0% found this document useful (0 votes)
19 views

Barnes Layer Analysis: R 2par, Per Astm G 57 & Barnes Method

The document details a Barnes layer analysis conducted on a pipeline relocation route in Ayer Keroh, Malacca. Resistivity measurements were taken at depths of 1, 2, 3, 6, and 9 meters and analyzed using the Barnes method to determine layer resistivities of 20,106 ohm-cm from 0-1 meter, 4,616 ohm-cm from 1-2 meters, and 754 ohm-cm from 2-3 meters.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views

Barnes Layer Analysis: R 2par, Per Astm G 57 & Barnes Method

The document details a Barnes layer analysis conducted on a pipeline relocation route in Ayer Keroh, Malacca. Resistivity measurements were taken at depths of 1, 2, 3, 6, and 9 meters and analyzed using the Barnes method to determine layer resistivities of 20,106 ohm-cm from 0-1 meter, 4,616 ohm-cm from 1-2 meters, and 754 ohm-cm from 2-3 meters.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

BARNES LAYER ANALYSIS

MAIN CONTRACTOR: ACE ENERGY SDN BHD

TEST LOCATION: Ayer Keroh Melaka

DATE: 20/05/2017
TITLE : Pipeline Relocation Route in Ayer Keroh Malacca

TESTERS: 1) Arzaine

SRT No : Chainage 750

METHODOLOGY: r = 2paR, per ASTM G 57 & Barnes Method

TEST INSTRUMENT: Digital Earth Tester Model Megger DET 5/4R

Spacing 4 Pin Wenner Data Barnes Layer Analysis


a R Spacing Resistivity 1/R D 1/R 1/(D 1/R) Spacing Layer Resistivity
(m) (Ohms) Factor (Ohm-cm) (Mhos) (Mhos) (Ohms) Factor Layer (m) (Ohm-cm)
1.0 32 628 20,106 0.031 n/a n/a n/a 0 - 1.0 20,106
2.0 6 1,257 7,540 0.167 0.136 7.35 628 1.0 - 2.0 4,616
3.0 1 1,885 1,885 1.000 0.833 1.20 628 2.0 - 3.0 754
6.0 3,770 1,885 3.0 - 4.0
9.0 5,655 1,885 4.0 - 5.0

(Table format from "Control of Pipeline Corrosion," by A. W. Peabody, pg. 91)


Resistivity (ohm.cm)

LAYERRESISTIVITY

R e s is t iv it y ( o h m .c m )
AVERAGE RESISTIVITY 25,0 0

25,000 20, 0

20,000 15,0 0
f(x) = − 16751.8816250551 ln(x) + 19848.7487430266

10, 0
15,000
5,0 0
10,000
0
5,000 1.0

2.0
0
3.0
1.0 2.0 3.0 6.0 9.0 Depth (m)
6.0
Depth (m)
9.0
BARNES LAYER ANALYSIS

MAIN CONTRACTOR: ACE ENERGY SDN BHD

TEST LOCATION: Ayer Keroh Melaka

DATE: 20/05/2017
TITLE : Pipeline Relocation Route in Ayer Keroh Malacca

TESTERS: 1) Arzaine

SRT No : Chainage 750

METHODOLOGY: r = 2paR, per ASTM G 57 & Barnes Method

TEST INSTRUMENT: Digital Earth Tester Model Megger DET 5/4R

Spacing 4 Pin Wenner Data Barnes Layer Analysis


a R Spacing Resistivity 1/R D 1/R 1/(D 1/R) Spacing Layer Resistivity
(m) (Ohms) Factor (Ohm-cm) (Mhos) (Mhos) (Ohms) Factor Layer (m)
1.0 32 628 20,106 0.031 n/a n/a n/a 0 - 1.0
2.0 6 1,257 7,540 0.167 0.136 7.35 628 1.0 - 2.0
3.0 1 1,885 1,885 1.000 0.833 1.20 628 2.0 - 3.0
6.0 3,770 1,885 3.0 - 4.0
9.0 5,655 1,885 4.0 - 5.0
Resistivity (ohm.cm)

(Table format from "Control of Pipeline Corrosion," by A. W. Peabody, pg. 91)


Resistivity (ohm.cm)

LAYER RESISTIVITY
25,000
AVERAGE RESISTIVITY
20,000
25,000
15,000
20,000
f(x) = − 16751.8816250551 ln(x) + 19848.7487430266
10,000
15,000
5,000
10,000
0
1.0
5,000
2.0
0
1.0 2.0 3.0 6.0 9.0 3.0

Depth (m) Depth (m) 6.0

9.0
s
Layer Resistivity
(Ohm-cm)
20,106
4,616
754

IVITY

6.0

9.0
BARNES LAYER ANALYSIS

MAIN CONTRACTOR: ACE ENERGY SDN BHD

TEST LOCATION: Ayer Keroh Melaka

DATE: 20/05/2017
TITLE : Pipeline Relocation Route in Ayer Keroh Malacca

TESTERS: 1) Arzaine

SRT No : Chainage 800

METHODOLOGY: r = 2paR, per ASTM G 57 & Barnes Method

TEST INSTRUMENT: Digital Earth Tester Model Megger DET 5/4R

Spacing 4 Pin Wenner Data Barnes Layer Analysis


a R Spacing Resistivity 1/R D 1/R 1/(D 1/R) Spacing Layer Resistivity
(m) (Ohms) Factor (Ohm-cm) (Mhos) (Mhos) (Ohms) Factor Layer (m)
1.0 10.63 628 6,679 0.094 n/a n/a n/a 0 - 1.0
2.0 5.74 1,257 7,213 0.174 0.080 12.50 628 1.0 - 2.0
3.0 3.84 1,885 7,238 0.260 0.086 11.63 628 2.0 - 3.0
6.0 3,770 1,885 3.0 - 4.0
9.0 5,655 1,885 4.0 - 5.0
Resistivity (ohm.cm)

(Table format from "Control of Pipeline Corrosion," by A. W. Peabody, pg. 91)


Resistivity (ohm.cm)

LAYER RESISTIVITY
25,000
AVERAGE RESISTIVITY
20,000
25,000
15,000
20,000
f(x) = − 16751.8816250551 ln(x) + 19848.7487430266
10,000
15,000
5,000
10,000
0
1.0
5,000
2.0
0
1.0 2.0 3.0 6.0 9.0 3.0

Depth (m) Depth (m) 6.0

9.0
s
Layer Resistivity
(Ohm-cm)
6,679
7,850
7,304

IVITY

6.0

9.0
BARNES LAYER ANALYSIS

MAIN CONTRACTOR: ACE ENERGY SDN BHD

TEST LOCATION: Ayer Keroh Melaka

DATE: 20/05/2017
TITLE : Pipeline Relocation Route in Ayer Keroh Malacca

TESTERS: 1) Arzaine

SRT No : Chainage 850

METHODOLOGY: r = 2paR, per ASTM G 57 & Barnes Method

TEST INSTRUMENT: Digital Earth Tester Model Megger DET 5/4R

Spacing 4 Pin Wenner Data Barnes Layer Analysis


a R Spacing Resistivity 1/R D 1/R 1/(D 1/R) Spacing Layer Resistivity
(m) (Ohms) Factor (Ohm-cm) (Mhos) (Mhos) (Ohms) Factor Layer (m)
1.0 18.44 628 11,586 0.054 n/a n/a n/a 0 - 1.0
2.0 10 1,257 12,566 0.100 0.046 21.74 628 1.0 - 2.0
3.0 3.35 1,885 6,315 0.299 0.199 5.03 628 2.0 - 3.0
6.0 3,770 1,885 3.0 - 4.0
9.0 5,655 1,885 4.0 - 5.0
Resistivity (ohm.cm)

(Table format from "Control of Pipeline Corrosion," by A. W. Peabody, pg. 91)


Resistivity (ohm.cm)

LAYER RESISTIVITY
25,000
AVERAGE RESISTIVITY
20,000
25,000
15,000
20,000
f(x) = − 16751.8816250551 ln(x) + 19848.7487430266
10,000
15,000
5,000
10,000
0
1.0
5,000
2.0
0
1.0 2.0 3.0 6.0 9.0 3.0

Depth (m) Depth (m) 6.0

9.0
s
Layer Resistivity
(Ohm-cm)
11,586
13,653
3,159

IVITY

6.0

9.0