also goes blank. Entering a
PIN turns the LEDs on and causes the text keypads to display text. If this option is disabled, the keypads are
never extinguished.
• Extinguish Mode Displays Date: If this option is enabled, when the keypad’s display is extinguished, the
text keypad's display shows the date and time on the first line, and the Call for Service Text (see page 26) on
the second line. If this option is disabled, the text keypad's display is blank.

You must select the “Enable Extinguish Mode" option in order to use the "Extinguish Mode Displays
Date” option.

• Restrict Installer PIN: If this option is enabled, the Installer’s PIN is restricted. The user must press [#][9][2]
to enable the Installer PIN. Once the Installer PIN is enabled, the installer may enter his PIN and access the
installer functions. If this option is disabled, the Installer’s PIN is always operative, and the Installer PIN can
clear Extinguish Mode.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 71

4.4.5 ABC Keys and Duress Parameters


The following parameters configure the keypad’s ABC keys and the Duress function for all keypads and areas.
Each key has 16 characters of programmable text that is displayed when the key is activated (press twice to
activate).

Area Options for ABC Keys

• Address:
− [A] Key: 0694
− [B] Key: 0696
− [C] Key: 0698
• Default:
− DS7240V2: 15 (Areas 1 to 4)
− DS7220V2: 3 (Areas 1 and 2)
• Selections: 0 to 15
Enter This Data Digit to Select Options
ABC Key Area Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Disabled for all Areas •
Keys work for Area 1 • • • • • • • •
Keys work for Area 2 • • • • • • • •
Keys work for Area 3 (DS7240V2 only) • • • • • • • •
Keys work for Area 4 (DS7240V2 only) • • • • • • • •
This parameter assigns areas to the keypad ABC Keys.

Alarm Response for ABC Keys

• Address:
− Alarm Response for [A] Key: 0695
− Alarm Response for [B] Key: 0697
− Alarm Response for [C] Key: 0699
• Default: 0 (No Alarm Response)
• Selections:
− 0 = No Alarm Response
− 1 = Activate Fire Alarm Response
− 2 = Activate Panic Alarm Response
− 3 = Activate Emergency Alarm Response
This parameter assigns the alarm response for the ABC keys.
• Fire Alarm Response: If enabled, this option displays “Fire Alarm Key #” at the text keypads. If
programmed, the control panel sends a Fire Alarm {75} report and activates the Fire Alarm output.
• Panic Alarm Response: If enabled, this option displays nothing and no sounds are emitted at the keypads. If
programmed, a Panic {6} report is sent and the Burglary Alarm output is activated.
• Emergency Alarm Response: If enabled, this option displays “Alarm Key #” at the text keypads. If
programmed, an Emergency Alarm {4} report is sent and the Burglary Alarm output is activated.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 72

Alarm Output Option for ABC Keys

• Address: 0700
• Default: 0
• Selections: 0 to 7
Enter This Data Digit to Select Options
Alarm Output Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Alarm Output for ABC Keys •
Alarm Output for [A] Key • • • •
Alarm Output for [B] Key • • • •
Alarm Output for [C] Key • • • •
Reserved

This parameter assigns an alarm output option to the ABC keys. The alarm output activates for the response type
assigned to each key. This is a global parameter that affects all areas.

ABC Key Reports/Ack Beep Options

• Address: 0701
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
ABC Keys Report & Ack Beep Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Alarm Report for ABC Keys •
Enable ABC Keys Reporting • • • • • • • •
Acknowledgement Beep for [A] Key • • • • • • • •
Acknowledgement Beep for [B] Key • • • • • • • •
Acknowledgement Beep for [C] Key • • • • • • • •
This is a global parameter that affects all areas.
• Enable ABC Keys Reporting: If this option is enabled, the keys report as follows:
− [A] Key reports as Zone 100
− [B] Key reports as Zone 101
− [C] Key reports as Zone 102
• Acknowledgement Beep for ABC Keys: If this option is enabled, the keypad beeps when the ARC receiver
acknowledges a report. If the key is not programmed for reports, the beep occurs on activation.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 73

Duress Reporting Options

• Address: 0702
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Duress Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No User Emergency Function Reporting •
Make User 32 a Duress User • • • • • • • •
Make User 31 a Duress User • • • • • • • •
Make User 30 a Duress User • • • • • • • •
Make User 29 a Duress User • • • • • • • •
This parameter creates up to 4 Duress users (and PINs). Creating a Duress user does not change any other
function programmed for that user.
Whenever a user enters a Duress PIN (PIN assigned to a Duress user), the control panel sends a Duress {74}
report and executes functions per the Duress user’s authority level.
To create a unique Duress user (and PIN) for each area, select Option 15 and then assign each of the four users
(User 29 through 32) to only one area.
To create one Duress user (and PIN) for all areas, select Option 1, 2, 4 or 8 and then assign that user (User 29
through 32) to all four areas.

ABC Keys and Duress Report Routing

• Address: 0703
• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
The [A] Key reports as Zone 100 for all areas, the [B] Key reports as Zone 101 for all areas and the [C] Key
reports as Zone 102 for all areas.
This is a global parameter that affects all areas. See “Communication Failure (Comm Fail)” for a description of the
Comm Fail event and “Dialing Attempt Tables” for the dialing sequence in the DS7200V2 Installer’s Guide
(P/N: 4998153893).

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).
The RF Keyfob “Panic” option follows this routing.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 74

Guard Code Options

• Address: 0705
• Default: 0 (No Guard Code Options)
• Selections:
− 0 = No Guard Code Options
− 1 = User 28 is a Guard Code
User 28 can be programmed as a Guard Code. The Guard Code only works in the areas to which User 28 is
assigned. The authority level assigned to the Guard Code (User 28) dictates which keypad functions the guard can
use.
For example, Authority Level Configuration Option 1 configures All On arming. If this is set to 0 (zero), the guard
can arm at any time. If the guard’s authority level does not allow All On arming, then the guard can never arm
All On. If the guard’s authority level allows All On arming, the guard can arm the area All On only if the Guard
Code was used to disarm the area.
Authority Level Configuration Options 2 and 3 configure Perimeter Only Arming and Partial On arming. If these
are set to 0 (zero), then the guard can arm in these modes at any time. If the guard’s authority level does not allow
these modes, then the guard can never arm using these modes. If the guard’s authority level allows these modes,
then the guard can arm the area using these modes only if the Guard Code was used to disarm the area.
Authority Level Configuration Option 4 configures system disarming. If this is set to 0 (zero), the guard can never
disarm the system. If the guard’s authority level does not allow disarming, the guard can never disarm the area. If
the guard’s authority level does allow disarming, then the Guard Code can only disarm the system if the system
had a non-silenced alarm.
Authority Level Configuration Options 5-15 operate the same for the Guard Code as they do for any other user
code. Enabling or disabling these options controls which functions the Guard Code can perform.

ABC Keys Text

• Address:
− [A]: 1298 to 1329
− [B]: 1330 to 1361
− [C]: 1362 to 1393
• Default:
− [A]: A Key Text
− [B]: B Key Text
− [C]: C Key Text
• Selections: See Table 3 on page 7
All control panel text is programmed from the text keypad in a special text-programming mode. See Text Entry
Addresses on page 7 for text programming instructions.
Enter up to 16 characters to describe the ABC key sequences.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 75

4.4.6 RF Keypads
The control panel supports up to four RF keypads. Each keypad has two programming parameters. RF keypads
report conditions such as low battery and tamper by transmitter number.
You must exit control panel programming in order to enter RF ID codes. Add RF ID codes after you complete
your programming session. See “Adding RF ID Codes” in DS7200V2 Installer’s Guide (P/N: 4998153893) for
complete instructions.

Table 12: RF Keypad Data Bus Addresses/Transmitter Numbers

RF Receiver 1 Transmitter Receiver 2 Transmitter


Keypad Data Bus Address Number Data Bus Address Number
1 52 255 60 247
2 53 254 61 246
3 54 253 62 245
4 55 252 63 244

RF Keypad # Options

• Address:
− RF Keypad 1: 2930
− RF Keypad 2: 2932
− RF Keypad 3: 2934
− RF Keypad 4: 2936
• Default: 0
• Selections: 0, 2, 4, 6
Enter This Data Digit to Select Options
RF Keypad # Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Reserved
Belongs to RF Receiver 2 • •
Supervised • •
Reserved

• Belongs to RF Receiver 2: If this option is enabled, RF Receiver 2 performs ID and monitoring functions for
the keypad. If this option is disabled, the keypad belongs to Receiver 1.
• Supervised: If this option is enabled, the control panel generates missing reports if it does not receive
communication from the RF keypad.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 76

RF Keypad # Area

• Address:
− RF Keypad 1: 2931
− RF Keypad 2: 2933
− RF Keypad 3: 2935
− RF Keypad 4: 2937
• Default: 0 (Disabled)
• Selections:
− 0 = Disabled (No Area Assigned)
− 1 = Assign RF Keypad to Area 1
− 2 = Assign RF Keypad to Area 2
− 3 = Assign RF Keypad to Area 3 (DS7240V2 only)
− 4 = Assign RF Keypad to Area 4 (DS7240V2 only)
To enable an RF keypad, assign it to an area. To disable an RF keypad, enter a 0 at this parameter.
4.4.7 Q Button Configuration

[Q] Button Alarm Response Options

• Address: 1263
• Default: 0
• Selections:
− 0 = No Alarm Response
− 1 = Panic Alarm Response
− 2 = Emergency Alarm Response
− 3 = Duress Alarm Response
This parameter assigns an alarm response to the [Q] button on the RF3501E 1-Button Pendant (or other device
with a [Q] button). This is a global parameter and affects the programming of all key fobs with [Q] buttons in all
areas.
• No Alarm Response: No alarm outputs are activated and no reports are sent. The [Q] button can be used to
control an output.
• Panic Alarm Response: If Alarm Output is enabled, the control panel sends a Panic {5} report and sounds
the alarm outputs. If Alarm Output is disabled, the control panel only sends an Invisible Panic {6} report. No
keypad tones or displays are generated. This option activates output function type 8|15.
• Emergency Alarm Response: This option displays “User Alarm” at the text keypads. The [Q] button sends
an Emergency Alarm {4} report, and the Burglary Alarm outputs are activated (optional). This option activates
output function type 8|15.
• Duress Alarm Response: This option sends a Duress {74} report. If configured, the text keypads display
“User Alarm” and the alarm outputs activate. This option makes the [Q] button function the same as Panic on
the keyfob. This option activates output function types 2|1, 2|2, and 8|15.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 77

[Q] Button Configuration Options

• Address: 1264
• Default: 0
• Selections: 0 to 1, 3 to 5, 7 to 9, 11 to 13, 15
Enter This Data Digit to Select Options
[Q] Button Configuration Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Enable [Q] Button Reporting • • • • • • • •
Enable [Q] Button Voice Verification • • • •
Enable [Q] Button Alarm Output • • • • • •
Enable [Q] Button Ack Beep • • • • • •
This parameter configures the [Q] button on the RF3501E 1-Button Pendant (or other device with a [Q] button.
This is a global parameter and affects the programming of all key fobs with [Q] buttons in all areas.
• Enable [Q] Button Reporting: If enabled, this option sends a report to the control panel using the ABC Keys
and Duress Report Routing (see page 73). If this option is disabled, the report is logged into the control panel’s
history only if the report routing specifies events to the log/printer. If Address 1263 is set to “No Alarm
Response,” then no report is sent and no event is placed in the control panel’s history log.
• Enable [Q] Button Voice Verification: If enabled, this option activates the Voice Verification response only
is a report is actually sent. When the report is acknowledged, the voice verification session begins.
• Enable [Q] Button Alarm Output: If enabled, this option activates alarm output types 1|5, 1|6, 1|8, 1|9, 1|10,
and 8|8.
• Enable [Q] Button Ack Beep: If enabled, this option beeps the area keypads after a report is sent. All
keypads in the area beep when the control panel receives the acknowledgement (ack) that the report was
received. The area keypads beep as soon as the [Q] button is pressed if any of the following conditions are
true:
− [Q] button alarm response is set to “No Alarm Response” (see Address 1263)
− [Q] button reporting is disabled
− [Q] button report routing does not send a report

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 78

4.4.8 RF Keyfobs
RF keyfobs (two- and four-button keychain keypads) are managed internally by the control panel. Keyfobs are
assigned to PINs (users) by entering IDs. No other programming parameters are required. Keyfobs generally
follow the authority level and area assignment for the PIN they are assigned to.
RF keyfobs report low battery conditions using the user number (1 to 32). The user’s ID number, not the
transmitter number, is used for open/close reports. Each receiver can handle 24 keyfobs. For 32 keyfobs, two RF
Receivers are required. Address 2938 must be set to a value from 1 to 14.
To add an RF keyfob into the system, see “Adding RF ID Codes” in the DS7200V2 Installer’s Guide
(P/N: 4998153893).

RF Keyfob Receiver Assignment Options

• Address: 2938
• Default: 8
• Selections: 1 to 14
Enter This Data Digit to Select Options
RF Keyfob Receiver Assignment Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected (all RF on RF Receiver 1)
Assign Keyfobs 1-8 to RF Receiver 2 • • • • • • •
Assign Keyfobs 9-16 to RF Receiver 2 • • • • • • •
Assign Keyfobs 17-24 to RF Receiver 2 • • • • • • •
Assign Keyfobs 25-32 to RF Receiver 2 • • • • • • •
This parameter assigns keyfobs in groups of eight to RF Receiver 2. Keyfobs not assigned to RF Receiver 2 are
automatically assigned to RF Receiver 1.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 79

RF Keyfob Options

• Address: 2939
• Default: 0
• Selections: 0, 1, 3 to 5, 7 to 9, 11 to 13, 15
Enter This Data Digit to Select Options
RF Keyfob Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Panic Enabled • • • • • • • •
Alarm Output on Panic • • • •
Assign [O] (trapezoid) key to Perimeter Only On • • • • • •
Assign [P] key to Partial On • • • • • •
This parameter configures all keyfobs for all areas and all PINs.
• Panic Enabled: This option configures the system’s response to the RF panic signal. Pressing the Lock and
Unlock keys on the keyfob simultaneously transmits a unique Panic signal to the RF Receiver. If the keyfob
Panic option is enabled, the system sends a Duress report. Duress reports from keyfobs follow ABC
Keys/Duress Report Routing (see ABC Keys and Duress Report Routing on page 73 and Duress Reporting Options
on page 73).
• Alarm Output on Panic: If this option is enabled, the keyfob activates the alarm output when the Lock and
Unlock keys are simultaneously pressed. The “Panic Enabled” option must enabled.
• Assign [O] (Trapezoid) Key to Perimeter Only: If this option is enabled, the keyfob arms the system
Perimeter Only when [O] is pressed. If you select this option, you cannot use [O] to activate Output Function
1|15.
• Assign [P] (Sun) Key to Partial On: If this option is enabled, the keyfob arms the system Partial On when
[P] is pressed. The [P] key on the RF keypads is also configured by this option. If you select this option, you
cannot use [P] to activate Output Function 2|0.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 80

4.5 Zone Parameters


4.5.1 Location Configuration
The DS7240V2 supports Locations 1 to 40. The DS7220V2 supports Locations 1 to 24. Locations become zones
by configuring the following parameters: Device, Zone Function, Area, and Zone Number. All four of these
parameters must be configured for each location being used in the system. See Table 13 for location parameter
addresses and defaults (defaults are shown in bold).

Table 13: Location Configuration Parameters

Location Parameters Device Parameter Selections


These columns show the addresses and These columns show the selections for the “Device” parameter. The Device parameter tells the control
defaults for each of the four location panel where to find the sensor loop (or transmitter) status for each Location.
parameters. These parameters configure
each location.
1 1 1,2 1,2 3
Location Device Zone Area Zone # On-board DX2010 DX2010 RF Rcvr 1 RF Rcvr 2 DACM
Function Device = 1 Device = 2 Doubled Device = 4 Device = 5 Device = 6
Device = 3 (optional)
1 0706 0707 0708 0709, 0710 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (11) (1) (0,1) doubled w/9 Loop 1 Xmitter 1 Xmitter 1
2 0711 0712 0713 0714, 0715 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (11) (1) (0,2) doubled w/10 Loop 2 Xmitter 2 Xmitter 2
3 0716 0717 0718 0719, 0720 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (12) (1) (0,3) doubled w/ 11 Loop 3 Xmitter 3 Xmitter 3
4 0721 0722 0723 0724, 0725 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (13) (1) (0,4) doubled w/ 12 Loop 4 Xmitter 4 Xmitter 4
5 0726 0727 0728 0729, 0730 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (13) (1) (0,5) doubled w/ 13 Loop 5 Xmitter 5 Xmitter 5
6 0731 0732 0733 0734, 0735 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (14) (1) (0,6) doubled w/ 14 Loop 6 Xmitter 6 Xmitter 6
7 0736 0737 0738 0739, 0740 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (14) (1) (0,7) doubled w/ 15 Loop 7 Xmitter 7 Xmitter 7
8 0741 0742 0743 0744, 0745 3.65 k Ω when DBus Adr 101 DBus Adr 50 DBus Adr 51 DACM
(1) (4) (1) (0,8) doubled w/ 16 Loop 8 Xmitter 8 Xmitter 8
9 0746 0747 0748 0749, 0750 Doubled w/ 1 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (0,9) 2.2 k Ω Loop 1 Loop 1; 3.65 kΩ Xmitter 9 Xmitter 9
10 0751 0752 0753 0754, 0755 Doubled w/ 2 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,0) 2.2 k Ω Loop 2 Loop 2; 3.65 kΩ Xmitter 10 Xmitter 10
11 0756 0757 0758 0759, 0760 Doubled w/ 3 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,1) 2.2 k Ω Loop 3 Loop 3; 3.65 kΩ Xmitter 11 Xmitter 11
12 0761 0762 0763 0764, 0765 Doubled w/ 4 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,2) 2.2 k Ω Loop 4 Loop 4; 3.65 kΩ Xmitter 12 Xmitter 12
13 0766 0767 0768 0769, 0770 Doubled w/ 5 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,3) 2.2 k Ω Loop 5 Loop 5; 3.65 kΩ Xmitter 13 Xmitter 13
14 0771 0772 0773 0774, 0775 Doubled w/ 6 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,4) 2.2 k Ω Loop 6 Loop 6; 3.65 kΩ Xmitter 14 Xmitter 14
15 0776 0777 0778 0779, 0780 Doubled w/ 7 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,5) 2.2 k Ω Loop 7 Loop 7; 3.65 kΩ Xmitter 15 Xmitter 15
16 0781 0782 0783 0784, 0785 Doubled w/ 8 DBus Adr 102 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,6) 2.2 k Ω Loop 8 Loop 8; 3.65 kΩ Xmitter 16 Xmitter 16
17 0786 0787 0788 0789, 0790 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,7) Loop 1 Loop 1; 2.2 kΩ Xmitter 17 Xmitter 17
18 0791 0792 0793 0794, 0795 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,8) Loop 2 Loop 2; 2.2 kΩ Xmitter 18 Xmitter 18
19 0796 0797 0798 0799, 0800 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (1,9) Loop 3 Loop 3; 2.2 kΩ Xmitter 19 Xmitter 19
20 0801 0802 0803 0804, 0805 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,0) Loop 4 Loop 4; 2.2 kΩ Xmitter 20 Xmitter 20
1
DBus = Data Bus
2
Xmitter = Transmitter
3
DACM = DACM door contact. Integrating the DACM door contact into the security system is optional. See
DACM Configuration on page 135 for instructions on integrating the DACM door contact into the security system.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 81

Table 13: Location Configuration Parameters (continued)

Location Parameters Device Parameter Selections


These columns show the addresses and These columns show the selections for the “Device” parameter. The Device parameter tells the
defaults for each of the four location control panel where to find the sensor loop (or transmitter) status for each Location.
parameters. These parameters configure
each location. Shaded cells only apply to the
DS7240V2.
1 1 1,2 1,2 3
Location Device Zone Area Zone # On-board DX2010 DX2010 RF Rcvr 1 RF Rcvr 2 DACM
Function Device = 1 Device = 2 Doubled Device = 4 Device = 5 Device = 6
Device = 3 (optional)
21 0806 0807 0808 0809, 0810 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,1) Loop 5 Loop 5; 2.2 kΩ Xmitter 21 Xmitter 21
22 0811 0812 0813 0814, 0815 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,2) Loop 6 Loop 6; 2.2 kΩ Xmitter 22 Xmitter 22
23 0816 0817 0818 0819, 0820 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,3) Loop 7 Loop 7; 2.2 kΩ Xmitter 23 Xmitter 23
24 0821 0822 0823 0824, 0825 DBus Adr 103 DBus Adr 106 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,4) Loop 8 Loop 8; 2.2 kΩ Xmitter 24 Xmitter 24
25 0826 0827 0828 0829, 0830 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,5) Loop 1 Loop 1; 3.65 kΩ Xmitter 25 Xmitter 25
26 0831 0832 0833 0834, 0835 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,6) Loop 2 Loop 2; 3.65 kΩ Xmitter 26 Xmitter 26
27 0836 0837 0838 0839, 0840 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,7) Loop 3 Loop 3; 3.65 kΩ Xmitter 27 Xmitter 27
28 0841 0842 0843 0844, 0845 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,8) Loop 4 Loop 4; 3.65 kΩ Xmitter 28 Xmitter 28
29 0846 0847 0848 0849, 0850 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (2,9) Loop 5 Loop 5; 3.65 kΩ Xmitter 29 Xmitter 29
30 0851 0852 0853 0854, 0855 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,0) Loop 6 Loop 6; 3.65 kΩ Xmitter 30 Xmitter 30
31 0856 0857 0858 0859, 0860 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,1) Loop 7 Loop 7; 3.65 kΩ Xmitter 31 Xmitter 31
32 0861 0862 0863 0864, 0865 DBus Adr 104 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,2) Loop 8 Loop 8; 3.65 kΩ Xmitter 32 Xmitter 32
33 0866 0867 0868 0869, 0870 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,3) Loop 1 Loop 1; 2.2 kΩ Xmitter 33 Xmitter 33
34 0871 0872 0873 0874, 0875 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,4) Loop 2 Loop 2; 2.2 kΩ Xmitter 34 Xmitter 34
35 0876 0877 0878 0879, 0880 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,5) Loop 3 Loop 3; 2.2 kΩ Xmitter 35 Xmitter 35
36 0881 0882 0883 0884, 0885 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,6) Loop 4 Loop 4; 2.2 kΩ Xmitter 36 Xmitter 36
37 0886 0887 0888 0889, 0890 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,7) Loop 5 Loop 5; 2.2 kΩ Xmitter 37 Xmitter 37
38 0891 0892 0893 0894, 0895 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (3,8) Loop 6 Loop 6; 2.2 kΩ Xmitter 38 Xmitter 38
39 0896 0897 0898 0899, 0900 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr DACM
(0) (0) (1) (3,9) Loop 7 Loop 7; 2.2 kΩ Xmitter 39 51Xmitter 39
40 0901 0902 0903 0904, 0905 DBus Adr 105 DBus Adr 107 DBus Adr 50 DBus Adr 51 DACM
(0) (0) (1) (4,0) Loop 8 Loop 8; 2.2 kΩ Xmitter 40 Xmitter 40
1
DBus = Data Bus
2
Xmitter = Transmitter
3
DACM = DACM door contact. Integrating the DACM door contact into the security system is optional. See
DACM Configuration on page 135 for instructions on integrating the DACM door contact into the security system.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 82

Zone Doubling Programming

Zone doubling requires 3.65 k Ω and 2.2 k Ω EOL resistors as shown in Table 13. If zone doubling is
not used, see On-board Location EOL Resistor Value on page 103, and DX2010 Configuration
Options on page 127, for on- and off-board zone EOL resistor configuration. For proper zone doubled
wiring, see the DS7200V2 Installer’s Guide (P/N: 4998153893).

To use both on-board and off-board zone doubling at the same time, use the following steps:
1. Double Locations 1 to 8 with Locations 9 to 16.
a. Set the Device Type for Locations 1 to 16 to 1 (on-board).
b. Set Address 1026 (On-board Location EOL Resistor Value) to 4 (Zone doubled, 2.2 k & 3.65 k
EOL resistors).
c. Use 3.65 k EOL resistors on Locations 1 to 8, and 2.2 k EOL resistors on Locations 9 to 16.
2. Double Locations 25 to 32 with Locations 33 to 40.
a. Set the Device Type for Locations 25 to 40 to 3 (DX2010 zone doubled).
b. Set the DX2010’s DIP switches to Address 107 (Locations 25 to 40). See Table 14.
c. Use 3.65 k EOL resistors on Locations 25 to 32, and 2.2 k EOL resistors on Locations 33 to 40.

Locations 17 to 24 cannot be used for zone doubling when doubling on-board and off-board zones at
the same time. These locations can still be used as RF zones, or as non-doubled zones.

Table 14: DX2010 DIP Switch Settings

DX2010 DIP Switch Settings


DIP S1 S2 S3 S4 S5 S6
Switches
Module 32 16 8 4 2 1
Address
101 OFF OFF OFF OFF OFF OFF
102 OFF OFF OFF OFF OFF ON
103 OFF OFF OFF OFF ON OFF
104 OFF OFF OFF OFF ON ON
105 OFF OFF OFF ON OFF OFF
106 OFF OFF OFF ON OFF ON
107 OFF OFF OFF ON ON OFF
Shaded rows apply only to the DS7240V2.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 83

Location ##, Device

• Address: See Table 13 on page 80


• Default: See Table 13 on page 80
• Selections:
− 0 = No Device Assigned (Disabled)
− 1 = On-board Zone (L-1 to L-8)
− 2 = Wired Zone Expander (DX2010) (configured for 8 inputs)
− 3 = Wired Zone Expander (DX2010) (configured for 16 inputs [zone doubled])
− 4 = RF Receiver 1 (see RF Receiver Configuration on page 123)
− 5 = RF Receiver 2 (see RF Receiver Configuration on page 123)
− 6 = DACM Door Contact (see DACM Configuration on page 135)
Each location in the control panel can be assigned to one of four types for devices:
• The control panel’s on-board sensor loops (L-1 to L-8)
• A DX2010 Input Expander
• A Data Bus RF Zone Expander (Receiver 1 or Receiver 2)
• A DACM’s door contact
Use each location’s Device parameter to assign the location to a device type.
You must exit control panel programming in order to enter the RF ID code. Add RF ID codes after you complete
your programming session. See “Adding RF ID Codes” in the DS7200V2 Installer’s Guide (P/N: 4998153893) for
complete instructions.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 84

Location ##, Zone Function

• Address: See Table 13 on page 80


• Default: See Table 13 on page 80
• Selections: 0 to 15 (see Table 15 for Default Zone Function Types)
The zone function determines how the system responds to changes on the sensor loop assigned to the location.
There are two general categories of zones: 24-hour and Controlled.
• 24-hour Zone: 24-hour zones are always on and cannot be turned off by the user. Faults on 24-hour zones
prevent turning the system on.
• Controlled Zone: Controlled zones are turned on and off when the user turns the system on (armed) and off
(disarmed).
See Table 15 for Zone Function selections.

Table 15: Default Zone Function Type Selections

Zone Function Default Zone Function Type


Selection
0 Disabled
1 24-hour Fire, Normally Open Contact
2 24-hour Fire with Alarm Verification, Normally Open Contact

24-Hour Zones
3 24-hour Voice Active Control Input, Normally Open Contact with EOL Resistor
4 24-hour Tamper (no EOL resistor)
5 24-hour Emergency (no alarm output)
6 24-hour Visible Panic (no alarm output)
7 24-hour Invisible Panic (no alarm output)
8 24-hour Burglary
9 Chime Mode only
10 Controlled Keyswitch, Momentary, All On, Off from Any Armed State Zones
Controlled
11 Controlled Entry/Exit Delay 1
12 Controlled Entry/Exit Delay 2
13 Controlled Follower
14 Controlled Instant
15 Controlled Instant (Perimeter)

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 85

Location ##, Area

• Address: See Table 13 on page 80


• Default: 1 (Area 1)
• Selections:
− 0 = No Area Assigned (Disabled)
− 1 = Assign Location ## to Area 1
− 2 = Assign Location ## to Area 2
− 3 = Assign Location ## to Area 3 (DS7240V2 only)
− 4 = Assign Location ## to Area 4 (DS7240V2 only)
This parameter assigns an area to a location. Each location can only be assigned to one area.

Location ##, Zone Number

• Address: See Table 13 on page 80


• Default: See Table 13 on page 80
• Selections: 0,1 to 4,0
This parameter determines the zone number that appears on keypad displays, the control panel event log and at
the optional printer. This is also the zone number reported to the ARC.

This parameter can be used to create a Zone 1 for each Area.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 86

Location ##, Zone Text

• Address: See Table 16


• Default: See Table 16
• Selections: See Table 3 on page 7

Table 16: Location Text Addresses/Defaults

Location Address Default Location Address Default


1 1650 Location 1 Text 21 2290 Location 21 Text
2 1682 Location 2 Text 22 2322 Location 22 Text
3 1714 Location 3 Text 23 2354 Location 23 Text
4 1746 Location 4 Text 24 2386 Location 24 Text
5 1778 Location 5 Text 25 2418 Location 25 Text
6 1810 Location 6 Text 26 2450 Location 26 Text
7 1842 Location 7 Text 27 2482 Location 27 Text
8 1874 Location 8 Text 28 2514 Location 28 Text
9 1906 Location 9 Text 29 2546 Location 29 Text
10 1938 Location 10 Text 30 2578 Location 30 Text
11 1970 Location 11 Text 31 2610 Location 31 Text
12 2002 Location 12 Text 32 2642 Location 32 Text
13 2034 Location 13 Text 33 2674 Location 33 Text
14 2066 Location 14 Text 34 2706 Location 34 Text
15 2098 Location 15 Text 35 2738 Location 35 Text
16 2130 Location 16 Text 36 2770 Location 36 Text
17 2162 Location 17 Text 37 2802 Location 37 Text
18 2194 Location 18 Text 38 2834 Location 38 Text
19 2226 Location 19 Text 39 2866 Location 39 Text
20 2258 Location 20 Text 40 2898 Location 40 Text
All control panel text is programmed from the text keypad in a special text-programming mode. See Text Entry
Addresses on page 7 for text programming instructions.
Enter up to 16 characters to describe each location.
Shaded cells only apply to the DS7240V2.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 87

RF Transmitters and Zone States

With the exception of the point transmitter, all RF transmitters show only two electrical zone states (Normal and
Faulted).

The RF3401E Point Transmitter can monitor both a reed switch (magnet) and a supervised sensor
loop. After the door/window transmitter's ID is added, the control panel shows one of the following
status messages depending on how the door/window transmitter is configured:
- "No magnet, no loop": the reed switch is open (no magnet is present), and there is no device
connected to the sensor loop
- "Reed switch closed": the reed switch is closed by a magnet
- "Loop closed": a device is connected to the sensor loop
- "Reed closed, loop closed": the reed switch is closed by a magnet, and a device is connected to
the sensor loop
The RF3405E Inertia Transmitter operates similarly as the RF3401E described above, however the
RF3405E can monitor both a reed switch (magnet) and a supervised sensor loop or a reed switch and
an inertia sensor loop. It cannot monitor a supervised sensor loop and an inertia sensor loop.

For this example, mount the point transmitter on a doorjamb, and mount its magnet on the door. Close the door
to place the magnet next to the reed switch. The control panel now recognizes the reed switch to be in a normal
(not faulted) state. From this point forward, it shows the zone (door/window transmitter) as shorted (faulted)
whenever it sees the reed switch faulted. It shows the zone as normal when the reed switch returns to normal,
even though the sensor loop remains faulted.
To continue with this example, connect a contact on a window near the door. Wire the contact and the EOL
resistor to the Door/Window transmitter’s sensor loop and close the window. The control panel now recognizes
the sensor loop to be in a normal (not faulted) state. From this point forward, it shows the zone (door window
transmitter) as faulted whenever it sees either the sensor loop or the reed switch faulted. It only shows the zone as
normal when both the reed switch and the sensor loop return to normal. When only the reed switch is monitored,
only the Normal and Shorted (Faulted) zone states are shown.

Cut out reed switch if not used.

Disabling a Zone (RF or Wired)

To disable a wired or wireless (RF) zone, do any of the following:


• Set the location’s device parameter to 0 (zero). See Location ##, Device on page 83.
• Set the location’s zone function parameter to 0 (zero). See Location ##, Zone Function on page 84.
• Set the location’s area parameter to 0 (zero). See Location ##, Area on page 85.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 88

4.5.2 Zone Function Configuration


The control panel can monitor any combination of up to 40 sensor loops and/or RF transmitters. Each sensor
loop or transmitter is assigned to a location. Each location is assigned to one of 15 Zone Functions so that the
control panel knows how to respond to sensor loop or transmitter changes.
See Table 17 for Zone Function Configuration parameter addresses and defaults (defaults are shown in bold).

Table 17: Zone Function Configuration Parameters

Zone Zone Function Type Pulse Pulse Options Options Report Alarm Restoral
Function Count Count Time 1 2 Enable Route Route
Trouble
Response
1 Adr 0906 Adr 0907 Adr 0908 Adr 0909 Adr 0910 Adr 0911 Adr 0912 Adr 0913
(1: 24-hr Fire) (0) (0) (0) (2) (11) (1) (1)
2 Adr 0914 Adr 0915 Adr 0916 Adr 0917 Adr 0918 Adr 0919 Adr 0920 Adr 0921
(2: 24-hr Fire with Verify) (0) (0) (0) (7) (9) (1) (1)
3 Adr 0922 Adr 0923 Adr 0924 Adr 0925 Adr 0926 Adr 0927 Adr 0928 Adr 0929
(3: 24-hr Control Input) (0) (0) (1) (0) (10) (1) (1)
4 Adr 0930 Adr 0931 Adr 0932 Adr 0933 Adr 0934 Adr 0935 Adr 0936 Adr 0937
(4: 24-hr Tamper) (0) (0) (8) (7) (9) (1) (1)
5 Adr 0938 Adr 0939 Adr 0940 Adr 0941 Adr 0942 Adr 0943 Adr 0944 Adr 0945
(5: 24-hr Emergency) (0) (0) (0) (5) (9) (1) (1)
6 Adr 0946 Adr 0947 Adr 0948 Adr 0949 Adr 0950 Adr 0951 Adr 0952 Adr 0953
(6: 24-hr Visible Panic) (0) (0) (0) (5) (9) (1) (1)
7 Adr 0954 Adr 0955 Adr 0956 Adr 0957 Adr 0958 Adr 0959 Adr 0960 Adr 0961
(7: 24-hr Invisible Panic) (0) (0) (0) (5) (9) (1) (1)
8 Adr 0962 Adr 0963 Adr 0964 Adr 0965 Adr 0966 Adr 0967 Adr 0968 Adr 0969
(8: 24-hr Burglary) (0) (0) (0) (7) (9) (1) (1)
9 Adr 0970 Adr 0971 Adr 0972 Adr 0973 Adr 0974 Adr 0975 Adr 0976 Adr 0977
(0: Chime Mode only) (0) (0) (0) (0) (9) (1) (1)
10 Adr 0978 Adr 0979 Adr 0980 Adr 0981 Adr 0982 Adr 0983 Adr 0984 Adr 0985
(10: Controlled Keyswitch) (0) (0) (8) (7) (9) (1) (1)
11 Adr 0986 Adr 0987 Adr 0988 Adr 0989 Adr 0990 Adr 0991 Adr 0992 Adr 0993
(11: Entry/Exit Delay 1) (0) (0) (0) (7) (9) (1) (1)
12 Adr 0994 Adr 0995 Adr 0996 Adr 0997 Adr 0998 Adr 0999 Adr 1000 Adr 1001
(12: Entry/Exit Delay 2) (0) (0) (0) (7) (9) (1) (1)
13 Adr 1002 Adr 1003 Adr 1004 Adr 1005 Adr 1006 Adr 1007 Adr 1008 Adr 1009
(13: Controlled Follower) (0) (0) (0) (7) (9) (1) (1)
14 Adr 1010 Adr 1011 Adr 1012 Adr 1013 Adr 1014 Adr 1015 Adr 1016 Adr 1017
(14: Controlled Instant) (0) (0) (0) (7) (9) (1) (1)
15 Adr 1018 Adr 1019 Adr 1020 Adr 1021 Adr 1022 Adr 1023 Adr 1024 Adr 1025
(14: Controlled Instant) (0) (0) (4) (7) (9) (1) (1)

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 89

Zone Wiring Configuration

The operation and configuration of the zone function depends on the method of zone wiring. A zone is a “Single
EOL resistor” zone if the zone is supervised with one end of line resistor. Table 18 defines configuration options
for single EOL resistor zones.

Table 18: Single EOL Resistor Zone Configuration Options

Device Selection as Address for Zone Wiring Configuration


shown in Table 13 Configuration Options Options
1 1026 1, 2, 3
2 1257 to 1261 4 to 11
4 or 5 1249 4 to 7
For On-board zones, device is 1. See On-board Location EOL Resistor Value on page 103.
For Wired-Expander zones, device is 2. See DX2010 Configuration Options on page 127.
For RF zones, Device is 4 or 5. See RF Receiver Configuration on page 123.
Tamper-wired zones, Zone-doubled zones, or No EOL resistor zones function differently. These non-single EOL
resistor zones are defined by the configuration options shown in Table 19.

Table 19: Tamper-wired, Zone Doubled, and No EOL Resistor


Zone Configuration Options

Device Selection as Address for Zone Wiring Configuration


shown in Table 13 Configuration Options Options
1 1026 0, 4, 5, 6
2 1257 to 1261 0 to 3
3 N/A Always
4 or 5 1249 0 to 3

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 90

Zone Function Type, Zone Function

• Address: See Table 17 on page 88


• Default: See Table 17 on page 88
• Selections: 0 to 15 (see Table 20)
See Table 20 for a description of each zone function type and the events and reports associated with that Zone
Function type, when the zone is wired using one of the following configurations: single EOL resistor, tamper-
wired, zone-doubled, or no EOL resistor.
• Controlled Zone: Controlled zones are turned on and off when the user turns the system on (armed) and off
(disarmed).
• 24-hour Zone: 24-hour zones are always on and cannot be turned off by the user.

Table 20: Zone Function Type Options

Zone Function Type Wiring Description Events/Reports


Configuration
0 Chime Single EOL No alarm or trouble response to opens or shorts (Chime Mode No events/reports.
Mode Only Resistor only).
Tamper-Wired, No alarm or trouble response to faults (Chime Mode only).
Zone-Doubled,
No EOL Resistor
1 24-hr Fire Single EOL Short on sensor loop starts Fire Alarm response. Open on sensor Fire Alarm {75-77}, Fire Missing {78}, Fire
Resistor loop starts trouble response. Activates Fire Alarm Output Restore from Alarm {79}, Fire Restore
(Temporal Code 3). from Missing {174}, Fire Trouble {80},
Tamper-Wired, Fault on sensor loop starts Fire Alarm response. Activates Fire Fire Trouble Restore {81}, Fire Bypass
Zone-Doubled, Alarm Output (Temporal Code 3). {26-27}, Swinger Shunt {33}, Restoral
No EOL Resistor from Swinger Shunt {173}, Fire
Unbypass {34}
2 24-hour Single EOL Short on sensor loop starts the verification process. Fire Alarm {75}, Fire Unverified {77}, Fire
Fire with Resistor Control panel activates Fire Verification output function for 15 Missing {78}, Fire Restore from Alarm
Alarm sec to reset smoke detectors. See Table 25 on page 112 for {79}, Fire Restore from Missing {174},
Verification Fire Verification Output Function information. Fire Trouble {80}, Fire Trouble Restore
{81}, Fire Bypass {26-27}, Fire Unbypass
Short on sensor loop within 120 sec of reset starts alarm
{34}
response. If zone remains normal or open for the 120-second
verification window, there is no alarm response.
Open on sensor loop starts trouble response.
Activates Fire Alarm Output (Temporal Code 3).
Tamper-Wired, Fault on sensor loop starts the verification process. Fire Alarm {75}, Fire Unverified {77}, Fire
Zone-Doubled, Control panel activates Fire Verification output function for 15 Missing {78}, Fire Restore from Alarm
No EOL Resistor sec to reset smoke detectors. See Table 25 on page 112 for {79}, Fire Restore from Missing {174},
Fire Verification Output Function information. Fire Bypass {26-27}, Fire Unbypass {34}
Fault on sensor loop within 120 sec of reset starts alarm
response. If zone remains normal for the 120-second verification
window, there is no alarm response.
Activates Fire Alarm Output (Temporal Code 3).
3 24-hr Single EOL Can be used to control various system functions. See Options 1 Trouble {139}, Trouble Restore {146}
Control Resistor for Zone Function Type 3 (24-hr Control Input) on page 97 for
Input more information. Only Trouble on Open option is available.
Tamper-Wired, Can be used to control various system functions. See Options 1 No events/reports.
Zone-Doubled, for Zone Function Type 3 (24-hr Control Input) on page 97 for
No EOL Resistor more information.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 91

Table 20: Zone Function Type Options (continued)

Zone Function Type Wiring Description Events/Reports


Configuration
4 24-hr Single EOL Can create a Tamper Alarm or a Tamper Trouble based on option Alarm {3}, Cross Alarm {10}, Unverified
Tamper Resistor programming. See Options 1 for Zone Function Type 4 (24-Hour Cross {17}, Bypass {30-31}, Swinger
Tamper) on page 98 for more information. Shunt {33}, Unbypass {36}, Swinger
Short or Open causes alarm response if no Trouble Option. Shunt Restore {173}, Trouble {139},
Trouble Restore {146}, Missing Trouble
Tamper-Wired, Can create a Tamper Alarm or a Tamper Trouble based on option
{88}, Restore from Alarm {112}, Restore
Zone-Doubled, programming. See Options 1 for Zone Function Type 4 (24-Hour
from Missing Trouble {176}
No EOL Resistor Tamper) on page 98 for more information.
Fault causes alarm response if no Trouble Option.
5 24-hr Single EOL Short or open causes alarm response if no Trouble Option. Alarm {4}, Cross Alarm {11}, Unverified
Emergency Resistor Cross {17}, Bypass {30-31}, Swinger
Tamper-Wired, Fault causes alarm response if no Trouble Option. Shunt {33}, Unbypass {36}, Swinger
Zone-Doubled, Shunt Restore {173}, Trouble {140},
No EOL Resistor Trouble Restore {147}, Missing Trouble
{88}, Restore from Alarm {113}, Restore
from Missing Trouble {176}
6 24-hour Single EOL Short or open causes alarm response if no Trouble Option. Alarm {5}, Cross Alarm {12}, Unverified
Visible Resistor Cross {17}, Bypass {30-31}, Swinger
Panic Shunt {33}, Unbypass {36}, Swinger
Tamper-Wired, Fault causes alarm response if no Trouble Option. Shunt Restore {173}, Trouble {141},
Zone-Doubled, Trouble Restore {148}, Missing Trouble
No EOL Resistor {88}, Restore from Alarm {114}, Restore
from Missing Trouble {176}
7 24-hr Single EOL Short or open causes alarm response if no Trouble Option. Alarm {6}, Cross Alarm {13}, Unverified
Invisible Resistor No alarm tones or alarm display at keypad even if the Alarm Cross {17}, Bypass {30-31}, Swinger
Panic Output option is enabled. Shunt {33}, Unbypass {36}, Swinger
Shunt Restore {173}, Trouble {142},
Tamper-Wired, Fault causes alarm response if no Trouble Option.
Trouble Restore {149}, Missing Trouble
Zone-Doubled, No alarm tones or alarm display at keypad even if the Alarm {88}, Restore from Alarm {115}, Restore
No EOL Resistor Output option is enabled. from Missing Trouble {176}
8 24-hr Single EOL Short or open causes alarm response if no Trouble Option. Burglary {7}, Cross Alarm {14}, Unverified
Burglary Resistor Trouble option generates alarm response when Area is armed All Cross {17}, Bypass {30-31}, Swinger
On/Perimeter Only/Partial On, Trouble response when area is Shunt {33}, Unbypass {36}, Swinger
Off. Shunt Restore {173}, Trouble {143},
Tamper-Wired, Fault causes alarm response if no Trouble Option. Trouble option Trouble Restore {150}, Missing Alarm
Zone-Doubled, generates alarm response when Area is armed All On/Perimeter {87}, Missing Trouble {88}, Restore from
No EOL Resistor Only/Partial On, Trouble response when area is Off. Alarm {116}, Restore from Missing Alarm
{175}, Restore from Missing Trouble
{176}
9 Reserved
10 Controlled Single EOL See Options 1 for Zone Function Type 10 (Controlled Alarm {9}, Bypass {28,29}, Forced Pt
Keyswitch Resistor Keyswitch) on page 98 for more information. Can be {32}, Swinger Shunt {33}, Unbypass
Tamper-Wired, programmed for a momentary or maintained keyswitch. Can also {35}, Swinger Shunt Restore {173},
Zone-Doubled, be programmed as Exit Terminator Button. See “Keyswitch” in the Trouble {145}, Trouble Restore {152},
No EOL Resistor DS7200V2 Installer’s Guide (P/N: 4998153893) for additional Missing Alarm {87}, Missing Trouble {88},
keyswitch information. Restore from Alarm {118}, Restore from
Missing Alarm {175}, Restore from
Missing Trouble {176}

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 92

Table 20: Zone Function Type Options (continued)

Zone Function Type Wiring Description Events/Reports


Configuration
11 Controlled Single EOL When control panel is On, short or open starts Entry Delay 1 if no Alarm {8}, Cross Alarm {15}, Unverified
Entry/Exit Resistor Trouble Option. Cross {17}, Bypass {28,29}, Forced Pt
Delay 1 Follows Entry Delay 1 or 2. Follows Exit Delay. {32}, Swinger Shunt {33}, Unbypass
{35}, Swinger Shunt Restore {173},
If this Zone Function type is programmed for Trouble and a
Trouble {144}, Trouble Restore {151},
trouble condition occurs when the control panel is armed, an
Missing Alarm {87}, Missing Trouble {88},
alarm event is generated. If a trouble condition occurs when the
Restore from Alarm {117}, Restore from
control panel is disarmed, a trouble event is generated. Entry/Exit
Missing Alarm {175}, Restore from
Delay and Start Entry Delay settings are ignored for trouble
Missing Trouble {176}
events.
Tamper-Wired, When control panel is On, fault starts Entry Delay 1 if no Trouble
Zone-Doubled, Option.
No EOL Resistor Follows Entry Delay 1 or 2. Follows Exit Delay.
If this Zone Function type is programmed for Trouble and a
trouble condition occurs when the control panel is armed, an
alarm event is generated. If a trouble condition occurs when the
control panel is disarmed, a trouble event is generated. Entry/Exit
Delay and Start Entry Delay settings are ignored for trouble
events.
12 Controlled Single EOL When control panel is On, short or open starts Entry Delay 2 if no Alarm {8}, Cross Alarm {15}, Unverified
Entry/Exit Resistor Trouble Option. Cross {17}, Bypass {28,29}, Forced Pt
Delay 2 Follows Entry Delay 1 or 2. Follows Exit Delay. {32}, Swinger Shunt {33}, Unbypass
{35}, Swinger Shunt Restore {173},
If this Zone Function type is faulted or bypassed at the start of
Trouble {144}, Trouble Restore {151},
Exit Delay or during Exit Delay, Exit Time is set to Exit Delay 2.
Missing Alarm {87}, Missing Trouble {88},
If this Zone Function type is programmed for Trouble and a Restore from Alarm {117}, Restore from
trouble condition occurs when the control panel is armed, an Missing Alarm {175}, Restore from
alarm event is generated. Missing Trouble {176}
If a trouble condition occurs when the control panel is disarmed,
a trouble event is generated.
Entry/Exit Delay and Start Entry Delay settings are ignored for
trouble events.
Tamper-Wired, When control panel is On, fault starts Entry Delay 2 if no Trouble
Zone-Doubled, Option.
No EOL Resistor Follows Entry Delay 1 or 2. Follows Exit Delay.
If this Zone Function type is faulted or bypassed at the start of
Exit Delay or during Exit Delay, Exit Time is set to Exit Delay 2.
If this Zone Function type is programmed for Trouble and a
trouble condition occurs when the control panel is armed, an
alarm event is generated.
If a trouble condition occurs when the control panel is disarmed,
a trouble event is generated.
Entry/Exit Delay and Start Entry Delay settings are ignored for
trouble events.
13 Controlled Single EOL Follows Exit Delay. Alarm {9} reports, Cross Alarm {16},
Follower Resistor Follows, but cannot start Entry Delay. Unverified Cross {17}, Bypass {28,29},
Tamper-Wired, Instant if first. Forced Pt {32}, Swinger Shunt {33},
Zone-Doubled, Unbypass {35}, Missing Alarm {87},
If this Zone Function type is programmed for Trouble and a
No EOL Resistor Swinger Shunt Restore {173}, Trouble
trouble condition occurs when the control panel is armed, an
{145}, Trouble Restore {152}, Missing
alarm event is generated.
Trouble {88}, Restore from Alarm {118},
If a trouble condition occurs when the control panel is Restore from Missing Alarm {175},
disarmed, a trouble event is generated.
Restore from Missing Trouble {176}
Entry/Exit Delay and Start Entry Delay settings are ignored for
trouble events.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 93

Table 20: Zone Function Type Options (continued)

Zone Function Type Wiring Description Events/Reports


Configuration
14 Controlled Single EOL When armed, short or open causes alarm response. Alarm {9} reports, Cross Alarm {16},
Instant Resistor Short or open during Entry/Exit Delay creates an instant alarm, Unverified Cross {17}, Bypass {28,29},
which terminates the Exit Delay period (see Panel Arming Forced Pt {32}, Swinger Shunt {33},
Options on page 46). Unbypass {35}, Missing Alarm {87},
Swinger Shunt Restore {173}, Trouble
If this Zone Function type is programmed for Trouble and a
{145}, Trouble Restore {152}, Missing
trouble condition occurs when the control panel is armed, an
Trouble {88}, Restore from Alarm {118},
alarm event is generated.
Restore from Missing Alarm {175},
If a trouble condition occurs when the control panel is disarmed, Restore from Missing Trouble {176}
a trouble event is generated.
Tamper-Wired, When armed, fault causes alarm response.
Zone-Doubled, Fault during Entry/Exit Delay creates an instant alarm, which
No EOL Resistor terminates the Exit Delay period (see Panel Arming Options on
page 46).
If this Zone Function type is programmed for Trouble and a
trouble condition occurs when the control panel is armed, an
alarm event is generated.
If a trouble condition occurs when the control panel is disarmed,
a trouble event is generated.
15 24-hr Door Single EOL Does not follow Entry or Exit Delay. Alarm, 24-hour Burg {7}, Restoral, 24-
Resistor Short or open during Entry/Exit Delay creates an instant alarm, hour Burg {116}, Trouble, 24-hour Burg
which terminates the Exit Delay period (see Panel Arming {143}, Restoral, 24-hour Burg {150}, RF
Options on page 46). BatteryLow {121}, RF Battery Restoral
{122}, RF Tamper Trouble {123}, RF
When the zone is faulted, and the area is disarmed, a timer starts.
Tamper Restoral {124}, Restore from
If the zone remains faulted for the programmed time (see Pulse
Missing Alarm {175}, Restore from
Count Time on page 94), the zone creates an alarm. If the zone is
Missing Trouble {176}
restored before the programmed time ends, no alarm is created.
If this Zone Function type is programmed for Trouble and a
trouble condition occurs when the control panel is armed, an
alarm event is generated.
If a trouble condition occurs when the control panel is disarmed,
a trouble event is generated.
Tamper-Wired, Does not follow Entry or Exit Delay.
Zone-Doubled, Fault during Entry/Exit Delay creates an instant alarm, which
No EOL Resistor terminates the Exit Delay period (see Panel Arming Options on
page 46).
When the zone is faulted, and the area is disarmed, a timer starts.
If the zone remains faulted for the programmed time (see Pulse
Count Time on page 94), the zone creates an alarm. If the zone is
restored before the programmed time ends, no alarm is created.
If this Zone Function type is programmed for Trouble and a
trouble condition occurs when the control panel is armed, an
alarm event is generated.
If a trouble condition occurs when the control panel is disarmed,
a trouble event is generated.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 94

Pulse Count

• Address: See Table 17 on page 88


• Default: See Table 17 on page 88
• Selections:
− 0 = Activate on first off-normal, debounce on-board points for 160 ms
− 1 = Activate on first off-normal, debounce on-board points for 50 ms
− 2-15 = number of pulses required within the programmed Pulse Count Time for an alarm to occur
This parameter determines the number of times a sensor loop must pulse (electronically off-normal) in the Pulse
Count Time before the control panel declares the zone faulted. This applies to both on- and off-board zones.
• Setting the Pulse Count to 0 (zero) tells the control panel to look for 1 pulse lasting at least 160 ms before
declaring the zone faulted.
• Setting the Pulse Count to 1 tells the control panel to look for 1 pulse lasting at least 50 ms before declaring
the zone faulted.
Leave the Pulse Count parameter at the default setting (0) unless advised by Bosch Technical Service.
If a single pulse starts the Pulse Count Timer and lasts 20 sec, the control panel declares the zone
faulted regardless of the Pulse Count.

Pulse Count Time

• Address: See Table 17 on page 88


• Default: See Table 17 on page 88
• Selections: 0-15 (see Table 21 and Table 22)
When the control panel detects a pulse (electronically off-normal), it starts a timer and waits the time selected in
this parameter to reach the Pulse Count and declare the zone faulted.
The Pulse Count Time only applies when the Pulse Count is greater than 1, or the 24-Hour Door Zone Function
Type is selected.
Use Table 21 when Location ##, Device is set to 1 (on-board zone). Use Table 22 when Location ##, Device is set to 2,
3, 4, or 5 (off-board zones).

If a single pulse starts the Pulse Count Timer and lasts 20 sec, the control panel declares the zone
faulted regardless of the Pulse Count.

Table 21: On-board Zone Pulse Count Time Selections

Pulse Count Time Selections for 50 ms Pulse Count Time Selections for 160 ms
Zone Scan Time (on-board zones) Zone Scan Time (on-board zones)
Selection Pulse Count Time Selection Pulse Count Time
0 0.5 sec 8 20 sec
1 1 second 9 30 sec
2 2 sec 10 40 sec
3 3 sec 11 50 sec
4 4 sec 12 60 sec
5 5 sec 13 90 sec
6 10 sec 14 120 sec
7 15 sec 15 200 sec

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 95

Table 22: Off-board Zone Pulse Count Time Selections

Pulse Count Time for Off-board Zones


Selection Pulse Count Time Selection Pulse Count Time
0 10 sec 8 20 sec
1 20 second 9 30 sec
2 40 sec 10 40 sec
3 60 sec 11 50 sec
4 80 sec 12 60 sec
5 100 sec 13 90 sec
6 200 sec 14 120 sec
7 300 sec 15 200 sec
Pulse Count/Pulse Count Time Example:
Follow these steps to program a zone function to detect four 60 ms pulses within 10 sec before it declares the zone
off-normal:
1. Enter “4” in the Pulse Count address of the Zone Function you are configuring. “4” identifies the number of
pulses the control panel must receive.
2. Since your time span is 10 sec, this zone function uses a zone scan time of 60 ms and is only for on-board
zones (see left side of Table 21). The selection for 10 sec is 6. Enter “6” into the Pulse Count Time address of
the Zone Function you are configuring.

When using the 24-Hour Door Zone Function Type, Pulse Count Time determines how long the zone
must be faulted when the area is disarmed before creating an alarm on the zone (range of 0.5 to 300
sec).

Options 1, Zone Function ##

Options 1 for Zone Function Types 0 to 2, 5 to 8, 11 to 15


• Address: See Table 17 on page 88
• Default: See Table 17 on page 88
• Selections: 0 to 15
Enter This Data Digit to Select Options
Options 1, Zone Function 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Enabled •
Enable Alarm Event Abort • • • • • • • •
Voice Verification • • • • • • • •
Armed for Perimeter Only Mode • • • • • • • •
Sensor Trouble Monitor • • • • • • • •
The option chart above applies to all zone function types except the following:
• Zone Function Type 3 (24-hr Control Input)
• Zone Function Type 4 (24-hr Tamper)
• Zone Function Type 10 (Controlled Keyswitch)
The following sub-sections explain how to program the zone function types listed above.
Zone Function Type 9 is reserved and cannot be programmed.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 96

• Alarm Event Abort (Non-Fire Zones Only): If enabled, this option assigns the Abort Window to a zone
function. See Alarm Event Abort Window on page 106 to learn how to set the Alarm Event Abort Window.
− If a user acknowledges a non-fire alarm zone event by entering their PIN before the Alarm Event Abort
Window expires, the following events occur:
− The alarm event is aborted. Alarm, Cancel and Restoral reports associated with the alarm are not
transmitted and the event becomes a Local Only event.
− A Cancel window starts with the initiation of the alarm event and follows the Bell Time. If the user
acknowledges the alarm inside the Cancel window (Bell Time), a Cancel {38} or a Fire Cancel {39} report
is sent. If the Abort Window is enabled, the Cancel report is sent if the user acknowledges the alarm after
the Abort window has expired, but before the Bell Time expires.
− The user hears a unique three long beep tone at the keypad.
− The text keypads indicate that the alarm was aborted on the display. It appears as a slow flash in Alarm
Memory at LED keypads.

The Alarm Event Abort option has no effect on Fire and Fire with Verification Zone Function types.
This option does not apply to alarm events initiated by the ABC Keys, the Duress PIN or the keyfob
Panic function.
• Voice Verification: If enabled, this option allows the control panel to control a 2-way Voice Verification
Module. This module allows the ARC personnel to verify alarms with a two-way voice session with the
premises. There are two other module connections to the control panel: the programmable relay output
programmed with the Voice Request output function, and a zone programmed as a Voice Active zone. The
control panel must also have one or more zones with the Voice Verification option selected.
− When a zone with Voice Verification generates an alarm event, the following events occur:
− The control panel transmits the alarm report to the receiver at the ARC.
− When the ARC receiver acknowledges the report, the control panel activates the Voice Request output
function. All reports are delayed. The Voice Verification Module has 30 sec to start a verification session.
− The verification module shorts the Voice Active input when it starts a verification session.
− When the Voice Active zone is shorted, the control panel silences the non-fire alarm outputs. Only the
user can silence a fire alarm output.
− As long as the Voice Active zone is shorted, the control panel continues to keep reports buffered.
− The Voice Verification Module ends the voice session by removing the short from the Voice Active zone.
Normal reporting (communication) resumes. If any Bell Time remains, the alarm outputs activate for the
remainder of Bell Time.
• Armed for Perimeter Only Mode: If enabled, this option determines the zones that arm when the user arms
the system Perimeter Only. Only those zones assigned to a Zone Function (Controlled Zone Function types)
with this option enabled are armed.

If a 24-Hour Door Zone is configured for Perimeter Only arming, it functions as a Controlled Instant
zone when the area is armed Perimeter Only. If the zone is not configured for Perimeter Only arming,
then it functions as a 24-Hour Door zone when the area is armed Perimeter Only (timer begins when
zone is faulted).

• Sensor Trouble Monitor: This option enables/disables reporting the sensor trouble monitor fault condition.
This option does not apply to fire zone types or non-fire 24-hour zone types. See Sensor Monitor Time on page
105 for a complete description of the Sensor Trouble Monitor parameter.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 97

Options 1 for Zone Function Type 3 (24-hr Control Input)


• Address: See Table 17 on page 88
• Default: See Table 17 on page 88
• Selections: 1 to 4, 9 to 12
The 24-hour Control Input zone function type uses the following parameter option chart.
Enter This Data Digit to Select Options
24-hour Control Input Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Voice Active Control Input • •
Alternate Communication Path Fault Input • •
Alarm Reset Control Input • •
Silence Outputs Control Input • •
No EOL Resistor Required • • • •

• Voice Active Control Input: If enabled, this option functions as a Voice Active zone. The control panel
must be off-hook and sending a report from a zone with the Voice Verification option selected. If the input
goes into “alarm” within 30 sec after the report is sent, all alarm outputs and keypad sounders assigned to the
same area as the input zone are silenced. Activation of this input does not create any events in the history log
or send any reports. When the input restores from “alarm,” the audible devices will resume sounding if any
bell time remains. The keypad sounders return to the alarm sound.
• Alternate Communication Path Fault Control Input: If enabled, this option allows various external
modules to be connected for sending reports. This option also allows an external module to signal that it is
unable to send reports. When this option goes into “alarm,” the control panel initiates a System Trouble
condition. Event 167 is placed in the history log and its report is sent if there is means of sending the report.
When this input restores from “alarm,” Event 168 is placed in the history log and its report is sent. The
System Trouble condition clears based on the configuration of the “Phone Line Fault Requires Reset” option
(see Phone Line Options on page 14).
• Alarm Reset Control Input: If enabled, this option allows the ARC to communicate with the control panel
through an external module and remotely reset the area. This reset can only occur if the control panel is
disarmed. Activation of this option does not create any events in the history log or send any reports.
• Silence Outputs Control Input: If enabled, this option functions as a bell silence zone. When the input goes
into “alarm,” all alarm outputs and keypad sounders assigned to the same area as the input zone are silenced.
The conditions are silenced as soon as the input goes active. Activation of this input does not create any
events in the history log or send any reports. When the input restores from “alarm,” the audible devices
resume sounding if any bell time remains. The keypad sounders return to the alarm sound.
• No EOL Resistor Required: This option determines whether the input zone functions with normal EOL
resistor supervision or without any EOL resistor supervision.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 98

Options 1 for Zone Function Type 4 (24-Hour Tamper)


• Address: See Table 17 on page 88
• Default: See Table 17 on page 88
• Selections: 0, 2, 8, 10
The 24-hour Tamper zone function type uses the following parameter option chart.
Enter This Data Digit to Select Options
24-hour Tamper Input Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Reserved
Voice Verification • •
Reserved
No EOL Resistor Required • •
See the option descriptions for “Voice Verification” and “No EOL Resistor Required” in Options 1 for Zone
Function Type 3 (24-hr Control Input) on page 97.
Options 1 for Zone Function Type 10 (Controlled Keyswitch)
• Address: See Table 17
• Default: 8 (Momentary, All On, Off from Any Armed State)
• Selections:
− 0 = Maintained, All On, Off from Any Armed State
− 1 = Maintained, All On, No Off
− 2 = Maintained, No On, Off from Any Armed State
− 4 = Maintained, Perimeter Only, Off from Any Armed State
− 5 = Maintained, Perimeter Only, No Off
− 6 = Maintained, No On, Off from Perimter Only or Partial On Arming
− 8 = Momentary, All On, Off from Any Armed State
− 9 = Momentary, All On, No Off
− 10 = Momentary, No On, Off from Any Armed State
− 12 = Momentary, Perimeter Only, Off from Any Armed State
− 13 = Momentary, Perimeter Only, No Off
− 14 = Momentary, No On, Off from Perimeter Only or Partial On Arming
− 15 = Exit Terminator Button
• Momentary Keyswitch: To silence alarms (stop Alarm output), operate the keyswitch. If the area is armed,
operating the keyswitch to silence the alarm also disarms the area. If the area is disarmed, operating a
momentary keyswitch to silence the alarm does not arm the area.
• Maintained Keyswitch: To silence alarms (stop Alarm output) while the area is armed, turn the keyswitch to
the disarmed position. The control panel disarms the area and silences alarms. To silence alarms (stop Alarm
output) while the area is disarmed, turn the keyswitch to the armed position (the control panel does not arm)
and then return to the disarmed position.
• Exit Terminator Button: This zone function activates in the same manner as the momentary keyswitch.
When Exit Delay is active, operating the exit terminator button terminates Exit Delay and immediately arms
the control panel. If Chime Mode is enabled and Exit Delay is not active, pressing the exit terminator button
activates the chime tone and the button functions as a doorbell.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 99

Options 2, Zone Function ##

• Address: See Table 17 on page 88


• Default: See Table 17 on page 88
• Selections: 0 to 15
Enter This Data Digit to Select Options
Options 2, Zone Function 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Enabled •
Swinger Shunt • • • • • • • •
Alarm Output • • • • • • • •
Can Be Bypassed or Force Armed • • • • • • • •
Cross-Zone • • • • • • • •

• Swinger Shunt: If enabled, this option activates Swinger Shunt functions for Alarm Output (Functions 1|5,
1|8 to 1|12, and 8|8) and Zone Reporting. See Swinger Count for Zone Reports on page 105 for additional
Swinger information.
• Alarm Output: If enabled, this option activates the alarm output functions (Output Function 1|8 to 1|12, and
8|8, see Output Parameters on page 107) for alarm events.
• Can Be Bypassed or Force Armed: Only zones assigned to a Zone Function with this option enabled can be
bypassed or force armed. Bypassed zones remain bypassed for the arming cycle. Force armed zones return to
the system automatically if they restore during the arming cycle. 24-hour zones (fire and non-fire) can be
made bypassable with this option.
• Cross-Zone: If enabled, this option creates a Cross-Zone Zone Function type using the following conditions:
− When any zone assigned to the Cross-Zone Function detects a pulse, the control panel starts a 60-second
timer.
− If a second zone assigned to the same Cross-Zone Function detects a pulse, the control panel creates a
Cross-Zone Alarm event for both zones.
− A second pulse on the first zone does not create an alarm event.
− If a single pulse on a Cross-Zone lasts 20 sec, the control panel creates an alarm event for that zone only;
it is not a Cross-Zone event.
− If programmed for unverified event reporting (see Zone Response Options on page 103), the control panel
sends an Unverified Cross {17} or a Fire Unverified {77} report when a pulse is detected without another
cross zone pulse to verify it. The Unverified event is not sent until the 60-second timer that starts when
the first zone is violated has expired.

Do not configure 24-Hour Door and 24-Hour Fire with Alarm Verification zone function types as Cross-
Zones.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 100

Reporting Enable, Trouble Response Options, Zone Function ##

Single EOL Resistor Configuration


• Address: See Table 17 on page 88
• Default: See Table 17 on page 88
• Selections: 0 to 15
Enter This Data Digit to Select Options
Reporting Enable, Trouble Response Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Alarm or Trouble Reports •
Alarm Reports Enabled • • • • • • • •
Trouble Response on Open • • • • • • • •
Trouble Response on Short • • • • • • • •
Alarm Restoral Reports Enabled • • • • • • • •
Use the option parameter key above if the zone is configured for a single EOL resistor. See Zone Wiring
Configuration on page 89 for more information.
The trouble response for non-24-hour zones and 24-hour burglary Zone Function types occurs only when their
area is disarmed. When armed, any zone fault generates an alarm response. Other 24-hour zone types (Tamper,
Emergency, Panic and Invisible) always have trouble response as programmed.

Fire zone types always have Trouble Response on Open and Alarm Response on Short regardless of
programming.

• Alarm Reports Enabled: If this option is enabled, the system generates Alarm reports.
• Trouble Response on Open: If this option is enabled, an open circuit generates a Trouble response.
• Trouble Response on Short: If this option is enabled, a shorted circuit generates a Trouble response.
• Alarm Restoral Reports Enabled: If this option is enabled, the system generates Alarm Restoral reports.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 101

No EOL Resistor, Zone Doubling, or Tamper-wired Configuration


• Address: See Table 17 on page 88
• Default: See Table 17 on page 88
• Selections: 0 to 15
Enter This Data Digit to Select Options
Reporting Enable, Trouble Response Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Alarm or Trouble Reports •
Alarm Reports Enabled • • • • • • • •
Normally Open Sensor Contacts • • • • • • • •
Trouble Response on Off-Normal • • • • • • • •
Alarm Restoral Reports Enabled • • • • • • • •
The Reporting Enable/Trouble Response options are modified when the input zone is configured for no EOL
resistor, zone doubling, or tamper-wired operation. See Zone Wiring Configuration on page 89 for more information.
• Alarm Reports Enabled: If this option is enabled, the system generates Alarm reports.
• Normally Open Sensor Contacts: Enable this option when the sensor contacts are Normally Open and
shorted contacts create a fault. Disable this option when the contacts are Normally Closed and an open
condition creates a fault.

Most RF zones require the zone function to be configured with Normally Open sensor contacts
disabled.

• Trouble Response on Off-Normal: If this option is enabled, an off-normal condition generates a Trouble
response. The trouble response for non-24-hour zones and 24-hour burglary Zone Function types occurs only
when the zones are disarmed. When armed, any zone fault generates an alarm response. Other 24-hour zone
types (Tamper, Emergency, Panic and Invisible) always have trouble response as programmed.
• Alarm Restoral Reports Enabled: If this option is enabled, the system generates Alarm Restoral reports.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 102

Alarm Report Routing, Zone Function ##

• Address: See Table 17 on page 88


• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
Reports for Alarm, Cancel and Exit Error events follow Alarm report routing. See “Communication Failure
(Comm Fail)” for a description of the Comm Fail event and “Dialing Attempt Tables” for dialing sequence in the
DS7200V2 Installer’s Guide (P/N: 4998153893).
Restoral reports are routed as shown in Alarm Restoral Report Routing, Zone Function ##. Trouble reports are routed
globally. See Global Reporting Options on page 19.

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).

Alarm Restoral Report Routing, Zone Function ##

• Address: See Table 17 on page 88


• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
Alarm reports are routed as shown in Alarm Report Routing. Trouble reports are routed globally. See Global
Reporting Options on page 19.

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 103

4.5.3 Global Zone Configuration

On-board Location EOL Resistor Value

• Address: 1026
• Default: 5 (Tamper-wired loops, single tamper-wired sensors)
• Selections:
− 0 = No EOL Resistor
− 1 = 1 k EOL Resistor
− 2 = 2.2 k EOL Resistor
− 3 = 3.65 k EOL Resistor
− 4 = Zone Doubled, 2.2 k & 3.65 k EOL Resistors
− 5 = Tamper-wired loops, single tamper-wired sensors
− 6 = Tamper-wired loops, multiple tamper-wired sensors (up to 5 max)
This parameter applies to the control panel’s eight on-board sensor loops.
If zone doubling is turned on, the locations are paired as shown in Table 23.

Table 23: EOL Resistor Location Pairing for Zone


Doubling

Location (Sensor Loop)


EOL Resistor 1 2 3 4 5 6 7 8
3.65 k 1 2 3 4 5 6 7 8
2.2 k 9 10 11 12 13 14 15 16

Zone Response Options (for all zones)

• Address: 1027
• Default: 0
• Selections: 0 to 3
Enter This Data Digit to Select Options
Zone Response Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Enable Smart Swinger • •
Unverified Events Send Trouble Reports • •
Reserved
Reserved

• Smart Swinger: If enabled, this option allows zones that were Swinger Shunted to report new alarm events if
they are faulted when Bell Time is running. The ARC receives alarm reports from zones that previously
reported as Swinger Shunted. When Bell Time is running, the Swinger Count applies to these zones. They
only send reports until Bell Time expires or until the swinger count is reached again at which time they
Swinger Shunt again. If these bypassed zones are faulted when Bell Time is not running, they remain Swinger
Shunted and do not send reports.
• Unverified Events Send Trouble Reports: If this option is enabled, Fire Alarm with Verification zones that
have single, unverified events generate an Unverified Event report. Zones with the Cross Zone option enabled
that have a single pulse generate an Unverified Event report.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 104

Bypass/Force Arm Report Routing

• Address: 1028
• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
This parameter sets the routing for Bypass and Forced reports. See “Communication Failure (Comm Fail)” for a
description of the Comm Fail event and “Dialing Attempt Tables” for dialing sequence in the DS7200V2 Installer’s
Guide (P/N: 4998153893).

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).

Swinger Count for Alarm Output

• Address: 1029
• Default: 3
• Selections:
− 0 (Swinger disabled)
− 1 to 15
Each individual zone has a swinger count for alarm output.
Swinger Shunt reports are not sent for Swinger Shunt for Alarm Output. Zone reports have their own swinger
count (see Swinger Count for Zone Reports on page 105). The Swinger Count is reset on both arming and disarming
of the system, allowing Swinger Shunt to work for both non-24-hour and 24-hour zones. A trouble condition
occurs after Swinger Shunt.
Example: Assume the Swinger Shunt option is enabled, the control panel is armed, no zones are in alarm and the
Swinger Count for Alarm Output is set to 2. Zones 1, 3 and 5 go into alarm. At the end of Bell Time, the Swinger
Count for Alarm Output for Zones 1,3 and 5 decrements from 2 to 1. Since the counter does not reach zero, no
zones are bypassed. A second alarm event for any of those zones bypasses that zone.

When the Swinger Count is set to zero (0), Swinger Count for Alarm Outputs is disabled. The alarm
outputs activate on every new alarm.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 105

Swinger Count for Zone Reports

• Address: 1030
• Default: 3
• Selections:
− 0 (Swinger disabled)
− 1 to 15
This parameter sets the swinger count for zone alarm, trouble, and restoral reports.
Swinger shut down for the dialer is a global function that affects all zones.
Swinger Shunt {33} reports are sent for Swinger Shunt of zones.
The Swinger Count is reset on both arming and disarming, allowing the Swinger Shunt feature to work for both
non-24-hour and 24-hour zones.
Example: Assume the Swinger Shunt option is enabled, the control panel is armed and there are no alarms. When
the zone sends an Alarm or Trouble event to the dialer, the swinger count for zone reports is checked. If the
counter is at zero, the zone is already Swinger Shunted and no report is sent. If the counter is not at zero, the
control panel decrements the counter. If the counter then goes to zero after the report is sent, the Swinger Shunt
{33} report is sent. The zone is then swinger shunted.
If the swinger count is set to zero (0), the Swinger Count for Zone Reports feature is disabled. The dialer sends all
alarm or trouble events.

Bypass/Swinger Shunt/Trouble Report Options

• Address: 1031
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Bypass, Swinger Shunt, Sensor Trouble Report Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Zone Bypass and Swinger Shunt Reports Enabled • • • • • • • •
Bypass and Swinger Shunt Restoral Reports Enabled • • • • • • • •
Sensor Trouble Reports Enabled • • • • • • • •
Sensor Trouble Restoral Reports Enabled • • • • • • • •
This is a global parameter that affects all areas. This parameter enables Zone Bypass, Swinger Shunt and Sensor
reports (and their respective restoral reports are enabled).

Sensor Monitor Time

• Address: 1032, 1033


• Default: 0,7
• Selections: 0 to 9
This parameter determines the number of days (00 to 99) that the control panel can function without sensor (zone)
activity (time accumulates only when the area is off/disarmed).
Assign this parameter by zone function in Options 1, Zone Function ## (see page 95). This parameter does not apply
to fire zone types or non-fire 24-hour zone types.
If there is no sensor activity after the entered time period, a trouble report is sent.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 106

Alarm Event Abort Window

• Address: 1034
• Default: 3 (45 sec)
• Selections:
− 0 to 1 = 15 sec
− 2 = 30 sec
− 3 to 15 = 45 sec
This parameter sets the length of time that a user has to enter a valid PIN and cancel an alarm before an alarm
report is sent.
If a user acknowledges a non-fire alarm event by entering their PIN before the Alarm Event Abort Window
expires, the following events occur:
1. The alarm event is aborted. Alarm, Cancel and Restoral reports associated with the alarm are not
transmitted. The alarm event becomes a local only event.
2. The user hears a unique three long beep tone at the keypad.
3. The text keypad indicates the aborted alarm on the display. The LED keypad indicates the aborted alarm
with a slow flash in Alarm Memory.
See Cancel Event Enabled on page 26 and the “Enable Alarm Event Abort” option in Options 1 for Zone Function
Types 0 to 2, 5 to 8, 11 to 15 on page 95 for more information.

This parameter only affects non-fire zones. Fire and Fire with Verification zones are not affected by
enabling this parameter.

Zone Trouble/Restoral from Trouble Report Routing

• Address: 1038
• Default: 1 (Reports to Destination 1, Events to Log/Printer)
• Selections:
− 0 = No Reports, no Events to Log/Printer
− 1 = Reports to Destination 1, Events to Log/Printer
− 2 = Reports to Destination 2, Events to Log/Printer
− 3 = Reports to Destinations 1 & 2, Events to Log/Printer
− 4 = Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
− 5 = No reports, Events to Log/Printer
Zone Trouble report events include the following:
• RF Low Battery {121}
• RF Tamper Trouble {121}
• Trouble Events {139 to 145}
Restoral from Trouble report events include Restoral from Trouble events {146 – 152}.
See “Communication Failure (Comm Fail)” for a description of the Comm Fail event and “Dialing Attempt
Tables” for dialing sequence in the DS7200V2 Installer’s Guide (P/N: 4998153893).

Enable reporting at the Global Reporting Options parameter (see Global Reporting Options on page
19), and enter at least one phone number (or IP address) for one routing destination (see Phone
Number 1 (2) for Destination 1 (2) on page 9).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 107

4.6 Output Parameters


4.6.1 Global Output Configuration
The DS7240V2 supports up to 20 outputs: four on-board Programmable Outputs (PO 1 to PO 4), and up to 16
off-board using two DX3010 Output Expanders. The DS7220V2 supports up to 12 outputs: four on-board
Programmable Outputs (PO 1 to PO 4), and up to 8 off-board using one DX3010 Output Expander.
Outputs 5 through 12 are on an off-board Data Bus device (DX3010 Output Expander or DX3020 X-10 Interface
Module) at Data Bus Address 150.
Outputs 13 through 20 (DS7240V2 only) are on an off-board Data Bus device (DX3010 Output Expander or
DX3020 X-10 Control Module) at Data Bus Address 151.

Global Output Options

• Address: 1039
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Global Output Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Output 2 is Supervised Horn/Strobe Speaker Output • • • • • • • •
Send Output Set/Reset Reports • • • • • • • •
Enable Strobe Arming Flash to indicate RF Keyfob &
• • • • • • • •
Keyswitch Arm/Disarm
Enable Alarm Output Arming Beep to indicate RF
• • • • • • • •
Keyfob & Keyswitch Arm/Disarm

• Output 2 Is Supervised Horn/Speaker Output: This option turns Programmable Output 2 (PO 2) into a
supervised siren driver. If a siren or speaker is not connected, the control panel generates a Siren Trouble
event that can include a Siren Trouble {193} report. The restoral event is reported with Siren Trouble Restore
{194}. See “On-board Output Setup” in the DS7200V2 Installer’s Guide (P/N: 4998153893) for more
information. Compatible speakers include D118 and D119 Speaker Drivers.
• Send Output Set/Reset Reports: This option allows the control panel to send Output Set {109 to 111} and
Output Reset {106 to 108} reports when outputs are operated by a user, a Sked or RPS (Remote Programming
Software).
• Enable Strobe Arming Flash to Indicate RF Keyfob and Keyswitch Arm/Disarm: This option allows the
Strobe Output Function (1|6) to indicate RF and keyswitch arming and disarming as follows:
− 3 sec = transition to Off (disarmed)
− 6 sec = transition to All On or Perimeter Only
• Enable Alarm Output Arming Beep to Indicate RF Keyfob and Keyswitch Arm/Disarm: This option
allows any Alarm Output Functions (1|8, 1|9, 1|10, and 8|8) to indicate RF and Keyswitch arming and
disarming as follows:
− 1 Beep = transition to Off (disarmed)
− 2 Beeps = transition to All On
− 3 Beeps = transition to Perimeter Only

The “Enable Alarm Output Arming Beep to Indicate RF Keyfob and Keyswitch Arm/Disarm” option is
only available for RF Keyfobs (not RF Keypads) and when arming from RPS or a keyswitch.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 108

Bell Time

• Address: 1040
• Default: 6 (min.)
• Selections: 0-15 (1-minute increments)
Bell Time determines how long, 0 to 15 min., the Alarm Output, Fire Alarm Output, Silent Alarm Output, and
Bell Time functions remain activated when triggered by an alarm event.

Siren Warble Frequency

• Address: 1041
• Default: 7
• Selections: 0 (lowest tone/frequency) to 15 (highest tone/frequency)
This parameter sets the siren warble frequency for non-fire alarm output functions.
Programmable Output 2 (PO 2) can be configured as a supervised horn/speaker output (see Global Output Options
on page 107).
This parameter sets the warble frequency for the alarm output functions (1|8, 1|9, 1|10, and 8|8). The setting
chosen here does not apply to other output functions.
Lowering the frequency effectively raises the perceived volume.

Alarm Output Arming Beep Volume

• Address: 1042
• Default: 7
• Selections: 0 (no sound) to 15 (loudest); 1 = quiet)
PO 2 can be configured as a supervised horn/speaker output (see Global Output Options on page 107).
This parameter sets the perceived volume for the Alarm Output Arming Beep.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 109

Strobe Output Type Options

• Address: 1043
• Default: 15
• Selections: 0 to 15
Enter This Data Digit to Select Options
Strobe Output Type Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Bell Time Activates Strobe Output Type •
Alarm Output Type 1,8 Activates Strobe • • • • • • • •
Alarm Output Type 1,9 Activates Strobe • • • • • • • •
Alarm Output Type 1,10 Activates Strobe • • • • • • • •
Alarm Output Type 1,11 Activates Strobe • • • • • • • •
This parameter configures the Strobe Output Type (see Output Function Type 1,6 Strobe in Table 25 on page
112). Choose any combination of these options to activate the strobe output type. PIN entry resets the function.

If no strobe output type is selected (0 is selected for this option), the strobe output follows Bell Time
(see Bell Time on page 108 for more information).

• Bell Time Activates Strobe Output Type: The Strobe Output Type 1,6 activates when an alarm event starts
Bell Time. PIN entry resets the function.
• Alarm Output Type 1|8 Activates Strobe: Any event that activates Alarm Output Type 1|8 also activates
Strobe Output Type 1|6. PIN entry resets the function.
• Alarm Output Type 1|9 Activates Strobe: Any event that activates Alarm Output Type 1|9 also activates
Strobe Output Type 1|6. PIN entry resets the function.
• Alarm Output Type 1|10 Activates Strobe: Any event that activates Alarm Output Type 1|10 also activates
Strobe Output Type 1|6. PIN entry resets the function.
• Alarm Output Type 1|11 Activates Strobe: Any event that activates Alarm Output Type 1|11 also activates
Strobe Output Type 1|6. PIN entry resets the function.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 110

4.6.2 Output Configuration


The DS7240V2 supports up to 20 outputs: four on-board Programmable Outputs (PO 1 to PO 4), and up to 16
off-board using two DX3010 Output Expanders. The DS7220V2 supports up to 12 outputs: four on-board
Programmable Outputs (PO 1 to PO 4), and up to 8 off-board using one DX3010 Output Expander.
PO 2 can be configured as a supervised speaker output (8 Ω, 10 watt). See “On-board Output Setup” in the
DS7200V2 Installer’s Guide (P/N: 4998153893) for more information.
• PO 1 to PO 4: On-board outputs
− PO 1 default: 1|10 Alarm: Controlled and 24-Hour zones (Fire and Non-Fire)
− PO 2 default: 1|6 Strobe
− PO 3 default: 0|1 Armed: All, Perimeter Only, or Partial On
− PO 4 default: 2|13 Ready to Arm
• PO 5 to PO 12: Off-board Data Bus device (DX3010 Octo-Output Expander or DX3020 X-10 Control
Module) set to Address 150
− PO 5 to PO 12 default: Disabled
• PO 13 to PO 20 (DS7240V2 only): Off-board Data Bus device (DX3010 Octo-Output Expander or DX3020
X-10 Control Module) set to Address 151
− PO 13 to PO 20 default: Disabled
See Table 24 for Output configuration parameter addresses and defaults.
Shaded cells only apply to the DS7240V2.

Table 24: Output Configuration Parameters

Output Area Function Mode Base Multiplier


Digit 1 Digit 2 Digit 1 Digit 2
1 Addr 1044 Addr 1045 Addr 1046 Addr 1047 Addr 1048 Addr 1049 Addr 1050
(1) (1) (10) (1) (0) (0) (0)
2 Addr 1051 Addr 1052 Addr 1053 Addr 1054 Addr 1055 Addr 1056 Addr 1057
(1) (1) (6) (1) (0) (0) (0)
3 Addr 1058 Addr 1059 Addr 1060 Addr 1061 Addr 1062 Addr 1063 Addr 1064
(1) (0) (1) (1) (0) (0) (0)
4 Addr 1065 Addr 1066 Addr 1067 Addr 1068 Addr 1069 Addr 1070 Addr 1071
(1) (2) (13) (1) (0) (0) (0)
5 Addr 1072 Addr 1073 Addr 1074 Addr 1075 Addr 1076 Addr 1077 Addr 1078
6 Addr 1079 Addr 1080 Addr 1081 Addr 1082 Addr 1083 Addr 1084 Addr 1085
7 Addr 1086 Addr 1087 Addr 1088 Addr 1089 Addr 1090 Addr 1091 Addr 1092
8 Addr 1093 Addr 1094 Addr 1095 Addr 1096 Addr 1097 Addr 1098 Addr 1099
9 Addr 1100 Addr 1101 Addr 1102 Addr 1103 Addr 1104 Addr 1105 Addr 1106
10 Addr 1107 Addr 1108 Addr 1109 Addr 1110 Addr 1111 Addr 1112 Addr 1113
11 Addr 1114 Addr 1115 Addr 1116 Addr 1117 Addr 1118 Addr 1119 Addr 1120
12 Addr 1121 Addr 1122 Addr 1123 Addr 1124 Addr 1125 Addr 1126 Addr 1127
13 Addr 1128 Addr 1129 Addr 1130 Addr 1131 Addr 1132 Addr 1133 Addr 1134
14 Addr 1135 Addr 1136 Addr 1137 Addr 1138 Addr 1139 Addr 1140 Addr 1141
15 Addr 1142 Addr 1143 Addr 1144 Addr 1145 Addr 1146 Addr 1147 Addr 1148
16 Addr 1149 Addr 1150 Addr 1151 Addr 1152 Addr 1153 Addr 1154 Addr 1155
17 Addr 1156 Addr 1157 Addr 1158 Addr 1159 Addr 1160 Addr 1161 Addr 1162
18 Addr 1163 Addr 1164 Addr 1165 Addr 1166 Addr 1167 Addr 1168 Addr 1169
19 Addr 1170 Addr 1171 Addr 1172 Addr 1173 Addr 1174 Addr 1175 Addr 1176
20 Addr 1177 Addr 1178 Addr 1179 Addr 1180 Addr 1181 Addr 1182 Addr 1183

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 111

Area, Output ##

• Address: See Table 24 on page 110


• Default: 1 (Assign Output to Area 1)
• Selections: 0-15
Enter This Data Digit to Select Options
Output Area Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Area Assigned (Output disabled) •
Assign Output to Area 1 • • • • • • • •
Assign Output to Area 2 • • • • • • • •
Assign Output to Area 3 (DS7240V2 only) • • • • • • • •
Assign Output to Area 4 (DS7240V2 only) • • • • • • • •
This parameter assigns an area to the output. Functions are only activated by keypads or zones assigned to the
same area. Outputs can be assigned to multiple areas.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 112

Function, Output ##

• Address: See Table 24 on page 110


• Default:
− PO 1: 1|10 Alarm: Controlled and 24-hr Zones (Fire and Non-Fire)
− PO 2: 1|6 Strobe
− PO 3: 0|1 Armed: All, Perimeter Only, or Partial On
− PO 4: 2|13 Ready to Arm
− PO 5 to PO 20: 0|0 Disabled
• Selections: 0,0 to 8,15 (see Table 25)
This parameter assigns each output to a specific function. The function determines when the output activates. The
Mode, Time and Multiplier parameters, in combination with this Function parameter, determine when the output
deactivates.
All output functions can be reset using [#][5][4] except Alarm Outputs that follow Function Types 1|8 to 1|12 and
2|11, and those functions that can be reset by pressing [System Reset].

Table 25: Output Function Types

Digit 1 Digit 2 Function Type Description


0 0 Disabled
0 1 Armed – All, Perimeter Only, or Output activates when the system is armed All On, Perimeter Only, or
Partial On Partial On. For Steady or Pulse modes, the output remains activated until
the system is turned off.
0 2 Armed – Perimeter Only or Output activates when the system is armed Perimeter Only, or Partial On.
Partial On For Steady or Pulse modes, the output remains activated until the system
is turned off, or moved to another armed state.
0 3 Armed – All Output activates when the system is turned All On. For Steady or Pulse
modes, the output remains activated until the system is turned off, or
moved to another armed state.
0 4 Auto Arm Alert Output activates at the start of the Auto Arm Alert. For Steady or Pulse
modes, the output remains activated for the duration of the alert. See
Auto On Alert Time on page 26.
0 5 Exit Delay or Entry Delay Output activates at the start of Exit Delay or Entry Delay. For Steady or
Pulse modes, the output remains activated until entry or exit delay ends.
0 6 Exit Delay Output activates at the start of Exit Delay. For Steady or Pulse modes, the
output remains activated until exit delay ends.
0 7 Exit Delay Finished (until Output activates at the end of Exit Delay. For Steady or Pulse modes, the
disarmed) output remains activated until the system is disarmed.
0 8 Armed with Ack For systems programmed for closing reports, the output activates when
the acknowledgement for the closing report is received. For systems not
sending closing reports, the output activates at the end of Exit Delay. For
Steady or Pulse modes, the output remains activated until the system is
disarmed.
0 9 Entry Delay Output activates at the start of Entry Delay. For Steady or Pulse modes
the output remains activated until Entry Delay ends.
0 10 Entry Delay + Chime Output activates at the start of Entry Delay. For Steady or Pulse modes,
the output remains activated until entry delay ends. The output also
activates whenever a Chime zone is faulted. The output does not
activate on Chime if Chime Tone is turned off.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 113

Table 25: Output Function Types (continued)

Digit 1 Digit 2 Function Type Description


0 11 Exit Delay, Entry Delay, Chime Output activates at the start of Exit Delay or Entry Delay. For Steady or
Pulse modes, the output remains activated until Entry or Exit Delay ends.
The output also activates whenever a Chime zone is faulted. The output
does not activate on Chime if Chime Tone is turned off.
0 12 Phone Line Fail Output activates when a Phone Line Fail condition is detected. For
Steady or Pulse modes, the output remains activated until the condition is
cleared. This output works independently of Phone Line Fault
Response Options (page 18).
0 13 Ack Received (any report) Output activates when the acknowledgement for any report is received.
For Steady or Pulse modes, [System Reset] resets. This output type is
event-driven. See Mode (Steady, Pulse, One Shot), Output ## on page
117 for more information.
0 14 AC Fail Output activates when a AC Fail condition is detected. For Steady or
Pulse modes, the output remains activated until the condition is cleared.
0 15 Low or Missing Battery Output activates when a control panel Low or Missing Battery condition
occurs. For Steady or Pulse modes, the output remains activated until the
condition is cleared.
1 0 PO 2 (on-board) Siren Output activates when a Siren Supervision Fail condition is detected. For
Supervision Fail Steady or Pulse modes, the output remains activated until the condition is
cleared and the [System Reset] key is pressed.
1 1 Sensor Trouble Monitor Output activates when a Sensor Trouble Monitor condition is detected in
conjunction with the selection made for the Sensor Monitor Time setting.
For Steady or Pulse modes, the output remains activated until the Sensor
Monitor Trouble condition is cleared.
1 2 Duress, [#][4][7] (reset) resets Output activates whenever a Duress PIN is entered. For Steady or Pulse
modes, the output remains activated until user presses [System Reset].
1 3 User Tamper, [#][4][7] (reset) Output activates on a User Tamper event. For Steady or Pulse modes,
resets the output remains activated until user presses [System Reset].
1 4 Arming Beeps (for Disarm/All On/Perimeter Only/Partial On Beeps for keyswitch/RF arming.
keyswitch/RF arming) 1=Off, 2=All, 3=Perimeter Only. Mode and Time parameters do not
apply. This function works in conjunction with Address 1039. See
Global Output Options on page 107. Available for on-board outputs
only.
1 5 Bell Time – Starts on any Output activates on any alarm event. Entering PIN terminates Bell Time.
Alarm Event. PIN entry Stops. For Steady and Pulse modes, the output remains activated for the
Activates on Bell Test. duration programmed in the Bell Time parameter.
1 6 Strobe Activates on Bell Time or output function as programmed. See Strobe
Output Type Options on page 109. PIN entry resets the function.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 114

Table 25: Output Function Types (continued)

Digit 1 Digit 2 Function Type Description


1 7 Silent Alarm Activated by alarm on non-fire zones programmed for No Alarm Output.
Follows Bell Time for Steady and Pulse modes. PIN stops. The following
conditions activate Silent Alarm:
- ABC Key programmed for Fire or Emergency and no Alarm Output
- RF Keyfob programmed for Fire or Emergency and no Alarm Output
- A zone programmed for Fire or Fire with Verify and no Alarm Output
- Any zone not programmed for Invisible Panic that is programmed for no
Alarm Output
- Any armed zone programmed as a controlled type that goes from
Supervised to Missing and programmed for no Alarm Output
- Any armed keyswitch programmed for no Alarm Output that goes from
Supervised to Missing or Short to Missing
- Any zone programmed for Swinger Count and Swinger Count for Alarm
Output that reaches its programmed value
1 8 Alarm – All On, Perimeter Only, Activated by alarm on zone when All On, Perimeter Only, and Partial On
and Partial On Arming, Non-fire Armed, or by alarm on Non-fire 24 hour zone, and by user/installer ‘Bell
24 hour alarms Test’. Follows Bell Time for Steady and Pulse modes. PIN resets. Follows
programming for ‘Alarm’ output types.
1 9 Alarm – Perimeter Only and Activated by alarm on zone when Perimeter Only, and Partial On Armed,
Partial On Arming Modes, Non- or by alarm on Non-fire 24 hour zone, and by user/installer ‘Bell Test’.
fire 24 hour alarms Follows bell time for Steady and Pulse modes. PIN resets.
Follows programming ‘Alarm’ output types.
1 10 Alarm –Controlled zones, 24-hr Activated by alarm on zone when All On, Perimeter Only, and Partial On
zones (Fire and Non-Fire) Armed, or by alarm on Fire and Non-fire 24 hour zone, and by
user/installer ‘Bell Test’. Follows bell time for Steady and Pulse modes.
Pulses in Temporal Code 3 format for Fire alarms only. PIN resets.
Off-board outputs cannot provide output in Temporal Code 3 format
(only on-board outputs). Off-board outputs provide a steady output.
Follows programming for ‘Alarm’ output types. Temporal Code 3 for
Fire alarms only.
1 11 Fire Alarm Activated by alarm on Fire zone, and by user/installer ‘Bell Test’. Follows
Bell Time. Pulses in Temporal Code 3 format. Mode and Time parameters
do not apply. PIN resets. Off-board outputs cannot provide output in
Temporal Code 3 format (only on-board outputs). Off-board outputs
provide a steady output. Follows programming for ‘Alarm’ output
types.
1 12 Fire Alarm, Latching Activated by alarm on Fire zone, and by user/installer ‘Bell Test’. Does not
pulse in Temporal Code 3 format. Mode and Time parameters do not
apply. [#][4][7] resets. Follows programming for ‘Alarm’ output types.
1 13 Fire Verification/Reset Normally on. Turns off on activation to reset smoke detectors. Verification
for Fire Verification Zone Function type and [System Reset] activate
output for approximately 15 sec. Mode and Time parameters do not apply.
Used for 4-wire smoke detectors.
1 14 System Trouble Activates on any System Trouble. Resets when all system troubles are
clear.
1 15 [O] Key (Trapezoid Key on RF Activates when [O] (Trapezoid key on RF Keyfob is pressed. [System
Key Fob) Reset] resets. Pressing [O] again also resets output when Output Mode
is set to Toggle. This output type is event-driven. See Mode (Steady,
Pulse, One Shot), Output ## on page 117 for more information.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 115

Table 25: Output Function Types (continued)

Digit 1 Digit 2 Function Type Description


2 0 [P] Key (Rising Sun Key on RF Activates when [P] (Rising Sun) key on RF Keyfob is pressed. [System
Fob) Reset] resets. Pressing [P] again also resets output when Output Mode
is set to Toggle. This output type is event-driven. See Mode (Steady,
Pulse, One Shot), Output ## on page 117 for more information.
2 1 ‘Panic’ on RF Fob Activates when Arm Key (locked icon) and Disarm Key (unlocked icon) on
RF Keyfob are pressed at the same time, or when [Q] is pressed and it is
set to Duress. See [Q] Button Alarm Response Options on page 76.
[#][4][7] resets.
2 2 ‘Panic’ on RF Fob, Bell Time, Activates when Arm Key (locked icon) and Disarm Key (unlocked icon) on
PIN resets RF Keyfob are pressed at the same time, or when [Q] is pressed and it is
set to Duress. Steady and Pulse modes follow bell time. PIN resets.
2 3 [A] Key Activates when appropriate keys are pressed. [System Reset] resets if no
2 4 [B] Key alarm response is assigned. These output types are event-driven. See
2 5 [C] Key Mode (Steady, Pulse, One Shot), Output ## on page 117 for more
information.
2 6 3 Unsuccessful Dialing Activates after 3 unsuccessful dialing attempts. Resets with first
Attempts successful call or [System Reset].
2 7 Communication Fail Event Activates after Communication Fail Event. Resets with any successful
communication or [System Reset].
2 8 Panel Off Hook Activates when the control panel takes the phone line off hook for a
dialing attempt. Resets when the control panel finishes with the phone
line and goes on hook.
2 9 Ring Detect Activates when the control panel detects a ring on the phone line. Resets
when ringing stops.
2 10 Voice Request For use with an optional Voice Verification Module. The output activates
for 2 sec when the control panel receives an acknowledgement of an
alarm report from a zone with the Voice Verification option enabled. Mode
and Time parameters do not apply.
2 11 Follow Keypad Sounder Available for on-board outputs only. Output follows keypad sounder Mode
and Time parameters do not apply.
2 12 Chime Activates per Chime configuration. Follows keypad sounder per Chime
Tone configuration.
2 13 Ready to Arm (No zones Output is activated (on) when: (1) control panel is disarmed & no zones
faulted) are faulted (2) control panel is armed & no zones are faulted (3) control
panel is armed and any zone is faulted. Output is deactivated (off) when
control panel is disarmed & any zone is faulted. Output is deactivated
even if the zone became faulted when control panel was armed.
2 14 Exit Error/Bad Set Activates if zone is faulted at the end of Exit Delay or if a Bad Set
condition occurs. Resets when the system is disarmed.
2 15 AC 60 Hz Activates on 60 Hz. Deactivates on 50 Hz.
3 0 Ground Start Activates for approximately 0.5 sec at the start of any dialing attempt. Use
to bring up dial tone in ground start phone systems.
3 1 Follow Zone Function 1 These 15 output functions activate for any fault on any zone assigned to
to the specified Zone Function.
3 15 Follow Zone Function 15
4 0 Change Outputs Activated/deactivated by Change Outputs function ([#][5][4]).
4 1 Alarm Zone Function 1 These 15 output functions activate for alarms on any zone assigned to the
to specified Zone Function and the area(s) the output is assigned to. They
reset when none of the zones assigned to the specified Zone Function
4 15 Alarm Zone Function 15
are in alarm.
5 0 Change Outputs Activated/deactivated by Change Outputs function ([#][5][4]).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 116

Table 25: Output Function Types (continued)

Digit 1 Digit 2 Function Type Description


5 1 Trouble Zone Function 1 These 15 output functions activate for troubles on any zone assigned to
to the specified Zone Function. They reset when none of the zones assigned
to the specified Zone Function are in trouble.
5 15 Trouble Zone Function 15
6 0 Change Outputs Activated/deactivated by Change Outputs function ([#][5][4]).
6 1 Follow PIN 1 These output functions activate when the specified PIN is entered.
to Output Function Type 7, 12 follows User 28, which can be programmed
6 15 Follow PIN 15 as the Guard Code User (see page 74).
7 0 Follow PIN 16 These output types are event-driven. See Mode (Steady, Pulse, One
Shot), Output ## on page 117 for more information.
to
PIN area assignments are ignored when these output functions are
7 15 Follow PIN 31
selected.
8 0 Follow PIN 32
8 1 Sked Only This output type is only available for Outputs 1 to 15. Activated by Skeds.
See Assign (Area or Output), Sked # on page 121 for more information.
8 2 Change Outputs Activated/deactivated by Change Outputs function ([#][5][4]).
8 3 Always On Output is always activated.
8 4 Verified Alarm Activates when the requirements for a verified alarm are met. Resets
when a PIN is entered.
8 5 Unverified Alarm Activates on any non-24-hr alarm, 24-hr tamper or 24-hr burglary alarm.
Resets when the verified alarm timer resets or when a PIN is entered.
8 6 Tamper Activates on any tamper condition. Resets when the tamper condition
restores.
8 7 Bypass Activates when any input is bypassed. Resets when all input bypasses
are cleared.
8 8 Enhanced Siren Activates on Exit Delay, Entry Delay, Chime, Alarm, Tamper, Trouble, or
Bad Set. Resets at the end of bell time or when a PIN is entered.
8 9 Alarm Cancel Activates on a cancelled alarm. Resets when alarm is cleared.
8 10 RF Transmitter Missing Activates when any RF transmitter is missing. Restores by pressing the
[System Reset] key.
8 11 RF Transmitter Low Battery Activates when any RF transmitter is reporting a low battery. Resets by
pressing the [System Reset] key.
8 12 RF Receiver Jamming Activates when RF Jamming is present. Resets by pressing the [System
Reset] key.
8 13 Fire Alarm Only Activates on Fire Alarm only. PIN resets. Does not pulse in Temporal
Code 3 format.
8 14 Personal Alarm Activates when one of its assigned areas is set to Personal Alarm. Resets
by entering a valid user PIN, pressing [System Reset], or by RPS (System
Reset command). Activates on any of the following conditions: (1) If a
Duress User PIN is entered (2) If an Emergency key is active in an area
and “Activate Panic Alarm Response” and “Alarm Output” are enabled for
the key (3) If a RF keyfob reports a Panic alarm (4) If a zone configured
for 24-hr Visible Panic (Zone Function Type 6) goes into alarm, or (5)
Certain [Q] button configurations. See Q Button Configuration on page
76.
8 15 [Q] Button Output activates when [Q] is pressed on a RF keyfob. For Steady or
Pulse modes, [System Reset] resets. This output function type is event-
driven. See Mode (Steady, Pulse, One Shot), Output ## on page 117
for more information.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 117

Mode (Steady, Pulse, One Shot), Output ##

• Address: See Table 24 on page 110


• Default:
− Outputs 1 to 4: 1 (Steady)
− Outputs 5 to 20: 0 (Disabled)
• Selections: 1 to 13 (see Table 26)
There are two types of outputs: state-driven outputs and event-driven outputs. State-driven outputs follow the
state of a condition, either on or off. For example, a state-driven output is Type 0|1 Armed. The output is active
when the control panel is armed and inactive when the control panel is disarmed.
Event-driven outputs follow events when they occur. These events have no On or Off state. For example, an
event-driven output is Type 0|13 Ack Received. When the key is pressed, the output is activated.
Table 26 describes the mode operation for both on-board and off-board outputs.

Table 26: Output Mode Options

Mode Mode Type Output Description


Type
1 Steady State Output turns on when the condition is active and turns off when the condition is
inactive.
Event Output turns on when the event occurs. [System Reset] turns the output off.
2 Latch State Output turns on when the condition is active and remains on until [System Reset] is
pressed.
Event Output turns on when the event occurs and remains on until [System Reset] is
pressed.
3 Toggle State When the condition goes from inactive to active, the output changes state. The
condition going from active to inactive has no effect.
Event Whenever the event occurs, the output changes state.
4 Pulse State When the condition is active, the output pulses. When the condition is inactive, the
output is off.
Event When the event occurs, the output pulses. The output remains pulsing until [System
Reset] is pressed.
5 One-Shot State When the condition changes from inactive to active, the output turns on. The output
turns off at the end of the One-Shot time. While the output is on, any changes in the
condition are ignored.
Event When the event occurs, the output turns on and remains on for the One-Shot time.
When the output is on, a second event does not affect the output.
6 One-Shot State When the condition changes from inactive to active, the output turns on and remains
with Re- on for the One-Shot time. If the condition goes inactive and active again, the One-Shot
Trigger time is restarted and the output remains on.
Event When the event occurs, the output turns on and remains on for the One-Shot time. If a
new event occurs when the output is on, the One-Shot time is restarted and the output
remains on.
7 One-Shot State When the condition changes from inactive to active, the output turns on and remains
with Reset on for the One-Shot time. If the condition goes inactive, the output is turned off early.
Event When the event occurs, the output turns on and remains on for the One-Shot time.
[System Reset] turns the output off early.
8 Steady, State Output turns on when the condition is inactive and turns off when the condition is
Reversed active.
Logic Normal Event Output turns off when the event occurs. [System Reset] turns the output on.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 118

Table 26: Output Mode Options (continued)

Mode Mode Type Output Description


Type
9 Latch, State Output turns off when the condition is active and remains off until [System Reset] is
Reversed pressed.
Logic Normal Event Output turns off when the event occurs and remains off until [System Reset] is
pressed.
10 Pulse, State When the condition is active, the output pulses. When the condition is inactive, the
Reversed output is on.
Logic Normal Event When the event occurs, the output pulses. The output continues pulsing until [System
Reset] is pressed, then turns on.
11 One-Shot, State When the condition changes from inactive to active, the output turns off. The output
Reversed turns on at the end of the One-Shot time. While the output is off, any changes in the
Logic Normal condition are ignored.
Event When the event occurs, the output turns off and remains off for the One-Shot time.
While the output is off, a second event does not affect the output.
12 One-Shot State When the condition changes from inactive to active, the output turns off and remains
with Re- off for the One-Shot time. If the condition goes inactive and active again, the One-Shot
Trigger, time is restarted and the output remains off.
Reversed Event When the event occurs, the output turns off and remains off for the One-Shot time. If a
Logic Normal new event occurs, the One-Shot time is restarted and the output remains off.
13 One-Shot State When the condition changes from inactive to active, the output turns off and remains
with Reset, off for the One-Shot time. If the condition goes inactive, the output is turned on early.
Reversed Event When the event occurs, the output turns off and remains off for the One-Shot time.
Logic Normal [System Reset] turns the output on early.

Base, Output ##

• Address: See Table 24 on page 110


• Default: 0 (Disabled)
• Selections:
− 0 = Disabled
− 1 = 200 ms (on-board outputs only)
− 2 = 1 second
− 3 = 1 minute
− 4 = 1 hour
Multiply the Base with the Multiplier to determine the output’s timing. See Table 27, on page 119, and Table 28, on
page 119.

Multiplier, Output ##

• Address: See Table 24 on page 110


• Default: 0,0 (Disabled)
• Selections: 0,0 to 9,9
Multiply the Base with the Multiplier to determine the output’s timing. See Table 27, on page 119, and Table 28, on
page 119.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 119

Steady, Pulse, and One-Shot Mode Configuration

• Steady and Toggle Modes: These modes are not affected by the Time Base and Time Multiplier parameters
below.
• Pulse Modes: The system calculates the On Time (activation) and the Off Time for outputs based on the
values in the Base and Multiplier columns (see Table 27). The duration, or On Time, of an output is
determined by selecting one of the four Base options from Table 27. Calculate the Off Time by multiplying the
Base by the Multiplier.

The Time Base of 200 ms in Table 27 and Table 28 is only available for on-board outputs.

Table 27: Pulse Mode Configuration

Base On Time Multiplier Off Time Tolerance


(On Time = Time of Base) (Off Time = Base x Multiplier)
0 0 N/A Always Off N/A
1 (200 ms) 200 ms 01 to 99 200 ms to 19.8 sec ±200 ms
2 (1 sec) 1 second 01 to 99 1 to 99 sec ±1 second
3 (1 min) 1 minute 01 to 99 1 to 99 min. ±1 minute
4 (1 hr) 1h 01 to 99 1 to 99 h ±1 h

• One Shot Modes: The duration of the On Time of a One Shot output is determined by multiplying the Base
by the Multiplier.

Table 28: One Shot Mode Configuration

Base Multiplier On Time Tolerance


(On Time = Base x Multiplier)
0 N/A 0 N/A
1 (200 ms) 01 to 99 200 ms to 19.8 sec ±200 ms
2 (1 sec) 01 to 99 1 to 99 sec ±1 second
3 (1 min) 01 to 99 1 to 99 min. ±1 minute
4 (1 hr) 01 to 99 1 to 99 h ±1 h

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 120

4.7 Sked Parameters


Skeds are programmable events that occur at a specified time of day and day of the week.
Users can extend Auto On, Auto Perimeter Only On and Auto Partial On time by one h using the Extend Auto
On Time function ([#][5][1]). When [#][5][1] is entered, the control panel sends an Auto On Extended {21} report.
Users can also change Skeds using the Change Skeds function ([#][5][2]). A Sked must first be entered before the
Change Skeds function is used.
The following sections and parameters detail the programming of each of the eight Skeds. The parameters in
Output Parameters on page 107 determine the characteristics of the output activation that occurs at the Sked time.
See Table 29 for Sked configuration parameter addresses.
The default setting for all Sked parameters is 0 (zero).

Table 29: Sked Configuration Parameters

Sked Type Assign Time Days 1 Days 2


(Area or Option Option
Output) (H _ _ _) (_H _ _) (_ _ M _) (_ _ _ M)
1 Addr 1184 Addr 1185 Addr 1186 Addr 1187 Addr 1188 Addr 1189 Addr 1190 Addr 1191
2 Addr 1192 Addr 1193 Addr 1194 Addr 1195 Addr 1196 Addr 1197 Addr 1198 Addr 1199
3 Addr 1200 Addr 1201 Addr 1202 Addr 1203 Addr 1204 Addr 1205 Addr 1206 Addr 1207
4 Addr 1208 Addr 1209 Addr 1210 Addr 1211 Addr 1212 Addr 1213 Addr 1214 Addr 1215
5 Addr 1216 Addr 1217 Addr 1218 Addr 1219 Addr 1220 Addr 1221 Addr 1222 Addr 1223
6 Addr 1224 Addr 1225 Addr 1226 Addr 1227 Addr 1228 Addr 1229 Addr 1230 Addr 1231
7 Addr 1232 Addr 1233 Addr 1234 Addr 1235 Addr 1236 Addr 1237 Addr 1238 Addr 1239
8 Addr 1240 Addr 1241 Addr 1242 Addr 1243 Addr 1244 Addr 1245 Addr 1246 Addr 1247

Type, Sked #

• Address: See Table 29


• Default: 0 (No type assigned)
• Selections:
− 0 = No Type Assigned (Sked disabled)
− 1 = Auto All On
− 2 = Auto Perimeter Only On
− 3 = Auto Partial On
− 4 = Auto Off
− 5 = Output On (DS7240V2: Outputs 1 to 15; DS7220V2: Outputs 1 to 12)
− 6 = Output Off (DS7240V2: Outputs 1 to 15; DS7220V2: Outputs 1 to 12)
The Sked Types "Output Function On" and "Output Function Off" override any output function at Sked time
(except for Alarm Output Functions 1|8 to 1|12). For example, an output function that turns a light on is
overridden by a Sked that turns the same light on.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 121

Assign (Area or Output), Sked #

• Address: See Table 29 on page 120


• Default: 0 (No Area or Output Assigned)
• Selections:
− 0 = No Area or Output Assigned (Sked disabled)
− 1 = Area 1 or Output 1
− 2 = Area 2 or Output 2
− 3 = Area 3 (DS7240V2 only) or Output 3
− 4 = Area 4 (DS7240V2 only) or Output 4
− 5 = Output 5
− 6 = Output 6
− 7 = Output 7
− 8 = Output 8
− 9 = Output 9
− 10 = Output 10
− 11 = Output 11
− 12 = Output 12
− 13 = Output 13 (DS7240V2 only)
− 14 = Output 14 (DS7240V2 only)
− 15 = Output 15 (DS7240V2 only)
Enter a zero (0) in this parameter to disable the Sked.
If the Sked Type is Auto On or Auto Off, this parameter assigns an Area to the Sked.
If the Sked Type is Output On or Output Off, this parameter assigns a programmable output. How the
programmable output functions at Sked time is determined in Output Parameters on page 107.
The output assigned to the Sked in this parameter can be any output. The Sked overrides that function at Sked
Time.

The Output On/Off Sked function is only available for Outputs 1 to 15 on the DS7240V2. On the
DS7220V2, it is only available for Outputs 1 to 12.

Time, Sked #

• Address: See Table 29 on page 120


• Default: 0000 (Sked disabled)
• Selections: 0 to 9
Enter the start time for the Sked. There are four digits in this entry, each one occupying an address.
Enter the time in 24-hour format (HHMM) where Midnight is 2400, noon is 1200 and 12:01 am is 0001.
Enter 0000 to disable the Sked.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 122

Days Option 1, Sked #

• Address: See Table 29 on page 120


• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Sked Days 1 Option 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Option Selected •
Every Day • • • • • • • •
Monday • • • •
Tuesday • • • •
Wednesday • • • •

This parameter assigns the day of the week the Sked occurs.

Entering zero (0) for this parameter disables the Sked if no selection is made in the Days Option 2,
Sked # parameter.
If the “Every Day” option is selected in the Days Option 1, Sked # parameter, it overrides any selection
made in the Days Option 2, Sked # parameter.

Days Option 2, Sked #

• Address: See Table 29


• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
Sked Days 2 Option 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Option Selected •
Thursday • • • • • • • •
Friday • • • • • • • •
Saturday • • • • • • • •
Sunday • • • • • • • •

This parameter assigns the day of the week the Sked occurs.

Entering zero (0) for this parameter disables the Sked if no selection is made in the Days Option 1,
Sked # parameter.
If the “Every Day” option is selected in the Days Option 1, Sked # parameter, it overrides any selection
made in the Days Option 2, Sked # parameter.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 123

4.8 Data Bus Device Parameters


The following parameters configure devices that connect to the control panel’s Data Bus.
4.8.1 RF Receiver Configuration

RF Receiver Options

• Address: 1249
• Default: 0
• Selections: 0 to 7
Enter This Data Digit to Select Options
Premises RF Receiver Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No RF Receiver Connected •
RF Receiver 1 connected, set to Address 50 • • • • • • • •
RF Receiver 2 connected, set to Address 51 • • • • • • • •
Disable RF Loop Tamper • • • • • • • •
Keyfobs Do Not Force Arm Faulted Zones • • • • • • • •

• RF Receiver 1 Connected, Set Receiver to Address 50: Enable this option if RF Receiver 1 has been
connected to the control panel. Set the RF receiver’s address to 50 (jumper setting OFF). See “Adding RF ID
Codes” in the DS7200V2 Installer’s Guide (P/N: 4998153893) for instructions. See RF Transmitters and Zone
States on page 87 for details on RF transmitters and zone states.
All status reports for the RF Receiver include the address. For example, if the cover is removed, Event {127}
(DBus Tamper) is generated.
• RF Receiver 2 Connected, Set Receiver to Address 51: Enable this option if RF Receiver 2 has been
connected to the control panel. Set the RF receiver’s address to 51 (jumper setting ON). See “Adding RF ID
Codes” in the DS7200V2 Installer’s Guide (P/N: 4998153893) for instructions. See RF Transmitters and Zone
States on page 87 for details on RF transmitters and zone states.
All status reports for the RF Receiver include the address. For example, if the cover is removed, Event {127}
(DBus Tamper) is generated (the address is included in the report).
• Disable RF Loop Tamper: The RF3401E transmitter’s loop can be wired with a single 2.2 k EOL resistor, or
it can be wired with dual 2.2 k EOL resistors. If this option is enabled, wire the RF3401E with a single 2.2 k
EOL resistor. The loop can report as normal, shorted, or open. If this option is disabled, wire the RF3401E is
with dual 2.2 k EOL resistors. The loop can report as normal, shorted, faulted, or open.
• Keyfobs Do Not Force Arm Faulted Zones: If this option is enabled, arming from a keyfob does not force
arm faulted zones. A faulted zone prevents the area from arming. If this option is disabled, arming from a
keyfob does force arm faulted zones.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 124

RF Receiver Supervision Interval

• Address: 1250
• Default: 5 (24 h)
• Selections:
− 0 = No Supervision
− 1=1h
− 2=2h
− 3=4h
− 4 = 12 h
− 5 = 24 h
RF transmitters (sensors) send a supervisory signal approximately once every 13 min.. The RF receiver expects to
hear this signal from every transmitter in the interval determined in this parameter. A “Missing” report is sent for
each device that the RF Receiver does not hear.

Fire transmitters have a fixed supervision interval of 4 h.

RF Jam Detect Level

• Address: 1251
• Default: 12
• Selections: 0-15
This parameter configures the RF receivers for jam detection.

Leave the RF Jam Detect Level parameter at the default setting unless advised by Bosch Technical
Service.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 125

4.8.2 RS-232 Module Configuration


The following parameters apply to the DX4010i and DX4010 RS-232 Serial Interface Modules.

Output Configuration Options

• Address: 1253
• Default: 0 (Disabled)
• Selections:
− 0 = Disabled(no RS-232 module connected)
− 1 = RS-232 Log Output using Internal Codes
− 2 = RS-232 Log Output using PC Compatible Codes
Set the RS-232 module to Data Bus Address 250. See “DX4010i/DX4010 Addressing” in the DS7200V2 Installer’s
Guide (P/N: 4998153893) for information.
This parameter only applies when the RS-232 module is used for RS-232 serial output. It does not apply if the
DX4010 is used for direct-connect remote programming.
• RS-232 Log Output using Internal Codes: If enabled, this option outputs the events using the internal
keypad character codes. Non-standard characters may not print correctly.
• RS-232 Log Output using PC Compatible Codes: If enabled, this option outputs the events using PC
compatible character codes. Non-standard characters are mapped to the closest matching character for display
or printing.

If you connect a printer to the RS-232 module and get unexpected results, check the module output
configuration (Address 1253), baud rate configuration (Address 1254) and parity/flow control/stop bit
configuration (Address 1255) for proper settings.

Baud Rate Options

• Address: 1254
• Default: 2 (2400 bps)
• Selections:
− 1 = 1200 bps
− 2 = 2400 bps
− 3 = 4800 bps
− 4 = 9600 bps
− 5 = 14400 bps
This parameter identifies which baud rate the RS-232 module should use for communication.

If you connect a printer to the RS-232 module and get unexpected results, check the module output
configuration (Address 1253), baud rate configuration (Address 1254) and parity/flow control/stop bit
configuration (Address 1255) for proper settings.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 126

Parity, Flow Control, Stop Bit Configuration

• Address: 1255
• Default: 0
• Selections: 0 to 7
Selection Parity Flow Control Stop Bits
None Odd Even Software Hardware 1 2
0 X X X
1 X X X
2 X X X
3 X X X
4 X X X
5 X X X
6 X X X
7 X X X
4.8.3 DX8010 Telephone Module Configuration

DX8010 Access Options

• Address: 1256
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
DX8010 Access Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Disabled, No DX8010 Connected •
Access Granted to Users with Authority Level 1 • • • • • • • •
Access Granted to Users with Authority Level 2 • • • • • • • •
Access Granted to Users with Authority Level 3 • • • • • • • •
Access Granted to Users with Authority Level 4 • • • • • • • •
Set this parameter to zero (0) if there are no DX8010 modules connected to the control panel, or to disable any
DX8010 modules that are connected to the control panel.
Selecting any of the other options allows system control for users assigned to the chosen authority level.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 127

4.8.4 DX2010 Configuration

DX2010 Configuration Options

• Address:
− 1257 = DX2010 Address 101
− 1258 = DX2010 Address 102
− 1259 = DX2010 Address 103
− 1260 = DX2010 Address 104 (DS7240V2 only)
− 1261 = DX2010 Address 105 (DS7240V2 only)
• Default: 0
• Selections: 0 to 11
Enter This Data Digit to Select Options
DX2010 Configuration Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
300 ms Debounce Time • • •
150 ms Debounce Time • • •
75 ms Debounce Time • • •
30 ms Debounce Time • • •
Tamper-wired EOL Resistors • • • •
Single 2.2 k EOL Resistor • • • •
Single 2.2 k EOL Resistor, 30% Zone • • • •
Reserved

When the location’s device parameter is set to 2 (see Location ##, Device on page 83), the sensor loop is taken from
a DX2010 module. This parameter configures the input modules. The debounce time selects how quickly the
input reacts to a change.
The single 2.2 k EOL resistor configurations use only one EOL resistor. The tamper-wired EOL resistor
configuration uses two-2.2 k EOL resistors and can report tamper as well as alarm.
The 30% zone causes an alarm whenever the EOL resistance changes by more than 30%. This setting makes the
zone more sensitive to false alarms than a standard zone. The 30% zone should only be used if required by local
regulations.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 128

4.9 Miscellaneous Programming Options


System Trouble Options

• Address: 1265
• Default: 0
• Selections: 0 to 3
Enter This Data Digit to Select Options
System Trouble Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected •
Enable AC Fail Trouble Tone • •
Enable Ground Fault Display and Trouble Tone • •
Reserved
Reserved

• Enable AC Fail Trouble Tone: This option enables the AC Fail Trouble Tone. All keypads sound the
trouble tone when an AC Fail condition occurs. This tone must be silenced from each area.
• Enable Ground Fault Display and Trouble Tone: This option enables the Ground Fault display on the
LCD keypad and the accompanying trouble tone (both LCD and LED keypads). All LCD keypads display a
Ground Fault message and all keypads sound a trouble tone when a Ground Fault condition occurs. The
display and tone must be cleared from each area.

If Ground Fault reports are disabled and the Ground Fault Display & Trouble Tone parameter is
disabled, then ground fault events are not logged.

Factory Default

• Address: 2944
• Default: 0 (Maintain user-specified changes)
• Selections:
− 0 = Maintain user-specified changes
− 1 = Return all parameters to factory default settings

This parameter restores all of the manufacturer’s default settings for all parameters (including this one)
when a “1” is entered.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 129

4.10 Network Communication

Firmware revision 2.10 or greater is required for network communication.

The control panel can be configured to communicate over an Ethernet network. Reports can be sent over this
network from the control panel to the ARC receiver. Remote programming can also be conducted over this
network. A DX4020 Network Interface Module (NIM) is required for network communication. See “Network
Interface Module (DX4020)” in the DS7200V2 Installer’s Guide (P/N: 4998153893) for installation/configuration
instructions.
Use the following steps to configure the control panel for network communication:
1. Enter an IP address for the ARC receiver [refer to IP Address 1 (2) for Destination 1 (2)].
2. If necessary, enter a port number for the ARC receiver’s IP address (refer to page 130).
3. Set the Alternate Communication Options parameter to “5” (refer to page 132).
4. Set the Network Interface Module Options parameter to “3” (refer to page 135).

IP Address 1 (2) for Destination 1 (2)

• Address:
− IP Address 1, Destination 1: 0000 to 0031
− IP Address 2, Destination 1: 0032 to 0063
− IP Address 1, Destination 2: 0066 to 0097
− IP Address 2, Destination 2: 0098 to 0129
• Default: All zeroes (0)
• Selections: 000.000.000.000 to 255.255.255.255
Each routing destination can be configured as a phone number or an IP address for network communication.
When entering an IP address, only the first 12 digits are used. For example, to enter an IP address of 172.30.1.101
into the Phone 1, Destination 1 addresses, enter the following digits in the first 12 addresses: 1, 7, 2, 0, 3, 0, 0, 0, 1,
1, 0, 1.
See Table 30 for entry selections.

Table 30: IP Address Entry Selections

Digit Enter at Keypad Digit Enter at Keypad


1 [1] 6 [6]
2 [2] 7 [7]
3 [3] 8 [8]
4 [4] 9 [9]
5 [5] 0 [0] or [1][0]

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 130

Port Number for IP Address 1 (2) for Destination 1 (2)

• Address:
− Port Number for IP Address 1, Destination 1: 3886 to 3890
− Port Number for IP Address 2, Destination 1: 3891 to 3895
− Port Number for IP Address 1, Destination 2: 3896 to 3900
− Port Number for IP Address 2, Destination 2: 3901 to 3905
• Default: 07700
• Selections: 0 to 65,535
Use the addresses listed above to associate the ARC’s IP address to a specific port number for network
communication.
This parameter uses five addresses for each routing destination to enter the port number:
• First Address: Enter the 10,000’s value (this value is multiplied by 10,000)
• Second Address: Enter the 1,000’s value (this value is multiplied by 1,000)
• Third Address: Enter the 100’s value (this value is multiplied by 100)
• Fourth Address: Enter the 10’s value (this value is multiplied by 100)
• Fifth Address: Enter the 1’s value (this value is added to the other values)
The following example shows how to enter 55555 as the port number for IP Address 1, Destination 1:
[5 x 10,000] + [5 x 1,000] + [5 x 100] + [5 x 10] + 5 = Port Number 55,555
Address 3886 Entry Address 3890 Entry

Address 3887 Entry Address 3889 Entry

Address 3888 Entry

Remote Programming Callback Number

• Address: 0181 to 0212


• Default: All zeroes (0)
• Selections: 000.000.000.000 to 255.255.255.255 (see Table 30 on page 129)
An IP address can be used to begin a remote programming session. See IP Address 1 (2) for Destination 1 (2) to
enter an IP address. See Remote Programming Call Back Number on page 16 for more information.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 131

Port Number for Remote Programming Callback

• Address: 3906 to 3910


• Default: 07700
• Selections: 0 to 65,535
Program the above addresses to identify the remote programming computer’s port number to the control panel.
This applies when the control panel begins an RPS session or calls the RPS computer back.
This parameter uses five addresses to enter the port number:
• First Address: Enter the 10,000’s value (this value is multiplied by 10,000)
• Second Address: Enter the 1,000’s value (this value is multiplied by 1,000)
• Third Address: Enter the 100’s value (this value is multiplied by 100)
• Fourth Address: Enter the 10’s value (this value is multiplied by 100)
• Fifth Address: Enter the 1’s value (this value is added to the other values)
The following example shows how to enter 55555 as the port number for Remote Programming Callback:
[5 x 10,000] + [5 x 1,000] + [5 x 100] + [5 x 10] + 5 = Port Number 55,555
Address 3906 Entry Address 3910 Entry

Address 3907 Entry Address 3909 Entry

Address 3908 Entry

Format for Destination 1 (2)

• Address:
Format for Destination 1: 0064
Format for Destination 2: 0130
• Default: 2 (Contact ID)
• Selections:
2 = Contact ID
3 = SIA 300
4 = Basic Pager
6 = BSIA Fast Format
7 = Personal Dialing Format
11 = SIA 300 with Text Blocks
If network communication is enabled, the control panel automatically selects Contact ID as the reporting format.
Contact ID only supports four-digit account numbers. This results in the control panel automatically truncating
account numbers for four digits.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 132

Alternate Communication Options

• Address:
− IP Address 1, Destination 1: 3506
− IP Address 2, Destination 1: 3514
− IP Address 1, Destination 2: 3522
− IP Address 2, Destination 2: 3530
• Default: 0
• Selections: 0, 1, 3, 5, 7
Enter This Data Digit to Select Options
Alternate Communication Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Alternate Communication •
Enable Alternate Communication • • • •
Enable Anti-Replay • •
Use ARC Acks • •
Reserved

• Enable Alternate Communication: Select this option to enable network communication. You must enter at
least one IP address as a routing destination. See IP Address 1 (2) for Destination 1 (2) on page 129 for more
information.
• Enable Anti-Replay: Anti-replay prevents unauthorized messages from being sent to the ARC and being
recognized as having originated from the control panel. Select this option to use the anti-replay procedure. To
use this option, make sure “Include IP Address” is enabled.
• Use ARC Acks: If this option is enabled, the control panel waits for an acknowledgment (Ack) from the ARC
before sending a second message. If this option is disabled, the control panel waits approximately 120 sec.
between sending messages (disable only for special applications).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 133

Remote Programming Callback Number Alternate Communication Options

• Address: 3538
• Default: 0
• Selections:
0 = No Alternate Communication
1 = Enable Alternate Communication
If an IP address is entered into the Remote Programming Callback Number addresses (Addresses 0181-0212),
RPS can be used to program the control panel over an Ethernet network.
Select “1” if an IP address is entered into the Remote Programming Callback Number addresses.

Alternate Communication Wait Time

• Address:
− IP Address 1, Destination 1: 3507 to 3509
− IP Address 2, Destination 1: 3515 to 3517
− IP Address 1, Destination 2: 3523 to 3525
− IP Address 2, Destination 2: 3531 to 3533
• Default: 0, 1, 3
• Selections: 0 to 1665 sec
Use this parameter to define how long the DX4020 waits before attempting to send additional reports to the ARC.
This parameter uses three addresses for each routing destination. In the first address, enter the 100’s value (this
value is multiplied by 100). In the second address, enter the 10’s value (this value is multiplied by 10). In the third
address, enter the 1’s value (the 100’s and 10’s values are added to the 1’s value).
The following example shows how to get an alternate communication wait time of 555 sec for IP Address 1,
Destination 1:
[5 x 100] + [5 x 10] + 5 = 555 sec
Address 3507 Entry
Address 3509 Entry
Address 3508 Entry

If the “Use ARC Acks” option is enabled and the alternate communication wait time is less than 5 sec, a
minimum of 5 sec is automatically used.
You can enter a value between 0 and 15 for each alternate communication wait time address.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 134

Alternate Communication Heartbeat Period

• Address:
− IP Address 1, Destination 1: 3510 to 3513
− IP Address 2, Destination 1: 3518 to 3521
− IP Address 1, Destination 2: 3526 to 3529
− IP Address 2, Destination 2: 3534 to 3537
• Default: 0, 0, 7, 5
• Selections: 0 to 1275 sec
Use this parameter to set the rate that the DX4020 polls the ARC.
This parameter uses four addresses for each routing destination. In the first address, enter the 1000’s value (this
value is multiplied by 1000). In the second address, enter the 100’s value (this value is multiplied by 100). In the
third address, enter the 10’s value (this value is multiplied by 10). In the fourth address, enter the 1’s value (the
1000’s, 100’s, and 10’s values are added to the 1’s value).
The following example shows how to get an alternate communication wait time of 5555 sec for IP Address 1,
Destination 1:
[5 x 1000] + [5 x 100] + [5 x 10] + 5 = 5555 sec
Address 3510 Entry
Address 3513 Entry
Address 3511 Entry
Address 3512 Entry
If the entries equal 0 sec, this parameter is disabled.
If the entries equal 1 to 4 sec, this parameter is automatically set to 5 sec.
If the entries exceed 1275 sec, this parameter is automatically set to 1275 sec.

Alternate Communication Heartbeat Retries

• Address: 3539 to 3540


• Default: 0, 2
• Selections: 0 to 99 retries
Use this parameter to define how many times the DX4020 tries to send reports to the ARC before declaring a
communication failure.
This parameter uses two addresses. Address 3539 sets the 10’s value, and Address 3540 sets the 1’s value. For
example, if you want the DX4020 to make 10 communication attempts before declaring a communication failure,
enter “1” in Address 3539 and “0” in Address 3540.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 135

Network Interface Module Options

• Address: 3541
• Default: 0
• Selections: 0 to 3
Enter This Data Digit to Select Options
Network Interface Module Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Alternate Communication •
Enable Alternate Communication • •
Include IP Address • •
Reserved
Reserved

• Enable Alternate Communication: Select this option to supervise the connection between the control panel
and the network interface module (DX4020). The network interface module’s DIP switch address must be set
to 134. Do not select this option if there is no network interface module connected to the system.
• Include IP Address: Select this option to use the IP address entered in IP Address 1 (2) for Destination 1 (2)
(see page 129) instead of the IP address stored in the DX4020 for network communication. Select “Enable
Alternate Communication” in Alternate Communication Options (refer to page 132) for the appropriate IP
address. Select this option when using a DX4020. Do not select this option when using a DX4010i.
4.11 DACM Configuration
The control panel supports up to 8 DACMs. However, each DACM added to the system replaces one
keypad. If 8 DACMs are added, you cannot add a keypad. For full system control, make sure at least
one text keypad is included in the system.
For complete installation, programming, addressing, and operation instructions, see the documentation
supplied with the DACM.

Configuring a DACM into the control panel is a three-step process:


1. Using Table 13 on page 80, assign the DACM’s door contact as a location. For example, DACM #1 will
be assigned to Location #5.
a. Enter “6” at Address 0726 for the device type.
b. Assign a zone function and enter it in Address 0727.
c. Assign an area to the DACM in Address 0728. Each DACM’s door contact can only use one
location.
d. Repeat the area assignment in Keypad/Door Access Control Module (DACM) Area Options. For
example, if you selected Area 1 for Address 0728, then you must enter “9” in Address 0679. This
address is for Keypad/DACM #1. “9” identifies the device as a DACM #1 in Area 1.
e. Assign a zone number in Addresses 0729-0730 if the zone number must be different than the
location number.
2. Enter the location number in DACM Location Assignment. For this example, enter “0” in Address 3546, and
“5” in Address 03547. This assigns the control panel’s Location #5 to DACM #1.
3. Assign global options in Address 3562 (see DACM Global Options on page 137). The entry you make here
affects all DACMs connected to the control panel.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 136

Keypad/Door Access Control Module (DACM) Area Options

• Address:
Keypad/DACM 1: 0679
Keypad/DACM 2: 0681
Keypad/DACM 3: 0683
Keypad/DACM 4: 0685
Keypad/DACM 5: 0687
Keypad/DACM 6: 0689
Keypad/DACM 7: 0691
Keypad/DACM 8: 0693
• Default:
Keypad/DACM 1: 1 (Device is a keypad/DACM assigned to Area 1)
Keypads/DACMs 2 to 8: 0 (No keypad/DACM assigned)
• Selections: 0 to 4, 9 to 12
Enter This Data Digit to Select Options
Keypad/DACM Area Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Keypad/DACM not assigned (disabled) •
Assign Keypad/DACM to Area 1 • •
Assign Keypad/DACM to Area 2 • •
Assign Keypad/DACM to Area 3 (DS7240V2 only) • •
Assign Keypad/DACM to Area 4 (DS7240V2 only) • •
Device is a Keypad • • • •
Device is a DACM • • • •

This parameter identifies the device connected to the control panel’s Data Bus (Addresses 1 to 8) as a DACM, and
assigns the DACM to an area.
The control panel supervises the connection to the DACM. If it fails to communicate with the control panel, the
control panel sends a “DBus Missing” {125} report.

DACM Location Assignment

• Address:
− DACM 1: 3546 to 3547
− DACM 2: 3548 to 3549
− DACM 3: 3550 to 3551
− DACM 4: 3552 to 3553
− DACM 5: 3554 to 3555
− DACM 6: 3556 to 3557
− DACM 7: 3558 to 3559
− DACM 8: 3560 to 3561
• Default: 0,0
• Selections:
− DS7240V2: 0,0 to 4,0
− DS7220V2: 0,0 to 2,4
A DACM door contact can occupy any location in the control panel. Use this parameter to assign a control panel
location to a DACM door contact.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 137

DACM Global Options

• Address: 3562
• Default: 0
• Selections: 0, 1, 3-5, 7
Enter This Data Digit to Select Options
DACM Global Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No DACM Global Options Selected •
Enable Arming Confirmation • • • •
Any User Confirms Arming • •
Use Tamper-Wired Processing • • •
Reserved

This is a global parameter that affects all DACMs connected to the control panel.
• Enable Arming Confirmation: If this option is enabled, verifying a user at the DACM reader during Exit
Delay cancels the remaining Exit Delay time and arms the control panel immediately. Only the user who
started the arming process can confirm arming. If this option is disabled, verifying a user at the DACM reader
during Exit Delay cancels the arming process (the system does not arm).
• Any User Confirms Arming: If this option is enabled, any user can confirm system arming. If this option is
disabled, only the user who started the arming process can confirm arming. This option only applies when
“Enable Arming Confirmation” is selected.
• Use Tamper-Wired Processing: If this option is enabled, an open door reports as faulted (the zone assigned
to the DACM functions as a tamper-wired zone). If this option is disabled, an open door reports as shorted
(the zone assigned to the DACM functions as a single EOL zone).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 138

5. Reference Materials
5.1 Control Panel Events and Reporting Formats
The following table includes each control panel event, the description for each event as it appears in the control
panel log, the reports sent for each event, the zone types linked to the event, and the RPS Event Alert Group
number. The RPS Event Group numbers also correspond with the Personal Dialing Format Event Group
numbers. See Personal Dialing Format on page 10 for more information.
The last column, Status Reports, indicates System Status events. An “R” indicates that reports for the event follow
the System Status routing. An “S” indicates that the event follows the System Status Swinger Count. System
reports do not include an Area number; they use the account number for Area 1.
If the control panel is configured for network communication, reports are sent using the Contact ID format.
The event numbers shown in the following table are the same numbers that show up on a pager for each
corresponding report.

Table 31: Control Panel Events and Reporting Formats

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
01 AC Fail AT AC Trouble 301 AC Loss AC Power to panel interrupted. 12 R S
02 AC Restore AR AC Restoral 301 AC Loss AC Power to panel restored. 12 R S
03 Alarm,Tamper TA Tamper Alarm 137 Tamper Alarm, Tamper Zone Type. 4-Tamper 3
04* Alarm,Emergency QA Emergency 101 Personal Alarm, Emergency Zone Type or 5- Emergency 3
Alarm Emergency ABC key programmed for
emergency response. [Q] button.
05* Alarm,Panic PA Panic Alarm 120 Panic Alarm, Panic-Visible Zone Type. [Q] 6- Visible Panic 3
button.
06* Alarm,Invisible HA Holdup Alarm 120 Panic Alarm, Panic- Invisible Zone Type 7-Invisible Panic 3
or ABC key programmed for panic
response. [Q] button.
07 Alarm,24-hr Burg BA Burglary 133 24 Hr Alarm, Burglary Zone Type. 8- Burglary 3
Alarm Safe 15 - Door
08 Alarm,Cntrl,Dly BA Burglary 134 Entry/Exit Alarm, Delay 1 or Delay 2 Zone 11- E/E Delay 1 3
Alarm Type. 12- E/E Delay 2
09 Alarm,Cntrl BA Burglary 130 Burglary Alarm, Keyswitch or Follower or 10- Keyswitch 3
Alarm Instant Zone Types. 13- Follower
14- Instant
10 Cross,Tamper BM Burglary 137 Tamper Alarm, Tamper Zone Type with 4-Tamper 3
Alarm Cross Cross Zone Option selected.
Zone
11 Cross,Emergency BM Burglary 101 Personal Alarm, Emergency Zone Type with 5- Emergency 3
Alarm Cross Emergency Cross Zone Option selected.
Zone
12 Cross,Panic BM Burglary 120 Panic Alarm, Panic-Visible Zone Type 6- Visible Panic 3
Alarm Cross with Cross Zone Option selected.
Zone
13 Cross,Invisible BM Burglary 120 Panic Alarm, Panic- Invisible Zone Type 7-Invisible Panic 3
Alarm Cross with Cross Zone Option selected.
Zone
14 Cross,24hr Burg BM Burglary 133 24 Hr Alarm, Burglary Zone Type with 8- Burglary 3
Alarm Cross Safe Cross Zone Option selected.
Zone

* Keypad [A], [B], or [C] keys report as Zones 100, 101, and 102. The [Q] button on a keyfob reports as User
Number +200.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 139

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
15 Cross,Cntrl,Dly BM Burglary 134 Entry/Exit Alarm, Delay 1 or Delay 2 Zone 11- E/E Delay 1 3
Alarm Cross Type with Cross Zone Option 12- E/E Delay 2
Zone selected.
16 Cross,Cntrl BM Burglary 130 Burglary Alarm, Follower or Instant Zone 13- Follower 3
Alarm Cross Types with Cross Zone Option 14- Instant
Zone selected.
17 Cross,Unverified BG Unverified 378 Cross- A fault on one non-fire zone type any with Cross 3
Event Burglary zone Trouble with the Cross Zone Option Zone Option
selected. This is not an alarm event.
18 Alarm Exit Error EA Exit Alarm 374 Exit Error Zone faulted at the end of Exit 11- E/E Delay 1 3
(zone) Delay. 12- E/E Delay 2
19 Alrm Recent Clse CR Recent 134 Entry/Exit Alarm event within 2 min. of 11- E/E Delay 1 3
Closing closing. 12- E/E Delay 2
20 Alrm Recent Clse CR Recent 130 Burglary Alarm event within 2 min. of 10- Keyswitch 3
Closing closing. 13- Follower
14- Instant
21 Auto On Extended CE Closing 464 Auto-arm Auto On Sked delayed one h by 10
Extend Time Extended user. Report follows Open/Close
routing.
22 Battery Low YT System 302 Low Panel battery is low. 12 R S
Battery Trouble System Battery
23 Battery Missing YM System 311 Battery Panel battery is missing. Very low, 12 R S
Battery Missing Missing/Dead shorted, or open batteries are
reported as missing.
24 Rstrl Batt Low YR System 302 Low Battery restoral from low battery. 12 R S
Battery Restoral System Battery
25 Rstrl Bat Missng YR System 311 Battery Battery Restoral from missing 12 R S
Battery Restoral Missing/Dead battery
26 Bypass,Fire,User FB Fire Bypass 571 Fire Selective bypass by user, fire zone 1- Fire 15
bypass types. 2- Fire with
Alarm
Verification
27 Bypass,Fire, RPS FB Fire Bypass 571 Fire Selective bypass by RPS, fire zone 1- Fire
bypass types. 2- Fire with
Alarm
Verification
28 Bypass,Ctrl,User BB Burglary 570 Selective bypass by user, 10 to 15- Zone 15
Bypass Zone/Sensor controlled zone types. Types
bypass
29 Bypass,Ctrl, RPS BB Burglary 570 Selective bypass by RPS, zone 10 to 15- Zone
Bypass Zone/Sensor types. Types
bypass
30 Bypass,24hr,User BB Burglary 572 24-Hr Selective bypass by user, 24-hour 3 to 9- 24-hour, 15
Bypass Zone Bypass non-fire zone types. Non-Fire Zone
Types
31 Bypass,24hr, RPS BB Burglary 572 24-Hr Selective bypass by RPS, 24-hour 3 to 9- 24-hour,
Bypass Zone Bypass non-fire zone types. Non-Fire Zone
Types
32 Bypass,Forced Zn BB Burglary 570 Zone force armed at force arming. 10 to 15- Zone 15
Bypass Zone/Sensor Types
bypass

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 140

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
33 Bypass,Swinger BB Burglary 575 Swinger Zone Swinger Shunted. All zone types 15
Bypass Shunt
34 UnBypss,Fire, Usr FU Fire UnBypass 571 Fire User cleared bypass (unbypass), 1- Fire 15
bypass Fire zone types. 2- Fire with
Alarm
Verification
35 UnBypss,Ctrl,Usr BU Burglary 570 User cleared bypass (unbypass), 10 to 15- Zone 15
Unbypass Zone/Sensor controlled zone types. Types
bypass
36 UnBypss,24hr,Usr BU Burglary 572 24-Hr User cleared bypass (unbypass), 3 to 9- 24-hour, 15
Unbypass Zone Bypass 24-hour zone types. Non-Fire Zone
Types
37 Call for Service YX Service 616 Service This report sent automatically at 12 R
Required Request Call for Service Interval. It does not
indicate a trouble condition.
38 Cancel Alarm BC Burglary 406 Cancel User acknowledged active alarm 8
Cancel before Bell Time expired, non-fire
zone types.
39 Cancel Fire FC Fire Cancel 406 Cancel User acknowledged active alarm 7
before Bell Time expired, fire zone
types.
40 CheckSum Fail YF Parameter 303 RAM Checksum on panel’s parameters 12 R S
Checksum Fail Checksum Bad failed. Panel program should be
verified.
41 ChkSum Fail,DBus YF Parameter 330 System Checksum on Data Bus device 12 R S
Checksum Fail Peripheral parameters failed. Device should
trouble be checked.
42 Cls,All,+Dly,Skd CA Automatic 403 Automatic System turned All On with 10
Closing O/C Entry/Exit Delay by Sked.
43 Cls,All,+Dly,KS CS Closing 409 Keyswitch System turned All On with 10
Keyswitch O/C Entry/Exit Delay by Keyswitch.
44 Cls,All,+Dly, RPS CQ Remote 400 System turned All On with
Closing Open/Close Entry/Exit Delay by RPS.
45 Cls,All,+Dly,Tel CQ Remote 407 Remote System turned All On with 10
Closing Arm/Disarm Entry/Exit Delay by Telephone.
46 Cls,All,+Dly,Usr CL Closing 401 O/C by System turned All On with 10
Report User Entry/Exit Delay by User.
47 Cls,All,-Dly,RPS CQ Remote 400 System turned All On with no delay
Closing Open/Close (instant) by RPS.
48 Cls,All,-Dly,Usr CL Closing 401 O/C by System turned All On with no delay 10
Report User (instant) by User.
49 Cls,Prt,+Dly,Skd CA Automatic 456 Partial Arm System armed Perimeter Only with 10
Closing Entry/Exit delay by Sked.
50 Cls,Prt,+Dly,KS CS Closing 442 Keyswitch System armed Perimeter Only with 10
Keyswitch Armed Stay Entry/Exit Delay by Keyswitch.
51 Cls,Prt,+Dly, RPS CQ Remote 456 Partial Arm System armed Perimeter Only with
Closing Entry/Exit Delay by RPS.
52 Cls,Prt,+Dly,Usr CL Closing 456 Partial Arm System armed Perimeter Only with 10
Report Entry/Exit Delay by User.
53 Cls,Prt,-Dly, RPS CQ Remote 456 Partial Arm System armed Perimeter Only with
Closing no delay (instant) by RPS.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 141

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
54 Cls,Prt,-Dly,Usr CL Closing 456 Partial Arm System armed Perimeter Only with 10
Report no delay (instant) by User.
55 Frc,All,+Dly,Skd CF Forced 403 Automatic System forced All On with 10
Closing O/C Entry/Exit Delay by Sked.
56 Frc,All,+Dly,KS CF Forced 400 O/C System forced All On with 10
Closing Entry/Exit Delay by Keyswitch.
57 Frc,All,+Dly, RPS CF Forced 400 O/C System forced All On with
Closing Entry/Exit Delay by RPS.
58 Frc,All,+Dly,Tel CF Forced 400 O/C System forced All On with 10
Closing Entry/Exit Delay by Telephone.
59 Frc,All,+Dly,Usr CF Forced 401 O/C by System forced All On with 10
Closing User Entry/Exit Delay by User.
60 Frc,All,-Dly,RPS CF Forced 400 O/C System forced All On with no delay
Closing (instant) by RPS.
61 Frc,All,-Dly,Usr CF Forced 401 O/C by System forced All On with no delay 10
Closing User (instant) by User.
62 Frc,Prt,+Dly,Skd NF Forced 456 Partial Arm System forced Perimeter Only with 10
Perimeter Arm Entry/Exit Delay by Sked.
63 Frc,Prt,+Dly,KS NF Forced 456 Partial Arm System forced Perimeter Only with 10
Perimeter Arm Entry/Exit Delay by Keyswitch.
64 Frc,Prt,+Dly, RPS NF Forced 456 Partial Arm System forced Perimeter Only with
Perimeter Arm Entry/Exit Delay by RPS.
65 Frc,Prt,+Dly,Usr NF Forced 456 Partial Arm System forced Perimeter Only with 10
Perimeter Arm Entry/Exit Delay by User.
66 Frc,Prt,-Dly, RPS NF Forced 456 Partial Arm System forced Perimeter Only with
Perimeter Arm no delay (instant) by RPS.
67 Frc,Prt,-Dly,Usr NF Forced 456 Partial Arm System forced Perimeter Only with 10
Perimeter Arm no delay (instant) by User.
68 Reserved
69 Comm Fail YC 354 Failure to Report failed to reach routing 12 R S
Communications communicate destination.
Fail event
70 CommFail, AltComm YC 354 Failure to Report failed to reach routing 12 R S
Communications communicate destination configured for Alternate
Fail event Communication.
71 Comm Restoral YK 354 Failure to After communication fail, report 12 R S
Communications communicate sent successfully to routing
Restoral event destination.
72 CommRstl, YK 354 Failure to After communication fail, report 12 R S
AltComm Communications communicate sent successfully to routing
Restoral event destination configured for Alternate
Communication.
73 Date/Time Change JT Time Changed 625 Time/Date Date/Time in panel changed. 12 R
reset
74* Duress HA Hold Up 121 Duress User entered Duress PIN or 1
Alarm pressed Panic key sequence or [Q]
button** on RF Keyfob. The Duress
report is sent in addition to any
other report that the user’s action
would generate.

* This event reports a user number + 200 when sent using SIA and Contact reporting formats.
** See [Q] Button Alarm Response Options on page 76 for more information.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 142

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
75 Fire,Alarm FA Fire Alarm 110 Fire Alarm event on fire zone type. 1- Fire 2
2- Fire with
Alarm
Verification
76 Fire,Cross FM Fire Alarm 110 Fire Verified alarm event on fire zone 1- Fire 2
Cross Zone type with Cross Zone Option. See
Zone Response Options on page
103.
77 Fire,Un-verified FG Unverified 378 Cross- Unverified alarm event on fire zone 1- Fire 5
Event-Fire zone Trouble type with Cross Zone Option. Or 2- Fire with
unverified event on Fire Verify zone Alarm
type. Verification
78 Fire,Missing FY Missing Fire 373 Fire Fire zone type assigned to zone 1- Fire 5
Trouble Trouble expander (wired or RF) not 2- Fire with
responding to panel’s status poll. Alarm
Verification
79 Fire,Alrm,Rstl FH Fire Alarm 110 Fire Restoral from alarm, Fire zone 1- Fire 7
Restore types. 2- Fire with
Alarm
Verification
80 Fire,Trouble FT Fire Trouble 373 Fire Fault (Trouble) condition on Fire 1- Fire 5
Trouble zone types. 2- Fire with
Alarm
Verification
81 Fire,Trbl,Rstl FJ Fire Trouble 373 Fire Restoral from Trouble, Fire zone 1- Fire 7
Restore Trouble types. 2- Fire with
Alarm
Verification
82 Instl Mode,Start LB Local Program 466 Service Installer PIN entered. Installer mode 11 R
On Premises accessed.
83 Instl Mode,End LX Local 466 Service Installer mode exited. 11 R
Programming Off Premises
Ended
84 Log Overflow JO Log Overflow 624 Event Log Panel log overflow condition. 12 R
Overflow Oldest events being overwritten.
85 Log Threshold JL Log Threshold 623 Event Log Panel log reached threshold. See 12 R
Log Supervision Configuration on
page 25.
86 AltCom Low Signl XL Low Received 350 Low Signal Strength detected on 12 R S
Signal Strength Communication Alternate Communication device.
Trouble
87 Missing,Alarm UZ Untyped 150 General Zone assigned to zone expander 8- 24-hr Burg 3
Missing Alarm Alarm (wired or RF) not responding to 10-15 Zone
panel’s status poll while the area is Types
armed.
88 Missing,Trouble UY Untyped 382 Loss of Zone assigned to zone expander 3-8, 10-15 Zone 6
Missing Trouble supervision - (wired or RF) not responding to Types
RPM panel’s status poll while the area is
disarmed.
89 Open,Skd OA Automatic 403 Automatic Opening by Sked. 10
Opening O/C
90 Open,RPS OQ Remote 400 Opening by RPS.
Opening Open/Close

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 143

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
91 Open,Usr OP Opening 401 O/C by Opening by user, by ID reported. 10
Report User
92 Open,KS OS Opening 409 Keyswitch Opening by Keyswitch. 10
Keyswitch O/C
93 Open,Skd,Alarm OR Disarm from 403 Automatic Opening after Alarm event by Sked. 10
Alarm O/C
94 Open,RPS,Alarm OR Disarm from 400 Opening after Alarm event by RPS.
Alarm Open/Close
95 Open,Usr,Alarm OR Disarm from 401 O/C by Opening after Alarm event, ID 10
Alarm User reported.
96 Open,KS,Alarm OR Disarm from 409 Keyswitch Opening after Alarm event by 10
Alarm O/C Keyswitch.
97 Reserved
98 Params Changed YG Parameter 306 Panel Panel parameters changed. 12 R
Changed Programming
Changed
99 Phone Line Fail LT Phone Line 351 Telco 1 Phone line voltage less than 3 V for 12 R S
Trouble fault 40 sec.
100 Phone Line Rstl LR Phone Line 351 Telco 1 After Phone Line Fail event, phone 12 R S
Restoral fault line voltage detected at greater
than 3 V for 40 sec.
101 Bad Call to RPS RA Remote 413 Panel attempted call to RPS, but 12 R
Programmer Call Unsuccessful was unsuccessful.
Failed access
102 RPS Access Fail RU Remote 413 RPS attempted to connect to panel R
Program Fail Unsuccessful but was not successful.
access
103 RPS Access OK RS Valid Remote 412 RPS successfully connected to R
Access Successful and disconnected from panel.
Download/
Access
104 Re-Boot,Panel RR Power Up 305 System Normal start up or reset after R S
reset programming.
105 Re-Boot,DBus RR Power Up 339 Exp. Unexpected reset (reboot) from 12 R S
Module Reset Data Bus device.
106 Output Reset,Usr RO Relay Open 320 Output Reset by User. 16 R
Sounder/Relay
107 Output Reset,Skd RO Relay Open 320 Output Reset by Sked. 16 R
Sounder/Relay
108 Output Reset, RPS RO Relay Open 320 Output Reset by RPS. R
Sounder/Relay
109 Output Set,Usr RC Relay Close 320 Output Set by User. 16 R
Sounder/Relay
110 Output Set,Skd RC Relay Close 320 Output Set by Sked. 16 R
Sounder/Relay
111 Output Set,RPS RC Relay Close 320 Output Set by RPS. R
Sounder/Relay
112 Rstrl,Tamper TR Tamper 137 Tamper Restoral from alarm, Tamper zone 4- Tamper 8
Restoral type.
113 Rstrl,Emergency QR Emergency 101 Personal Restoral from alarm, Emergency 5- Emergency 8
Restoral Emergency zone type.
114 Rstrl,Panic PR Panic 120 Panic Restoral from alarm, Panic zone 6- Visible Panic 8
Restoral type.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 144

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
115 Rstrl,Invisible HR Holdup 120 Panic Restoral from alarm, Invisible zone 7-Invisible Panic 8
Restoral type.
116 Rstrl,24-hr Burg BR Burglary 133 24hr Restoral from alarm, 24-hour 8- Burglary 8
Restoral (Safe) burglary zone types. 15 – Door
117 Rstrl,Cntrl,Dly BR Burglary 134 Entry/Exit Restoral from alarm, Delay 1 or 2 11- E/E Delay 1 8
Restoral zone types. 12- E/E Delay 2
118 Rstrl,Cntrl BR Burglary 130 Burglary Restoral from alarm, Keyswitch, 10- Keyswitch 8
Restoral Follower, or Instant zone types. 13- Follower
14- Instant
119 Rcvr Jam XQ RF 344 RF Jammed condition detected on 9 R S
Interference Receiver Jam premises RF receiver.
Detect
120 Rcvr Jam Rstl XH RF 344 RF Jammed condition detected on 9 R S
Interference Receiver Jam premises RF receiver cleared.
Restoral Detect Restoral
121 RF Battery Low XT Transmitter 384 RF Low Low Battery detected on premises Any zone type 9
Battery Trouble Battery RF transmitter.
122 RF Battery Rstl XR Transmitter 384 RF Low Low Battery condition detected on Any zone type 9
Battery Restoral Battery premises RF transmitter cleared.
123 RF Tamper Trbl TT Tamper 383 Sensor Premises RF Transmitter Tamper Any zone type 9
Trouble Tamper Fault (Trouble).
124 RF Tamper Rstl TR Tamper 383 Sensor Premises RF Transmitter Tamper Any zone type 9
Trouble Restore Tamper Restoral.
125 Dbus Missing EM Expansion 333 Exp. Data Bus device not responding to 12 R S
Device Missing Module Failure polling.
126 Dbus Missng,Rstl EN Expansion 333 Exp. Data Bus device declared as 12 R S
Missing Restore Module Failure missing now responding to polling.
127 Dbus Tamper ES Expansion 341 Exp. Tamper open on Data Bus Device 12 R S
Device Tamper Module Tamper Tamper.
128 Dbus Tamper,Rstl EJ Expansion 341 Exp. Data Bus Device Tamper Restoral. 12 R S
Tamper Restore Module Tamper
129 Dbus Trouble ET Expansion 330 System Fault (Trouble) detected on Data 12 R S
Trouble Peripheral Bus Device.
Trouble
130 Dbus Troubl,Rstl ER Expansion 330 System Data Bus Device Fault (Trouble) 12 R S
Restoral Peripheral condition cleared.
Trouble
131 Dbus OverCurrent YI Overcurrent 330 System Over current condition detected on 12 R S
Trouble Peripheral Data Bus device.
Trouble
132 Dbus OvrCur,Rstl YJ Overcurrent 330 System Over current condition on Data Bus 12 R S
Restore Peripheral device restored.
Trouble
133 Sensor Mon Trbl NA No Activity 391 Sensor Sensor fault (trouble) detected. 11-15 Zone 6
Watch trouble Reports follow zone trouble routing. Types
134 Sensor Mon Rstl NS Activity 391 Sensor Sensor trouble condition restored. 11-15 Zone 6
Restored Watch trouble Reports follow zone trouble routing. Types
135 Sensor Reset Local Event Only User entered System Reset key 12
sequence ([#][4][7]).

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 145

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
136 System Inactive CD Closing System was not armed in Inactive 12 R
Delinquent Interval.. System Reset key
sequence ([#][4][7]) or arming
resets this trouble.
137 Test,OK RP Automatic 602 Period No system troubles at automatic 13
Test Test Report test report time.
138 Test,Off-Normal RY Test Off 608 Period System trouble present at test time. 13
Normal Test Report,
System Trouble
Present
139 Trbl,Tamper TT Tamper 380 Sensor Trouble condition on Tamper or any 4-Tamper or any 6
Trouble Trouble tamper-wired zones. zone
140 Trbl,Emergency QT Emergency 380 Sensor Trouble condition on Emergency 5- Emergency 6
Trouble Trouble zone type.
141 Trbl,Panic PT Panic Trouble 375 Panic Trouble condition on Panic zone 6- Visible Panic 6
Zone Trouble type.
142 Trbl,Invisible HT Holdup 375 Panic Trouble condition on Invisible zone 7-Invisible Panic 6
Trouble Zone Trouble type.
143 Trbl,24-hr Burg BT Burglary 380 Sensor Trouble condition on Burglary zone 8- Burglary 6
Trouble Trouble type. 15 - Door
144 Trbl,Cntrl,Dly BT Burglary 380 Sensor Trouble condition on Delay zone 11- E/E Delay 1 6
Trouble Trouble types. 12- E/E Delay 2
145 Trbl,Cntrl BT Burglary 380 Sensor Trouble condition on Keyswitch, 10- Keyswitch 6
Trouble Trouble Follower, and Instant zone types. 13- Follower
14- Instant
146 Rstrl,Trbl,Tmpr TJ Tamper 380 Sensor Restoral from Tamper trouble 4- Tamper or 8
Trouble Restore Trouble condition. any zone
147 Rstrl,Trbl,Emerg QJ Emergency 380 Sensor Restoral from trouble condition on 5- Emergency 8
Trouble Restore Trouble Emergency zone type.
148 Rstrl,Trbl,Panic PJ Panic Trouble 375 Panic Restoral from trouble condition on 6- Visible Panic 8
Restore Zone Trouble Panic zone type.
149 Rstrl,Trbl,Invis HJ Holdup 375 Panic Restoral from trouble condition on 7-Invisible Panic 8
Trouble Restore Zone Trouble Invisible zone type.
150 Rstrl,Trbl,24-hr BJ Burglary 380 Sensor Restoral from trouble condition on 8- Burglary 8
Trouble Restore Trouble Burglary zone type. 15 - Door
151 Rstrl,Trbl,Dly BJ Burglary 380 Sensor Restoral from trouble condition on 11- E/E Delay 1 8
Trouble Restore Trouble Delay zone types. 12- E/E Delay 2
152 Rstrl,Trbl,Cntrl BJ Burglary 380 Sensor Restoral from trouble condition on 10- Keyswitch 8
Trouble Restore Trouble Keyswitch, Follower, and Instant 13- Follower
zone types. 14- Instant
153 User Code Area Set JY User Code User Code ‘added’ by assigning 16 R
Added area.
154 User Code Change JV User Code User Code changed. 16 R
Changed
155 User Code Delete JX User Code User Code deleted. 16 R
Deleted
156 User Code Tamper JA User Code 461 Wrong Invalid User Codes entered at 16 R
Tamper Code Entry keypad exceeded User Tamper
Retry Count. See page 62.
157 User Level Set JZ User Level Set User Level set. 16 R

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 146

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
158 Walk Test Start TS Test Start 607 Walk Test Walk Test started with Walk Test 11
Mode key sequence ([#][4][4]).
159 Walk Test End TE Test End 607 Walk Test Walk Test ended by user or timed 11
Mode out.
160 Siren Trouble YA Bell Fault 320 Sounder Trouble condition detected on PO 12 R S
Relay 2 configured as supervised siren
output.
161 Siren Restoral YH Bell Restored 320 Sounder Trouble condition on supervised 12 R S
Relay siren output cleared.
162 Grnd Fault IA Equipment 310 Ground Ground fault detected on panel’s 12 R S
Failure Condition Fault sensor loops, Option Bus, or Aux
power outputs.
163 Grnd Fault,Rstl IR Equipment Fail 310 Ground Ground fault condition cleared. 12 R S
Restoral Fault
164 First Open OP Opening 400 Panel is configured for multiple 10
Report Open/Close area first to open, last to close
function. See Arming Options 2 on
page 38. First area has opened.
165 Last Close CL Closing 400 Panel is configured for multiple 10
Report Open/Close area first to open, last to close
function. See Arming Options 2 on
page 38. Last area has closed.
166 AltCom Cond NC Network 350 Trouble detected on Alternate 12 R S
Condition Communication Communication network.
Trouble
167 AltComm Fail NT Network 350 Network failure detected on 12 R S
Failure Communication Alternate Communication network.
Trouble
168 AltComm Rstrl NR Network 350 Network communication resumed 12 R S
Restoral Communication on Alternate Communication
Trouble network.
169 Reserved
170 Reserved
171 Reserved
172 Reserved
173 Rstrl,Swinger BU Burglary 575 Swinger Restoral from Swinger Shunt. Any zone type 8
Unbypass Shunt
174 Rstrl,Fire,Miss Local Event Only Local Event Restoral from Fire Missing. Local 1- Fire 7
Only event, no report. 2- Fire with
Alarm
Verification
175 Rstrl,Alarm,Miss Local Event Only Local Event Restoral from Missing, Non-Fire Any non-fire 8
Only zones. Local event, no report sent. zone type
176 Rstrl,Trble,Miss Local Event Only Local Event Restoral from Fault (Trouble), Non- Any non-fire 8
Only Fire zones. Local event, no report. zone type
177 Rstl,Low Signl Local Event Only Local Event Restoral from Alternate 12 R S
Only Communication Low Signal
Strength event.
178 UnBypss,Fire,RPS FU Fire Unbypass 571 Fire Bypass on Fire zone type cleared 1- Fire
bypass using RPS (un-bypass). 2- Fire with
Alarm
Verification

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 147

Table 31: Control Panel Events and Reporting Formats (continued)

Event Event as shown in SIA Report Contact ID Event Description Zone Types RPS Status
Control Panel Log Report Linked to Event Event Report
Group
179 UnBypss,Ctrl,RPS BU Burglary 570 Bypass on zone type cleared using 10 to 15- Zone
Unbypass Zone/Sensor RPS (un-bypass) Types
bypass
180 UnBypss,24hr,RPS BU Burglary 572 24 hour Bypass on 24-hour zone type 3 to 9- 24-hour,
Unbypass zone bypass cleared using RPS (un-bypass) Non-Fire Zone
Types
181* RF Battery Low XT Transmitter 384 RF Low Low battery condition on RF 9 R
Battery Trouble Battery Keyfob.
182* RF Battery Rstl XR Transmitter 384 RF Low Low battery condition on RF 9 R
Battery Restoral Battery Keyfob restored.
183 Trbl,Default PIN Local Event Only Local Event Installer or User PINS have not
Only been changed from default.
184 Rstl,Default PIN Local Event Only Local Event Installer or User default PINS have
Only been changed.
185 Failed to Arm EE Exit Error 454 Failed to Arming attempt failed. 3
Close
186 Verified Alarm BV Burglary 139 Intrusion Verified Alarm. 3
Verified Alarm
187 Dbus Missng Alrm TA Tamper Alarm 137 Tamper Data bus device not responding to 12 R S
Alarm polling. (Shows Zone 41)
188 Dbs Mis Alm Rstl TR Tamper 137 Tamper Data bus device declared as 12 R S
Restoral Alarm missing now responding to polling.
(Shows Zone 41)
189 Dbus Tamper Alrm TA Tamper Alarm 137 Tamper Tamper open on Data bus Device 12 R S
Alarm Tamper. (Shows Zone 42)
190 Dbs Tmp Alm Rstl TR Tamper 137 Tamper Data bus device tamper restoral. 12 R S
Restoral Alarm (Shows Zone 42)
191 Dbus Trouble Alm TA Tamper Alarm 137 Tamper Trouble detected on data bus 12 R S
Alarm device. (Shows Zone 43)
192 Dbs Trb Alm Rstl TR Tamper 137 Tamper Data bus device trouble condition 12 R S
Restoral Alarm cleared. (Shows Zone 43)
193 Siren Missg Alrm TA Tamper Alarm 137 Tamper Trouble condition detected on PO 12 R S
Alarm 2 configured as supervised siren
output. (Shows Zone 44)
194 Siren Alarm Rstl TR Tamper 137 Tamper Trouble condition on supervised 12 R S
Restoral Alarm siren output cleared. (Shows Zone
44)

* This event reports a user number + 200 when sent using SIA and Contact reporting formats.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 148

5.2 Glossary
24-Hour Zone: Zones that are always on even when the system is turned off. Two types: Fire Zones and Non-Fire Zones.
Account The account number is the number the control panel transmits to the ARC receiver. It is not the Personal
Number: Identification Number (PIN). The account number is not sufficient identification to abort an alarm.
Address: Once the installer selects a value for a parameter, the control panel stores the selection in memory. Each
parameter uses one or more Addresses. When programming from the keypad, the installer enters a selection
directly into the memory Address(es). When programming from the remote programmer, the installer need
only make one entry per parameter.
All On: All zones are armed. All On with No Entry (Instant) is an option.
ARC: Alarm Receiving Center. A facility where trained personnel monitor a security system 24 h a day. The security
system might be programmed to contact the ARC during alarm conditions, enabling ARC personnel to
dispatch the proper authorities.
Area (Partition): An installer-specified collection of zones that can be armed and disarmed independently. An Area can report
with its own account number. Opening, closing, alarm, trouble and restoral reports are all associated with an
Area. You can organize the control panel’s zones and users into independent areas, in essence creating
independent systems with a single control panel.
Authority Level: A programmable feature that determines which functions a user can perform in a specified Area.
Burg Alarm A constant warble tone.
Tone:
Bypass: To selectively remove zones temporarily from the system.
Checksum: A method of checking accuracy of transmitted information. A number representing the total number of bits of
information transmitted is included with the transmission. The microprocessor counts the bits of information
received and compares its sum to the transmitted checksum number. If the numbers do not match, the
transmission is in error.
Cross Zone: Two zones that are configured to initiate an alarm when both zones have been faulted. 24-Hour Door and 24-
Hour Fire with Alarm Verification zones cannot be set for Cross Zone configuration.
Data Digit: Selections for data range from 0 to 15 (16 selections total). The programming selection made at each
parameter is the Data Digit. For many programming parameters, there are less than 16 choices. To properly
enter a data digit that is only one digit in length, press the appropriate number key on the keypad, or press
[0] followed by the appropriate number key. Then press [*] to enter your choice into the system. For example,
[4][*] and [0][4][*] are the same entry.
DACM: Door Access Control Module.
Duress PIN: A PIN that arms and disarms the system just like a user PIN does, however it also sends an alarm signal to
the ARC without sounding an alarm on the premises.
Entry Delay: A programmed delay of the system alarm responses that allow a person to enter the building through the
Entry door to turn the system off. An alarm response begins if the control panel is not disarmed before Entry
Delay expires.
Error Tone: The same warble tone as the Trouble tone, but not repeated.
Faulted Zone: A zone that is not normal (for example, an open door or window).
Fire Alarm Tone: A warble tone that is on for one second, then briefly off (repeatedly).
Follower Zone: A zone programmed to initiate an instant alarm unless a Delay zone is faulted first. When a Delay zone is
faulted first, the Follower zone assumes the Entry Delay time of the Delay zone.
Force Arming: A method of overriding the safety feature that prevents arming with a faulted zone on a control panel.
Global: Something that affects the entire system (for example, global zone configuration refers to the programmable
features that affect all zones).
Groups: The programming parameters described in this manual are organized into groups. Most groups primarily
contain parameters that are related in some way. For example, the Authority Levels Group contains
parameters that configure the control panel’s four Authority Levels.
Handshake: A signal sent by one end of the communications channel to the other indicating reception of signal.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 149

Instant Alarm: A zone type that initiates an alarm immediately when faulted. This zone type does not follow any Entry/Exit
delay time.
Keyfob: A small, hand-held wireless device usually designed to fit on a key chain. It consists of buttons that allow the
user to perform various functions, depending on the keyfob, such as arming/disarming the system, operating
outputs or sending reports.
Keyswitch: Two types: Momentary and Maintained. To operate a Momentary Keyswitch, insert the key, turn it and
release it. The key returns to its starting position automatically. The key cannot be removed unless it is in the
starting position. A Maintained Keyswitch typically has two positions marked “Armed” and “Disarmed.” To
operate, insert the key, turn to desired position and remove the key.
Latching: The locking in of a circuit by means of a holding contact.
Location: A Location represents the following parameter assignments: Area, Zone Number and Device. A Location tells
the control panel in which Area a device is assigned and by which Zone Number it reports as.
No Entry: Turning the system on without Entry Delay.
Off Display: The display that appears when the system is turned off and no keys are pressed (normal display).
One-Time PIN: A One-Time PIN can only be used once to turn the system off. This PIN is typically given to personnel who
need temporary access to the premises, such as a baby-sitter or a service/maintenance crew.
Options: Options are a unique type of parameter that allows the installer to configure up to four features by entering a
Data Digit at a single Address.
PSTN: Public Switched Telephone Network. An assembly of communications facilities and central office equipment
operated jointly by authorized common carriers that provides the general public with the ability to establish
communications channels via discrete dialing codes.
Parity: A method of checking the accuracy of transmitted data by adding an extra bit to the number when necessary
to make the number odd or even.
Parameter: Each program parameter sets a specific value or chooses an option.
Partial On: A user-defined subset of the zones that arm. Partial On with No Entry (Instant) is an option.
Perimeter Only: An installer-defined subset of the zones that arm. Perimeter Only with No Entry (Instant) is an option.
PIN: Personal Identification Number. A unique number issued at the time of installation of each system. This PIN is
required to operate the system (arm/disarm, test system, initiate functions, etc.). The PIN is not the same as
the account number.
Press: These are used interchangeably instructing you to push down and then release a key.
RPS: Remote Programming Software is a Windows-based account management and control panel programming
utility designed to remotely set up and program specific control panels.
Restoral Report: A signal transmitted upon the removal of a trouble or alarm condition from a zone.
Sked: A scheduling parameter that allows a selected event to happen at a specific time.
Swinger Shunt: A programmable feature that determines the number of alarms or troubles the zone can transmit. If the
number is exceeded, the zone is bypassed for the remainder of the arming period.
Tamper: Tamper conditions can be generated several different ways. A tamper-wired zone can report tamper because
the zone is open or shorted. An RF transmitter can report a zone tamper because its case was tampered. A
zone can be configured as a tamper zone. An off-normal tamper zone is a tamper condition. Different
hardware devices can report tamper, including keypads, zone expanders, and RF receivers.
Trouble: A service condition that needs to be corrected, such as a broken wire.
Verified Alarm: When the area is armed, the first alarm (an unverified alarm) sends its normal alarm report. The Verified Alarm
timer begins. If a second alarm occurs while the Verified Alarm Timer is running, the second alarm sends its
normal alarm report and then sends a Verified Alarm report. If a second alarm occurs after the Verified Alarm
Timer has expired, the second alarm starts the Verified Alarm Timer again and only sends its normal alarm
report. A third alarm would have to occur when the Verified Alarm Timer is running in order to send the
Verified Alarm report.
Visible Zone: A zone that displays at keypads during alarm or trouble conditions.
Zone: The control panel reports changing conditions on the sensor loops as Zone events. For example, when the
condition on On-board Sensor Loop 1 changes from Normal (supervised EOL resistor in place) to Shorted,
the control panel can be programmed to create an alarm event for Zone 1. That alarm event appears in
keypad displays as “Alarm, Zn 1.” If programmed for reporting, the control panel would send an “Alarm, Zn 1”
report to the ARC receiver in the programmed reporting format.
Zone Function: Use to construct “personality types” for zones used in the control panel. Each unique Zone Function
Configuration determines responses to specific conditions occurring on the zones.
Zone Type: Describes what the zone does. For example, Fire zone, Burglar zone, 24-hour zone, etc.

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | Index EN | 150

Index
A C
ABC Keys Call for Service Interval ............................................................. 23
Ack Beep Options................................................................. 72 Call for Service Text................................................................... 26
Alarm Output Option ............................................................ 72 Call for Service/System Inactive Options ............................. 24
Alarm Response .................................................................... 71 Call Forwarding Auto On/Off Digits....................................... 15
Area Options .......................................................................... 71 Cancel Event Enabled ............................................................... 26
Report Routing....................................................................... 73 Contact Set/Exit Delay Cancel Zone Options..................... 45
Reports .................................................................................... 72 Control Panel Events ...............................................................138
Text ........................................................................................... 74 D
AC Fail Report Delay................................................................. 34
AC Fail/Low Battery Report Options..................................... 22 Date Format and Enable PIN Trouble .................................... 33
AC Power Supervision Options.............................................. 21 Daylight Saving Clock Advance Time.................................... 34
Ack Wait Time............................................................................. 20 Daylight Saving Clock Reverse Time ..................................... 34
Alarm Event Abort Window ...................................................106 Daylight Saving Time Calendar ............................................... 33
Alarm Output Arming Beep Volume ....................................108 Disabling a Zone......................................................................... 87
Alarm Report Routing, Zone Function ## ..........................102 Door Access Control Module
Alarm Restoral Report Routing, Zone Function ## .........102 Global Options.....................................................................137
Answering Machine Bypass .................................................... 17 Location Assignment ..........................................................136
Area # Account Number .......................................................... 48 DS7446KP Keypad ................................................................... 67
Area # Opening/Closing Reporting Options....................... 49 DTMF/Pulse Dialing ................................................................... 15
Area Configuration Duress
Area # Account Number...................................................... 48 Report Routing....................................................................... 73
Area # Opening/Closing Reporting Options.................. 49 Reporting Options................................................................. 73
Area Idle Text.......................................................................... 51 DX2010 Configuration Options............................................127
Area Name Text ..................................................................... 50 DX4010 RS-232 Module Configuration
Lock Area # Reporting......................................................... 50 Parity, Flow Control, Stop Bit ...........................................126
Area Idle Text............................................................................... 51 DX4010i/DX4010
Area Name Text .......................................................................... 50 Baud Rate Options .............................................................125
Area Option, User # .................................................................. 66 Output Configuration Options..........................................125
Arming Options 1....................................................................... 37 RS-232 Module Configuration .........................................125
Arming Options 2....................................................................... 38 DX8010 Telephone Module Configuration
Authority Level Configuration Access Options ...................................................................126
Option 1 All On Arming ....................................................... 52 E
Option 10 System Functions 2 .......................................... 58 Enable Alarm Event Abort......................................................... 95
Option 11 Move to Area ...................................................... 59 Entry Delay Time 1 (2)............................................................... 41
Option 12 Extend Auto-On Time ....................................... 59 Exit Delay Time 1 (2).................................................................. 43
Option 13 System Functions 3 .......................................... 60 Exit Programming Mode...............................................................7
Option 14 Change PIN ........................................................ 60 Exit Terminator Zone Options.................................................. 45
Option 15 View Log ............................................................. 61 Exit Time Restart......................................................................... 40
Option 2 Perimeter Only Arming ....................................... 53 Expert Addresses ..........................................................................6
Option 3 Partial On Arming ................................................ 53 Expert Programming Mode..........................................................5
Option 4 Disarming the System......................................... 54
Option 5 One-Time Disarm................................................. 54 F
Option 6 Send Open/Close Reports ............................... 55 Factory Default..........................................................................128
Option 7 Force Arm/Bypass............................................... 56 Format for Destination 1 (2)........................................... 10, 131
Option 8 All Areas On/Off .................................................. 56
G
Option 9 System Functions 1............................................. 57
Authority Level, User #.............................................................. 65 Global Open/Close Options
Auto On Alert Time .................................................................... 26 Arming Options 1 .................................................................. 37
Automatic Test Report Options .............................................. 31 Arming Options 2 .................................................................. 38
Automatic Test Report Time .................................................... 31 Bypass/Force Arm Limit....................................................... 38
Contact Set/Exit Delay Cancel Zone Options ................ 45
B Entry Delay Time 1 (2) ............................................41, 42, 43
Basic Pager Display .................................................................. 12 Exit Delay Time 1 (2)............................................................. 43
Bell Time.....................................................................................108 Exit Terminator Zone Options ............................................. 45
Bypass/Force Arm Limit ........................................................... 38 Exit Time Restart .................................................................... 40
Bypass/Force Arm Report Routing......................................104 Open/Close Reporting Options......................................... 39
Bypass/Swinger Shunt/Trouble Report Options..............105 Opening/Closing Report Routing...................................... 40

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | Index EN | 151

Panel Arming Options .......................................................... 46 L


Perimeter Only Mode Delay Time ...................................... 42
Tamper Reset/Arming Options .......................................... 44 Local Programming Options .................................................... 36
Verified Alarm Timer.............................................................. 47 Location (Zone) Configuration
Global Output Configuration Disabling a Zone.................................................................... 87
Alarm Output Arming Beep Volume................................108 Location ##, Area ................................................................. 85
Bell Time................................................................................108 Location ##, Device ............................................................. 83
Global Output Options ......................................................107 Location ##, Zone Function ............................................... 84
Siren Warble Frequency....................................................108 Location ##, Zone Number................................................. 85
Global Output Options ...........................................................107 Location Text .......................................................................... 86
Global Reporting Options ........................................................ 19 Zone Doubling Programming.............................................. 82
AC Fail/Low Battery Report Options................................ 22 Lock Area # Reporting.............................................................. 50
AC Power Supervision Options......................................... 21 Log Supervision Configuration................................................ 25
Ack Wait Time........................................................................ 20 N
Auto On Alert Time ............................................................... 26 Network Communication
Call for Service Interval ........................................................ 23 Alternate Communication Options ..................................132
Call for Service Text.............................................................. 26 Alternate Communication Wait Time ..............................133
Call for Service/System Inactive Options ........................ 24 Altnerate Communication Heartbeat Period..................134
Cancel Event Enabled.......................................................... 26 Altnerate Communication Heartbeat Retries.................134
Global Reporting Options ................................................... 19 Format for Destination 1 (2) ..............................................131
Log Supervision Configuration........................................... 25 IP Address 1 (2) for Destination 1 (2) ............................129
System Alarm Reports/Output Options........................... 28 Network Interface Module Options .................................135
System Inactive Interval........................................................ 23 Port Number for IP Addresses .........................................130
System Status Report Routing........................................... 23 Port Number for Remote Programming Callback.........131
System Status Report Swinger Count ............................. 22 Remote Programming Callback Number........................130
Global Zone Configuration
Alarm Event Abort Window...............................................106 O
Bypass/Force Arm Report Routing .................................104 On-board Location EOL Resistor Value..............................103
Bypass/Swinger Shunt/Trouble Report Options .........105 Open/Close Reporting Options.............................................. 39
On-board Location EOL Resistor Value.........................103 Opening/Closing Report Routing........................................... 40
Swinger Count for Alarm Output.....................................104 Option Parameters
Swinger Count for Zone Reports ....................................105 Understanding the Charts ......................................................8
Zone Response Options ..................................99, 103, 142 Options 1, Zone Function ##
Zone Trouble/Restoral from Trouble Report Routing..106 24-Hour Control Input Zone Function Types .................. 97
Gobal Zone Configuration 24-Hour Tamper Input Zone Function Types .................. 98
Sensor Monitor Time ..........................................................105 Controlled Keyswitch Types ............................................... 98
Guard Code Options ................................................................ 74 Options for Zone Function Types 0-2, 5-8, 11-15......... 95
H Options 2, Zone Function ##.................................................. 99
Output Configuration
How to Program ............................................................................5 Area ........................................................................................111
I Function .................................................................................112
Installer PIN.................................................................................. 63 Mode ......................................................................................117
Installer Programming Mode.......................................................5 Multiplier ................................................................................118
Integral Voice Verification Module.......................................... 14 Steady, Pulse, and One-Shot Mode Configuration .....119
IP Address P
Alternate Communication Options ..................................132 Panel Arming Options ............................................................... 46
Entering a Routing Destination.........................................129 Panel Wide Parameters
Port Number .........................................................................130 Format for Destination 1 (2) ................................................ 10
K Phone Number 1 (2) for Destination 1 (2)..........................9
Keypad Programming...................................................................5 Routing Destinations................................................................9
Keypads Parameter Addresses
Keypad # Area Options ..............................................69, 136 Editing a Data Digit Entry........................................................6
Keypad # Options................................................................. 67 Fixing an Incorrect Entry..........................................................6
Keypad Response Options ................................................. 70 Overview of ................................................................................5
Scrolling through Addresses .................................................5
Viewing an Address .................................................................5

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | Index EN | 152

Parameter Chart Options Enable Strobe Arming Flash to Indicate RF Keyfob and
1 Second Bell Test on Closing Ack.................................. 49 Keyswitch Arm/Disarm ..................................................107
AC Tag-along ......................................................................... 21 Enable Supervision................................................................ 18
Acknowledgement Beep for ABC Keys........................... 72 Enable System Tamper Alarm Output .............................. 28
Alarm Event Abort ................................................................. 96 Enable Weekly Test Reminder ........................................... 24
Alarm Output .......................................................................... 99 Exit Error .................................................................................. 39
Alarm Output on Panic......................................................... 79 Exit Terminator Button .......................................................... 98
Alarm Reports Enabled ......................................................100 Extend Handshake ................................................................ 19
Alarm Reset Control Input................................................... 97 Extinguish Mode Displays Date.......................................... 70
Alarm Restoral Reports Enabled............................ 100, 101 Fire Alarm Response............................................................. 71
Allow Force Arming of Tampers/Troubles ....................... 44 First Area to Open/Last Area to Close Reporting.......... 38
Allow User Reset of Tampers/Troubles ........................... 44 Include IP Address ..............................................................135
Alternate Communication Path Fault Control Input ....... 97 Keyfobs Do Not Force Arm Faulted Zones....................123
Answering Machine Bypass When All On/Perim Only On Keypad Programming Enabled........................................... 36
.............................................................................................. 37 Maintained Keyswitch........................................................... 98
Any User Confirms Arming................................................137 Make Area 1 Common Area................................................ 38
Armed for Perimeter Only Mode ........................................ 96 Momentary Keyswitch........................................................... 98
Assign [O] Key to Perimeter Only ..................................... 79 No EOL Resistor Required.................................................. 97
Assign [P] Key to Partial On ............................................... 79 No Phone Line Supervision................................................. 18
Beep Keypad on System Trouble...................................... 67 Normally Open Sensor Contacts.....................................101
Belongs to RF Receiver 2 ................................................... 75 Open/Close Reports for Area # Enabled ........................ 49
Burg Alarm & Strobe Functions ......................................... 18 Open/Close Reports for Perimeter Only Mode.............. 49
Burg Alarm After Two Failed Attempts............................. 20 Opening Reports Enabled................................................... 39
Call for Service Display at Call for Service Interval ....... 24 Output 2 Is Supervised Horn/Speaker Output.............107
Call for Service Display at System Inactive Interval....... 24 Panel is Disarmed during Exit Delay.................................. 46
Call for Service Report at Call for Service Interval ........ 24 Panic Alarm Response ..................................................71, 76
Call RPS at Test Time .......................................................... 31 Panic Enabled ........................................................................ 79
Can Be Bypassed or Force Armed ................................... 99 Phone Line Fault Requires Reset....................................... 14
Closing Reports Enabled..................................................... 39 PK32 (Programming Key) Enabled.................................... 36
Cross-Zone ............................................................................. 99 R Function ............................................................................... 14
Defer Test Report if Other Report is Sent in Test Interval Recent Closing ...................................................................... 39
.............................................................................................. 31 Restrict Installer PIN ............................................................. 70
Delay Alarm Output............................................................... 19 Restrict Open/Close Reports............................................. 49
Disable AC Fail Local Annunication.................................. 21 RF Receiver 1 Connected .................................................123
Disable RF Loop Tamper...................................................123 RF Receiver 2 Connected .................................................123
Do Not Wait for Dial Tone................................................... 14 RF Receiver Supervised....................................................... 75
Duress Alarm Response ...................................................... 76 RS-232 Log Output using Internal Codes.....................125
Emergency Alarm Response........................................ 71, 76 RS-232 Log Output using PC Compatible Codes......125
Enable [Q] Button Ack Beep.............................................. 77 Send Output Set/Reset Reports .....................................107
Enable [Q] Button Alarm Output ....................................... 77 Send System Tamper Alarm Reports ............................... 28
Enable [Q] Button Voice Verification................................ 77 Send System Tamper Alarm Restoral Reports ............... 28
Enable ABC Keys Reporting .............................................. 72 Send Tamper Trouble Reports ........................................... 27
Enable AC Fail Trouble Tone............................................128 Send Tamper Trouble Restoral Reports........................... 27
Enable Alarm Output Arming Beep to Indicate RF Keyfob Send Test Report .................................................................. 29
and Keyswitch Arm/Disarm ..........................................107 Sensor Trouble Monitor........................................................ 96
Enable All Areas All On ([#][8][0]).................................... 38 Silence Outputs Control Input............................................ 97
Enable All Areas Off ([#][8][1]) ......................................... 38 Smart Swinger......................................................................103
Enable All On-No Exit ........................................................... 37 Start Exit Delay with Faulted Zones .................................. 46
Enable Alternate Communication ....................................135 Swinger Shunt........................................................................ 99
Enable Area Display.............................................................. 67 Tamper Alarm when Armed................................................. 27
Enable Arm/Disarm/Bypass Tracking ............................... 21 Tamper Alarm when Disarmed ........................................... 27
Enable Arming Confirmation .............................................137 Terminate Remote Programming Connection on Alarm35
Enable Bad Set Operation .................................................. 46 Test Battery............................................................................. 29
Enable Exit Tone .................................................................... 67 Test Bell............................................................................28, 29
Enable Extinguish Mode....................................................... 70 Test Report Only if System is Armed................................ 31
Enable Ground Fault Display and Trouble Tone ..........128 Test Reports for All Areas.................................................... 31
Enable Installer Mode Reports ........................................... 36 Test Strobe ............................................................................. 28
Enable Internal Crystal to Keep Time................................ 21 Trouble Response on Off-Normal....................................101
Enable Keypad Tamper Response .................................... 70 Trouble Response on Open..............................................100
Enable Remote Programming............................................. 35 Trouble Response on Short ..............................................100
Enable Remote Programming Callback ........................... 35 Unverified Events Send Trouble Reports .......................103
Enable Reporting................................................................... 19 Use Tamper-Wired Processing ........................................137

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | Index EN | 153

User Tamper Activates Burg Alarm Output..................... 62 Walk Test Start/End.............................................................. 31


User Tamper Reports Enabled........................................... 62 Zone Trouble ........................................................................106
Voice Active Control Input .................................................. 97 Zone Trouble Restoral ........................................................106
Voice Verification................................................................... 96 Reporting Enable, Trouble Response Options..................100
Perimeter Only Mode Delay Time........................................... 42 No EOL Resistor, Zone Doubling, or Tamper-wired
Personal Dialing Format............................................................ 10 Configuration ...................................................................101
Phone Line Options................................................................... 14 Single EOL Resistor Configuration .................................100
Phone Number 1 (2) for Destination 1 (2)...............................9 Reporting Format Configuration
Phone, Auto-Forward and RPS Configuration Basic Pager Display.............................................................. 12
Answering Machine Bypass................................................ 17 Personal Dialing Format ....................................................... 10
Phone Line Fault Response Options ................................ 18 SIA 300 with Text Blocks .................................................... 12
Phone Line Options .............................................................. 14 Reporting Formats....................................................................138
Remote Programming Call Back Number........................ 16 Reserved Addresses ....................................................................6
RPS Answer Ring Count..................................................... 17 RF Keyfobs
Phone, Auto-Forward, and RPS Configuration Receiver Assignment Options ............................................ 78
Call Forwarding Auto On/Off Digits.................................. 15 RF Keyfob Options................................................................ 79
DTMF/Pulse Dialing .............................................................. 15 RF Keypads
Integral Voice Verification Module ..................................... 14 RF Keypad # Area................................................................. 76
PIN Configuration/Installer PIN RF Keypad # Options........................................................... 75
Installer PIN............................................................................. 63 RF Receiver Configuration
PIN Length .............................................................................. 61 RF Jam Detect Level ...........................................................124
User Tamper Lockout Time ................................................. 62 RF Receiver Options ..........................................................123
User Tamper Options ........................................................... 62 RF Receiver Supervision Interval .....................................124
User Tamper Retry Count.................................................... 62 RF Transmitters and Zone States........................................... 87
PIN Length ................................................................................... 61 Routing Destinations ....................................................................9
PIN, User # .................................................................................. 65 RPS Answer Ring Count .......................................................... 17
Programming Chart Options S
Enable Alternate Communication ....................................132
Enable Anti-Replay..............................................................132 Scope of Document......................................................................4
Use ARC Acks .....................................................................132 Sensor Monitor Time ...............................................................105
Programming Options SIA 300 with Text Blocks ......................................................... 12
AC Fail Report Delay ............................................................ 34 Siren Warble Frequency.........................................................108
Date Format and Enable PIN Trouble ............................... 33 Sked Configuration
Daylight Saving Clock Advance Time............................... 34 Assign (Area or Output).....................................................121
Daylight Saving Clock Reverse Time ................................ 34 Days Option 1 ......................................................................122
Daylight Saving Time Calendar .......................................... 33 Days Option 2 ......................................................................122
Local Programming Options............................................... 36 Time ........................................................................................121
Remote Programming Options........................................... 35 Type ........................................................................................120
Three-way Calling.................................................................. 14 Swinger Count for Alarm Output..........................................104
Pulse Count................................................................................. 94 Swinger Count for Zone Reports .........................................105
Pulse Count Time....................................................................... 94 System Alarm Reports/Output Options ................................ 28
System Inactive Interval............................................................. 23
Q System Status Report Routing................................................ 23
Q Button Configuration System Status Report Swinger Count .................................. 22
Alarm Response Options .................................................... 76 System Test Configuration Options....................................... 28
Configuration Options.......................................................... 77 System Test Enable Options ................................................... 29
R System Trouble Options .........................................................128

Remote Programming Call Back Number ...................16, 130 T


Alternate Commuication Options ....................................133 Tamper Reset/Arming Options ............................................... 44
Remote Programming Callback Port Number ...................131 Test Report Routing................................................................... 32
Remote Programming Options ............................................... 35 Tests.............................................................................................. 28
Report Routing Automatic Test Report Options ......................................... 31
ABC Keys................................................................................ 73 Automatic Test Report Time ............................................... 31
Alarm ......................................................................................102 System Test Enable Options .............................................. 29
Alarm Restoral......................................................................102 Test Report Routing.............................................................. 32
Bypass ...................................................................................104 Walk Test Configuration Options ...................................... 30
Duress...................................................................................... 73 Walk Test Enable Options................................................... 30
Force Arm..............................................................................104 Walk Test Start/End Report Routing ................................ 31
Opening/Closing ................................................................... 40
System Status ........................................................................ 23
Tests......................................................................................... 32

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | Index EN | 154

U W
User Area Option ....................................................................... 66 Walk Test Configuration Options ........................................... 30
User Tamper Lockout Time...................................................... 62 Walk Test Enable Options ....................................................... 30
User Tamper Options................................................................ 62 Walk Test Start/End Report Routing ..................................... 31
User Tamper Retry Count ........................................................ 62 Z
Users
Area Option, User # ............................................................. 66 Zone Doubling Programming................................................... 82
Authority Level, User #......................................................... 65 Zone Function Configuration
PIN, User # ............................................................................. 65 Alarm Report Routing .........................................................102
Alarm Restoral Report Routing.........................................102
V Options 1................................................................................. 95
Verified Alarm Timer................................................................... 47 Options 2................................................................................. 99
Pulse Count ............................................................................ 94
Pulse Count Time .................................................................. 94
Reporting Enable, Trouble Response Options .............100
Zone Function Type, Zone Function ................................. 90
Zone Response Options........................................99, 103, 142
Zone Trouble/Restoral from Trouble Report Routing.......106
Zone Wiring Configuration....................................................... 89

Bosch Security Systems | 8/04 | 4998153891C


DS7200V2-EXP | Expert Programming Guide | Notes EN | 155

Notes

Bosch Security Systems | 8/04 | 4998153891C


Bosch Security Systems
www.boschsecurity.us

© 2004 Bosch Security Systems


4998153891C

You might also like