Hydrostatic Test
Hydrostatic Test
Note: For guidelines on safe practices, please refer to the OLSEH safety manual. Please note that, it is
the responsibility of the Lab In charges to ensure safety in their labs. It is the responsibility of all users to
follow safety directives.
1 When to test?
1. Steel cylinders should be tested every five years and have an indefinite service life until they fail a
hydro test and visual inspection.
2. Aluminum cylinders (not including hoop-wrapped composite cylinders i.e. FRP-2) should be tested
every five years and have an indefinite service life until they fail a hydro test and visual inspection.
3. Hoop-wrapped cylinders should be tested every three years and have a 15-year service life.
4. Cylinders containing hydrogen are susceptible to embrittlement.
a) At the very least we require permanent tanks for hydrogen is made of SS 316, as per ASME
Section VIII Div.1.
b) The safety test must qualify the cylinder especially for H2 storage. Else, replace the cylinder after
every 7 years.
5. If there is any doubt about the suitability of the cylinder for filling, it should be returned to a
certified hydrostatic test facility for examination and retesting.
a) The cylinder must be removed from service and retested if there is any evidence of
a leak, crack, defect or damage.
b) Cylinders which show evidence of exposure to high heat or flames (paint turned to a brown or
black color, decals missing, or gauge lens melted) need to be removed from service and
requalified prior to filling.
c) Cylinder that show significant corrosion.
d) Old cylinders that have not been used, not been pressurized or not been tested in last 5 years.
2 Vendors for Hydrostatic Testing:
Following vendors can be contacted for hydrostatic testing. The list is incomplete, you are welcome to
use any vendor that is qualified as per Karnataka State and has the requisite credentials. The vendor
should have a Government license and should be certified vendor for certifying the procedure which
was followed.
The hydrostatic test parameters must be clearly defined during the design phase and stated in the
project specifications. Guidelines set forth in the AWWA M41 Manual and the ANSI/AWWA C600
Standard is as follows: "Test Pressure shall be 1.25 times the operating pressure. Duration of the test is
two hours.