SPG 40
SPG 40
Test and
Fault Locating System
SPG 40
Issue 9 (01/2017) – EN
128312675
3
Manufacturer:
Seba Dynatronic
Mess- und Ortungstechnik GmbH
Dr.-Herbert-Iann-Str. 6
96148 Baunach
Germany
E-mail: [email protected]
Internet: www.megger.com
Copyright
The information contained in this document is for informational purposes only and is subject to
change without notice. Megger makes no warranty of any kind with regard to the information
contained in this manual, including but not limited to the implied warranties of merchantability
and fitness for a particular purpose. Megger shall not be liable for errors contained herein, nor
for incidental or consequential damages from the furnishing of this information.
This manual contains proprietary information that is protected by copyright. All rights are
reserved.
© Megger 2005
4
Index
1 Safety Advice 6
1.1 General Advice 6
1.2 Electrical Advice 8
2 Technical Description 10
4 Introduction 12
4.1 Stand-alone unit 12
4.2 Combined fault locating system Surgeflex 40 (SFX 40) 13
5 Safety 14
5.1 Key Switch 14
5.2 FΩ protection device 14
5.3 FU-Safety Circuit 15
5.4 VDE clauses 0104 16
5.4.1 Mobile (non-stationary) test unit 16
5.4.2 Area of Danger 16
5.4.3 Emergency OFF button 16
6 Operating 17
6.1 Connections and controls 17
6.2 Electrical Connection 19
6.2.1 Connection Sequence 19
6.2.2 Safety Earth 20
6.2.3 Auxiliary Earth / FU-Safety Circuit 20
6.2.4 Connecting the HV-line to a faulty cable 21
6.2.5 Cordoning off open cable ends 23
6.2.6 Electrical connection of a time domain reflectometer 23
6.2.7 Connecting the SPG 40 to the mains 23
6.3 Menus and Mode Operation 24
6.3.1 Switching On 24
6.3.2 Rotary Selector 25
6.4 Remote control using Teleflex SX 25
6.5 High Voltage control 26
6.5.1 High Voltage HV on 26
6.5.2 High voltage is active 26
6.5.3 Turning OFF high voltage 26
7 Functions 27
7.1 Setup- Menu 27
7.2 Safety Menu 28
7.3 Testing Mode 29
man_spg40_en_09-4.doc
5
7.3.1 Insulation Resistance Test 29
7.3.2 40 kV – DC Proof Test 30
7.4 Operation mode Breakdown Recognition 31
7.5 Fault Prelocating 32
7.5.1 Prelocating mode ARM (Arc Reflection Method) 32
7.5.2 Prelocating mode ICE (Impulse Current Equipment) 34
7.5.3 Prelocating mode Decay 35
7.5.4 Prelocating mode ICE-Plus (optional) 36
7.6 Pinpointing Mode 39
7.6.1 Acoustic method 39
7.6.2 Step Voltage Method 41
7.7 Burn Mode 42
General
This manual contains basic advice for the installation and operation of
the product. It is essential to make this manual accessible to the
authorised and skilled operator. He needs to read this manual closely.
The manufacturer is not liable for damage to material or humans due to
neglectance of this manual and this and the following safety advices.
Intended application
Safe operation is only realised when using the equipment for its
intended purpose (see chapter "Introduction"). Using the equipment for
other purposes may lead to human danger and damage of equipment of
involved installations. The limits described under technical data may not
be exceeded. Operating products of Megger in condensing environment
may lead to flash-over, danger and damage. The instruments should
only be operated under tempered conditions. It is not allowed to operate
Megger products at direct contact with humidity, water or near
aggressive chemicals nor explosive gases and fumes.
man_spg40_en_09-4.doc
7
Operation in traffic environment
To ensure safety for operators and traffic, the country-specific
regulations must be observed.
Transport and operating position
The device may only be operated and transported in an upright
(standing) position!
1. De-energise
2. Protect against re-energising
3. Confirm absence of voltage
4. Ground and short-circuit
5. Cover up or bar-off neighbouring energised parts
man_spg40_en_09-4.doc
9
10
2 Technical Description
man_spg40_en_09-4.doc
11
3 Scope of delivery and Options
Scope of delivery 1:
Description Item
Test and fault locating device SPG 40
Set of cables VL SPG-40
consisting of:
AC mains connection NKG S2
Earthing connection cable EK 1
Auxiliary earth cable MK 54-B
High voltage connection
HSK 27
(25 on manual cable reel)
HKZ 02-1 (red) and
MC connection adapter
HKZ 03-1 (black)
Operating manual
Options:
Description Item
NH adapter 700-10-0437
Operational earth connection with brass
EKS 80
screw-on clamp
Operational earth connection adapter
EKD 80
with big and flexible handle-screw
TDR (Time Domain Reflectometer) Teleflex SX, T 3060 or others
Surge Wave Receiver Digiphone
Step Voltage Indicator ESG NT
Line Location System Ferrolux or others
Dimensions incl. foot plate
External operating panel (B x H x T):
500 x 430 x 240 mm
External safety device
1006953
with HV operaring function
External safety device 820003206
1
If permanently installed in a test van or on a trolley, the scope of delivery may be different.
12
4 Introduction
The SPG 40 has been developed for fault locating in low and medium voltage
networks. Its functions are:
DC-Testing,
Breakdown recognition,
Measuring leakage resistance,
ARM filter for prelocating with a TDR (optional),
Further prelocating methods (Decay, ICE, ICE-Plus)
Pinpoint locating with step voltage or acoustic method,
Burning.
The SPG 40 uses operation with just one rotary selector. For
safety reasons the high voltage setting must be activated with a separate
hardware button.
The operating panel is located in the top panel of the SPG 40 but it is
optionally available as external control unit.
man_spg40_en_09-4.doc
13
4.2 Combined fault locating system Surgeflex 40 (SFX 40)
While – when combined with the T3060 – the operating steps are to be carried
out individually on the operating elements of the respective device, the
Teleflex SX is suitable for direct control of the SPG 40. Supplemented by the
necessary HV operating elements (Teleflex SX-M), it can thus be used for
comprehensive remote control of a spatially separate SPG 40 in a test van
(Compact City).
14
5 Safety
WARNING
Risk of fatal injury from electric shock!
Switching off or bypassing the safety equipment described in
the following two sections will put persons and materials at
significant risk. For this reason, prior to a manual shut-off the
operator must ensure that the earthing conditions allow the
device to be worked with safely on his own responsibility by
taking suitable measures and measurements.
For safe earthing the loop ‘operating earth’ – ‘safety earth’ is monitored
(indicated in the following figure with o). The resistance between operating
and safety earthing must not exceed 6 Ω, otherwise the device cannot be
switched to ‘stand-by’. If this should happen during operation (i.e. earth clamp
gets disconnected), the SPG 40 will immediately shut off and ground the cable
and the HV part of the unit. The menu ‘safety circuit’ will appear, signaling
‘FOHM loop resistance – error’. It may be necessary to make a connection xa.
operating earth – safety earth to meet the requirements (see chapter 6.2.4).
In some rare cases it is possible that the station earthing loop between
operational earth and safety earth does not have a resistance lower than 6 Ω.
Providing that all of the conditions set out in chapter 6.2.2 are fulfilled,
the protective monitoring may be switched off in the setup in this case (see
chapter 7.1). This is done at operators responsibility. An indication will show in
the main menu that F Ω protection is switched off.
FΩ
man_spg40_en_09-4.doc
15
5.3 FU-Safety Circuit
Also for safety for the operator, the auxiliary earth connection [23] must be
connected to a ground rod as close as possible to the SPG 40. The FU-safety
circuit of the SPG 40 will immediately shut the unit off and ground the cable
and the HV part of the unit over a resistor if the voltage between the
instrument and the surrounding earth gets higher than 33 V AC / -40 V DC, or
if the resistance of the earth loop between safety earth and auxiliary earth gets
higher than 150 kΩ. The menu ‘safety circuit’ will appear on screen, signaling
‘FU – step voltage - error’.
OE
power cable
e.g. without sheath
FΩ < 6Ω
a.
PE
FU
AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth
Fig. 1: FΩ – monitoring
In some areas the ground resistance between instrument (earthed at station
earth) and the terrain where the instrument is set up may be higher than
150 kΩ due to ground conditions (e.g. dry sand, rock). Providing that all of
the measures described in chapter 6.2.3 have been taken, the step voltage
monitoring may be switched off in the setup in this case (see chapter 7.1).
This is done at operators responsibility. An indication will show in the main
menu that FU protection is switched off.
FU
16
5.4 VDE clauses 0104
man_spg40_en_09-4.doc
17
6 Operating
1. 2. 3. 4. 5. 6. 7.
white green red
Fig. 2: Controls
Element Function
1. emergency OFF button
2. push-button – white on/off switch
press: activates system controls
lit: device is switched on
3. key switch
4. push-button – green: HV-ON key
lit: HV readiness for switching on
(high voltage can be switched on)
press: Switches the high voltage on; earthing of the
output is cancelled
5. push-button - red : HV-OFF key
lit: HV-operation
(high voltage present at output)
press: switches high voltage off
(output will be grounded over a discharge
resistor)
6. rotary selector with enter function
7. display
18
8 9 10 11 12 14 13 15 16 17 18 16
23 22 21 20 19
(1)
depending on instrument version,
see type label on instrument.
man_spg40_en_09-4.doc
19
6.2 Electrical Connection
The device should never be operated without the earth lead being
connected. The earth lead establishes the connection between the
device and the safety earth and ensures that the device is touch-
proof.
The earthing provided through the earth contact of the mains
connection is not sufficient.
Without the earth lead being connected, the housing leakage
current could exceed 3.5 mA, if the earth connection to the wall
socket is interrupted (safety hazard according to EN 61010).
man_spg40_en_09-4.doc
21
6.2.4 Connecting the HV-line to a faulty cable
The HV-connecting cable has to have a minimum length of 25 m (scope of
delivery) to avoid excess currents. These currents could develop due to the
discharge characteristic of the surge capacitor when the flash-over in the
cable occurs at a very short distance of the point of connection.
power cable
OE
i.e. with shield
FΩ < 6Ω
PE
FU
AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth
OE a.
power cable
FΩ < 6Ω i.e. without shield
PE
FU
AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth
power cable
with shield
FΩ < 6Ω a.
PE
FU PE
AE
OE: operating earth
PE: safety earth / station earth
AE: auxiliary earth
man_spg40_en_09-4.doc
23
6.2.5 Cordoning off open cable ends
As the high voltage pulses or DC voltage applied to the faulty cable are
hazardous, the cable ends have to be cordoned off in accordance with local
safety regulations (i.e. VDE 0104 regulations). The user has to make sure that
also the ends of branches (tees) are cordoned off and protected.
6.3.1 Switching On
Only when the AC mains connection is not plugged in, the SPG 40 is
completely turned off. The moment that the AC mains connector is plugged
into a power supply, the SPG 40 is in stand-by mode – no button is lit yet.
Press the white push button [2] to start the SPG 40.
The white push-button lights up. The control and safety circuits are activated
and system controls switches the operating menu on. The device will
automatically go on ‘stand-by’.
There is no high voltage generated at this point as the HV outlet is still
earthed.
SPG 40
Select Menu FΩ
10:32:16
FU
Breakdown
Setup Testing
Recognition
man_spg40_en_09-4.doc
25
6.3.2 Rotary Selector
Turn = select or change values
Press = confirm (enter function)
In remote control mode, all operating modes (with the exception of the optional
ICE Plus locating method) can be controlled directly from the Teleflex SX. The
SPG 40 display is darkened in this mode and the encoder [6] has no function.
The remote control mode on the Teleflex SX must be activated before
measurement is begun.
Remote control
active
! In the burning and pinpoint locating (step voltage) modes the voltage
adjustment does not have to be confirmed with the rotary selector but is
immediately active at the output.
man_spg40_en_09-4.doc
27
7 Functions
SPG 40
10:32:16
Day: 10 Hour: 10
Month: 05 Minute: 32
Year: 2005 Second: 16
return
60 English
Date/Time
Contrast Language
active active
return
F-Ohm F-U
Safety Circuit
FU – step voltage ok
FOHM loop resistance error
Emergency Off Switch ok
External Emergency Off Switch ok
Key switch ok
Over temperature ok
System ok
HV connector ok
Earth connection ok
Rear door ok
return clear
man_spg40_en_09-4.doc
29
7.3 Testing Mode
Insulation Resistance
5000 V 12 MΩ
Testing – 40 kV
750 kΩ
9000 V 12 mA
Remaining Time
return HV-ON
12:52 min
Operation :
If a breakdown occurs during the test with the timer turned on, the SPG 40 will
shut off and ground the cable over a discharge resistor and the breakdown
voltage will be displayed (identical to 'Breakdown recognition'-mode). If a
breakdown occurs during testing but with the timer turned off, the SPG 40 will
not switch off automatically but will continue to show the insulation resistance.
The insulation resistance is shown on the top right corner of the display as
soon as a minimum voltage of 100 V and a minimum current of 10 µA are
measured. The displays of insulation resistance and leakage current
measurement are auto-ranging.
man_spg40_en_09-4.doc
31
7.4 Operation mode Breakdown Recognition
550 V 12 mA
Operation :
Ventilation
The surge operation creates ozon. It is necessary to operate
the instrument under well ventilated condition to keep ozon
levels below limit values for the operator.
ARM - Prelocating
(Arc Reflection Method)
6000 V 12.5 kV
Range
Output Voltage
return HV- ON
man_spg40_en_09-4.doc
33
Operation :
Ventilation
The surge operation creates ozon. It is necessary to operate
the instrument under well ventilated condition to keep ozon
levels below limit values for the operator.
ICE
8000 V 12.5 kV
Range
Output Voltage
return 5s HV- ON
Timer
push green button HV-OFF
enabling HV source, please wait ...
set voltage – enter
Fig. 14: Menu ICE (impulse current / surge pulse method)
Operation :
DECAY
1 MΩ
9000 V 9 mA
Remaining Time
return HV-ON
12:52 min
If a breakdown occurs during the test with the timer turned on, the SPG 40 will
shut off and ground the cable over a discharge resistor and the breakdown
voltage will be displayed (identical to 'Breakdown recognition'-mode).
If a breakdown occurs during testing but with the timer turned off, the SPG 40
will not switch off automatically but will continue to show the insulation
resistance. The insulation resistance is shown on the top right corner of the
display as soon as a minimum voltage of 100 V and a minimum current of 10
µA are measured. The displays or insulation resistance and leakage current
measurement are auto-ranging.
ICE-Plus
cableinput : set new cable data
how many sections : 1
section : 1 sectionlength : 500 m
cablediameter : 150 qmm
cabletyp : connection :
Operation :
man_spg40_en_09-4.doc
37
1. Select operating mode ‘Prelocation’ in main menu.
2. Select operating mode ‘ICE-Plus’ in prelocation menu.
3. Activate field "cable data".
4. Under “cableinput” (at the top) select one of the following:
“accept old cable data” (no changes, continue with step 10)
“modify cable data” (change previous data)
“set new cable data” ( enter a completely new set of data)
5. Enter the number of sections for mixed cables (max. 5 parts)
6. Enter lengths of sections. When dealing with mixed cables, the
exactness of the result depends on how exact the input is. For single
sections the length just has to be changed if the object to be measured is
longer than the pre-set value.
If the length entered is to short and the fault is behind the stated cable
end, this is shown at the bottom of the display with “Faultdistance >
Cablelength”.
7. Select the conductor diameter from the provided values.
8. Selection of cable type. Select one of the following possibilities:
with sheath 4 conductors 5 conductors
without sheath
ICE-Plus
2000 V
Output Voltage
return HV-ON
HV-OFF
Fig. 17: Menu ICE-Plus
man_spg40_en_09-4.doc
39
7.6 Pinpointing Mode
Ventilation
The surge operation creates ozon. It is necessary to operate
the instrument under well ventilated condition to keep ozon
levels below limit values for the operator.
Pinpointing - acoustic
( and ICE – Prelocating )
8000 V 12.5 kV
Range
Output Voltage
return 5s HV- ON
Timer
push green button HV-OFF
enabling HV source, please wait ...
set voltage – enter
man_spg40_en_09-4.doc
41
7.6.2 Step Voltage Method
Pinpointing -
Step voltage 5 kV
400 V 70 %
2500 V DC 70 %
max. voltage Sequence max. current
1:3
return
1:4 HV-ON
1:6
Operation :
Burning
450 V 30 %
2500 V 8 kV 30 %
max. voltage Burning max. current
return HV - ON
Operating :
man_spg40_en_09-4.doc
43
8 Shutting Down the Fault Location System
After the measurements on a cable have been completed, the system can be
switched off by pressing the ON/OFF button.
When disconnecting the test system, proceed in reverse sequence to the
manner in which the connection (see section 6.2) was made. The following
safety instructions must be strictly adhered to.
WARNING
Risk of life due to electrical shock!
• Follow the five safety rules (see section 1.2).
• Even if switched off properly and discharged using the
discharge device, the system components that were
under voltage should only be touched once they have
been discharged using a suitable discharge rod as well
as having been earthed and shorted.
• Only undo the earthing and short circuiting measures
when the system has been disconnected and the test
object is to be operated again.
44
9 Care and Maintenance
Maintenance
For installation and operation of the instrument it is not necessary to open the
housing of the instrument. Opening the housing will void the warranty and
liability of the manufacturer.
To identify potential problems at an early stage and keep the system in good
condition, it is essential for the following tasks to be carried out independently
and at appropriate intervals depending on the amount of use:
• Remove dust and dirt
• Check the functionality of the emergency stop switch
• Inspect the cables and connecting lines for cracks and damage
Repair
The equipment may only be used when working properly. When irregularities
or malfunctions appear that cannot be solved consulting this manual, the
equipment must immediately be put out of operation and marked as not
functional. In this case inform the person in charge who should inform the
Megger service to resolve the problem. The instrument may only be operated
when the malfunction is resolved.
Cleaning
Cleaning a Megger product may only be done with the instrument turned off
High Voltage equipment must also be discharged and short-circuited. Under
these conditions a slightly wet towel may be used to whip off the equipment.
Avoid using aggressive cleaners and substances like acids.
man_spg40_en_09-4.doc
45
10 Service and Service Contacts
Service international:
Seba Dynatronic
Mess- und Ortungstechnik GmbH
Baunach
Dr.-Herbert-Iann-Str. 6
96148 Baunach
Germany
+49 (0) 9544/68-0
+49 (0) 9544/68-2273
[email protected]
man_spg40_en_09-4.doc