TransformerDifferentialTAPCalcs r1
TransformerDifferentialTAPCalcs r1
Summary a
force desired current ratio of 1.0000 to choose TAP 1 = TAP 2 = 5.0
desired ratio = 0.6497 unitless
best tap ratio = 0.6400 unitless
difference = 0.0097 unitless
TAP 1 = 3.2 amps
TAP 2 = 5.0 amps
mismatch = 1.51%
TAP 1 = TAP 2 = 5.0
Summary
desired current ratio = 0.6497 unitless
best tap ratio = 0.6400 unitless
difference = 0.0097 unitless
TAP 1 = 3.2 amps a
force desired current ratio of 1.0000 to choose TAP 1 = TAP 2 = 5.0
TAP 2 = 5.0 amps
mismatch (MM) 1.51% DIFF TAP 1/TAP 2 TAP 1 TAP 2
9.9999a 1.0000 2.9 2.9
0.2566 0.9062 2.9 3.2
0.1789 0.8286 2.9 3.5
0.1135 0.7632 2.9 3.8
0.0408 0.6905 2.9 4.2
0.0192 0.6304 2.9 4.6
0.0697 0.5800 2.9 5.0
0.3163 0.3333 2.9 8.7
0.4538 1.1034 3.2 2.9
9.9999a 1.0000 3.2 3.2
0.2646 0.9143 3.2 3.5
0.1925 0.8421 3.2 3.8
0.1122 0.7619 3.2 4.2
0.0460 0.6957 3.2 4.6
0.0097 0.6400 3.2 5.0
0.2818 0.3678 3.2 8.7
0.5572 1.2069 3.5 2.9
0.4441 1.0938 3.5 3.2
9.9999a 1.0000 3.5 3.5
0.2714 0.9211 3.5 3.8
0.1837 0.8333 3.5 4.2
0.1112 0.7609 3.5 4.6
0.0503 0.7000 3.5 5.0
0.2474 0.4023 3.5 8.7
0.6607 1.3103 3.8 2.9
0.5378 1.1875 3.8 3.2
0.4361 1.0857 3.8 3.5
9.9999a 1.0000 3.8 3.8
0.2551 0.9048 3.8 4.2
0.1764 0.8261 3.8 4.6
0.1103 0.7600 3.8 5.0
0.2129 0.4368 3.8 8.7
0.7986 1.4483 4.2 2.9
0.6628 1.3125 4.2 3.2
0.5503 1.2000 4.2 3.5
0.4556 1.1053 4.2 3.8
9.9999a 1.0000 4.2 4.2
0.2634 0.9130 4.2 4.6
0.1903 0.8400 4.2 5.0
0.1669 0.4828 4.2 8.7
0.9366 1.5862 4.6 2.9
0.7878 1.4375 4.6 3.2
0.6646 1.3143 4.6 3.5
0.5609 1.2105 4.6 3.8
0.4456 1.0952 4.6 4.2
9.9999a 1.0000 4.6 4.6
0.2703 0.9200 4.6 5.0
0.1209 0.5287 4.6 8.7
1.0745 1.7241 5.0 2.9
0.9128 1.5625 5.0 3.2
0.7789 1.4286 5.0 3.5
0.6661 1.3158 5.0 3.8
0.5408 1.1905 5.0 4.2
0.4373 1.0870 5.0 4.6
0.3503 1.0000 5.0 5.0
0.0749 0.5747 5.0 8.7
2.3503 3.0000 8.7 2.9
2.0691 2.7187 8.7 3.2
1.8361 2.4857 8.7 3.5
1.6398 2.2895 8.7 3.8
1.4218 2.0714 8.7 4.2
1.2416 1.8913 8.7 4.6
1.0903 1.7400 8.7 5.0
9.9999a 1.0000 8.7 8.7
1 = TAP 2 = 5.0