Ga 30
Ga 30
Instruction book
Original instructions
COPYRIGHT NOTICE
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and
drawings.
This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as
identified in the Declaration of Conformity.
2019 - 11
No. 2920 7109 51
www.atlascopco.com
Instruction book
Table of contents
1 Safety precautions..........................................................................................................6
2 General description...................................................................................................... 12
2.1 INTRODUCTION.................................................................................................................................12
3.1 CONTROLLER...................................................................................................................................27
3.4 MENU............................................................................................................................................ 31
3.6 SHUTDOWN..................................................................................................................................... 36
2 2920 7109 51
Instruction book
4.1 CONTROLLER...................................................................................................................................56
4.7 SHUTDOWN..................................................................................................................................... 66
5 OSCi (optional)..............................................................................................................91
5.1 INTRODUCTION.................................................................................................................................91
5.2 OPERATION.....................................................................................................................................92
5.4 PICTOGRAPHS................................................................................................................................. 97
2920 7109 51 3
Instruction book
5.7 WARNINGS......................................................................................................................................99
6.3 OPERATION...................................................................................................................................108
7 Installation...................................................................................................................114
4 2920 7109 51
Instruction book
9 Maintenance................................................................................................................ 142
10 Problem solving..........................................................................................................155
11 Technical data.............................................................................................................159
2920 7109 51 5
Instruction book
1 Safety precautions
Explanation
Danger to life
Warning
Important note
If the machine is equipped with an automatic restart after voltage failure function and if
this function is active, be aware that the machine will restart automatically when the
power is restored if it was running when the power was interrupted!
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at
people. Never use the air to clean dirt from your clothes. When using the air to clean
equipment, do so with extreme caution and wear eye protection.
7. The owner is responsible for maintaining the unit in safe operating condition. Parts and
accessories shall be replaced if unsuitable for safe operation.
8. It is prohibited to walk or stand on the unit or on its components.
6 2920 7109 51
Instruction book
9. If compressed air is used in the food industry and more specifically for direct food contact, it
is recommended, for optimal safety, to use certified Class 0 compressors in combination
with appropriate filtration depending on the application. Please contact your customer center
for advice on specific filtration.
2920 7109 51 7
Instruction book
12. The electrical connections must correspond to the applicable codes. The machines must be
earthed and protected against short circuits by fuses in all phases. A lockable power
isolating switch must be installed near the compressor.
13. On machines with automatic start/stop system or if the automatic restart function after
voltage failure is activated, a sign stating "This machine may start without warning" must be
affixed near the instrument panel.
14. In multiple compressor systems, manual valves must be installed to isolate each
compressor. Non-return valves (check valves) must not be relied upon for isolating pressure
systems.
15. Never remove or tamper with the safety devices, guards or insulation fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure must be protected by a pressure relieving device or devices as
required.
16. Piping or other parts with a temperature in excess of 70˚C (158˚F) and which may be
accidentally touched by personnel in normal operation must be guarded or insulated. Other
high temperature piping must be clearly marked.
17. For water-cooled machines, the cooling water system installed outside the machine has to
be protected by a safety device with set pressure according to the maximum cooling water
inlet pressure.
18. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
19. If the device is a dryer and no free extinguishing system is present in the air net close to the
dryer, safety valves must be installed in the vessels of the dryer.
Also consult following safety precautions: Safety precautions during operation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
8 2920 7109 51
Instruction book
6. Keep all bodywork doors shut during operation. The doors may be opened for short periods
only, e.g. to carry out routine checks. Wear ear protectors when opening a door.
On machines without bodywork, wear ear protection in the vicinity of the machine.
7. People staying in environments or rooms where the sound pressure level reaches or
exceeds 80 dB(A) shall wear ear protectors.
8. Periodically check that:
• All guards are in place and securely fastened
• All hoses and/or pipes inside the machine are in good condition, secure and not
rubbing
• No leaks occur
• All fasteners are tight
• All electrical leads are secure and in good order
• Safety valves and other pressure relief devices are not obstructed by dirt or paint
• Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in
good repair, free of wear or abuse
• Air cooling filters of the electrical cabinet are not clogged
9. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a
workroom, take precautions against air pollution and possible contamination of the breathing
air.
10. On water-cooled compressors using open circuit cooling towers, protective measures must
be taken to avoid the growth of harmful bacteria such as Legionella pneumophila bacteria.
11. Do not remove any of, or tamper with, the sound-damping material.
12. Never remove or tamper with the safety devices, guards or insulations fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure shall be protected by a pressure relieving device or devices as
required.
13. Yearly inspect the air receiver. Minimum wall thickness as specified in the instruction book
must be respected. Local regulations remain applicable if they are more strict.
Also consult following safety precautions: Safety precautions during installation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
2920 7109 51 9
Instruction book
3. Use only genuine spare parts for maintenance or repair. The manufacturer will disclaim all
damage or injuries caused by the use of non-genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "Work in progress; do not start" shall be attached
to the starting equipment.
6. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
7. Close the compressor air outlet valve and depressurize the compressor before connecting
or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all
sources of pressure and relieve the entire system of pressure.
9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety
precautions against toxic vapors of cleaning liquids.
10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by
covering the parts and exposed openings with a clean cloth, paper or tape.
11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be
completely purged, e.g. by steam cleaning, before carrying out such operations. Never weld
on, or in any way modify, pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is
overheated, the machine shall be stopped but no inspection covers shall be opened before
sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil
vapor when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure
vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they
function properly. They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating
pressures, temperatures and time settings are correct. Check that all control and shut-down
devices are fitted and that they function correctly. If removed, check that the coupling guard
of the compressor drive shaft has been reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of
the oil separator vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture
from entering them, e.g. when steam cleaning.
19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on
the bodywork and in the air inlet and outlet systems of the compressor, is in good condition.
If damaged, replace it by genuine material from the manufacturer to prevent the sound
pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate
bowls.
21. Only if applicable, the following safety precautions are stressed when handling
refrigerant:
• Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if
required, use breathing protection.
• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin
with water. If liquid refrigerant contacts the skin through clothing, never tear off or
remove the latter; flush abundantly with fresh water over the clothing until all refrigerant
is flushed away; then seek medical first aid.
10 2920 7109 51
Instruction book
Also consult following safety precautions: Safety precautions during installation and
Safety precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
2920 7109 51 11
Instruction book
2 General description
2.1 Introduction
GA 30+ up to GA 45+ are single-stage, oil-injected screw compressors driven by an electric
motor. The compressors are available in air-cooled and water-cooled version.
The compressors are controlled by an Elektronikon™ controller.
GA Workplace
GA Workplace compressors are enclosed in a sound-insulated bodywork. The Elektronikon
control module is fitted to the panel on the right hand side. An electric cabinet comprising the
motor starter is located behind this panel. A condensate trap with Centrifugal Water Drain (WSD)
is provided.
12 2920 7109 51
Instruction book
Reference Name
AV Air outlet valve
Ca Air cooler
Co Oil cooler
CV/Vs Check valve/oil stop valve
E Compressor element
ER Elektronikon™ controller
FN Cooling fan
M1 Drive motor
S3 Emergency stop button
UA Unloader
Da (Dm) Condensate outlets
GA Workplace Full-Feature
GA Workplace Full-Feature compressors are enclosed in a sound-insulated bodywork. The
Elektronikon control module is fitted to the panel on the right side. An electric cabinet comprising
the motor starter is located behind this panel. The compressors are provided with an air dryer.
2920 7109 51 13
Instruction book
The dryer is integrated in the sound-insulated bodywork. The dryer removes water from the
compressed air by cooling the air to near freezing point. The condensate is automatically drained.
14 2920 7109 51
Instruction book
Reference Name
1 Electric cubicle
AF Air filter
AR Air receiver (oil separator vessel)
AV Air outlet valve
Ca Air cooler
Co Oil cooler
CV/Vs Check valve/oil stop valve
Da Automatic condensate outlets
Dm Manual condensate outlets
DR Dryer
E Compressor element
ER Elektronikon™ controller
FN Cooling fan
M1 Drive motor
OF Oil filter
S3 Emergency stop button
2920 7109 51 15
Instruction book
Reference Name
UA Unloader
Flow diagrams
16 2920 7109 51
Instruction book
Reference Description
A Intake air
B Air/oil mixture
C Oil
D Wet compressed air
E Condensate
F Dried compressed air
Description
Air drawn through filter (AF) and open inlet valve (IV) of unloader is compressed in compressor
element (E). A mixture of compressed air and oil flows into the air receiver/oil separator (AR) via
check valve (CV). The air is discharged through outlet valve (AV) via minimum pressure valve
(Vp) and air cooler (Ca).
The air cooler is provided with a moisture trap (MT).
2920 7109 51 17
Instruction book
On Full-Feature compressors, the air flows through air dryer (DR) before it is discharged through
outlet valve (AV). Also see section Air dryer.
In all circumstances, minimum pressure valve (Vp) keeps the pressure in the separator tank (AR)
above a minimum value, required for lubrication. An integrated check valve prevents the
compressed air downstream the valve from being vented to atmosphere during unloaded
operation. When the compressor is stopped, check valve (CV) and inlet valve (IV) close,
preventing compressed air (and oil) to be vented into the air filter.
Flow diagram
Oil system
References Description
1 Compressed air flow to the air outlet valve (Workplace units)
Compressed air flow to the air dryer (compressors with integrated dryer)
A Intake air
B Air/oil mixture
C Oil
D Wet compressed air
18 2920 7109 51
Instruction book
Description
In air receiver/oil separator (AR), most of the oil is removed from the air/oil mixture by centrifugal
action. The remaining oil is removed by oil separator (OS). The oil collects in the lower part of air
receiver/oil separator (AR), which serves as an oil tank.
The oil system is provided with a thermostatic bypass valve (BV). When the oil temperature is
below its set point, bypass valve (BV) shuts off the supply to oil cooler (Co) and the oil cooler is
bypassed.
Air pressure forces the oil from air receiver/oil separator (AR) through oil filter (OF) and oil stop
valve (Vs) to compressor element (E).
Bypass valve (BV) starts opening the supply from cooler (Co) when the oil temperature has
increased to the set point. At approx. 15 ˚C (27 ˚F) above the set point, all the oil flows through
the oil cooler.
Oil stop valve (Vs) prevents the compressor element from flooding with oil when the compressor
is stopped. The valve is opened by element outlet pressure when the compressor is started.
Air-cooled compressors
References Description
A Intake air
B Air/oil mixture
C Oil
D Wet compressed air
E Condensate
2920 7109 51 19
Instruction book
Description
The cooling system on air-cooled compressors comprises air cooler (Ca) and oil cooler (Co).
The cooling air flow is generated by fan (FN).
Water-cooled compressors
References Description
A Intake air
B Air/oil mixture
C Oil
D Wet compressed air
F Water flow
Description
The cooling system on water-cooled compressors comprises air cooler (Cwa) and oil cooler
(Cwo).
They are connected to a cooling water circuit. The water flows through the inlet pipe, the coolers
and the outlet pipe.
20 2920 7109 51
Instruction book
Drain connections
The compressors have an centrifugal water separator WSD25 (1). The condensate formed in the
air cooler accumulates in the collector. When the condensate reaches a certain level, it is
discharged through the automatic drain outlet (Da). Also, the condensate water can be
discharged manually through the manual drain outlet (Dm).
On Full-Feature compressors, an additional centrifugal water drain WSD25 (2) is provided. The
condensate trap of the heat exchanger is drained by WSD25 and discharged through automatic
drain outlet (Da1). Also, the condensate water can be discharged manually through the manual
drain outlet (Dm1).
2920 7109 51 21
Instruction book
Reference Designation
Da Automatic drain connection
Dm Manual drain connection
Da1 Automatic drain connection of the dryer (only on Full-Feature units)
Dm1 Manual drain connection of the dryer (only on Full-Feature units)
22 2920 7109 51
Instruction book
Loading
When the net pressure is below the loading pressure, solenoid valve (Y1) is energised. Results:
• The space above unloading valve/blow-off valve (UV) is connected with the oil separator
tank pressure (1) via the solenoid valve.
• Unloading valve/blow-off valve (UV) moves downwards, closing off the connection to
channels (2) and (3).
• Underpressure from the compressor element causes loading plunger (LP) to move
downwards and inlet valve (IV) to open fully.
Air delivery is 100%, the compressor runs loaded.
Unloading
If the air consumption is less than the air output of the compressor, the net pressure increases.
When the net pressure reaches the unloading pressure, solenoid valve (Y1) is de-energised.
Results:
• The pressure above unloading valve/blow-off valve (UV) is released to atmosphere and the
space above valve (UV) is no longer in connection with the oil separator tank pressure (1).
• Unloading valve/blow-off valve (UV) moves upwards, connecting the oil separator tank
pressure (1) with channels (2) and (3).
• The pressure in channel (2) causes the loading plunger (LP) to move upwards, causing inlet
valve (IV) to close, while the pressure is gradually released to atmosphere.
• The pressure in the separator tank stabilises at low value. A small amount of air is kept
drawn in to guarantee a minimal pressure, required for lubrication during unloaded
operation.
Air output is stopped, the compressor runs unloaded.
Electrical components
The electrical system comprises following components:
2920 7109 51 23
Instruction book
Reference Designation
F1/2/3 Fuses
F7/F8/F9 Fuses (only on Full-Feature)
F21 Overload relay, compressor motor
Q15 Circuit breaker, fan motor (on air-cooled compressors)
K5 Auxiliary relay
K11 Auxiliary contactor
K12 Auxiliary contactor
K15 Auxiliary contactor, fan motor (on air-cooled compressors)
K21 Line contactor
K22 Star contactor
K23 Delta contactor
T1 Transformer
PE Earth terminal
Electrical diagram
The complete electrical diagram can be found in the electric cubicle.
24 2920 7109 51
Instruction book
Flow diagram
Air dryer
Reference Name
AI Air inlet
AO Air outlet
1 Air/air heat exchanger
2 Air/refrigerant heat exchanger/evaporator
3 Condensate separator
4 Automatic drain / condensate outlet
5 Refrigerant compressor
6 Refrigerant condenser
7 Liquid refrigerant dryer/filter
8 Capillary
9 Bypass valve
10 Condenser cooling fan
11 Pressure switch, fan control
12 Liquid separator
2920 7109 51 25
Instruction book
Refrigerant circuit
Compressor (5) delivers hot, high-pressure refrigerant gas which flows through condenser (6)
where most of the refrigerant condenses.
The liquid refrigerant flows through liquid refrigerant dryer/filter (7) to capillary tube (8). The
refrigerant leaves the capillary tube at about evaporating pressure.
The refrigerant enters evaporator (2) where it withdraws heat from the compressed air by further
evaporation at about constant pressure. The heated refrigerant leaves the evaporator and is
sucked in by the compressor (5) through a liquid separator (12).
Bypass valve (9) regulates the refrigerant flow. Fan (10) is switched on or off by switch (11)
depending on the pressure degree of the condensate.
26 2920 7109 51
Instruction book
3.1 Controller
Introduction
The controller has following functions:
• Controlling the unit
• Protecting the unit
• Monitoring components subject to service
• Automatic restart after voltage failure (ARAVF)
A number of time based automatic start/stop commands may be programmed. Take into
account that a start command will be executed (if programmed and activated), even after
manually stopping the unit.
2920 7109 51 27
Instruction book
Shutdown warning
A shutdown warning level is a programmable level below the shutdown level.
If one of the measurements exceeds the programmed shutdown warning level, a message will
appear on the display and the general alarm LED will light up to warn the operator before the
shutdown level is reached.
The message disappears as soon as the warning condition disappears or after a manual warning
reset on the display.
A warning will also appear if the dew point temperature is too high in relation to the ambient
temperature (on units with integrated dryer).
When the shutdown warning is shown, press stop button to stop the unit and wait until the unit
has stopped. Switch off the voltage, inspect the unit and remedy if necessary. The warning
message will disappear as soon as the warning condition disappears.
Service warning
The service timer has a programmed time interval. If the service timer exceeds the programmed
value, this will be indicated on the display to warn the operator to carry out the service actions.
When the service warning is shown, stop the unit, switch off the voltage and carry out the
required service actions. See section Preventive Maintenance.
If the function is activated and provided the controller was in the automatic operation
mode, the unit will automatically restart if the supply voltage to the module is restored.
The ARAVF label (see section Pictographs) shall be glued near to the controller.
28 2920 7109 51
Instruction book
Control panel
2920 7109 51 29
Instruction book
Menu icons
Menu Icon
Main screen
Machine Settings
Data
Service
Controller Settings
Information
Status icons
Icon Description
Motor Stopped
Running Unloaded
Manual Unload
Running Loaded
30 2920 7109 51
Instruction book
System icons
Icon Description
Basic User
Advanced User
Service User
Reset
This chapter gives a general survey of available icons. Not all icons mentioned in this
chapter are applicable to every machine.
3.4 Menu
Procedure
Starting from the main screen, use the left vertical swipe bar to navigate through the menu items.
Use the horizontal swipe bar to navigate through the different screens of a menu item.
The page indicator
shows how many screens there are available for the current menu item, depending on the user
access level.
2920 7109 51 31
Instruction book
Menu structure
32 2920 7109 51
Instruction book
This is the main menu structure. The structure can be different depending on the configuration of
the unit.
Select
In these examples, the upper value is selected.
To select the lower value, swipe down on the left vertical swipebar.
Modify
To modify the selected value, tap the right vertical swipebar.
Function
The Main screen is the screen that is shown automatically when the voltage is switched on. It is
switched off automatically after a few minutes when there is no touch input.
Swipe left to navigate to the following screens:
• Predefined IO or counter data (optional)
• Setpoint used (optional)
• Manual unload (optional)
• Status
2920 7109 51 33
Instruction book
Description
Parameters
Starting from the main screen, swipe left to scroll through predefined IO or counter data.
(optional)
34 2920 7109 51
Instruction book
Example
Setpoint used
Starting from the main screen, swipe left until the Setpoint used screen is shown.
To switch to a different setpoint, swipe up or down on the left vertical swipebar or tap next to the
corresponding square.
Manual unload
Starting from the main screen, swipe left until the Manual unload screen is shown.
Manual unload can only be activated when the machine is in LOAD and Local control.
To manually unload the unit, tap on the left vertical swipebar.
Status
Starting from the main screen, swipe left until the Status screen is shown.
2920 7109 51 35
Instruction book
To reset the alarm, press the confirm button under the reset icon.
To cancel without resetting, press the cancel button under the red ‘X’ icon.
3.6 Shutdown
Description
The unit will be shut down in following circumstances:
• In case the temperature at the outlet of the element exceeds the programmed shutdown
level (detected by temperature sensor (TT11) or by temperature switch (TSHH11)).
• In case of too high air/oil temperature (detected by additional temperature switch
(TSHH21)).
• In case of overload of the motor (M1) or the fan motor (M2).
• In case of error of the outlet pressure sensor (PT20).
• In case of incorrect phase sequence, detected by phase sequence relay (K25).
Swipe left (8) until the actual element outlet temperature appears.
36 2920 7109 51
Instruction book
The above screen shows that the temperature at the outlet of the element is 117 ˚C. Actions:
• Switch off the voltage and remedy the problem cause.
• After remedying and when the shutdown condition has disappeared, switch on the voltage
and restart the unit.
Actions:
• Switch off the voltage and remedy the problem cause.
• In case of incorrect phase sequence, reverse two phases of the supply cable.
• If the additional temperature switch (TSHH21) has tripped, you must contact the Atlas
Copco customer center.
2920 7109 51 37
Instruction book
• After remedying and when the shutdown condition has disappeared, switch on the voltage
and restart the unit. The shutdown message will disappear automatically when the shutdown
condition has disappeared.
Function
The Machine Settings menu provides the ability to view and modify several machine settings.
Swipe left to navigate to the following screens:
• Setpoint 1 (optional)
• Setpoint 2 (optional)
• Regulation
• Control Mode
• Auto Restart
Procedure
To view the Machine Settings menu:
1. Tap the Home button
Setpoint 1
Starting from the Machine Settings menu, swipe left until the Setpoint 1 screen is shown.
To select a load and unload setpoint, or to modify the values, see section Select or modify a
setting.
38 2920 7109 51
Instruction book
Setpoint 2
Starting from the Machine Settings menu, swipe left until the Setpoint 2 screen is shown.
To select a load and unload setpoint, or to modify the values, see section Select or modify a
setting.
Regulation
Starting from the Machine Settings menu, swipe left until the Regulation screen is shown.
To select a menu item, or to change the setting, see section Select or modify a setting.
Control Mode
Starting from the Machine Settings menu, swipe left until the Control Mode screen is shown.
Auto Restart
Starting from the Machine Settings menu, swipe left until the Auto Restart screen is shown.
The controller has a built-in function to automatically restart the compressor when voltage is
restored after voltage failure. This function is deactivated in compressors leaving the factory and
2920 7109 51 39
Instruction book
can only be modified after entering a password, please consult your supplier to activate this
function.
To select a menu item, or to change the setting, see section Select or modify a setting.
Function
The Aux. Equipment parameters menu provides the ability to view and modify several settings
related to the auxiliary equipment of the unit.
Swipe left to navigate to the following screens:
• Dryer (optional)
• Fan (optional)
• Phase sequence detection (optional)
• Internal or External SmartBox
Procedure
To view the Aux. Equipment parameters menu:
1. Tap the Home button
Dryer
Starting from the Aux. Equipment parameters menu, swipe left until the Dryer screen is shown.
To select a menu item, or to change the setting, see section Select or modify a setting.
40 2920 7109 51
Instruction book
SmartBox
Starting from the Aux. Equipment parameters menu, swipe left until the Internal SmartBox screen
is shown.
To select a menu item, or to change the setting, see section Select or modify a setting.
Function
The Data menu provides the ability to view several important values.
Swipe left to navigate to the following screens:
• Counters
• Inputs
• Outputs
Procedure
To view the Data menu:
1. Tap the Home button
Counters
Starting from the Data menu, swipe left until the Counters screen is shown.
2920 7109 51 41
Instruction book
Select
To select a different item, swipe up or down on the left vertical swipebar.
Inputs
Starting from the Data menu, swipe left until the Inputs screen is shown.
Select
To select a different item, swipe up or down on the left vertical swipebar.
Outputs
Starting from the Data menu, swipe left until the Outputs screen is shown.
Select
To select a different item, swipe up or down on the left vertical swipebar.
Function
The Service menu provides the ability to reset the service timer. This menu is only available as
Service user.
Swipe left to navigate to the following screens:
• Next service
42 2920 7109 51
Instruction book
Procedure
To view the Service menu:
1. Use the controller as a Service user
.
See Controller settings menu to change the user profile.
2. Tap the Home button
Next Service
Starting from the Service menu, swipe left until the Next Service screen is shown.
The Next Service will be triggered after the Running Hours value exceeds the Next Service value.
Reset
Tap the right vertical swipebar, the following screen is now shown:
To cancel without resetting, press the cancel button under the red ‘X’ icon.
To reset the alarm, press the confirm button under the reset icon. The following screen is now
shown:
2920 7109 51 43
Instruction book
Function
The Controller Settings menu provides the ability to view and modify several settings of the
controller.
Swipe left to navigate to the following screens:
• Access Level
• Language
• Units
• CAN Settings
• Ethernet Settings
• Display Timeout
Procedure
To view the Controller Settings menu:
1. Tap the Home button
Access Level
Starting from the Controller Settings menu, swipe left until the Access Level screen is shown.
Enter a password
44 2920 7109 51
Instruction book
The Service user profile is protected by a password. After selecting the Service user profile, the
following screen pops up:
The user can enter the password by swiping up or down on the right vertical swipebar to select
the first digit.
Tap ‘→’ to be able to enter the second digit.
Once the 4 digits are entered, the user can confirm by tapping ‘V’ or decline by tapping ‘X’.
Language
Starting from the Controller Settings menu, swipe left until the Language screen is shown.
Units
The units displayed can be modified through this menu.
CAN Settings
The list of CAN Settings is shown. When CAN is turned off, the settings can be modified.
Ethernet Settings
The list of Ethernet Settings is shown. When ethernet is turned off, IP address, Subnet mask and
Gateway can be modified.
Do not forget to turn on ethernet settings after changing these settings. Otherwise the
controller can’t connect anymore!
Display Timeout
Starting from the Controller Settings menu, swipe left until the Display Timeout screen is shown.
Display timeout is used to save energy and save the lifetime of the display. Timer starts after last
operator actions on the push buttons or swipe bars.
2920 7109 51 45
Instruction book
Function
The Information menu provides the ability to view important information.
Swipe left to navigate to the following screens:
• Help
• Information
Procedure
To view the Information menu:
1. Tap the Home button
Help
Starting from the Information menu, swipe left until the Help screen is shown.
The manufacturer’s website is shown.
Info
Starting from the Information menu, swipe left until the Info screen is shown.
Following items are displayed:
• Mac Address
• Application Description
• Application Software: nr + version
• Operation: nr + version
• BOOT Software: nr
46 2920 7109 51
Instruction book
Getting started
Make sure you are logged in as administrator.
• Use the internal network card from your computer or a USB to LAN adapter.
• Use a UTP cable (CAT 5e) to connect to the controller (see picture below).
2920 7109 51 47
Instruction book
• Use the check box Internet Protocol version +4 (TCP/IPv4) (1) (see picture). To avoid
conflicts, uncheck other properties if they are checked. After selecting TCP/IPv4, click on the
Properties button (2) to change the settings.
48 2920 7109 51
Instruction book
• That IP address will be excluded from the DNS server, so it will be reserved for the
controller.
• Also get the correct Gateway and Subnet mask settings. For example:
• IP = 10.25.43.200
• Gateway = 10.25.42.250
• Subnet mask = 255.255.254.0
• Connect the controller to the company's network (LAN) by using a UTP cable (min. CAT 5e).
• Adapt IP Address
• Adapt Gateway IP
• Adapt Subnetmask
• Switch on the Ethernet communication
• Wait a few minutes so the controller can be connected to the LAN network
All screen shots are indicative. The number of displayed fields depends on the selected
options.
2920 7109 51 49
Instruction book
• Open your browser and type the IP address of the controller you want to view in your
browser (in this example http://192.168.100.100). The interface opens:
• On the left side of the interface, you can find the navigation menu.
If a license for ESi is foreseen, the menu contains 3 buttons.
• Machine: shows all generator settings.
• ES: shows the ESi status (if a license is provided).
• Preferences: allows to change temperature and pressure unit.
50 2920 7109 51
Instruction book
Unit settings
All unit settings can be displayed or hidden. Put a check mark in front of each point of interest
and it will be displayed. Only the machine status is fixed and can not be removed from the main
screen.
Analog inputs
Lists all current analog input values. The measurement units can be changed in the preference
button from the navigation menu.
Counters
Lists all current counter values from controller and unit.
Info status
Machine status is always shown on the web interface.
Digital inputs
Lists all digital inputs and their status.
Digital outputs
Lists all digital outputs and their status.
2920 7109 51 51
Instruction book
Special protections
Lists all special protections of the unit.
Service plan
Displays all levels of the service plan and their status. This screen shot underneath only shows
the running hours. It is also possible to show the current status of the service interval.
52 2920 7109 51
Instruction book
2920 7109 51 53
Instruction book
Parameters
54 2920 7109 51
Instruction book
Protections
Service plan
The built-in service timer will give a Service warning message after a pre-programmed time
interval has elapsed.
Also see section Preventive maintenance schedule.
Consult Atlas Copco if a timer setting has to be changed. See section Calling up/modifying
service timer settings. The intervals must not exceed the nominal intervals and must coincide
logically.
Terminology
Term Explanation
ARAVF Automatic restart after voltage failure. See section Elektronikon regulator and Activating
automatic restart.
Restart delay This parameter allows to programme that not all compressors are restarted at the same
time after a power failure (ARAVF active).
Compressor The regulator does not accept inconsistent settings, e.g. if the warning level is
element outlet programmed at 95 ˚C (203 ˚F), the minimum limit for the shutdown level changes to 96
˚C (204 ˚F). The recommended difference between the warning level and shutdown
level is 10 ˚C (18 ˚F).
Delay at Is the time for which the signal must exist before the compressor is shut down. If it is
shutdown signal required to program this setting to another value, consult Atlas Copco.
Minimum stop Once the compressor has automatically stopped, it will remain stopped for the minimum
time stop time, whatever happens with the net air pressure. Consult Atlas Copco if a setting
lower than 20 seconds is required.
Unloading/ The regulator does not accept illogical settings, e.g. if the unloading pressure is
Loading pressure programmed at 7.0 bar(e) (101 psi(g)), the maximum limit for the loading pressure
changes to 6.9 bar(e) (100 psi(g)). The recommended minimum pressure difference
between loading and unloading is 0.6 bar (9 psi(g)).
2920 7109 51 55
Instruction book
4.1 Controller
Introduction
The controller has following functions:
• Controlling the unit
• Protecting the unit
• Monitoring components subject to service
• Automatic restart after voltage failure (ARAVF)
A number of time based automatic start/stop commands may be programmed. Take into
account that a start command will be executed (if programmed and activated), even after
manually stopping the unit.
56 2920 7109 51
Instruction book
Shutdown warning
A shutdown warning level is a programmable level below the shutdown level.
If one of the measurements exceeds the programmed shutdown warning level, a message will
appear on the display and the general alarm LED will light up to warn the operator before the
shutdown level is reached.
The message disappears as soon as the warning condition disappears.
A warning will also appear if the dew point temperature is too high (on units with integrated
dryer).
When the shutdown warning is shown, press stop button to stop the unit and wait until the unit
has stopped. Switch off the voltage, inspect the unit and remedy if necessary. The warning
message will disappear as soon as the warning condition disappears.
Service warning
A number of service operations are grouped as a Service Plan. Each Service Plan has a
programmed time interval. If the service timer exceeds a programmed value, this will be indicated
on the display to warn the operator to carry out the service actions belonging to that Service Plan.
When the service warning is shown, stop the unit, switch off the voltage and carry out the
required service actions. See section Preventive Maintenance.
If the function is activated and provided the regulator was in the automatic operation
mode, the unit will automatically restart if the supply voltage to the module is restored.
The ARAVF label (see section Pictographs) shall be glued near to the controller.
2920 7109 51 57
Instruction book
Control panel
58 2920 7109 51
Instruction book
Menu icons
Inputs
Outputs
Counters
Service Plan
Service History
Service
functions
Clean Screen
Remaining
Running Time
2920 7109 51 59
Instruction book
Regulation
Control
Parameters
Fan
Internal
SmartBox
Auto Restart
CAN Settings
Localisation Language
Date/Time
Units
User Password
Help
Information
Status icons
Icon Description
Motor Stopped
60 2920 7109 51
Instruction book
Running Unloaded
Manual Unload
Running Loaded
Failed to Load
Manual Stop
System icons
Icon Description
Basic User
Advanced User
Service User
Antenna 25%
2920 7109 51 61
Instruction book
Antenna 50%
Antenna 75%
Antenna 100%
Energy recovery
Dryer
Element
Drain(s)
Analogue Output
Menu
Reset
Auto Restart
Filter(s)
Cooler
Valve(s)
Power Meter
Input icons
Icon Description
Pressure
62 2920 7109 51
Instruction book
Temperature
Special Protection
Open
Closed
This chapter gives a general survey of available icons. Not all icons mentioned in this
chapter are applicable to every machine.
Function
The Main screen is the screen that is shown automatically when the voltage is switched on. It is
switched off automatically after a few minutes when there is no touch input.
Description
2920 7109 51 63
Instruction book
Function
The screen is used to directly access some frequently used functions.
Procedure
The Quick access screen can be viewed by swiping left, starting from the main screen.
Description
Through this screen, several important settings can be viewed and modified.
64 2920 7109 51
Instruction book
Function Description
Setpoints Several setpoints can be modified by tapping this icon.
Control mode The control mode can be changed by tapping this icon.
• Local control via start/stop buttons
• Remote control via digital input(s)
• LAN control via the network.
When in Remote or LAN control, the start/stop buttons on the controller will not work.
Display language The display language of the controller can be changed by tapping this icon.
Manual unload (only When tapped, the machine will go in Manual unload mode until the icon is tapped
on fixed speed units) again.
Week timer Week timers can be set by tapping this icon.
Remaining running The Remaining running time can be set and modified by tapping this icon.
time
Internal SmartBox The reception quality of the internal antenna can be monitored.
Each bar represents 25% reception strength. If the four bars are filled, the reception
strength is 100%. If only one bar is filled, the reception strength is just 25%.
Auto restart Auto restart can be activated by tapping this icon.
Tap on the select warning icon (4) to see the Status menu.
In case of element outlet temperature warning, the display will appear as below:
2920 7109 51 65
Instruction book
It remains possible to scroll through other screens, to check the actual status of other
parameters. Press stop key (7) to stop the unit and wait until the unit has stopped. Switch off the
voltage, inspect the unit and remedy. The warning message will disappear as soon the warning
condition disappears.
4.7 Shutdown
Description
The unit will be shut down in following circumstances:
• In case the temperature at the outlet of the element exceeds the programmed shutdown
level (detected by temperature sensor (TT11) or by temperature switch (TSHH11)).
• In case of too high air/oil temperature (detected by additional temperature switch
(TSHH21)).
• In case of overload of the motor (M1) or the fan motor (M2).
• In case of error of the outlet pressure sensor (PT20).
• In case of incorrect phase sequence, detected by phase sequence relay (K25).
66 2920 7109 51
Instruction book
The above screen shows that the temperature at the outlet of the element is 116 ˚C. Actions:
• Switch off the voltage and remedy the problem cause.
• After remedying and when the shutdown condition has disappeared, switch on the voltage
and restart the unit.
2920 7109 51 67
Instruction book
Actions:
• Switch off the voltage and remedy the problem cause.
• In case of incorrect phase sequence, reverse two phases of the supply cable.
• If the additional temperature switch (TSHH21) has tripped, you must contact the Atlas
Copco customer center.
• After remedying and when the shutdown condition has disappeared, switch on the voltage
and restart the unit. The shutdown message will disappear automatically when the shutdown
condition has disappeared.
Function
This screen is used to display the different menus where settings can be viewed or changed.
Procedure
The Menu screen can be viewed by tapping the Menu button or by swiping right, starting from the
main screen.
68 2920 7109 51
Instruction book
Description
Menu structure
Operating the controller can be done by swiping through screens and tapping icons or menu
items.
2920 7109 51 69
Instruction book
This is the main menu structure. The structure can be different depending on the configuration of
the unit.
Function
This screen is used to display the following submenus:
• Status
• Inputs
• Outputs
• Counters
• Aux. Equipment
These submenus can be entered by tapping the icons.
Procedure
To enter the Data menu screen:
1. Tap the Menu button
2. Tap the Data icon
70 2920 7109 51
Instruction book
Description
Reference Designation
(1) Status menu
(2) Inputs menu
(3) Outputs menu
(4) Counters menu
(5) Auxiliary equipment menu
Status menu
Tap the Status icon to enter the Status menu.
Inputs menu
Tap the Inputs icon to enter the Inputs menu.
2920 7109 51 71
Instruction book
Outputs menu
Tap the Outputs icon to enter the Outputs menu.
Counters menu
Tap the Counters icon to enter the Counters menu.
This menu shows an overview of all actual hours and counters of the unit and controller.
72 2920 7109 51
Instruction book
Function
This screen is used to display the following submenus:
• Service
• Service functions (Only visible as advanced user)
• Clean screen
These submenus can be entered by tapping the icons.
Procedure
To enter the Service menu screen:
1. Tap the Menu button
2. Tap the Service icon
Description
Reference Designation
(1) Service
(2) Service functions (Only visible as advanced user)
(3) Clean screen
Service menu
Tap the Service icon to enter the Service menu.
2920 7109 51 73
Instruction book
This menu shows the remaining Running Hours and the remaining Real Time Hours until the next
service. The first row (A) shows the Running Hours when the first service is needed (green), the
second row shows the Real Time Hours (blue)
A service overview can be viewed by tapping icon (1).
The service plan can be viewed by tapping icon (2). Through this menu, the service plan can be
modified:
1. Tap the desired service plan. A selection screen will pop up.
2. Change the Running Hours by tapping ‘–’ or ‘+’.
3. Confirm by tapping ‘V’ or decline by tapping ‘X’.
The service history can be viewed by tapping icon (3).
When a service plan interval is reached, a message will appear on the screen. When service has
been performed, the service timer can be reset by tapping the reset button (4).
Depending on the machine, this menu can have a different set of functions. Many of them are
password protected, as they are only accessible for authorized personnel.
Clean screen
Tap the Clean Screen icon to start the 15 seconds countdown to perform cleaning of the
touchscreen.
74 2920 7109 51
Instruction book
The touchscreen and the start and stop button become inactive for 15 seconds.
Function
This screen is used to set up to 4 different week timers with each up to 8 settings per day.
The week timers can be activated through this screen.
A Remaining Running Time can be set from 5 up to 240 minutes.
Procedure
To enter the Week Timer menu screen:
1. Tap the Menu button
2. Tap the Week Timer icon
Description
Function
This screen is used to display the saved data in case of an alarm.
These submenus can be entered by tapping the icons.
2920 7109 51 75
Instruction book
Procedure
To enter the Event history menu screen:
1. Tap the Menu button
2. Tap the Event History icon
Description
Reference Designation
(1) Saved Data
Saved data
Tap the Saved Data icon to enter the Saved Data menu.
Scroll through the items swiping up and down in this list. The event date and time is shown at the
right side of the screen.
Press on one of the items in the list for more information reflecting the status of the unit when the
shutdown occurred.
Function
This screen is used to display the following submenus:
• Alarms
• Regulation
• Control Parameters
Only visible if the machine has adaptable parameters.
• Aux. Equipment parameters
• Auto Restart
These submenus can be entered by tapping the icons.
76 2920 7109 51
Instruction book
Procedure
To enter the Machine settings menu screen:
1. Tap the Menu button
2. Tap the Machine Settings icon
Description
Reference Designation
(1) Alarms menu
(2) Regulation menu
(3) Control Parameters menu
(4) Aux. Equipment Parameters menu
(5) Auto Restart menu
Alarms menu
Tap the Alarms icon to enter the Alarms menu.
Regulation menu
Tap the Regulation icon to enter the Regulation menu.
2920 7109 51 77
Instruction book
78 2920 7109 51
Instruction book
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Through this menu, the automatic restart can be activated. The activation is password protected.
The automatic restart settings can also be changed.
Enter a password
When tapping a password protected item, a selection screen pops up. The user can enter the
password by swiping up or down to select the desired number. Once the 4 digits are entered, the
user can confirm by tapping ‘V’ or decline by tapping ‘X’.
Modify a setting
When clicking a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Function
This screen is used to display the following submenus:
• Network Settings
• Localisation
• User Password
• Help
• Information
These submenus can be entered by tapping the icons.
Procedure
To enter the Controller Settings menu screen:
1. Tap the Menu button
2. Tap the Controller Settings icon
2920 7109 51 79
Instruction book
Description
Reference Designation
(1) Network Settings menu
(2) Localisation menu
(3) User Password menu
(4) Help menu
(5) Information menu
Ethernet Settings
The list of Ethernet Settings is shown. When ethernet is turned off, the settings can be modified.
CAN Settings
The list of CAN Settings is shown. When CAN is turned off, the settings can be modified.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.
Localisation menu
Tap the Localisation icon to enter the Localisation menu.
80 2920 7109 51
Instruction book
Language
The language setting of the controller can be modified through this menu.
Date/Time
The date and time settings of the controller can be modified through this menu.
Units
The units displayed can be modified through this menu.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.
The user password can be activated or deactivated through this menu. Enter and confirm a user
password to activate, repeat to deactivate.
Enter a password
When tapping a password protected item, a selection screen pops up. The user can enter the
password by swiping up or down to select the desired number. Once the 4 digits are entered, the
user can confirm by tapping ‘V’ or decline by tapping ‘X’.
Help menu
Tap the Help icon to enter the Help menu.
2920 7109 51 81
Instruction book
This menu can show a link to the web page of your supplier, a helpdesk phone number or other
helpful information.
Information menu
Tap the Information icon to enter the Information menu.
Function
Through this pop-up screen the access level settings can be viewed or changed.
Procedure
The Access Level screen can be viewed or changed by tapping the Access Level button at the
upper right corner of the screen.
Description
82 2920 7109 51
Instruction book
Tap the Service access level icon (1) and confirm (2).
The screen information bar (1) now shows the current status of the unit instead of the machine
serial number.
The Received Signal Strength Indicator (RSSI) value is now shown in the Internal SmartBox
menu. See Quick access screen.
In the service menu, an extra menu item is now available. See Service menu.
Getting started
Make sure you are logged in as administrator.
• Use the internal network card from your computer or a USB to LAN adapter.
• Use a UTP cable (CAT 5e) to connect to the controller (see picture below).
2920 7109 51 83
Instruction book
84 2920 7109 51
Instruction book
• Use the check box Internet Protocol version +4 (TCP/IPv4) (1) (see picture). To avoid
conflicts, uncheck other properties if they are checked. After selecting TCP/IPv4, click on the
Properties button (2) to change the settings.
2920 7109 51 85
Instruction book
• Adapt IP Address
• Adapt Gateway IP
• Adapt Subnetmask
• Switch on the Ethernet communication
• Wait a few minutes so the controller can be connected to the LAN network
All screen shots are indicative. The number of displayed fields depends on the selected
options.
86 2920 7109 51
Instruction book
• Open your browser and type the IP address of the controller you want to view in your
browser (in this example http://192.168.100.100). The interface opens:
• On the left side of the interface, you can find the navigation menu.
If a license for ESi is foreseen, the menu contains 3 buttons.
• Machine: shows all generator settings.
• ES: shows the ESi status (if a license is provided).
• Preferences: allows to change temperature and pressure unit.
2920 7109 51 87
Instruction book
Unit settings
All unit settings can be displayed or hidden. Put a check mark in front of each point of interest
and it will be displayed. Only the machine status is fixed and can not be removed from the main
screen.
Analog inputs
Lists all current analog input values. The measurement units can be changed in the preference
button from the navigation menu.
Counters
Lists all current counter values from controller and unit.
Info status
Machine status is always shown on the web interface.
Digital inputs
Lists all digital inputs and their status.
Digital outputs
Lists all digital outputs and their status.
88 2920 7109 51
Instruction book
Special protections
Lists all special protections of the unit.
Service plan
Displays all levels of the service plan and their status. This screen shot underneath only shows
the running hours. It is also possible to show the current status of the service interval.
Parameters
2920 7109 51 89
Instruction book
Service plan
The built-in service timers will give a Service warning message after their respective pre-
programmed time interval has elapsed.
Also see section .
Consult Atlas Copco if a timer setting has to be changed. The intervals must not exceed the
nominal intervals and must coincide logically. See section Modifying general settings.
Terminology
Term Explanation
ARAVF Automatic Restart After Voltage Failure. See section Elektronikon regulator and
Modifying general settings.
Power recovery Is the period within which the voltage must be restored to have an automatic restart. Is
time accessible if the automatic restart is activated. To activate the automatic restart function,
consult Atlas Copco.
Restart delay This parameter allows to programme that not all compressors are restarted at the same
time after a power failure (ARAVF active).
Compressor The recommended minimum setting is 70 ˚C (158 ˚F). For testing the temperature
element outlet sensor the setting can be decreased to 50 ˚C (122 ˚F). Reset the value after testing.
The regulator does not accept illogical settings, e.g. if the warning level is programmed
at 95 ˚C (203 ˚F), the minimum limit for the shutdown level changes to 96 ˚C (204 ˚F).
The recommended difference between the warning level and shutdown level is 10 ˚C
(18 ˚F).
Delay at Is the time for which the signal must exist before the compressor is shut down. If it is
shutdown signal required to program this setting to another value, consult Atlas Copco.
Oil separator Use only Atlas Copco oil separators. The recommended maximum pressure drop over
the oil separator element is 1 bar (15 psi).
Minimum stop Once the compressor has automatically stopped, it will remain stopped for the minimum
time stop time, whatever happens with the net air pressure. Consult Atlas Copco if a setting
lower than 20 seconds is required.
Unloading/ The regulator does not accept inconsistent settings, e.g. if the unloading pressure is
Loading pressure programmed at 7.0 bar(e) (101 psi(g)), the maximum limit for the loading pressure
changes to 6.9 bar(e) (100 psi(g)). The recommended minimum pressure difference
between loading and unloading is 0.6 bar (9 psi(g)).
90 2920 7109 51
Instruction book
5 OSCi (optional)
5.1 Introduction
Compressed air produced by oil-injected compressors contains a small quantity of oil. During the
cooling of the air in the aftercooler and in the refrigeration dryer (on compressors with built-in
refrigeration dryer), oil-containing condensate is formed.
The OSCi is a condensate treatment device, designed to separate most of this oil from the water
and to sorb it in its replaceable filters, thus preventing contamination of the environment. It is
capable to break and sorb most stable emulsions. The OSCi is insensitive to shocks and
vibrations because of the use of filters and can be used with all types of drains. The condensate
meets the requirements of the environmental codes.
The OSCi is installed inside a separate box, hinged to the compressor canopy.
2920 7109 51 91
Instruction book
5.2 Operation
General
1 Condensate inlet
2 Foam cover
3 Oleophilic filter
4 Service drains with valve
5 Air injection connection
6 OGC filter
7 Activated carbon filter
8 Condensate test outlet
9 Condensate outlet
The OSCi 3790 housing consists of 3 interconnected vessels. The oil-containing condensate is
injected (1) in discontinuous bursts at a downward angle into the first vessel which acts as
expansion chamber. The specially designed cover has a combination of pressure-relieving holes
and a foam (2). Since the pressure is relieved here, the entire OSCi device is pressureless. In the
first vessel, a floating filter (3) made of special synthetic fibres takes up most of the directly
separable hydrocarbons from the condensate. The filter sinks as it saturates with hydrocarbons
and hence the lifetime progress of the filter can be measured by an indicator that rests on the
bag. A conventional sight glass is installed for visual inspection of the filter position and the
condensate level. On top of that, an electronic position sensor (8 - View of OSCi, 1 - View of
OSCi inlet) is connected to the controller of the compressor to keep track of the filter lifetime
without the need to open the compressor canopy.
The outlet of the first vessel is situated at the bottom and is connected to the upper half of the
second vessel. In the second vessel, the pre-filtered condensate is brought in contact with a filter
92 2920 7109 51
Instruction book
bag (6), filled with oleophilic granular clay (OGC). Through a connection (5) at the bottom of the
second vessel, air is injected into the condensate. This airflow breaks stable emulsions by
enhancing the sorption process of oil onto the OGC. The air supply also prevents the formation of
certain anaerobic bacteria. Also the cover of the second vessel is equipped with ventilation holes
to prevent pressure buildup. The airflow is taken from the aftercooler (on air cooled units) or from
the water separator (WSD) (on water cooled units). An integrated nozzle with strainer limits the
airflow (approximately 450 l/h at reference conditions), while a solenoid valve makes sure no
compressed air is used when the compressor is not delivering air.
The condensate further flows to the third vessel, through a pipe connecting both lower halves of
the vessels. An activated carbon filter (7) cleans the condensate further, and the clean
condensate flows out of connection (9). A test outlet (8) is positioned below the normal outlet.
Both outlets are connected to the compressor drain plate by their corresponding tubes.
At the bottom of the vessels, drain tubes with valves (4) are provided for easy servicing.
In this setup, the cleaning process can be understood by splitting it up per vessel:
• First vessel: pre-separation and sorption of most of the free, directly separable oil
• Second vessel: emulsion separation and oil sorption
• Third vessel: sorption of the remaining oil
View of OSCi
2920 7109 51 93
Instruction book
1 Clamping ring
2 Foam cover
3 Location of sample bottles and connection material (during shipping only)
4 Service drains with valve
5 Fixation bolts
6 Wire and tube clamp
7 Overflow switch
8 Filter position sensor and visual indication of the filter position
Detail views
94 2920 7109 51
Instruction book
1 Condensate outlet
2 Condensate test outlet
Drain plate
2920 7109 51 95
Instruction book
96 2920 7109 51
Instruction book
Drain plate
5. Connect an outlet tube leading to the sewage system (19 mm inner diameter). Since the
OSCi functions at atmospheric pressure, the outlet piping must always be positioned below
the outlet connection on the OSCi vessel 3, unless a pump (able to run dry) is installed (not
provided).
6. Check that the filter in the first tower is of circular shape and that it can move freely up and
down. Pour clean water along the inner edge of the first tower until water flows out of the
outlet connection or until the water reaches the bottom of the sensor chamber (visible
through the sight-glass). The oleophilic filter (vessel 1) will start to float. Verify that the
sensor arm (8) is in the upward position and rests on the edge of the filter bag.
7. Check that there are no leaks at the connections between vessel 1, 2 and 3. If there is a
leak, proceed to Problem solving, fault 3.
8. Put the cover back on the first tower, tighten the clamping ring and close the compressor
bodywork.
• All outlet tubes outside the compressor must be positioned below the outlet drain
connection (drain plate) of the compressor, at least up to where a pump is installed.
• Outlet piping must be installed with a slight downward slope to the sewer, unless a
pump is installed.
5.4 Pictographs
2920 7109 51 97
Instruction book
Following important parameters of the OSCi can be consulted from the controller display:
• The remaining filter lifetime, expressed as a percentage compared to new filters (100%)
• The status of the overflow switch
To consult these data, please follow the steps given in the following sections.
98 2920 7109 51
Instruction book
Reference Description
(1) OSCi remaining: OSCi filters remaining lifetime
To take a look at the status of the OSCi overflow sensor, swipe down in the list.
Reference Description
(1) OSCi overflow
5.7 Warnings
Service required
This warning indicates that the remaining filter lifetime has dropped below 10%. In this case, a
service kit with new filters needs to be ordered. The service LED on the control panel of the
Elektronikon™ Touch controller will light up. To consult the warning, tap the Alarm button.
Reference Description
(1) Compressor outlet
When tapped, the screen shows the “OSCi Remaining” warning. When you tap the warning, the
screen shows the remaining lifetime and the service minimum (10%). The “10” will be blinking.
2920 7109 51 99
Instruction book
Once the filter has reached a lifetime below 10%, this warning will remain active until new filters
are inserted correctly (sensor arm in tower 1 should rest on the filter edge!). When the new filters
are installed correctly and the percentage is above 10% (normally between 90% and 100%), the
warning will disappear automatically.
Overflow warning
This is a protection alarm, indicating that the water level in the OSCi is too high. The warning
LED will light up on the control panel of the Elektronikon™ Touch controller. In this case consult
section Problem solving. If the problem is not solved in time, water can escape from the OSCi
and leak onto the compressor frame and outside of the compressor. To consult the warning, tap
the alarm button:
Reference Description
(1) Compressor outlet
Reference Description
(1) Status
(2) OSCi Overflow
When you tap the warning, the screen will show that the water level in the OSCi is too high.
By fixing the problem (see section Problem solving), this warning will disappear automatically.
5.8 Maintenance
Check the filters regularly as explained below in order to prevent untreated condensate
from entering the sewer.
Sample the condensate weekly.
• If the filters are not installed properly, oil-containing condensate can leave the OSCi.
• When new activated carbon filters are placed, the outgoing water may initially look
black (caused by carbon dust). This is not harmful.
• Each new filter is provided with a label. The correct position is marked on the label.
• Used filters can be heavy.
• See to it that no condensate comes into contact with eyes, mouth, …
• If the compressor has not been in operation during a long period, bacteria formation
could occur inside the OSCi. Depending on the amount of bacteria it is advised to
clean the OSCi before putting the compressor back into operation.
Oleophilic filter
Initially, the oleophilic filter (3 - Condensate flow scheme) will float almost completely on the
condensate and only the bottom part will act as filtration medium. By sorbing more and more oil,
the filter will sink and new filter material will be exposed to the condensate. When the top of the
filter reaches the surface of the condensate in the first vessel, the filter is saturated and needs to
be replaced. This is automatically transmitted to the Elektronikon® regulator via the level sensor
(1 - View of OSCi inlet), but the customer can also check this visually through the sight-glass.
contact with other components of the compressor. Use the cable holder on vessel 2 to fix
the redundant parts of the tubes and wires. See to it that the outlet tube and the test tube
are nowhere higher than the respective outlet connections on vessel 3 (View of OSCi outlet).
11. Pour clean water along the inner edge of vessel 1 until water flows out of the outlet tube (1-
View of OSCi outlet), or until the water reaches the bottom of the sensor chamber (visible
through the sight-glass). The oleophilic filter will start to float. Do not push the filter down.
12. Put the cover back on the vessel and tighten the clamping ring.
13. Close/reposition the compressor bodywork.
Atlas Copco has a complete range of service kits available. Service kits comprise all parts
needed for servicing components and offer the benefits of using genuine Atlas Copco parts while
keeping the maintenance budget low.
1 Oleophilic filter
2 Buckets (can be used to receive the used filters after maintenance)
3 OGC filter
4 Gloves
5 Activated carbon filter
Automatic as well as manual safety devices to prevent overflow are present. Besides the
automatic overflow switch (7-View of OSCi), which is mounted in a side-chamber on the second
vessel and gives an alarm when condensate level is too high, the customer can check for high
condensate level through the sight glass. On a case-by-case basis, it can be decided to
automatically shut down the compressor in case of an overflow alarm. When overflow occurs, the
resulting waste water must be treated as oil-containing water and must be disposed of according
to local regulations.
Description
A large part of the energy required for any compression process is transformed into heat. For oil-
injected screw compressors, the major part of the compression heat is dissipated through the oil
system. The energy recovery (ER) systems are designed to recover most of this heat by
transforming it into warm or hot water without any adverse influence on the compressor
performance. The water can be used for diverse applications.
Components
The energy recovery system is completely integrated and mainly comprises:
• Stainless steel oil/water heat exchanger
• Thermostatic by-pass valve for energy recovery heat exchanger(s) (BV2)
• Two temperature sensors for water inlet and outlet control (3 and 4)
• The necessary bolts, flexibles, etc.
• Oil drain plug.
Reference Designation
1 Water inlet pipe
2 Water outlet pipe
3 Temperature sensor, water inlet pipe
4 Temperature sensor, water outlet pipe
5 Oil drain plug
6 Oil flexible from compressor oil separator vessel to ER unit
7 Oil flexible from ER unit to oil filter housing
PRV Pressure relief valve
BV2 Location of heat exchanger by-pass valve (BV2)
HE Heat exchanger
V1 Selector valve
AR Oil separator tank
OF Oil filter housing
BV1 Location of oil cooler bypass valve (BV1)
Field installation
The main components are assembled ex-factory as a compact unit which fits inside the bodywork
of the compressor. Consult your dealer for installing and connecting the energy recovery unit.
General
The energy recovery systems can be applied as low temperature rise/high water flow systems or
as high temperature rise/low water flow systems.
6.3 Operation
Description
The compressor oil flow is controlled by two thermostatic valves (BV1 and BV2), ensuring reliable
compressor operation and optimum energy recovery.
Bypass valve (BV1) is integrated in the oil filter housing of the compressor and controls the oil
flow through the main oil cooler (Co) of the compressor. Bypass valve (BV2) controls the oil flow
through the oil/water heat exchanger (HE) of the ER unit. Both valves consist of an insert
(thermostat) mounted in a housing.
BV2 starts closing the bypass line over the heat exchanger (HE) at the lower limit of its
temperature range. At the upper limit of its temperature range, the bypass line is completely
closed and all the oil flows through the ER heat exchanger.
On compressors versions with a maximum pressure lower than 13 bar (175 psi), BV2 starts
opening at 40 ˚C (104 ˚F) and is completely open at 55 ˚C (131 ˚F).
On compressors with a maximal pressure of 13 bar (175 psi), BV2 starts opening at 60 ˚C (140
˚F) and is completely open at 75 ˚C (167 ˚F).
The housing of BV2 is provided with a special wheel (V1), allowing to control the energy recovery
system.
As can be seen on the ER label, the ER unit is integrated in the oil circuit and will recover energy
when the wheel is completely turned in clockwise.
When the wheel is turned out anticlockwise, the heat exchanger (HE) is bypassed and no energy
will be recovered.
ER label
Attention: It is only allowed to turn the wheel completely in or out. No in-between position is
allowed!
The oil cooler bypass valve (BV1) starts closing the bypass over the oil cooler (Co) at the lower
limit of its temperature range. At the upper limit of its temperature range, the bypass is completely
closed and all the oil flows through the oil cooler (Co).
BV1 must have a higher opening temperature (set point) than BV2 in order to prevent the heat
from being dissipated in the compressor oil cooler (Co) rather than in the oil/water heat
exchanger (HE) when using the compression heat as source for energy recovery.
Thermostat BV1 starts to open at 75 ˚C (167 ˚F) and is completely open at 90 ˚C (194 ˚F).
• Compressor start-up
When the compressor is started up from cold, the oil temperature will be low. Bypass valve (BV2)
shuts off the oil supply through the heat exchanger (HE) and bypass valve (BV1) shuts off the oil
supply through the oil cooler (Co) to prevent the compressor oil from being cooled. The oil flows
from the oil separator vessel (AR) through the oil filter(s) (OF) back to compressor element (E).
All energy input is used to rapidly warm up the compressor oil. No energy is recovered.
• Maximum energy recovery
As soon the oil temperature reaches the set point (opening temperature) of bypass valve (BV2),
the valve starts closing off the bypass over the heat exchanger (HE) oil line, gradually allowing
the oil to flow through the heat exchanger (HE). As the oil temperature rises to approx. 15 ˚C (27
˚F) above the set point, all the oil passes through the heat exchanger. The exchange of heat
between the compressor oil and the heat recovery water is maximum. The oil from the heat
exchanger outlet flows via oil filter (OF), oil stop valve (Vs - if present), compressor element (E)
and separator (AR) back to the inlet of heat exchanger (HE). Bypass valve (BV1) bypasses the
oil cooler (Co) as long as the oil temperature remains below its set point.
Operation principle at different loads:
• Low consumption of recovered energy
The temperature of the oil leaving heat exchanger (HE) rises. When the temperature rises
above its set point, oil cooler bypass valve (BV1) will gradually allow the oil to be cooled in
the oil cooler (Co).
• Recovery water flow too high/temperature too low
In this case, bypass valve (BV2) will open the bypass line allowing oil from heat exchanger
(HE) to be mixed with oil from separator (AR). Energy is transferred from the compressor oil
to the water, but at a relatively low temperature level.
6.4 Maintenance
Compressor oil
For references used consult section Energy recovery unit.
Oil change:
1. Check if the wheel (V1) is totally turned in clockwise (energy recovery in use).
2. Run the unit until warm. Stop the unit, switch off the isolating switch and close the air outlet
valve of the compressor.
3. Depressurize the compressor and drain the oil by opening the drain valve. Also drain the oil
from the heat exchanger by removing the drain plug on the oil piping of the ER-unit.
Reinstall the drain plug after draining.
4. Resume oil change as described in section Oil and Filter Change in this book.
Units with the energy recovery option are factory filled with 8000h oil.
The oil should be changed every 4000h because the oil temperature is higher in units with
energy recovery.
Reference conditions
See section Reference conditions and limitations.
Reading settings
In addition to other data, the following temperatures can be read on the controller display:
• The water inlet temperature of the energy recovery system
• The water outlet temperature of the energy recovery system
For water-cooled units:
• The water inlet temperature of the energy recovery system
• The water outlet temperature of the energy recovery system
• The cooling water outlet temperature of the compressor
Modifying settings
If the programmed warning settings for the water temperatures are exceeded, a warning
indication is shown on the controller:
To modify a setting, consult the relevant section in the description of the controller.
Recoverable energy
The recoverable energy can be calculated from:
RECOVERED ENERGY (kW) = 4.2 x water flow (l/s) x water temperature rise (˚C)
In the tables below, typical examples are given.
7 Installation
Description
1 Compressor
Install the compressor unit on a solid, level floor, suitable for taking its weight.
Safety
The operator must apply all relevant safety precautions, including those mentioned in this
book.
Outdoor/altitude operation
Fix speed compressors can be sold with option rain protection. With this option, this compressor
can be installed outside under a shelter, in frost free conditions. If frost might occur, the
appropriate measures should be taken to avoid damage to the machine and its ancillary
equipment. In this case, and also if operating above 1000 m (3300 ft), consult Atlas Copco.
Moving/lifting
The compressor can be moved by a lift truck using the slots in the frame. Take care not to
damage the bodywork during lifting or transport. Before lifting, reinstall the transport securing
bolts. Make sure that the forks protrude from the other side of the frame. The compressor can
also be lifted after inserting beams in the slots. Make sure that the beams cannot slide and that
they protrude from the frame equally. The chains must be held parallel to the bodywork by chain
spreaders in order not to damage the compressor. The lifting equipment must be placed in such
a way that the compressor is lifted perpendicularly. Lift gently and avoid twisting.
In case of units equipped with the Lifting Device Option, it is not allowed to lift the
compressor if the canopy parts or lifting supports are not completely installed. When the
compressor is being lifted, it is also forbidden to come under the load or to perform
maintenance activities to it.
Important remark
To preserve the protection degree of the electric cubicle and to protect its components from
dust from the environment, it is mandatory to use a proper cable gland when connecting the
supply cable to the compressor.
Reference Designation
(1) Customer’s installation
(2) Option
(3) All voltages (50 and 60 Hz)
Instructions
1. Provide an isolating switch.
2. Check that the motor cables and wires inside the electric cabinet are clamped tight to their
terminals.
3. Check the fuses and the setting of the overload relay. See section Electrical cable size.
4. Connect the power supply cables to their terminals L1, L2, L3.
5. Connect earth conductor bolt (PE).
• LAN control: The compressor is controlled via a local network. Consult Atlas Copco.
See section Electrical system to locate the connectors.
General
Cooling water needs to fulfill certain requirements in order to avoid problems of scaling,
fouling, corrosion or bacterial growth.
In open circuit cooling towers, protective measures must be taken to avoid the growth of
harmful bacteria such as legionella pneumophila when there is a risk of inhalation of the
water droplets.
No general recommendation can encompass the effects of all combinations of the various
compounds, solids and gases typically found in cooling water in interaction with different
materials. Therefore the recommendations formulated in our Cooling Water Specifications are a
general guide line for acceptable coolant quality. However, where strict limits apply, a statement
is made in the specification.
The water requirements refer to untreated water. When water is treated, some parameters will
change. Water treatments should be carried out by a specialized water treatment company,
taking the responsibility for the performance of the treated cooling water and the compatibility
with the materials in the cooling circuit. This includes not only the selection of the appropriate
additives, but also the correct application, monitoring of concentrations and properties, prevention
of sludge formation and maintenance of the system. This applies also to treatment with antifreeze
products. They must be provided with suitable stabilizers and inhibitors. Specifications are also
depending on the type of cooling circuit (open, once through / recirculating with tower / closed)
and on the application (Standard – max 65 °C cooling water temperature at the outlet) or Energy
Recovery (water temperature up to 95 °C).
In case water is not in line with recommended values or if any doubt, consult the manufacturer.
pH
Type of cooling system Materials Standard Energy recovery
Single pass Containing copper 6.8 - 9.3 6.8 - 9.3
Stainless steel with carbon 6.8 - 9.3 6.8 - 9.3
steel and / or cast iron
Stainless steel only 6 - 9.3 6 - 9.3
Recirculating (with tower) Containing copper 6.8 - 9.3 not applicable
Stainless steel with carbon 6.8 - 9.3
steel and / or cast iron
Stainless steel only 6 - 9.3
Closed loop Containing copper 7.5 - 9.3 7.5 - 9.3
Stainless steel with carbon 7.5 - 9.3 7.5 - 9.3
steel and / or cast iron
Stainless steel only 6 - 9.3 6 - 9.3
Ca (ppm Ca CO3)
Type of cooling system Standard Energy recovery
Single pass < 500 <2
Recirculating (with tower) < 500 not applicable
Closed loop < 1000 < 50
As a general rule, the RSI index should be between 5.6 and 7.5. If that is not the case,
contact a specialist.
RSI < 5.5 5.6 < RSI < 6.2 6.3 < RSI < 6.8 6.9 < RSI < 7.5 7.6 < RSI
Cl- (ppm) 200 350 500 350 200
Sulphate (ppm)
Type of cooling system Standard Energy recovery
Single pass < 1000 < 200
Recirculating (with tower) < 1000 not applicable
Closed loop < 400 < 200
Copper (ppm)
Type of cooling system Standard Energy recovery
Single pass <1 < 0.2
Recirculating (with tower) <1 not applicable
Closed loop <1 < 0.2
10. Ammonium
The limit of 0.5 ppm is a rejection limit.
The limitation only applies for copper containing systems.
11. Suspended solids
Large particles (size > 10 µm) should not be present as they can be filtered out.
Small particles (< 0.5 µm) are not taken into account.
For particles between 0.5 µm and 10 µm, the following limits apply:
Biology (CFU/ml)
Type of cooling system Standard Energy recovery
Single pass < 105 / < 107 < 103 / < 105
Recirculating (with tower) < 105 / < 107 not applicable
Closed loop < 103 / < 105 < 103 / < 105
The table shows the recommended values. The values in bold are rejection limits.
If additives are used in the cooling water, take into account that the cooling capacity will
change.
Δm = ((Cpw - Cpa) * X) / (Cpw *(1-X) + X*Cpa) * 100 %
with
Δm: change of mass flow of the coolant
Cpw: specific heat capacity of water
Cpa: specific heat capacity of the additives
X: the percentage of additives
7.5 Pictographs
Description
Pictographs
1 2
3 4
5 6
7 8
9 10
11 12
15 16
17
Reference Designation
1 Warning: Always read the manual, switch off the voltage, depressurise compressor and
lock out/ tag out before repairing.
2 Keep the doors closed during operation
3 Switch off the voltage before removing protecting cover inside electric cubicle
4 Warning, voltage
5 Automatic condensate drain
6 Stop the compressor before cleaning the coolers
7 Lightly oil the gasket of the oil filter, screw it on and tighten by hand (approx. half a turn)
8 Before connecting the compressor electrically, consult the Instruction book for the motor
rotation direction
9 Compressor remains pressurized for 180 seconds after switching off the voltage
10 Torques for steel (Fe) or brass (CuZn) bolts
11 Switch off the voltage and wait at least 6 minutes before removing the screen
12 Oil outlet (option DD/PD filters)
17 Automatic Restart After Voltage Failure (ARAVF)
Reference Designation
15 Cooling water inlet
16 Cooling water outlet
8 Operating instructions
For the location of the air outlet valve and the drain connections, see sections Introduction
and Condensate system.
Preparations
1. Consult the sections Electrical cable size, Installation proposal and Dimension drawings.
2. The following transport fixtures, painted red, must be removed:
• Bolts or bolts and bushes under the oil separator vessel (1)
• Bolts and bushes under the gear casing (2)
• Bolt and bushes or support under the motor (3)
3. Check that the electrical connections correspond to the applicable codes and that all wires
are clamped tight to their terminals.
The installation must be earthed and protected against short circuits by fuses of the inert
type in all phases. An isolating switch must be installed near the compressor.
4. Check transformer (T1) for correct connection.
Check the settings of drive motor overload relay (F21).
Check that the motor overload relay is set for manual resetting.
5. On air-cooled compressors, check the setting of circuit breaker (Q15). Also check that the
switch on the circuit breaker is in position I.
6. Fit air outlet valve (AV). See section Introduction for the location of the valve.
Close the valve.
Connect the air net to the valve.
On compressors equipped with a dryer bypass, fit the air outlet valve to the dryer bypass
pipe.
7. Connect the condensate drain outlet(s) to a drain collector.
See section Condensate system.
The drain pipes to the drain collector must not dip into the water. If there is a risk for
freezing, the pipes must be insulated.
For draining of pure condensate water, install an oil/water separator which is available from
Atlas Copco as an option. See section OSCi
8. For compressors with a DD or a DD and PD filter: connect the automatic drain of the filters
to a suitable drain collector.
9. On water-cooled compressors, drain valves, shut-off valves and a regulating valve should be
fitted by the customer in the cooling water piping.
10. Provide labels, warning the operator that:
• The compressor may automatically restart after voltage failure (if activated, consult
Atlas Copco).
• The compressor is automatically controlled and may be restarted automatically.
If the compressor has not run for the past 6 months, it is strongly recommended to
improve the lubrication of the compressor element before starting.
To do so:
1. Disconnect the inlet hose.
2. Remove the unloader (UA).
3. Pour approximately 0.75 l (0.20 US gal, 0.17 Imp gal) of compressor oil into the
compressor element inlet. For oil specifications, see section Oil specifications.
4. Reinstall the unloader and reconnect the inlet hose.
Make sure that all connections are tight.
Location of unloader
Procedure
1. If the compressor has not run for the past 6 months, it is strongly recommended to improve
the lubrication of the compressor element before starting. See section Initial start.
2. Check oil level. Top up if necessary.
3. If necessary, empty the dust trap of the filter, see section Air filter.
If the red part of the air filter service indicator shows full out, replace the air filter element.
Reset the service indicator (VI) by pushing the knob in the extremity of the indicator.
4. On water-cooled compressors:
• Check that the cooling water drain valves in the inlet and outlet pipes are closed.
• Open the cooling water inlet valve.
• Open the water flow regulating valve. This step can be skipped if the setting of this
valve has not been changed.
8.3 Starting
For the position of the air outlet valve and the drain connections, see sections
Introduction and Condensate system.
Procedure
1. Open the air outlet valve.
2. Switch on the voltage. Check that voltage on LED lights up.
3. Press the start button on the control panel. The compressor starts running and the automatic
operation LED lights up. Ten seconds after starting, the drive motor switches over from star
to delta and the compressor starts running loaded.
4. On water-cooled compressors, the cooling water is used to cool the compressor oil and
compressed air. Regulate the cooling water flow during loaded operation to obtain the most
suitable temperature at the outlet of the compressor element. This temperature is
determined by the condensation point of water at operating conditions (lower temperature
limit) and the maximum desirable oil temperature (100 °C / 212 °F) as upper limit. For good
practice, regulate the cooling flow to obtain an element outlet temperature approximately 5°
C above the relevant (lower limit) temperature obtained from the figure below. If the
calculated temperature is higher than 100° C, this will lead to more rapid oil deterioration,
which will have an impact on oil service intervals. Consult Atlas Copco for best practices in
this case. Also consult Atlas Copco in case condensate should form in the oil.
For optimal operation, the cooling water outlet temperature must never exceed the value
specified in section Reference conditions and limitations.
loaded operation to obtain a temperature between 70 °C (158 °F) and 75 ˚C (167 ˚F) at the
outlet of the compressor element.
Warnings
The operator must apply all relevant Safety precautions. Also consult section Problem
solving.
Keep the doors closed during operation. They may be opened for short periods only to
carry out checks.
When the motors are stopped and LED (automatic operation) is alight, the motors may
start automatically.
6. Remove the plug and add oil until the level reaches the filler opening.
7. Fit and tighten the plug (FC).
Unlock the emergency stop button, select the STOP icon and press reset before starting.
Air filter
Regularly check the service indicator. If the colored part of service indicator (VI) shows full out,
replace the air filter element. Reset the service indicator by pushing the knob in the extremity of
the indicator body.
Drains
Regularly check that condensate is discharged during operation. See section Condensate
system. The amount of condensate depends on environmental and working conditions.
If an OSCi is installed, also check the level in the oil collector. See section Maintenance OSCi.
Check the display (6) regularly for readings and messages. The display normally shows the
compressor outlet pressure, while the status of the compressor is indicated by pictographs.
Remedy the trouble if alarm LED (1) is lit or flashes.
The display (6) will show a service message if a service plan interval has been exceeded or if a
service level for a monitored component has been exceeded. The service LED is on. Carry out
the service actions of the indicated plans or replace the component and reset the relevant timer.
Compressors with Eletronikon™ Touch controller:
Check the display (1) regularly for readings and messages. The display normally shows the
compressor outlet pressure, while the status of the compressor is indicated by pictographs.
Remedy the trouble if alarm LED (2) is lit or flashes.
The display (1) will show a service message if a service plan interval has been exceeded or if a
service level for a monitored component has been exceeded. The service LED is on. Carry out
the service actions of the indicated plans or replace the component and reset the relevant timer.
8.6 Stopping
Control panel
Procedure
Step Action
- For Elektronikon™ Swipe, press stop button (9). Automatic operation LED (3) goes out and
the compressor stops after 30 seconds of unloaded operation.
For Elektronikon™ Touch, press stop button (6). Automatic operation LED (4) goes out and
the compressor stops after 30 seconds of unloaded operation.
- To stop the compressor in the event of an emergency, for Elektronikon™ Swipe, press the
emergency stop button. Alarm LED (1) flashes.
To stop the compressor in the event of an emergency, for Elektronikon™ Touch, press the
emergency stop button. Alarm LED (2) flashes.
• Remedy the problem cause and unlock the stop button by pulling it out.
• Reset the alarm.
Do not use the emergency stop button for normal stopping!
- Close the air outlet valve.
- Press the test button on top of the electronic water drain(s) (if supplied) to the depressurize the
piping between air receiver and outlet valve, next open the manual drain valve (Dm). See
section Condensate system.
Switch off the voltage.
- On water-cooled compressors:
• Close the cooling water inlet valve.
• If freezing temperatures can be expected, drain the cooling system completely.
Warning
Procedure
Step Action
- Stop the compressor and close the air outlet valve.
- Open the manual drain valve.
- Switch off the voltage and disconnect the compressor from the mains.
- Unscrew the oil filler plug only one turn to permit any pressure in the system to escape.
Consult section Oil and oil filter change to locate the filler plug.
- Shut off and depressurize the part of the air net which is connected to the outlet valve.
Disconnect the compressor air outlet pipe from the air net.
- On water-cooled compressors:
• Isolate and disconnect the water system from the cooling water net.
• Drain the water circuit.
- Drain the oil.
- Drain the condensate circuit and disconnect the condensate piping from the condensate net.
9 Maintenance
Warning
Service kits
For overhauling or carrying out preventive maintenance, service kits are available (see section
Service kits).
Service contracts
Atlas Copco offers several types of service contracts, relieving you of all preventive maintenance
work. Consult your Atlas Copco Customer Centre.
General
When servicing, replace all removed O-rings and washers.
Intervals
The local Atlas Copco Customer Centre may overrule the maintenance schedule, especially the
service intervals, depending on the environmental and working conditions of the compressor.
The longer interval checks must also include the shorter interval checks.
Maintenance checklist
Period Operation
Daily Check oil level.
Check readings on display.
Check air filter service indicator.
Check that condensate is discharged during operation.
Drain condensate.
On water-cooled units: check for cooling water flow.
Monthly Check that condensate is discharged when pressing the test button on top of the
electronic water drain.
On compressors with integrated dryer:
• Stop the compressor, close the air outlet valve and switch off the voltage.
• Remove any dirt from the condenser inlet with a vacuum cleaner.
• Next, clean with an air jet in the reverse direction of the normal flow. Use low
pressure air. Keep the compressed air nozzle more than 30 cm away from the
condenser to avoid damaging the of condenser fins.
• Remove dust from inside the dryer, e.g. with a vacuum cleaner.
Do not use water or solvents to clean the condenser.
3-monthly (1) Check coolers. Clean if necessary.
Remove the air filter element and inspect. If necessary, clean using an air jet. Replace
damaged or heavily contaminated elements.
Check the filter element of the electric cabinet. Replace if necessary
Check the oil return hole.
Yearly or every Replace the wearing parts of the electronic water drain(s). A service kit is available.
8000 hours (2) Refer to the motor data plate for greasing instructions of the motor bearings (for motors
equipped with grease nipples).
Every 5 years or Replace all rubber hoses.
40000 hours (2)
Avoid mixing lubricants of different brands or types as they may not be compatible and
the oil mix may have inferior properties. A label, indicating the type of oil filled ex factory,
is stuck on the air receiver/oil tank.
Note: the presence of dust and/or high humidity may require a shorter exchange interval. Consult
Atlas Copco.
Note: the presence of dust and/or high humidity may require a shorter exchange interval. Consult
Atlas Copco.
Note: the presence of dust and/or high humidity may require a shorter exchange interval. Consult
Atlas Copco.
Roto-Foodgrade Fluid
Special oil, delivered as an option.
Atlas Copco's Roto-Foodgrade Fluid is a unique high quality synthetic lubricant, specially created
for oil injected screw compressors that provide air for the food and beverage industry. This
lubricant keeps the compressor in excellent condition. Roto-Foodgrade Fluid can be used for
compressors operating at ambient temperatures between 0 ˚C (32 ˚F) and 40 ˚C (104 ˚F).
Roto-Foodgrade Fluid has all required certification for use in food & beverage industry: like NSF-
H1, Kosher, Halal and Allergen Free approvals.
See the table below for oil exchange intervals:
Note: the presence of dust and/or high humidity may require a shorter exchange interval. Consult
Atlas Copco.
* Whichever comes first.
General
Keep the outside of the electric motor clean for efficient cooling. If necessary, remove dust with a
brush and/or compressed air jet.
Bearing maintenance
The bearing at the drive end side is lubricated by the oil system and requires no periodic
maintenance.
The non drive end side bearing of motors without grease nipples requires no periodic
maintenance.
Motors with a grease nipple at the non drive end side must follow the maintenance interval as
mentioned on the motor data plate.
Recommendations
1. Never remove the element while the compressor is running.
2. For minimum downtime, replace the dirty element by a new one.
3. Discard the element when damaged.
Procedure
1. Stop the compressor. Switch off the voltage.
2. Release the snap clips of air filter (AF) and remove the cover and the air filter element.
Discard the filter element.
3. Fit the new element and the cover.
4. Reset service indicator (VI) by pushing the knob in the extremity of the body.
5. Reset the air filter service warning.
Warning
Procedure
Step Description
- Run the compressor until warm. Stop the compressor after 3 minutes of unloaded operation.
Close the air outlet valve and switch off the voltage. Wait a few minutes and depressurise by
unscrewing oil filler plug (FC) just one turn to permit any pressure in the system to escape.
- Air cooled units: loosen the vent plug (VP) of the oil cooler and wait for 5 minutes.
- Remove drain plug (DP1) and open drain valve (Dm).
Also drain the oil by removing the drain plug:
• on the check valve (DP2)
• on the gear casing (DP3)
- Collect the oil in a collector and deliver it to the local collection service. Refit and tighten the drain
and vent plugs after draining.
Close the drain valve (Dm).
- Remove the oil filter (OF). Be aware that this filter has a left thread connection. Clean the seat
on the manifold. Oil the gasket of the new filter and screw it into place. Tighten firmly by hand.
- Remove filler plug (FC).
Fill the air receiver (AR) with oil until the level reaches the filler neck.
Take care that no dirt drops into the system. Refit and tighten filler plug (FC).
- Run the compressor loaded for a few minutes. Stop the compressor and wait a few minutes to
allow the oil to settle.
- Depressurise the system by unscrewing filler plug (FC) just one turn to permit any pressure in the
system to escape. Remove the plug.
Fill the air receiver with oil until the level reaches the filler neck.
Tighten the filler plug.
- Reset the service warning after carrying out all service actions in the relevant Service Plan.
9.6 Coolers
General
Keep the coolers clean to maintain their efficiency.
• Remove any dirt from the coolers with a fibre brush. Brush in the direction of the cooling fins.
Also remove any dirt from the fan with a fibre brush.
• Next, clean with an air jet in the reverse direction to normal flow. Use low pressure air. If
necessary, the pressure may be increased up to 6 bar(e) (87 psig).
• If it is necessary to wash the coolers with a cleaning agent, consult Atlas Copco.
• Remove the cover used during cleaning.
• Mount the service plates (1) at the fan compartment.
Testing
Before removing the valve, depressurize the compressor. See also section Problem solving.
The safety valve (SV) can be tested on a separate air line. If the valve does not open at the set
pressure stamped on the valve, it needs to be replaced.
Warning
No adjustments are allowed. Never run the compressor without safety valve.
Safety precautions
Refrigeration dryers of ID type contain refrigerant HFC.
When handling refrigerant, all applicable safety precautions must be observed. Please be
specifically aware of the following points:
• Contact of refrigerant with the skin will cause freezing. Special gloves must be worn. If
contacted with the skin, the skin should be rinsed with water. On no account may clothing be
removed.
• Fluid refrigerant will also cause freezing of the eyes; always wear safety glasses.
• Refrigerant is harmful. Do not inhale refrigerant vapours. Check that the working area is
adequately ventilated.
Be aware that certain components such as the refrigerant compressor and the discharge pipe
can become quite hot (up to 110 °C - 230 °F). Therefore, wait until the dryer has cooled down
before removing the panels.
Before starting any maintenance or repair work, switch off the voltage and close the air inlet and
outlet valves.
Local legislation
Local legislation may stipulate that:
• Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its
function must be undertaken by an authorised control body.
• The installation should be checked once a year by an authorised control body.
General
For all references see section Introduction.
The following remarks should be kept in mind:
• Keep the dryer clean.
• Brush or blow off the finned surface of condenser monthly.
• Inspect and clean the electronic condensate drain monthly.
Service kits
For overhauling and for preventive maintenance, a wide range of service kits is available. Service
kits comprise all parts required for servicing the component and offer the benefits of genuine
Atlas Copco parts while keeping the maintenance budget low.
Also a full range of extensively tested lubricants, suitable for your specific needs is available to
keep the compressor in excellent condition.
Consult the Spare Parts List for part numbers.
Procedure
Run the compressor regularly, e.g. twice a week, until warm. Load and unload the compressor a
few times.
If the compressor is going to be stored without running from time to time, protective
measures must be taken. Consult your supplier.
Used filters or any other used material (e.g. desiccant, lubricants, cleaning rags, machine parts,
etc.) must be disposed of in an environmentally friendly and safe manner, and in line with the
local recommendations and environmental legislation.
Electronic components are subject to the EU Directive 2012/19/EC for Waste Electrical and
Electronic Equipment (WEEE). As such, these parts must not be disposed of at a municipal
waste collection point. Refer to local regulations for directions on how to dispose of this product in
an environmental friendly manner.
10 Problem solving
Warning
Before carrying out any maintenance, repair work or adjustment, press the stop button,
wait until the compressor has stopped and close the air outlet valve.
Open the manual drain valve(s).
Press the emergency stop button and switch off the voltage. Open and lock the isolating
switch.
Depressurise the oil separator vessel by opening the oil filler plug one turn.
For location of components: see sections Introduction, Condensate system and Initial
start.
The air outlet valve can be locked during maintenance or repair as follows:
• Close the valve.
• Remove the screw fixing the handle with the wrench delivered with the
compressor.
• Lift the handle and turn it until the slot of the handle fits over the blocking edge on
the valve body.
• Fit the screw.
• Always switch off the voltage. Only pressing the emergency stop button is not
sufficient to make the compressor voltage free.
• If the machine is equipped with an automatic restart after voltage failure function
and if this function is active, be aware that the machine will restart automatically
when the power is restored if it was running when the power was interrupted.
11 Technical data
Control panel
Important
The readings mentioned below are valid under the reference conditions (see section
Reference conditions and limitations).
Reference Reading
Air outlet pressure Modulates between programmed unloading and loading pressures.
Compressor element For air-cooled units: approx. 60 ˚C (108 ˚F) above cooling air inlet temperature
outlet temperature For water-cooled units: approx. 60 ˚C (108 ˚F) above cooling water inlet
temperature.
Dewpoint temperature See section Compressor data.
Cooling water outlet Below 50 ˚C (122 ˚F).
temperature
Important
• The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables
at nominal current below 5% of the nominal voltage (IEC 60204-1).
• If cables are grouped together with other power cables, it may be necessary to use
cables of a larger size than those calculated for the standard operating conditions.
• Use the original cable entry. See section Dimension drawings.
To preserve the protection degree of the electric cubicle and to protect its
components from dust from the environment, it is mandatory to use a proper
cable gland when connecting the supply cable to the compressor.
• Local regulations remain applicable if they are stricter than the values proposed
below.
• Currents are calculated with the full service factor but we suggest to add 10% due
to over- and under-voltage.
Fuses are maximum allowed values calculated for full service factor and 10%
over- and under-voltage.
• Caution:
• Always double-check the fuse size versus the calculated cable size. If
required, reduce fuse size or enlarge cable size.
• Cable length should not exceed the maximum length according to IEC60204
table 10
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
gL/gG gL/gG
V Hz A A A A
GA 30+ 200 50 132 160 145 160
GA 30+ 400 50 66 80 70 80
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
gL/gG gL/gG
V Hz A A A A
GA 30+ 200 60 133 160 142 160
GA 30+ 230 60 115 160 124 160
GA 30+ 380 60 70 80 74 100
GA 30+ 460 60 58 80 62 80
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
gL/gG gL/gG
V Hz A A A A
GA 37 200 50 167 200 179 200
GA 37 400 50 84 100 88 100
GA 37 200 60 172 200 188 224
GA 37 230 60 149 200 160 200
GA 37 380 60 90 100 95 125
GA 37 460 60 75 100 79 100
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
gL/gG gL/gG
V Hz A A A A
GA 37+ 200 50 152 200 163 200
GA 37+ 400 50 76 100 80 100
GA 37+ 200 60 172 200 188 224
GA 37+ 230 60 149 200 160 200
GA 37+ 380 60 90 100 95 125
GA 37+ 460 60 75 100 79 100
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
gL/gG gL/gG
V Hz A A A A
GA 45 200 50 213 250 229 250
GA 45 400 50 107 125 111 125
GA 45 200 60 214 250 225 250
GA 45 230 60 186 224 197 224
GA 45 380 60 114 160 118 160
GA 45 460 60 94 125 98 125
Compressor type I (1) Max. fuse (1) I (2) Max. fuse (2)
gL/gG gL/gG
V Hz A A A A
GA 45+ 200 50 203 224 215 250
GA 45+ 400 50 102 125 106 125
GA 45+ 200 60 223 250 234 315
GA 45+ 230 60 194 224 205 224
GA 45+ 380 60 118 160 123 160
GA 45+ 460 60 98 125 102 125
Possible configurations
There are 3 possible cabling layouts:
Maximum allowed current in function of the ambient temperature for installation method B2
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
4 mm² < 27 A < 23 A < 21 A < 19 A < 16 A
6 mm² < 34 A < 30 A < 27 A < 24 A < 21 A
10 mm² < 46 A < 40 A < 36 A < 33 A < 28 A
16 mm² < 62 A < 54 A < 49 A < 44 A < 38 A
25 mm² < 80 A < 70 A < 63 A < 57 A < 49 A
35 mm² < 99 A < 86 A < 78 A < 70 A < 60 A
50 mm² < 118 A < 103 A < 93 A < 84 A < 72 A
70 mm² < 149 A < 130 A < 118 A < 106 A < 91 A
95 mm² < 179 A < 156 A < 141 A < 127 A < 109 A
120 mm² < 206 A < 179 A < 163 A < 146 A < 126 A
Maximum allowed current in function of the ambient temperature for installation method C
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
4 mm² < 32 A < 28 A < 25 A < 23 A < 20 A
6 mm² < 41 A < 36 A < 32 A < 29 A < 25 A
10 mm² < 57 A < 50 A < 45 A < 40 A < 35 A
16 mm² < 76 A < 66 A < 60 A < 54 A < 46 A
25 mm² < 96 A < 84 A < 76 A < 68 A < 59 A
35 mm² < 119 A < 104 A < 94 A < 84 A < 73 A
50 mm² < 144 A < 125 A < 114 A < 102 A < 88 A
70 mm² < 184 A < 160 A < 145 A < 131 A < 112 A
95 mm² < 223 A < 194 A < 176 A < 158 A < 136 A
120 mm² < 259 A < 225 A < 205 A < 184 A < 158 A
Maximum allowed current in function of the ambient temperature for installation method F
conductor temperature 70°C
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 110 A < 96 A < 87 A < 78 A < 67 A
35 mm² < 137 A < 119 A < 108 A < 97 A < 84 A
50 mm² < 167 A < 145 A < 132 A < 119 A < 102 A
70 mm² < 216 A < 188 A < 171 A < 153 A < 132 A
95 mm² < 264 A < 230 A < 209 A < 187 A < 161 A
120 mm² < 308 A < 268 A < 243 A < 219 A < 188 A
150 mm² < 356 A < 310 A < 281 A < 253 A < 217 A
185 mm² < 409 A < 356 A < 323 A < 290 A < 249 A
240 mm² < 485 A < 422 A < 383 A < 344 A < 296 A
300 mm² < 561 A < 488 A < 443 A < 398 A < 342 A
400 mm² < 659 A < 573 A < 518 A < 467 A < 402 A
Maximum allowed current in function of the ambient temperature for installation method
F,conductor temperature 90°C
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 135 A < 123 A < 117 A < 110 A < 103 A
35 mm² < 169 A < 154 A < 147 A < 139 A < 128 A
50 mm² < 207 A < 188 A < 180 A < 170 A < 157 A
70 mm² < 268 A < 244 A < 233 A < 220 A < 204 A
95 mm² < 328 A < 298 A < 285 A < 269 A < 249 A
120 mm² < 383 A < 349 A < 333 A < 314 A < 291 A
150 mm² < 444 A < 404 A < 386 A < 364 A < 337 A
185 mm² < 510 A < 464 A < 443 A < 418 A < 388 A
240 mm² < 607 A < 552 A < 528 A < 498 A < 461 A
300 mm² < 703 A < 639 A < 611 A < 576 A < 534 A
400 mm² < 823 A < 749 A < 716 A < 674 A < 625 A
• Add 10 % to the total compressor current (ItotPack or ItotFF from the tables) and divide
by 2
• Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
• Install fuses of half the size of the recommended maximum fuse size on each cable.
• When using 2 x 3 phases + PE as in (3):
• Add 10 % to the total compressor current (ItotPack or ItotFF from the tables) and divide
by √3
• Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
• Fuse size: the recommended maximum fuse size divided by √3 on each cable.
• Size of the PE cable:
• For supply cables up to 35 mm²: same size as supply cables
• For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
• Example: Itot = 234 A, maximum ambient temperature is 45 °C, recommended fuse = 315 A
• Single supply cables (3 phases + PE - configuration (1)):
• I = 234 A + 10 % = 234 x 1.1 = 257.4 A
• The table for method F, 70 °C cable temperature and ambient temperature of 45
°C allows a maximum current of 323 A for a 185 mm² cable. So use a 3 x 185 mm²
+ 95 mm² cable.
• If the table for method F, 90 °C cable temperature and ambient temperature of 45
°C is used, 120 mm² is sufficient. So a single cable 3 x 120 mm² + 70 mm² is
sufficient .
• Parallel supply cable (2 x 3 phases + PE - configuration (2)):
• I = (234 A + 10 %)/2 = (234 x 1.1)/2 = 128.7 A
• Install 160 A fuses on each cable instead of 315 A.
• For a cable of 95 mm², method F, 70 °C cable temperature and ambient
temperature of 45 °C, the maximum current is 209 A x 0.8 = 167.2 A. So 2 parallel
cables of 3 x 95 mm² + 50 mm² are sufficient.
• For a cable of 95 mm², method F, 90 °C cable temperature and ambient
temperature of 45 °C, the maximum current is 233 A x 0.8 = 186.4 A. So 2 parallel
cables of 3 x 70 mm² + 35 mm² are sufficient.
General
The regulating and safety devices are factory-adjusted to give optimum performance of the dryer.
Do not alter the setting of any of the devices.
Reference conditions
Limits
Reference conditions
All data specified below apply under reference conditions, see section Reference
conditions and limitations.
GA 30 +
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Frequency Hz 50 50 50 50 60 60 60 60
Maximum (unloading) bar(e) 7.5 8.5 10 13 7.4 9.1 10.8 12.5
pressure, Workplace
units
Maximum (unloading) psig 109 123 145 189 107 132 157 181
pressure, Workplace
units
Maximum (unloading) bar(e) 7.3 8.3 9.8 12.8 7.2 8.9 10.6 12.3
pressure, Workplace
Full-Feature units
Maximum (unloading) psig 106 120 142 186 104 129 154 178
pressure, Workplace
Full-Feature units
Reference working bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
pressure
Reference working psig 102 116 138 181 100 125 150 175
pressure
Pressure drop over bar(e) 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13
dryer, Workplace Full-
Feature units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Pressure drop over psig 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
dryer, Workplace Full-
Feature units
Set point of thermostatic ˚C 40 40 40 60 40 40 40 60
valve
Set point of thermostatic ˚F 104 104 104 140 104 104 104 140
valve
Motor shaft speed r/min 2956 2956 2956 2956 3565 3565 3565 3565
Nominal motor power kW 30 30 30 30 30 30 30 30
Nominal motor power hp 40.2 40.2 40.2 40.2 40.2 40.2 40.2 40.2
Temperature of air ˚C 27 27 27 27 27 27 27 27
leaving outlet valve,
Workplace units
Temperature of air ˚F 81 81 81 81 81 81 81 81
leaving outlet valve,
Workplace units
Pressure dew point, ˚C 3 3 3 3 3 3 3 3
Workplace Full-Feature
units
Pressure dew point, ˚F 37.4 37.4 37.4 37.4 37.4 37.4 37.4 37.4
Workplace Full-Feature
units
Temperature of air ˚C 23 23 23 23 23 23 23 23
leaving outlet valve,
Workplace Full-Feature
units
Temperature of air ˚F 73 73 73 73 73 73 73 73
leaving outlet valve,
Workplace Full-Feature
units
Dryer power at full load, kW 1.4 1.4 1.4 1.4 1.6 1.6 1.6 1.6
Workplace Full-Feature
units
Dryer power at full load, hp 1.9 1.9 1.9 1.9 2.1 2.1 2.1 2.1
Workplace Full-Feature
units
Dryer power at no load, kW 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.4
Workplace Full-Feature
units
Dryer power at no load, hp 1.6 1.6 1.6 1.6 1.9 1.9 1.9 1.9
Workplace Full-Feature
units
Refrigerant type, R410A R410A R410A R410A R410A R410A R410A R410A
Workplace Full-Feature
units
Refrigerant quantity, kg 0.8 0.8 0.8 0.8 0.9 0.9 0.9 0.9
Workplace Full-Feature
units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Refrigerant quantity, lb 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9
Workplace Full-Feature
units
Cooling water l/min 35 35 35 35 35 35 35 35
consumption (at water
inlet temperature below
35 ˚C and temperature
rise of 15 ˚C), water-
cooled units
Cooling water cfm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
consumption (at water
inlet temperature below
95 ˚F and temperature
rise of 27 ˚F), water-
cooled units
Cooling water l/min 55 55 55 55 55 55 55 55
consumption (at water
inlet temperature
between 35 and 40 ˚C
and temperature rise of
10 ˚C), water-cooled
units
Cooling water cfm 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
consumption (at water
inlet temperature
between 95 and 104 ˚F
and temperature rise of
18 ˚F), water-cooled
units
Oil capacity, air-cooled l 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6
units
Oil capacity, air-cooled US gal 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12
units
Oil capacity, air-cooled Imp gal 3.43 3.43 3.43 3.43 3.43 3.43 3.43 3.43
units
Oil capacity, water- l 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9
cooled units
Oil capacity, water- US gal 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73
cooled units
Oil capacity, water- Imp gal 3.94 3.94 3.94 3.94 3.94 3.94 3.94 3.94
cooled units
Sound pressure level dB(A) 65 65 65 65 65 65 65 65
(according to ISO 2151
(2004))
GA 37
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Frequency Hz 50 50 50 50 60 60 60 60
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Maximum (unloading) bar(e) 7.5 8.5 10 13 7.4 9.1 10.8 12.5
pressure, Workplace
units
Maximum (unloading) psig 109 123 145 189 107 132 157 181
pressure, Workplace
units
Maximum (unloading) bar(e) 7.3 8.3 9.8 12.8 7.2 8.9 10.6 12.3
pressure, Workplace
Full-Feature units
Maximum (unloading) psig 106 120 142 186 104 129 154 178
pressure, Workplace
Full-Feature units
Reference working bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
pressure
Reference working psig 102 116 138 181 100 125 150 175
pressure
Pressure drop over bar(e) 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13
dryer, Workplace Full-
Feature units
Pressure drop over psig 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
dryer, Workplace Full-
Feature units
Set point of thermostatic ˚C 40 40 40 60 40 40 40 60
valve
Set point of thermostatic ˚F 104 104 104 140 104 104 104 140
valve
Motor shaft speed r/min 2956 2956 2956 2956 3565 3565 3565 3565
Nominal motor power kW 37 37 37 37 37 37 37 37
Nominal motor power hp 49.6 49.6 49.6 49.6 49.6 49.6 49.6 49.6
Temperature of air ˚C 27 27 27 27 27 27 27 27
leaving outlet valve,
Workplace units
Temperature of air ˚F 81 81 81 81 81 81 81 81
leaving outlet valve,
Workplace units
Pressure dew point, ˚C 3 3 3 3 3 3 3 3
Workplace Full-Feature
units
Pressure dew point, ˚F 37.4 37.4 37.4 37.4 37.4 37.4 37.4 37.4
Workplace Full-Feature
units
Temperature of air ˚C 23 23 23 23 23 23 23 23
leaving outlet valve,
Workplace Full-Feature
units
Temperature of air ˚F 73 73 73 73 73 73 73 73
leaving outlet valve,
Workplace Full-Feature
units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Dryer power at full load, kW 1.34 1.4 1.4 1.4 1.6 1.6 1.6 1.6
Workplace Full-Feature
units
Dryer power at full load, hp 1.8 1.9 1.9 1.9 2.2 2.1 2.1 2.1
Workplace Full-Feature
units
Dryer power at no load, kW 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.4
Workplace Full-Feature
units
Dryer power at no load, hp 1.6 1.6 1.6 1.6 1.9 1.9 1.9 1.9
Workplace Full-Feature
units
Refrigerant type, R410A R410A R410A R410A R410A R410A R410A R410A
Workplace Full-Feature
units
Refrigerant quantity, kg 1 0.8 0.8 0.8 1 0.9 0.9 0.9
Workplace Full-Feature
units
Refrigerant quantity, lb 2.1 1.8 1.8 1.8 2.2 1.9 1.9 1.9
Workplace Full-Feature
units
Cooling water l/min 39 39 39 39 39 39 39 39
consumption (at water
inlet temperature below
35 ˚C and temperature
rise of 15 ˚C), water-
cooled units
Cooling water cfm 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
consumption (at water
inlet temperature below
95 ˚F and temperature
rise of 27 ˚F), water-
cooled units
Cooling water l/min 59 59 59 59 59 59 59 59
consumption (at water
inlet temperature
between 35 and 40 ˚C
and temperature rise of
10 ˚C), water-cooled
units
Cooling water cfm 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
consumption (at water
inlet temperature
between 95 and 104 ˚F
and temperature rise of
18 ˚F), water-cooled
units
Oil capacity, air-cooled l 15.6 15.6 15.6 15.6 15.6 15.6 15.6 15.6
units
Oil capacity, air-cooled US gal 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12
units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Oil capacity, air-cooled Imp gal 3.43 3.43 3.43 3.43 3.43 3.43 3.43 3.43
units
Oil capacity, water- l 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9
cooled units
Oil capacity, water- US gal 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73
cooled units
Oil capacity, water- Imp gal 3.94 3.94 3.94 3.94 3.94 3.94 3.94 3.94
cooled units
Sound pressure level dB(A) 69 69 69 69 69 69 69 69
(according to ISO 2151
(2004))
GA 37+
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Frequency Hz 50 50 50 50 60 60 60 60
Maximum (unloading) bar(e) 7.5 8.5 10 13 7.4 9.1 10.8 12.5
pressure, Workplace
units
Maximum (unloading) psig 109 123 145 189 107 132 157 181
pressure, Workplace
units
Maximum (unloading) bar(e) 7.3 8.3 9.8 12.8 7.2 8.9 10.6 12.3
pressure, Workplace
Full-Feature units
Maximum (unloading) psig 106 120 142 186 104 129 154 178
pressure, Workplace
Full-Feature units
Reference working bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
pressure
Reference working psig 102 116 138 181 100 125 150 175
pressure
Pressure drop over bar(e) 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13
dryer, Workplace Full-
Feature units
Pressure drop over psig 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
dryer, Workplace Full-
Feature units
Set point of thermostatic ˚C 40 40 40 60 40 40 40 60
valve
Set point of thermostatic ˚F 104 104 104 140 104 104 104 140
valve
Motor shaft speed r/min 2956 2956 2956 2956 3565 3565 3565 3565
Nominal motor power kW 37 37 37 37 37 37 37 37
Nominal motor power hp 49.6 49.6 49.6 49.6 49.6 49.6 49.6 49.6
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Temperature of air ˚C 27 27 27 27 27 27 27 27
leaving outlet valve,
Workplace units
Temperature of air ˚F 81 81 81 81 81 81 81 81
leaving outlet valve,
Workplace units
Pressure dew point, ˚C 3 3 3 3 3 3 3 3
Workplace Full-Feature
units
Pressure dew point, ˚F 37.4 37.4 37.4 37.4 37.4 37.4 37.4 37.4
Workplace Full-Feature
units
Temperature of air ˚C 23 23 23 23 23 23 23 23
leaving outlet valve,
Workplace Full-Feature
units
Temperature of air ˚F 73 73 73 73 73 73 73 73
leaving outlet valve,
Workplace Full-Feature
units
Dryer power at full load, kW 1.34 1.34 1.4 1.4 1.6 1.6 1.6 1.6
Workplace Full-Feature
units
Dryer power at full load, hp 1.8 1.8 1.9 1.9 2.2 2.1 2.1 2.1
Workplace Full-Feature
units
Dryer power at no load, kW 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.4
Workplace Full-Feature
units
Dryer power at no load, hp 1.6 1.6 1.6 1.6 1.9 1.9 1.9 1.9
Workplace Full-Feature
units
Refrigerant type, R410A R410A R410A R410A R410A R410A R410A R410A
Workplace Full-Feature
units
Refrigerant quantity, kg 1 1 0.8 0.8 1 0.9 0.9 0.9
Workplace Full-Feature
units
Refrigerant quantity, lb 2.1 1.1 1.8 1.8 2.2 1.9 1.9 1.9
Workplace Full-Feature
units
Cooling water l/min 39 39 39 39 39 39 39 39
consumption (at water
inlet temperature below
35 ˚C and temperature
rise of 15 ˚C), water-
cooled units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Cooling water cfm 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
consumption (at water
inlet temperature below
95 ˚F and temperature
rise of 27 ˚F), water-
cooled units
Cooling water l/min 59 59 59 59 59 59 59 59
consumption (at water
inlet temperature
between 35 and 40 ˚C
and temperature rise of
10 ˚C), water-cooled
units
Cooling water cfm 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
consumption (at water
inlet temperature
between 95 and 104 ˚F
and temperature rise of
18 ˚F), water-cooled
units
Oil capacity, air-cooled l 21 21 21 21 21 21 21 21
units
Oil capacity, air-cooled US gal 5.55 5.55 5.55 5.55 5.55 5.55 5.55 5.55
units
Oil capacity, air-cooled Imp gal 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62
units
Oil capacity, water- l 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9
cooled units
Oil capacity, water- US gal 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73
cooled units
Oil capacity, water- Imp gal 3.94 3.94 3.94 3.94 3.94 3.94 3.94 3.94
cooled units
Sound pressure level dB(A) 65 65 65 65 65 65 65 65
(according to ISO 2151
(2004))
GA 45
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Frequency Hz 50 50 50 50 60 60 60 60
Maximum (unloading) bar(e) 7.5 8.5 10 13 7.4 9.1 10.8 12.5
pressure, Workplace
units
Maximum (unloading) psig 109 123 145 189 107 132 157 181
pressure, Workplace
units
Maximum (unloading) bar(e) 7.3 8.3 9.8 12.8 7.2 8.9 10.6 12.3
pressure, Workplace
Full-Feature units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Maximum (unloading) psig 106 120 142 186 104 129 154 178
pressure, Workplace
Full-Feature units
Reference working bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
pressure
Reference working psig 102 116 138 181 100 125 150 175
pressure
Pressure drop over bar(e) 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13
dryer, Workplace Full-
Feature units
Pressure drop over psig 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
dryer, Workplace Full-
Feature units
Set point of thermostatic ˚C 40 40 40 60 40 40 40 60
valve
Set point of thermostatic ˚F 104 104 104 140 104 104 104 140
valve
Motor shaft speed r/min 2956 2956 2956 2956 3565 3565 3565 3565
Nominal motor power kW 45 45 45 45 45 45 45 45
Nominal motor power hp 60.4 60.4 60.4 60.4 60.4 60.4 60.4 60.4
Temperature of air ˚C 27 27 27 27 27 27 27 27
leaving outlet valve,
Workplace units
Temperature of air ˚F 81 81 81 81 81 81 81 81
leaving outlet valve,
Workplace units
Pressure dew point, Full- ˚C 3 3 3 3 3 3 3 3
Feature units
Pressure dew point, Full- ˚F 37.4 37.4 37.4 37.4 37.4 37.4 37.4 37.4
Feature units
Temperature of air ˚C 23 23 23 23 23 23 23 23
leaving outlet valve,
Workplace Full-Feature
units
Temperature of air ˚F 73 73 73 73 73 73 73 73
leaving outlet valve,
Workplace Full-Feature
units
Dryer power at full load, kW 1.34 1.34 1.4 1.4 1.6 1.6 1.6 1.6
Workplace Full-Feature
units
Dryer power at full load, hp 1.8 1.8 1.9 1.9 2.2 2.1 2.1 2.1
Workplace Full-Feature
units
Dryer power at no load, kW 1.2 1.2 1.2 1.2 1.4 1.4 1.4 1.4
Workplace Full-Feature
units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Dryer power at no load, hp 1.6 1.6 1.6 1.6 1.9 1.9 1.9 1.9
Workplace Full-Feature
units
Refrigerant type, R410A R410A R410A R410A R410A R410A R410A R410A
Workplace Full-Feature
units
Refrigerant quantity, kg 1 1 0.8 0.8 1 0.9 0.9 0.9
Workplace Full-Feature
units
Refrigerant quantity, lb 2.1 2.1 1.8 1.8 2.2 1.9 1.9 1.9
Workplace Full-Feature
units
Cooling water l/min 45 45 45 45 45 45 45 45
consumption (at water
inlet temperature below
35 ˚C and temperature
rise of 15 ˚C), water-
cooled units
Cooling water cfm 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
consumption (at water
inlet temperature below
95 ˚F and temperature
rise of 27 ˚F), water-
cooled units
Cooling water l/min 65 65 65 65 65 65 65 65
consumption (at water
inlet temperature
between 35 and 40 ˚C
and temperature rise of
10 ˚C), water-cooled
units
Cooling water cfm 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
consumption (at water
inlet temperature
between 95 and 104 ˚F
and temperature rise of
18 ˚F), water-cooled
units
Oil capacity, air-cooled l 16.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6
units
Oil capacity, air-cooled US gal 4.39 4.39 4.39 4.39 4.39 4.39 4.39 4.39
units
Oil capacity, air-cooled Imp gal 3.65 3.65 3.65 3.65 3.65 3.65 3.65 3.65
units
Oil capacity, water- l 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9
cooled units
Oil capacity, water- US gal 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73
cooled units
Oil capacity, water- Imp gal 3.94 3.94 3.94 3.94 3.94 3.94 3.94 3.94
cooled units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Sound pressure level dB(A) 72 72 72 72 72 72 72 72
(according to ISO 2151
(2004))
GA 45+
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Frequency Hz 50 50 50 50 60 60 60 60
Maximum (unloading) bar(e) 7.5 8.5 10 13 7.4 9.1 10.8 12.5
pressure, Workplace
units
Maximum (unloading) psig 109 123 145 189 107 132 157 181
pressure, Workplace
units
Maximum (unloading) bar(e) 7.3 8.3 9.8 12.8 7.2 8.9 10.6 12.3
pressure, Workplace
Full-Feature units
Maximum (unloading) psig 106 120 142 186 104 129 154 178
pressure, Workplace
Full-Feature units
Reference working bar(e) 7 8 9.5 12.5 6.9 8.6 10.3 12
pressure
Reference working psig 102 116 138 181 100 125 150 175
pressure
Pressure drop over bar(e) 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13
dryer, Workplace Full-
Feature units
Pressure drop over psig 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
dryer, Workplace Full-
Feature units
Set point of thermostatic ˚C 40 40 40 60 40 40 40 60
valve
Set point of thermostatic ˚F 104 104 104 140 104 104 104 140
valve
Motor shaft speed r/min 2956 2956 2956 2956 3565 3565 3565 3565
Nominal motor power kW 45 45 45 45 45 45 45 45
Nominal motor power hp 60.4 60.4 60.4 60.4 60.4 60.4 60.4 60.4
Temperature of air ˚C 27 27 27 27 27 27 27 27
leaving outlet valve,
Workplace units
Temperature of air ˚F 81 81 81 81 81 81 81 81
leaving outlet valve,
Workplace units
Pressure dew point, ˚C 3 3 3 3 3 3 3 3
Workplace Full-Feature
units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Pressure dew point, ˚F 37.4 37.4 37.4 37.4 37.4 37.4 37.4 37.4
Workplace Full-Feature
units
Temperature of air ˚C 23 23 23 23 23 23 23 23
leaving outlet valve,
Workplace Full-Feature
units
Temperature of air ˚F 73 73 73 73 73 73 73 73
leaving outlet valve,
Workplace Full-Feature
units
Dryer power at full load, kW 1.33 1.34 1.34 1.4 1.7 1.6 1.6 1.6
Workplace Full-Feature
units
Dryer power at full load, hp 1.8 1.8 1.8 1.9 2.3 2.2 2.2 2.1
Workplace Full-Feature
units
Dryer power at no load, kW 1.2 1.2 1.2 1.2 1.5 1.4 1.4 1.4
Workplace Full-Feature
units
Dryer power at no load, hp 1.6 1.6 1.6 1.7 2.1 1.9 1.9 1.9
Workplace Full-Feature
units
Refrigerant type, R410A R410A R410A R410A R410A R410A R410A R410A
Workplace Full-Feature
units
Refrigerant quantity, kg 1 1 1 0.8 1 1 1 0.9
Workplace Full-Feature
units
Refrigerant quantity, lb 2.3 2.1 2.1 1.8 2.3 2.2 1.2 1.9
Workplace Full-Feature
units
Cooling water l/min 50 50 50 50 50 50 50 50
consumption (at water
inlet temperature below
35 ˚C and temperature
rise of 15 ˚C), water-
cooled units
Cooling water cfm 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77
consumption (at water
inlet temperature below
95 ˚F and temperature
rise of 27 ˚F), water-
cooled units
Cooling water l/min 75 75 75 75 75 75 75 75
consumption (at water
inlet temperature
between 35 and 40 ˚C
and temperature rise of
10 ˚C), water-cooled
units
7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi
Cooling water cfm 2.65 2.65 2.65 2.65 2.65 2.65 2.65 2.65
consumption (at water
inlet temperature
between 95 and 104 ˚F
and temperature rise of
18 ˚F), water-cooled
units
Oil capacity, air-cooled l 23 23 23 23 23 23 23 23
units
Oil capacity, air-cooled US gal 6.08 6.08 6.08 6.08 6.08 6.08 6.08 6.08
units
Oil capacity, air-cooled Imp gal 5.06 5.06 5.06 5.06 5.06 5.06 5.06 5.06
units
Oil capacity, water- l 17.9 17.9 17.9 17.9 17.9 17.9 17.9 17.9
cooled units
Oil capacity, water- US gal 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73
cooled units
Oil capacity, water- Imp gal 3.94 3.94 3.94 3.94 3.94 3.94 3.94 3.94
cooled units
Sound pressure level dB(A) 66 66 66 66 66 66 66 66
(according to ISO 2151
(2004))
General
Digital outputs
Digital inputs
Analog inputs
This vessel can contain pressurized air. This can be potentially dangerous if the equipment is misused.
This vessel must only be used as a compressed air/oil separator tank and must be operated within the
limits specified on the data plate.
No alterations must be made to this vessel by welding, drilling or other mechanical methods without the
written permission of the manufacturer.
The pressure and temperature of this vessel must be clearly indicated.
The safety valve must correspond with pressure surges of 1.1 times the maximum allowable operating
pressure. It should guarantee that the pressure will not permanently exceed the maximum allowable
operating pressure of the vessel.
Use only oil as specified by the manufacturer.
www.atlascopco.com