CHAPTER 1

ANALYSIS AND DESIGN OF CONCRETE ROOF ON THE STRUCTURE

Or CONCRETE SLAB

INTRODUCTION

Concrete slab is a flat piece of concrete, supported by the walls, beams or columns of a structure. It serves
as a walking surface. In addition to that it serves as a load bearing member, as in slab homes. It is a very
common and important structural element, is constructed to provide flat, useful surfaces. It is a horizontal
structural component, with top and bottom surfaces parallel or near so.

In reinforced concrete construction, slabs are used to provide flat surfaces. The span in the larger direction
is denoted by Ly and that in the shorter direction by Lx. slabs may be supported on two opposite sides
only in which case the structural action of the slab may be in one way i.e. the load carrying by the slab in
the direction normal to the supporting beams and is used when the moment in the long axis is negligible.
Also, when the ratio of Ly/Lx is more than two, it can be defined as one-way slab. Slabs which are
supported on unyielding supports like walls and stiff beams on all four sides and if the ratio of Ly/Lx is
less than or equal to two, then the action of slabs may be in two-way. The boundaries of a two-way slab
can be simply supported or restrained at the edges. Slabs resting on walls are considered as simply
supported slabs, wherein edges are free to rotate. Slab constructed monolithically with beams have some
restrained against rotation. These slabs may be continuous or discontinuous. Slab design is predominantly
done for bending (or flexure) behavior.

HOW TO ANALASIS and DESIGN CONCRETE ROOF

The analysis parts include three main load analysis.

which are namely;

 Wind load analysis


 Dead load analysis and
 Live load analysis
A. WIND LOAD ANALYSIS

Wind: Wind is a moving air which in turn possesses energy and this kinetic energy should be
resisted by using appropriate deign for different kinds of structural elements like roofs, walls the
action of wind can be a type of suction or pressure to our structures both externally or internally.
However, these effects are more magnified for structure with more openings and large surface
areas. And we focus on sensitive part of the building that is flat roof for analysis and design of its
parts.

Wind as a moving air has an effect on building structures. Wind actions fluctuate with time,
hence its effect on different situations and structures should be carefully analyzed.
Wind acts directly on the external surfaces of enclosed structures, through porosity of the
External surface, internal surface through opening. Wind pressure act on areas of the surfaces
producing forces perpendicular to the surface of the structure or on individual cladding or
covering components.

The effect of wind on structures is significant on light and dynamic structures. It does have
considerable effect on vertically standing walls, columns and beams etc. Therefore; its effect can
be easily studied on roof structures such as truss structures and flat slabs. Therefore, our analysis
on wind load actions and its design will focus on roofs analysis and design and calculation of
wind forces on flat roofs.

Structures deflect or stop the wind pressure converting the winds kinetic energy in to potential
energy of pressure creating load.

METHOD OF ANALYSIS

There are two methods for wind load analysis; namely,

1. The quasi-static method

2. Detailed dynamic analysis.

The former analysis is applied to structures whose structural properties do not make them
susceptible to dynamic exaltation.

The latter analysis is applied to structures which are likely to be susceptible to dynamic
exaltation. The choice of the above two methods depends on the value of the structure and of
their dynamic coefficient. The dynamic coefficient depends on the type of structure (concrete,
steel, composite), the height of the structure and its breadth.

The quasi-static method is more preferred for use in structures whose Cd value is less or equal to
1.2 (Section of ECS-145). For our case the building variables are: Height of building =28m and
Width of building is =18.39m. The value of the dynamic coefficient of this building is: Cd
0.9375 that is Cd

There are two types of loads (wind pressure) acting on the roof;

A) External wind pressure (we)

B) Internal wind pressure (wi)

A. External wind pressure (We)

The external We= wind pressure that acts on the roof is obtained using the following formula

we= qref*ce(ze)*Cpe
Where, We = external wind pressure

qref = reference mean wind pressure

Cpe = external wind pressure coefficient

Information about the building Location

 Location- Adiss Ababa, Ethiopia


 Type B+G+8 multipurpose building
 Altitude of Adiss Ababa – 2355m
 Altitude = altitude of location + height of building
= 2355 + 28
= 2383 m

According to EBCS
Table:
Site altitude 0 500 1000 1500 200

ρ (Kg/m3) 1.2 1.12 1.06 1 0.94

For the altitude which ≥2000m, take ρ= 0.94

Basic wind velocity(vb)

from CES-145 section 4.5 (4.10)

Reference wind pressure (q ref) = ½  vb 2 Where: ρ= air density in Kg/m3 and is dependent on
altitude;

Reference wind velocity, vb = 22m/s

q ref = ½  vb 2

= ½ *0.94*222

=0.227kpa
Exposure coefficient (ce(ze))

Urban areas in which at least 15 % of the surface is covered with buildings and their average
height exceeds 15m

Height of the building = 28

Terrain category - zone 4 (IV)

Figure: illustrations of exposure factor ce(ze)

Figure terrain category

From the above graph

(ce(ze)) = 1.9
Height of roof=0m

Height of building=27m

length of building 2nd – roof level =b=23.77m

width of building = d = 18.4m

Reference height=Ze= h + hp =27+1= 28m

e=mi n ( b ,2 h )

e=min ( 23.77 m , 2∗28 m=5 m 6 )=23.77 m

From e we get the dimensions of the areas according to EN 1991-1-4:2005 Figure 7.6

Table:

Zone Width (m) Depth (m) Area, A(m2) specification

F e/4 = 5.943 e/10 = 2.377 14.127 A>10m2

G b-e/2 = 11.685 e/10 = 2.377 27.775 A>10m2

H b = 23.77 e/2 – e/10 = 9.506 225.958 A>10m2

I b = 23.77 d-e/2 = 9.87m 233.919 A>10m2

H I
wind direction G

Now, the external pressure coefficient also depends on the roof type. The following roof types
are included: Sharp eaves, With parapets, curved eaves and, Mansard eaves
For the roof type of parapet with the parapet height hp

hp=100cm, hp/h=1/28=0.036 it is between 0.025 and 0.05, by interpolation

zone F G H I

Area cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1

hp/h = 0.025 -1.6 -2.2 -1.1 -1.8 -0.7 -1.2 +0.2, -0.2

hp/h = 0.036 -1.52 -1.012 -0.7 +0.2, -0.2

hp/h = 0.05 -1.4 -2 -0.9 -1.6 -0.7 -1.2 +0.2, -0.2

All area of zone is >10m2, so we take A(cpe,10) for all zone.

External Wind Load

Zone external pressure External wind load (KN/m2)


coefficient
We(ze)= qref*ce(ze)*Cpe=0.227*1.9* Cpe

Area F -1.52 -0.656

Area -1.012 -0.436


G

Area -0.7 -0.302


H

Area I -/+ 0.2 -/+ 0.086


B) Internal wind pressure (wi)

internal wind pressure that acts on the roof is obtained using the following formula

Wi(ze)= qref *ce(ze)*Cpi

Wi = internal wind pressure, qref = reference mean wind pressure, Cpi = internal pressure
coefficients

Area of Openings

Opening Length, height, m Area, m2 summatio µ h/d


m n

Wind parallel 1.6 1.2 1.92 4.52 0.497 1.522


side
1.6 0.7 1.12

1.6 0.7 1.12


Right side view
0.6 0.6 0.36

Left side view 1.6 1.2 1.92 7.24

0.6 0.6 0.36

1.6 1.2 1.92

1.6 0.7 1.12

1.6 1.2 1.92

Wind ward 1.6 2.5 4 19.36

2.84 2 5.68

2.84 2 5.68

1.6 2. 5 4

2.5 1.6 4 7.84

1.2 1.6 1.92

1.2 1. 1.92
Leeward

summation of openingarea where negative Cpe


µ=
summation of all opening area

Figure: Cpi for uniformity distributed opening

From the chart Cpi = 0.12

wi (ze)= qref *ce(ze)*Cpi

= 0.227*1.9*0.12

=0.052

Net wind pressure on the Roof (Wnet= We(ze)-Wi (ze))

Zone We(ze), KN/m2 Wi (ze), KN/m2 Wnet, KN/m2

F -0.656 0.052 -0.708

G -0.436 0.052 -0.488

H -0.302 0.052 -0.354

I -/+ 0.086 0.052 -0.138 / -0.034


The maximum wind load on the roof is -0.708 KN/m2, it implies that the wind load on the roof is suction.

B. DEAD LOAD ANALYSIS on CONCRETE ROOF

Material Data

 C-25, S-400, Class-I work


 Thickness of plastering on two side =30mm
 Unit weight of plastering =23kN/m3
 Unit weight of concrete=25kN/m3

Figure: roof layout


Depth determination

According to ES EN 1992 -1-1:2015 page 126, [7.16a] the depth for deflection can calculated
by:

Table 7.4N: Basic ratios of 𝑠𝑝𝑎𝑛/𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ for reinforced concrete members without axial
compression (Source: ES EN 1992 Part 1.1:2015 section 7.4.2)
Thickness of the slabs given in the architectural drawing should be checked weather it is
adequate for deflection. Material used

 C-25
 S-400
Assumption: - Slab is lightly reinforced (𝜌=0.5 %) QO= √𝑓𝑐𝑘 ∗ 10 − 3 = 5 ∗ 10 − 3

Simply we can calculate depth of slab by the following formula

L/d=26…..................... for end span (from ES-EN 1992; 2015 table7.4 page 128)

L/d =30…................... for interior span or all side fixed support

L/d=8…....................... for cantilever, C25/30, S400 Concrete cover (ES EN:1990 :2014)

D = d + cover+ Ø /2 Where cover is given by:

 cover =Cnom = Cmin+ΔCdev


 Cmin = max of (Cmin, b, Cmin, dur + ΔCdur – ΔCdur, st - ΔCdur, add, 10mm)
 Cmin = max of (10, 10+ 0 – 0-0, 10mm)
 Cmin = 10
 Cnom = 10+10 = 20mm

We take Ø=10mm for slab reinforcement and concrete cover of 20mm d’=20+10/2 = 25mm
500/fyk=500/400=1.25

d=Lx/(l/d*500/fyk)
D=d+d’ whereas d’=25mm

l
N.B we used S-400, the value of must multiple by 500/fyk=500/400= 1.25
d
panels position K Lx(m) Ly(m) Slab type l/d l/d*500/fyk d(mm) D(mm)

P-1 end span 1.3 1.05 2.5 One -way 24.05 30.06 34.93 59.93

P-2 end span 1.3 2.5 3.78 two -way 24.05 30.06 83.167 108.17

P-3 end span 1.3 2.5 4.08 two -way 24.05 30.06 83.167 108.17

P-4 end span 1.3 2.5 4.1 two -way 24.05 30.06 83.167 108.17

P-5 end span 1.3 2.5 5 two -way 24.05 30.06 83.167 108.17

P-6 end span 1.3 1.05 5.22 One-way 24.05 30.06 34.93 59.93

P-7 Interior span 1.5 3.78 5.22 two -way 27.75 35 108 133

P-8 Interior span 1.5 4.08 5.22 two -way 27.75 35 116.57 141.57

P-9 Interior span 1.5 4.1 5.22 two -way 27.75 35 117.14 142.14

P-10 end span 1.3 5 5.22 two -way 24.05 30.06 166.33 191.33

P-11 end span 1.3 3.78 3.79 two -way 24.05 30.06 125.75 150.75

P-12 Interior span 1.5 3.79 4.08 two -way 27.75 35 108.29 133.29

P-13 Interior span 1.5 3.78 4.1 two -way 27.75 35 108 133

P-14 end span 1.3 3.79 4.1 two -way 24.05 30.06 126.08 151.08

P-15 end span 1.3 3.22 3.78 two -way 24.05 30.06 107.12 132.12

P-16 Interior slab 1.5 3.22 4.08 two -way 27.75 35 92 117

P-17 interior 1.5 3.22 4.1 two -way 27.75 35 92 117

P-18 end span 1.3 2.09 3.85 two -way 24.05 30.06 69.528 94.528

P-19 end span 1.3 3.78 5.71 two -way 24.05 30.06 125.75 150.75

P-20 interior 1.5 4.08 5.71 two -way 27.75 35 116.57 141.57

P-21 end span 1.3 4.1 5.71 two -way 24.05 30.06 136.39 161.39

P-22 end span 1.3 2.62 3.78 two -way 24.05 30.06 87.159 112.16

P-23 end span 1.3 2.62 4.08 two -way 24.05 30.06 87.159 112.16

P-24 cantilever 0.4 1.4 3.79 One -way 7.4 9.25 151.35 176.35

P-25 cantilever 0.4 0.74 2.2 One -way 7.4 9.25 80 105
From the table above, the governed depth is 191.33 for end span slab.

but we take that safer construction the depth of slab is 200mm.

Dead load Calculation


DL
Self-weight D(t)m Y(KN/m ) 3
(KN/m2) Factored Load (Pd)
floor slab 0.20 25 5 6.75
PVC Tile 0.005 16 0.008 0.108
mortar screed 0.02 23 0.46 0.621
ceiling screed 0.01 16 0.16 0.216
Total load 7.695
Parapet Wall Load on Slab
For Cantilevers:
Height of wall=1m
Thickness of wall=0.2m
Unit weight Y=14 KN/m3
Pd, par =14*0.2*1 = 1.35*2.8 =3.78KN
So, the loads which applied on the slabs are:
 Live load =1 KN/m2,
 Dead load =5.62 KN/m2
 Wind load = -0.708 KN/m2
LOAD COMBINATION
Load combinations refer to the various combinations of different types of loads that a structure
may be subjected to during its design lifetime. These combinations are essential for assessing the
safety and stability of a structure under the varying conditions it might encounter, such as dead
loads, live loads, wind loads, or seismic loads.
function of load combinations
 To ensure that a structure can safely support and resist a combination of different loads
that it may encounter during its design life.
 Safety and Reliability: Load combinations are designed to account for the worst-case
scenarios in structural loading.
 prevent the structure from being compromised or failing under unpredictable or extreme
loading events.
In our slab we have different load combination which contain live load, dead load and wind load.
1. 1.35DL + 1.5LL =1.35*5.7 + 1.5*1 = 9.195 KN/m2
2. 1.35DL+1.5LL+0.9WL =1.35*5.7+1.5*1+0.9*(-0.708) = 8.558 KN/m2
3. 1.35DL+1.05LL+1.5WL=1.35*5.7+1.05*1+1.05*(-0.708)
=8.002 KN/m2
Then, we select the governed load which are first combination.
The design factored load is Pd=9.195 KN/m2
For this design of structure Solid slab is used this type of slab is supported with beams and columns, with
the load transferred to those elements.

A Solid slab is classified as either:

One-way: Supported by beams on two opposite sides, carrying the load along one direction.

Two-way: Supported by beams on all four sides, carrying the load along both directions.

When a slab is supported other than on two opposite sides only, the precise amount and distribution of the
load taken by each support, and consequently the magnitude of the bending moments on the slab, are not
easily calculated if assumptions resembling practical conditions are made. Therefore, approximate
analyses are generally used. The method applicable in any particular case depends on the shape of the
panel of slab, the condition of restraint at supports, and the type of load.

Some basic methods for the analysis of two-way slabs are

1. Coefficient method of analysis


2. Yield line method of analysis
3. Strip method of analysis.

Among them Coefficient method of analysis is used in determination of moments which is used in the
design of slab.

 Moment Analysis of Two-way Solid slab by Using Coefficient Method


Analysis two-way slab system consist of a number of rectangular slab panels are made based on analysis
of individual slab panels simultaneously loaded by the maximum design load of slab by treating edges of
slab panels as either simply supported or fully fixed or unsupported edge.
In slabs where the corners are prevented from lifting and provision for torsion is made the maximum
design moments per unit width are given by the following equations.
 𝑀𝑥𝑠 = α𝑥𝑠Pd *𝑙𝑥 2, 𝑀𝑦𝑠 = α𝑦𝑠Pd * 𝑙𝑥 2, 𝑀𝑥𝑓 = α𝑥𝑓Pd * 𝑙𝑥 2, 𝑀𝑦𝑓 = α𝑦𝑓Pd *𝑙𝑥 2
 α𝒙𝒔 Moment coefficient in the shorter direction over supports
 α𝑥𝑓 Moment coefficient in the shorter direction at spans
 α𝑦𝑠 Moment coefficient in the longer direction over supports
 α𝑦𝑓 Moment coefficient in the longer direction at spans
 Pd Factored uniform design load
 𝑀𝑥𝑠 Maximum design ultimate moments in the shorter direction
over supports on strips of unit width
 𝑀𝑥𝑓 Maximum design ultimate moments in the shorter direction at mid-span on strips of unit width
 𝑀𝑦𝑠 Maximum design ultimate moments in the longer direction over supports on strips of unit width
 𝑀𝑦𝑓 Maximum design ultimate moments in the longer direction at mid-span on strips of unit width

Types of panel moments Short Span Coefficients, α𝑥s, α𝑥f αys,


considered αyf
1 1.1 1.2 1.3 1.4 1.5 1.75 2.0
Interior panels negative
α𝑥s, 0.031 .037 0.042 0.046 0.050 0.053 0.059 0.063 0.032
α𝑥f 0.024 0.028 0.032 0.035 0.037 0.040 0.044 0.048 0.024
One short edge
discontinuous α𝑥s, 0.039 0.044 0.048 0.052 0.055 0.058 0.063 0.067 0.037
α𝑥f 0.029 0.033 0.036 0.039 0.041 0.043 0.047 0.050 0.028
One long edge
discontinuous negative 0.039 0.049 0.056 0.063 0.068 0.073 0.082 0.089 0.037
α𝑥s,
α𝑥f
0.030 0.036 0.042 0.047 0.051 0.055 0.062 0.067 0.028
Two adjacent edges
discontinuous α𝑥s, 0.047 0.056 0.063 0.069 0.074 0.078 0.087 0.093 0.045
α𝑥f 0.036 0.042 0.047 0.051 0.055 0.059 0.065 0.070 0.034
Two short edges
discontinuous, α𝑥s, 0.046 0.050 0.054 0.057 0.060 0.062 0.067 0.070 -
α𝑥f 0.034 0.038 0.040 0.043 0.045 0.047 0.050 0.053 0.034
Two long edges
discontinuous, α𝑥s, _ _ _ _ _ _ _ 0.045
α𝑥f 0.034 0.046 0.056 0.065 0.072 0.078 0.091 0.100 0.034
Three edges discontinuous
(long edge continuous) 0.057 0.065 0.071 0.076 0.081 0.084 0.092 0.098 _
α𝑥s,
α𝑥f 0.043 0.048 0.053 0.057 0.060 0.063 0.069 0.074 0.044
Three edges discontinuous
(short edge continuous) 0.058
α𝑥s
α𝑥f 0.042 0.054 0.063 0.071 0.078 0.084 0.096 0.105 0.044
Four edges discontinuous 0.043 0.046 0.056 0.065 0.072 0.078 0.091 0.100 0.034
Positive moment mid span

Lx P-7, P-8, P-9,

P-12, P-13,
P-16, P-17, P-20

ly

Interior panels

P-2, P-3

P-4, P-19
l
x P-21

ly

One long edge discontinuous panel

P-10, P-11

P-14, P-15
lx
P-18, P-22

ly

One short edge discontinuous panel

P-5, P-18

P-22, P-23
lx

ly

Two adjacent edges discontinuous


α𝑥𝑓Pd *
α𝑦𝑠Pd *

α𝑦𝑓Pd
𝑀𝑦𝑓 =
𝑀𝑥𝑓 =
α𝑥𝑠Pd

𝑀𝑦𝑠 =
𝑀𝑥𝑠 =
panel

α𝑥𝑓

*𝑙𝑥 2

*𝑙𝑥 2
ly/lx

α𝑦𝑓
α𝑦𝑠
α𝑥𝑠

𝑙𝑥 2

𝑙𝑥 2
pd

ly
lx

0.055
9.195 2.5 3.78 1.51 4.218 2.126 3.178 1.609
P-2 0.0734 0.037 3 0.028
P-3 9.195 2.5 4.08 1.63 0.0780 0.037 0.059 0.028 4.483 2.126 3.391 1.609
P-4 9.195 2.5 4.1 1.64 0.0780 0.037 0.059 0.028 4.483 2.126 3.391 1.609
P-5 9.195 2.5 5 2 0.093 0.045 0.07 0.034 5.345 2.586 4.023 1.954
P-7 9.195 3.78 5.22 1.38 0.049 0.032 0.037 0.024 6.438 4.204 4.861 3.153
P-8 9.195 4.08 5.22 1.28 0.045 0.032 0.034 0.024 6.888 4.898 5.204 3.674
P-9 9.195 4.1 5.22 1.27 0.045 0.032 0.034 0.024 6.956 4.946 5.255 3.71
P-10 9.195 5 5.22 1.04 0.043 0.037 0.032 0.028 9.885 8.505 7.356 6.437
P-11 9.195 3.78 3.79 1 0.039 0.037 0.03 0.028 5.124 4.861 3.941 3.679
P-12 9.195 3.79 4.08 1.08 0.0302 0.032 0.027 0.024 3.989 4.226 3.566 3.17
P-13 9.195 3.78 4.1 1.08 0.0302 0.032 0.027 0.024 3.968 4.204 3.547 3.153
P-14 9.195 3.79 4.1 1.08 0.0113 0.037 0.032 0.028 1.492 4.887 4.226 3.698
P-15 9.195 3.22 3.78 1.17 0.047 0.037 0.035 0.028 4.481 3.527 3.337 2.669
P-16 9.195 3.22 4.08 1.27 0.045 0.032 0.034 0.024 4.29 3.051 3.241 2.288
P-17 9.195 3.22 4.1 1.27 0.045 0.032 0.034 0.024 4.29 3.051 3.241 2.288
P-18 9.195 2.09 3.85 1.84 0.089 0.045 0.067 0.034 3.575 1.807 2.691 1.366
0.055
9.195 3.78 5.71 1.51 9.643 4.861 7.265 3.679
P-19 0.0734 0.037 3 0.028
P-20 9.195 4.08 5.71 1.4 0.050 0.032 0.037 0.024 7.653 4.898 5.663 3.674
0.050
9.195 4.1 5.71 1.39 10.43 5.719 7.821 4.328
P-21 0.0675 0.037 6 0.028
P-22 9.195 2.62 3.78 1.44 0.076 0.045 0.057 0.034 4.797 2.84 3.598 2.146
P-23 9.195 2.62 4.08 1.56 0.08 0.045 0.06 0.034 5.049 2.84 3.787 2.146

P-24 1.4 3.79 2.707 4.843


P-25 0.74 2.2 3.143 14.303

3.78KN
For Cantilever slab P-24 Taking 1𝑚 strip 9.195KN/m
𝑀par = 9.195𝑥 1.42 /2 +3.78*1.4
= 14.303 𝑘𝑁𝑚/m
1.4m

3.78KN
9.195KN/m
For Cantilever slab P-25 Taking 1𝑚 strip
𝑀par =9.195𝑥 0.72 /2 +3.78*0.7
0.7m
= 4.843 𝑘𝑁𝑚/m

P-25

4.843

P23 5.049 P22 4.797


2.84 2.146 2.84 2.84 2.146 2.84
P24
3.787 3.598
14.303
5.049 4.797

P21 5.719 P20 4.898 P19 4.861

10.43 7.821 10.43 7.653 5.663 7.653 9.643 7.265 9.643

4.328 3.674 3.679

5.719 4.898 4.861


P18 3.575 P17 4.29 P16 4.29 P15 4.481

1.366 1.807 3.051 2.288 3.051 3.051 2.288 3.051 3.527 2.669 3.527

2.691 3.241 3.241 3.337

3.575 4.29 4.29 4.481

P14 5.679 P13 3.968 P12 3.989 P11 4.861

3.698 4.887 4.204 3.153 4.204 4.226 3.17 4.226 5.124 3.941 5.124

4.226 3.547 3.566 3.679

5.679 3.968 3.989 4.861

P10 8.505 P9 4.946 P8 4.898 P7 4.204 P6

9.885 7.356 9.885 6.956 5.255 6.956 6.888 5.204 6.888 6.438 4.861 6.438 6.336

6.437 3.71 3.674 3.153 0.713


4.204
8.505 4.946 4.898

P5 5.345 P4 4.483 P3 4.483 P2 4.218 P1

2.586 1.954 2.586 2.126 1.609 2.126 2.126 1.609 2.126 2.126 1.609 2.126 6.336

4.023 3.391 3.391 3.178 0.713

Adjusted moment
𝑀𝑥𝑓 = α𝑥𝑓Pd * 𝑙𝑥 2
𝑀𝑦𝑠 = α𝑦𝑠Pd * 𝑙𝑥 2

𝑀𝑦𝑓 = α𝑦𝑓Pd *𝑙𝑥 2


𝑀𝑥𝑠 = α𝑥𝑠Pd *𝑙𝑥 2
panel

α𝑥𝑓
ly/lx

α𝑦𝑓
α𝑦𝑠
α𝑥𝑠
pd

ly
lx
3.04 4.009
P-1 Left
9.195 2.5 3.78 1.51 2.126 1.609
P-2 left 0.0734 0.037 0.0553 0.028
right 3.04

Upper 4.211 3.185


9.195 2.5 4.08 1.63 0.028 2.126 1.609
P-3 Left 0.0780 0.037 0.059
Right 2.126

upper 4.691 1.401


9.195 2.5 4.1 1.64 0.028 2.379 1.356
P-4 left 0.0780 0.037 0.059
Right 2.126 1.609

Upper 4.715 3.159

P-5 Right 2.379 2.161

Upper 7.481 1.887

P-6 left 6.387 0.662

P-7 Left 9.195 3.78 5.22 1.38 0.049 0.032 0.037 0.024 6.663

Right 6.387 4.912

Upper 4.481

lower 4.211 3.146

P-8 left 9.195 4.08 5.22 1.28 0.045 0.032 0.034 0.024 6.922 5.429

6.663
Right
4.515
Upper
4.691 4.057
Lower
P-9 Upper 4.534 5.667

Lower 4.715
Left 9.195 4.1 5.22 1.27 0.045 0.032 0.034 0.024 8.564 5.289
Right 6.922
P-10 Upper 7.315 7.627
Lower 7.481
Right 8.564 8.677

P-11 Left 9.195 3.78 3.79 1 0.039 0.037 0.03 0.028 4.658 4.523

Upper 4.671

Lower 4.481 4.059

P-12 Left 9.195 3.79 4.08 1.08 0.0302 0.032 0.027 0.024 4.215 3.181
Right 4.658

Upper 4.14 3.415

Lower 4.515

P-13 Upper 4.129 3.407

Lower 4.534

Left 9.195 3.78 4.1 1.08 0.0302 0.032 0.027 0.024 4.546 3.142

Right 4.215

P-14 Upper 4.713 5.522

Right 9.195 3.79 4.1 1.08 0.043 0.037 0.032 0.028 4.546 4.039

Lower 7.315

P-15 Left 9.195 3.22 3.78 1.17 0.047 0.037 0.035 0.028 3.280 2.916

Upper 4.671

Lower 4.671 3.147

P-16 Left 9.195 3.22 4.08 1.27 0.045 0.032 0.034 0.024 3.051 2.288

Right 3.280

Upper 4.679

Lower 4.14 3.391

P-17 Left 9.195 3.22 4.1 1.27 0.045 0.032 0.034 0.024 2.631 2.708

Right 3.051

upper 5.203

Lower 4.129 3.402

P-18 Lower 4.713 1.553

Right 9.195 2.09 3.85 1.84 0.089 0.045 0.067 0.034 2.631 0.542

P-19 Lef 9.195 3.78 5.71 1.51 0.0734 0.037 0.0553 0.028 8.610 8.298

Upper 4.829

Lower 4.671 3.711

P-20 Left 9.195 4.08 5.71 1.4 0.050 0.032 0.037 0.024 9.044 4.706

Right 8.610

Upper 4.946

Lower 4.679 3.893

P-21 Right 9.044 9.207

Upper 5.719

Lower 5.203 4.844

P-22 Left 9.195 2.62 3.78 1.44 0.076 0.045 0.057 0.034 2.84 2.146

Lower 4.829 3.598

P-23 Right 9.195 2.62 4.08 1.56 0.08 0.045 0.06 0.034 2.84 2.146
Upper 5.049

Lower 4.946 3.89

P-24 1.4 3.79 2.707 4.843


P-25 0.74 2.2 3.143 14.303

Determine design constants

Material: Concrete 𝐶25/30 𝑓𝑐𝑘 = 25𝑀𝑝𝑎

0.85∗fck 0.85∗25
fcd = = = 14.167 𝑀𝑃𝑎
γc 1.5

𝑓𝑐𝑡𝑘 𝑀𝑃𝑎

Steel: 𝑆 − 400, 𝑓𝑦𝑘 = 400𝑀𝑝𝑎

fyk 400
𝑓𝑦𝑑 = = = 347.83𝑀𝑃𝑎
γ s 1.15

Check thickness of the slab required for flexure

Minimum effective depth to avoid any compression steel (singly reinforced) is given by:

Md
<𝐾𝑏𝑎𝑙 , 𝑀𝑑 𝑀𝑚𝑎𝑥 = 14.303𝑘𝑁𝑚 𝑏 = 1𝑚 𝑠𝑡𝑟𝑖𝑝 𝑤𝑖𝑑𝑡ℎ
fcdbd 2

dmin ≥
√ Md =
√ 14.303∗1000000 = 58.501 mm
0.295∗fcd∗b 0.295∗14.167∗1000

The overall thickness D of the slab = d + d’ = 58.501 + 25 = 83.501𝑚𝑚 < 𝐷𝑢𝑠𝑒𝑑

83.501𝑚𝑚 𝐷𝑢𝑠𝑒𝑑 = 200𝑚𝑚 … … … … … … … … … … … … … … … 𝑂𝑘!


𝑑1 = 200 − 25 − 10/2 = 170 𝑚𝑚 𝑑2 = 200 − 25 − 10 − 10/2 = 160 𝑚𝑚

Calculate flexural reinforcement 𝐴𝑠

Check maximum and minimum reinforcement areas (Refer ES EN 1992: 2015 clause 9.2.1.1)

{
0.26 fctmbt d
𝐴𝑠,𝑚𝑖𝑛 = 𝑀𝑎𝑥. f yk
0.0013 bt d

= 𝑀𝑎𝑥.¿

=𝑀𝑎𝑥.¿ =283.429 mm2

𝐴𝑠,𝑚𝑎𝑥 𝟖𝟎𝟎𝟎𝒎𝒎𝟐

𝑏𝑡 =Width of tension zone = Take 1𝑚 width 𝐴𝑐= area of concrete = b*D

bas
Spacing of reinforcement 𝒔 =
As

Check minimum spacing of reinforcement (refer ES EN 1992: 2015 clause 8.2)

{
ϕbar=12 mm
𝑠𝑚𝑖𝑛 = 𝑀𝑎𝑥. ϕagg .+5 mm
20 m m

𝑠𝑚𝑖𝑛= 20mm

Check maximum spacing of reinforcement (refer ES EN 1992: 2015 clause 9.3.1)

 For slabs less than 200mm thick the following maximum spacing rules apply:
𝑚𝑚
 For the principal reinforcement: 𝑠𝑚𝑎𝑥 = 𝑀𝑖𝑛.
𝟒𝟎𝟎𝒎𝒎

𝑚𝑚
 For the secondary reinforcement: 𝑠𝑚𝑎𝑥 = 𝑀𝑖𝑛.
𝟒𝟓𝟎𝒎𝒎

Where h is the depth of the slab

b∗as 1000∗78.54
𝑆𝑚𝑖𝑛 = = = 277.106 mm
As , min 283.429
𝑠𝑚𝑖𝑛 = 277.106 mm < 𝑠𝑚𝑎𝑥 𝑻𝒂𝒌𝒆 𝒔 = 𝟐𝟕𝟎𝒎𝒎

Area of reinforcement needed for the corresponding design moment is calculated using the following
equation.
Md
As =
fyd∗z
Where:
𝑀d = Design moment
𝑓yd= Design yield capacity of reinforcement = 347.83 MPa
Z = Moment arm
Where:
Z =0.5d (1+√ 1−2 k ) ≤ 0.95d

Md
K= b∗d∗d∗fcd ≤ 0.295
Depth(mm)

Provided(m
S, provided
No of Bars
calculated
Moment
Location

Effective

Spacing
As, min

S, max
(KNm)

(mm2)

(mm2)

S, req

(mm)
(mm)
(mm)

(mm)
Panel

Strip

As,

m)
Kz

k
z
P1
Support B/n P1&P2 3.04 170 0.95 161.5 54.11704 283.429 4 277.106 400 270 7E-09 ɸ10 c/c 270
Span Shorter(x) 4.009 170 0.95 161.5 71.36684 283.429 4 277.106 400 270 1E-08 ɸ10 c/c 270
Support B/n P2&P1 ɸ10 c/c 270
3.04 170 0.95 161.5 54.11704 283.429 4 277.106 400 270 7E-09
Support B/nP2&P3 ɸ10 c/c 270
2.126 170 0.95 161.5 37.84632 283.429 4 277.106 400 270 5E-09
P2 ɸ10 c/c 270
Support B/n P2&P7 4.211 160 0.95 152 79.64795 283.429 4 277.106 400 270 1E-08
Span Shorter(x) 2.185 160 0.95 152 41.32766 283.429 4 277.106 400 270 6E-09 ɸ10 c/c 270
Span Longer(y) 1.609 170 0.95 161.5 28.64287 283.429 4 277.106 400 270 4E-09 ɸ10 c/c 270
Support B/nP3&P2 ɸ10 c/c 270
2.126 170 0.95 161.5 37.84632 283.429 4 277.106 400 270 5E-09
Support B/nP3&P4 ɸ10 c/c 270
2.126 170 0.95 161.5 37.84632 283.429 4 277.106 400 270 5E-09
P3 ɸ10 c/c 270
Support B/n P3&P8 4.691 160 0.95 152 88.7268 283.429 4 277.106 400 270 1E-08
Span Shorter(x) 1.401 160 0.95 152 26.49888 283.429 4 277.106 400 270 4E-09 ɸ10 c/c 270
Span Longer(y) 1.609 170 0.95 161.5 28.64287 283.429 4 277.106 400 270 4E-09 ɸ10 c/c 270
Support B/n P4&P3 ɸ10 c/c 270
2.126 170 0.95 161.5 37.84632 283.429 4 277.106 400 270 5E-09
Support B/n P4&P5 ɸ10 c/c 270
2.379 170 0.95 161.5 42.35014 283.429 4 277.106 400 270 6E-09
P4 Support B/n P4&P9 ɸ10 c/c 270
4.715 160 0.95 152 89.18074 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
3.159 160 0.95 152 59.75015 283.429 4 277.106 400 270 9E-09
Span Longer(y) ɸ10 c/c 270
1.609 170 0.95 161.5 28.64287 283.429 4 277.106 400 270 4E-09
Support B/nP5 & P4 ɸ10 c/c 270
2.379 160 0.95 152 44.99703 283.429 4 277.106 400 270 7E-09
B/n P5 & ɸ10 c/c 270
Support
P10 7.481 170 0.95 161.5 133.1742 283.429 4 277.106 400 270 2E-08
P5
Span Shorter(x) ɸ10 c/c 270
1.887 170 0.95 161.5 33.59173 283.429 4 277.106 400 270 5E-09
Span Longer(y) ɸ10 c/c 270
2.161 160 0.95 152 40.87372 283.429 4 277.106 400 270 6E-09
Support B/nP6 & P7 ɸ10 c/c 270
6.387 170 0.95 161.5 113.6992 283.429 4 277.106 400 270 2E-08
P6
Span Shorter(x) ɸ10 c/c 270
0.662 170 0.95 161.5 11.7847 283.429 4 277.106 400 270 2E-09
Support B/nP7 & P11 ɸ10 c/c 270
4.481 160 0.95 152 84.7548 283.429 4 277.106 400 270 1E-08
Support B/nP7 & P8 ɸ10 c/c 270
6.663 170 0.95 161.5 118.6124 283.429 4 277.106 400 270 2E-08
Support B/nP7 & P6 ɸ10 c/c 270
6.387 170 0.95 161.5 113.6992 283.429 4 277.106 400 270 2E-08
P7
Support B/nP7 & P2 ɸ10 c/c 270
4.211 160 0.95 152 79.64795 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
4.912 170 0.95 161.5 87.44174 283.429 4 277.106 400 270 1E-08
Span Longer(y) ɸ10 c/c 270
3.146 160 0.95 152 59.50426 283.429 4 277.106 400 270 9E-09
P8 Support B/nP8 & P7 ɸ10 c/c 270
6.663 160 0.95 152 126.0257 283.429 4 277.106 400 270 2E-08
Support B/nP8 & P9 ɸ10 c/c 270
6.922 170 0.95 161.5 123.2231 283.429 4 277.106 400 270 2E-08
Support B/nP8 & P3 ɸ10 c/c 270
4.691 170 0.95 161.5 83.50757 283.429 4 277.106 400 270 1E-08
Support B/nP8 & P12 ɸ10 c/c 270
4.515 160 0.95 152 85.39789 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
5.429 170 0.95 161.5 96.6452 283.429 4 277.106 400 270 1E-08
Span Longer(y) ɸ10 c/c 270
4.057 160 0.95 152 76.73516 283.429 4 277.106 400 270 1E-08
Support B/nP9 & P8 ɸ10 c/c 270
6.922 160 0.95 152 130.9245 283.429 4 277.106 400 270 2E-08
Support B/nP9 & P10 ɸ10 c/c 270
8.564 170 0.95 161.5 152.4534 283.429 4 277.106 400 270 2E-08
Support B/nP9 & P4 ɸ10 c/c 270
4.715 170 0.95 161.5 83.93481 283.429 4 277.106 400 270 1E-08
P9
Support B/nP9 & P13 ɸ10 c/c 270
4.534 160 0.95 152 85.75726 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
5.289 170 0.95 161.5 94.15297 283.429 4 277.106 400 270 1E-08
Span Longer(y) ɸ10 c/c 270
5.667 160 0.95 152 107.1871 283.429 4 277.106 400 270 2E-08
Support B/nP10 & P9 ɸ10 c/c 270
8.564 170 0.95 161.5 152.4534 283.429 4 277.106 400 270 2E-08
Support B/nP10 & P5 ɸ10 c/c 270
7.481 160 0.95 152 141.4976 283.429 4 277.106 400 270 2E-08
B/nP10 & ɸ10 c/c 270
P10 Support
P14 7.315 160 0.95 152 138.3578 283.429 4 277.106 400 270 2E-08
Span Shorter(x) ɸ10 c/c 270
8.677 170 0.95 161.5 154.465 283.429 4 277.106 400 270 2E-08
Span Longer(y) ɸ10 c/c 270
7.627 160 0.95 152 144.2591 283.429 4 277.106 400 270 2E-08
Support B/nP11 & P7 ɸ10 c/c 270
4.481 160 0.95 152 84.7548 283.429 4 277.106 400 270 1E-08
B/n P11 & ɸ10 c/c 270
Support
P12 4.658 170 0.95 161.5 82.92012 283.429 4 277.106 400 270 1E-08
P11 Support B/nP11 & ɸ10 c/c 270
P15 4.671 160 0.95 152 88.34851 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
4.523 170 0.95 161.5 80.5169 283.429 4 277.106 400 270 1E-08
Span Longer(y) ɸ10 c/c 270
4.059 160 0.95 152 76.77298 283.429 4 277.106 400 270 1E-08
B/nP12 & ɸ10 c/c 270
Support
P11 4.658 160 0.95 152 88.10263 283.429 4 277.106 400 270 1E-08
B/nP12 & ɸ10 c/c 270
Support
P13 4.215 160 0.95 152 79.72361 283.429 4 277.106 400 270 1E-08
Support B/nP12 & P8 ɸ10 c/c 270
4.515 170 0.95 161.5 80.37448 283.429 4 277.106 400 270 1E-08
P12
B/nP12 & ɸ10 c/c 270
Support
P16 4.14 170 0.95 161.5 73.69886 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
3.415 170 0.95 161.5 60.79266 283.429 4 277.106 400 270 8E-09
Span Longer(y) ɸ10 c/c 270
3.181 160 0.95 152 60.16626 283.429 4 277.106 400 270 9E-09
B/nP13 & ɸ10 c/c 270
Support
P12 4.215 160 0.95 152 79.72361 283.429 4 277.106 400 270 1E-08
B/nP13 & ɸ10 c/c 270
Support
P14 4.546 160 0.95 152 85.98423 283.429 4 277.106 400 270 1E-08
Support B/nP13 & P9 ɸ10 c/c 270
4.534 170 0.95 161.5 80.71271 283.429 4 277.106 400 270 1E-08
P13
B/nP13 & ɸ10 c/c 270
Support
P17 4.129 170 0.95 161.5 73.50304 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
3.407 170 0.95 161.5 60.65025 283.429 4 277.106 400 270 8E-09
Span Longer(y) 3.142 ɸ10 c/c 270
160 0.95 152 59.42861 283.429 4 277.106 400 270 9E-09
Support B/n P14 & P13 ɸ10 c/c 270
4.546 160 0.95 152 85.98423 283.429 4 277.106 400 270 1E-08
B/nP14 & ɸ10 c/c 270
Support
P10 7.315 170 0.95 161.5 130.2191 283.429 4 277.106 400 270 2E-08
P14 Support B/nP14 & ɸ10 c/c 270
P18 4.713 170 0.95 161.5 83.89921 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
5.522 160 0.95 152 104.4445 283.429 4 277.106 400 270 2E-08
Span Longer(y) ɸ10 c/c 270
4.039 170 0.95 161.5 71.90089 283.429 4 277.106 400 270 1E-08
B/nP15& ɸ10 c/c 270
Support
P16 3.28 160 0.95 152 62.03878 283.429 4 277.106 400 270 9E-09
B/nP15 & ɸ10 c/c 270
Support
P11 4.671 170 0.95 161.5 83.15154 283.429 4 277.106 400 270 1E-08
P15 Support B/nP15 & ɸ10 c/c 270
P19 4.671 170 0.95 161.5 83.15154 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
3.147 170 0.95 161.5 56.02182 283.429 4 277.106 400 270 8E-09
Span Longer(y) ɸ10 c/c 270
2.916 160 0.95 152 55.15398 283.429 4 277.106 400 270 8E-09
B/nP16 & ɸ10 c/c 270
Support
P15 3.28 160 0.95 152 62.03878 283.429 4 277.106 400 270 9E-09
B/nP16 & ɸ10 c/c 270
Support
P17 3.051 160 0.95 152 57.70741 283.429 4 277.106 400 270 8E-09
B/nP16 & ɸ10 c/c 270
Support
P16 P12 4.14 170 0.95 161.5 73.69886 283.429 4 277.106 400 270 1E-08
B/nP16 & ɸ10 c/c 270
Support
P20 4.679 170 0.95 161.5 83.29395 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
3.391 170 0.95 161.5 60.36542 283.429 4 277.106 400 270 8E-09
Span Longer(y) ɸ10 c/c 270
2.288 160 0.95 152 43.27583 283.429 4 277.106 400 270 6E-09
B/nP17 & ɸ10 c/c 270
Support
P16 3.051 160 0.95 152 57.70741 283.429 4 277.106 400 270 8E-09
B/nP17 & ɸ10 c/c 270
Support
P18 2.631 160 0.95 152 49.76342 283.429 4 277.106 400 270 7E-09
P17
B/nP17 & ɸ10 c/c 270
Support
P13 4.129 170 0.95 161.5 73.50304 283.429 4 277.106 400 270 1E-08
Support B/nP17 & 5.203 170 0.95 161.5 92.62202 283.429 4 277.106 400 270 1E-08 ɸ10 c/c 270
P21

Span Shorter(x) ɸ10 c/c 270


3.402 170 0.95 161.5 60.56124 283.429 4 277.106 400 270 8E-09
Span Longer(y) ɸ10 c/c 270
2.708 160 0.95 152 51.21982 283.429 4 277.106 400 270 7E-09
B/nP18 & ɸ10 c/c 270
Support
P17 2.631 160 0.95 152 49.76342 283.429 4 277.106 400 270 7E-09
B/nP18 & ɸ10 c/c 270
Support
P18 P14 4.713 170 0.95 161.5 83.89921 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
1.553 170 0.95 161.5 27.64597 283.429 4 277.106 400 270 4E-09
Span Longer(y) ɸ10 c/c 270
0.542 160 0.95 152 10.25153 283.429 4 277.106 400 270 1E-09
B/nP19 & ɸ10 c/c 270
Support
P20 8.61 170 0.95 161.5 153.2723 283.429 4 277.106 400 270 2E-08
B/nP19& ɸ10 c/c 270
Support
P15 4.671 160 0.95 152 88.34851 283.429 4 277.106 400 270 1E-08
P19 Support B/n P19 & ɸ10 c/c 270
P22 4.829 160 0.95 152 91.33697 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
8.298 170 0.95 161.5 147.7182 283.429 4 277.106 400 270 2E-08
Span Longer(y) ɸ10 c/c 270
3.711 160 0.95 152 70.19082 283.429 4 277.106 400 270 1E-08
B/nP20 & ɸ10 c/c 270
Support
P19 8.61 170 0.95 161.5 153.2723 283.429 4 277.106 400 270 2E-08
B/nP20 & ɸ10 c/c 270
Support
P21 9.044 170 0.95 161.5 160.9982 283.429 4 277.106 400 270 2E-08
B/nP20& ɸ10 c/c 270
Support
P20 P16 4.679 160 0.95 152 88.49983 283.429 4 277.106 400 270 1E-08
B/n P20& ɸ10 c/c 270
Support
P23 4.946 160 0.95 152 93.54993 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
4.706 170 0.95 161.5 83.7746 283.429 4 277.106 400 270 1E-08
Span Longer(y) ɸ10 c/c 270
3.893 160 0.95 152 73.63322 283.429 4 277.106 400 270 1E-08
B/n P21 & ɸ10 c/c 270
Support
P20 9.044 170 0.95 161.5 160.9982 283.429 4 277.106 400 270 2E-08
B/n P21& ɸ10 c/c 270
Support
P17 5.203 160 0.95 152 98.4109 283.429 4 277.106 400 270 1E-08
P21 Support B/nP21& ɸ10 c/c 270
P24 5.719 160 0.95 152 108.1707 283.429 4 277.106 400 270 2E-08
Span Shorter(x) ɸ10 c/c 270
9.207 170 0.95 161.5 163.8999 283.429 4 277.106 400 270 2E-08
Span Longer(y) ɸ10 c/c 270
4.844 160 0.95 152 91.62068 283.429 4 277.106 400 270 1E-08
B/nP22 & ɸ10 c/c 270
Support
P23 2.84 160 0.95 152 53.7165 283.429 4 277.106 400 270 8E-09
P22 Support B/nP22 & ɸ10 c/c 270
P19 4.829 170 0.95 161.5 85.9642 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
3.598 170 0.95 161.5 64.05036 283.429 4 277.106 400 270 9E-09
Span Longer(y) ɸ10 c/c 270
2.146 160 0.95 152 40.59 283.429 4 277.106 400 270 6E-09
B/nP23 & ɸ10 c/c 270
Support
P20 4.946 170 0.95 161.5 88.047 283.429 4 277.106 400 270 1E-08
B/n P23 & ɸ10 c/c 270
Support
P22 2.84 160 0.95 152 53.7165 283.429 4 277.106 400 270 8E-09
P23 Support B/n P23 & ɸ10 c/c 270
P25 5.049 170 0.95 161.5 89.88057 283.429 4 277.106 400 270 1E-08
Span Shorter(x) ɸ10 c/c 270
3.89 170 0.95 161.5 69.24845 283.429 4 277.106 400 270 1E-08
Span Longer(y) ɸ10 c/c 270
2.146 160 0.95 152 40.59 283.429 4 277.106 400 270 6E-09
B/n P24 & ɸ10 c/c 270
P24 Support
P21 14.3 170 0.95 161.5 254.6171 283.429 4 277.106 400 270 3E-08
B/n P25 & ɸ10 c/c 270
P25 Support
P23 4.843 170 0.95 161.5 86.21343 283.429 4 277.106 400 270 1E-08