Sius 612102 e
Sius 612102 e
Service Instructions
DX17VSS***B* / DZ17VSA***B* Inverter Outdoor Units
with R-410A Refrigerant
Coils, Air Handler & Accessories
WARNING
Only personnel that have been trained to install, adjust, service
or repair(hereinafter, “service”) the equipment specified in this
manual should service the equipment. The manufacturer will not
PROP 65 WARNING
be responsible for any injury or property damage arising from FOR CALIFORNIA CONSUMERS
improper service or service procedures. If you service this unit,
you assume responsibility for any injury or property damage WARNING
which may result. In addition, in jurisdictions that require one or
more licenses to service the equipment specified in this manual, Cancer and Reproductive Harm -
only licensed personnel should servise the equipment. www.P65Warnings.ca.gov
Improper installation, adjustment, servicing or repair of the 0140M00517-A
equipment specified in this manual, or attempting to install,
adjust, service or repair the equipment specified in this manual
without proper training may result in product damage, property
damage, personal injury or death.
© 2021
WARNING
TO AVOID POSSIBLE EXPLOSION: notice: When the outdoor unit is connected to main
•NEVER APPLY FLAME OR STEAM TO A REFRIGERANT CYLINDER. IF YOU power, the inverter control board has a small current flowing
into it to be prepared for operation when needed. Due to
MUST HEAT A CYLINDER FOR FASTER CHARGING, PARTIALLY IMMERSE
this, the control board components have to be cooled even
IT IN WARM WATER.
when the unit is not running. For this cooling operation, the
•NEVER FILL A CYLINDER MORE THAN 80% FULL OF LIQUID outdoor unit fan may come on at any time, including in the
REFRIGERANT.
winter months. Any obstruction to the outdoor fan should
•NEVER ADD ANYTHING OTHER THAN R-410A TO A RETURNABLE be avoided at all times when the unit is powered to prevent
R-410A CYLINDER. THE SERVICE EQUIPMENT USED MUST BE LISTED damage.
OR CERTIFIED FOR THE TYPE OF REFRIGERANT USE.
The successful development of hermetically sealed refriger-
•STORE CYLINDERS IN A COOL, DRY PLACE. NEVER USE A CYLINDER ation compressors has completely sealed the compressor's
AS A PLATFORM OR A ROLLER. moving parts and electric motor inside a common housing,
minimizing refrigerant leaks and the hazards sometimes
associated with moving belts, pulleys or couplings.
WARNING
Fundamental to the design of hermetic compressors is
TO AVOID POSSIBLE EXPLOSION: a method whereby electrical current is transmitted to the
•USE ONLY RETURNABLE (NOT DISPOSABLE) SERVICE CYLINDERS WHEN compressor motor through terminal conductors which pass
REMOVING REFRIGERANT FROM A SYSTEM. through the compressor housing wall. These terminals are
•ENSURE THE CYLINDER IS FREE OF DAMAGE WHICH COULD LEAD TO A sealed in a dielectric material which insulates them from
LEAK OR EXPLOSION. the housing and maintains the pressure tight integrity of
•ENSURE THE HYDROSTATIC TEST DATE DOES NOT EXCEED 5 YEARS. the hermetic compressor. The terminals and their dielectric
•ENSURE THE PRESSURE RATING MEETS OR EXCEEDS 400 PSI. embedment are strongly constructed, but are vulnerable
to careless compressor installation or maintenance proce-
WHEN IN DOUBT, DO NOT USE THE CYLINDER. dures and equally vulnerable to internal electrical short cir-
cuits caused by excessive system contaminants.
In either of these instances, an electrical short between the
WARNING terminal and the compressor housing may result in the loss
of integrity between the terminal and its dielectric embed-
TO AVOID POSSIBLE INJURY, EXPLOSION OR DEATH, PRACTICE SAFE
ment. This loss may cause the terminals to be expelled,
HANDLING OF REFRIGERANTS.
thereby venting the vaporous and liquid contents of the
compressor housing and system.
A venting compressor terminal normally presents no danger
CAUTION to anyone, providing the terminal protective cover is proper-
THE COMPRESSOR PVE OIL FOR R-410A UNITS IS EXTREMELY ly in place.
SUSCEPTIBLE TO MOISTURE ABSORPTION AND COULD CAUSE If, however, the terminal protective cover is not properly in
COMPRESSOR FAILURE. DO NOT LEAVE SYSTEM OPEN TO ATMOSPHERE place, a venting terminal may discharge a combination of
ANY LONGER THAN NECESSARY FOR INSTALLATION.
(a) hot lubricating oil and refrigerant
(b) flammable mixture (if system is contaminated
with air)
NOTICE
in a stream of spray which may be dangerous to anyone in
T�� ������ ������ (����������� �� ������ ��� �������
��������) ���� �� ������������ �������� ��� A��-C�����������, the vicinity. Death or serious bodily injury could occur.
H������, ��� R������������ I�������� (AHRI) ������. Under no circumstances is a hermetic compressor to be
NOTE: I����������� �� ��������� ������� �� ��� ���������. electrically energized and/or operated without having the
D����� �� ������� ��� �� ������������ �� ��������� ������� �� terminal protective cover properly in place.
��� ������� ����� ��� ��������.
See Service Section S-17 for proper servicing.
3
Brand Engineering
D - Daikin Minor Revision
Type Engineering
X - AC R-410A Major Revision
Z - HP R-410A
Voltage
SEER 1 - 208/230 V single phase 60 Hz
17 - 17 SEER
Tonnage Nominal
18 - 18 SEER
20 - 20 SEER 18 - 1.5 ton
24 - 2.0 ton
Compressor 30 - 2.5 ton
V - Variable Speed 36 - 3.0 ton
42 - 3.5 ton
Feature Set 48 - 4.0 ton
S - Side Discharge Communicating 60 - 5.0 ton
Region
S - Southeast & North
A - All
Brand Engineering
D - Daikin Single-Piece Major/Minor Revisions
Air Handler
Unit Application Refrigerant
V - Multi Position Variable-Speed 4 - R-410A
Motor-Communicating
Electrical
Tonnage Nominal 1 - 208/230 V, 1 Phase, 60 Hz
24 - 2.0 ton 48 - 4.0 ton
36 - 3.0 ton 60 - 5.0 ton Cabinet Width
42 - 3.5 ton B - 17½"
C - 21"
System Compatibility D - 24½"
F - FIT
Communicating
Expansion Device C - Yes
E - Electronic Expansion Valve
C H P E 2430 B 4 AA
C+
C-
MULTIMETER
(DC.VOLTAGE RANGE)
USE TESTER TO
CHECK THE VOLTAGE
DC+ “C+” AND DC- “C-” IS
50 V OR LESS.
Capacitor Voltage
C+
C-
MULTIMETER
(DC.VOLTAGE RANGE)
USE TESTER TO
CHECK THE VOLTAGE
DC+ “C+” AND DC- “C-” IS
50 V OR LESS.
Capacitor Voltage
Tm
Ts
Ta
Tli
Tgi Td
Tl
Tm
Ts Td
Ta
Tli
Tgi
Tl
Tm
Ts Td
Tb
Ta
Tli
Tgi
Tl
Tm
Ts Td
Tb
Ta
Tli
Tgi
Tl
10
Pressure Pressure
Stop equalizing Startup Steady control Oil return Steady control Residual operation Restart standby Stop equalizing
before start before start
%Demand > 0
Thermo-on
COOLING OPERATION FLOW
SYSTEM OPERATION
Oil return
Startup frequency Residual operation
frequency frequency
%Demand %Demand
Stop Stop
Compressor
Pressure
50 pulse Pressure Lowering SH equalizing 50 pulse
SH control SH control
(Minimum) equalizing (EEV position (Open)) (Minimum)
Indoor EEV
Close
Outdoor solenoid valve
Pressure
equalizing Steady control: 8 steps
Low differential pressure and low pressure ratio protection control Stop
Stop
Outdoor fan control
Indoor fan motion Thermostat command Interlocking with compressor frequency (Low ~ High) Thermostat
Low command
2021/02/17
11
9:00:05
12
SiUS612102E.indb
12
Power on %Demand>0
%Demand>0 %Demand=0
Thermo-on (Forced) thermo-off Thermo-on
Compressor 0 frequency
Residual
Pressure Prior to Start up operation Pressure
equalizing Start up EEV defrost EEV Defrost EEV position EEV EEV equalizing
position position position position
0 pulse SH control SH control
Outdoor EEV 0 pulse
Startup Startup
Pressure Steady control: 8 step Steady control: 8 step
fan step fan step
equalizing Low differential pressure and low Low differential pressure and
Outdoor fan control Stop pressure ratio protection control Stop low pressure ratio protection control Stop
Hot start Steady control (Indoor fan) Defrost heat mode Hot start Steady control (Indoor fan)
Indoor fan command No command No command
2021/02/17
9:00:05
SiUS612102E.indb
13
POSSIBLE CAUSE
Test Method Remedy
X IN ANALYSIS GUIDE INDICATE
“POSSIBLE CAUSE”
X X X X X X X
Outdoor coil thermistor failure X X X X X X Check resistance and connections to verify operation; Replace if needed
Outdoor air thermistor failure X X X X X Check resistance and connections to verify operation; Replace if needed
OD recirculation X X X X X X Re-arrange OD position
ID recirculation X X X X X X Re-arrange ID position
Dirty OD heat-exchanger X X X X X X Check OD heat-exchanger; Clean
Dirty ID heat-exchanger X X X X X X Check ID heat-exchanger; Clean
Outdoor ambient temp is too high X X X X X X X -
Outdoor ambient temp is too low X X X X X X -
ID return air temp is too high X X -
ID return air temp is too low X X X X X X -
Mixture of non-condensable gas X X X X X X X X Recover refrigerant, evacuate pipe, and re-charge
OD fan motor failure X X X X X X X Replace OD fan motor
Over charge X X X X X X X X Recover part of charge
Under charge X X X X X X X X Test for leaks, Add refrigerant
Leak X X X X X X X X X Specify and repair the leak point
OD control board failure X Replace OD control board
ID failure X X X X X X X X X X X X X X Replace ID
Compressor failure X X X X X X X X X Replace compressor
Compressor and gas furnace are operating at the
X -
same time
Cooling loop is not attached X X Attach cooling loop to cold plate
Cooling loop grease is not enough X X Add grease
Low ID CFM X X X X X X X Check airflow Trim, Check ID fan motor; Repair/replace if needed
Outdoor Normal Temperature Operating Range for Cooling Analysis: 67-115°F / Indoor Normal Temperature Operating Range: 65 - 85°F
2021/02/17
13
9:00:05
14
POSSIBLE CAUSE
SiUS612102E.indb
Test Method Remedy
14
X IN ANALYSIS GUIDE INDICATE
“POSSIBLE CAUSE”
Pressure sensor failure X X X X X X X X Check resistance and connections to verify operation; Replace if needed
Outdoor suction thermistor failure X X X X X X X X Check resistance and connections to verify operation; Replace if needed
Outdoor discharge thermistor failure X X X X X X X Check resistance and connections to verify operation; Replace if needed
Outdoor coil thermistor failure X X X X X Check resistance and connections to verify operation; Replace if needed
Outdoor coil defrost thermistor failure X X X X X Check resistance and connections to verify operation; Replace if needed
Outdoor liquid thermistor failure X X Check resistance and connections to verify operation; Replace if needed
Outdoor air thermistor failure X X X X X X Check resistance and connections to verify operation; Replace if needed
OD recirculation X X X X X X X Re-arrange OD position
ID recirculation X X X X X Re-arrange ID position
Dirty OD heat-exchanger X X X X X X X Check OD heat-exchanger; Clean
Dirty ID heat-exchanger X X X X X Check ID heat-exchanger; Clean
Outdoor ambient temp is too high X X X X X -
Outdoor ambient temp is too low X X X X X X X X -
ID return air temp is too high X X X X -
ID return air temp is too low X X X -
Mixture of non-condensible gas X X X X X X Recover refrigerant, evacuate pipe, and re-charge
OD fan motor failure X X X X X X Replace OD fan motor
RV failure X X X X X X X X Check RV: Repair/replace if needed
RV coil failure X X X X X Check RV coil: Repair/replace if needed
Over charge X X X X X X Recover part of charge
Under charge X X X X X X X X X Test for leaks, Add refrigerant
Leak X X X X X X X X X Specify and repair the leak point
ID failure X X X X X X X X X X X X X X Replace ID
OD control board failure X Replace OD control board
Compressor failure X X X X X X X X X X X Replace compressor
Cooling loop is not attached X X Attach cooling loop to cold plate
Cooling loop grease is not enough X X Add grease
Low ID CFM X X X X X Check airflow Trim, Check ID fan motor; Repair/replace if needed
Outdoor Normal Temperature Operating Range for Heating Analysis: 17 - 62°F / Indoor Normal Temperature Operating Range: 65 - 85°F
2021/02/17
9:00:05
SERVICING
Table of Contents
S-1 CHECKING VOLTAGE..................................... 16 S-17 CHECKING COMPRESSOR........................... 23
S-2 CHECKING WIRING........................................ 16 S-17A Resistance Test......................................... 24
S-3A Thermostat and Wiring.......................... 16 S-17B Ground Test................................................ 24
S-3E DAIKIN COMMUNICATING THERMOSTAT .... 16 S-26 TESTING thermistor, EEV COIL AND
S-4 Checking Transformer And control SOLENOID VALVE COIL RESISTANCE........ 24
circuit............................................................ 17 S-100 REFRIGERATION REPAIR PRACTICE......... 25
S-12 CHECKING HIGH PRESSURE SWITCH....... 17 S-101 leak testing (nitrogen or
S-13 CHECKING INDOOR UNIT / OUTDOOR UNIT nitrogen-traced)..................................... 26
PRESSURE SENSOR...................................... 18 S-102 EVACUATION................................................... 26
1.0 AIRFLOW CONSIDERATION.......................... 18 S-103 CHARGING....................................................... 28
2.0 AIRFLOW RATE LIMITATION......................... 18 S-104 CHECKING COMPRESSOR EFFiCIENCY... 29
3.0 AIRFLOW TRIM SETTING LIMITATION........... 19 S-114 NON-CONDENSABLE..................................... 29
S-52 CHECKING HEATER ELEMENTS.................. 19 S-115 COMPRESSOR BURNOUT............................ 29
S-60 ELECTRIC HEATER (OPTIONAL ITEM)........ 19 S-202 duct static pressures and/or static
S-61A CHECKING HEATER LIMIT CONTROL(S).... 20 pressure drop across coils............. 30
S-61B CHECKING HEATER FUSE LINK S-203 AIR HANDLER EXTERNAL STATIC............... 30
(OPTIONAL ELECTRIC HEATERS)............... 21 S-203A two piece indoor unit external
S-16G CHECKING EMERSON ULTRATECH™ static............................................................ 31
ECM MOTORS................................................. 21
NOTE: Please refer to the Service Manual of each unit about the Gas Furnaces and Modular Blower.
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to
do so may cause property damage, personal injury or death.
15
1. Remove outer case, control panel cover, etc., from unit WARNING
being tested.
LINE VOLTAGE NOW PRESENT.
With power ON:
With power ON, check the thermostat.
WARNING
1. Use a voltmeter to check for 24 volt at thermostat wires
LINE VOLTAGE NOW PRESENT. C and R in the thermostat.
2. No voltage indicates trouble in the wiring or transformer
2. Using a voltmeter, measure the voltage across L1 and source.
L2 terminals of outdoor unit or at the field connections
for the indoor units or heaters. 3. Check the continuity of the thermostat and wiring. Re-
pair or replace as necessary.
3. No reading - indicates open wiring, open fuse(s), no
power or etc., from unit to fused disconnect service. S-3E DAIKIN COMMUNICATING THERMOSTAT
Repair as needed. Typical wiring will consist of two wires between the indoor
4. With ample voltage at line voltage connectors, energize unit and outdoor unit, and four wires between the indoor
the unit. unit and thermostat. The figure that follows shows the
required wires: data lines, 1 and 2; “R” (24 VAC hot) and “C”
Unit Supply Voltage (VAC) (24 VAC common).
Unit Type
Voltage Min. Max. <In Case of Air Handler>
Outdoor Unit, Air Handler (DV*FEC),
208/230 197 253 Communica�ng Thermostat
Modular Blower, Heater Kit 1 2 C R (In case of Daikin One+
Gas Furnaces 115 103 126 Smart Thermostat)
125 �. (*)
Cased Coil (CAPE(A)*/CHPE*) 24 22.6 25.5
1 2 R C Air Handler Blower
Integrated Control Module
NOTE: When operating electric heaters on voltages oth- 250 �. (*)
er than 230 volt, refer to the System Operation section on
Outdoor unit
electric heaters to calculate temperature rise and airflow. 1 2 R C
Integrated Control Module
Low voltage may cause insufficient heating.
16
WARNING
LINE VOLTAGE NOW PRESENT.
17
18
19
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
Electrical Checks - High Voltage Power Circuits 2. Check voltage between pins on the 4-wire motor
control harness between the motor and control board.
3. Voltage on pins should read:
HIGH VOLTAGE!
Disconnect ALL power before servicing Pins 1 to 4 = 3.3VDC
or installing. Multiple power sources Pins 1 to 2 = 3.3VDC
may be present. Failure to do so may Pins 3 to 4 = 15VDC
cause property damage, personal injury
or death. Motor Control/End Bell Checks
}
power harness.
1 Not use (Lines 1 and 2 will be 3. Remove the blower assembly from the indoor unit.
connected for 120 VAC Power
2 4. Remove the (3) screws securing the control/end
Connector applications only)
bell to the motor. Separate the control/end bell.
3 Disconnect the 3-circuit harness from the control/end
Gnd
bell to remove the control/end bell from the motor.
4 AC Line Connection 5. Inspect the NTC thermistor inside the control/end
bell (see figure below). Replace control/end bell if
5 AC Line Connection thermistor is cracked or broken.
WARNING
Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which
supports a hermetic compressor or electrical terminal
suddenly disintegrates due to physical abuse or as a
result of an electrical short between the terminal and
the compressor housing, the terminal may be
expelled, venting the vapor and liquid contents of the
compressor housing and system.
HIGH VOLTAGE! Ignition cannot occur at the venting terminal without the
Disconnect ALL power before servicing presence of contaminant air, and cannot occur externally
or installing. Multiple power sources from the venting terminal without the presence of an exter-
may be present. Failure to do so may nal ignition source.
cause property damage, personal injury Therefore, proper evacuation of a hermetic system is es-
or death. sential at the time of manufacture and during servicing.
1. Disconnect power to air handler or modular blower. To reduce the possibility of external ignition, all open flame,
electrical power, and other heat sources should be extin-
NOTE: Motor contains capacitors that can hold a charge for guished or turned off prior to servicing a system.
several minutes after disconnecting power. Wait 5 minutes
after removing power to allow capacitors to discharge.
2. Disassemble motor as described in steps 2 through
4 above.
3. Locate the 3-circuit harness from the motor. Using
an ohmmeter, measure the resistance between each
motor phase winding. The resistance levels should
be equal. Replace the motor if the resistance levels
are unequal, open circuited or short circuited.
4. Measure the resistance between each motor phase
winding and the motor shell. Replace the motor if
any phase winding is short circuited to the motor
shell.
5. Reassemble motor and control/end bell in reverse
of disassembly. Replace blower assembly into air
handler or modular blower.
23
WARNING
OHMMETER Damage can occur to the glass embedded terminals if
the leads are not properly removed. This can result in
terminal and hot oil discharging.
24
DANGER
HIGH VOLTAGE! Always remove the refrigerant charge in a proper
Disconnect ALL power before servicing manner before applying heat to the system.
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury NOTICE
or death. There is no specific “Pump down” function.
When the unit needs to be removed/relocated,
1. Disconnect power to all equipments. please recover all refrigerant from the system.
Use the service ports (2 locations) on the stop
2. Disconnect the thermistor connector from the control board.
valves to recover refrigerant. You may not recover
3. Connect an ohmmeter across the thermistor terminals. all refrigerant unless you use the 2 service ports.
The ohmmeter should read the resistance shown in the
table THERMISTOR RESISTANCE AND TEMPERA- When repairing the refrigeration system:
TURE CHARACTERISTICS. Replace the thermistor if
the thermistor is open, shorted, or outside the valid re-
sistance range. HIGH VOLTAGE!
Testing EEV Coil Resistance Disconnect ALL power before servicing
or installing. Multiple power sources
To check the resistance of the EEV coil, first disconnect may be present. Failure to do so may
the EEV cable from the control board. Read resistance cause property damage, personal injury
between the connector pins, and then make sure the resis- or death.
tance falls in the range of 40 to 50 Ω.
Outdoor unit (HP): 3.5 - 5.0 ton 1. Never open a system that is under vacuum. Air and
Outdoor unit (HP): 1.5 - 3.0 ton Indoor unit moisture will be drawn in.
2. Plug or cap all openings.
3. Remove all burrs and clean the brazing surfaces of the
tubing with sand cloth or paper. Brazing materials do
not flow well on oxidized or oily surfaces.
4. Clean the inside of all new tubing to remove oils and
pipe chips.
5. When brazing, sweep the tubing with dry nitrogen to
prevent the formation of oxides on the inside surfaces.
6. Complete any repair by replacing the liquid line drier in
the system, evacuate and charge.
BRAZING MATERIALS
Important note: Torch heat required to braze tubes of
various sizes is proportional to the size of the tube. Tubes
of smaller size require less heat to bring the tube to braz-
ing temperature before adding brazing alloy. Applying too
much heat to any tube can melt the tube. Service personnel
Testing Solenoid Valve Coil Resistance
must use the appropriate heat level for the size of the tube
To check the resistance of the solenoid valve coil, first dis-
being brazed.
connect the cable from the control board. Read resistance
NOTE: The use of a heat shield when brazing is recommended
between the connector pins, and then make sure the resis-
to avoid burning the serial plate or the finish on the unit. Heat
tance falls in the range of 1,480 to 1,820 Ω.
trap or wet rags should be used to protect heat sensitive
components such as stop valves, EEV and filters.
Copper to Copper Joints - Sil-Fos used without flux (alloy
of 15% silver, 80% copper, and 5% phosphorous). Recom-
mended heat 1400°F.
Copper to Steel Joints - Silver Solder used without a flux
(alloy of 30% silver, 38% copper, 32% zinc). Recommend-
ed heat - 1200°F.
25
26
Stop valve
Open
Hexagonal wrench
Close
27
Stop Valve Charge the system with the exact amount of refrigerant.
Stop valve Tightening Wrench
Tonnage Piping Type See the Installation Manual for the correct refrigerant charge.
size torque size
An inaccurately charged system will cause future prob-
1.5 - 2.0 Liquid 3/8” 4 - 6 lb·ft 3/16”
Front lems.
ton Gas 3/4” 14 - 16 lb·ft 5/16”
sealing 1. When using an ambient compensated calibrated charging
2.5 - 3.0 Liquid 3/8” type 4 - 6 lb·ft 3/16”
cylinder, allow liquid refrigerant only to enter the high side.
ton Gas 7/8” 14 - 16 lb·ft 5/16”
Liquid 3/8” Front 4 - 5 lb·ft 4 mm 2. Once the system stops taking refrigerant, close the valve
3.5 - 5.0 and back on the high side of the charging manifold.
ton Gas 7/8” sealing 14 - 16 lb·ft 8 mm
type
3. Start the system and charge the balance of the gas
state refrigerant through the low side.
Service Port
NOTE: R-410A should be drawn out of the storage contain-
Tightening torque
er or drum in liquid form due to its fractionation properties,
Service port but should be "Flashed" to its gas state before entering the
7.9 - 10.8 lb·ft
(3.5 - 5.0 ton only) system. There are commercially available restriction devic-
es that fit into the system charging hose set to accomplish
this. DO NOT charge liquid R-410A into the compressor.
4. With the system still running, close the valve on the
charging cylinder. At this time, you may still have some
liquid refrigerant in the charging cylinder hose and will
definitely have liquid in the liquid hose. Reseat the liq-
uid line core. Slowly open the high side manifold valve
and transfer the liquid refrigerant from the liquid line
hose and charging cylinder hose into the gas stop valve
port. CAREFUL: Watch so that liquid refrigerant does
not enter the compressor.
28
CAUTION
Do not allow the sludge or oil to contact the skin.
Severe burns may result.
29
30
Supply Static
Blower
(inside)
Inclined
Manometer or Modular Blower
Magnehelic gauge
Cased Coil
(CAPE(A)/CHPE)
Return Static
Air
flow
Return Duct
31
WARNING
HIGH VOLTAGE !
DISCONNECT ALL POWER BEFORE SERVICING.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
AUX ALARM
(Only for DV*FEC )
C R 2 1
ACC-OUT
FUS E
TB1
F 2U
TB8
ECM Motor
X8A
ACC-IN
X7A
TB7
TB6
(Accessory)
(Only for
TB10
DV*FEC )
TB3
RX LED
(H3P) X13A
OFF
F1U
FUSE
ON
X12A
STATUS LED
DS 6
CPU LED
(H2P)
S21 S22
X2A
DS 5
Heater Kit
Output
X1A
Micro
Processor
SEG2 7seg
BS 2
SEG1 7seg
OFF
ON
LE AR N
S5 S6 S7 S8
BS 1
DS2
DS1
DS3
X3A X15A X5A
EEV
COIL PRESSURE SENSOR THERMISTOR
32
33
34
3. Airflow shows es�mated CFM of indoor unit. For example, if the CFM is 1240 CFM, 7 segment display
shows “A…12…40…”
_A
Airflow No display Upper 2-digit of No display Lower 2-digit of No display
(2sec.) (0.5sec.) CFM (2sec.) (0.5sec.) CFM (2sec.) (0.5sec.)
1. State 3. Airflow
2. When the unit is having some major and minor error code in standby normal mode, 2-digit 7 segment
displays keep showing error code.
2. Error code
35
4. When the unit is having some minor error code during defrost opera�on in normal mode, 2-digit 7
segment displays show state “dF,” error code and airflow status.
5. When the unit is having some minor error code during Emergency mode, 2-digit 7 segment displays
show state “EE” and error code.
36
DISPLAY
The display consists of 2 digits.
It is also possible to erase all the diagnos cs codes from this menu.
37
No Display
38
SiUS612102E.indb
Code Display
39
• Assure 208/230 volt and 24 volt power to blower and control board.
• No 24 volt power to control board • Manual disconnect switch OFF
• Check fuse F2U on control board.
1 • Blown fuse or circuit breaker • No 24 volt power to control board
EE No display* • Check for possible short in 115/208/230 volt and 24 volt circuits. Repair as
• Control board has an internal • Blown fuse or faulty circuit breaker
necessary.
fault • Control board has internal fault
• Replace the control board.
SERVICING
Selecting "no heater kit" and • Select the valid heater kit on thermostat
Eb E_Eb • No heater kit selected
receiving electric heat demand • Valid dip switch selection (heater kit selection out of range of the unit configuration)
TROUBLESHOOTING
• Replace fuse
• Fuse (F1U) is blown
E5 E_E5 Fuse open • Check wiring to AUX alarm, heater kit, communication connection.
• Connector TB10 is open
• Replace the control board
• High water level in the evaporation coil • Check water level in drain pan
EF E_EF Auxiliary switch open • The connected alarm device is activated • Check alarm device.
• Auxiliary alarm terminals (TB4, TB5) are open • Close auxiliary terminals TB4 and TB5 if not used
d0 E_d0 Data not on network • No shared data on the network • Populate shared data set using memory card.
d1 E_d1 Invalid data on network • Wrong shared data on the network • Populate shared data set using memory card.
• Fan/motor obstruction or blocked filters • Check for obstruction on the fan/motor/ductwork, clean filters
Blower motor operating in power, • Power interruption (low voltage) • Verify the input voltage at the motor
b3 E_b3
Temp or speed limiting conditions • Incorrect wiring • Check wiring
• Blockage in the airflow (ductwork) or ductwork undersized • Replace motor
*1: When “EE” is displayed on the LED display, it indicates the state of Emergency mode.
2021/02/17
39
INDOOR UNIT ERROR CODES (DV*FEC/CAPE(A)*/CHPE*)
9:00:13
Error Control board LED
40
Description Possible Causes Corrective Actions
Code Display
SiUS612102E.indb
• Fan/motor obstruction or abnormal motor loading • Check for obstruction on the fan/motor/ductwork
40
Blower motor - current trip (or) • Power interruption (low voltage) • Verify the input voltage at the motor
b4 E_b4
lost rotor • High loading conditions, blocked filters • Check filters, grilles, duct system, coil air inlet/outlet for blockages.
• Blockage in the airflow (ductwork) or ductwork undersized • Replace motor
• Verify line voltage to blower is within the range specified on the ID blower rating
plate
• Blower motor stops for over/ • High AC line voltage to ID blower
SERVICING
• Replace motor
ID blower motor does not have
required parameters to function. • Wrong/no shared data on the network • Check for locked rotor condition (see above error code for details)
b7 E_b7
Motor fails to start 40 consecutive • Locked motor rotor condition • Replace control board or motor
times.
• Check for obstruction on the fan/motor
• Check ductwork/filter for blockage, clean filters
• Remove obstruction. Verify all registers are fully open
• Fan/motor obstruction or blocked filters
Low indoor airflow (without • Check the connections and the rotation of the motor
b9 E_b9 • Restrictive ductwork or ductwork undersized
electric heat mode) • Verify the input voltage at the motor
• ID motor failure
• Verify ductwork is appropriately sized for system. Resize/replace ductwork if
needed
• Replace motor
• Check for obstruction on the fan/motor
• Check ductwork/filter for blockage, clean filters
• Fan/motor obstruction or blocked filters • Remove obstruction. Verify all registers are fully open
Low indoor airflow (with electric • Restrictive ductwork or ductwork undersized • Check the connections and the rotation of the motor
9b E_9b
heat mode) • ID motor failure • Verify the input voltage at the motor
• Combination mistake of outdoor unit and indoor unit • Verify ductwork is appropriately sized for system. Resize/replace ductwork if
needed
• Replace motor
• Check Indoor EEV coil connection (control board and junction connector)
• Indoor EEV coil not connected • Replace EEV coil
70 E_70 EEV disconnection detected
• Incorrect wiring to EEV • Check the resistance value of EEV coil
• Replace the control board
• Check the connection to liquid thermistor (control board and junction connector)
• Open (or) short circuit of the liquid thermistor (X5A) • Check the resistance value of the thermistor
73 E_73 Liquid side thermistor abnormality
• Liquid thermistor reading incorrect or values outside the normal range • Replace thermistor
• Replace the control board
• Check the connection to gas thermistor (control board and junction connector)
• Open (or) short circuit of the gas thermistor (X5A) • Check the resistance value of the thermistor
74 E_74 Gas side thermistor abnormality
• Gas thermistor reading incorrect or values outside the normal range • Replace thermistor
• Replace the control board
• Check the connection to pressure sensor (control board and junction connector)
• Open (or) short circuit of the pressure sensor (X15A) • Check the output voltage of the pressure sensor
75 E_75 Pressure sensor abnormality
• Pressure sensor reading incorrect or values outside the normal range • Replace pressure sensor
• Replace the control board
Indoor unit - outdoor unit,
• Open communication circuit • Check for Indoor unit and other unit wiring.
Gas furnace or blower unit
76*2 E_76 • Incorrect wiring between OD unit, gas furnace or modular blower • Replace the control board
communication error
• No power supply to OD unit, gas furnace or modular blower • Check power supply to OD unit, gas furnace or modular blower
(during operation)
• Incorrect wiring between ID unit and thermostat.
• Check for thermostat and indoor unit wiring
Indoor unit - thermostat The system may have the communication erro without error code 77 on the indoor
• Verify the input voltage at the ID unit and thermostat
77*2 E_77 communication error (start-up & unit control board.
• Replace the control board or thermostat
during operation) • Thermostat failure
• Press "LEARN" button on control board for more than 5 seconds to reestablish network
• Power interruption (low voltage)
Indoor unit - outdoor unit,
• Open communication circuit • Check for Indoor unit and other unit wiring.
gas furnace or blower unit
78*2 E_78 • Incorrect wiring between OD unit, gas furnace or modular blower • Replace the control board
communication error (startup
• No power supply to OD unit, gas furnace or modular blower • Check power supply to OD unit, gas furnace or modular blower
operation)
INDOOR UNIT ERROR CODES (DV*FEC/CAPE(A)*/CHPE*)
2021/02/17
9:00:13
SERVICING
EMERGENCY MODE FOR EEV APPLICABLE 1. HEATING EMERGENCY MODE
INDOOR UNIT Emergency Heating Mode is to be used when communica-
tion between each equipment is not functioning properly.
There are the following steps to setup Heating Emergency Mode.
WARNING
WHEN SETTING AND WIRING, BE SURE TO TURN OFF THE POWER OF
EQUIPMENT.
WARNING
WHEN SETTING AND WIRING, BE SURE TO TURN OFF THE POWER OF
EQUIPMENT.
42
43
Dip Switch
Default Factory Settings
Switch # Setting Function
1 OFF No Use
2 OFF No Use
Indoor unit DS-1
3 OFF No Use
4 OFF No Use
5 OFF No Use
6 OFF No Use
Indoor unit DS-2
7 OFF No Use
8 OFF No Use
9 OFF Heater Kit Selection in Emergency Mode (Only for DV*FEC)
10 OFF Heater Kit Selection in Emergency Mode (Only for DV*FEC)
Indoor unit DS-3
11 OFF Heater Kit Selection in Emergency Mode (Only for DV*FEC)
12 OFF Heater Kit Selection in Emergency Mode (Only for DV*FEC)
13 ON Allow in Emergency Mode [Fan Emergency Mode] (Only for DV*FEC)*
14 OFF Allow in Emergency Mode [Fan Emergency Mode] (Only for DV*FEC)*
Indoor unit DS-4
15 ON EEV Enable**
16 OFF No Use
17 ON Emergency EEV Opening**
18 OFF Emergency EEV Opening**
Indoor unit DS-5
19 OFF EEV Emergency Mode**
20 OFF No Use
21 OFF Emergency mode (Cooling & Heating Emergency Mode)*
22 OFF Emergency mode (Cooling & Heating Emergency Mode)*
Indoor unit DS-6
23 OFF No Use
24 OFF No Use
1 ON Termination Resistor
Outdoor unit DS-1
2 ON Termination Resistor
1 OFF Cooling Emergency mode*
Outdoor unit DS-2
2 OFF Cooling Emergency mode*
DISPLAY
The display consists of 3 digits.
OFF
ON
MODES
There are 5 modes which can be accessed using the setting display:
“FAULT CODE, FAULT HISTORY, MONITORING, SETTING MODE 1” and “SETTING MODE 2”.
To enter any of these modes, use the schemes shown in this section. Each mode has its own
corresponding “Screen #” within the display itself which allows the user to navigate and use the
features. (Example: The Fault Code is accessed and displayed from
“Screen Zero” of the 7-segment display. The Fault History is accessed and displayed using
“Screen One” of the display, etc.)
45
46
This mode will allow the user to see the six most recent system faults.
For a list of the fault codes, please see the TROUBLESHOOTING tables in this document.
Press RECALL.
Press RECALL.
Press RECALL.
47
Press RECALL
to increase the value.
Press RECALL.
Press
RECALL.
Press RECALL.
Item number
Display flickers
at 1 second
Press TEST
intervals.
to confirm the setting.
Value
Press RECALL.
Press RECALL.
48
Blink interval:
< SCREEN 2 > 0.4 sec. On - 0.4 sec. Off
Press RECALL
to increase the value.
< Changing Setting Display >
Press RECALL
Press RECALL. to increase the value.
Press TEST.
Press
RECALL.
Press RECALL.
Press
RECALL.
*1
*1 Some models have setting items (Setting No.) up to “3.12” depending on the production date of the outdoor units.
Refer to page 52 “SCREEN3 (SETTING MODE1)” for the items that can be set.
49
Press RECALL
to increase the number.
< Changing setting display >
Press RECALL.
Press RECALL.
Press TEST.
Press
RECALL.
Press RECALL.
Press
RECALL.
Press RECALL.
Press RECALL.
50
Setting
Contents Notes
No.
Setting
Contents Notes
No.
Setting
Contents Notes
No.
0: Stop
1: Cooling Start-up
2: Heating Start-up*1
2 Operation code 3: Oil Return Operation
4: Heating Operation*1
5: Defrost Operation*1
6: Cooling Operation
unit: %
4 % Demand
(Cut off the decimal first place)
unit: %
5 Act % demand
(Cut off the decimal first place)
*1 HP only 51
52
0:Same Level
3 Vertical Rise 1:Outdoor Lower
2:Indoor Lower
System Verification Test
4 0:ON 1:OFF
(System test)
7 Force Defrost Cycle*1 0:ON 1:OFF
Maximum Compressor RPS for 0: -10.0 RPS 1: -9.5 RPS 2: -9.0 RPS 3: -8.5 RPS Can adjust comp RPS
10 4: -8.0 RPS 5: -7.5 RPS 6: -7.0 RPS 7: -6.5 RPS
Cooling in each 0.5 RPS.
8: -6.0 RPS 9: -5.5 RPS 10: -5.0 RPS 11: -4.5 RPS
12: -4.0 RPS 13: -3.5 RPS 14: -3.0 RPS 15: -2.5 RPS
16: -2.0 RPS 17: -1.5 RPS 18: -1.0 RPS 19: -0.5 RPS
20: 0.0 RPS 21: 0.5 RPS 22: 1.0 RPS 23: 1.5 RPS
Maximum Compressor RPS for 24: 2.0 RPS 25: 2.5 RPS 26: 3.0 RPS 27: 3.5 RPS Can adjust comp RPS
11
Heating*1 28: 4.0 RPS 29: 4.5 RPS 30: 5.0 RPS 31: 5.5 RPS in each 0.5 RPS.
32: 6.0 RPS 33: 6.5 RPS 34: 7.0 RPS 35: 7.5 RPS
36: 8.0 RPS 37: 8.5 RPS 38: 9.0 RPS 39: 9.5 RPS
40: 10.0 RPS
COOLING BOOST MODE
12 0:ON 1:OFF
Selection
0:105F, 1:100F, 2:95F,
COOLING BOOST MODE
13 3:90F, 4:85F, 5:80F, 6:75F,
Temperature
7:70F, 8:Always ON
0:LEVEL1
16 Noise down level 1:LEVEL2
2:LEVEL3
*1 HP only
NOTE: Parameters as per factory setting are highlighted in bold and underlined.
53
54
• Faulty outdoor air thermistor or not properly • Check the connection to outdoor air thermistor; Repair/replace if
25 E25 The outdoor air thermistor is open or shorted.
connected needed
The control determines that the pressure sensor • Pressure sensor inoperable or not properly • Check the connection to pressure sensor; Repair/replace if
26 E26
is not reacting properly. connected needed
The control has detected that the Outdoor Coil • Outdoor coil defrost thermistor inoperable or • Check the connection to OD coil defrost thermistor; Repair/
27 E27
Defrost thermistor is out of range. not properly connected replace if needed
The control has detected that the Outdoor Coil • Outdoor coil thermistor inoperable or not • Check the connection to OD coil thermistor; Repair/replace if
28 E28
thermistor is out of range. properly connected needed
The control has detected that the Liquid thermistor • Liquid thermistor inoperable or not properly • Check the connection to liquid thermistor; Repair/replace if
29 E29
is out of range. connected needed
• Wiring to control board disconnected
Indicates the control board may need to be • Check wiring to control board; Repair as needed
30 E30 • Faulty control board
replaced. • Replace control board if necessary
• Electrical Noise
• Ambient air conditions too high
• Stop valve not completely open
• Cycle power; re-try during usable ambient temperature range
• Cooling bracket screw(s) missing or not
• Check grease applying condition <3.5 - 5.0 ton only>
properly fastened <3.5 - 5.0 ton only>
This error indicates the equipment is experiencing • Check screw tightening condition <3.5 - 5.0 ton only>
• No or poor thermal grease coating between
32 E32 high temperature faults on the outdoor unit control • Check for restriction in line
cooling plumbing and cooling bracket on control
board. • Check refrigerant charge level; Adjust if needed
board <3.5 - 5.0 ton only>
• Check the opening of stop valve, should be full open; Repair/
• No flow or limited flow through control board
replace if needed
cooling circuit (potential restriction in line or low
refrigerant) <3.5 - 5.0 ton only>
• Ambient air conditions too high
• Stop valve not completely open
• Cycle power; re-try during usable ambient temperature range
• Cooling bracket screw(s) missing or not
This error indicates the equipment is experiencing • Check grease applying condition <3.5 - 5.0 ton only>
properly fastened <3.5 - 5.0 ton only>
high temperature faults on the outdoor unit • Check screw tightening condition <3.5 - 5.0 ton only>
• No or poor thermal grease coating between
33 - control board. Control has determined continued • Check for restriction in line
cooling plumbing and cooling bracket on control
operation is acceptable. This indicates they may • Check refrigerant charge level; Adjust if needed
board <3.5 - 5.0 ton only>
be a problem with the equipment. • Check the opening of stop valve, should be full open; Repair/
• No flow or limited flow through control board
replace if needed
cooling circuit (potential restriction in line or low
refrigerant) <3.5 - 5.0 ton only>
• Check power supply for in-rush current during start-up or steady
• Current spike in supply state operation
• Stop valve not completely open • Check the opening of stop valve, should be full open; Repair/
Control board detected a high current condition.
34 E34 • The compressor wire is lost phase replace if needed
This indicates the potential for a short circuit.
• Faulty control board • Check the wire between control board and compressor
• Faulty compressor • Replace control board if necessary
• Check the compressor; Repair/replace if needed
• Check installation clearances.
• Short circuit condition
• Check the opening of stop valve, should be full open; Repair/
• Stop valve not completely open
replace if needed
35 E35 Control board detected a high current condition. • Overcharge
• Check refrigerant charge level; Adjust if needed
• Faulty control board
• Replace control board if necessary
• Faulty compressor
• Check the compressor; Repair/replace if needed.
• Faulty outdoor solenoid valve coil
• Check outdoor solenoid valve coil; Repair /replace if needed
• Faulty outdoor solenoid valve
• Check outdoor solenoid valve; Replace /repair if needed
The control encountered an abnormal condition • Blocked/restricted outdoor unit coil and/or lines
36 E36 • Check and clean outdoor unit coil and/or lines
during the startup procedure. • The compressor wire is lost phase
• Check the wire between control board and compressor
• Inconsistent compressor load
• Replace control board if necessary
• Faulty control board
• Check wiring from Outdoor fan motor to control board; Repair if
Indicates the control board may need to be • Outdoor fan motor not connected properly
37 E37 needed
replaced. • Faulty control board
• Replace control board if necessary
• Correct low/high line voltage condition; Contact local utility if
• High or low voltage from supply
The control has detected a voltage related issue needed
38 E38 • The compressor wire is lost phase
with the compressor. • Check the wire between control board and compressor
• Faulty control board
• Replace control board if necessary
Indicates the control board may need to be • Thermistors inoperable or improperly connected • Check the connection to thermistors; Repair/replace if needed
39 E39
replaced. • Faulty control board • Replace control board if necessary
Control determines that its compressor • Check memory card data vs. outdoor unit model
• Memory card not correct
40 E40 requirement is different than the compressor • Verify control board size vs. outdoor unit model; Replace control
• Control board mismatch
capability. board if necessary
• Refrigerant leak
• Test for system leaks using leak test procedure
• Low refrigerant charge
• Check refrigerant charge level; Adjust if needed
The control has detected a low refrigerant • Thermistors inoperable or not properly
41 E41 • Check the connection to thermistor; Repair/replace if needed
condition. connected
• Check outdoor solenoid valve coil; Repair /replace if needed
• Faulty outdoor solenoid valve coil
• Check outdoor solenoid valve; Replace /repair if needed
• Faulty outdoor solenoid valve
• Check circuit breakers and fuses; Replace if needed
Control detects a low power supply voltage • Verify unit is connected to power supply as specified on rating
42 E42 • Low line voltage supply
condition. plate
• Correct low line voltage condition; Contact local utility if needed
55
56
57
58
60
61
SiUS612102E.indb
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
62
AC 1.5 - 3.0 ton
WIRING DIAGRAMs
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
2021/02/17
9:00:18
HIGH VOLTAGE!
SiUS612102E.indb
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO
63
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
AC 3.5 - 5.0 ton
WIRING DIAGRAMs
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
2021/02/17
63
9:00:18
64
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SiUS612102E.indb
64
HP 1.5 - 3.0 ton
WIRING DIAGRAMs
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
2021/02/17
9:00:19
HIGH VOLTAGE!
SiUS612102E.indb
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO
65
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
HP 3.5 - 5.0 ton
WIRING DIAGRAMs
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
2021/02/17
65
9:00:19
WIRING DIAGRAMs
DV*FEC
NOTE: THESE INSTRUCTIONS ARE SPECIFICALLY FOR
DV*FEC MODELS. DO NOT ATTEMPT TO APPLY THESE
DIAGRAMS TO ANY OTHER MODELS. HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE
SERVICING. MULTIPLE POWER SOURCES MAY BE
PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
OVERCURRENT PU - PURPLE
RD BK GY BL PROT. DEVICE
PL3
1 2 3 4 5 6 7 8 9 10 11 12
PL4
PLUG CONNECTION WH - WHITE
RD
BK
EQUIPMENT GND
THERMOSTAT
WH
INSTALLING FIELD GROUND COMPONENT CODES:
AUX ALARM
(ALARM)
(SEE NOTE 9) ~
~ AUX ALARM
GY BK (OFF) ON OFF PL1, PL2 POWER/HEATER
(ALARM) CONNECTOR
~
~
BR TB4
GR
BL RD DS1 - DS6 SELECTOR SWITCH
~
~ TB5
TB5 TB4 TR1 TH1
TL THERMAL LIMIT
X8A C R 2 1
TB2 TB1 TR TRANSFORMER
RELAY OUT
BL ACC-OUT F2U F1U, F2U FUSE LINK
(ACC-OUT) TB8
RAM MONITOR
RX LED
TH2 TR2 (SEE NOTE 6)
X7A
TB10 TB3
PS
F1U CPU LED STATUS LED
(SEE NOTE 6)
1 2 3 4
DS5
1 2 3 4
1 2 3 4
1 2 3 4
NOTES:
PLACE RED WIRES ON 208 V TERMINAL OF 2-TRANSFORMER (TR1/TR2) FOR 208 VAC OPERATION.
IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED
WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY.
RED STATUS LED PROVIDES NETWORK STATUS. GREEN RX LED INDICATES NETWORK TRAFFIC. USE LEARN BUTTON TO RESET NETWORK.
REMOVE SHORT RED CIRCUITING WIRE AND PUT AUX ALARM SWITCH WHEN INSTALLING AUX ALARM SWITCH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
66
EEV
TH2 ACC-IN ACC-OUT
WIRING
TB10 TB6 TB8 GROUND TO
F1U
X1A
GR FIELD GROUND
TB5
X3A TR2 COM
GR
X2A TB3 TB7 PU
K2R K1R GR
DATA SHARE TB4 YL
PRESSURE SEG1 SEG2
DS6
SENSOR TB2
X15A
115/208/230VAC
PS TR1
(SEE NOTE 7)
S21 S22 S23 S24 60 Hz
TB1
X5A YL PU
TH1
F2U RD
BS1 BS2 BK
120 208 230
(SEE NOTE 4) X12A VAC VAC VAC
THERMISTOR FAULT RECALL
COM
(HEAT FLASH
EXCHANGER LEARN CPU LED HAP WRITER TR1
(SEE NOTE 5) (SEE
1,2) NOTE 1)
DS1 X13A 24VAC
INTEGRATION
TYPE ON RAM MONITOR YL
PU
OFF
S1 S2 S3 S4
STATUS LED
H2P
DS2 (SEE NOTE 5)
MPU
H3P
X8A
RX LED
S5 S6 S7 S8
(SEE NOTE 5) C BL BK 1
DS3 DS4 DS5 TRANSMISSION
R RD WIRING GY 2
X7A
2 GY RD R
S9 S10 S11 S12 S13 S14 S15 S16 S17 S18 S19 S20 BK EEV COIL
1 BL C
M
THERMISTOR
(HEAT
EXCHANGER 1,2)
INSIDE CONTROL BOX PRESSURE
SENSOR
NOTES: INTEGRATED CONTROL:
1. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS LOW VOLTAGE INSIDE CABINET
MUST BE USED WHEN SERVICING. OF COIL
2. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS LOW VOLTAGE FIELD
UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH INSIDE FURNACE
WIRING MATERIAL HAVING A TEMPERATURE RATING OF HIGH VOLTAGE OR BLOWER UNIT
AT LEAST 105°C. USE COPPER CONDUCTORS ONLY.
3. UNIT MUST BE PERMANENTLY GROUNDED AND CONFIRM HIGH VOLTAGE FIELD
COLOR CODES:
TO N.E.C AND LOCAL CODES. JUNCTION
4. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST BL - BLUE
RECENT, DEPRESS FAULT RECALL BUTTON FOR MORE TERMINAL RD - RED
THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT
PLUG CONNECTION YL - YELLOW
INPUTS)
5. RED STATUS LED PROVIDES NETWORK STATUS, GREEN OR - ORANGE
EQUIPMENT GND BK - BLACK
RX LED INDICATES NETWORK TRAFFIC. USE LEARN
BUTTON TO RESET NETWORK. FIELD GROUND GY - GREY
COMPONENT CODES:
6. THE POSITION OF SELECTOR SWITCHES (DS1 - DS6) BR - BROWN
ON TR1 COIL TRANSFORMER
INDICATE FACTORY SETTING. DIP SWITCH (OFF) OFF GR - GREEN
7. SELECTION OF CORRECT SUPPLY VOLTAGE FOR F1U, F2U FUSE LINK WH - WHITE
TRANSFORMER DEPENDS ON POWER SUPPLY VOLTAGE DS1 - DS6 SELECTOR SWITCH PU - PURPLE
TO GAS FURNACE OR BLOWER UNIT.
8. USE N.E.C CLASS 2 WIRE.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
67
68
Slit
Hook
69
Clamp
70
Fan motor
lead wire
71
Fold back
with a slit.
72
Fan
motor
73
Clamp
Solenoid valve
coil connector
Solenoid valve
coil
Four way valve coil Electronic expansion
valve coil
74
Clamp
75
Defrost thermistor
76
Clamp
77
78
Radiation
shield plate
79
Main control
board
80
81
Partition
plate
Slit
Hook
Sound
blanket
(outer top)
Sound
blanket
(outer body)
82
Sound blanket
(outer body)
Sound
blanket
(inner top)
83
Sound
blanket
(inner body)
Terminal cover
Protection bushing
Black (U)
Yellow (W)
84
Retainer (3)
assy
OL (1)
Retainer
(2)
OL lead wire
Compressor
Pass the harness
85
Partition
plate
Slit
Hook
Sound
blanket
(outer top)
Sound
blanket
(outer body)
86
Sound blanket
(outer body)
Sound
blanket
(inner top)
87
Sound
blanket
(inner body)
Terminal cover
Protection bushing
Black (U)
Yellow (W)
88
OL
89
Putty
90
91
4 Remove 8 screws
and remove the front
panel (1).
Back view
92
External power
supply and
ground wires
93
Conduit tube
94
Hook Partition
plate 0~10mm
hook Clamp
Fan motor
lead wire Lower the hook of Make sure the fan
the partition plate motor lead wire is
to let the fan motor fixed tight. Clamp
lead wire pass the lead wire at a
through. After the maximum of 10 mm
lead wire is passed, (0.4 in) from the
return the hook. partition plate.
Clamp
(weather Clamp
resistant tie) (weather
resistant tie)
Hook
95
96
Hook
3 Remove the outdoor air ■ For 3.5 - 4.0 ton models ■ For 5.0 ton model
thermistor and outdoor
heat exchanger middle
Outdoor air thermistor
thermistor.
Defrost thermistor
97
Suction
thermistor
Clamp
■W
hen reassembling, the slit
of the insulation tube must
be positioned opposite to
the suction pipe thermistor.
Slit
Electronic expansion
valve coil
98
OL lead
wire
OL relay connector
99
Hook
Outdoor air
thermistor
Heat exchanger
middle thermistor
100
Suction
thermistor
Clamp
■W
hen reassembling, the slit
of the insulation tube must
be positioned opposite to
the suction pipe thermistor.
Slit
Detach the OL
(overload protector)
relay connector.
OL relay
connector Liquid pipe
thermistor
101
(0.2 in)
5 mm
2 Remove 2 screws and Electrical box Apply cooling
remove the electrical grease
box.
102
OL
Four way
valve coil
Solenoid
valve coil
Power
supply
Ground
4 Remove 11 screws
and remove the main Insulation
control board and sheet
insulation sheet.
103
Conduit
tube
2 Remove the sound 3.5 - 4.0 ton models 5.0 ton models
blanket (top).
Sound Sound
blanket blanket
(inner top) (inner top)
Sound
blanket
(body)
104
Terminal
cover
U
U U: Black
V V: Red
V
W W
W: Yellow
105
Retainer (3)
assy
(1)
Retainer
OL
(2)
OL lead wire
Compressor
Pass the harness
7 Heat up the brazed 3.5 - 4.0 ton models 5.0 ton models ■ Before working, be sure
parts of compressor to remove any putties, the
piping and disconnect terminal cover, and other
it. plastic pieces that may burn.
Also, provide a protective
Remove the 2 nuts sheet or a steel plate so that
that secure the the brazing flame cannot
compressor. influence peripheries.
Brazed
Brazed part ■ Slit range of piping weight.
part
45
°
45°
Nut Nut
106
Conduit
tube
2 Remove the sound 3.5 - 4.0 ton models 5.0 ton models
blanket (top).
Sound Sound
blanket blanket
(inner top) (inner top)
Sound
blanket
(body)
107
Terminal
cover
U
U U: Black
V V: Red
V
W W
W: Yellow
108
OL
Brazed
part
Nut
109
Rear cover
Heat exchanger
110
Partition plate
111
Rear cover
Heat exchanger
112
Partition plate
113
▪ This software can monitor inverter sensor data (temperature, pressure) and actuator status
(compressor, solenoid, etc.). Data/status items that are supported by this software differ
from model to model.
▪ D-Checker gathers operating data from an inverter through a PCB connector on the
outdoor unit.
▪ Note: The values shown in this addendum are intended for instruction purposes only.
Please refer to product specific literature (IO Manual) for appropriate operation ranges for
current unit.
Installing D-Checker
3
▪1 Copy the latest version of D-checker software
to any folder on PC.
▪2 Execute software
10
10▪ Press OK when Finished
114
115
Note: D-checker will Not communicate with a system in sleep mode or hibernate.
116
Click OK (F1)
117
Click OK (F1)
If Recording is required,
click Start Rec. (F6) Time recorded will populate
Select Op. All Data (F3) Select Op. Selected Data (F4)
118
Click OK (F1)
119
120
121
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE
• Products • Parts
• Warranties • Contractor Programs and Training
• Customer Services • Financing Options
SiUS612102E
02/2021 AK.K