0% found this document useful (0 votes)
26 views

Test Report12324

The report details insulation resistance tests on two 3-phase induction motors at a project site. Motor SBR2 failed the test by having a resistance below standards, while SBR1 passed.

Uploaded by

jpsablan.gccm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views

Test Report12324

The report details insulation resistance tests on two 3-phase induction motors at a project site. Motor SBR2 failed the test by having a resistance below standards, while SBR1 passed.

Uploaded by

jpsablan.gccm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Parada, Valenzuela City

Telefax: (+632) 291-1261


VAT Reg TIN: 218-113-464

INSULATION TEST REPORT

PROJECT TITLE: MACTAN NEWTOWN SOFT STARTER DATE: January 23, 2024
CUSTOMER: ESTATE MANAGEMENT/THE MACTAN NEWTOWN
REF. P.O #: TMNEA-23-00010
LOCATION: NEWTOWN MACTAN,LAPU-LAPU CITY CEBU

TYPE: 3 PHASE INDUCTION MOTOR


BRAND: TECO Rated Voltage: 380V
Model: AEEFS1-YC1 TEMP: 30
Designation:SBR2 Current rating: 83.4A
Location: PUMP ROOM

I. INSULATION RESISTANCE TEST (Ω)


VOLTAGE SETTING: 500

CONNECTION TEST VALUE IN MΩ


W1 -V1 76.50
W1-U1 65.40
U1-V1 89.40
W2-V2 71.10
W2-U2 126.00
U2-V2 113.00

REMARKS: Minimum resistance per ANSI/NETA 2017 Table 100.1


is 100 Mega Ohms.
Winding of SBR2 failed the minimum resistance as per
Ansi/NETA standards.
Repair/Replacement is recommended.

WITNESSED BY:

ENGR. JONATHAN M. DELA CRUZ,REE ENGR. GILBERT P. GUERRERO,PEE


TEST CONDUCTED BY: CERTIFIED BY:
Parada, Valenzuela City
Telefax: (+632) 291-1261
VAT Reg TIN: 218-113-464

INSULATION TEST REPORT

PROJECT TITLE: MACTAN NEWTOWN SOFT STARTER DATE: January 23, 2024
CUSTOMER: ESTATE MANAGEMENT/THE MACTAN NEWTOWN
REF. P.O #: TMNEA-23-00010
LOCATION: NEWTOWN MACTAN,LAPU-LAPU CITY CEBU

TYPE: 3 PHASE INDUCTION MOTOR


BRAND: TECO Rated Voltage: 380V
Model: AEEFS1-YC1 TEMP: 30
Designation:SBR1 Current rating: 83.4A
Location: PUMP ROOM

I. INSULATION RESISTANCE TEST (Ω)


VOLTAGE SETTING: 500

CONNECTION TEST VALUE IN MΩ


W1 -V1 204.00
W1-U1 163.00
U1-V1 146.00
W2-V2 236.00
W2-U2 144.00
U2-V2 165.00

REMARKS: Minimum resistance per ANSI/NETA 2017 Table 100.1


is 100 Mega Ohms.
Winding of SBR1 passed the minimum resistance as per
Ansi/NETA standards.

WITNESSED BY:

ENGR. JONATHAN M. DELA CRUZ,REE ENGR. GILBERT P. GUERRERO,PEE


TEST CONDUCTED BY: CERTIFIED BY:

You might also like