Truefrontaccess 12 355 MRF
Truefrontaccess 12 355 MRF
TRUE
FRONT
ACCESS
HIGH RATE MAX
UPS 12-355MRF
Valve Regulated Lead Acid (VRLA) Battery Series
Designed for UPS Standby Power Applications
SPECIFICATIONS
Constant Power Discharge Ratings - Watts per cell @ 77ºF (25ºC)
Operating Time (in minutes) to 1.67 volts per cell
20 Hour Rate @
Model Number Voltage Per Unit 5 10 15 20 30 40 50 60 90
77ºF (25ºC) to 1.75
UPS12-355MRF 12 V 108 Ah 591.3 440.8 358.4 299.7 229.4 190.5 164.9 146.6 105.6
12-1079/0611/CD www.cdtechno.com
SPECIFICATIONS
DIMENSIONS
A B C D E F G H
MODEL in mm in mm in mm in mm in mm in mm in mm in mm
UPS12-355MRF 18.5 469 19.5 496 20.1 511 18.5 470 8.5 216 9.3 235 4.3 110 4.2 107
* All dimensions in inches and (millimeters). All dimensions are for reference only. Contact a C&D Representative for complete dimensional information.
Float Charging Voltage 13.5 to 13.8 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. Batteries stored at temperatures greater than 77°F
(25°C) will require recharge sooner than batteries stored at lower
temperatures. See C&D brochure 41-7272, Self-Discharge and Inventory
Control for details.
Equalize charge and cycle 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
service voltage
Terminal: Inserted - Inter-unit Threaded copper alloy insert terminal to accept M6 bolt
connector provided
UPS 12-355MRF
Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage (in minutes)
End Point
5 10 15 20 30 40 45 50 60 90
Volts/Cell
1.75 543.9 411.8 334.9 283.3 220.6 183.8 170.6 159.6 142.2 103.1
1.70 578.3 431.1 350.5 294.0 226.0 188.0 174.4 163.0 145.1 104.7
1.67 591.3 440.8 358.4 299.7 229.4 190.5 176.6 164.9 146.6 105.6
1.65 600.6 447.7 364.0 303.7 231.7 192.5 178.5 166.8 148.3 106.5
Note: Specifications subject to change without notification. Above ratings do not include interunit connector voltage drops
Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc.
without notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes
no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its control,
1400 Union Meeting Road C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suitability
P.O. Box 3053 • Blue Bell, PA 19422-0858 of such product(s) for any particular use or in any specific application or arising from any course of dealing or usage
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630 of trade. The user is solely responsible for determining the suitability of the product(s) featured herein for user’s
[email protected] intended purpose and in user’s specific application.
www.cdtechno.com Copyright 2011 C&D TECHNOLOGIES, INC. Printed in U.S.A. 12-1079 0611/CD