0% found this document useful (0 votes)
59 views

Automatic Power Factor Controller

The document provides specifications and operating instructions for an automatic power factor controller. It describes the device's features such as suitable voltage and current measurements, bank selection capabilities, and protection functions. It also details installation guidelines, a display overview, and fault finding procedures.

Uploaded by

ssaranlk797
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views

Automatic Power Factor Controller

The document provides specifications and operating instructions for an automatic power factor controller. It describes the device's features such as suitable voltage and current measurements, bank selection capabilities, and protection functions. It also details installation guidelines, a display overview, and fault finding procedures.

Uploaded by

ssaranlk797
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Features: Specifications:

OPERATION & INSTRUCTION


MANUAL Ø Suitable for Thyristor switched Capacitor panel. Ø Measurement Voltage (L-L): 415 Volt + 10 %.
Ø Input Measurement Current: 1A / 5 A.
v Read the manual carefully before the device is Ø Various possibilities for bank selection. Including user
installed. Ø Contact rating for output suitable for 1Amp, 440V
defined bank values in KVAR.
v Only qualified staff is allowed to perform the Ø Measurement accuracy: Class-1
installation.
Ø Input sensing line-to-line voltage. Ø Operating temperature: 0 to 55°C.
v Connect the relay as per the wiring diagram in
the manual. Ø Selectable current input range. 1Amp and 5Amp. (CT Ø Storage temperature: -10 to +75°C
v Before connecting the relay check the supply input) Ø Output commands models for 8,12 and 16
voltage. output.
v Please check whether the CT is connected at Automatic Power Factor Controller Ø Protection against Over/Under voltage, Over/Under Method for Keyboard/Display Editing:
the Main Incomer. Load etc
SPF relay keyboard has 7 keys,
v Connect the CT when the relay is in OFF ENT- key is at center and there are UP, DOWN - for scrolling the display
condition. Use suitable size cable for the CT. windows, MODE and SAVE-keys are placed at right and left side of
Ø Compensation on fundamental waveform, KVAR
DOWN key.
v Do not disturb the connection when the relay is calculation and also the effects of supply frequency and
ENT MODE-key is used to have access in different mode of relay operations
ON. and also used for editing data in the memory . For editing any
voltage.
v Please ensure the discharge time interval of parameter in the relay, press mode switch the Password window will be
MODE SAVE displayed, if password is enabled. (By default it is disabled). Enter
capacitor. SPF-08T Ø Output of relay contacts available up to 08 steps. password by using arrow keys then press ENT. Using UP & DOWN key,
v Disconnect the device if it does not work during select one of the following mode.
Ø EDIT PARAMETERS
commissioning. Ø AUTO OPERATION
Ø Standard 144 X 144 mm panel flush mounting
v Do not install the device if it is in damaged arrangement. Max depth 60mm. Recommended cutout Ø MANUAL OPERATION
condition. POWER FACTOR CONTROLLER for panel front door is 138x138 mm. Then press ENT switch to enter the specific mode. (During
commissioning edit the required parameters by setting in the EDIT
PARAMETER mode, then follow the AUTO or MANUAL mode selection).
TX - Transformer mode GX - Generator mode

Display: Fault Finding Guidelines:


The Display is LCD and the factory set (Default) condition Fault Type Probable Reason Action to Take
shows the PF, which is power factor, sensed from the load
sensing CT i.e. the Transformer/supply grid. The screen also Input supply not coming.
Unit Does not turn ON. LCD is q ü Check the input supply to restore
shows “ IND” for Inductive Power Factor & “ CAP” for blank with no Backlit. q Input side fuses blown ü Check fuses in the unit for OK.
Capacitive Power Factor. The last digit on the upper line of
display shows the operation mode i.e. 'A 'for auto mode and Unit not turning ON any capacitor This is perfectly OK if unit is powered
'M' for Manual mode. The bottom line of the LCD display As this is normal action, need not take any action.
banks, immediately after Power on. up, there is a delay of correction time
Refer wiring diagram in the back side of controller test certificate. shows capacitor bank status. Unit will start performing normally after the
that is provided in the unit only after stipulated time delay.
For enquiry contact : 09422031641 which units can turn on outputs.
Display in other Parameters:
With whatever capacitor banks ON, Check connection as per control Correct the wiring as per the scheme requirements
To observing other system related parameters Scroll up/down SPF does not indicate the PF as wiring diagram. Check that Load and the CT positioning.
keys. Following is the sequence of the parameters displayed improved. CT put is in correct phase
on LCD screen. Relay shows Capacitive PF while Phase Sequence of CT Check the KW in the Relay if it is negative
there is No Capacitive Load Interchange the CT polarity.
Display Overall Values: Displays the Overall values
(average) like voltage, current, Active Power, Reactive Power, Main Energy Meter PF reading & q CT position & rating ü Check the CT position & correct it as per given
Apparent power, Frequency. Relay PF reading is not matched q Excessive Distance between in Scheme 1 or 2.
Relay & Energy Meter ü CT wiring should be up to 10mtr.
Display Power: Displays the power related Parameters like
P.F., kW, kVA, and kVAr. Thyristor controlled by this q Wiring to the command wiring is ü Check the continuity for any open ckt.
unit is/are not turning ON/OFF open circuit ü Check the Common terminal of relay.
Display Step kVAr: Displays the values of kVAr output i.e. even if front LCD indication shows q Card control circuit fuses are
measured for every step. correct. ü Replace the fuses in control circuit.
blown Relays in SPF module faulty
ü If above all is in OK condition replace the
Display Auxiliary Functions: SPF relay new one.
Displays the unit ID,utilization counter and. internal temperature
Lots of faults that are seen as faults are due to wrong parameter setting. It is recommend going through the details on
Display Harmonics : Parameter setting explanation part of this manual and setting them correctly.
Displays voltage and current harmonics
Easy programming to start the relay SPF-08T CUT CT PRIMARY MAINS:1 0 00
Easy programming to start the relay SPF-04/08/12/16
SWITCH ON SUPPLY
DISPLAY SHOW
ENT
START 4 TIMES
P.F = 0.976 IND A OK DISPLAY SHOWS

CONNECT 415 V AC SUPPLY PF Up Lim : Mains P.F = 0.976 IND A OK


L1 L2 CAP : 0 : 0.99 0
L2 - Y Phase Input MODE CUT CT PRIMARY MAINS:1 4 00
L1 - R phase Input
MODE
SELECT ENT
EDIT PARAMETER
CONNECT THE CT TERMINAL
SELECT
S1 S1 S2 PF Up Lim : Mains EDIT PARAMETER
S2-S1 (1A) : B phase C.T. For 1A Secondary CAP : 0 : 0.99 9
5A 1A COM S2-S1 (5A) : B Phase C.T. For 5 A Secondary

ENT
PF UP Lim : Mains ENT
[IND : 1] : 0.990
CONNECT THE OUT PUT TERMINALS
TO FIRING CARD
YES STEP CONNECTED : 08
EXT -PT RATIO : 0001.0 IS TO
COM C1 C2 C3 C4 C5 C6 C7 C8
CHANGE UP ENT
LIMIT ? PF LOW Lim : Mains
[IND :1] : 0.970 YES
PF Up Lim : MaIns IS TO CHANGE
NO : 0.990 STEPS ?
NC : NO CONNECTION IND : 1 ENT
CUR CT PRIMARY MAINS :1000
NO
GEN SUPPLY
PF LOW Lim : Mains
P N YES
[IND :1] : 0.970
ENT PF Up Lim : MaIns
IS TO CHANGE CT : 0.990
PRIMARY ? CAP : O
SAVE
NO CUR CT PRIMARY MAINS :100 0 ENT
DISPLAY SHOWS
2 TIMES
P.F = 0.976 IND A OK
________________
1 2 3 4 5

STEP CONNECTED : 0 8 CORRECTED TIME SEC : 0002 0

IS TO YES ENT
CHANGE
TYPE ?
Unequal bank (1) KVAR : 1 5
ENT CORRECTION TYPE
STEP CONNECTED : 0 7 CORRECTED TIME SEC : 000 2 0 Unequal : 0 1

ENT
ENT
Unequal bank (1) KVAR : 0 5
FIXED -BANK SETTING
CORRECTED TIME SEC: 000 1 0
ENT

ENT
DEFAULT MODE AUTO : 0

EXT FIXED KWAR :25 Unequal bank (2) KVAR :0015


DISCHARGE TIME SEC : 00070
COMPENSATION KVAR MEAN :1
IS TO YES ENT Unequal BANK [1] KVAR :10
CHANGE
TIME ?
IS TO Unequal bank (2) KVAR :0025
DISCHARGE TIME SEC : 0007 0 YES ENT
CAP BANK VOLTAGE ( L-L) : 440V CHANGE
BANK KVAR?

Unequal bank (1) KVAR : 1 0 SAVE

CORRECTION TIME SEC : 00020 DISCHARGE TIME SEC : 000 7 0 DISPLAY SHOWS

P.F = 0.976 IND A OK


IS TO YES
ENT Unequal bank (1) KVAR : 1 5
CHANGE
TIME ? Now the initial settings
DISCHARGE TIME SEC : 000 6 0 of relay is completed
6 7 8 9 10
Features: Specifications:
OPERATION & INSTRUCTION
Ø Suitable for Thyristor switched Capacitor panel. Ø Measurement Voltage (L-L): 415 Volt + 10 %.
MANUAL
Ø Input Measurement Current: 1A / 5 A.
v Read the manual carefully before the device is Ø Various possibilities for bank selection. Including user
installed. Ø Contact rating for output suitable for 1Amp, 440V
defined bank values in KVAR.
v Only qualified staff is allowed to perform the Ø Measurement accuracy: Class-1
installation.
Ø Input sensing line-to-line voltage. Ø Operating temperature: 0 to 55°C.
v Connect the relay as per the wiring diagram in
the manual. Ø Selectable current input range. 1Amp and 5Amp. (CT Ø Storage temperature: -10 to +75°C
v Before connecting the relay check the supply input) Ø Output commands models for 8,12 and 16
voltage. output.
v Please check whether the CT is connected at Automatic Power Factor Controller Ø Protection against Over/Under voltage, Over/Under Method for Keyboard/Display Editing:
the Main Incomer. Load etc
SPF relay keyboard has 7 keys,
v Connect the CT when the relay is in OFF ENT- key is at center and there are UP, DOWN - for scrolling the display
condition. Use suitable size cable for the CT. windows, MODE and SAVE-keys are placed at right and left side of
Ø Compensation on fundamental waveform, KVAR
DOWN key.
v Do not disturb the connection when the relay is calculation and also the effects of supply frequency and
ENT MODE-key is used to have access in different mode of relay operations
ON. and also used for editing data in the memory. For editing any
voltage.
v Please ensure the discharge time interval of parameter in the relay, press mode switch the Password window will be
MODE SAVE displayed, if password is enabled. (By default it is disabled). Enter
capacitor. password by using arrow keys then press ENT. Using UP & DOWN key,
SPF-16T Ø Output of relay contacts available up to 04 steps.
v Disconnect the device if it does not work during select one of the following mode.
Ø EDIT PARAMETERS
commissioning. Ø AUTO OPERATION
Ø Standard 144 X 144 mm panel flush mounting
v Do not install the device if it is in damaged arrangement. Max depth 60mm. Recommended cutout Ø MANUAL OPERATION
condition. POWER FACTOR CONTROLLER for panel front door is 138x138 mm. Then press ENT switch to enter the specific mode. (During
commissioning edit the required parameters by setting in the EDIT
TX - Transformer mode PARAMETER mode, then follow the AUTO or MANUAL mode selection).
GX - Generator mode

Control Wiring Diagram: Display: Fault Finding Guidelines:


The Display is LCD and the factory set (Default) condition Fault Type Probable Reason Action to Take
shows the PF, which is power factor, sensed from the load
sensing CT i.e. the Transformer/supply grid. The screen also Input supply not coming.
Unit Does not turn ON. LCD is q ü Check the input supply to restore
shows “ IND” for Inductive Power Factor & “ CAP” for blank with no Backlit. q Input side fuses blown ü Check fuses in the unit for OK.
Capacitive Power Factor. The last digit on the upper line of
display shows the operation mode i.e. 'A 'for auto mode and Unit not turning ON any capacitor This is perfectly OK if unit is powered
'M' for Manual mode. The bottom line of the LCD display As this is normal action, need not take any action.
banks, immediately after Power on. up, there is a delay of correction time
shows capacitor bank status. Unit will start performing normally after the
that is provided in the unit only after stipulated time delay.
Refer wiring diagram in the back side of controller test certificate. which units can turn on outputs.
Display in other Parameters:
For enquiry contact : 09422031641 With whatever capacitor banks ON, Check connection as per control Correct the wiring as per the scheme requirements
To observing other system related parameters Scroll up/down SPF does not indicate the PF as wiring diagram. Check that Load and the CT positioning.
keys. Following is the sequence of the parameters displayed improved. CT put is in correct phase
on LCD screen. Relay shows Capacitive PF while Phase Sequence of CT Check the KW in the Relay if it is negative
there is No Capacitive Load Interchange the CT polarity.
Display Overall Values: Displays the Overall values
(average) like voltage, current, Active Power, Reactive Power, Main Energy Meter PF reading & q CT position & rating ü Check the CT position & correct it as per given
Apparent power, Frequency. Relay PF reading is not matched q Excessive Distance between in Scheme 1 or 2.
Relay & Energy Meter ü CT wiring should be up to 10mtr.
Display Power: Displays the power related Parameters like
P.F., kW, kVA, and kVAr. Thyristor controlled by this q Wiring to the command wiring is ü Check the continuity for any open ckt.
unit is/are not turning ON/OFF open circuit ü Check the Common terminal of relay.
Display Step kVAr: Displays the values of kVAr output i.e. even if front LCD indication shows q Card control circuit fuses are
measured for every step. correct. ü Replace the fuses in control circuit.
blown Relays in SPF module faulty
ü If above all is in OK condition replace the
Display Auxiliary Functions: SPF relay new one.
.
Displays the unit ID,utilization counter and .internal temperature
Lots of faults that are seen as faults are due to wrong parameter setting. It is recommend going through the details on
Display Harmonics : Parameter setting explanation part of this manual and setting them correctly.
Displays voltage and current harmonics
CUT CT PRIMARY MAINS:1 0 00
Easy programming to start the relay SPF-16T
Easy programming to start the relay SPF-04/08/12/16
SWITCH ON SUPPLY
DISPLAY SHOW
ENT
4 TIMES
START P.F = 0.976 IND A OK DISPLAY SHOWS

PF Up Lim : Mains P.F = 0.976 IND A OK


CONNECT 415 V AC SUPPLY CAP : 0 : 0.99 0
MODE CUT CT PRIMARY MAINS:1 4 00
L1 L2
L2 - Y Phase Input
L1 - R phase Input MODE
SELECT ENT
EDIT PARAMETER
CONNECT THE CT TERMINAL SELECT
PF Up Lim : Mains EDIT PARAMETER
S1 S1 S2 CAP : 0 : 0.99 9
S2-S1 (1A) : B phase C.T. For 1A Secondary
5A 1A COM S2-S1 (5A) : B Phase C.T. For 5 A Secondary
ENT
PF UP Lim : Mains ENT
[IND : 1] : 0.990
CONNECT THE OUT PUT TERMINALS
TO FIRING CARD STEP CONNECTED : 04
YES
EXT -PT RATIO : 0001.0 IS TO
COM C1 C2 C3 C4 C5 C6 C7 C8 C151 C16
CHANGE UP ENT
LIMIT ? YES
PF LOW Lim : Mains IS TO CHANGE
[IND :1] : 0.970 STEPS ?
PF Up Lim : MaIns
NC : NO CONNECTION NO : 0.990
IND : 1 ENT
NO
CUR CT PRIMARY MAINS :1000
GEN SUPPLY
P N PF LOW Lim : Mains
YES
PF Up Lim : MaIns [IND :1] : 0.970
IS TO CHANGE CT ENT
CAP : O : 0.990
PRIMARY ?
SAVE
NO CUR CT PRIMARY MAINS :100 0 ENT
DISPLAY SHOWS
2 TIMES
P.F = 0.976 IND A OK
________________
1 2 3 4 5

STEP CONNECTED : 0 4 8 CORRECTED TIME SEC : 0002 0

IS TO YES ENT
CHANGE
TYPE ?
Unequal bank (1) KVAR : 1 5
ENT CORRECTION TYPE
STEP CONNECTED : 0 37 CORRECTED TIME SEC : 000 2 0 Unequal : 0 1

ENT
ENT
Unequal bank (1) KVAR : 0 5

CORRECTED TIME SEC: 000 1 0


ENT

ENT
FIXED -BANK SETTING
DEFAULT MODE AUTO : 0

Unequal bank (2) KVAR :0015


DISCHARGE TIME SEC : 00070
COMPENSATION KVAR MEAN :1
IS TO YES ENT Unequal BANK [1] KVAR :10
EXT FIXED KWAR :25
CHANGE
TIME ?
IS TO Unequal bank (2) KVAR :0025
DISCHARGE TIME SEC : 0007 0 YES ENT
CAP BANK VOLTAGE ( L-L) : 440V CHANGE
BANK KVAR?

Unequal bank (1) KVAR : 1 0 SAVE

CORRECTION TIME SEC : 00020 DISCHARGE TIME SEC : 000 7 0 DISPLAY SHOWS
P.F = 0.976 IND A OK
IS TO YES
ENT Unequal bank (1) KVAR : 1 5
CHANGE
TIME ? Now the initial settings
DISCHARGE TIME SEC : 000 6 0 of relay is completed
6 7 8 9 10
Features: Specifications:
OPERATION & INSTRUCTION
MANUAL Ø Suitable for Thyristor switched Capacitor panel. Ø Measurement Voltage (L-L): 415 Volt + 10 %.
Ø Input Measurement Current: 1A / 5 A.
v Read the manual carefully before the device is Ø Various possibilities for bank selection. Including user
installed. Ø Contact rating for output suitable for 1Amp, 440V
defined bank values in KVAR.
v Only qualified staff is allowed to perform the Ø Measurement accuracy: Class-1
installation.
Ø Input sensing line-to-line voltage. Ø Operating temperature: 0 to 55°C.
v Connect the relay as per the wiring diagram in
the manual. Ø Selectable current input range. 1Amp and 5Amp. (CT Ø Storage temperature: -10 to +75°C
v Before connecting the relay check the supply input) Ø Output commands models for 8,12 and 16
voltage. output.
v Please check whether the CT is connected at Automatic Power Factor Controller Ø Protection against Over/Under voltage, Over/Under Method for Keyboard/Display Editing:
the Main Incomer. Load etc
SPF relay keyboard has 7 keys,
v Connect the CT when the relay is in OFF ENT- key is at center and there are UP, DOWN - for scrolling the display
condition. Use suitable size cable for the CT. windows, MODE and SAVE-keys are placed at right and left side of
Ø Compensation on fundamental waveform, KVAR
DOWN key.
v Do not disturb the connection when the relay is calculation and also the effects of supply frequency and
ENT MODE-key is used to have access in different mode of relay operations
ON. and also used for editing data in the memory. For editing any
voltage.
v Please ensure the discharge time interval of parameter in the relay, press mode switch the Password window will be
MODE SAVE displayed, if password is enabled. (By default it is disabled). Enter
capacitor. SPF-12T password by using arrow keys then press ENT. Using UP & DOWN key,
Ø Output of relay contacts available up to 12 steps.
v Disconnect the device if it does not work during select one of the following mode.
Ø EDIT PARAMETERS
commissioning. Ø AUTO OPERATION
Ø Standard 144 X 144 mm panel flush mounting
v Do not install the device if it is in damaged arrangement. Max depth 60mm. Recommended cutout Ø MANUAL OPERATION
condition. POWER FACTOR CONTROLLER for panel front door is 138x138 mm. Then press ENT switch to enter the specific mode. (During
commissioning edit the required parameters by setting in the EDIT
TX - Transformer mode PARAMETER mode, then follow the AUTO or MANUAL mode selection).
GX - Generator mode

Display: Fault Finding Guidelines:


The Display is LCD and the factory set (Default) condition Fault Type Probable Reason Action to Take
shows the PF, which is power factor, sensed from the load
sensing CT i.e. the Transformer/supply grid. The screen also Input supply not coming.
Unit Does not turn ON. LCD is q ü Check the input supply to restore
shows “ IND” for Inductive Power Factor & “ CAP” for blank with no Backlit. q Input side fuses blown ü Check fuses in the unit for OK.
Capacitive Power Factor. The last digit on the upper line of
display shows the operation mode i.e. 'A 'for auto mode and Unit not turning ON any capacitor This is perfectly OK if unit is powered
'M' for Manual mode. The bottom line of the LCD display As this is normal action, need not take any action.
banks, immediately after Power on. up, there is a delay of correction time
shows capacitor bank status. Unit will start performing normally after the
that is provided in the unit only after stipulated time delay.
which units can turn on outputs.
Refer wiring diagram in the back side of controller test certificate. Display in other Parameters:
With whatever capacitor banks ON, Check connection as per control Correct the wiring as per the scheme requirements
For enquiry contact : 09422031641 To observing other system related parameters Scroll up/down SPF does not indicate the PF as wiring diagram. Check that Load and the CT positioning.
keys. Following is the sequence of the parameters displayed improved. CT put is in correct phase
on LCD screen. Relay shows Capacitive PF while Phase Sequence of CT Check the KW in the Relay if it is negative
there is No Capacitive Load Interchange the CT polarity.
Display Overall Values: Displays the Overall values
(average) like voltage, current, Active Power, Reactive Power, Main Energy Meter PF reading & q CT position & rating ü Check the CT position & correct it as per given
Apparent power, Frequency. Relay PF reading is not matched q Excessive Distance between in Scheme 1 or 2.
Relay & Energy Meter ü CT wiring should be up to 10mtr.
Display Power: Displays the power related Parameters like
P.F., kW, kVA, and kVAr. Thyristor controlled by this q Wiring to the command wiring is ü Check the continuity for any open ckt.
unit is/are not turning ON/OFF open circuit ü Check the Common terminal of relay.
Display Step kVAr: Displays the values of kVAr output i.e. even if front LCD indication shows q Card control circuit fuses are
measured for every step. correct. ü Replace the fuses in control circuit.
blown Relays in SPF module faulty
ü If above all is in OK condition replace the
Display Auxiliary Functions : SPF relay new one.
Displays the unit ID,utilization counter and. internal temperature Lots of faults that are seen as faults are due to wrong parameter setting. It is recommend going through the details on
Display Harmonics : . Parameter setting explanation part of this manual and setting them correctly.
.
Displays voltage and current harmonics
CUT CT PRIMARY MAINS:1 0 00
Easy programming to start the relay SPF-12T
SWITCH ON SUPPLY
DISPLAY SHOW
ENT
START P.F = 0.976 IND A OK 4 TIMES DISPLAY SHOWS

CONNECT 415 V AC SUPPLY PF Up Lim : Mains P.F = 0.976 IND A OK


L1 L2 CAP : 0 : 0.99 0
L2 - Y Phase Input MODE CUT CT PRIMARY MAINS:1 4 00
L1 - R phase Input
MODE
SELECT ENT
CONNECT THE CT TERMINAL EDIT PARAMETER
SELECT
S1 S1 S2 PF Up Lim : Mains EDIT PARAMETER
S2-S1 (1A) : B phase C.T. For 1A Secondary
5A 1A COM S2-S1 (5A) : B Phase C.T. For 5 A Secondary CAP : 0 : 0.99 9

ENT
PF UP Lim : Mains ENT
CONNECT THE OUT PUT TERMINALS [IND : 1] : 0.990
TO FIRING CARD
COM C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 YES STEP CONNECTED : 08
EXT -PT RATIO : 0001.0 IS TO
CHANGE UP ENT
LIMIT ? PF LOW Lim : Mains
[IND :1] : 0.970 YES
NC : NO CONNECTION PF Up Lim : MaIns IS TO CHANGE
NO : 0.990 STEPS ?
IND : 1
GEN SUPPLY ENT
CUR CT PRIMARY MAINS :1000
NO
P N
PF LOW Lim : Mains
YES
PF Up Lim : MaIns [IND :1] : 0.970
IS TO CHANGE CT ENT
CAP : O : 0.990
PRIMARY ?
SAVE
NO CUR CT PRIMARY MAINS :100 0 ENT
DISPLAY SHOWS
2 TIMES
P.F = 0.976 IND A OK
________________
1 2 3 4 5

STEP CONNECTED : 0 8 CORRECTED TIME SEC : 0002 0

IS TO YES ENT
CHANGE
TYPE ?
Unequal bank (1) KVAR : 1 5
ENT CORRECTION TYPE
STEP CONNECTED : 0 7 CORRECTED TIME SEC : 000 2 0 Unequal : 0 1

ENT
ENT
Unequal bank (1) KVAR : 0 5

CORRECTED TIME SEC: 000 1 0


ENT

ENT FIXED -BANK SETTING


DEFAULT MODE AUTO : 0

Unequal bank (2) KVAR :0015


DISCHARGE TIME SEC : 00070
COMPENSATION KVAR MEAN :1
IS TO YES EXT FIXED KWAR :25 Unequal BANK [1] KVAR :10
ENT
CHANGE
TIME ?
IS TO Unequal bank (2) KVAR :0025
DISCHARGE TIME SEC : 0007 0 YES ENT
CAP BANK VOLTAGE ( L-L) : 440V CHANGE
BANK KVAR?

Unequal bank (1) KVAR : 1 0 SAVE

CORRECTION TIME SEC : 00020 DISCHARGE TIME SEC : 000 7 0 DISPLAY SHOWS
P.F = 0.976 IND A OK
IS TO YES
ENT Unequal bank (1) KVAR : 1 5
CHANGE
TIME ? Now the initial settings
DISCHARGE TIME SEC : 000 6 0 of relay is completed
6 7 8 9 10