0% found this document useful (0 votes)
227 views46 pages

SPG 40

Uploaded by

ISGE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
227 views46 pages

SPG 40

Uploaded by

ISGE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

Operating Manual

Test and
Fault Locating System
SPG 40

Issue 9 (01/2017) – EN
128312675
3
Manufacturer:

Seba Dynatronic
Mess- und Ortungstechnik GmbH
Dr.-Herbert-Iann-Str. 6
96148 Baunach
Germany

 +49 (0) 9544 / 68-0


 +49 (0) 9544 / 68-2273

E-mail: [email protected]
Internet: www.megger.com

Copyright
The information contained in this document is for informational purposes only and is subject to
change without notice. Megger makes no warranty of any kind with regard to the information
contained in this manual, including but not limited to the implied warranties of merchantability
and fitness for a particular purpose. Megger shall not be liable for errors contained herein, nor
for incidental or consequential damages from the furnishing of this information.
This manual contains proprietary information that is protected by copyright. All rights are
reserved.
© Megger 2005
4
Index
1 Safety Advice 6
1.1 General Advice 6
1.2 Electrical Advice 8

2 Technical Description 10

3 Scope of delivery and Options 11

4 Introduction 12
4.1 Stand-alone unit 12
4.2 Combined fault locating system Surgeflex 40 (SFX 40) 13

5 Safety 14
5.1 Key Switch 14
5.2 FΩ protection device 14
5.3 FU-Safety Circuit 15
5.4 VDE clauses 0104 16
5.4.1 Mobile (non-stationary) test unit 16
5.4.2 Area of Danger 16
5.4.3 Emergency OFF button 16

6 Operating 17
6.1 Connections and controls 17
6.2 Electrical Connection 19
6.2.1 Connection Sequence 19
6.2.2 Safety Earth 20
6.2.3 Auxiliary Earth / FU-Safety Circuit 20
6.2.4 Connecting the HV-line to a faulty cable 21
6.2.5 Cordoning off open cable ends 23
6.2.6 Electrical connection of a time domain reflectometer 23
6.2.7 Connecting the SPG 40 to the mains 23
6.3 Menus and Mode Operation 24
6.3.1 Switching On 24
6.3.2 Rotary Selector 25
6.4 Remote control using Teleflex SX 25
6.5 High Voltage control 26
6.5.1 High Voltage HV on 26
6.5.2 High voltage is active 26
6.5.3 Turning OFF high voltage 26

7 Functions 27
7.1 Setup- Menu 27
7.2 Safety Menu 28
7.3 Testing Mode 29
man_spg40_en_09-4.doc
5
7.3.1 Insulation Resistance Test 29
7.3.2 40 kV – DC Proof Test 30
7.4 Operation mode Breakdown Recognition 31
7.5 Fault Prelocating 32
7.5.1 Prelocating mode ARM (Arc Reflection Method) 32
7.5.2 Prelocating mode ICE (Impulse Current Equipment) 34
7.5.3 Prelocating mode Decay 35
7.5.4 Prelocating mode ICE-Plus (optional) 36
7.6 Pinpointing Mode 39
7.6.1 Acoustic method 39
7.6.2 Step Voltage Method 41
7.7 Burn Mode 42

8 Shutting Down the Fault Location System 43

9 Care and Maintenance 44

10 Service and Service Contacts 45


6
1 Safety Advice

1.1 General Advice

General
This manual contains basic advice for the installation and operation of
the product. It is essential to make this manual accessible to the
authorised and skilled operator. He needs to read this manual closely.
The manufacturer is not liable for damage to material or humans due to
neglectance of this manual and this and the following safety advices.

Setting up and operating the instrument may only be done by authorised


and skilled personnel. According to DIN VDE 0104 (EN 50191) and DIN
VDE 0105 (EN 50110) as well as the accident prevention regulation
(Unfallverhütungsvorschrift UVV), skilled personnel is defined as a
person who is qualified to work, judge and realize dangers due to his
professional education, knowledge and experience and his knowledge
of applicable regulations. Locally applying regulations have to be
observed.

Working with equipment of Megger


All electrical regulations of the country where the instrument is operated
have to be observed as well as national regulations for prevention of
accidents and existing regulations for the safety and operation of
equipment of the involved companies. After working with the equipment,
make sure to de-energise, protect against re-energising, discharge,
ground and short-circuit the instrument and installations that have been
worked on. Original accessories ensure safe operation of the equipment.
It is not allowed and the warranty is lost if other accessories than the
original ones are used with the equipment. Repairs and service must
only be done by Megger or authorised service departments of Megger.
Megger recommends having the equipment serviced and checked once
per year at a Megger service location.

Intended application
Safe operation is only realised when using the equipment for its
intended purpose (see chapter "Introduction"). Using the equipment for
other purposes may lead to human danger and damage of equipment of
involved installations. The limits described under technical data may not
be exceeded. Operating products of Megger in condensing environment
may lead to flash-over, danger and damage. The instruments should
only be operated under tempered conditions. It is not allowed to operate
Megger products at direct contact with humidity, water or near
aggressive chemicals nor explosive gases and fumes.

Behaviour at malfunction of normal operation


The equipment may only be used when working properly. When
irregularities or malfunctions appear that cannot be solved consulting
this manual, the equipment must immediately be put out of operation
and marked as not functional. In this case inform the person in charge
who should inform the Megger service to resolve the problem. The
instrument may only be operated when the malfunction is resolved.

man_spg40_en_09-4.doc
7
Operation in traffic environment
To ensure safety for operators and traffic, the country-specific
regulations must be observed.
Transport and operating position
The device may only be operated and transported in an upright
(standing) position!

Using cardiac pacemaker


Physical processes during operation of high voltage may endanger
persons wearing a cardiac pacemaker when near these high voltage
facilities.

Fire fighting in electrical installations


 Recommended extinguishing agent: carbon dioxide (CO2)
 Carbon dioxide is electrically non conductive and does not leave
residue. It is safe to use in energized facilities as long as the
minimum distances are observed.
 It is essential to observe the safety instruction on the extinguishing
agent.
 Applicable is DIN VDE 0132.
8
1.2 Electrical Advice

Dangers when operating with high voltage


Special attention and safety-conscious behaviour is needed when
operating high voltage facilities and especially non-stationary equipment.
The regulations VDE 0104 about setting up and operation of electric test
equipment, i.e. the corresponding EN 50191 as well as country-specific
regulations and standards must be observed.

Advice about handling high voltage


Safety installations may not be by-passed nor deactivated.
Operation requires minimum two people whereas the second person
must be able to activate the emergency-OFF button in case of danger.
To avoid hazardous electric charges of metallic parts in the vicinity, all
metallic parts must be grounded.
To avoid drawing dangerous arcs, switching should only be done in
de-energized condition.
HV test equipment and burn-down equipment is short-circuit proof.
Hazardous voltage may be present if a short circuit is opened during
operation. If measuring short-circuit current is necessary, it is advisable
to connect an arrester in parallel with the measuring instrument (e.g.
90 V glow arrester).
Adequate safety precautions must be met when using transient
measuring techniques, using HV test instruments or surge generators.
The equipment and all accessories must be connected according to
applicable standards VDE, EN or DIN as well as country-specific
regulations.

Always follow the 5 Safety Rules !


These five safety rules must always be followed when working
with high voltage:

1. De-energise
2. Protect against re-energising
3. Confirm absence of voltage
4. Ground and short-circuit
5. Cover up or bar-off neighbouring energised parts

man_spg40_en_09-4.doc
9
10
2 Technical Description

Display ¼ VGA display for status, input, help and


results, „single-button-operation“
Insulation Test
Voltages 500 ... 5000 V, in steps of 500 V
Ranges 1 kΩ, 1 MΩ, 100 MΩ
DC Testing 0 … 40 kV DC
Leakage current display:
0 ... 1/10 mA auto-ranging
(0 … 100 mA during changing phase)
Breakdown recognition 0 ... 40 kV;
Burning 0 ... 8 kV ; 700 mA
0 ... 20 kV ; 100 mA
Surge generator SPG 40-25 0 … 12.5 kV and 0 … 25 kV
SPG 40-32 0 … 16 kV and 0 … 32 kV
Surge generator - options: 0 ... 4 kV, 0 ... 8 kV or 0 … 4/8 kV
0 ... 3 kV, 0 ... 6 kV or 0 … 3/6 kV
Surge energy max. 1000 Joules in each range
(optional: 2000 Joules)
Surge rate 3 … 10 sec. and single pulse
Sheath fault location 0 ... 5 kV, 0 … 10 kV,
adjustable current output
pulse ratio: continuous, 1:3 ; 1:4; 1:6 (sec)
HV-Fault Prelocation (with optional TDR)
ARM (integrated filter),
Impulse Current (integrated coupler)
Decay (integrated coupler)
ICE-Plus
Operating temp. -10 ... + 50 °C
Mains supply 230 VAC ±10% (optional: 115 VAC ±10%);
50 / 60 Hz (Sinus)
Power input 1.7 kVA max.
AC mains fuses 2 x T 8 A (for 230 V)
2 x T 16 A (for 115 V)
Protection category IP20 (according to EN 60529)
Dimensions 545 x 430 x 1050 mm (L x W x H)
Weight approx. 116 kg

man_spg40_en_09-4.doc
11
3 Scope of delivery and Options

Scope of delivery 1:

Description Item
Test and fault locating device SPG 40
Set of cables VL SPG-40
consisting of:
AC mains connection NKG S2
Earthing connection cable EK 1
Auxiliary earth cable MK 54-B
High voltage connection
HSK 27
(25 on manual cable reel)
HKZ 02-1 (red) and
MC connection adapter
HKZ 03-1 (black)
Operating manual

Options:

Description Item
NH adapter 700-10-0437
Operational earth connection with brass
EKS 80
screw-on clamp
Operational earth connection adapter
EKD 80
with big and flexible handle-screw
TDR (Time Domain Reflectometer) Teleflex SX, T 3060 or others
Surge Wave Receiver Digiphone
Step Voltage Indicator ESG NT
Line Location System Ferrolux or others
Dimensions incl. foot plate
External operating panel (B x H x T):
500 x 430 x 240 mm
External safety device
1006953
with HV operaring function
External safety device 820003206

1
If permanently installed in a test van or on a trolley, the scope of delivery may be different.
12
4 Introduction

The SPG 40 has been developed for fault locating in low and medium voltage
networks. Its functions are:
 DC-Testing,
 Breakdown recognition,
 Measuring leakage resistance,
 ARM filter for prelocating with a TDR (optional),
 Further prelocating methods (Decay, ICE, ICE-Plus)
 Pinpoint locating with step voltage or acoustic method,
 Burning.

4.1 Stand-alone unit

The SPG 40 uses operation with just one rotary selector. For
safety reasons the high voltage setting must be activated with a separate
hardware button.
The operating panel is located in the top panel of the SPG 40 but it is
optionally available as external control unit.

man_spg40_en_09-4.doc
13
4.2 Combined fault locating system Surgeflex 40 (SFX 40)

Combined with a reflectometer of type Teleflex SX or T3060, the SPG 40 is


enhanced by the most common HV pre-locating methods and so upgraded to
a fully fledged fault locating system (SFX 40).

While – when combined with the T3060 – the operating steps are to be carried
out individually on the operating elements of the respective device, the
Teleflex SX is suitable for direct control of the SPG 40. Supplemented by the
necessary HV operating elements (Teleflex SX-M), it can thus be used for
comprehensive remote control of a spatially separate SPG 40 in a test van
(Compact City).
14
5 Safety

WARNING
Risk of fatal injury from electric shock!
Switching off or bypassing the safety equipment described in
the following two sections will put persons and materials at
significant risk. For this reason, prior to a manual shut-off the
operator must ensure that the earthing conditions allow the
device to be worked with safely on his own responsibility by
taking suitable measures and measurements.

Because the SPG 40 generates a hazardous voltage of more than 1 kV it must


be operated by trained specialists only. The following safety measures should
be followed:

5.1 Key Switch

For product liability reasons measuring devices generating hazardous


voltages have to be protected against accidental activation by unauthorised
users. For this purpose the SPG 40 has a key switch, to avoid unauthorised
operation by persons other than the operator. (see page 17, Fig. 2)

5.2 FΩ protection device

For safe earthing the loop ‘operating earth’ – ‘safety earth’ is monitored
(indicated in the following figure with o). The resistance between operating
and safety earthing must not exceed 6 Ω, otherwise the device cannot be
switched to ‘stand-by’. If this should happen during operation (i.e. earth clamp
gets disconnected), the SPG 40 will immediately shut off and ground the cable
and the HV part of the unit. The menu ‘safety circuit’ will appear, signaling
‘FOHM loop resistance – error’. It may be necessary to make a connection xa.
operating earth – safety earth to meet the requirements (see chapter 6.2.4).
In some rare cases it is possible that the station earthing loop between
operational earth and safety earth does not have a resistance lower than 6 Ω.
Providing that all of the conditions set out in chapter 6.2.2 are fulfilled,
the protective monitoring may be switched off in the setup in this case (see
chapter 7.1). This is done at operators responsibility. An indication will show in
the main menu that F Ω protection is switched off.

man_spg40_en_09-4.doc
15
5.3 FU-Safety Circuit

Also for safety for the operator, the auxiliary earth connection [23] must be
connected to a ground rod as close as possible to the SPG 40. The FU-safety
circuit of the SPG 40 will immediately shut the unit off and ground the cable
and the HV part of the unit over a resistor if the voltage between the
instrument and the surrounding earth gets higher than 33 V AC / -40 V DC, or
if the resistance of the earth loop between safety earth and auxiliary earth gets
higher than 150 kΩ. The menu ‘safety circuit’ will appear on screen, signaling
‘FU – step voltage - error’.

HV-connecting cable (sheathed)

OE
power cable
e.g. without sheath
FΩ < 6Ω
a.
PE
FU

AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth
Fig. 1: FΩ – monitoring
In some areas the ground resistance between instrument (earthed at station
earth) and the terrain where the instrument is set up may be higher than
150 kΩ due to ground conditions (e.g. dry sand, rock). Providing that all of
the measures described in chapter 6.2.3 have been taken, the step voltage
monitoring may be switched off in the setup in this case (see chapter 7.1).
This is done at operators responsibility. An indication will show in the main
menu that FU protection is switched off.

FU
16
5.4 VDE clauses 0104

5.4.1 Mobile (non-stationary) test unit


VDE standard 0104 states that the set-up of the instrument, including the
beginning of the cable to be measured, represents a non-stationary test
installation and is considered as a test site without protection against human
contact. The same also applies to the end(s) of the cable to be tested.

5.4.2 Area of Danger


Test sites without protection against direct human contact are considered
‘areas of danger with various zones of danger levels’ and have to be cordoned
off, secured and marked accordingly.

5.4.3 Emergency OFF button


Test sites in general have to be equipped with an emergency OFF button.
The SPG 40 has a red emergency OFF button on the face plate (see page 17,
Fig. 2). An external safety device with an emergency stop switch is optionally
available (820003206). It can be connected to the jack [6] on the rear
connecting panel (see page 18, Fig. 3) When using the SPG 40 without the
external emergency OFF button, the standard dummy plug has to be placed in
jack [20] so that the device can be switched on.

man_spg40_en_09-4.doc
17
6 Operating

6.1 Connections and controls

1. 2. 3. 4. 5. 6. 7.
white green red
Fig. 2: Controls

Element Function
1. emergency OFF button
2. push-button – white on/off switch
press: activates system controls
lit: device is switched on
3. key switch
4. push-button – green: HV-ON key
lit: HV readiness for switching on
(high voltage can be switched on)
press: Switches the high voltage on; earthing of the
output is cancelled
5. push-button - red : HV-OFF key
lit: HV-operation
(high voltage present at output)
press: switches high voltage off
(output will be grounded over a discharge
resistor)
6. rotary selector with enter function
7. display
18

8 9 10 11 12 14 13 15 16 17 18 16

23 22 21 20 19

Fig. 3: Connections - back

8. CAN bus connection to external control panel (optional)


9. Control connection to external control panel (optional)
10. CAN bus connection to Teleflex SX / T 30-E control panel
11. Control line to separated control elements (1)
SPG 40-1 (since 2015): Teleflex SX-M, system control panel
of a test van or external safety
device
SPG 40 (until 2014): „T30-E HV-Control“ box
12. Safety earth
13. ARM trigger
14. ARM signal
15. Safety circuit for earth connection and door contacts
16. Fuses (1) 115 V: T16 A H250 ;
230 V: T8 A H250
17. Protected 13.5 VDC power output for TFX SX and T30-E
(max. 60 W)
18. Integration and status check of an external HV connector
19. AC power supply 115 / 230 V (1) / 50/60 Hz
20. External emergency-off-button and signal lights (see "options")
21. Output of signal for surge pulse mode (impulse current mode)
22. Output of signal for decay mode
23. Auxiliary earth connection for FU-protection

(1)
depending on instrument version,
see type label on instrument.

man_spg40_en_09-4.doc
19
6.2 Electrical Connection

During electrical connection, please observe the safety precations in section


1.2.

6.2.1 Connection Sequence


The electrical connection must be carried out in the sequence shown in the
figure. Connection to the mains occurs last!

230 V (optional 110 V),


50/60 Hz (Sinus)

Connection of the earthing cable


Connection of the FU cable (auxiliary earth)
Connection to the test object
Connection to the mains
Connection of the external safety device (optional)
20
6.2.2 Safety Earth
The SPG 40 has to be earthed before use. To do so connect the protective
earth connection [10] to a good safety earth (e.g. station earth, etc.) using the
earth lead EK1 supplied.
Note that the earthing clamp should only be attached to clean metallic points
of contact.

The device should never be operated without the earth lead being
connected. The earth lead establishes the connection between the
device and the safety earth and ensures that the device is touch-
proof.
The earthing provided through the earth contact of the mains
connection is not sufficient.
Without the earth lead being connected, the housing leakage
current could exceed 3.5 mA, if the earth connection to the wall
socket is interrupted (safety hazard according to EN 61010).

6.2.3 Auxiliary Earth / FU-Safety Circuit


Connect the auxiliary earth connection [23] to a earthing rod as close as
possible to the SPG 40 with the connecting cable MK 54-B supplied. The FU-
safety circuit of the SPG 40 will immediately shut the unit off and ground the
cable and the HV part of the unit if the voltage between the instrument and the
surrounding earth gets higher than 33 V AC / -40 V DC, or if the resistance of
the earth loop between safety earth and auxiliary earth gets higher than
150 kΩ.
If the safety circuit menu appears and the “FU” fault is reported after switching
the system on despite the connected auxiliary earth, the following tips may
provide a remedy:
• Try inserting the earthing rod in other locations which may be more
suitable. In heavily built-up areas, the gaps between the concrete
slabs can be used, for example.
• Use water to moisten the location where the earthing rod has been
inserted.
• Attach the auxiliary earth to a foundation earth (e.g. a lightning
protection system). Do not use the same foundation earth to which
you have already connected the main earthing cable.

man_spg40_en_09-4.doc
21
6.2.4 Connecting the HV-line to a faulty cable
The HV-connecting cable has to have a minimum length of 25 m (scope of
delivery) to avoid excess currents. These currents could develop due to the
discharge characteristic of the surge capacitor when the flash-over in the
cable occurs at a very short distance of the point of connection.

SPG 40 HV-connecting cable (shielded)

power cable
OE
i.e. with shield
FΩ < 6Ω
PE
FU

AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth

Fig. 4: Connecting to LV cable with sheath

SPG 40 HV-connecting cable (shielded)

OE a.
power cable
FΩ < 6Ω i.e. without shield

PE
FU

AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth

Fig. 5: Connecting to a multi-conductor cable without sheath


22

a) Testing, acoustic field pinpoint locating, prelocation (with TDR)

If possible the operating earth of the HV connection line should be connected


to the earthed shield of the faulty cable (Fig. 4).
If no sheath is available, or in case of a ‘phase – phase fault’, the operating
earth should be connected to one of the two faulty conductors. This core now
has to be connected to the operating earth or a PEN-conductor using an earth
bridge xa.x (Fig. 5). Without this bridge the SPG 40 could not be turned on
due to the F-Ohm protection (see chapter 5.2).
The center conductor of the HV connecting cable is connected to the faulty
phase.

b) Sheath testing / Step voltage pinpoint locating


Shielded cables: the shield of the object to be tested has to be separated from
the earth on both ends and connected to the main conductor of the HV
connecting cable.
Unshielded cables: the coax "centre" conductor of the HV feed line is
connected to the cable shield. The operating earth (shield) of the HV
connecting cable has to be connected to the operating earth of the station.

HV-connecting cable (shielded)

power cable
with shield
FΩ < 6Ω a.
PE
FU PE

AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth

Fig. 6: Connecting to the cable shield

man_spg40_en_09-4.doc
23
6.2.5 Cordoning off open cable ends
As the high voltage pulses or DC voltage applied to the faulty cable are
hazardous, the cable ends have to be cordoned off in accordance with local
safety regulations (i.e. VDE 0104 regulations). The user has to make sure that
also the ends of branches (tees) are cordoned off and protected.

6.2.6 Electrical connection of a time domain reflectometer


The combination of SPG 40 and a reflectometer is usually supplied already
wired ex works on a trolley or as a test van assembly (Compact City). Two
individual devices, however, can also be quickly and easily combined on site
using the required connection cable.

For notes on connecting the reflectometer, please read the


corresponding operating manual.

6.2.7 Connecting the SPG 40 to the mains


Now the SPG 40 can be connected to the mains. Make sure that the mains
voltage is the same as the supply voltage of the SPG 40 (230 V AC or
115 V AC, according to the type label of the instrument).

! Notes concerning generator operation: The device may only be operated


using a generator if this has been approved by Megger. Megger must
therefore always be consulted before initial use of a generator! Generators
which do not supply a sine wave voltage must not be used!
24
6.3 Menus and Mode Operation

6.3.1 Switching On
Only when the AC mains connection is not plugged in, the SPG 40 is
completely turned off. The moment that the AC mains connector is plugged
into a power supply, the SPG 40 is in stand-by mode – no button is lit yet.
Press the white push button [2] to start the SPG 40.
The white push-button lights up. The control and safety circuits are activated
and system controls switches the operating menu on. The device will
automatically go on ‘stand-by’.
There is no high voltage generated at this point as the HV outlet is still
earthed.

SPG 40
Select Menu FΩ
10:32:16

FU
Breakdown
Setup Testing
Recognition

Prelocating Pinpointing Burning

Fig. 7: Main menu


For a more detailed explanation of the main menu see chapter 7.

man_spg40_en_09-4.doc
25
6.3.2 Rotary Selector
Turn = select or change values
Press = confirm (enter function)

Operation is made simple by the functions. Modes are selected


in the menu by turning, and activated by pressing the rotary selector [6].
Within a mode, values are changed by turning. To confirm the selected
settings the rotary selector has to be pressed again (ENTER).
The main menu operating modes are explained in chapter 7, page 27.

6.4 Remote control using Teleflex SX

In remote control mode, all operating modes (with the exception of the optional
ICE Plus locating method) can be controlled directly from the Teleflex SX. The
SPG 40 display is darkened in this mode and the encoder [6] has no function.
The remote control mode on the Teleflex SX must be activated before
measurement is begun.

Remote control
active

To do so, SPG 40 and Teleflex SX must be connected to each other properly


and both must be switched on. Aside from that, the firmware version on both
devices must support remote control mode.

For notes on the necessary firmware versions, on activating the


remote control mode and on operating the Teleflex SX, please read
the Teleflex SX operating manual.
26
6.5 High Voltage control

6.5.1 High Voltage HV on


Once the test mode has been selected the "HV enabled" mode is established
by activating the field "HV – ON". The command ‘push green button’ appears
in the status line at the bottom of the screen once HV – ON has been entered.
Subsequently, the green illuminated button [4] must be pressed (if this does
not happen within 5 seconds, the “HV – ON” field must be re-activated).
Now the SPG 40 is in "HV enabled" mode: the red button [5] lights up as the
light in the green button [4] goes off and HV is activated. Now the selected
mode is active. This configuration means Danger –High Voltage enabled",
shown in the display as the high voltage arrow-symbol, even if no HV is
generated at the output. The soft-discharge grounding is deactivated.
Note: If the green button [4] goes off without the red button [5] lighting up (e.g.
broken light bulb), the device is also on ‘High voltage enabled’ and High
voltage could be on!

6.5.2 High voltage is active


In the testing, breakdown recognition, ARM and pinpoint locating (acoustic
field method) modes the desired value of the voltage is first pre-set by turning
the rotary selector. High voltage is present at the output after the enter button
has been pushed.
The red push-button [5] is lit.

! In the burning and pinpoint locating (step voltage) modes the voltage
adjustment does not have to be confirmed with the rotary selector but is
immediately active at the output.

6.5.3 Turning OFF high voltage


Turning the high voltage off is done by pressing the red lit button [5] or by
activating the field HV-OFF. The HV source will be shut off and the cable
under test as well as the SPG 40 will be grounded over a discharge resistor.
The display will show the safety ground symbol. The instrument is in the state
"HV stand-by" and the green button is lit.

man_spg40_en_09-4.doc
27
7 Functions

7.1 Setup- Menu

SPG 40
10:32:16

Day: 10 Hour: 10
Month: 05 Minute: 32
Year: 2005 Second: 16
return

60 English
Date/Time
Contrast Language

active active
return
F-Ohm F-U

Fig. 8: Setup menu


28
7.2 Safety Menu

Safety Circuit
FU – step voltage ok
FOHM loop resistance error
Emergency Off Switch ok
External Emergency Off Switch ok
Key switch ok
Over temperature ok
System ok
HV connector ok
Earth connection ok
Rear door ok

return clear

Fig. 9: Menu safety circuit


The Safety Menu will appear automatically in case of any error.
To return to the normal operating mode the error must be eliminated and
confirmed with “clear”.

man_spg40_en_09-4.doc
29
7.3 Testing Mode

The Testing mode offers the possibility of an insulation resistance test up to 5


kV or a DC proof test up to 40 kV.

7.3.1 Insulation Resistance Test

Insulation Resistance

5000 V 12 MΩ

Output Voltage Insulation Resistance

return 5000 V HV-ON


max. voltage

push green button HV-OFF


enabling HV source, please wait ...
time stopped, no breakdown occurred

Fig. 10: Menu Insulation Resistance Test

1. Select operating mode ‘testing’ in main menu.


2. Select 'Insulation Test 5 kV'
3. Activate field “HV-ON”.
4. Press green button (within 5 sec.).
5. Set maximum voltage in steps of 500 V.
6. Read insulation resistance value.
7. Turn off with the field “HV-OFF” or by pushing the red button [5].
30
7.3.2 40 kV – DC Proof Test

Testing – 40 kV
750 kΩ
9000 V 12 mA

Output Voltage Leakage Current 0 – 100 mA

9000 V Testing Time


Timer on
max. voltage 45 min

Remaining Time
return HV-ON
12:52 min

push green button HV-OFF


enabling HV source, please wait ...
timer is active …
test over, no breakdown
time stopped, no breakdown occurred
Fig. 11: Menu DC-Testing

Operation :

1. Select operating mode ‘testing’ in main menu.


2. Activate field “HV-ON”.
3. Press green button (within 5 sec.).
4. Set maximum voltage
(increase in 2 kV steps, decrease in 1 kV steps).
If the clock is activated the voltage setting cannot be changed
5. Set clock (only if wanted).
Total testing time and remaining test time are shown.
Testing with timer : breakdown recognition active
Testing without timer : insulation resistance measurment
6. Turn off with the field “HV-OFF” or by pushing the red button [5].

If a breakdown occurs during the test with the timer turned on, the SPG 40 will
shut off and ground the cable over a discharge resistor and the breakdown
voltage will be displayed (identical to 'Breakdown recognition'-mode). If a
breakdown occurs during testing but with the timer turned off, the SPG 40 will
not switch off automatically but will continue to show the insulation resistance.
The insulation resistance is shown on the top right corner of the display as
soon as a minimum voltage of 100 V and a minimum current of 10 µA are
measured. The displays of insulation resistance and leakage current
measurement are auto-ranging.

man_spg40_en_09-4.doc
31
7.4 Operation mode Breakdown Recognition

Breakdown recognition is the simplest way of finding the breakdown voltage.


The operator sets the maximum voltage as an upper limit for the automatic
test. The SPG 40 raises the output voltage slower than in testing mode up to
the selected maximum voltage with a time ramp of between 0.8 and 4 kV/sec
until a breakdown occurs. After a breakdown occurred, the breakdown voltage
is shown.
This mode does not have a timer function as in testing, but the SPG 40 will
automatically turn off the high voltage after the breakdown has occurred.
Beside the 40 kV range there is an 8 kV range available for better resolution of
the result.
Breakdown recognition

550 V 12 mA

Output Voltage Leakage Current


Breakdown Voltage

return 2000 V HV-ON


max. voltage

push green button HV-OFF


enabling HV source, please wait ...
set voltage – enter
breakdown has occurred

Fig. 12: Menu Breakdown Recognition

Operation :

1. Select “breakdown recognition” in main menu.


2. Select voltage range for breakdown recognition 8 kV or 40 kV
3. Activate field “HV-ON”.
4. Push green button (within 5 sec.)
5. Select maximum voltage (set value)
6. Press the rotary selector to start test, voltage will start rising.
If a breakdown occurs, the breakdown voltage is shown at the top left.
The information line at the bottom of the display will show “breakdown
has occurred” and the SPG 40 will turn off the high voltage and ground
the tested cable and the SPG 40 over a discharge resistor. If no
breakdown occurs the high voltage remains on.
7. Turn off with the field “HV-OFF” or by pushing the red button [5]
32
7.5 Fault Prelocating

7.5.1 Prelocating mode ARM (Arc Reflection Method)


The ARM method requires a TDR (Time Domain Reflectometer) to be
connected. Selecting this mode will internally connect the ARM filter and surge
generator. Connect the signal connection of the TDR to the connection for
ARM [14] and the TDR trigger connection to the ARM Trigger [13].
Releasing a "Single Shot" will discharge the surge capacitor of the SPG 40 via
an inductive filter (choke) into the faulty cable.

Wear Ear Protection


Surge operation can cause high and sudden noise levels. It is
strongly recommended to wear hearing protection during surge
operation. Keep in mind that this will limit the operators
awareness for ambient dangers.

Ventilation
The surge operation creates ozon. It is necessary to operate
the instrument under well ventilated condition to keep ozon
levels below limit values for the operator.

ARM - Prelocating
(Arc Reflection Method)

6000 V 12.5 kV
Range
Output Voltage

6000 V Single Shot


max. voltage

return HV- ON

push green button HV - OFF


enabling HV source , please wait ...
set voltage – enter

Fig. 13: Menu Arc Reflection Method ARM

man_spg40_en_09-4.doc
33
Operation :

1. Select ‘Prelocation’ in main menu.


2. Activate field ‘ARM’.
3. After selecting the desired voltage range the above menu (Fig. 13: Menu
Arc Reflection Method ARM) appears.
Note: When using half the voltage of the selected range only a quarter of
the energy is available or when using 1/3 of the voltage, only 1/9 of the
energy is available.
4. Activate field “HV-ON”.
5. Push green button (within 5 sec.)
6. TDR adjustments:
6 a. Adjust settings of the connected TDR and acquire reference trace
with the SPG 40 still set at 0 kV.
Also when retrieving a new reference trace at a later time, the
voltage should again be set to 0 kV to avoid interference with the
power supply.
Remember to set the trigger delay of the TDR to 500 μs.
6 b. Arm trigger of the TDR for triggering the fault trace.
7. Select voltage.
8. Release single pulse: By activating the field “single pulses” only one
single pulse is released into the faulty cable and will create a flash-over.
This will trigger the TDR to store the fault trace.
9. Turn off with the field “HV-OFF” or by pushing the red button [5].
34
7.5.2 Prelocating mode ICE (Impulse Current Equipment)
The ICE method (also called "surge pulse" method) requires a TDR
(Time Domain Reflectometer) to be connected to the connection I [21]. The
TDR must be set to ICE-mode.

Wear Ear Protection


Surge operation can cause high and sudden noise levels. It is
strongly recommended to wear hearing protection during surge
operation. Keep in mind that this will limit the operators
awareness for ambient dangers.

Ventilation
The surge operation creates ozon. It is necessary to operate
the instrument under well ventilated condition to keep ozon
levels below limit values for the operator.

ICE

8000 V 12.5 kV
Range
Output Voltage

8000 V Single Shot Timer on


max. voltage

return 5s HV- ON
Timer
push green button HV-OFF
enabling HV source, please wait ...
set voltage – enter
Fig. 14: Menu ICE (impulse current / surge pulse method)
Operation :

1. Select ‘Prelocation’ in main menu.


2. Activate field ‘ICE’.
3. After selecting the desired voltage range the above menu appears (Fig.
14: Menu ICE (impulse current / surge pulse method)).
Note: The impulse energy is 1000 J at full voltage in the respective
selected range. When using half the voltage of the selected range only a
quarter of the energy is available or when using 1/3 of the voltage, only
1/9 of the energy is available.
4. Activate field “HV-ON”.
man_spg40_en_09-4.doc
35
5. Push green button (within 5 sec.)
6. TDR adjustments:
6 a. Adjust settings of the connected TDR.
6 b. Arm trigger of the TDR.
7. Select max. voltage.
8. Release single pulse:
By activating the field “single pulses” only one single pulse is released into
the faulty cable.
This will trigger the TDR to store a ICE-diagram if the settings were
correct. Else change settings of the TDR and release another single
pulse.
9. Turn off with the field “HV-OFF” or by pushing the red button [5].

7.5.3 Prelocating mode Decay


The Decay method requires a TDR (Time Domain Reflectometer) to be
connected to the connection U [22]. The TDR must be set to Decay-mode.

DECAY
1 MΩ
9000 V 9 mA

Output Voltage Leakage Current 0 – 10 mA

9000 V Testing Time


Timer on
max. voltage 45 min

Remaining Time
return HV-ON
12:52 min

push green button HV-OFF


enabling HV source, please wait ...
timer is active …
time stopped, no breakdown occurred

Fig. 15: Menu Decay


36
Operation :

1. Select operating mode ‘Prelocation’ in main menu.


2. Select operating mode ‘Decay’ in prelocation menu.
3. Activate field “HV-ON”.
4. Press green button (within 5 sec.).
5. Adjust settings of the connected TDR.
6. Arm trigger of the TDR.
7. Set maximum voltage (increase by 2 kV, decrease by 1 kV).
8. Voltage rises to where a breakdown occurs (or max. voltage setting). The
breakdown will trigger the TDR to store a Decay-diagram if the settings
were correct. Else change settings of the TDR and increase voltage to
where a breakdown occurs again.
If the clock is activated the voltage setting cannot be changed
9. Turn off with the field “HV-OFF” or by pushing the red button [5].

If a breakdown occurs during the test with the timer turned on, the SPG 40 will
shut off and ground the cable over a discharge resistor and the breakdown
voltage will be displayed (identical to 'Breakdown recognition'-mode).
If a breakdown occurs during testing but with the timer turned off, the SPG 40
will not switch off automatically but will continue to show the insulation
resistance. The insulation resistance is shown on the top right corner of the
display as soon as a minimum voltage of 100 V and a minimum current of 10
µA are measured. The displays or insulation resistance and leakage current
measurement are auto-ranging.

7.5.4 Prelocating mode ICE-Plus (optional)


The ICE-Plus method is not influenced by branches (tees) in LV networks.

ICE-Plus
cableinput : set new cable data
how many sections : 1
section : 1 sectionlength : 500 m
cablediameter : 150 qmm
cabletyp : connection :

return cable data next

Fig. 16: Menu ICE-Plus - cable data

Operation :

man_spg40_en_09-4.doc
37
1. Select operating mode ‘Prelocation’ in main menu.
2. Select operating mode ‘ICE-Plus’ in prelocation menu.
3. Activate field "cable data".
4. Under “cableinput” (at the top) select one of the following:
“accept old cable data” (no changes, continue with step 10)
“modify cable data” (change previous data)
“set new cable data” ( enter a completely new set of data)
5. Enter the number of sections for mixed cables (max. 5 parts)
6. Enter lengths of sections. When dealing with mixed cables, the
exactness of the result depends on how exact the input is. For single
sections the length just has to be changed if the object to be measured is
longer than the pre-set value.
If the length entered is to short and the fault is behind the stated cable
end, this is shown at the bottom of the display with “Faultdistance >
Cablelength”.
7. Select the conductor diameter from the provided values.
8. Selection of cable type. Select one of the following possibilities:
with sheath 4 conductors 5 conductors
without sheath

9. Connection: The following connections are available:


38
10. Confirm the cable data input by pressing “next”.
11. Another menu opens, as shown in the figure below.

ICE-Plus

2000 V

Output Voltage

2000 V single puls 460 m


max. faultdistance

return HV-ON

HV-OFF
Fig. 17: Menu ICE-Plus

12. Activate field “HV-ON”.


13. Press green button (within 5 sec.).
14. Enter max. voltage (set value). This value should be at least 1500 V for
good results (check maximum test voltage of the cable!) and always a
good amount higher than the fault breakdown voltage.
15. Press the field ‘single pulse’. The impulse capacitor is now discharged
into the faulty cable and the fault length shown on the display.
16. Turn off with the field “HV-OFF” or by pushing the red button [5].

man_spg40_en_09-4.doc
39
7.6 Pinpointing Mode

There are two kinds of pinpoint locating to choose from:


 The sound field method with a surge wave generator.
 The step voltage method with a DC output voltage 0 … 5 kV, which can
be pulsed.

7.6.1 Acoustic method

Wear Ear Protection


Surge operation can cause high and sudden noise levels. It is
strongly recommended to wear hearing protection during surge
operation. Keep in mind that this will limit the operators
awareness for ambient dangers.

Ventilation
The surge operation creates ozon. It is necessary to operate
the instrument under well ventilated condition to keep ozon
levels below limit values for the operator.

Pinpointing - acoustic
( and ICE – Prelocating )

8000 V 12.5 kV
Range
Output Voltage

8000 V Single Shot Timer on


max. voltage

return 5s HV- ON
Timer
push green button HV-OFF
enabling HV source, please wait ...
set voltage – enter

Fig. 18: Menu ICE (impulse current / surge pulse method)


40
Operating :

1. Select ‘Pinpointing’ in main menu.


2. Activate field ‘Acoustic’.
3. After selecting the desired voltage range the above menu appears (Fig.
18: Menu ICE (impulse current / surge pulse method)).
Note: The impulse energy is 1000 J at full voltage in the respective
selected range. When using half the voltage of the selected range only a
quarter of the energy is available or when using 1/3 of the voltage, only
1/9 of the energy is available.
4. Activate field “HV-ON”.
5. Push green button (within 5 sec.)
8. Select max. voltage.
9. Single pulse or timing:
By activating the field “Single Shot” only one single pulse is released into
the faulty cable.
After the field ‘Timer on’ has been activated, another field appears. Here a
pulse rate ranging from 3 to 10 seconds can be selected.
10. Use your pinpoint locator to locate the fault
11. Turn off with the field “HV-OFF” or by pushing the red button [5].

man_spg40_en_09-4.doc
41
7.6.2 Step Voltage Method

Pinpointing -
Step voltage 5 kV

400 V 70 %

Output Voltage Output Current 1000mA

2500 V DC 70 %
max. voltage Sequence max. current
1:3
return
1:4 HV-ON
1:6

push green button HV-OFF


enabling HV source, please wait ...
set voltage

Fig. 19: Menu Pinpoint locating-Step voltage

Operation :

1. Select ‘Pinpointing’ in main menu


2. Activate field ‘Step Voltage’.
3. Select 5 kV or 10 kV voltage range. The above menu will appear.
4. Activate field “HV-ON”.
5. Push green button (within 5 sec.)
6. Set voltage, but watch output current.
Important! In this operating mode the set voltage is immediately present at
the output.
7. Setting pulse rate. Available are DC and
pulse rates 1:3 / 1:4 / 1:6
8. Select max. current. Default is 10% of current scale max. value.
(max. 75% = 750 mA).
voltage range current range max. current
5 kV 1000 mA 750 mA
10 kV 1000 mA 750 mA
9. Pinpoint the fault location with a step voltage locator (e.g. ESG 80-2)
10. Turn off with the field “HV-OFF” or by pushing the red button [5].
42
7.7 Burn Mode

Burning

450 V 30 %

output voltage current display 1000mA

2500 V 8 kV 30 %
max. voltage Burning max. current

return HV - ON

push green button HV-OFF


enabling HV source, please wait ...
set voltage

Fig. 20: Menu Burning

Operating :

1. Select ‘burning’ in main menu.


2. Select voltage range 8 kV or 20 kV.
3. Activate field “HV-ON”.
4. Press green button (within 5 sec.)
5. Setting the voltage. Observe the output current.
Important: in the burn mode voltage is immediately present at the output,
which makes it easier to set the desired output current via the voltage
adjustment
5. Set max. current. Default is 30%.
Even if voltage is changed manually, the output current stays constant as
to the selected "max. current" value in relation to the end-of-scale value of
the "current display".
(in 8 kV range max. 75% = 750 mA).
voltage range current range max. current
8 kV 1000 mA 750 mA
20 kV 100 mA 100 mA
7. Turn off by using field ‘HV-OFF’ or by pressing red push-button [5].

man_spg40_en_09-4.doc
43
8 Shutting Down the Fault Location System

After the measurements on a cable have been completed, the system can be
switched off by pressing the ON/OFF button.
When disconnecting the test system, proceed in reverse sequence to the
manner in which the connection (see section 6.2) was made. The following
safety instructions must be strictly adhered to.

WARNING
Risk of life due to electrical shock!
• Follow the five safety rules (see section 1.2).
• Even if switched off properly and discharged using the
discharge device, the system components that were
under voltage should only be touched once they have
been discharged using a suitable discharge rod as well
as having been earthed and shorted.
• Only undo the earthing and short circuiting measures
when the system has been disconnected and the test
object is to be operated again.
44
9 Care and Maintenance

Note: Care and maintenance of instruments must only be done on


de-energised instruments and only by electrically skilled personnel.

Maintenance
For installation and operation of the instrument it is not necessary to open the
housing of the instrument. Opening the housing will void the warranty and
liability of the manufacturer.
To identify potential problems at an early stage and keep the system in good
condition, it is essential for the following tasks to be carried out independently
and at appropriate intervals depending on the amount of use:
• Remove dust and dirt
• Check the functionality of the emergency stop switch
• Inspect the cables and connecting lines for cracks and damage

Additionally Megger recommends a yearly safety check of the instrument by a


Megger service centre.

Repair
The equipment may only be used when working properly. When irregularities
or malfunctions appear that cannot be solved consulting this manual, the
equipment must immediately be put out of operation and marked as not
functional. In this case inform the person in charge who should inform the
Megger service to resolve the problem. The instrument may only be operated
when the malfunction is resolved.

Cleaning
Cleaning a Megger product may only be done with the instrument turned off
High Voltage equipment must also be discharged and short-circuited. Under
these conditions a slightly wet towel may be used to whip off the equipment.
Avoid using aggressive cleaners and substances like acids.

man_spg40_en_09-4.doc
45
10 Service and Service Contacts

Megger products are undergoing a tight quality monitoring. If you should


experience any problems or if you would like to inquire about any other
comprehensive Megger service, please contact us. The current services of
Megger are listed on the internet under
www.megger .com

Service international:

Seba Dynatronic
Mess- und Ortungstechnik GmbH
Baunach
Dr.-Herbert-Iann-Str. 6
96148 Baunach
Germany
 +49 (0) 9544/68-0
 +49 (0) 9544/68-2273
[email protected]

Service Centres in Germany:

Seba Dynatronic Hagenuk KMT Seba Dynatronic


Mess- und Kabelmesstechnik GmbH Servicecenter West
Ortungstechnik GmbH
Baunach Radeburg Grevenbroich
Dr.-Herbert-Iann-Str. 6 Röderaue Blumenstrasse 27
96148 Baunach 01471 Radeburg 41515 Grevenbroich
Germany Germany Germany
 +49 (0) 9544/68-0  +49 (0) 35208/84-211  +49 (0) 2181/4999-99
 +49 (0) 9544/68-2273  +49 (0) 35208/84-250  +49 (0) 2181/4999-55
[email protected] [email protected] [email protected]
46

man_spg40_en_09-4.doc

You might also like